40
Raytheon Marine GmbH High Seas Products Postfach 1166 D -- 24100Kiel Germany Tel +49--4 31--30 19--0 Fax +49--4 31--30 19--291 Email [email protected] www.raymarine.com R 3318E/131--037NG010.DOC032 Edition: 14. Sep. 1998 Amplifier Box Type 131--037 NG010 SERVICE MANUAL 1 Installation and First Putting into Operation 2 Care, Maintenance, Repair and Spare--parts Catalogue 3 Description

131-037NG010

Embed Size (px)

DESCRIPTION

raheon manalas

Citation preview

  • Raytheon Marine GmbHHigh Seas ProductsPostfach 1166D -- 24100 KielGermanyTel +49--4 31--30 19--0Fax +49--4 31--30 19--291Email [email protected]

    R

    3318E/131--037NG010.DOC032 Edition: 14. Sep. 1998

    AmplifierBox

    Type 131--037 NG010

    SERVICE MANUAL

    1 Installation and First Putting into Operation2 Care, Maintenance, Repair and Spare--parts Catalogue3 Description

  • Weitergabe sowie Vervielfltigung dieser Unterlage, Verwertung undMitteilung ihres Inhaltes nicht gestattet, soweit nicht ausdrcklichzugestanden. Zuwiderhandlungen verpflichten zu Schadenersatz.

    Copying of this document, and giving it to others and the use orcommunication of the contents thereof, are forbidden without expressauthority. Offenders are liable to the payment of damages.

    Toute communication ou reproduction de ce document, touteexploitation ou communication de son contenu sont interdites, saufautorisation expresse. Tout manquement cette rgle est illicite etexpose son auteur au versement de dommages et intrts.

    Sin nuestra expresa autorizacin, queda terminantemente prohibida lareproduccin total o parcial de este documento, as como su usoindebido y/o su exhibicin o comunicacin a terceros. De los infractoresse exigir el correspondiente resarcimiento de daos y perjuicios.

  • Amplifier Box

    Amplifier BoxService Manual

    3318E/131--037NG010.DOC032Edition: 08. July 1998

    Declaration of conformity

    We declare that this product meets the major protection requirements which are definedin the Council Direction on the approximation of the Laws of the Member States relatingto the electromagnetic compatibility (89/336/EEC). The following standard were referredto in examining the product for electromagnetic compatibility

    DIN EN 60945 (IEC 945+A1), March 1994Marine Navigational Equipment

    This declaration is declared binding for the producer/importer,Raytheon Anschtz GmbH, Zeyestrae 16--24, D--24106 Kiel,by

    Wolfgang Schme

    ...........................................Quality Assurance Manager

    Important Information on Electromagnetic Compatibility (EMC)-- Use in accordance with the intended purpose of the product:

    The product is intended to be operated on sea--going ships.-- Measures to ensure and to maintain the electromagnetic compatibility.

    The user/operator has to bear in mind the following:-- Assembly, cabling is to be made exclusively in accordance with the given assem-

    bly and installation documents.Here, special attention is to be paid to the EMC--relevant measures such as

    -- Establish the prescribed ground connections-- Make use of the prescribed cable types-- Apply the screenings to the prescribed points.

    -- Operation is to be performed with closed casing only (built--in devices must not beoperated outside the desk)

    -- After maintenance and repair work has been carried out, the initial state (originalstate) is to be established again.Here also, special attention is to be paid to carrying out the EMC--relevant mea-sures:

    -- Establish ground connections, put on screenings-- Connect the disconnected electrical protective means (EMC filters)-- Replace the defective electrical protective means by original parts-- Use original parts only-- Close the casing or incorporate the device into the desk, resp.

  • Amplifier Box

    Service Manual

    3318E/131--037NG010.DOC032 Edition: 08. July 1998

  • Amplifier Box

    Amplifier BoxService Manual

    I 3318E/131--037NG010.DOC032Edition: 08. July 1998

    CONTENTS Page

    1 Installation and First Putting into Operation 1-- 1. . . . . . . . . . . . . . . . . . . . . . . . . . . .1.1 Installation 1-- 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2 First Putting into Operation 1-- 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.1 Required Testing Equipment 1-- 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.2 Preconditions for Putting into Operation 1-- 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.3 Adjusting the Current Limitation for NFU Control 1-- 2. . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.4 Adjusting the Proportional Amplifier, Type 131--037.01 1-- 2. . . . . . . . . . . . . . . . . . . . . .

    1.2.4.1 Notes on the Proportional Amplifier 1-- 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.4.2 Zero Current and Rated Current Adjustment 1-- 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.4.2.1 Zero Current Adjustment for Starboard Solenoid Valve 1-- 3. . . . . . . . . . . . . . . . . . . . . .

    1.2.4.2.2 Rated Current Adjustment for Starboard Solenoid Valve 1-- 3. . . . . . . . . . . . . . . . . . . . .

    1.2.4.2.3 Zero Current Adjustment for Port Solenoid Valve 1-- 4. . . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.4.2.4 Rated Current Adjustment for Port Solenoid Valve 1-- 4. . . . . . . . . . . . . . . . . . . . . . . . . .

    1.2.4.2.5 Table of Adjusting Potentiometers 1-- 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2 Care, Maintenance, Repair, Spare Parts Catalogue 2-- 1. . . . . . . . . . . . . . . . . . . . . .2.1 Care and Maintenance 2-- 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2 Repair 2-- 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1 Circuit Description of the Proportional Amplifier, Type 131--037.01 2-- 1. . . . . . . . . . . .

    2.2.1.1 Setpoint Specification 2-- 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1.2 Modulation Limitation 2-- 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1.3 Zero--point Lift Function 2-- 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1.4 Zero--point Lift Suppression 2-- 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1.5 Utilization of a Sub--area of the Valve Characteristic 2-- 7. . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1.6 Ramp Shaper 2-- 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1.7 Superimposition of Hum (Iosc.) 2-- 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1.8 Enable / Disable of Power Stages 2--10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1.9 Activation of Relays for Internal Setpoint and

    Ramp Manipulating Time Specification 2--11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1.10 Monitoring and Operational Indicators 2--12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1.11 Test List 2--13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.2.1.12 Troubleshooting Instruction 2--14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3 Spare Parts Catalogue 2--15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2.3.1 Notes on Ordering 2--15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • Amplifier Box

    Service Manual

    II3318E/131--037NG010.DOC032 Edition: 08. July 1998

    CONTENTS Page

    3 Description 3-- 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.1 General Information 3-- 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.2 Construction of the Amplifier Box 3-- 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3 Description 3-- 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.1 Proportional Amplifier, Type 131--037.01 3-- 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.2 Power Supply Unit 3-- 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.3 Relay D1 3-- 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.4 Relay D2 3-- 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.3.5 Relay D3 3-- 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.4 Technical Data 3-- 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Annex

    Dimensional Drawing, Amplifier Box 131 E 037 HP014Wiring Diagram, Amplifier Box 131 D 037 HP015

  • Amplifier Box

    Amplifier BoxService Manual

    1--1 3318E/131--037NG010.DOC032Edition: 08. July 1998

    1 Installation and First Putting into Operation

    1.1 InstallationThe dimensions relevant to the installation of the Amplifier Box are to be drawn from theDimensional Drawing 131 E 037 HP014 in the Annex.

    Note!For performing installation work, use must be made of the connection and circuitdiagrams that are added to the equipment concerned !

    1.2 First Putting into Operation

    Attention:The adjusting work described in this chapter is exclusively to be carried out bytrained service personnel taking into account the safety measures!

    For any work leading to rudder movement, it must previously be ensured that nei-ther persons nor material might be endangered by the rudder or by the steeringgear!

    1.2.1 Required Testing EquipmentFor putting into operation, the following testing equipment is required:

    Multimeter with the following ranges:

    -- Volt (DC), internal resistance 20 kOhm/V-- Ampere-- Ohm

    1.2.2 Preconditions for Putting into OperationThe system components have been connected in accordance with the relevant installa-tion and connection diagrams and are ready for operation.

  • Amplifier Box

    Service Manual

    1--23318E/131--037NG010.DOC032 Edition: 08. July 1998

    1.2.3 Adjusting the Current Limitation for NFU Control-- Set the steering mode selector to NFU-- Connect the ammeter to between L1.15 and L1.22 or L1.23, resp.

    15 16 17 18 19 20 21 22 23

    A

    L1

    -- Adjust the rated current at R1 to the value indicated by the manufacturer of thesolenoid valves (e.g. 650 mA).

    1.2.4 Adjusting the Proportional Amplifier, Type 131--037.01

    1.2.4.1 Notes on the Proportional Amplifier

    Note!

    The proportional amplifier may only be removed when made dead.

    On delivery, two adjustment protocols incl. the preset values and the inserted jumpersare attached to the proportional amplifier (to be found in the inside door pocket).

    In case of a new installation, the jumpers are to be checked -- and, if required, to be cor-rected -- in accordance with this protocol.

    In the normal case, the values to be adjusted have been preset by the factory, providedthat the information on the solenoid valves used was known before delivery of the equip-ment.

  • Amplifier Box

    Amplifier BoxService Manual

    1--3 3318E/131--037NG010.DOC032Edition: 08. July 1998

    These values as well as the jumpers are then recorded in the adjustment protocol.If the values preset at the works should not coincide with the indicated values of the so-lenoid valves used, these must be re--adjusted by the service technician as described inthe following.

    These values are to be written into the adjustment protocols, and one of them is to besent to the Raytheon Marine Service Department.

    1.2.4.2 Zero Current and Rated Current Adjustment-- Set the steering mode selector to FU-- Connect voltmeter (DC) to L1.18 () and L1.19 (+)-- Should the jumpers B3, B6, B12, B14 and B16 not be inserted, these are to be

    inserted for the subsequent adjustments only.-- Connect the ammeter into the solenoid valve line L1.24-- Install the jumper to between L1.10 and L1.11

    10 11 12 18 19

    A

    L1

    V

    24 25

    A

    +

    1.2.4.2.1 Zero Current Adjustment for Starboard Solenoid Valve-- Adjust the voltmeter indication with potentiometer A1 to 0.8V-- Adjust the zero current with potentiometer NULL A to the zero current

    (e.g. 200 mA) indicated by the solenoid valve manufacturer.

    1.2.4.2.2 Rated Current Adjustment for Starboard Solenoid Valve-- Adjust the voltmeter indication with potentiometer A1 to 10V-- Adjust the rated voltage with potentiometer AB A to the rated

    current (e.g. 650 mA) indicated by the solenoid valve manufacturer.

    Note:Check zero current and rated current once more and, if required, correct them!

  • Amplifier Box

    Service Manual

    1--43318E/131--037NG010.DOC032 Edition: 08. July 1998

    1.2.4.2.3 Zero Current Adjustment for Port Solenoid Valve-- Connect the ammeter into the solenoid valve line L1.25-- Insert the jumper to between L1.10 and L1.12-- Adjust the voltmeter indication with potentiometer A2 to 0,8V-- Adjust the zero current with potentiometer NULL B to the zero current

    (e.g. 200mA) indicated by the solenoid valve manufacturer.

    1.2.4.2.4 Rated Current Adjustment for Port Solenoid Valve-- Adjust the voltmeter indication with potentiometer A2 to 10V-- Adjust the rated current with potentiometer AB B to the rated

    current (e.g. 650 mA) indicated by the solenoid valve manufacturer.

    Note:Check zero current and rated current once more and, if required, correct them!

    ATTENTION:Jumpers that have been inserted for the previously described adjustment only,must absolutely be removed!

    Set the potentiometers A1 and A2 to the left stop and leave it as that!

  • Amplifier Box

    Amplifier BoxService Manual

    1--5 3318E/131--037NG010.DOC032Edition: 08. July 1998

    1.2.4.2.5 Table of Adjusting Potentiometers

    Identifierortrimmer

    Function Range,clock-wise

    Operatingmode,settingrange

    Jumper

    inserted open

    Adjust-ment byfactory

    Relayposi-tion

    AB A Ratedcurrentadjust-ment forSTBDsolenoidvalve

    0 to100%Irated

    100%

    NULL A Zerocurrentadjust-ment forSTBDsolenoidvalve

    0 to 40%Irated

    0%

    AB B Ratedcurrentadjust-ment forPORTsolenoidvalve

    0 to100%Irated

    100%

    NULL B Zero cur-rent ad-justmentforPORTsolenoidvalve

    0 to 40%Irated

    0%

    A1 Internalset value

    0 to max0 to +10V0 to --10Vexternalpreset

    B3B4

    B4B3B3, B4

    0x

    K1

    A2 Internalset value

    0 to max0 to +10V0 to --10Vexternalpreset

    B5B6

    B6B5B5, B6

    0x

    K2

  • Amplifier Box

    Service Manual

    1--63318E/131--037NG010.DOC032 Edition: 08. July 1998

    B25

    B22

    B3B4

    B5B6

    B10B9

    B8B7

    B13B12B15B17B14B16

    B19B20

    IOSZAB BNULL B

    AB ANULL A

    V2 V1 A4 A3 A2 A1

    POTENTIOMETERR48 R34 R38 R33 R37 R28 R27 R22 R21 R20 R19

    Fig. 1--1: Components Diagram of the Proportional Amplifier, Type 131--037.01

  • Amplifier Box

    Amplifier BoxService Manual

    1--7 3318E/131--037NG010.DOC032Edition: 08. July 1998

    Amplifier Box

    Manufacturer: HERIONOrder No.: ...........................Solenoid Type: ...........................

    Adjusted variables:

    Function:

    Setpoint A1Setpoint A2

    Ramp time V1Ramp time V2

    Current solenoid Aat setpoint +10V(modulation limitation)

    Current solenoid Aat setpoint 0V(zero--point lift / jump)

    Current solenoid Bat setpoint --10V(modulation limitation)

    Current solenoid Bat setpoint 0V(zero--point lift / jump)

    Hum superimpositionHum frequency

    Lettersymbol:

    A1A2

    V1V2

    Ab.A

    Zero A

    Ab.B

    Zero B

    Ioscfosc

    Adjustedvalues:

    ................

    ................

    ................

    ................

    ................

    ................

    ................

    ................

    ................

    ................

    DIM

    VV

    OhmOhm

    A

    A

    A

    A

    AssHz

    Specifiedvalues:

    ................

    ................

    ................

    ................

    ................

    ................

    ................

    ................

    ................

    ................

    Jumpers (mark jumpers fitted with X)B3 B7 B12 B16 B22B4 B8 B13 B17 B25B5 B9 B14 B19B6 B10 B15 B20Responsible for Quality Assurance: ...................................Responsible for Commissioning: ....................................

  • Amplifier Box

    Service Manual

    1--83318E/131--037NG010.DOC032 Edition: 08. July 1998

  • Amplifier Box

    Amplifier BoxService Manual

    2--1 3318E/131--037NG010.DOC032Edition: 08. July 1998

    2 Care, Maintenance, Repair, Spare Parts Catalogue

    2.1 Care and MaintenanceNo care nor maintenance by the ships personnel is required for the Amplifier Box.

    2.2 Repair

    Attention:Repair work is exclusively to be carried out by trained service personnel taking intoaccount the safety measures!

    For any work leading to rudder movement, it must previously be ensured that nei-ther persons nor material might be endangered by the rudder or by the steeringgear!

    2.2.1 Circuit Description of the Proportional Amplifier, Type 131--037.01(See Block Diagram, Fig. 2--1).

  • Amplifier Box

    Service Manual

    2--23318E/131--037NG010.DOC032 Edition: 08. July 1998

    d12 d10z10d14 z12 z20 z22d28z26d24 b2 z2d2 b4

    b30b28b26b24b22b20b18b16

    d26

    z28

    z24

    z14

    d20

    z18

    z16

    d16

    d22

    d18z32d32z30d30b6b8b10

    b12b14b32

    z8 d6 z6 z4 d4 d8

    Fig. 2--1: Block Diagram of the Proportional Amplifier

  • Amplifier Box

    Amplifier BoxService Manual

    2--3 3318E/131--037NG010.DOC032Edition: 08. July 1998

    2.2.1.1 Setpoint SpecificationThe solenoid current is adjusted by specifying a setpoint.

    The setpoint can be specified either externally or internally.

    External: Setpoint specification via setpoint input terminal z20.Internal: Call--up of 1 to 4 adjustable setpoints via relays.

    Depending on the version of the proportional amplifier, an external setpoint can be spe-cified in the form of a voltage or current signal.The current input has an internal resistance of 500 Ohm, such that for an external set-point of 0 to 20 mA, the internal voltage level (which can be measured at MS) is 0 to10V.

    External

    0 to 10V / 0 to 20 mA0 to --10V / 0 to --20 mA

    Internal

    0 to 10V0 to --10V

    Final stage

    Solenoid ASolenoid B

    Setpoint range

    External setpoint specification for valves with two solenoids:If other sources are used for the setpoint specification instead of the voltages of +15Vsupplied by the proportional amplifier, these sources must be referred to the analogzero!

    Internal setpoint specification:The internal setpoint specification is carried out by means of the setpoint trimmersA1/A2.The adjusted setpoints can be activated by means of the internal relays K1/K2.

    Setpoints

    ExternalA1A2A3A4

    Controlled relay

    NoneK1K2K3K4 not used

    The relay with the highest index number has priority.

  • Amplifier Box

    Service Manual

    2--43318E/131--037NG010.DOC032 Edition: 08. July 1998

    The setpoint trimmers are connected to the internal reference voltage via jumpers insuch a way as to allow a voltage of 0 to 10V to be adjusted.Polarity can be changed by re--positioning the jumper concerned.

    Note:To provide an external setpoint specification for the setpoint trimmers, the jumper con-nection concerned must be removed.The permissible voltage range is 0 to 15V.

    Trimmer Polarity Jumper Factory--adjusted

    closed open 2 solenoids 1 solenoid

    A1 +--

    external setpointspecification

    B3B4

    B4B3

    B3, B4

    x x

    A2 +--

    external setpointspecification

    B5B6

    B6B5

    B5, B6

    x x

    A3

    (not used)

    +--

    external setpointspecification

    B7B8

    B8B7

    B7, B8

    x x

    A4

    (not used)

    +--

    external setpointspecification

    B9B10

    B10B9

    B9, B10

    x x

  • Amplifier Box

    Amplifier BoxService Manual

    2--5 3318E/131--037NG010.DOC032Edition: 08. July 1998

    2.2.1.2 Modulation LimitationThe trimming potentiometers AB A for solenoid A and AB B for solenoid B can be usedto attenuate the setpoint--specific modulation range of the power stage.It is thus possible to utilize only a sub--area of the valve characteristic (high resolution).

    Q = FlowP = PressureI = Solenoid CurrentW = Setpoint

    Solenoid B Solenoid AQB QA/PIB IA

    --10V/--20mA 0 10V/20mAW

    AB B AB A

    100%

    2.2.1.3 Zero--point Lift Function(only with proportional amplifiers for 2 solenoids)

    The zero--point lift function enables the solenoid current for each solenoid to be liftedeven with extremely small setpoints; separate adjustment is provided via the trimmingpotentiometers Zero A and Zero B.The zero--point lift is always operative only for the particular solenoid which is subject tosetpoint control.

    Q = FlowP = PressureI = Solenoid CurrentW = Setpoint

  • Amplifier Box

    Service Manual

    2--63318E/131--037NG010.DOC032 Edition: 08. July 1998

    2.2.1.4 Zero--point Lift Suppression(only with proportional amplifiers for 2 solenoids)

    The zero--point lift suppression is used to suppress the zero--point lift for setpoint specifi-cations in the range from approx. + 6% of the limit value (+10V / + 20 mA). This preventsthe solenoids from being activated alternately by very small setpoint fluctuations in thezero--range.

    Q = FlowP = PressureI = Solenoid CurrentW = Setpoint

  • Amplifier Box

    Amplifier BoxService Manual

    2--7 3318E/131--037NG010.DOC032Edition: 08. July 1998

    2.2.1.5 Utilization of a Sub--area of the Valve Characteristic(Example)

    The zero--point lift and the modulation limitation make it possible to utilize sub--areas ofthe valve characteristic in the normal setpoint range.In the example below, the working range of the proportional valve with the characteristicQA = f(IA) or QA = f(w), see Figure a, is to equal only 20 -- 60% of the nominal rangewith a setpoint specification of 0 to +10V.

    Adjustment:-- Set lift by means of trimmer Zero A in such a way that the lower range limit for QA

    is reached at w = 0V (see Figure c).

    -- Reduce the modulation limitation by means of trimmer AB A in such a way that theupper range limit for QA is reached with w = 10V (see Figure c).

    Figure a

    Characteristic with-out zero--point lift atmax. modulation li-mitation

    Figure b

    Characteristic withzero--point lift

    Figure c

    Characteristic withzero--point lift andreduced modulationrange

    The procedure is similar for the utilization of sub--areas of the other characteristic branch(solenoid B).

  • Amplifier Box

    Service Manual

    2--83318E/131--037NG010.DOC032 Edition: 08. July 1998

    2.2.1.6 Ramp ShaperThe ramp shaper ensures a steady rise in the output voltage when the input voltagerises abruptly.After the elapse of the manipulating time, the input and output voltages are of identicalvalue. The ramp shaper fitted on the PCB enables two ramps to be separately adjustedand selected by means of relays.These relays can be activated either via an SPS control or via parallel activation with thesetpoint.The adjustment of ramp manipulating time is linear.

    The jumpers enable internal or external operation to be selected separately for eachramp.

    For internal operation, the trimmers on the proportional amplifier are used.

    Ramp shaper, internal:

    Ramp

    V1V2

    Trimmer

    V1V2

    Activation of ramps V1 and V2:

    Ramp

    V1V2

    Relay

    K5K6

    If the relays K5 and K6 are not activated, the ramp is inoperative.Relay K6, ramp V2 has priority.

  • Amplifier Box

    Amplifier BoxService Manual

    2--9 3318E/131--037NG010.DOC032Edition: 08. July 1998

    Time range adjustment:

    Time range atw = 10V / 20 mA

    t1: 10ms -- 1st2: 100ms -- 10s

    Jumperclosed open

    B12 B13B13 B12

    Basic adjustmentby manufacturer

    x

    Internal/external ramp time adjustment:

    Ramp

    V1

    V2

    Operationmode

    int.

    ext.

    int.

    ext.

    closed

    B14

    B15

    B16

    B17

    open

    B15

    B14

    B17

    B16

    Basic adjustmentby manufacturer

    x

    x

    Jumper

    2.2.1.7 Superimposition of Hum (Iosc.)The trimming potentiometer Iosc. can be used to adjust the hum amplitude of the valvecurrent for solenoids A and B.The adjustment range is 0 to 40% of the modulation range. The hum frequency can beadjusted to 50Hz or 100Hz by means of a jumper.

    Position and setting of jumpers for selection of hum frequency:

    Hum frequency

    50Hz

    100Hz

    closed

    B 19

    B 20

    open

    B 20

    B 19

    Basic adjustmentby manufacturer

    x

    Jumper

    The superimposition of hum (dither) on the solenoid current improves the static frictionand thus the hysteresis of the valve.

    Optimum adjustment is achieved when small changes in the setpoint are registered bythe final control element, the hum amplitude used should always be the least possible.

  • Amplifier Box

    Service Manual

    2--103318E/131--037NG010.DOC032 Edition: 08. July 1998

    2.2.1.8 Enable / Disable of Power StagesTo enable the power stages, a control signal U > 14V must be applied to the enable in-put of the proportional amplifiers (jumper B22).If the input is open--circuit or the control voltage U < 10V, the output stage is disable.The enable is signalled by the enable LED (yellow).

    B 22 inserted by manufacturer

    Enable via internaljumper B22

  • Amplifier Box

    Amplifier BoxService Manual

    2--11 3318E/131--037NG010.DOC032Edition: 08. July 1998

    2.2.1.9 Activation of Relays for Internal Setpoint andRamp Manipulating Time SpecificationTo activate the relays K1 -- K6, the proportional amplifier supplies a voltage of 24V.The coil zero of the relays K1 to K6 is connected to the common potential.A jumper can be used to connect this common point to the zero of the proportional am-plifier or isolate this from the zero of the proportional amplifier for floating control.The common point is fed to the terminal z28.

    Activation of relays with non--floating contacts:

    Ref. point

    Zero ofamplifier PCB

    Free(floating control)

    closed

    B 25

    Basic adjustmentby manufacturer

    x

    open

    B 25

    Jumper

  • Amplifier Box

    Service Manual

    2--123318E/131--037NG010.DOC032 Edition: 08. July 1998

    2.2.1.10 Monitoring and Operational IndicatorsThe proportional amplifier is provided with circuitry to monitor the internal supply volt-ages.The enable signal is linked logically to this monitoring circuitry in such a way that thepower stages are enabled only if the correct signal combination is present.

    The operational status of the proportional amplifier is shown by the following LED indica-tors:

    Indication

    Operation

    Fault mode

    Enable

    Designation

    V 11

    V 17

    V 19

    Colour

    Green

    Red

    Yellow

    The operational indicator V 11 (green) signalizes that the internal supply voltages +15Vare present.

    The fault indicator V 17 (red) will light if the internal supply voltages fail or an enable ismissing, jumper B22 missing.

    The enable is signalized by V 19 (yellow).

  • Amplifier Box

    Amplifier BoxService Manual

    2--13 3318E/131--037NG010.DOC032Edition: 08. July 1998

    2.2.1.11 Test List

    Testing device: Multimeter with the following ranges:Volt (AC, DC), internal resistance 20 kOhm/VoltAmpereOhm

    Measurement

    Voltage supply

    Solenoid currentA

    Solenoid currentB

    Internalsupply voltage

    NFUsupply voltage

    Voltage failure

    Signalafter ramp

    Supply voltagefor steering modeselector

    TP+

    L1.5L1.4L1.3L1.2

    L1.6

    L1.8

    L1.10

    L1.15

    L1.17

    L1.19

    L1.20

    -- ( I )

    L1.1L1.1L1.1L1.1

    L1.7

    L1.9

    L1.18

    L1.14

    L1.16

    L1.18

    L1.14

    Measured value

    440V AC or400V AC or230V AC or115V AC

    After balancing

    After balancing

    +24V DC

    +24V DC

    open circuit

    0 ... +10V DC

    +24V DC

    Conditions

    Correspondingstarter boxswitched on

    Setpoint to be ap-plied to input:L1.10 to L1.11orL1.10 to L1.12

    Correspondingstarter boxswitched on

    Correspondingstarter boxswitched on

    Proportional am-plifier withoutfunction

    Only with corre-sponding inputsignal and whenramp functionis activated !

    Correspondingstarter boxswitched on

  • Amplifier Box

    Service Manual

    2--143318E/131--037NG010.DOC032 Edition: 08. July 1998

    2.2.1.12 Troubleshooting Instruction

    Measures for trouble detection:

    1: Check the operating voltageapplied to terminals L1.1 ... L1.5

    2: Check the 24V DC voltage on theoutput of the mains transformer at +/--

    1: Check the 24V DC supply voltage

    2: Replace the proportional amplifier

    Trouble:

    Green and YellowLEDs on theproportional ampli-fier not alight !

    Red LED on theproportional ampli-fier not alight !

  • Amplifier Box

    Amplifier BoxService Manual

    2--15 3318E/131--037NG010.DOC032Edition: 08. July 1998

    2.3 Spare Parts Catalogue

    2.3.1 Notes on OrderingTo ensure fast processing of replacement parts orders and to make sure that the correctreplacement part is delivered, the following details are required:

    1. Name of the ship2. Raytheon Anschtz order number:

    e.g.: 610 0 616373. Device type (refer to type label) that the replacement part is required for:

    e.g.: Amplifier Box, Type 131--037 NG010.4. Exact designation of the replacement part from the specifications given in the

    replacement parts catalogue

    Example:

    Stock No. Designation Drawing No.

    1.607 172 Screw M 4x10 DIN 7985 A4

    5. Required number of parts

  • Amplifier Box

    Service Manual

    2--163318E/131--037NG010.DOC032 Edition: 08. July 1998

  • ErsatzteilkatalogSPARE PARTS

    VerstrkerkastenAMPLIFIER BOXType 131--037 NG010, 131--037 MOD024 CATALOGUE

    14.578 1

    5

    1

    1

    3

    1

    4

    2

    6

  • ErsatzteilkatalogSPARE PARTS

    VerstrkerkastenAMPLIFIER BOXType 131--037 NG010, 131--037 MOD024 CATALOGUE

    All depicted items which are not mentioned in the text are not applicable for this unit. Since further development may necessitate making modifi-cations to existing equipment, its conformity with the relevant illustrations and drawings is not always ensured. RAYTHEON MARINE will beunder no liability whatever that may arise from any such differences.

    14.578 2RA/S--SU 9809 EDITION 02

    Pos. Lager--Nr.STOCK--NO.

    Benennung DESIGNATION Zeichnungs--Nr.PART--No.

    Stck.QTY.

    Herst.--CodeMFRC

    Versorgungs--Nr.NATO--STOCK--NO.

    1 1.721 453 Relais Relay DIL ER--22--G 3 D8942

    2 1.762 123 Sicherung 3,15A T Fuse 3.15A T IEC 127--2 1 --

    3 2.014 166 Netzteil Power Supply Unit ISK--E 1 --

    4 1.507 975 Proportionalverstrker Proportional Amplifier 131--037.01 E01 1 D0138

    5 1.778 377 Drehwiderstand 33W Potentiometer 33W P10 1 D8439

    61 3.609 123 Ventilberwachungs--PCB Solenoid Monitoring PCB 131--037.03 1 D2865

    --------------------------------------------------1 in MOD024

  • Amplifier Box

    Amplifier BoxService Manual

    3--1 3318E/131--037NG010.DOC032Edition: 08. July 1998

    3 Description

    3.1 General InformationThe ANSCHTZ Amplifier Box is a central component in the ships steering controlsystem. It makes available a DC output signal for activating the solenoids for proportio-nal valves. In accordance with this output current, the valves ensure stepless control ofthe oil delivery volume the steering gear pumps.Use of the amplifier box can be made both for FU and for NFU operation.

    7

    4

    5

    3

    1

    6

    2

    8

    Fig. 3--1: Construction of the Amplifier Box

    1 Relay D32 Fuse3 Power Supply Unit4 Relay D15 Relay D26 Proportional Amplifier7 Potentiometer R18 Casing (Cover removed)

  • Amplifier Box

    Service Manual

    3--23318E/131--037NG010.DOC032 Edition: 08. July 1998

    3.2 Construction of the Amplifier BoxThe amplifier box consists of

    -- Casing-- Proportional Amplifier, Type 131--037.01-- Power Supply Unit, consisting of

    -- Transformer M1-- Rectifier and-- Fuse

    -- Relay D1-- Relay D2-- Relay D3-- Terminal Strip

    3.3 Description

    3.3.1 Proportional Amplifier, Type 131--037.01The Proportional Amplifier, Type 131--037.01 makes available a DC output signal for ac-tivating the solenoids for proportional valves. In accordance with this output current, thevalves ensure stepless control of the oil delivery volume for the steering gear pumps.

    The external set value is given by the analog set rudder signal.

    The internal set value specifications can be configured and are activated via the steeringcontrol signals (port/starboard) applied to the input side.

    The proportional amplifier is designed as a single board and includes the following cha-racteristics:

    -- Type acc. to DIN 41612-- 24V supply voltage-- Power consumption 35VA as a maximum-- 32--pole connector-- Adjustable lift function-- Short--circuit--proof and ground--fault--proof final stages-- Current limitation to max. 1600 mA each direction.

  • Amplifier Box

    Amplifier BoxService Manual

    3--3 3318E/131--037NG010.DOC032Edition: 08. July 1998

    3.3.2 Power Supply UnitThe power supply unit consists of

    -- transformer M1-- rectifier and-- fuse

    From the input voltage, the power supply unit produces the internal supply voltage of24V DC (unregulated) for the proportional amplifier.The power supply unit is fused on its secondary by 3.15A (slow).

    3.3.3 Relay D1The relay D1 monitors the 24V DC output voltage of the proportional amplifier and signa-lizes voltage failure alarm via a floating contact.

    3.3.4 Relay D2An externally connected operating mode selector permits change--over from follow--upcontrol (FU) or AUTO to non--follow--up control (NFU). By that, the relay D2 switches R1for current limitation into the output circuit.

    3.3.5 Relay D3Not used here!

  • Amplifier Box

    Service Manual

    3--43318E/131--037NG010.DOC032 Edition: 08. July 1998

    3.4 Technical Data Primary voltages: 115V/230V/400V/440V 0.72A 50--60Hz

    Type of enclosure: IP 00 (without casing)IP 44 (with casing)

    EMC: see Declaration of conformity

    Activation of solenoids up to 1.6A

    Making available of a regulable NFU voltage supply

    Internal change--over from FU/AUTO to NFU

    Floating alarm contact

    Possibility of internal or external set--value specification

    The device is approved by German Lloyd

    Mechanical Data See dimensional drawing 131 E 037 HP014

    Proportional Amplifier

    Solenoid current: 1.6A

    Supply: 24V 10%; 50--60HzPower consumption: 32.5VAAlternatively:Supply: 24V DC (4V)Power consumption: 1.4AOutput current for solenoid: 1.6ASolenoid current R20: 2.5 ... 5.5Solenoid connecting line: 1.5mm2, max. 60m

    2.5mm2, max. 100m4.0mm2, max. 160m

  • Amplifier Box

    Amplifier BoxService Manual

    3--5 3318E/131--037NG010.DOC032Edition: 08. July 1998

    Inputs, analog

    Setpoint at pin z20:for solenoid A: 0 ... 10Vfor solenoid B: 0 ... --10Vinput resistance: 200

    Alternatively:for solenoid A: 0 ... 20mAfor solenoid B: 0 ... --20mAinput resistance: 200

    Setpoint at pin d10, z10, d14, z12: 0 ... 15Vinput resistance: 15k

    Manipulating time at pins d28, z26:input resistance: 330

    Control inputs, digital

    Activation of relays K1 ... K6:nominal relay voltage: 24Vcurrent consumption per relay: 20mA

    Enable signal of power stage: 24V; tol. +2V, --9V

    Input resistance: 2,7k

  • Amplifier Box

    Service Manual

    3--63318E/131--037NG010.DOC032 Edition: 08. July 1998

    Outputs

    For supply of setpoint adjustersand actual--value pick--up:

    output voltage: +15V, 0.6V--15V, 0.6V

    output current: max. 75mA with +15Vmax. 50mA with --15V

    For supply of internal relays and enable: +24V; tol. +2V, --8Vmax. 75mA

    Master Slave MS pin d12: 0 ... +10V

    External Load: > 100k

    Manipulating time, ext.: 0 ... 10V

    Output current for solenoid: 0.8 or 1.6 or 2.4A

    Transmission characteristics

    Zero--point lift with solenoids A and B: 0 ... 40% InominalZero--point lift suppression: approx. 6% of limit valueZero--point lift with solenoids A: 0 ... 40% InominalModulation limitation: 0 ... 100% InominalManipulating time of ramp shaper internal/external for abrupt setpoint change of 10V:

    range 1: 0.01 ... 1s; tol. 10%range 2: 0.1 ... 10s; tol. 10%

    General characteristic data

    Superimposed hum: 0 ... 30% InominalHum frequency: 50 or 100HzTime to ready/warm--up time: 10min

  • Amplifier Box

    Amplifier BoxService Manual

    3--7 3318E/131--037NG010.DOC032Edition: 08. July 1998

    Mechanical Data

    Dimensions (length x width x depth): 172mm x 100mm x 50mm

    Weight: 400g

    Ambient temperature, storage: --20C ... +70C

    Ambient temperature, operation: --8C ... +55C

    Connections:plug connector: 32--pin connector, DIN 41612 Type F

    Test plug:plug connector: 2--row, 10--pin, to fit tester TE 01

  • Amplifier Box

    Service Manual

    3--83318E/131--037NG010.DOC032 Edition: 08. July 1998