10MAR10 ISSUED FOR IDR MC KFT LRP JA
07MAY10 ISSUED FOR INFORMATION AA KFT LRP JA
MOVED TO VENDOR PACKAGE)
07JUN10 RE-ISSUED FOR INFORMATION (FIRE WATER PUMP STARTER AA KFT LRP JA
05OCT10 ISSUED FOR CLIENT REVIEW MRC LRP KC JA
28OCT10 ISSUED FOR DESIGN MRC LRP JA ME
ISSUED FOR CONSTRUCTION MAV DF JA/KC CW
F
G
H
I
J
0
PGHU-CV-EDSLD-400001 SINGLE LINE DIAGRAM HGCP AREA POWER RETICULATION SHEET 1
PGHU-CV-EDSYM-000001 ELECTRICAL CIRCUIT SYMBOLS & EQUIPMENT DESIGNATIONS LEGEND SHEET
PGHU-CV-EDECI-400003 TO 400004 HV PROTECTION AND METERING DIAGRAMS
PGHU-CV-EDECI-400005 TO 400006 LV PROTECTION AND METERING DIAGRAMS
PGHU-CV-EDECI-414001~02/415001 AREA 41 PROTECTION AND METERING DIAGRAMS
PGHU-CV-EDECI-450001 WELLPADS PROTECTION & METERING DIAGRAM
JA
KFT
NONE10MAR10MC
0PGHU-CV-EDSLD-400002
AREA POWER RETICULATION (SHEET 2 OF 2)HIDES GAS CONDITIONING PLANT
SINGLE LINE DIAGRAMPNG LNG PROJECT
630ANC NC NC
BUS B
M3~
FIRE WATER PUMP PACKAGE40-PFW41102
(550kW)
POWER GENERATION HV SWITCHROOM40-LER81120
CO
NTIN
UE
D FR
OM D
RA
WIN
G P
GH
U-C
V-E
DSL
D-400001
HIDES WELLPAD B 45-LER71220
HIDES WELLPAD C 45-LER71230
40-SWG82270
40-MCC82274 40-MCC82275
40-MCC82272 40-MCC82273
BOOSTER COMPRESSOR MAIN LV SWITCHROOM 40-LER81170
BOOSTER COMPRESSOR No.1LV SWITCHROOM
40-LER65710
NO
NO
NO
NC NC
NC NC
NC NC
NC NCNC NC
ATS
BOOSTER COMPRESSOR No.2LV SWITCHROOM
40-LER65720
40-XF82370
6.6kV/420V1.6MVA ONAN
Dyn11
40-XF82371
6.6kV/420V1.6MVA ONANDyn11
45-DP82830
400V, 160A, 3+N+E, 10kA FOR 1 Sec
45-XF82330
6.6kV/420V100kVA ONAN
Dyn11Z=4%
45-DP82820
400V, 160A, 3+N+E, 10kA FOR 1 Sec
45-XF82320
6.6kV/420V100kVA ONAN
Dyn11Z=4%
HIDES WELLPAD D 45-LER71240
45-DP82840
400V, 160A, 3+N+E, 10kA FOR 1 Sec
45-XF82340
6.6kV/420V100kVA ONAN
Dyn11Z=4%
HIDES WELLPAD E 45-LER71250
45-DP82850
400V, 160A, 3+N+E, 10kA FOR 1 Sec
45-XF82350
6.6kV/420V100kVA ONAN
Dyn11Z=4%
HIDES WELLPAD F 45-LER71260
45-DP82860
400V, 160A, 3+N+E, 10kA FOR 1 Sec
HIDES WELLPAD G 45-LER71270
45-DP82870
400V, 160A, 3+N+E, 10kA FOR 1 Sec
45-XF82370
6.6kV/420V100kVA ONAN
Dyn11Z=4%
NO NO
NO
630A
NOTE 1
40-SWG82320
40-SWG82321
BUS A
40-EJB82310HGCP HV INTERFACEJUNCTION BOX
RTD
250A
630A630A
250A 160A
45-XF82360
6.6kV/420V100kVA ONAN
Dyn11Z=4%
FUTURE ANGORE WELLPAD FEEDER
NC NO
630A 630A
40-EJB82311HGCP HV INTERFACEJUNCTION BOX
NOTE 2 NOTE 2
NO NO
250A 250A
NO630A
630ANO
SPARE SPARE SPARE SPARE
NC
FUTURE
40-BD82270 40-BD82271
NOTE 4 NOTE 4
NOTE 4 NOTE 4 NOTE 4 NOTE 4 NOTE 4 NOTE 4
315A
41-SWG82320
100A 315A
315A
315A
6.6kV, 630A, 3+E, 31.5kA RMS SYM FOR 3 Secs
100A
41-XF82311
6.6kV/420V750kVA ONANDyn11Z=5%
41-XF82310
6.6kV/420V750kVA ONAN
Dyn11Z=5%
41-SWG82210
400V, 1600A, 3+N+E, 80kA FOR 1 Sec
41-SWG82211
NON-ESSENTIAL SERVICES
41-SWG82222 41-SWG82223
400V, 3500A, 3+N+E, 80kA FOR 1 Sec
41-XF82323
6.6kV/420V2MVA ONANDyn11Z=6.25%
41-XF82322
6.6kV/420V2MVA ONAN
Dyn11Z=6.25%
ESSENTIAL & HVAC SERVICES
41-XF82321
6.6kV/420V2MVA ONANDyn11Z=6.25%
41-XF82320
6.6kV/420V2MVA ONAN
Dyn11Z=6.25%
NC NC NC NC
NO
ATSATS
41-SWG82220
400V, 3500A, 3+N+E, 80kA FOR 1 Sec
41-SWG82221
NC NC
NO
ATS
NO
INDUSTRIAL PARK LV SWITCHROOM41-LER81110
NOTE 1NOTE 1NOTE 1
NOTE 4 NOTE 4 NOTE 4NOTE 4 NOTE 4 NOTE 4
41-BD82222 41-BD82223
c:\
pdfm
aker\P
DF
MA
KERIN\56
777263_
8.D
WG 2011-09-12 03:4
6
REFERENCE DRAWING NUMBER REFERENCE DRAWING TITLE
DRAWN BY
DRAWING NO:
DATE SCALE CKD
APPD
REVISION
A1
23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 4039 412117 18 19 20 225 6 7 8 9 10 11 12 13 14 15 16
14
15
16
17
18
19
20
21
22
23
25
24
26
0 1 2 3 4
9
10
11
12
13
5
6
7
8
1
3
2
4
0
REV DATE REVISION DESCRIPTION BY CHD ENG APPD
Esso Highlands Limited
14
15
16
17
18
19
20
21
22
23
25
24
26
9
10
11
12
13
5
6
7
8
1
3
2
4
0
23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 4039 412117 18 19 20 225 6 7 8 9 10 11 12 13 14 15 160 1 2 3 4
CBI Clough JV
EPC4: HGCP and WELLPADS PROJECT
41-BD82220 41-BD82221
41-SWG82321 6.6kV, 630A, 3+E, 31.5kA RMS SYM FOR 3 Secs
OPERATIONS ROTATOR COMMUNITY SWITCHROOM
41-LER81120
AUTO TRANSFER SYSTEM SHALL BE INHIBITED UNDER FAULT CONDITIONS.1.
2. CABLES SHALL BE RUN TO TRANSFORMER LOCATION, COILED, LABELLEDAND SECURED FOR FUTURE CONNECTION.
NOTES:
3. SURGE PROTECTION TO BE INSTALLED WHERE REQUIRED FOR LIGHTNINGOVERVOLTAGES/SWITCHING TRANSIENTS.
4. LV SYSTEM EARTHED VIA MEN LINKS LOCATED IN LV SWITCHBOARDS.
NOTE 5 NOTE 5
5. SPARE WELLPAD FEEDER USED DURING BUSBAR MAINTENANCE.
NC
NC
NC
NC
NC
45-SWG82320
NC
6. IN ESSENTIAL MODE HV FEEDER U/V PROTECTION IS DISABLED &
FEEDERS/LOADS ARE RE-ENERGIZED SEQUENTIALLY.
80kA FOR 1 Sec
45-SWG82330 45-SWG82340 45-SWG82360 45-SWG82370
25A
25A
25A
25A
25A
25A
45-SWG82350