Power Oscillation Monitoring  A P SGuard Wid e Area Monitorin g Sys tem ap plication  App lic ati on Power oscillation monitoring is a PSGuard application used for the detection of power swings in a high voltage power system. POM  gives the oper ating personal an immediate awareness of the power system state in terms of oscillations, so that operators will see the urgency of the situation more quickly. The POM algorithm processes the selected  voltage and curr ent phasor inputs and dete cts the various power swing modes, which can e.g. lead to angular instability causing disturb- ances. POM quickly identifies the frequency and the damping of swing modes and, in the first instance, it provides improved power system  visibility. Add itionally PO M indicates the fre- quency of an oscillation, which may then be compared with the existing known modes of the  power system, i.e., the operator may distinguish if a local or inter-area mode is excited. When oscillations in a power system are known and monitored constantly, it is possible for the utilities to safely operate power-carrying com-  ponents closer to their design limits without  jeopardising the stabi lity, security or reliability. This means that bottlenecks will be avoided. Thus POM helps utilities to reduce costs and achieve greater functionality from P&C systems. Typically, no costs are incurred for the trans- mission of the measurement values. Function The POM algorithm only needs time synchron- ized Phasor measurements taken by two Phasor  Measurement Units ( PM Us) as a base for further calculations, no additional sensors are necessary. Oscillations are detected in the measured signals by employing the Kalman filtering techniques algorithm, which tries to fit the measurements

1001 Pom Psguard Datasheet

Embed Size (px)

Citation preview

Page 1: 1001 Pom Psguard Datasheet

 

Power Oscillation Monitoring

 A PSGuard Wide Area Monitoring System application

 Application

Power oscillation monitoring is a PSGuardapplication used for the detection of powerswings in a high voltage power system. POM

 gives the operating personal an immediateawareness of the power system state in terms

of oscillations, so that operators will see theurgency of the situation more quickly.

The POM algorithm processes the selected voltage and current phasor inputs and detectsthe various power swing modes, which cane.g. lead to angular instability causing disturb-ances. POM quickly identifies the frequency andthe damping of swing modes and, in the firstinstance, it provides improved power system

 visibility. Additionally POM indicates the fre-quency of an oscillation, which may then becompared with the existing known modes of the

 power system, i.e., the operator may distinguishif a local or inter-area mode is excited.

When oscillations in a power system are knownand monitored constantly, it is possible for theutilities to safely operate power-carrying com-

 ponents closer to their design limits without jeopardising the stability, security or reliability.This means that bottlenecks will be avoided.

Thus POM helps utilities to reduce costs andachieve greater functionality from P&C systems.Typically, no costs are incurred for the trans-mission of the measurement values.

Function

The POM algorithm only needs time synchron-ized Phasor measurements taken by two Phasor

 Measurement Units (PMUs) as a base for furthercalculations, no additional sensors are necessary.Oscillations are detected in the measured signalsby employing the Kalman filtering techniquesalgorithm, which tries to fit the measurements

Page 2: 1001 Pom Psguard Datasheet

 

   ©    C

  o  p  y  r   i  g

   h   t   2   0   0   5   A   B   B

 .   A   l   l  r   i  g

   h   t  s  r  e  s  e  r  v  e

   d

   1   K   H   A  -

   0   0   1   0   0   1  -

   S   E   N

  -   P   D   F  -

   1   0

 .   0   5  -

   P  r   i  n

   t  e   d   i  n   S  w

   i   t  z  e  r   l  a  n

   d

 ABB Switzerland Ltd

Power Technology Systems

Brown Boveri Strasse 6

CH-5400 Baden/Switzerland

Phone +41-58- 585 77 44

Fax +41-58- 585 55 77

E-mail [email protected]

www.abb.com/poweroutage

to a linearized model. The oscillation properties are

extracted from the linearized model parameters.

The signal types in which oscillations may be bestobserved are: voltage magnitude, voltage phase angledifference, frequency and current magnitude. A measuredsignal is continuously provided with a constant sampling

 period, this means that the highest detectable oscillationhas a frequency of 1 Hz.

User defined warning and alarm levels can be set online,as a significant help in detecting dangerous changes in the

 power system.

POM works as a support tool for reducing the impactof unavoidable disturbances by warning before local

 protection tools might trip a heavily loaded line.

The results of the POM application are visualizedwith the PSGuard Basic Monitoring module and canadditionally be integrated in SCADA EMS / Networkcontrol systems with RTU-live interfaces.

To analyse and reinterpret past oscillationscenarios or events, historical data canbe easily accessed in the PSG Database,where all output values are stored with atime resolution of 100 milliseconds. With

the export module included, the user canexport this data as CSV files offline, whichcan then be easily imported into businessapplications such as Excel.

With the help of the stored data, long-term statistics can be collected and basedon its evaluation; system improvementscan be executed for example: retuning ofPower System Stabilizers (PSS) to dampthe frequencies that appear to be the mostdangerous ones.

Online output provided

  Frequency of the most important oscillation mode   Amplitude of the most important oscillation mode   Damping of the most important oscillation mode   Estimated oscillation amplitude of the analyzed signal   Trend indication of the oscillations, the damping and

the amplitude updated every 100 milliseconds

  Online warning and emergency alerting

Offline output provided

  Access to historical data

  Data export to business applications such as Excel

Benefits

Short-term operation benefits

  Immediate awareness of the power system state interms of the presence of oscillations, thus an operatorsees the urgency of the situation

  Increased power transfer at defined security   Early warning to avoid power system collapse

  Online assessment of actual power system damping

  Indication of the frequency of an oscillation which maythen be compared with the known existing modes ofthe power system, i.e. the operator may distinguish if alocal or inter-area mode is excited

Long-term scheduling and planning benefits

  With the help of the stored data, long-term statisticscan be collected and, based on their evaluation, systemimprovements can be implemented

  Provides a basis for tuning Power System Stabilizers(PSS) in the network planning process