Upload
carrieandsmuts
View
235
Download
0
Embed Size (px)
Citation preview
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
1/12
Single-phase overhead
distribution switchesTypes DCD, RBD, SID, LSID, and ITD
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
2/122 Single-phase overhead distribution switches |ABB product bulletin
DCD distribution class disconnect switch
Product features
Base and back strap: strengthened channel of galvanized
steel for corrosion protection and solid operation
Insulators available in silicone or porcelain
Self-aligning silver to silver contacts ensure long life
Entire blade is silver-plated copper
Loadbreak hooks made of galvanized steel for corrosion
protection, to be used with loadbreak tool
Standard two-hole NEMA plated pad or optional two-piece
parallel groove
All testing is in accordance with IEEE 37.34
Application
The DCD disconnect switch is a hookstick-operated switch
used to sectionalize or isolate circuits on electrical distribution
systems through 38 kV. The distribution switch can be mounted
on a single or double crossarm and is rated for 600 or 900 A
continuous current and 65 kA peak withstand current (40 kA
momentary).
Operation
ABB disconnect switches include loadbreak hooks for use
with a portable loadbreak tool. Silver-plated contacts enhance
efficient current transfers. The pull-ring activates the latch as a
pry-out lever for easy opening and ice breaking.
Blade operation
A blade stop limits the blade range of motion to the 90 and
160 postions, and a latch prevents the switch from opening
under high momentary current.
Mounting
The DCD can be mounted in the following configurations:
Vertical or underhung
Polemount
Single or double crossarm
BACKUPSTRAP
E5.18[131.45]
A
B
D
G 5.5-7.62[139.7-193.6]
G
C
BACK STRAP OPTION COMES WITH 8"OR 10" GALVANIZED CARRIAGEBOLTS, 2 BOLT OR 4 BOLT O PTIONS.
BASE
F
1.75[44.45]
0.63[15.88
ACCEPTS 1/2" BOLTS
0.94[23.81]
3
[76.2
]
1.
5
[3 8
.1
]
0.
81
[20.
57]
5.18[131.45]
A B C D E F G
Voltageclass(kV)
BIL(kV) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (lb) (kg) (lb) (kg)
15 110 25.10 637 11.67 296 8.00 203 13.29 338 12.50 317 22.60 574 4.63-6.77 118-172
40
(600 A) 18
21
(900 A) 9.5
27 125 28.57 726 15.07 383 9.00 229 14.29 363 15.90 404 26.00 660 6.38-8.47 162-215
42
(600 A) 19
23
(600 A) 10
38 150 28.57 726 15.07 383 10.0 254 15.32 389 15.90 404 26.00 660 6.38-8.47 162-215
44
(600 A) 20
26
(900 A) 12
Unit dimensions
Outline drawing
Porcelainweight
Siliconeweight
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
3/12ABB product bulletin | Single-phase overhead distribution switches
Creep Strike
Porcelain Silicone Porcelain Silicone
Voltage
class (kV)BIL(kV) (in) (mm) (in) (mm) (in) (mm) (in) (mm)
15 110 17.60 441 19.53 496 7.71 196 7.79 198
27 125 22.95 583 28.30 719 8.55 217 9.26 234
38 150 23.87 606 39.52 1003 9.81 249 10.62 270
Insulator details
Maximumvoltage (kV)
BIL(kV)
Continuouscurrent (A)
Peakwithstandcurre
(kA Asym)
15 110 600/900 65
27 125 600/900 6538 150 600/900 65
Ratings
Vertical or underhung Polemount Single crossarm
Selection guide
Description Code Definition
Switch type S Type DCD switch
Max kV, BIL
1 15 kV, 110 kV BIL
2 27 kV, 125 kV BIL
5 38 kV, 150 kV BIL
Blade stop
N No stop
A 90 stop
B 160 stop
InsulatorsP Porcelain gray 2.25" bolt circle
J Silicone gray 2.25" bolt circle
Terminal connectors
A NEMA 2-hole with captured 0.5" hardware (galvanized)
C NEMA 2-hole with two-piece clamshell #2-500MCM (10013A44G01)
N NEMA 2-hole pad standard
H NEMA 2-hole with two-piece clamshell 4/0-500MCM (10013A44G02)
BaseS Smooth slots in base for 0.5" carriage bolts
C Serrated slots in base for .375" carriage bolts
Mounting brackets
N No back bracket
8 Two 8" long, .375-16 carriage bolts with back bracket and hardware
1 Two 10" long, .375-16 carriage bolts with back bracket and hardware
A Four 8" long, .375-16 carriage bolts with back bracket and hardware
B Four 10" long, .375-16 carriage bolts with back bracket and hardware
Unused N Space holder for future options
Continuous current6 600 amperes
9 900 amperes
Specials0 None
B Stainless steel nameplate
Example: S2BJNC1N60 = DCD, 27 kV, 125 kV BIL, 160 stop, silicone insulators, standard NEMA 2-hole pads, base with serrated slots, back bracket with two 10" carriage bolts an
hardware, 600 A, no specials
DCD mounting configurations
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
4/124 Single-phase overhead distribution switches |ABB product bulletin
Product features
Base and back strap: strengthened channel of galvanized
steel for corrosion protection and solid operation
Insulators available in silicone or porcelain
Self-aligning silver to silver contacts ensure long life
Entire blade is silver-plated copper
Loadbreak hooks made of galvanized steel for corrosion
protection, to be used with loadbreak tool
Bypass blade is left- or right-hand operation
Standard two-hole NEMA plated pad or optional two-piece
parallel groove
All testing is in accordance with IEEE 37.34
Application
The RBD distribution bypass disconnect switch provides an
economical means for bypassing and disconnecting reclosers
or other equipment, allowing quick system reconfigurations to
perform maintenance on any device without interrupting service.
Operation
In normal operation, the bypass blade is open and the two
disconnect blades are closed, allowing the unit to be energized.
When maintenance, testing, repair, or removal is required, first
close the bypass blade to provide a parallel current path. Then
open both disconnect blades of the bypass switch. Service
continuity is maintained and the unit is isolated from the line.
Reverse the process to put the unit back in service.
RBD distribution class bypass disconnect switch
Recloser
Disconnectblade
Recloserbypass switch
Source Bypass blade Load
Disconnectblade
RBD bypass operating positions
Recloser
Disconnectblade
Recloserbypass switch
SourceBypassblade Load
Disconnectblade
RBD normal operating positions
A
C
J
I
1.06[26.92]
E60
FBG
D
H
30
1.75[44.
45]
0.63[15.
88]
1.25
[31.75]
ACCEPTS
1/2" BOLTS
1.75
[44.45]
0.61
[15.49]
0.61
[15.49]
1.72[43.
69]
ACCEPTS
1/2" BOLTSDD
Blade operation
A blade stop limits the blade range of motion to the 90 and
160 postions, and a latch prevents the switch from opening
under high momentary current.
Mounting
The RBD can be mounted in the following configurations:
Vertical or underhung
Polemount
Single or double crossarm
RBD mounting configurations
Outline drawing
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
5/12ABB product bulletin | Single-phase overhead distribution switches
Selection guide
Description Code Definition
Switch type R Type RBD bypass switch
Max kV, BIL
1 15 kV, 110 kV BIL
2 27 kV, 125 kV BIL
5 38 kV, 150 kV BIL
Blade stop for parallel disconnectblades
N No stop
A 90 stop
Blade stop for bypass disconnectblade
N No stop (not available on crossarm mounting)
A 90 stop (required on crossarm mounting)
B 160 stop (not available on crossarm mounting)
InsulatorsP Porcelain gray 2.25" bolt circle
J Silicone gray 2.25" bolt circle
Terminal connectors
A NEMA 2-hole with captured 0.5" hardware (galvanized)
C NEMA 2-hole with two-piece clamshell #2-500MCM (10013A44G01)
N NEMA 2-hole pad standard
H NEMA 2-hole with two-piece clamshell 4/0-500MCM (10013A44G02)
Mounting brackets
N No back bracket
8 Four 8" long, .375-16 carriage bolts with two back brackets and hardware
1 Four 10" long, .375-16 carriage bolts with two back brackets and hardware
P Pole mount frame 30 from horizontal
Y Galvanized steel crossarm combo (3 RBDs on crossarm)
Z Non-metal crossarm combo (3 RBDs on crossarm)
Bypass bladeL Left-hand operation of bypass blade (operates to the left)
R Right-hand operation of bypass blade (operates to the right)
Continuous current6 600 amperes
9 900 amperes
Specials 0 None
Example: R1NAPNPL60 = RBD, 15 kV, 110 kV BIL, no stops on parallel blades, 90 stop on bypass blade, porcelain insulators, 2-hole NEMA pads, polemount frame, left hand
operation of bypass blade, 600 A, no specials
A B C D E F G H I J
Voltageclass(kV)
BIL(kV) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (lb) (kg) (lb) (k
15 110 12.22 310 12.50 317 20.86 530 14.03 356 8.0 203 22.6 574 11.67 296 22.49 571 11.43 290 5.50 140 91 41 54 2
27 125 15.63 397 15.90 404 24.27 617 15.03 382 9.0 229 26.0 660 15.07 383 25.82 656 13.13 333 5.50 140 99 45 55 2
38 150 15.63 397 15.90 404 24.27 617 15.03 382 10.0 254 26.0 660 15.07 383 25.82 656 13.13 333 5.50 140 103 47 57 2
Unit dimensions
Maximumvoltage (kV)
BIL(kV)
Continuouscurrent (A)
Peakwithstand curren
(kA Asym)
15 110 600/900 65
27 125 600/900 6538 150 600/900 65
Creep Strike
Porcelain Silicone Porcelain Silicone
Voltage class
(kV)BIL(kV) (in) (mm) (in) (mm) (in) (mm) (in) (mm)
15 110 17.60 441 19.53 496 7.71 196 7.79 198
27 125 22.95 583 28.30 719 8.55 217 9.26 234
38 150 23.87 606 39.52 1003 9.81 249 10.62 270
Insulator details Ratings
Porcelainweight
Silicoweig
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
6/126 Single-phase overhead distribution switches |ABB product bulletin
SID disconnect switch
Product features
Light weight alternative to double insulator disconnect switch
Reduces the need of double crossarm for mounting when
using cutout bracket
Insulators available in silicone, porcelain, and polymer concrete
Self aligning silver-to-silver contacts to ensure long life
Entire blade is silver-plated copper
Loadbreak hooks made of galvanized steel for corrosion
protection, to be used with loadbreak tool
Standard two-pole NEMA plated pad or optional two-piece
parallel groove
All testing is in accordance with IEEE 37.34
Description
The SID disconnect switch is a single insulator disconnect with
a double-bar switch blade and two, 2-hole extended NEMA pad
terminals. The SID is a lightweight, flexible alternative to the
commonly used double insulator design. In addition, the SID
disconnect incorporates the ABB quality approach to cutout
design.
Application
The SID is used as a disconnect on overhead distribution
feeders and in outdoor distribution substations. It is used to
provide a visible break point for maintenance personnel, as
a sectionalizing point, or as a loadbreak switch when used in
conjunction with a portable loadbreak tool.
Mounting
The SID can be mounted like a standard cutout, directly on apole for use as a disconnect between overhead and under-
ground lines, or as a visible disconnect for maintenance of line
equipment. This standard cutout type design allows for ease of
installation with a clear indication of its position.
The SID can be mounted in the following scenarios:
Single or double crossarm underhung
Crossarm similar to a cutout
Crossarm vertically
Riser pole application
Pole mount extended angle
10.78[273.69]
2015
'B' RADIUS
'A'
1.25[31.75]
0.63[15.88]
6.63[168.32]
1.75[44.45]
4.6[118.
Type
Voltagerating(kV)
BIL(kV)
Dimension A B radius Creep Strike
in mm in mm in mm in mm
Porcelain 15.5 110 24.6 625 13.5 342 9.1 231 6.75 170
Silicone 15.5 110 24.6 625 13.5 342 15.0 380 5.25 133
Polymer concrete 15.5 110 24.6 625 13.5 342 9.1 231 7.00 178
Porcelain 27 125 28.0 711 16.9 429 12.8 325 8.50 216
Silicone 27 125 28.0 711 16.9 429 18.9 480 7.50 190
Polymer concrete 27 125 28.0 711 16.9 429 12.8 325 8.50 216
Porcelain 38 150 28.0 711 16.9 429 17.0 432 10.75 273
Silicone 38 150 28.0 711 16.9 429 23.6 600 8.50 216
Unit dimensions
Outline drawing
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
7/12ABB product bulletin | Single-phase overhead distribution switches
Selection guide
Description Code Definition
Switch type D Type SID Switch
Max kV, BIL
1 15 kV, 110 kV BIL, 9.1" creep (279C075)
2 27 kV, 125 kV BIL, 12.8" creep (279C342)
4 27 kV, 150 kV BIL, 18" creep (279C341)
5 38 kV, 150 kV BIL, 18" creep (279C341)
6 38 kV, 150 kV BIL, 600 mm creep silicone
7 38 kV, 170 kV BIL, 26" creep porcelain (8433C39)
9 38 kV, 170 kV BIL, 30" creep porcelain (5853C96)
Blade stop
N No stop
R 90 stop
B 160 stop
Terminal connectors
A NEMA 2-hole with captured 0.5" hardware (galvanized)
C NEMA 2-hole with two-piece clamshell #2-500MCM (10013A44G01)
D NEMA 2-hole with double eyebolt terminal #2-350MCM
H NEMA 2-hole with two-piece clamshell 4/0-500MCM (10013A44G02)
T NEMA 2-hole pad standard
Brackets
B NEMA B bracket only (403A101G03)E Extended bracket (367C802G04)
U U pole mounting bracket (403A101G03 and 3905B11H02)
N No bracket
Hooks L Galvanized steel hooks
Continuous current600 600 amperes
900 900 amperes
Unused 0 Space holder for future options
Unused 0 Space holder for future options
Insulator
A Porcelain
J Silicone
Z Polymer concrete
Crossarm, extended angle
SID mounting configurations
Pole mount extended angle Standard pole mount Underhung
Example: D1RHNL600A = SID, 15 kV, 110 kV BIL, 90 stop, NEMA 2-hole pads with clamshell 4/0-500MCM, no bracket, galvanized hooks, 600 A, no special options
Maximumvoltage (kV)
BIL(kV)
Continuouscurrent (A)
Peakwithstand curren
(kA Asym)
15.5 110 600 65
27 125 600 6538 150 600 65
15.5 110 900 65
27 125 900 65
38 150 900 65
Voltageclass (kV)
BIL(kV)
Continuouscurrent (A)
PorcelainPolymerconcrete Silicone
lbs kg lbs kg lbs kg
15.5 110 600 14.7 6.7 14.1 6.4 10.9 4.9
15.5 110 900 15.6 7.1 15.0 6.8 12.0 5.427 125 600 18.4 8.3 17.6 8.0 13.1 5.9
27 125 900 19.3 8.8 18.5 8.4 14.0 6.4
38 150 600 25.2 11.4 19.9 9.0
38 150 900 26.1 11.8 20.8 9.4
Weights Ratings
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
8/128 Single-phase overhead distribution switches |ABB product bulletin
Product features
Light weight alternative to double insulator disconnect switch
Reduces the need of double crossarm for mounting when
using cutout bracket
Insulators available in silicone, porcelain, and polymer concrete
Self aligning silver-to-silver contacts to ensure long life
Entire blade is silver-plated copper
Self contained loadbreak capability to be used only with
a hookstick
Standard two-pole NEMA plated pad or optional two-piece
parallel groove
All testing is in accordance with IEEE 37.34
Description
The LSID disconnect switch is a single insulator disconnect
with self-contained loadbreak capabilities, a double-blade door,
and two 2-hole extended NEMA pad terminals. The LSID is a
lightweight, flexible alternative to the commonly used double
insulator design. In addition, the LSID disconnect incorporates
the ABB quality approach to cutout design.
Application
The LSID is used as a disconnect on overhead distribution
feeders and in outdoor distribution substations. It is also used
to provide a visible break point for maintenance personnel. The
self-contained loadbreak concept enables the utility to interrupt
load current by operating the switch with a simple hookstick.
Mounting
The LSID can be mounted like a standard cutout, directlyon a pole for use as a disconnect between overhead and
underground lines, or as a visible disconnect for maintenance
of line equipment. This standard cutout design provides a clear
indication of its position and allows for easy installation.
An optional mounting kit is available that allows for a variety of
mounting scenarios:
Single or double crossarm underhung
Crossarm similar to a cutout
Crossarm vertically
Riser pole application
LSID disconnect switch
10.78[273.70]
'B'R
adiu
s
20.39[517.98]
0.
63
[15.
88]
1.
75
[44.
45]
'A'
2015
1.25[31.75]
6.
76
[171.
70]
Type
Voltagerating(kV)
BIL(kV)
Dimension A B radius Creep Strike
in mm in mm in mm in mm
Porcelain 15.5 110 24.6 625 13.5 342 9.1 231 6.75 170
Silicone 15.5 110 24.6 625 13.5 342 15.0 380 5.25 133
Polymer concrete 15.5 110 24.6 625 13.5 342 9.1 231 7.00 178
Porcelain 15/27 125 28.0 711 16.9 429 12.8 325 8.50 216
Silicone 15/27 125 28.0 711 16.9 429 18.9 480 7.50 190
Polymer concrete 15/27 125 28.0 711 16.9 429 12.8 325 8.50 216
Porcelain 15/27 150 28.0 711 16.9 429 17.0 432 10.75 273
Silicone 15/27 150 28.0 711 16.9 429 23.6 600 8.50 216
Unit dimensions
Outline drawing
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
9/12ABB product bulletin | Single-phase overhead distribution switches
Example: B2NCBN600J = LSID, 27 kV, 125 kV BIL, no stop, NEMA 2-hole pads with clamshell 2-500MCM, NEMA B bracket, 600 A, silicone insulator
Selection guide
Description Code Definition
Switch type B Type LSID loadbreak switch
Max kV, BIL
1 15 kV, 110 kV BIL, 9.1" creep (279C075)
2 15/27 kV, 125 kV BIL, 12.8" creep (279C342)
4 15/27 kV, 150 kV BIL, 18" creep (279C341)
7 15/27 kV, 170 kV BIL, 26" creep (8433C39)
Blade stop
N No stop
R 90 stop
B 160 stop
Terminal connectors
A NEMA 2-hole with captured 0.5" hardware (galvanized)
C NEMA 2-hole with two-piece clamshell #2-500MCM (10013A44G01)
D NEMA 2-hole with double eyebolt terminal #2-350MCM
H NEMA 2-hole with two-piece clamshell 4/0-500MCM (10013A44G02)
T NEMA 2-hole pad standard
Brackets
B NEMA B bracket only (403A101G03)
E Extended bracket (367C802G04)
U U pole mounting bracket (403A101G03 and 3905B11H02)
N No bracket
Unused N Space holder for future options
Continuous current/loadbreak6 600 ampere continuous/600 amperes MAX loadbreak
9 900 ampere continuous/600 amperes MAX loadbreak
Unused N Space holder for future options
Unused N Space holder for future options
Insulators
A Porcelain
J Silicone
Z Polymer concrete
Maximumvoltage (kV)
BIL(kV)
Continuouscurrent (A)
Loadbreakcurrent (A)
Peakwithstand curren
(kA Asym)
15.5 110 600 600 65
15/27 125 600 600 6515/27 150 600 600 65
15.5 110 900 600 65
15/27 125 900 600 65
15/27 150 900 600 65
Voltageclass (kV)
BIL(kV)
Conti-nuouscurrent
(A)
PorcelainPolymerconcrete Silicone
lbs kg lbs kg lbs kg
15.5 110 600 16.7 7.6 15.8 7.2 12.8 5.8
15/27 125 600 20.4 9.3 19.6 8.9 15.1 6.8
15/27 150 600 27.2 12.3 21.9 9.9
15.5 110 900 17.6 8.0 16.7 7.6 13.7 6.2
15/27 125 900 21.3 9.7 20.5 9.3 16.0 7.3
15/27 150 900 28.1 12.7 22.8 10.3
Extended angle Standard pole mount Underhung
Weights Ratings
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
10/1210 Single-phase overhead distribution switches |ABB product bulletin
ITD inline tension disconnect switch
Product features
Lightweight silicone insulator provides extra leakage distance
and BIL ratings to ensure inline switches are not the flashover
point
Self aligning silver-to-silver contacts to ensure long life
Entire blade is silver-plated copper
Loadbreak hooks made of galvanized steel for corrosion
protection, to be used with loadbreak tool
Standard two-pole NEMA plated pad or optional two-piece
parallel groove
All testing is in accordance with IEEE 37.34
Description
The ITD inline tension disconnect is a hookstick-operated
switch used to manually switch de-energized or parallel circuits
of overhead distribution lines rated 15 through 38 kV, 150
and 200 kV BIL. The ITD is installed directly in the line and
is used to sectionalize the circuit. Switches are selected by
continuous current and voltage ratings. The ITD is rated for
600 and 900 A continuous current and 65 kA peak withstand
current (40 kA momentary).
Operation
All ITD disconnect switches include loadbreak hooks. Use the
appropriate loadbreak device to open the switch under load.
The pull-ring can be utilized for easy opening and ice breaking.
The hook portion of the contact-casting matches the blade
latch for positive closure.
Blade operationA blade stop limits the blade range of motion to the 90 and
160 postions, and a latch prevents the switch from opening
under high momentary current.
Maximumvoltage (kV)
BIL(kV)
Continuouscurrent (A)
Peakwithstand current
(kA Asym)
15 & 27 150 600/900 65
27 & 38 200 600/900 65
Creep
Silicone
Voltage class
(kV)
BIL
(kV) (in) (mm)
15 & 27 150 23.23 590
27 & 38 200 39.00 991
Insulator details Ratings
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
11/12ABB product bulletin | Single-phase overhead distribution switches
Selection guide
Description Code Definition
Switch type T Type ITD switch
Max kV, BIL3 38 kV, 200 kV BIL
5 27 kV, 150 kV BIL
Blade stop
N No stop
A 90 stop
B 160 stop
Terminal connectors
A NEMA 2-hole with captured 0.5" hardware (galvanized)
C NEMA 2-hole with two-piece clamshell #2-500MCM (10013A44G01)
D NEMA 2-hole with double eyebolt terminal (#2-350 MCM)
N NEMA 2-hole pad standard
H NEMA 2-hole with two-piece clamshell 4/0-500MCM (10013A44G02)
Insulator
A Tongue/tongue (TT), silicone
B Clevis/clevis (CC), silicone
M Tongue/clevis (TC), tongue at hinge end of switch, silicone
N Tongue/clevis (TC), clevis at hinge end of switch, silicone
Unused N Space holder for future options
Continous current6 600 amperes
9 900 amperes
Specials 0 None
Unused N Space holder for future options
Unused N Space holder for future options
Example: T5NCNN9000 = ITD, 27 kV, 150 kV BIL, no stop, two-iece clamshell #2-500MCM, tongue/clevis silicone insulator, 900 A, no specials
A B C D
Voltage class
(kV)BIL(kV) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (lb) (k
15 & 27 150 17.92 455 12.94 326 15.08 383 28.54 725 11.0 5
27 & 38 200 20.70 526 17.26 438 19.67 500 33.13 841 14.0 6
A
B
C
D
0.630 DIA CLEVIS PIN
COTTER KEY
INSULATOR SHED DESIGNWILL VARY, SHED MAX
DIAMETER WILL BE 3.75"
0.690 DIAMETER HOLE
1.75[44.45]
0.63[15.88]
1.
25
[31.
75]
ACCEPTS 1/2" BOLTS
Unit dimensions
Outline drawing
Silicone weig
8/3/2019 1VAG0002 DB_Single Phase Overhead Switches
12/12
Contact us
Note:
We reserve the right to make technical changes or modify the contents of this
document without prior notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB does not accept any responsibility whatsoever for
potential errors or possible lack of information in this document. We reserve
all rights in this document and in the subject matter and illustrations contained
therein. Any reproductionin whole or in partsis forbidden without ABBs prior
written consent.
Copyright 2010 ABB.
All rights reserved.
ABB Inc.
Medium Voltage Distribution Components
406 Banner Ave.
Greensboro, NC 27401
Phone: +1 336 275-7310
Fax: +1 336 275-1965
www.abb.com/mediumvoltage