1011 HPACEngineering Burd

Embed Size (px)

Citation preview

  • 8/9/2019 1011 HPACEngineering Burd

    1/7

  • 8/9/2019 1011 HPACEngineering Burd

    2/744 HPAC ENGINEERING OCTOBER 2011

    DESIGN CRITERIA FOR PRIMARY/SECONDARY AND PRIMARY-LOOP-ONLY SYSTEMS

    tion that in real-life conditions, the

    relative chilled-water-flow variation

    in the plant is changing in direct pro-

    portion to the relative plant cooling

    load, or W ≈ Q 1:

    WFTDRREQ = (CPDCL ÷ CPCLMFC)

    × SCSCF (3)

    where:

    CPDCL = chiller-plant design cool-

    ing load in tons

    CPCLMFC = chiller-plant cooling

    load in tons at the end of mechanical

    cooling season or at the load associ-

    ated with implementation of various

    control strategies (i.e., reset chilled-

    water temperature control, etc.)

    SCSCF = system control strategy

    correction factor, which is equal to

    or less than 1. SCSCF equals 1 for

    systems that do not utilize reset

    chilled-water temperature control at

    the chiller plant or variable airflow

    rate at terminal units, etc. Otherwise,

    As a result, the available chilled-

    water-flow turndown ratio (which

    represents system water flow con-

    trollable range shown in Figure 2) for

    the PLOVF system (WFTDRAVLPLOVF)

    should be reduced as compared with

    WFTDRAVLP/S for the P/S system by

    the overall system operational safety

    factor (OSOSF) of 0.82 to 0.9. Thus:

    WFTDRAVLP/S = WFTDRDEAVL

    WFTDRAVLPLOVF = (0.82 to 0.9) ×

    WFTDRDEAVL

    Required Evaporator Chilled-

    Water-Flow Turndown Ratio

    Required evaporator chilled-wa-

    ter-flow turndown ratio (WFTDRREQ)

    is another important parameter while

    selecting P/S or PLOVF systems for a

    chiller-plant application. WFTDRREQ 

    for a chilled-water plant can be eval-uated for P/S and PLOVF systems

    from the following equation, which

    is based on the conservative assump-

    determined from Equation 1.

    Schematical representation of

    comparative available chilled-water

    turndown ratios for P/S and PLOVF

    systems is shown in Figure 2. Be-

    cause of the independent-loops ar-

    rangement of the two-loop system

    and its unique architecture, the P/S

    system is able to utilize all of the

    available evaporator chilled-water-

    flow turndown ratio. On the otherhand, a PLOVF system, because of

    the specifics of its architecture and

    rigid dependency of the flows via

    the generation and distribution pip-

    ing loop system, is able to utilize

    less than full available evaporator

    chilled-water turndown ratio. Figure

    2 outlines suggested parameters, in-

    cluding operational safety factors

    for F1HL and F1LL, to avoid PLOVF-

    system shutdown on high and low

    chiller evaporator flows or prema-ture addition or removal of a chiller

    and associated ancillary equipment

    from the line.

    1.1 to 1.05 F1LL

    Notes:F1HL—Evaporator allowable high-limit water-flow rate, gpmF1LL—Evaporator allowable low-limit water-flow rate, gpm∆T

    DEMAX, ∆T

    DEMIN—Maximum or minimum evaporator

    design chilled-water temperature, respectively, °F∆T

    DEDP—Distribution piping system design temperature

    differential, °FWFTDR

    AVL P/S, WFTDR

    AVL PLOVF—Available chilled-water-flow

    turndown ratio for P/S and PLOVF systems, respectivelyOSOSF—Overall system operational safety factor forP/S and PLOVF systems

    F1HL F1HL

    F1LL F1LL∆TDEMAX

    ∆TDEMIN

    System operationalsafety factor for F1HL

    WFTDRAVL P/S

     =

    1.0 × (F1HL/F1LL)       ∆       T       D       E       D       P

    0.9 to 0.95 F1HL

    WFTDRAVL PLOVF

     =(0.9 to 0.95) ×

    F1HL/(1.1 to 1.05) ×F1LL = (0.82 to 0.9) ×

    (F1HL/F1LL)

    OSOSF = 0.82 to 0.9

    P/S systemwater flow

    controllable range

    PLOVF systemwater flow

    controllable range

    System operationalsafety factor for F1LL

    OSOSF = 1.0

    FIGURE 2. Chiller evaporator comparativeavailable chilled-water turndown ratio

    schematical representation for P/S and

    PLOVF systems.

    Notes and symbols: 1 and 2 — Series chiller-evaporator arrangement bypass pipes3 — Chiller-plant decoupling pipe

    4 — P/S- or PLOVF-system primary-loop pump

    5 — P/S-system secondary-loop pump

    6 — Chiller-evaporator arrangement A and B have equal cooling loads

    7 — For the specifics of control system arrangements, see1

    W — Chiller-plant cumulative relative water-flow rate via chillers’ evaporators

    WCPGS

    , WCPDS

    — Chiller-plant water flow rate via generation and distribution systems, respectively

    TINT

    — Intermediate chilled-water temperature between chillers 1 and 2

      — Additional electrical valves for series chiller-evaporator control arrangements

    VFD — Variable-speed pumps control arrangement1

    Relative parameters are shown overlined

    VFD

    VFD

    VFD

    VFD

    Load

    Load

    Chiller #1

    Chiller #1 Chiller #2

    Chiller #2

    B. Series chillers evaporation arrangement

    A. Parallel chillers evaporation arrangementW

    CPGSW

    CPDS

    WCPGS

    WCPDS

    Distribution SystemGeneration system

    Distribution SystemGeneration system

     

    W/2

    W/2

    W W

    W

    W

    4

    2

    1

    4 5

    5

    3

    3

    TINT

    FIGURE 1. Examples of a parallel chillers evaporators arrangement and a series chiller

    evaporator arrangement.

  • 8/9/2019 1011 HPACEngineering Burd

    3/7

    SCSCF should be assumed to be less

    than 1.

    Reset Temperature Control and

    Required Chiller-Plant Chilled-

    Water Turndown Ratio

    Figure 3 is illustrative of the impact

    of the reset chilled-water-tempera-

    ture control strategy. This is analyzed

    for the cooling coil (which is assumed

    to be maintained at ideal clean heat-

    exchanger-surface conditions) with a

    design load of 28.5 tons.1 The air-han-

    dling units are operating with con-

    stant airflow; we assumed a minimum

    mechanical cooling load of 2.9 tons.

    The upper graph shows four op-

    tional control strategies related to

    chilled-water supply temperature.

    Option 1 is associated with constant

    relative chilled-water temperature T1

    = 1 (T1 = 40°F) over the system’s en-

    tire operational hours. (Note: relative

    parameters are shown overlined.)

    Option 2 resets relative chilled-water

    temperature from T1 = 40ºF (T1 = 1)

    at design conditions with relative

    cooling load Q = 1 to T1 = 47.5ºF (T1 =

    1.19) at Q = 0.1.

    Options 3 and 4 are a combination

    of options 1 and 2. Option 3 main-

    tains design chilled-water tempera-

    ture of 40°F (T1 = 1) until Q is reduced

    to 0.52. After that, it gradually resets

    relative chilled-water temperature to

    47.5°F (T1 = 1.19) at Q = 0.1. Option

    4 maintains relative design chilled-

    water temperature of 40°F (T1 = 1)

    until Q is reduced to 0.29 and after

    that gradually resets relative chilled-water temperature to 47.5°F (T1 =

    1.19) at Q = 0.1.

    The graph in the middle of Figure

    3 depicts relative temperature-dif-

    ferential variations associated with

    control strategies shown in the upper

    graph. The relative temperature dif-

    ferential (∆T) increases for Option 1

    from ∆T = 1 at Q = 1 to ∆T = 1.25 (or

    by a factor of 1.25) when the relative

    cooling load, Q, decreases from the

    design value of 1 to 0.1; ∆T decreasesfor options 2, 3, and 4, respectively,

    from 1 at design load Q = 1 to 0.2 at Q

    = 0.1 or by the factor of 5.

    The bottom graph in Figure 3

    shows relative chilled-water-flow-

    rate (W) variation as a function of the

    relative cooling load Q. Under the

    Option 1 chilled-water-temperature

    control strategy, W reduces from 1

    to 0.08 when Q is lowered from 1 at

    design conditions to 0.1, respectively.

    At the same time, options 2, 3, and 4experience reduction of W from 1 at

    design conditions to 0.5 at the end of

    the mechanical cooling season.

    Thus, Figure 3 indicates that the

    reset chilled-water temperature con-

    trol has a pronounced impact on

    WFTDRREQ in the chiller plant. The

    unchanged magnitude of chilled-

    water temperature T1 = 40°F for the

    considered conditions (Option 1)

    leads to the reduction of the relative

    chilled-water flow from 1 to 0.08 (re-sulting in WFTDRREQ = 12.5), while

    Q fluctuates from 1 to 0.1. Option 2

    would result in W variation from 1 to

    OCTOBER 2011 HPAC ENGINEERING 45

    DESIGN CRITERIA FOR PRIMARY/SECONDARY AND PRIMARY-LOOP-ONLY SYSTEMS

    Relative cooling load, Q

    1.20

    1.15

    1.10

    1.05

    1.00

    0.95

    1.4

    1.2

    1.0

    0.8

    0.6

    0.4

    0.2

    0.0

    1.2

    1.0

    0.8

    0.6

    0.4

    0.2

    0.0

    0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1

    Option 1

    Option 2

    Option 3

    Option 4

    Option 1

    Option 2

    Option 3

    Option 4

    Relative cooling load, Q

    0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1

    Relative cooling load, Q

        R   e    l   a   t    i   v   e   c    h    i    l    l   e    d  -   w   a   t   e   r

       t   e   m   p   e   r   a   t   u   r   e    d    i    f    f   e   r   e

       n   t    i   a    l ,    ∆    T

        R   e    l   a   t    i   v   e   c    h    i    l    l   e    d  -   w   a   t   e   r

        fl   o   w   r   a   t   e ,

        W

        R   e    l   a   t    i   v   e   s   u   p   p    l   y

       c    h    i    l    l   e    d  -   w   a   t   e   r   t   e   m   p

       e   r   a   t   u   r   e ,

        T    1

    0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1

     

    Notes: Supply chilled water temperature at design relative cooling load Q = 1 is assumed to be 40°FOption 1: Constant chilled-water temperature maintained at its design level VFTDR

    REQ = 12.5

    Option 2: Linear reset chilled-water temperature control from design conditionsto 0.1 relative cooling load (WFTDR

    REQ = 2)

    Option 3: Reset chilled-water temperature control at 0.52 relative cooling load and below (WFTDRREQ

     = 2.1)

    Option 4: Reset chilled-water temperature control at 0.29 relative cooling load and below (WFTDRREQ = 4.2)

    Option 1

    Option 2

    Option 3

    Option 4

    FIGURE 3. Relative chilled-water-plant parameters at various cooling loads and supply

    chilled-water temperature control strategies.

  • 8/9/2019 1011 HPACEngineering Burd

    4/7

    PARKER BOILER’S NEW 205 SERIES TC CONDENSING BOILERS!

    PARKER BOILER CO

    5930 Bandini Blvd,

    Los Angeles, CA 90040

    Ph. (323)727-9800

    Fax (323) 722-2848

    www.parkerboiler.com [email protected]

    NEVER A COMPROMISE FOR QUALITY OR SAFETY

    DESIGN

    TOLERANCE

     

    ASME

    H

    0.5 (WFTDRREQ = 2).

    Under Option 3, the magnitude of

    W is reduced from 1 to 0.47 (WFT-

    DRREQ = 2.1) at Q = 0.52 and then W

    increases to 0.5 (WFTDRREQ = 2) at Q

    = 0.1. Finally, under Option 4, W is re-

    duced from W = 1 to W = 0.24 (WFT-

    DRREQ = 4.2) and then W increases to

    W = 0.5 (WFTDRREQ = 2). The higher

    magnitude of WFTDRREQ should be

    selected between the two turndown

    ratio values that relate to options 3

    and 4 to establish the resulting value

    of WFTDRREQ for the system.

    Chiller-Water-Plant Required

    Number of Chillers

    The number of chillers sharing the

    plant load at a given chiller’s load

    safety factor should be selected for

    both P/S and PLOVF systems with

    the purpose of making WFTDRAVL 

    equal or higher than WFTDRREQ to

    eliminate water flow via the decou-

    pling pipe and to optimize chiller-

    plant electrical energy use.

    The required number of chillers

    for the plant optimal operation can

    be calculated from the following

    equation:

    NREQ = (WFTDRREQ ÷ WFTDRAVL) ×

    CPLSF (4)

    where:

    WFTDRAVL = available chilled-wa-

    ter turndown ratio for a chiller plant

    with P/S and PLOVF systems

    WFTDRREQ = required chilled-wa-

    ter turndown ratio for a chiller plant

    with P/S and PLOVF systems

    CPLSF = chiller-plant load safety

    factor

    If the installed number of chill-

    ers in the plant (NI) is less than NREQ,

    then WFTDRRE Q  is greater than

    WFTDRAVLP/S & PLOVF and the applica-

    tion of the P/S system will be ben-

    eficial from the energy-conservation

    point of view as compared with a

    PLOVF system. If NI is greater than or

    equal to NREQ, then WFTDRREQ is less

    than or equal to WFTDRAVLP/S & PLOVF,

    and both P/S and PLOVF systems are

    equally energy-efficient.

    Chilled-Water Plants With Parallel

    and Series Chiller Evaporators

    Schematical representations of the

    chiller plant with a parallel and series

    connection of the chillers’ evapora-

    tors and P/S and PLOVF systems are

    shown in Figure 1.

    Chilled-water systems with par-

    allel chiller-evaporator connections

    (Figure 1A) are common. The chiller’s

    plant load and the relative water-flow

    rate is equally (W ÷ 2) shared by a

    number of chillers on line until it is

    reduced to a single chiller. The paral-

    lel chiller arrangement is relatively

    46 HPAC ENGINEERING OCTOBER 2011

    Circle 177

    DESIGN CRITERIA FOR PRIMARY/SECONDARY AND PRIMARY-LOOP-ONLY SYSTEMS

  • 8/9/2019 1011 HPACEngineering Burd

    5/7OCTOBER 2011 HPAC ENGINEERING 47

    DESIGN CRITERIA FOR PRIMARY/SECONDARY AND PRIMARY-LOOP-ONLY SYSTEMS

    the entire mechanical cooling season.

    We considered four control strat-

    egy options outlined earlier in Figure

    3. The conditions shown in Table 1 for

    a P/S system under Option 1 (without

    chilled-water reset temperature con-

    trol) will require the installation of

    nine 67-ton chillers. The same option

    for a PLOVF system will require the

    unit cooling-coil parameters will not

    change. Each table also includes two

     values of OSOSF for PLOVF system

    that are either 0.9 (Option 1A) or 0.82

    (Option 1B). Required number of chill-

    ers is calculated utilizing Equation 4 to

    satisfy the conditions under which a

    chiller plant will not have water flow-

    ing through the decoupling pipe for

    simple in operation and maintenance.

    Chilled-water systems with series

    chiller-evaporator connections are

    mostly utilized in custom-made appli-

    cations. The same series connection

    is equally applicable for a P/S and

    PLOVF system and variable-speed

    pump control. The series-chillers ar-

    rangement (assuming that identical

    chillers to be employed in both series

    and parallel arrangements) requires

    a substantial increase of the pressure

    drop via the evaporator (because of

    a twofold W increase in relative wa-

    ter flow via a chiller at design con-

    ditions). In this instance, the design

    pressure drop will be approximately

    eight times higher in a series ar-

    rangement (Figure 1B) than in a par-

    allel arrangement (Figure 1A).

    The series arrangement is less

    dependable in operation and will

    require employment of additional

    electrically operated control valves

    to remove/add a chiller from/to the

    line to adjust the load or to isolate

    a failed chiller (Figure 1B). The se-

    ries arrangement will make the reset

    chilled-water temperature control

    more challenging to implement, even

    for a P/S system because of the in-

    troduction of the additional variable

    parameter (TINT in Figure 1B) repre-

    senting the temperature of chilled

    water leaving Chiller 1 and entering

    Chiller 2.

    When the identical and equal

    number of chillers with similar

    load-sharing strategy is utilized, the

    chilled-water turndown ratio will bethe same for both parallel and series

    chillers’ evaporator arrangements.

    Specifying Chillers

    Tables 1 and 2 demonstrate com-

    parative chiller-plant analysis of the

    required number of chillers for P/S

    and PLOVF systems. The data in these

    tables are related to two sets of values

    for distribution-piping-system design

    temperature differential: ∆TDEDP =

    15°F (Table 1) and ∆TDEDP = 10°F (Table2). For the purpose of analysis of the

    ∆TDEDP impact on required number

    of chillers, we assumed that terminal-

     TABLE 1. Comparative chiller-plant turndown ratios and required number of chillers for

    P/S and PLOVF systems (∆ T DEDP = 15°F).

     Parameter

    P/SOption 1

    PLOVFOption 1A

    PLOVFOption 1B

    P/SOption 2

    P/SOption 3

    P/SOption 4

    Overall system operationalsafety factor, OSOSF

    1 0.90 0.82 1 1 1

    WFTDRREQ 12.5 12.5 12.5 2 2.1 4.2WFTDRAVL. DES 1.5 1.3 1.2 1.5 1.5 1.5

    Required number ofchillers, NREQ

    8.4 9.3 10.2 1.3 1.4 2.8

    Installed number ofchillers, NI

    9 10 11 2 2 3

    Required individual chillersdesign load, tons

    67 60 55 300 300 200

    Notes:1. Chiller plant design cooling load, tons: 6002. Installed chiller plant cooling load capacity, tons: 6003. Assumed chiller-plant load safety factor: 14. Assumed maximum chiller evaporator design chilled-water temperature differential

    (∆TDEMAX) = 22.4 °F

    5. Assumed distribution piping system design temperature differential (∆TDEDP) = 15 °F6. Control options 1, 2, 3 and 4 are in reference to Figure 37. AHUs serviced by the chiller plant are assumed to be operating with constant-air-flow control

    arrangement8. Reset chilled water temperature control is assumed to be applicable only for P/S system1

     TABLE 2. Comparative chiller-plant turndown ratios and required number of chillers for

    P/S and PLOVF systems (∆ T DEDP = 10°F).

     Parameter

    P/SOption 1

    PLOVFOption 1A

    PLOVFOption 1B

    P/SOption 2

    P/SOption 3

    P/SOption 4

    Overall system operationalsafety factor, OSOSF

    1 0.90 0.82 1 1 1

    WFTDRREQ 12.5 12.5 12.5 2 2.1 4.2

    WFTDRAVL. DES 2.2 2.0 1.8 2.2 2.2 2.2

    Required number of

    chillers, NREQ5.6 6.2 6.8 0.9 0.9 1.9

    Installed number ofchillers, NI

    6 7 7 1 1 2

    Required individual chillersdesign load, tons

    100 86 86 600 600 300

    Notes:1. Chiller-plant design cooling load, tons: 6002. Installed chiller-plant cooling-load capacity, tons: 6003. Assumed chiller-plant load safety factor: 14. Assumed maximum chiller evaporator design chilled water temperature differential

    (∆TDEMAX) = 22.4 °F5. Assumed distribution piping system design temperature differential (∆TDEDP) = 10 °F6. Control options 1, 2, 3 and 4 are in reference to Figure 37. AHUs serviced by the chiller plant are assumed to be operating with constant-air-flow control

    arrangement

    8. Reset chilled water temperature control is assumed to be applicable only for P/S system1

  • 8/9/2019 1011 HPACEngineering Burd

    6/7

    TM

    Introducing Atherion. In mythology, the name refers to the clean air

    only the gods could breathe. In reality, it’s the way Modine brings thefresh air from outside into your workplace.

    Designed to provide significant outdoor air ventilation to any space.

     15-30 ton commercial packaged ventilation system with optional energy recovery

    Meets latest ASHRAE 90.1 and 62.1 standards for efficiency, green buildingand indoor air quality

    Best-in-class MERV 16 filtration

     Higher IAQ with up to 100% outside air ventilation

    Industry-leading high efficiency gas heating option withConservicore™ Technology

    Integrates Modine’s PF™ microchannel condenser technology

    The latest in cooling technology with factory-installed

    microprocessor controlsR A I S E Y O U R C O M F O R T L E V E L  

    MODINE MANUFACTURING COMPANY |  1-800-828-HEAT |  WWW.MODINEHVAC.COM

    For more information, call 1-800-828-HEAT or visit www.MODINEHVAC.com.

    STEP INSIDE FOR A BREATH OF FRESH AIR.

    48 HPAC ENGINEERING OCTOBER 2011

    installation of either 10 60-ton chill-

    ers (Option 1A) or 11 55-ton chillers

    (Option 1B). Thus, the PLOVF system

    will utilize a higher number of chill-

    ers to satisfy given conditions.

    Table 1 further indicates that the

    number of installed chillers (NI) for a

    P/S system under Option 2 (assuming

    continual reset water-temperature

    control through the entire cooling

    season) could be reduced to two 300-

    ton chillers. The number of installed

    chillers (NI) under options 3 and 4

    (assuming reset water-temperature

    control during off-design conditions)

    for a P/S system could be reduced to

    two 300-ton chillers or three 200-ton

    chillers, respectively.

    Table 2 shows the number of chill-

    ers required for the system with

    ∆TDEDP = 10ºF could be reduced by

    the factor of 1.5 compared with the

    system with ∆TDEDP = 15ºF because

    of the higher WFTDRAVL value cal-

    culated from Equation 1. Still, the

    number required for a P/S system

    under options 2, 3, and 4 remains

    substantially lower than for a PLOVF

    system.

    In a real-life situation, it is unlikely

    (perhaps, with the exception of mod-

    ular chillers) that the number of chill-

    ers would be increased to nine or 10

    (Table 1) or to six or seven (Table 2)

    for a chiller plant with P/S and PLOVF

    systems because of the additional

    cost associated with the multiple

    chillers and their ancillary equipment

    (cooling towers, condenser pumps,

    controls, etc.). Because of that, two

    300-ton chillers are most likely to be

    installed for the considered plant.

    This is equivalent of the condi-

    tions when NI is less than NREQ and

    WFTDRREQ is greater than WFT-

    DRAVL for both P/S and PLOVF sys-

    tems. Under these scenarios, a P/S

    system will provide lower annual

    electrical energy usage for the chiller

    plant compared with a PLOVF sys-

    tem. As an additional benefit, a P/S

    system will reduce the number of

    times a system swtiches 

    from two-

    chiller to single-chiller operation and vice versa by about 10 percent to 18

    percent, compared to a PLOVF sys-

    tem with an OSOSF of 0.9 or 0.82,

    respectively.

    Summary

    This investigation specifies design

    criteria and required conditions at

    which P/S and PLOVF systems will

    have no energy wasteful chilled-wa-

    ter flow via the decoupling pipe of

    the chiller plants with parallel andseries chiller-evaporator arrange-

    ments and essentially operate as sin-

    gle-loop systems. As long as both P/SCircle 178

    DESIGN CRITERIA FOR PRIMARY/SECONDARY AND PRIMARY-LOOP-ONLY SYSTEMS

  • 8/9/2019 1011 HPACEngineering Burd

    7/7

    InfraMation 2011The Leading Infrared Camera Users Conference!

    Bally’s in Las Vegas | November 9 - 11

    Share your passion for thermalimaging and discover innovationsin Building Thermography. Visitwww.inframation.org to learn moreand register today.

    DiscoverHiddenProblems Before They Take aChilling Turn

    Prevent energy costs and HPAC fi xes fromskyrocketing, and warm your customers’ hearts.Spot signs of trouble early with the help of anaffordable FLIR i-Series thermal imaging camera.

    NASDAQ: FLIR

    The thermal images shown are for illustrative purposes only, and may not have been taken by the camera series depicted.

     Visi t www.fl ir.com/hpac-i to explore how

    i-Series can help you keep away the chill.

    Or call 866.477.3687 today.

    Quality – Innovation – Trust

    i-Series

    Point-and-Shoot Simplicity

    Starting Under $1,200

      OCTOBER 2011 HPAC ENGINEERING 49

    and PLOVF systems operate in this

    mode (assuming both systems have

    the same major parameters, identi-

    cal chiller and evaporator arrange-

    ments, equal design chilled-water-

    pump horsepower, overall flow, head

    pressure, variable-frequency-drive

    controls, etc.), their annual electrical

    energy use will be optimal and equal.

    The other findings of the article are

    as follows:

    • Satisfying the above conditions

    requires a larger number of chillers

    with a lower design cooling capacity

    as compared with current engineer-

    ing practice for both P/S and PLOVF

    systems and may call for the employ-

    ment of modular chillers.

    • The procedure of selecting and

    specifying available and required

    chilled-water turndown ratio for the

    evaporators of a chiller plant with

    P/S or PLOVF systems is presented

    to optimize electrical energy use.

    • The number of chillers for P/S

    or PLOVF systems is selected based

    on the optimal distribution-piping-

    system temperature differential

    and chiller-plant load safety factor

    to match the required and available

    magnitudes of the chilled-water turn-

    down ratio.

    • A P/S system requires a lower

    number of chillers in a chiller plant

    compared with a PLOVF system

    because of the higher controllable

    range of water-flow rate for P/S sys-

    tem and the ability to realize a reset

    chilled-water-temperature control

    strategy.• A PLOVF system compared with

    a P/S system—assuming both sys-

    tems have an equal number of chill-

    ers and chiller capacities—will need

    more frequent changes in the num-

    ber of operating chillers and their as-

    sociated ancillary equipment over the

    cooling season because of the lower

    available magnitude of chilled-water

    turndown ratio.

    • The similar procedures and de-

    sign criteria are equally applicable forthe selection of available and required

    magnitudes of a hot water boiler-plant

    turndown ratio, as well as a number

    of boilers in the central boiler plant

    with P/S or PLOVF systems.

    References

    1) Burd, A., & Burd, G. (2010, De-

    cember). Primary/secondary-loop vs.

    primary-loop-only systems. HPAC

     Engineering , pp. 36-45. Available at

    http://bit.ly/Burd_1210

     Did you find this art icle useful? Send

    comments and suggestions to Senior

     Editor Ron Rajecki at ron.rajecki@

    penton.com.

    Circle 179

    DESIGN CRITERIA FOR PRIMARY/SECONDARY AND PRIMARY-LOOP-ONLY SYSTEMS