1600kVA (33-433) gtp

Embed Size (px)

Citation preview

  • 7/31/2019 1600kVA (33-433) gtp

    1/3

    1

    2

    3

    45

    6

    7

    8

    1

    2

    3

    4

    5

    6

    78 Terminal Arrangement HV

    LV

    1

    2

    3

    4

    3

    4

    5

    1

    2

    3

    Rated current of H.V.( Amps ) 27.99 (Line current)

    Rated current of L.V.( Amps ) 2133.41

    c.Voltage of each step 412.5V

    Vector Symbol Dyn11

    Tapingsa. No.of positions 17 (16 Steps)

    b. Range + 5 % to - 15 % in steps of 1.25 %

    a. H.V. Winding Delta

    b. L.V. Winding Star

    c. Neutral brought out for earthing Yes

    Over load capacity As per IS : 6600

    1.04. WINDING CONNECTION DETAILS

    Connections

    Max. Temperature rise in oil by 50

    thermometer above 50 C ambient

    Temperature (Deg.C)

    Max.Temperature rise above 50 C ambient 55

    temperature of winding by resistancemethod. (Deg.C)

    1.03. RATING

    Rated Voltage of H.V.( Volts ) 33000

    Rated voltage of L.V.(Volts) 433

    Frequency Variation + / - 3 %

    Combined Voltage and Frequency variation + / - 10 %Bare Bushings

    Bus duct

    No. Of Phases 3

    Frequency ( Hz ) 50

    Voltage variation + / - 10 %

    1.02. SYSTEM PARTICULARS

    Nominal Voltage (V) 33000

    Highest System Voltage (V) 36000

    Specifications and Standard as per IS IS 2026

    Type of Cooling ONAN

    Wound Copper Double Wound

    Make SERVOMAX INDIA LTD.

    Type Core Type Oil ImmersedLocation Outdoor

    TECHNICAL SPECIFICATION OF TRANSFORMER

    The transformer will be designed and manufactured as per IS:2026-1977 and will be supplied with first filling

    of oil to IS:335 of 1993.

    1.01. GENERAL SPECIFICATIONS

    Rated KVA 1600

    Service & Duty Continuous

  • 7/31/2019 1600kVA (33-433) gtp

    2/3

    *1

    *2

    *3

    4

    5

    1 UPF 0.8 P.F.

    98.87 98.59

    99.07 98.84

    99.22 99.03

    99.18 98.98

    2

    3

    1

    2

    3

    4

    L.V Winding (KV) 3

    b.One minute power Frequency

    withstand voltage

    H.V Winding (KV ) 70

    withstand voltage

    H.V Winding (KV peak) 170

    L.V Winding (KV Peak) N.A

    In oil 7

    Out of oil 201.12. TEST VOLTAGES

    a.Impulse (1.2 / 50 micro second wave)

    In oil 60

    Out of oil 355

    L.V. to Earth (mm)

    d.Between LV Winding and core Solid Cylinder

    1.10. TYPE OF JOINTS IN WINDING Brazed

    1.11. MINIMUM CLEARANCES

    H.V to Earth (mm)

    a.HV Winding turn Insulation DPC

    b.LV Winding turn Insulation DPC

    c.Between HV and LV Winding Oil Duct + Solid Cylinder + Oil Duct

    1.08. WINDING INSULATION LEVEL

    a.HV Winding (KV uniform) 36

    b.LV Winding (KV uniform) 1.1

    1.09. INSULATION OF CONDUCTORS

    Type of Winding

    a.HV Winding Continuous disc

    b.LV Winding Helical

    Type of Construction Core Type

    Insulation between laminations Carlit

    Type of joint between core limb and yoke Mitered

    Maximum efficiency (Percentage) 99.25

    Load at which Max.efficiency occurs KVA 606.56*Subject to IS tolerance

    1.07. CONSTRUCTIONAL DETAILS

    b. 75% Full Load

    c. 50% Full Load

    d. 25% Full Load

    Regulation at full load at 75 Deg.C 0.8 u.p.f 4.59%

    1.06. EFFICIENCY

    Efficiency at 75 Deg.C.

    a. 100% Full Load

    normal Tap 6.25

    Regulation at full load at 75 Deg.C u.p.f 1.19%

    Copper losses at rated current and rated

    frequency at 75 deg.C(Watts)At Normal Tap. 16000Percentage Impedance at 75 Deg.C at

    1.05. LOSSES AND OTHERS

    No load losses at rated frequency and

    voltage (Watts) 2300

  • 7/31/2019 1600kVA (33-433) gtp

    3/3

    1

    2

    3

    4

    1

    2

    3

    4

    5 Length Breadth Height

    3100 2550 2550

    S.N

    1

    2

    3

    45

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    1617

    18

    19

    20

    21

    1

    2

    1

    Yours faithfully,

    for SERVOMAX INDIA LTD.

    [MARKETING INCHARGE]

    1.18. TESTS

    ROUTINE TESTS

    As per IS : 2026 all the Routine tests are carried out by our work , in the presence ofyour representative.

    We now look forward to receive your valued order

    Thanking you,

    RTCC PANEL One

    1.17. PAINTING

    Surface preparation By Grit Blasting

    Paint Enamel Light Grey, Shade No. 631, of IS : 5

    OTI One

    WTI One

    MARSHALLING BOX One

    Uni- directional Flat Rollers Four

    Separate Neutral Bushing OneGOR One

    Filter valve with blanking plate One

    Explosion vent with Diaphragm One

    Radiators (Detachable) Adequate

    Air release device One

    Thermometer Pocket One

    Drain valve with blanking plate One

    Oil filling hole with cap One

    Oil Level Indicator One

    Dehydrating Silicagel Breather One

    Lifting Lugs Four

    OLTC OneConservator with Drain plug One

    1.16. STANDARD FITTINGS AND ACCESSORIES

    DESCRIPTION QTY

    Rating and terminal marking plate One

    Earthing Terminals Two

    Total Weight of Transformer (Kg.) 6415

    Overall dimensions of the transformer

    (approx.) in mm

    1.15. Parts to be detached for transport Rollers, Breather & Radiators

    (Core and windings with clamps )Volume of insulating oil (Ltr.) 2355

    Tank and fittings (Kg.) 1895

    Thickness of cover plates (mm) 6

    Thickness of radiator (pipes or sheets) 1.25 mm

    1.14. WEIGHTS AND DIMENSIONS (APPROX.)

    Net untanking weight (Kg.) 2515

    1.13. DETAILS OF TANK AND MATERIALS M.S

    Thickness of side plates(mm) 5

    Thickness of bottom plates (mm) 6