Nuclear Air Cleaning Conference

Filter Test Facility Report On The Testing of HEPA

Filters for the DOE

August 2008

Page 2: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

2

Air Techniques International Test Laboratory1708 Whitehead Rd., Baltimore, MD 21207

Page 3: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

3

Air Techniques International Test Laboratory Overview

• Air Techniques International established an independent Filter Test Laboratory in Baltimore, Maryland

• DOE performs a ASME/ANSI NQA-1 Quality Audit

• DOE issued contract to ATI Filter Test Laboratory (ATITL) to perform tasks of the former DOE Filter Test Facility

• Secretary of Energy Memo, June 4, 2001, the Filter Test Lab is to be utilized by DOE Site Contractors

• Testing service is provided to the DOE complex

• DOE work has top priority

Page 4: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

4

Rejection Categories

Resistance: Criteria of ≤ 1.0 “ w.g. for filters rated ≥ 500-1250 cfm and 1.3” w.g. for filters rated ≤125 - ≥2000 cfm

Penetration: ≤0.03%

Manufacturing Defects: • Filter Frame/Case Defective• Gaskets• Faceguard installation• Filter pack installation• Defective media• Sealant problems• Separators• Missing rivets or bolts• Dimensional tolerance• Out of square measurements

Page 5: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

5

Rejection Categories

P.O/ Specification Discrepancy:• Missing UL labels• Labeled incorrectly• Filters rated incorrectly• Wrong model number• Packaging

Shipping Damage: • (Inspect Damage to Shipping Crates, Pallets & Filter Cartons)• Reject Filter when Damaged

Page 6: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

6

Summary Of Filter Rejections

•*Test facility closed 5 months for relocation and audit

•**Partial Year

9.8%3543,59720008.0%2172,72220014.8%1022,1272002 5.4%1512,77220036.3%2153,44120047.2%1682,3312005*

11.8%**184**1554**2008**

19.6%4852472200710.4%21320442006

PercentageRejected

NumberRejected

NumberTested

Fiscal Year

(Oct 1 – Sept. 30)

Page 7: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

7

Summary Of Filter Rejections

•*Test facility closed 5 months for relocation and audit

•**Partial Year

3545270364302000

217491743002001

102832422002002

151527932602003

215486863632004

166281561982005*

184054923802008**

48502142382762007

213184814702006

TotalShipping Damage

P.O./Spec Discrepancy

Mfg. Defects

Penetration ResistanceFiscal Year

(Oct 1 – Sept. 30)

Page 8: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

8

HEPA FILTERS TESTED / REJECTED

# Filters Tested and % Failure by Fiscal Year

0500

1000150020002500300035004000

2000 2001 2002 2003 2004 2005 2006 2007 2008 (10

months) Fiscal Year

# Fi

lters

0.0%

5.0%

10.0%

15.0%

20.0%

25.0%

% F

ailu

re

Total Tested Percent Rejected

Page 9: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

9

HEPA FILTER REJECTION BY NUMBER

Total Filters Rejected by Fiscal Year

050

100150200250300350400450500

2000 2001 2002 2003 2004 2005 2006 2007 2008 (10

months) Fiscal Year

# Fi

lters

Rej

ecte

d

Page 10: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

10

HEPA FAILURES BY TYPE

# Failures (Resistance, Penetration & Manufacturing ) by Fiscal Year

0

50

100

150

200

250

2000 2001 2002 2003 2004 2005 2006 2007 2008 (10

months) Fiscal Year

# Fa

ilure

s

Resistance Penetration Manufacturing

Page 11: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

11

HEPA FAILURES BY TYPE

# Failures (PO/Specification Discreps & Shipping ) by Fiscal Year

050

100150200250300

2000 2001 2002 2003 2004 2005 2006 2007 2008 (10

months) Fiscal Year

# Fa

ilure

s

PO/Spec Discreps Shipping Damage

Page 12: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

12

ATI FILTER TEST FACILITYOPERATIONS

Page 13: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

13

ATITL Quality Program Plan

1.0 POLICY2.0 SCOPE3.0 REFERENCES4.0 DEFINITIONS5.0 ORGANIZATION

5.1 Structure5.2 Functional Responsibilities

6.0 QUALITY ASSURANCE REQUIREMENT7.0 DESIGN CONTROL8.0 PROCUREMENT CONTROL9.0 INSPECTION & TEST10.0 DOCUMENT CONTROL

Page 14: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

14

ATITL Quality Program Plan

11.0 CONTROL OF PURCHASED ITEMS AND SERVICES12.0 IDENTIFICATION AND CONTROL OF ITEMS 13.0 CONTROL OF PROCESSES14.0 PERSONNEL TRAINING, QUALIFICATION AND CERTIFICATION15.0 CONTROL OF MEASURING AND TEST EQUIPMENT16.0 HANDLING, STORAGE AND SHIPPING17.0 INSPECTION, TEST AND OPERATING STATUS18.0 CONTROL OF NONCONFORMING ITEMS19.0 CORRECTIVE ACTIONS20.0 QUALITY ASSURANCE RECORDS21.0 QUALITY ASSURANCE AUDITSAPPENDICESFigures – Organization Chart

Page 15: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

15

RECOMMENDED SHIPPING CRATE

Page 16: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

16

NOT RECOMMENDED FILTER SHIPPING METHODS

Page 17: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

17

UNLOADING FILTER BOXES

Page 18: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

18

INSPECTION CHECK LIST

Page 19: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

19

DAMAGED BOX & FILTER

Page 20: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

20

INSPECTION

Page 21: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

21

CASE SQUARE INSPECTION

Page 22: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

22

PENTRATION / RESISTANCE TEST

Page 23: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

23

FILTER TEST

Page 24: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

24

TEST LABEL - REPACKING

Page 25: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

25

RE-BOX FILTER

Page 26: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

26

RE-PACK FILTERS IN CRATE

Page 27: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

27

SHIPPING

Page 28: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

28

REJECTEXAMPLES

Page 29: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

29

GASKET - REJECT

Page 30: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

30

FLUID SEAL - REJECT

Page 31: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

31

CASE - REJECT

Page 32: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

32

FILTER CASE - REJECT

Page 33: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

33

FILTER CASE - REJECT

Page 34: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

34

Summary

• ALL MANUFACTURERS’ FILTER QUALITY HAS VARIED DURING LAST NINE YEARS AS SHOWN BY THE FILTER TEST FACILITY (FTF) REPORTS

• A NEED FOR SPECIFICATION CONSISTENCY (Reference To ASME AG-1 &/or DOE-STD-3020-2005)

• A NEED FOR MANUFACTURERS’ TO TIGHTEN QUALITY CONTROL

• A NEED FOR QUALITY CONTROL INSPECTIONS OF MANUFACTURERS IN ADDITION TO AUDITS

Page 35: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

35

Any Questions?

• Eric Hanson, ATI President

• Dave Crosby, Vice President of Filter Testing

• Julie Stormo, Lab Manager

• Jan Fretthold, Lab Supervisor

• ATI Test Lab e-mail address [email protected] (phone) 410-277-3448 (fax)

Page 36: 17. Filter Test Facility Report on the Testing of HEPA ...isnatt.org/Conferences/30/17. Filter Test Facility Report on the... · Filter Test Facility Report On The Testing of HEPA

Air Techniques International

36