Rated current of H.V.( Amps ) 27.99 (Line current)
Rated current of L.V.( Amps ) 2133.41
c.Voltage of each step 412.5V
Vector Symbol Dyn11
Tapingsa. No.of positions 17 (16 Steps)
b. Range + 5 % to - 15 % in steps of 1.25 %
a. H.V. Winding Delta
b. L.V. Winding Star
c. Neutral brought out for earthing Yes
Over load capacity As per IS : 6600
1.04. WINDING CONNECTION DETAILS
Connections
Max. Temperature rise in oil by 50
thermometer above 50 C ambient
Temperature (Deg.C)
Max.Temperature rise above 50 C ambient 55
temperature of winding by resistancemethod. (Deg.C)
1.03. RATING
Rated Voltage of H.V.( Volts ) 33000
Rated voltage of L.V.(Volts) 433
Frequency Variation + / - 3 %
Combined Voltage and Frequency variation + / - 10 %Bare Bushings
Bus duct
No. Of Phases 3
Frequency ( Hz ) 50
Voltage variation + / - 10 %
1.02. SYSTEM PARTICULARS
Nominal Voltage (V) 33000
Highest System Voltage (V) 36000
Specifications and Standard as per IS IS 2026
Type of Cooling ONAN
Wound Copper Double Wound
Make SERVOMAX INDIA LTD.
Type Core Type Oil ImmersedLocation Outdoor
TECHNICAL SPECIFICATION OF TRANSFORMER
The transformer will be designed and manufactured as per IS:2026-1977 and will be supplied with first filling
of oil to IS:335 of 1993.
1.01. GENERAL SPECIFICATIONS
Rated KVA 1600
Service & Duty Continuous
7/31/2019 1600kVA (33-433) gtp
2/3
*1
*2
*3
4
5
1 UPF 0.8 P.F.
98.87 98.59
99.07 98.84
99.22 99.03
99.18 98.98
2
3
1
2
3
4
L.V Winding (KV) 3
b.One minute power Frequency
withstand voltage
H.V Winding (KV ) 70
withstand voltage
H.V Winding (KV peak) 170
L.V Winding (KV Peak) N.A
In oil 7
Out of oil 201.12. TEST VOLTAGES
a.Impulse (1.2 / 50 micro second wave)
In oil 60
Out of oil 355
L.V. to Earth (mm)
d.Between LV Winding and core Solid Cylinder
1.10. TYPE OF JOINTS IN WINDING Brazed
1.11. MINIMUM CLEARANCES
H.V to Earth (mm)
a.HV Winding turn Insulation DPC
b.LV Winding turn Insulation DPC
c.Between HV and LV Winding Oil Duct + Solid Cylinder + Oil Duct
1.08. WINDING INSULATION LEVEL
a.HV Winding (KV uniform) 36
b.LV Winding (KV uniform) 1.1
1.09. INSULATION OF CONDUCTORS
Type of Winding
a.HV Winding Continuous disc
b.LV Winding Helical
Type of Construction Core Type
Insulation between laminations Carlit
Type of joint between core limb and yoke Mitered
Maximum efficiency (Percentage) 99.25
Load at which Max.efficiency occurs KVA 606.56*Subject to IS tolerance
1.07. CONSTRUCTIONAL DETAILS
b. 75% Full Load
c. 50% Full Load
d. 25% Full Load
Regulation at full load at 75 Deg.C 0.8 u.p.f 4.59%
1.06. EFFICIENCY
Efficiency at 75 Deg.C.
a. 100% Full Load
normal Tap 6.25
Regulation at full load at 75 Deg.C u.p.f 1.19%
Copper losses at rated current and rated
frequency at 75 deg.C(Watts)At Normal Tap. 16000Percentage Impedance at 75 Deg.C at
1.05. LOSSES AND OTHERS
No load losses at rated frequency and
voltage (Watts) 2300
7/31/2019 1600kVA (33-433) gtp
3/3
1
2
3
4
1
2
3
4
5 Length Breadth Height
3100 2550 2550
S.N
1
2
3
45
6
7
8
9
10
11
12
13
14
15
1617
18
19
20
21
1
2
1
Yours faithfully,
for SERVOMAX INDIA LTD.
[MARKETING INCHARGE]
1.18. TESTS
ROUTINE TESTS
As per IS : 2026 all the Routine tests are carried out by our work , in the presence ofyour representative.
We now look forward to receive your valued order
Thanking you,
RTCC PANEL One
1.17. PAINTING
Surface preparation By Grit Blasting
Paint Enamel Light Grey, Shade No. 631, of IS : 5
OTI One
WTI One
MARSHALLING BOX One
Uni- directional Flat Rollers Four
Separate Neutral Bushing OneGOR One
Filter valve with blanking plate One
Explosion vent with Diaphragm One
Radiators (Detachable) Adequate
Air release device One
Thermometer Pocket One
Drain valve with blanking plate One
Oil filling hole with cap One
Oil Level Indicator One
Dehydrating Silicagel Breather One
Lifting Lugs Four
OLTC OneConservator with Drain plug One
1.16. STANDARD FITTINGS AND ACCESSORIES
DESCRIPTION QTY
Rating and terminal marking plate One
Earthing Terminals Two
Total Weight of Transformer (Kg.) 6415
Overall dimensions of the transformer
(approx.) in mm
1.15. Parts to be detached for transport Rollers, Breather & Radiators
(Core and windings with clamps )Volume of insulating oil (Ltr.) 2355
Tank and fittings (Kg.) 1895
Thickness of cover plates (mm) 6
Thickness of radiator (pipes or sheets) 1.25 mm
1.14. WEIGHTS AND DIMENSIONS (APPROX.)
Net untanking weight (Kg.) 2515
1.13. DETAILS OF TANK AND MATERIALS M.S
Thickness of side plates(mm) 5
Thickness of bottom plates (mm) 6