1.Short Circuir Calculation

Embed Size (px)

Citation preview

  • 7/31/2019 1.Short Circuir Calculation

    1/12

    PREPARED BY

    Voltage Rating E :E kV 0.415 0.415 DG Rating :P kVA 2000 1500 Sub transient Reactance :Xd" P.U 0.109 0.108 % Reactance : Xd" % =Xd" in PU *100 10.90 10.80 Reactance in P.U :Ohm =% Xd" * kV 2 * 10 / rated kVA 0.009386263 0.0124002

    Impedence of the DG isgiven by :Zg Ohm =(E/Psc)*1000 0.0861125 0.114816667 0

    Short Ciruit kVA (Psc) atDG terminal is given by. :Psc kVA =(P/%Xd)*100 18348.62385 13888.88889 9124

    Short Circuit Current isGiven by :Isc kA =(Psc in kVA)/(1.732XEX1000) 2 5.52745465 19.32286498 12.6

    Enter the data as per your DG Sync panel configuration

    DG's E in kV P in kVA Xd" in PU Xd" in % Psc in kVA Isc in k1 0.415 1000 0.14 14 7142.857143 2 0.415 1000 0.13 13 7692.307692 3 0.415 2000 0.109 10.9 18348.62385 4 0.415 2000 0.109 10.9 18348.62385 5 0.415 2000 0.109 10.9 18348.62385 6 0.415 1000 0.13 13 7692.307692

    Total fault level 9000 77573.34409 kVA

    The equivalent Z @ at theDG Synch panel 0.002220157 Ohm(Which is given by parallel method ofcomputing equivalent impedance)

    A Short Ckt. Current @ DG sync panel is thecumulativiof all thi individual DG short 97.22173182 kAcircuit current.

    B Short Ckt. Current @ DG syncpanel is 107.9236263 kA

    Data from

    DG SHORT CIRCUIT CALCULATION

    OR

    =(Total Fault level /1.732*E*1000)

    AJAY KUMAR

  • 7/31/2019 1.Short Circuir Calculation

    2/12

    From To R X Z

    Trr-1 EB/DG PANEL-1 0.000129 0.0000705 0.005145268

    EB/DG PANE SMSB-A&B 0.000129 0.0000705 0.000275639

    EB/DG PANE SMSB-C&D 0.000129 0.0000705 0.000275639

    SMSB-A&B MLP 0.00021 0.0000718 0.001664514

    SMSB-C&D AHU-1 0.000264 0.0000716 0.002051528

    SMSB-1 UPS-B1 0.00016 0.0000839 0.002709949

    SMSB-1 UPS-ACOP 0.00016 0.0000839 0.002709949

    SMSB-A&B CAFETERIA 0.00021 0.0000718 0.039948339

    SMSB-2 AHU-2 0.000264 0.0000716 0.002051528

    SMSB-2 UPS-C1 0.00016 0.0000839 0.001806633

    SMSB-2 UPS-D1 0.00016 0.0000839 0.001806633

    SMSB-2 UPS-ACOP 0.00016 0.0000839 0.001806633

    SMSB-A&B LC 0.00021 0.0000718 0.016645141

    SMSB-C&D LC 0.00021 0.0000718 0.016645141

    MLP MLP-B 0.000409 0.0000724 0.024921516

    MLP MLP-C 0.000409 0.0000724 0.019937212

    MLP MLP-D 0.000409 0.0000724 0.024921516

    MLP-B LDB-01B 0.00394 0.0000837 0.078817779

    MLP-C LDB-01C 0.00394 0.0000837 0.078817779

    MLP-D LDB-01D 0.00394 0.0000837 0.078817779

    LDB-01B R1 0.00798 0.399

    LDB-01C R1 0.00798 0.399

    LDB-01D R1 0.00798 0.399

    AHU-1 AHU PANEL-B 0.000409 0.0000724 0.024921516

    AHU-2 AHU PANEL-C 0.000409 0.0000724 0.019937212

    LDB-01C

    LDB-01D

    R1

    R1

    R1

    LC

    AHU PANEL-B

    AHU PANEL-C

    MLP-B

    MLP-C

    MLP-D

    LDB-01B

    Impedance of cable or BBTLocations

    EB/DG PANEL

    AHU-2

    SMSB-1

    CAFETERIA

    UPS-ACOP

    Fault @ Different

    UPS-C1

    UPS-ACOP

    UPS-D1

    SMSB-2

    MLP

    AHU-1

    UPS-B1

    LC

  • 7/31/2019 1.Short Circuir Calculation

    3/12

    From To R X Z Impedance of cable or BBT

    LocationsFault @ Different

    AHU-2 AHU PANEL-D 0.000409 0.0000724 0.024921516

    AHU PANEL- AHU-41C 0.00394 0.0000884 0.118229747 MLP-C LDB-41C 0.00394 0.0000837 0.118226668

    UPS-B1 UPSBBT-B 0.000129 0.0000836 0.005380214

    UPS-C1 UPSBBT-C 0.000129 0.0000836 0.005380214

    UPS-D1 UPSBBT-D 0.000129 0.0000836 0.005380214

    UPSBBT-B UPS FDB-01B 0.000931 0.000103 0.014050205

    UPSBBT-C UPS FDB-01C 0.000931 0.000103 0.014050205

    UPSBBT-D UPS FDB-01C 0.000931 0.000103 0.014050205

    UPS FDB-01B UDB-01B 0.00147 0.0000808 0.022083284

    UPS FDB-01C UDB-01C 0.00147 0.0000808 0.022083284

    UPS FDB-01D UDB-01D 0.00147 0.0000808 0.022083284

    UDB-01B R1 0.00798 0.399

    UDB-01C R1 0.00798 0.399

    UDB-01D R1 0.00798 0.399

    UPSBBT-D

    UDB-01C

    UDB-01C

    R1

    R1

    R1

    UPSBBT-B

    UPSBBT-C

    LDB-41C

    AHU-41C

    AHU PANEL-D

    UPS FDB-01C

    UPS FDB-01C

    UDB-01B

    UPS FDB-01B

  • 7/31/2019 1.Short Circuir Calculation

    4/12

  • 7/31/2019 1.Short Circuir Calculation

    5/12

    Constant CABLE REQUIREDCABLEC S in Sqmm USED

    11.1 161.488048 BBT

    11.1 155.6626212 8x300

    11.1 155.6626212 1x300

    11.1 127.8188244 2x185

    11.1 122.7151623 2x150

    11.1 114.9093413 2x150

    11.1 114.9093413 2x150

    11.1 24.993549 2x185

    11.1 122.7151623 1x300

    11.1 125.8960907 2x150

    11.1 125.8960907 2x150

    11.1 125.8960907 2x150

    11.1 48.9754599 2x150

    11.1 48.9754599 2x150

    11.1 34.75106834 1x95

    11.1 40.67423278 1x95

    11.1 34.75106834 1x95

    11.1 10.52173396 10

    11.1 11.00704984 10

    11.1 10.52173396 10

    11.1 2.322898127 2.5

    11.1 2.345731747 2.5

    11.1 2.322898127 2.5

    11.1 34.36252268 1x95

    11.1 40.14295992 1x95

  • 7/31/2019 1.Short Circuir Calculation

    6/12

    Constan CABLE REQUIREDCABLEC S in Sqmm USED

    11.1 34.36252268 1x95

    11.1 8.044310014 1x611.1 8.065589196 1x10

    11.1 2.163653833 2x185

    11.1 2.167214993 2x185

    11.1 2.167214993 2x185

    11.1 2.109732619 1x25

    11.1 2.113118354 1x25

    11.1 2.113118354 1x25

    11.1 2.03020944 1x16

    11.1 2.033344554 1x16

    11.1 2.033344554 1x16

    11.1 1.207707066 2.5

    11.1 1.20881579 2.5

    11.1 1.20881579 2.5

  • 7/31/2019 1.Short Circuir Calculation

    7/12

    PREPARED BY AJAY KUMAR

    System Voltage Primary : E1 11 KV

    System Voltage Secondary : E2 415 VShort Circuit MVA @11KV Side : Psc 193 MVATransformer rating : P 1600 KVATransformer %Impedance : %Z 6.25Transformation ratio : K 0.037727SC Current withstand time : t 1 SecConstant for PVC Aluminium cable : C 13.2Constant for PVC Copper cable : C 8.69Constant for XLPE Aluminium cable : C 10.63 Constant for XLPE Copper cables : C 6.99

    The minimum size of the conductor(S) in Sqmm S= Iw*C*Sqrt(t) required to withstand shortcircuit current(Iw) inkA for t sec is given by

    Total Impedance of Upstream network Zup= (E1*E1)/Psc= 0.626943005 Ohm

    Zup= Zup*K*K = 0.000892358 Ohm

    Zt= (E2*E2)/(P*1000)*%Z/100= 0.006727539 Ohm

    Fault Current on the Secondary of Transformer Isec= (E2)/(1.732*(Zup+Zt) = 31.44 kA

    From To No of R X Z RunsMAIN LT PANEL Stenter 0.000161 0.000071 0.007038 5

    MAIN LT PANEL Pad M/c Panel 0.000129 0.0000705 0.007595 3

    MAIN LT PANEL Dyeing 0.000102 0.0000704 0.009295 3

    MAIN LT PANEL Boiler 0.000102 0.0000704 0.004957 3

    MAIN LT PANEL Compressor 0.00021 0.0000718 0.013316 2

    MAIN LT PANEL Lighting

    MAIN LT PANEL

    SHORT CIRCUIT CALCULATION

    Impedance of cable or BBT

    Zup on Low Voltage Side

    Fault @ DifferentLocationsmain power panel-1

    Dyeing

    Boiler

    Compressor

    Lighting

    Pad M/c Panel

    Impedance of the transformer

  • 7/31/2019 1.Short Circuir Calculation

    8/12

    ReactanceAl Cu

    1.5 0.01550 0.0001072.5 0.00950 0.0000985

    4 0.00950 0.00590 0.00009276 0.00590 0.00394 0.0000884

    10 0.00394 0.00234 0.000083716 0.00244 0.00147 0.0000808

    Approx. AC ResistanceAluminiumArea in Sqmm

  • 7/31/2019 1.Short Circuir Calculation

    9/12

    Area AC Reactance @ 50HzSqmm Ohm/Meter

    Al Cu Al/Cu

    25 0.001530 0.000931 0.0000810035 0.001110 0.000671 0.0000783050 0.000818 0.000496 0.0000750070 0.000565 0.000344 0.0000740095 0.000409 0.000248 0.00007240

    120 0.000323 0.000197 0.00007120150 0.000264 0.000160 0.00007160185 0.000210 0.000129 0.00007180240 0.000161 0.000099 0.00007100300 0.000129 0.000080 0.00007050 0.000128400 0.000102 0.000064 0.00007040500 0.000078 0.000052 0.00007020

    630 0.000061 0.000043 0.00006980.

    AC Resistance @ 90deg.COhm / Meters

  • 7/31/2019 1.Short Circuir Calculation

    10/12

    Ohm/Meter Ohm/MeterArea Sqmm Arm UnarmAl / Cu Al. Cu Al / Cu Al / Cu

    1.5 0.015500 0.00015502.5 0.009500 0.0001420

    4 0.00950 0.005900 0.00013206 0.00590 0.003940 0.0001230

    10 0.00394 0.002340 0.0001340 0.000114016 0.00244 0.001470 0.0001250 0.000108025 0.00153 0.000931 0.0001200 0.000103035 0.00111 0.000671 0.0001140 0.000098650 0.00082 0.000496 0.0001080 0.000093770 0.00057 0.000344 0.0001020 0.000090095 0.00041 0.000248 0.0001000 0.0000865

    120 0.00032 0.000197 0.0000968 0.0000841150 0.00026 0.000160 0.0000941 0.0000839185 0.00021 0.000129 0.0000932 0.0000836240 0.00016 0.000099 0.0000900 0.0000813300 0.00013 0.000080 0.0000881 0.0000795400 0.00010 0.000064 0.0000873 0.0000787500 0.00008 0.000052 0.0000859 0.0000779630 0.00006 0.000037 0.0000843 0.0000765800 0.00005 0.000029 0.0000826 0.0000755

    1000 0.00004 0.000023 0.0000829 0.0000752

    Flexible Cables

    Area SqmmAl / Cu

    1.5 0.01332.5 0.00798

    4 0.00495

    Approx. ACReactance at 50Hz

    Approx. ACresistance at 20 deg

    Approx. ACresistance at 90 deg

  • 7/31/2019 1.Short Circuir Calculation

    11/12

    Copper Conductor

    AC Resistance Reactance400 0.00000724 0.00000292600 0.000 0.00000229800 0.000 0.000

    1000 0.000 0.0000017771200 0.000 0.000001381500 0.000 0.000001131600 0.273 0.0932000 0.245 0.0822500 0.182 0.0673000 0.140 0.0553500 0.124 0.0484000 0.110 0.0434500 0.094 0.0405000 0.083 0.330

    6300 0.074 0.031

    Aluminum conductor

    AC Resistance Reactance400 0.00001202 0.00000271600 0.00001134 0.0000023800 0.00000797 0.00000175

    1000 0.00000642 0.000001541200 0.00000404 0.00000144

    1500 0.00000335 0.000001091600 0.00000287 0.00000093 Shearing Most Useful2000 0.00000023 0.000000742500 0.00000184 0.000000633200 0.00000142 0.000000523500 0.00000122 0.000000394000 0.00000110 0.000000324500 0.00000096 0.000000265000 0.000 0.00000017

    Ampere Rating