FILE: CONDOCS.DWG SCALE: AS NOTED DWG NO. PROJ MGR. MR CHECKED BY OT DRAWN BY LL SEAL & SIGNATURE PROJ NO. 10295.00 DRAWING TITLE NEW YORK, NEW YORK 3ST FLOOR 750 THIRD AVENUE JOB TITLE SL GREEN REALTY CORPORATION NO. DATE ISSUE/REVISION BY - 11.20.15 ISSUE FOR BID OT T-000.00 NEW YORK, NEW YORK 750 THIRD AVENUE 31ST FLOOR SL GREEN REALTY CORPORATION TITLE SHEET M/E/P/S ENGINEER ARCHITECTURAL DRAWINGS M/E/P/S ENGINEERING DRAWINGS DM-001.00 DEMOLITION PLAN M-001.00 MECHANICAL LEGENDS, NOTES, ABBREVIATIONS AND DRAWING LIST E-802.00 ELECTRICAL SPECIFICATIONS SHEET #2 A-002.00 CONSTRUCTION PLAN M-101.00 31ST FLOOR MECHANICAL PLANS E-803.00 ELECTRICAL SPECIFICATIONS SHEET #3 A-003.00 POWER/TELEPHONE PLAN M-201.00 31ST FLOOR MECHANICAL PIPING PLAN EN-001.00 ENERGY ANALYSIS COMPLIANCE SHEET A-004.00 REFLECTED CEILING PLAN M-501.00 MECHANICAL DETAILS 1 OF 3 EN-002.00 ENERGY CODE SUPPORTIVE DOCUMENT A-005.00 FINISH PLAN M-502.00 MECHANICAL DETAILS 2 OF 3 FA-101.00 31ST FLOOR FIRE ALARM PLAN A-006.00 FURNITURE PLAN M-503.00 MECHANICAL DETAILS 3 OF 3 FA-601.00 FIRE ALARM NOTES, SYMBOLS LIST AND RISER DIAGRAM A-007.00 PARTITION TYPES M-801.00 MECHANICAL SPECIFICATIONS 1 OF 3 P-001.00 PLUMBING NOTES, DETAILS AND DRAWING LIST A-008.00 DOOR & HARDWARE SCHEDULE M-802.00 MECHANICAL SPECIFICATIONS 2 OF 3 P-101.00 31ST FLOOR PLUMBING PLAN AND RISER DIAGRAMS A-009.00 PANTRY DETAILS M-803.00 MECHANICAL SPECIFICATIONS 3 OF 3 P-801.00 PLUMBING SPECIFICATIONS A-010.00 CORE BATHROOM ELEVATIONS M-901.00 31ST FLOOR MECHANICAL DEMOLITION PLAN SP-001.00 SPRINKLER NOTES, LEGENDS, DRAWING LIST AND PLOT PLAN A-011.00 MILLWORK ELEVATIONS E-001.00 ELECTRICAL NOTES AND DRAWING LIST SP-101.00 31ST FLOOR SPRINKLER PLAN E-002.00 ELECTRICAL SYMBOLS LIST SP-501.00 SPRINKLER DETAILS E-101.00 31ST FLOOR ELECTRICAL LIGHTING PLAN SP-601.00 SPRINKLER RISER DIAGRAM E-201.00 31ST FLOOR ELECTRICAL POWER PLAN SP-801.00 SPRINKLER SPECIFICATIONS E-301.00 31ST FLOOR MECHANICAL POWER PLAN SP-901.00 31ST FLOOR SPRINKLER DEMOLITION PLAN AND TEMP LOOP E-501.00 ELECTRICAL DETAILS SHEET #1 E-502.00 ELECTRICAL DETAILS SHEET #2 E-503.00 ELECTRICAL DETAILS SHEET #3 E-504.00 ELECTRICAL DETAILS SHEET #4 E-601.00 ELECTRICAL RISER DIAGRAM E-701.00 PANEL SCHEDULES E-801.00 ELECTRICAL SPECIFICATIONS SHEET #1 AARP NEW YORK STATE OFFICE MG ENGINEERING, P.C. 116 W. 32ND STREET, 12TH FLOOR NEW YORK, N.Y. 10001 P. 212.643.9055 F. 212.643.0503 CONTACT: BRIAN BATEMAN

2 - Bid Set Dated 11.20.15

  • Upload
    mjasd

  • View
    22

  • Download
    0

Embed Size (px)

DESCRIPTION

BIDDING DOCUMENT

Citation preview

  • FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    T-000.00

    NEW YORK, NEW YORK750 THIRD AVENUE

    31ST FLOORSL GREEN REALTY CORPORATION

    TITLE SHEET

    M/E/P/S ENGINEER

    ARCHITECTURAL DRAWINGS M/E/P/S ENGINEERING DRAWINGSDM-001.00 DEMOLITION PLAN M-001.00 MECHANICAL LEGENDS, NOTES, ABBREVIATIONS AND DRAWING LIST E-802.00 ELECTRICAL SPECIFICATIONS SHEET #2

    A-002.00 CONSTRUCTION PLAN M-101.00 31ST FLOOR MECHANICAL PLANS E-803.00 ELECTRICAL SPECIFICATIONS SHEET #3

    A-003.00 POWER/TELEPHONE PLAN M-201.00 31ST FLOOR MECHANICAL PIPING PLAN EN-001.00 ENERGY ANALYSIS COMPLIANCE SHEET

    A-004.00 REFLECTED CEILING PLAN M-501.00 MECHANICAL DETAILS 1 OF 3 EN-002.00 ENERGY CODE SUPPORTIVE DOCUMENT

    A-005.00 FINISH PLAN M-502.00 MECHANICAL DETAILS 2 OF 3 FA-101.00 31ST FLOOR FIRE ALARM PLAN

    A-006.00 FURNITURE PLAN M-503.00 MECHANICAL DETAILS 3 OF 3 FA-601.00 FIRE ALARM NOTES, SYMBOLS LIST AND RISER DIAGRAM

    A-007.00 PARTITION TYPES M-801.00 MECHANICAL SPECIFICATIONS 1 OF 3 P-001.00 PLUMBING NOTES, DETAILS AND DRAWING LIST

    A-008.00 DOOR & HARDWARE SCHEDULE M-802.00 MECHANICAL SPECIFICATIONS 2 OF 3 P-101.00 31ST FLOOR PLUMBING PLAN AND RISER DIAGRAMS

    A-009.00 PANTRY DETAILS M-803.00 MECHANICAL SPECIFICATIONS 3 OF 3 P-801.00 PLUMBING SPECIFICATIONS

    A-010.00 CORE BATHROOM ELEVATIONS M-901.00 31ST FLOOR MECHANICAL DEMOLITION PLAN SP-001.00 SPRINKLER NOTES, LEGENDS, DRAWING LIST AND PLOT PLAN

    A-011.00 MILLWORK ELEVATIONS E-001.00 ELECTRICAL NOTES AND DRAWING LIST SP-101.00 31ST FLOOR SPRINKLER PLAN

    E-002.00 ELECTRICAL SYMBOLS LIST SP-501.00 SPRINKLER DETAILS

    E-101.00 31ST FLOOR ELECTRICAL LIGHTING PLAN SP-601.00 SPRINKLER RISER DIAGRAM

    E-201.00 31ST FLOOR ELECTRICAL POWER PLAN SP-801.00 SPRINKLER SPECIFICATIONS

    E-301.00 31ST FLOOR MECHANICAL POWER PLAN SP-901.00 31ST FLOOR SPRINKLER DEMOLITION PLAN AND TEMP LOOP

    E-501.00 ELECTRICAL DETAILS SHEET #1

    E-502.00 ELECTRICAL DETAILS SHEET #2

    E-503.00 ELECTRICAL DETAILS SHEET #3

    E-504.00 ELECTRICAL DETAILS SHEET #4

    E-601.00 ELECTRICAL RISER DIAGRAM

    E-701.00 PANEL SCHEDULES

    E-801.00 ELECTRICAL SPECIFICATIONS SHEET #1

    AARP NEW YORK STATE OFFICE

    MG ENGINEERING, P.C.116 W. 32ND STREET, 12TH FLOORNEW YORK, N.Y. 10001P. 212.643.9055F. 212.643.0503CONTACT: BRIAN BATEMAN

  • FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    GENERAL REQUIREMENTSPART 1 GENERAL

    1.01 GENERAL

    A. EXAMINE PREMISES CAREFULLY AND REPORT IN WRITING ANY DISCREPANCIES TOTHE ARCHITECT BEFORE PROCEEDING WITH ANY WORK.

    B. THE GENERAL CONDITIONS OF THE CONTRACT, THE AMERICAN INSTITUTE OF ARCHITECTS STANDARD DOCUMENT #A201 "GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION," APRIL 1987 EDITION OR MOST CURRENT PUBLISHED EDITION, 14 ARTICLES, 24 PAGES AND THE FOLLOWING SUPPLEMENTARYREQUIREMENTS APPLY TO ALL SECTIONS OF THIS SPECIFICATION.

    C. WHERE "GENERAL AND SUPPLEMENTARY CONDITIONS" SPECIFIED IN THESE DOCUMENTS MODIFY THE AIA GENERAL CONDITIONS, THEY SHALL TAKE PRECEDENCE.

    D. WHERE "GENERAL AND SUPPLEMENTARY CONDITIONS" CLAUSES ARE REPEATED, ITSHALL BE UNDERSTOOD AS CALLING SPECIAL ATTENTION TO THEM OR AS A FURTHER QUALIFICATION, AND SHALL NOT BE ASSUMED AS OMITTING ANY FURTHERCLAUSE OF THE GENERAL CONDITIONS.

    E. MAINTAIN ADEQUATE PROTECTION OF THE WORK FROM DAMAGE AND PROTECTTHE OWNER'S PROPERTY AND THE PUBLIC FROM INJURY OR LOSS ARISING IN CONNECTION WITH THIS WORK. MAKE GOOD ANY SUCH DAMAGE, INJURY ORLOSS, AND ACCEPT EXCLUSIVE LIABILITY AND HOLD HARMLESS THE OWNER ANDARCHITECT AGAINST INJURIES OR CLAIMS THEREFORE OF ALL PERSONS AND ANYALLEGED DAMAGE TO PROPERTY IN CONNECTION WITH THE WORK. ERECT ANDMAINTAIN AT ALL TIMES, AS REQUIRED BY THE CONDITIONS AND PROGRESS OF THEWORK, ALL NECESSARY SAFEGUARDS FOR THE PROTECTION OF THE WORKMENAND THE PUBLIC.

    F. ALL WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE WITH THE LATEST RULES AND REGULATIONS OF ALL MUNICIPAL CODES AND STATE LAWS OR REGULATIONS. NOTHING IN THESE PLANS OR SPECIFICATIONS IS TO BE CONSTRUEDTO PERMIT WORK NOT CONFORMING TO THESE CODES. IN CASES WHERE CODEREQUIREMENTS DIFFER, THE MORE STRINGENT CODE SHALL TAKE PRECEDENCE.

    G. INDEMNITYPROVISION MUST BE MADE TO INSURE THE "HOLD HARMLESS AGREEMENT" WHICHREADS AS FOLLOWS:

    1. THE CONTRACTOR HEREBY AGREES TO INDEMNIFY AND SAVE HARMLESS THE OWNER, BUILDING MANAGEMENT AND ARCHITECT FROM AND AGAINST ALL LIABILITY CLAIMS AND DEMANDS ON ACCOUNT OF INJURY TO PERSONS INCLUDING DEATH RESULTING THEREFROM AND DAMAGE TO PROPERTY ARISING OUT OF THE PERFORMANCE OF THESE CONTRACT DOCUMENTS BY THECONTRACTOR'S PROPERTY. THE CONTRACTOR SHALL, AT HIS OR ITS OWN EXPENSE, DEFEND ANY AND ALL ACTIONS AT LAW BROUGHT AGAINST THE OWNERAND THE SAME OWNER'S REPRESENTATIVE ABOVE AND SHALL PAY ALL ATTORNEY'SFEES AND ALL EXPENSES, AND PROMPTLY DISCHARGE ANY JUDGMENTS ARISINGTHEREFROM. THESE CONDITIONS SHALL ALSO APPLY TO ANY SUBCONTRACTEDOPERATIONS.

    2. THE CONTRACTOR SHALL SECURE AND PROTECT THE WORK AND SHALL BEAR ANDBE LIABLE FOR, AND SHALL REPAIR AND REPLACE ALL LOSS AND DAMAGE OF ANYKIND WHICH MAY HAPPEN TO THE WORK AT ANY TIME PRIOR TO THE FINAL COMPLETION AND ACCEPTANCE THEREOF FROM ANY CAUSE WHATSOEVER, ANDTHE OWNER AND ARCHITECT WILL NOT, IN ANY MANNER, BE ANSWERABLE OR RESPONSIBLE FOR ANY LOSS OR DAMAGE THAT SHALL HAPPEN TO THE WORK ORANY PART THEREOF, NOR FOR ANY MATERIALS, EQUIPMENT, TOOLS, PLANT, FACILITIES OR OTHER THINGS THAT MAY BE EMPLOYED THEREIN OR PLACED UPONTHE PREMISES BY THE CONTRACTOR, THE LATTER BEING SOLELY RESPONSIBLE THEREFORE UNTIL THE WORK HAS BEEN FULLY ACCEPTED BY THE OWNER.

    3. THE CONTRACTOR HEREBY AGREES, TO THE EXTENT PERMITTED BY LAW, TO ASSUMETHE ENTIRE RESPONSIBILITY AND LIABILITY FOR AND DEFENSE OF AND TO PAY ANDINDEMNIFY THE OWNER AND THE ARCHITECT (COLLECTIVELY THE "INDEMNITIES")AGAINST ANY LOSS, EXPENSE OR LIABILITY AND WILL HOLD EACH OF THEM HARMLESS FROM ANY PAY, ANY LOSS, DAMAGE, COST OR EXPENSE (INCLUDINGWITHOUT LIMITATION, JUDGMENTS, ATTORNEY'S FEES, COURT COSTS AND THE COSTOF APPELLATE PROCEEDINGS), WHICH THE INDEMNITIES (COLLECTIVELY OR INDIVIDUALLY) INCUR BECAUSE OF INJURY TO OR DEATH OF ANY PERSON OR ONACCOUNT OF DAMAGE TO PROPERTY, INCLUDING LOSS OF USE THEREOF, OR ANYOTHER CLAIM ARISING OUT OF, IN CONNECTION WITH OR AS A CONSEQUENCEOF THE PERFORMANCE OF THE WORK, AND/OR ANY ACT OR OMISSION OF THECONTRACTOR OR ANY OF ITS SUBCONTRACTORS, OFFICERS, DIRECTORS, EMPLOYEES, AGENTS OR ANYONE DIRECTLY OR INDIRECTLY EMPLOYED BY THECONTRACTOR OR ANYONE WHOSE ACTS THE CONTRACTOR MAY BE LIABLE AS ITRELATES TO THE SCOPE OF THIS CONTRACT. HOWEVER, NOTHING HEREIN CONTAINED SHALL REQUIRE THE CONTRACTOR TO PROVIDE INDEMNIFICATIONAGAINST THE PROPORTION OF ANY LIABILITY FOR CLAIMS WHICH ARE PROVEN TOHAVE ARISEN FROM THE NEGLIGENCE OF THE PARTY ASKED TO BE DEFENDED, INDEMNIFIED OR HELD HARMLESS. CONTRACTOR WILL PURCHASE AND MAINTAINSUCH INSURANCE AS WILL PROTECT IT FROM ANY COSTS AND EXPENSES RELATINGTO THE FOREGOING, INCLUDING, WITHOUT LIMITATION, CONTRACTUAL COVERAGE COVERING THE FOREGOING INDEMNITY, AND SHALL PROVIDE THEOWNER WITH CERTIFICATES EVIDENCING SAME IN THE FORM ANNEXED HERETO.

    H. INSURANCE TO BE PROVIDED BY THE CONTRACTOR

    1. THE CONTRACTOR SHALL, THROUGH AGENTS AND IN AMOUNTS AND BY COMPANIES TO BE APPROVED BY THE OWNER, OBTAIN, MAINTAIN IN FORCE DURING THE PERIOD COVERED BY THE CONTRACT AND PAY FOR SUCH INSURANCE AS REQUIRED HEREIN. IF THE CONTRACTOR SHALL FAIL TO DELIVERCERTIFICATES FOR ITS INSURANCE OR THE INSURANCE OF ITS SUBCONTRACTORSTO THE OWNER WITHIN FORTY-EIGHT (48) HOURS AFTER DEMAND, AND IN ANY EVENT, PRIOR TO COMMENCEMENT OF THE WORK ON THE PROJECT, THE OWNERMAY OBTAIN SUCH INSURANCE FOR THE CONTRACTOR AND PAY PREMIUMS THEREON, AND THE CONTRACTOR SHALL REPAY THE OWNER, ON DEMAND, ANYSUM OR SUMS PAID THEREFORE, TOGETHER WITH INTEREST THEREON, OR THE OWNER,MAY DEDUCT SUCH SUM OR SUMS, TOGETHER WITH INTEREST THEREIN, FROM ANY MONEY DUE OR TO BECOME DUE TO THE CONTRACTOR UNDER THISCONTRACT. AS PROVIDED BELOW, EVERY POLICY OF INSURANCE REQUIRED HEREUNDER SHALL NAME THE INDEMNITIES AS ADDITIONAL INSURED AND SHALLPROVIDE FOR GIVING THE OWNER AND THE OTHER INDEMNITIES IF SO REQUESTEDIN WRITING THIRTY (30) DAYS' PRIOR WRITTEN NOTICE OF THE CANCELLATION THEREOF.

    2. ANY POLICY OF INSURANCE COVERING THE CONTRACTOR'S OWN TOOLS, PLANTAND FACILITIES AGAINST LOSS BY PHYSICAL DAMAGE SHALL INCLUDE AN ENDORSEMENT PROVIDING THAT THE UNDERWRITERS WAIVE THEIR RIGHTS OF SUBROGATION AGAINST THE OWNER.

    3. THE CONTRACTOR SHALL NOT COMMENCE WORK UNDER THIS CONTRACT UNTIL ITHAS OBTAINED ALL OF THE INSURANCE REFERRED TO HEREIN AND THE CONTRACTOR AND/OR SUBCONTRACTOR SHALL BE REQUIRED TO MAINTAIN THEFOLLOWING INSURANCE IN AMOUNTS NOT LESS THAN THOSE SPECIFIED BELOW:

    a. WORKERS COMPENSATION IN ACCORDANCE WITH THE LAWS OF THE STATE WITHJURISDICTION.

    b. EMPLOYER'S LIABILITY INSURANCE IN AN AMOUNT NOT LESS THAN $100,000.

    c. COMPREHENSIVE GENERAL LIABILITY/UMBRELLA LIABILITY FOR:

    (1) BODILY INJURY LIABILITY INSURANCE

    (2) PROPERTY DAMAGE LIABILITY WITH LIMITS IN THE AMOUNTS PER BUILDING MANAGEMENT OR AT AMOUNTS REQUESTED BY THE CLIENT FOR SINGLE LIMIT EACH OCCURRENCE, INCLUDING, BUT NOT LIMITED TO, COMPREHENSIVE FORMPREMISES - OPERATIONS, EXPLOSION AND COLLAPSE HAZARD, PRODUCTS/COMPLETED OPERATIONS HAZARD (2) YEARS' EXTENSION BEYOND COMPLETION OF PROJECT), CONTRACTUAL COVERAGE (INCLUDING COVERAGEFOR THE INDEMNITY CLAUSES PROVIDED UNDER THIS CONTRACT), BROAD FORMPROPERTY DAMAGE, INDEPENDENT CONTRACTORS, PERSONAL INJURY (EMPLOYEES EXCLUSION DELETED) AND 'X,' 'C' AND 'U' EXCLUSIONS DELETED.

    (3) COMPREHENSIVE AUTOMOBILE LIABILITY COMPREHENSIVE, OWNED, HIRED, NON-OWNED WITH LIMITS $500,000 COMBINED SINGLE LIMIT EACH OCCURRENCE.

    (4) THE CONTRACTOR SHALL VERIFY THAT THESE REQUIREMENTS ARE ACCEPTABLE TOTHE OWNER. IF NOT, THEY SHALL OBTAIN INSURANCE COVERAGE IN ACCORDANCE WITH THEIR REQUIREMENTS.

    4. THE ABOVE INSURANCE SHALL, WITHOUT LIABILITY ON THE PART OF THE OWNER

    FOR PREMIUMS THEREOF, INCLUDE THE FOLLOWING:

    a. ENDORSEMENT AS ADDITIONAL INSURERS OF:

    (1) OWNER, ARCHITECT AND THEIR PARTNERS, DIRECTORS, OFFICERS, EMPLOYEES,AGENTS AND REPRESENTATIVES; AND

    (2) ALL OTHER INDEMNITIES NAMED IN THE CONTRACT.

    b. THIRTY (30) DAY PRIOR NOTICE OF CANCELLATION TO EACH NAME INSURED; AND

    c. WAIVER OF SUBROGATION

    5. THE ABOVE POLICIES SHALL BE ENDORSED TO CONTAIN THE FOLLOWING WORDING VERBATIM:

    "OWNER IS INTERESTED IN THE MAINTENANCE OF THIS INSURANCE AND IT IS AGREED THAT THIS INSURANCE WILL NOT BE CANCELED, MATERIALLY CHANGEDOR NOT RENEWED WITHOUT AT LEAST THIRTY (30) DAYS' ADVANCE WRITTEN NOTICE TO THE OWNER AND THE OTHER ADDITIONAL INSURERS AS SO REQUESTED IN WRITING. THE CONTRACTOR HEREBY AGREES, TO THE EXTENT PERMITTED BY LAW, TO ASSUME THE ENTIRE RESPONSIBILITY AND LIABILITY FOR ANDDEFENSE OF AND TO PAY AND INDEMNIFY THE OWNER FOR THE PROJECT AND THEARCHITECT (COLLECTIVELY THE "INDEMNITIES") AGAINST ANY LOSS, EXPENSE ORLIABILITY AND WILL HOLD EACH OF THEM HARMLESS FROM ANY PAY, ANY LOSS,JUDGMENTS, ATTORNEY'S FEES, COURT COSTS AND THE COST OF APPELLATE PROCEEDINGS), WHICH THE INDEMNITIES (COLLECTIVELY OR INDIVIDUALLY) INCURBECAUSE OF INJURY TO OR DEATH OF ANY PERSON OR ON ACCOUNT OF DAMAGE TO PROPERTY, INCLUDING LOSS OF USE THEREOF, OR ANY OTHER CLAIMARISING OUT OF, IN CONNECTION WITH OR AS A CONSEQUENCE OF THE PERFORMANCE OF THE WORK, AND/OR ANY ACT OR OMISSION OF THE CONTRACTOR OR ANY OF ITS SUBCONTRACTORS, OFFICERS, DIRECTORS, EMPLOYEES, AGENTS OR ANYONE DIRECTLY OR INDIRECTLY EMPLOYED BY THECONTRACTOR OR ANYONE WHOSE ACTS THE CONTRACTOR MAY BE LIABLE AS ITRELATES TO THE SCOPE OF THIS CONTRACT. HOWEVER, NOTHING HEREIN CONTAINED SHALL REQUIRE THE CONTRACTOR TO PROVIDE INDEMNIFICATIONAGAINST THE PROPORTION OF ANY LIABILITY FOR CLAIMS WHICH ARE PROVEN TOHAVE ARISEN FROM THE NEGLIGENCE OF THE PARTY ASKED TO BE DEFENDED, INDEMNIFIED OR HELD HARMLESS. CONTRACTOR WILL PURCHASE AND MAINTAINSUCH INSURANCE AS WILL PROTECT IT FROM ANY COSTS AND EXPENSES RELATINGTO THE FOREGOING, INCLUDING, WITHOUT LIMITATION, CONTRACTUAL COVERAGE COVERING THE FOREGOING INDEMNITY, AND SHALL PROVIDE THEOWNER WITH CERTIFICATES EVIDENCING SAME."

    1.02 SUMMARY OF WORK

    A. THE CONSTRUCTION SCHEDULE AND OPERATIONS SHALL BE SUBJECT TO APPROVAL OF THE OWNER AND THE BUILDING MANAGEMENT.

    B. CONTRACTOR'S USE OF PREMISES1. CONTRACTOR SHALL LIMIT HIS USE OF THE PREMISES FOR WORK AND FOR

    STORAGE TO THE AREA DESIGNATED BY BUILDING MANAGEMENT.

    2. EACH CONTRACTOR ASSUMES RESPONSIBILITY FOR THE PROTECTION AND SAFEKEEPING OF HIS MATERIALS STORED AT THE SITE.

    3. THE CONTRACTOR IS ADVISED THAT LIMITED STORAGE SPACE IS AVAILABLE IN THESPACE TO BE RENOVATED.

    C. WORK RELATED REQUIREMENTS1. MOVEMENT OF WORKMEN AND MATERIALS INTO THE BUILDING WILL BE ALONG

    ROUTES AND AT TIMES AS DIRECTED AND RESTRICTED BY THE BUILDING MANAGEMENT.

    2. WORK IN THE BUILDING WILL BE PERMITTED DURING THE HOURS AND DAYS ESTABLISHED BY THE BUILDING MANAGEMENT AND OTHER ALTERNATE HOURS ASARRANGED WITH AND APPROVED BY THE BUILDING MANAGEMENT.

    3. THE CONTRACTOR SHALL SCHEDULE DELIVERY OF MATERIALS AND REMOVALS OFDEBRIS WITH THE BUILDING MANAGEMENT. CONTRACTOR SHALL GIVE ADEQUATE NOTICE OF REQUIREMENTS.

    4. THE CONTRACTOR SHALL NOT ERECT SIGNS.

    5. TEMPORARY FIELD OFFICE SPACE IN THE CONSTRUCTION AREA SHALL BE PROVIDED BY THE CONTRACTOR. CONTRACTOR SHALL PROVIDE HIS OWN FURNITURE. THE CONTRACTOR SHALL PROVIDE A TELEPHONE FOR COMMUNICATIONS AND SUBCONTRACTORS' USE.

    6. THE CONTRACTOR SHALL ARRANGE WITH THE BUILDING MANAGEMENT FOR HISOWN UTILITY SERVICES INCLUDING ELECTRICAL POWER, WATER AND LIGHTING.THE COST OF HOOK_UP AND DISTRIBUTION SHALL ALSO BE PAID FOR BY THE CONTRACTOR. SERVICES NOT AVAILABLE FROM THE BUILDING SHALL BE PROVIDED BY THE CONTRACTOR AT HIS OWN EXPENSE.

    7. THE CONTRACTOR AND HIS PERSONNEL MAY USE EXISTING TOILET FACILITIES FORHIS EMPLOYEES. HOWEVER, THE CONTRACTOR IS RESPONSIBLE FOR PROTECTINGTHE EXISTING TOILET FACILITY AND RESTORING IT TO ITS ORIGINAL CONDITION UPON COMPLETION OF THE JOB.

    8. WHERE DISAGREEMENTS OCCUR BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, OR WITHIN EITHER DOCUMENT ITSELF OR BETWEEN THE SPECIFICATIONS AND THE BUILDING RULES AND STANDARDS, THE ITEM OR ARRANGEMENT OF BETTER QUALITY, GREATER QUANTITY OR HIGHER COST SHALLBE INCLUDED IN THE CONTRACT.

    9. CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS ANDCONDITIONS ON THE JOB AND THE ARCHITECT'S OFFICE MUST BE NOTIFIED OF ANYVARIATIONS FROM THE DIMENSIONS AND CONDITIONS SHOWN BY THESE DRAWINGS.

    10. ALL CONSTRUCTION, DIMENSIONS AND DETAILS SHALL CONCUR WITH AND BE DETERMINED FROM THESE DRAWINGS ONLY.

    11. ALL MATERIALS, ASSEMBLIES, FORMS AND METHODS OF CONSTRUCTIONS ANDSERVICE EQUIPMENT TO BE INCORPORATED IN THE WORK SHALL BE IN STRICT ACCORDANCE WITH THE LATEST EDITION OF THE ASTM SPECIFICATIONS APPLICABLE, AND TO CONFORM TO THE STANDARDS AND RECOMMENDATIONSOF THE VARIOUS TRADE INSTITUTES (ACI, AIBC, ETC.), WHERE APPLICABLE. ALL MATERIALS INCORPORATED INTO THE WORK SHALL BE NEW AND SHALL COMPLYWITH THE LOCAL CODE REQUIREMENTS.

    12. CONTRACTORS SHALL BE RESPONSIBLE FOR ADEQUATELY BRACING AND PROTECTING ALL WORK DURING CONSTRUCTION AGAINST DAMAGE, BREAKAGES,COLLAPSE, DISTORTIONS AND OFF-ALIGNMENT ACCORDING TO APPLICABLE CODES, STANDARDS AND GOOD PRACTICE.

    13. CONSTRUCTION SHALL COMPLY WITH ALL FEDERAL, STATE AND LOCAL CODES,ORDINANCES, RULES AND REGULATIONS PERTAINING TO LABOR AND MATERIALS.

    14. ALL NOTES HEREIN MENTIONED WITH THOSE OF THE VARIOUS DRAWINGS SHALLAPPLY TO ALL DRAWINGS AND FORM PART OF THE CONTRACT.

    15. EACH CONTRACTOR WILL BE HELD STRICTLY RESPONSIBLE FOR HIS WORK. ANYDISCREPANCIES IN THE PLANS OR DETAILS SHALL BE CALLED TO THE ATTENTION OFTHE ARCHITECT.

    16. ALL MATERIALS, ASSEMBLIES, FORMS AND METHODS OF CONSTRUCTION AND SERVICE EQUIPMENT SHALL MEET THE FOLLOWING REQUIREMENTS:

    a. IT SHALL HAVE BEEN ACCEPTED PRIOR TO THE EFFECTIVE DATE OF THE CODE.

    b. IT SHALL HAVE BEEN ACCEPTED FOR USE UNDER THE PRESCRIBED CODE TEST METHODS BY THE COMMISSIONER, OR

    c. IT SHALL HAVE BEEN APPROVED BY THE BOARD OF STANDARDS AND APPEALS.

    17. ALL MATERIALS OR ASSEMBLIES REQUIRED TO HAVE A FIRE RESISTANCE RATINGSHALL COMPLY WITH LOCAL CODES AND REQUIREMENTS.

    18. ALL EXITS SHALL BE KEPT READILY ACCESSIBLE AND UNOBSTRUCTED AT ALL TIMES.

    19. FINISH FLOORING IN ALL EXITS SHALL BE OF NON-COMBUSTIBLE MATERIALS.

    20. THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 2 FOOT-CANDLES AT THE FLOOR LEVEL IN EXITS, AT EXIT DISCHARGES, AND IN PUBLICCORRIDORS AND SHALL NOT BE LESS THAN 1 FOOT-CANDLE AT THE FLOOR LEVELIN EXIT ACCESS COMPONENTS OTHER THAN PUBLIC CORRIDORS..

    21. EXIT LIGHTING SHALL BE ON CIRCUITS THAT ARE SEPARATE FROM ANY OTHER CIRCUITS, TAKEN OFF AHEAD OF THE MAIN SWITCH.

    22. WHERE REQUIRED, LOCATION OF EVERY EXIT SHALL BE CLEARLY INDICATED BY EXITSIGNS, PLACED, IF REQUIRED, AT AN ANGLE WITH THE EXIT OPENING. INSTALL DIRECTIONAL SIGNS TO SERVE AS GUIDE FROM ALL PORTIONS OF THE CORRIDOROR FLOOR, SIGNS SHALL BE ON SEPARATE CIRCUITS, TAKEN OFF AHEAD OF THEMAIN SWITCH.

    23. EXIT SIGNS SHALL BE INTERNALLY LIGHTED, HAVING AN INITIAL BRIGHTNESS OF THELETTERS OF AT LEAST 25' LAMBERT. LETTERS SHALL BE BLOCK LETTERING, AT LEAST 8"HIGH, WITH 9/16" STROKES.

    24. CORRIDORS AND EXIT PASSAGEWAYS SHALL HAVE A MINIMUM CLEAR HEIGHT OF7'-6" FOR AT LEAST 75% OF THE FLOOR AREA WITH NO POINT LESS THAN 7'-0" IN HEIGHT. PROJECTION BELOW THE CEILING SHALL NOT OBSTRUCT FULL VIEW OF EXITSIGNS.

    25. CONDUITS IN FIRE-RATED PARTITIONS WILL NOT EXCEED 3/4" DIAMETER. OUTLETS INPARTITIONS SHALL BE BACKED UP WITH APPROVED MATERIALS.

    26. NO CONDUITS, PIPES, MEDICINE CABINETS, ETC. SHALL ENCROACH UPON FIRE-RATED PARTITIONS ENCLOSING PUBLIC CORRIDORS, STAIRS, ELEVATOR SHAFTS OR VENT SHAFTS.

    27. EXIT DOORS SHALL BE READILY OPERABLE AT ALL TIMES FROM THE SIDE FROM WHICH EGRESS IS TO BE MADE. DOORS OPENING INTO INTERIOR ENCLOSED STAIRSHALL NOT BE LOCKED FROM EITHER SIDE EXCEPT THAT DOORS MAY BE LOCKEDTO PREVENT ACCESS TO THE STAIRS FROM THE OUTDOORS AT THE STREET LEVEL.

    28. PIPE SPACE AND WALL FURRINGS SHALL CONSIST OF METAL CHANNELS AND 5/8"GYPSUM WALLBOARD, EXCEPT AS OTHERWISE SHOWN.

    29. ALL COMBUSTIBLE FLOORING TO HAVE FLAME SPREAD RATING IN ACCORDANCEWITH BOCA '93.

    30. THE BATHROOM SIDE OF PARTITIONS SHALL BE 5/8" WATER RESISTANT GYPSUM WALLBOARD OR BACKER BOARD, IF ROOM IS TO RECEIVE TILE OR STONE.

    31. VENTILATION SHAFT WALLS SHALL BE AS FOLLOWS: ONE LAYER OF 5/8" FIRE CODEGYPSUM WALL BOARD EACH SIDE OVER 1" GYPSUM COREBOARD; TOTAL WIDTHTO BE 2-1/4". INSTALLATION AS RECOMMENDED BY MANUFACTURER.

    32. ALL DUCT SHAFTS OFFSETS SHALL BE ENCASED WITH 2-HOUR FIRE RATED MATERIAL.

    33. ALL PERMITS ISSUED BY THE NYC DEPARTMENT OF BUILDINGS SHALL BE POSTED IN ACONSPICUOUS PLACE OPEN FOR PUBLIC INSPECTION FOR THE ENTIRE TIME OF THECONSTRUCTION AND THE USE AND OPERATION OF THE EQUIPMENT OR UNTIL THEEXPIRATION OF THE PERMIT.

    34. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. DRAWINGS ARE NOT TO BE SCALED. ALL WORK SHALL BELAID OUT BY DIMENSIONS. LAYOUT TO BE APPROVED BY ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.

    35. FURNISH AND INSTALL ADEQUATE TEMPORARY LIGHTING THROUGHOUT THE ENTIRESPACE AS WELL AS ANY ANCILLARY FACILITIES AFFECTED OR SERVED BY THE SPACE.

    36. DEFINITIONS

    a. INDICATED: SHOWN ON DRAWINGS BY NOTES, GRAPHICS OR SCHEDULES, ORWRITTEN INTO OTHER PORTIONS OF CONTRACT DOCUMENTS. TERMS SUCH AS "SHOWN," "NOTED," "SCHEDULED" AND "SPECIFIED" HAVE SAME MEANING AS "INDICATED," AND ARE USED TO ASSIST THE READER IN LOCATING PARTICULAR INFORMATION.

    b. DIRECTED, REQUESTED, APPROVED, ACCEPTED, ETC.: THESE TERMS IMPLY "BY THEARCHITECT" UNLESS OTHERWISE INDICATED.

    c. REVIEWED BY ARCHITECT: IN NO CASE RELEASES CONTRACTOR FROM RESPONSIBILITY TO FULFILL REQUIREMENTS OF CONTRACT DOCUMENTS.

    d. PROJECT SITE: SPACE AVAILABLE TO CONTRACTOR AT LOCATION OF PROJECT,EITHER EXCLUSIVELY OR TO BE SHARED WITH SEPARATE CONTRACTORS, FOR PERFORMANCE OF WORK.

    e. FURNISH: SUPPLY AND DELIVER TO PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY INSTALLATION AND SIMILAR SUBSEQUENT REQUIREMENTS.

    f. INSTALL: OPERATIONS AT PROJECT SITE, INCLUDING UNLOADING, UNPACKING,ASSEMBLY, ERECTION, PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING, CURING, PROTECTING, CLEANING AND SIMILAR OPERATIONS.

    g. PROVIDE: FURNISH AND INSTALL, COMPLETE AND READY FOR INTENDED USE.

    h. INSTALLER: ENTITY (FIRM OR PERSON) ENGAGED TO INSTALL WORK, BY CONTRACTOR, SUBCONTRACTOR OR SUB-SUBCONTRACTOR. INSTALLERS ARE REQUIRED TO BE SKILLED EXPERTS IN WORK THEY ARE ENGAGED TO INSTALL.

    i. OVERLAPPING/CONFLICTING REQUIREMENTS: MOST STRINGENT (GENERALLY MOST COSTLY) APPLIES AND WILL BE ENFORCED, UNLESS MORE DETAILED LANGUAGE WRITTEN DIRECTLY INTO CONTRACT DOCUMENTS CLEARLY INDICATES THAT A LESS STRINGENT REQUIREMENT IS ACCEPTABLE. REFER UNCERTAINTIES TO ARCHITECT FOR DECISION BEFORE PROCEEDING.

    j. ABBREVIATIONS, PLURAL WORDS: ABBREVIATIONS, WHERE NOT DEFINED IN CONTRACT DOCUMENTS, WILL BE INTERPRETED TO MEAN THE NORMAL CONSTRUCTION INDUSTRY TERMINOLOGY, DETERMINED BY RECOGNIZED GRAMMATICAL RULES, BY THE ARCHITECT. PLURAL WORDS WILL BE INTERPRETEDAS SINGULAR AND SINGULAR WORDS WILL BE INTERPRETED AS PLURAL WHERE APPLICABLE FOR CONTEXT OF CONTRACT DOCUMENTS.

    k. CONTRACT DOCUMENTS: REQUIREMENTS OF THE WORK ARE CONTAINED IN THECONTRACT DOCUMENTS AND INCLUDE CROSS-REFERENCE THEREIN TO PUBLISHINFORMATION, WHICH IS NOT NECESSARILY BOUND THEREWITH.

    1.03 PROJECT COORDINATION

    A. THE CONTRACTOR SHALL:1. COORDINATE WORK OF HIS OWN EMPLOYEES.

    2. EXPEDITE HIS WORK TO ENSURE COMPLIANCE WITH SCHEDULES.

    3. COORDINATE AND SCHEDULE HIS WORK WITH THAT OF OTHER CONTRACTORSAND WITH WORK BY THE OWNER.

    4. NOT RESTRICT ACCESS TO THE BUILDING DURING HOURS OF OPERATION. PROVIDEADEQUATE PROTECTION OF THE PUBLIC FROM CONSTRUCTION ACTIVITIES. MAINTAIN PEDESTRIAN RIGHT_OF_WAY ON PUBLIC SIDEWALKS.

    B. CONSTRUCTION ORGANIZATION AND START UPTHE ARCHITECT SHALL ESTABLISH ON_SITE LINES OF AUTHORITY AND COMMUNICATIONS, INCLUDING THE FOLLOWING:

    1. SCHEDULING AND CONDUCTING A PRE_CONSTRUCTION MEETING AND PROGRESS MEETINGS.

    2. ESTABLISHING PROCEDURES FOR TRANSMITTAL OF INTRA_PROJECT COMMUNICATIONS.

    3. INTERPRETING CONTRACT DOCUMENTS AND ASSISTING IN RESOLUTION OF QUESTIONS OR CONFLICTS WHICH MAY ARISE.

    1.04 SUBMITTALS

    A. GENERAL: SUBMIT SHOP DRAWINGS, PRODUCT DATA AND SAMPLES AS REQUIREDBY THE CONTRACT DOCUMENTS.

    B. SHOP DRAWINGS: DRAWINGS SHALL BE PRESENTED IN A CLEAR AND THOROUGHMANNER. DETAILS SHALL BE IDENTIFIED BY REFERENCE TO DETAILS SHOWN ON THECONTRACT DRAWINGS.

    C. PRODUCT DATA: EACH COPY SHALL BE CLEARLY MARKED TO:1. IDENTIFY PERTINENT PRODUCTS.

    2. SHOW PERFORMANCE CHARACTERISTICS AND CAPACITIES.

    3. SHOW DIMENSIONS AND REQUIRED CLEARANCES.

    D. SAMPLES: SAMPLES SHALL BE OF SUFFICIENT SIZE AND QUANTITY TO CLEARLY ILLUSTRATE:

    1. FUNCTIONAL CHARACTERISTICS OF THE PRODUCT.

    2. FULL RANGE OF COLOR, TEXTURE AND PATTERN.

    E. SUBMISSION REQUIREMENTS1. MAKE SUBMITTALS PROMPTLY IN ACCORDANCE WITH APPROVED SCHEDULE AND

    IN SUCH SEQUENCE AS TO CAUSE NO DELAY IN THE WORK OR IN THE WORK OFANY OTHER CONTRACTOR.

    2. NUMBER OF REQUIRED SUBMITTALS

    a. SHOP DRAWINGS: SUBMIT THREE (3) OPAQUE REPRODUCTIONS AND ONE (1) SEPIA REPRODUCIBLE.

    b. PRODUCT DATA: SUBMIT THREE (3) COPIES OF DATA.

    c. SAMPLES: SUBMIT THE NUMBER STATED IN EACH SPECIFICATION SECTION. IF NOTSTATED, PROVIDE TWO (2) SETS OF EACH SAMPLE REQUESTED.

    3. SUBMITTAL INFORMATION

    a. THE DATE OF SUBMISSION AND THE DATES OF ANY PREVIOUS SUBMISSIONS.

    b. THE PROJECT TITLE AND NUMBER.

    c. THE NAME OF THE:

    (1) ARCHITECT

    (2) CONTRACTOR

    (3) MANUFACTURER

    (4) MANUFACTURER'S REPRESENTATIVE

    d. IDENTIFICATION OF THE PRODUCT, WITH THE APPROPRIATE SPECIFICATION SECTION NUMBER.

    e. INDICATION OF LOCATION WHERE ITEM IS TO BE INSTALLED.

    f. FIELD DIMENSIONS, IF REQUIRED, CLEARLY IDENTIFIED AS SUCH.

    g. IDENTIFICATION OF DEVIATIONS FROM CONTRACT DOCUMENTS.

    h. IDENTIFICATION OR REVISIONS ON RESUBMITTALS.

    i. AN 8" X 3" BLANK SPACE FOR ARCHITECT'S STAMP.

    F. RESUBMISSION REQUIREMENTS1. SHOP DRAWINGS AND PRODUCT DATA

    a. REVISE INITIAL DRAWINGS OR DATA AND RESUBMIT AS SPECIFIED FOR THE INITIALSUBMITTAL.

    b. INDICATE ANY CHANGES WHICH HAVE BEEN MADE.

    2. SUBMIT NEW SAMPLES AS REQUIRED FOR INITIAL SUBMITTAL.

    1.05 SECURITY

    A. PROTECT OPERATIONS AT THE SITE AND BE RESPONSIBLE FOR THEFT, VANDALISMOR DAMAGE RESULTING FROM CONTRACTOR'S WORK OR EMPLOYEES.

    B. COMPLY WITH SECURITY REQUIREMENTS OF THE BUILDING MANAGEMENT.C. MAINTAIN A CURRENT LIST OF APPROVED PERSONS AND SUBMIT A COPY OF THE

    LIST TO THE BUILDING MANAGER.D. ONLY PERSONNEL PROPERLY IDENTIFIED WILL BE PERMITTED ON THE SITE.1.06 MATERIAL AND EQUIPMENT

    A. DELIVERY AND HANDLING1. ARRANGE DELIVERIES OF PRODUCTS IN ACCORDANCE WITH CONSTRUCTION

    SCHEDULES TO AVOID CONFLICT WITH WORK AND CONDITIONS AT THE SITE.

    a. DELIVER PRODUCTS IN UNDAMAGED CONDITION, IN MANUFACTURER'S ORIGINAL CONTAINERS OR PACKAGING, WITH IDENTIFYING LABELS INTACT AND LEGIBLE.

    b. IMMEDIATELY ON DELIVERY, INSPECT SHIPMENTS TO ENSURE COMPLIANCE WITHREQUIREMENTS OF CONTRACT DOCUMENTS AND APPROVED SUBMITTALS ANDTHAT PRODUCTS ARE PROPERLY PROTECTED AND UNDAMAGED.

    2. PROVIDE EQUIPMENT AND PERSONNEL TO HANDLE PRODUCTS BY METHODS WHICH PREVENT SOILING AND DAMAGE.

    B. STORAGE AND PROTECTION1. STORE PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS, WITH

    SEALS AND LABELS INTACT AND LEGIBLE. THE CONTRACTOR SHALL PROVIDE ADDITIONAL OFF SITE STORAGE SPACE AS REQUIRED.

    2. ARRANGE STORAGE IN A MANNER TO PROVIDE EASY ACCESS FOR INSPECTION.MAKE PERIODIC INSPECTIONS OF STORED PRODUCTS TO ENSURE THAT PRODUCTS ARE MAINTAINED UNDER SPECIFIED CONDITIONS AND FREE FROM DAMAGE OR DETERIORATION.

    3. PROVIDE SUBSTANTIAL COVERINGS AS NECESSARY TO PROTECT INSTALLED PRODUCTS FROM DAMAGE FROM TRAFFIC AND SUBSEQUENT CONSTRUCTIONOPERATIONS. REMOVE WHEN INSTRUCTED BY THE ARCHITECT.

    C. SUBSTITUTIONS AND PRODUCT OPTIONS1. PRODUCT LIST: WITHIN TEN (10) DAYS AFTER CONTRACT DATE, SUBMIT TO THE

    ARCHITECT A COMPLETE LIST OF MAJOR PRODUCTS PROPOSED TO BE USED, WITHTHE NAME OF THE MANUFACTURER AND THE INSTALLING SUBCONTRACTOR.

    2. PRODUCT OPTIONS

    a. FOR PRODUCTS SPECIFIED BY NAMING SEVERAL PRODUCTS OR MANUFACTURERS,SELECT ANY ONE OF THE PRODUCTS OR MANUFACTURERS NAMED WHICH COMPLIES WITH THE SPECIFICATIONS.

    b. FOR PRODUCTS SPECIFIED BY NAMING ONE OR MORE PRODUCTS OR MANUFACTURERS AND "OR EQUAL," CONTRACTOR SHALL SUBMIT A REQUEST FORSUBSTITUTION FOR ANY PRODUCT OR MANUFACTURER NOT SPECIFICALLY NAMED.

    c. FOR PRODUCTS SPECIFIED BY NAMING ONLY ONE PRODUCT AND MANUFACTURER, THERE IS NO OPTION.

    3. SUBSTITUTIONS

    a. FOR A PERIOD OF FIFTEEN (15) DAYS AFTER CONTRACT DATE, THE ARCHITECT WILLCONSIDER WRITTEN REQUESTS FROM CONTRACTOR FOR SUBSTITUTION OF PRODUCTS.

    b. SUBMIT A SEPARATE REQUEST FOR EACH PRODUCT COMPLETE WITH SUPPORTINGDOCUMENTATION AND WITH SAMPLES AS APPROPRIATE, INCLUDING:

    (1) COMPARISON OF THE QUALITIES OF THE PROPOSED SUBSTITUTION WITH THAT SPECIFIED.

    (2) CHANGES REQUIRED IN OTHER ELEMENTS OF THE WORK BECAUSE OF THE SUBSTITUTION.

    (3) EFFECT ON THE CONSTRUCTION SCHEDULE.

    (4) COST DATA COMPARING THE PROPOSED SUBSTITUTION WITH THE PRODUCT SPECIFIED.

    (5) SOURCE OF REPLACEMENT MATERIALS.

    c. THE ARCHITECT SHALL BE THE JUDGE OF THE ACCEPTABILITY OF THE PROPOSEDSUBSTITUTION.

    4. A REQUEST FOR A SUBSTITUTION CONSTITUTES A REPRESENTATION THAT CONTRACTOR:

    a. HAS INVESTIGATED THE PROPOSED PRODUCT AND DETERMINED THAT IT IS EQUALTO OR SUPERIOR IN ALL RESPECTS TO THAT SPECIFIED.

    b. WILL PROVIDE THE SAME WARRANTIES FOR THE SUBSTITUTION AS FOR THE PRODUCTSPECIFIED.

    c. WAIVES ALL CLAIMS FOR ADDITIONAL COSTS, UNDER HIS RESPONSIBILITY, WHICHMAY SUBSEQUENTLY BECOME APPARENT.

    5. THE ARCHITECT WILL REVIEW REQUESTS FOR SUBSTITUTIONS WITH REASONABLE PROMPTNESS AND NOTIFY CONTRACTOR, IN WRITING, OF THE DECISION TO ACCEPT OR REJECT THE REQUESTED SUBSTITUTION.

    1.07 CLEANING

    A. GENERAL1. EXECUTE CLEANING, DURING PROGRESS OF THE WORK AND AT COMPLETION OF

    THE WORK, AS REQUIRED BY GENERAL CONDITIONS.

    2. CONDUCT CLEANING AND DISPOSAL OPERATIONS TO COMPLY WITH CODES, ORDINANCES AND REGULATIONS.

    B. MATERIALS1. USE ONLY THOSE CLEANING MATERIALS AND METHODS RECOMMENDED BY THE

    MANUFACTURER OF THE SURFACE MATERIAL TO BE CLEANED.

    2. USE CLEANING MATERIALS ONLY ON SURFACES RECOMMENDED BY THE CLEANING MATERIAL MANUFACTURER.

    C. DURING CONSTRUCTION1. THE CONTRACTOR SHALL KEEP THE WORK FREE FROM ACCUMULATIONS OF WASTE

    MATERIALS AND RUBBISH RESULTING FROM CONSTRUCTION OPERATIONS ON ADAILY BASIS.

    2. THE WORK SHALL BE PROTECTED AND CLEANED AT THE END OF EACH WORK DAY.

    D. FINAL CLEANING1. REMOVE GREASE, MASTIC, ADHESIVES, DUST, DIRT, STAINS, FINGERPRINTS, LABELS

    AND OTHER FOREIGN MATERIALS FROM SIGHT_EXPOSED SURFACES INCLUDINGNEW GLASS ENTRANCE DOORS.

    2. PRIOR TO FINAL ACCEPTANCE, CONTRACTOR, ARCHITECT AND OWNER'S REPRESENTATIVE SHALL CONDUCT AN INSPECTION OF SIGHT_EXPOSED INTERIORSURFACES AND ALL WORK AREAS, TO VERIFY THAT THE ENTIRE WORK IS CLEAN.

    1.08 MAINTENANCE DATA

    A. COMPILE AND PRODUCE DATA AND RELATED INFORMATION APPROPRIATE FOROWNER'S MAINTENANCE OF PRODUCTS FURNISHED UNDER CONTRACT.

    B. PREPARE MAINTENANCE DATA IN AN ORGANIZED MANNER AND AS REFERENCEDIN OTHER PERTINENT SECTIONS OF THESE SPECIFICATIONS.

    C. INSTRUCT OWNER'S PERSONNEL IN MAINTENANCE OF PRODUCTS.

    G-100.00

    GENERAL REQUIREMENTS

  • EXISTING SINK TO BEREMOVED, CUT PLUMBINGBACK TO SOURCE

    EXISTING FINISHES/ CEILING& LIGHT FIXTURES TO BEREMOVED THROUGHOUT .LIGHT FIXTURES TO BESALVAGED, STORED &PROTECTED FOR POTENTIALREUSE

    EXISTINGELECTRICAL PANEL

    TO REMAIN

    REMOVE EXISTING STALLS,MILLWORK, FLOORING, WALL

    TILE, LIGHTING, SWITCHES,CEILING, FIXTURES ETC.

    REMOVE EX. GYP. BD. ATBATHROOM WALLS. MODIFY

    ROUGHING AS REQUIRED FORBATHROOM LAYOUT. REFER

    TO A-002.

    FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    DEMOLITION PLAN - 31ST FLOORSCALE: 1/8" = 1'-0"

    1

    DM-001.00

    DEMOLITION PLAN31ST FLOOR

    1. CONSTRUCTION WORK WILL BE CONFINED TO THE INTERIOR SPACE ANDWILL NOT CREATE DUST, DIRT OR OTHER SUCH INCONVENIENCES TO OTHERBUILDING TENANTS.

    2. CONSTRUCTION WORK WILL NOT BLOCK HALLWAYS OR MEANS OF EGRESSFOR TENANTS OF THE BUILDING.

    3. CONSTRUCTION WORK WILL NOT INVOLVE INTERRUPTION OF HEATING,WATER OR ELECTRIC SERVICES TO OTHER TENANTS OF THE BUILDING.

    4. CONSTRUCTION WORK WILL BE CONFINED TO NORMAL WORKING HRS. 8AM TO 5 PM, MON. THRU FRI., EXCEPT LEGAL HOLIDAYS AND/OR ASREQUIRED BY BUILDING MANAGEMENT.

    5. EXISTING FIRE ALARM & CLASS "E" SYSTEM & WIRING TO BE COILED &SUPPORTED IN CEILING FOR RELOCATION.

    6. CLASS "E" SYSTEM & ALARMS MUST REMAIN ACTIVE AT ALL TIMES7. PROVIDE FIRE WATCH AT ALL TIMES REQ'D BY BUILDING RULES AND

    REGULATIONS AND APPLICABLE CODES.

    TENANT SAFETY NOTES

    LEGEND/NOTESDEMO PLAN

    EXISTING DOOR AND FRAME TO BE

    EXISTING DOOR TO REMAIN

    EXISTING PARTITION TO REMAIN

    REMOVED

    EXISTING PARTITION TO BE REMOVED

    1. NO WORK TO BE DONE IN SPACES MARKED EXISTING EXCEPT WHERE NOTED2. REMOVE, CLEAN AND REINSTALL EXISTING WINDOW TREATMENTS IN PERIMETEROFFICES U.O.N.3. CLEAN, REPAINT, REPAIR ALL CONVECTOR COVERS. F&I CONVECTOR COVERSTO MATCH EXT. AS REQ'D U.O.N.4. REMOVE CARPET & RELATED MATERIALS THROUGHOUT. GC TO SURVEYCONDITION OF EXISTING SLAB AND PROVIDE SCRAPING OF FLOOR AS REQUIREDTO PROVIDE A CLEAN SURFACE FOR INSTALLATION OF SPECIFIED FLOORING.SCORE WALL ABOVE BASE PRIOR TO REMOVAL. SKIM COAT AND PATCH WALL ASREQ'D FOR INSTALLATION OF NEW BASE.5. REMOVE WALLCOVERING FROM ALL REMAINING SURFACES & PREP WALLSFOR SPECIFIED FINISHES6. LOWER ELEVATOR CALL BUTTONS TO 42" AFF U.O.N.7. PREP ELEVATOR DOORS & FRAMES FOR ELECTROSTATIC PAINTING.8. SAVE AND INSTALL ALL FLOOR STOPS UNLESS OTHERWISE SPECIFIED DURINGCARPET REMOVAL.9. REMOVE ALL PARTITIONS, CEILINGS, LIGHTING, POWER, VOICE DATA,MILLWORK. FLOORING & FINISHES AS REQ'D TO COMPLETE WORK INDICATED ONTHE CONTRACT DOCUMENTS.10. ALL DEMOLITION TO BE PERFORMED ON OVERTIME. COORDINATE WITHBUILDING RULES AND REGULATIONS.11. ALL OUTLETS ON WALLS TO BE DEMOLISHED TO BE REMOVED TO SOURCE(INCLUDING WIRING AND CONDUIT AS REQ'D UON). ALL OUTLETS IN EXISTINGPARTITIONS ARE TO REMAIN. GC TO TRACE WIRING AS REQ'D AND SEPARATE ASREQ'D TO MAINTAIN POWER TO EXISTING DEVICES.12. REFER TO ENGINEERING DRAWINGS PRIOR TO REMOVAL OF ALL MEPS ITEMS.13. PROVIDE TEMPORARY BARRICADE AND/OR PARTITIONS AT OPENINGS INFLOORS AND CEILINGS14. ALL DISCONNECTS AT BUILDING CORE TO BE RECONNECTED.

    PLOT PLAN

    N

    AREA OF WORK: 31ST FLNO CHANGE IN USE,OCCUPANCY OR EGRESS

    BOROUGH: MANHATTANBLOCK: 1301LOT: 33ADDRESS, ZIP CODE: 750 THIRD AVENUE, 10017LOT AREA: 38, 225 SFDISTANCE TO CORNER INTERSECTION: 0LOT FRONTAGE(DIMENSIONS OF BUILDING): 200.83 FTLOT DEPTH(DIMENSIONS OF BUILDING): 230.5 FTNUMBER OF BUILDINGS: 1NUMBER OF FLOORS: 34ZONING USE GROUP: C5-3 COMMERCIALBUILDING OCCUPANCY GROUP: EZONING MAP #: 08DCONSTRUCTION CLASSIFICATION: CLASS 1AREA OF WORK: 24TH FLOOR

  • OFFICE3117

    WELLNESS RM3103

    CLOSET3104

    OFFICE3106

    OFFICE3107

    OFFICE3108

    OFFICE3109

    OFFICE3110

    3109

    OFFICE3111

    TEAM ROOM3113

    OPEN AREA3112

    OFFICE3114

    BREAK OUT3115

    STORAGE3102

    RECEPTION3101

    OPEN AREA3134

    MEN'S RM3132A

    AV/IT3132

    ADA BATHROOM3130

    PANTRY3120

    STORAGE3121

    OFFICE3123

    OFFICE3124

    OFFICE3125

    OFFICE3126

    CONF. ROOM3127

    OFFICE3128

    STORAGE3129

    OPEN AREA3131

    OFFICE3105

    OFFICE3119

    OFFICE3118

    CONF. ROOM3116

    4

    2

    4 4 4 4

    2 2 2 2

    2

    22

    2

    2

    1

    2

    2

    2 2 2 2 2

    4

    44 4 4 4 2

    2

    2

    4

    11

    1

    1

    1

    2

    4

    4

    2

    42

    24

    4

    42

    2

    1

    1

    1

    1

    1

    3

    1

    3

    4

    5

    6

    7

    8 9 10 11 12

    13

    14

    15

    16

    19

    17

    18

    20

    21

    2324252627

    29

    30

    3132

    28

    22

    33

    ??????? ?????? ?????? ?????? ?????? ???????

    ??????

    ???????

    8'-4

    "47

    '-3"

    11'-2

    "9'

    -8"

    12'-4"8'-8"9'-0"9'-0"8'-8"

    11'-2

    "16'

    -2"

    8'-8

    "

    12'-2"

    25'-7"

    11'-8"11

    '-1"

    4'-8

    "

    34

    STORAGE3103A

    7'-0

    "

    7'-3

    "

    35

    1

    1

    15'-11"

    4

    8'-7"

    13'-0"

    8'-6

    "8'

    -11"

    8'-1

    1"

    6'-11"

    10'-4

    "

    1

    11'-8"

    8'-2"

    5'-6

    "

    6'-1"

    7'-9

    "

    12'-6"

    31'-8"

    18'-4

    "

    5

    SLIDING GLASS DOOR OFFICE FRONT SYSTEMBY TAG WALL OR EQUAL.. PROVIDEBLOCKING AT GYP. BD HEADER. HEADERNEED NOT EXTEND SHEETROCK TO SLABABOVE - LEAVE OPEN FOR RETURN AIR (TYP.AT OFFICE FRONTS).

    MANUALLY OPERATED MODERN FOLDPARTITION W/ FABRIC PANELS. PROVIDE STEELINFRASTRUCTURE AT SLAB FOR HANGINGPANEL SYSTEM. PROVIDE ACOUSTIC BARRIERABOVE CEILING BETWEEN ROOMS.

    2 A-007-

    ?????????????????????????????????????????HIGH) AT ALL WALLS ADJACENT TO OFFICE

    DESKS, TYP. FOR UPPER CABINETS AT ALLOFFICES. BLOCKING MOUNTING HEIGHT TBD.

    BY TENANT

    F&I (5) PLASTIC LAMINATE 24" DEEPADJUSTABLE SHELVES ON DUAL SLOT HEAVYDUTY STANDARDS & BRACKETS. PROVIDE INWALL BLOCKING AS REQUIRED.

    PLASTIC LAMINATE UPPER AND LOWER CABINETSWITH PLASTIC LAMINATE COUTNERTOP. PROVIDE

    BLOCKING AS REQUIRED.

    AT CONFERENCE ROOM 3116 PROVIDESUPPLEMENTAL A.C. UNIT FOR SCHEDULEDHEAT LOAD. PROVIDE RE-HEAT CAPABILITIESFOR WINTER USE.

    2

    2

    2

    1

    1

    2

    F&I 12x24 LOUVER@ DOOR

    A-0081

    A-0072

    ALIGN

    1

    2

    2

    2

    OPEN STORAGE3133

    WOMEN'S RM3131A

    36

    38

    37

    39

    34

    40

    1'-0

    "HO

    LD

    34" AFF

    36" AFF

    F&I (1) PLASTIC LAMINATE 18" DEEP ADJUSTABLESHELF ON DUAL SLOT HEAVY DUTY STANDARDS &

    FULL HEIGHT BRACKETS. PROVIDE IN WALLBLOCKING AS REQUIRED.

    LANDLORD TO F&I 18"VERTICAL GRAB-BAR AT

    EXISTING ADA BATHROOM PROVIDE ALTERNATE FOR ADA BATHROOM UPGRADE. PROVIDE LINE ITEM PRICING FOR TILE

    WORK, PLUMBING FIXTURES, CEILING/LIGHTING.

    CORE RESTROOMS TO RECEIVE FULL BUILDING STANDARD COSMETIC UPGRADES INCLUDINGCEILINGS, LIGHTING, FULL HEIGHT WALL TILE, FLOOR TILE, PLUMBING FIXTURES ON EXISTING

    ROUGHING, ACCESSORIES, ST. ST. PARTITIONS, ETC. - BY LANDLORD.

    2

    3

    4

    OFFICE3122

    CORNER BEADS

    1" x 2" RECTANGULARTUBE ALUMINUM EXTRUSION

    SCREWED TO METAL STUD

    1/4" THK. CLOSED CELLNEOPRENE COMPRESSEDTO 1/8"

    5/8" GYPSUM BOARDCAULK AT CONVECTOR

    1"x2" RECTANGULAR TUBE ALUMINUMEXTRUSION CEMENTED WITH CAULK ATMULLION AND AT CONVECTOR

    FACE OF CONVECTOR

    PARTITION (AS SPECIFIED)

    (BOTH SIDES)

    1" THK. U.S.G.THERMAFIBER 'SAFB'MINERAL WOOL (AT ALL EDGES)

    EXISTING WINDOW

    2" MAX. CLEARANCE

    4"

    1" x 2" RECTANGULARTUBE ALUMINUM EXTRUSION

    SCREWED TO METAL STUD

    5/8" GYPSUM BOARDCAULK AT CONVECTOR

    1"x2" RECTANGULAR TUBE ALUMINUMEXTRUSION CEMENTED WITH CAULK ATMULLION AND AT CONVECTOR

    FACE OF CONVECTOR

    PARTITION (AS SPECIFIED)(BOTH SIDES)

    1" THK. U.S.G.THERMAFIBER 'SAFB'MINERAL WOOL

    EXISTING WINDOW

    1'-0" CLEARANCEFROM FACE OF CONVECTOR

    4"

    2" MAX

    1/4" THK. CLOSED CELLNEOPRENE COMPRESSEDTO 1/8"

    FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    CONSTRUCTION PLAN - 31ST FLOORSCALE: 1/8" = 1'-0" N

    1

    A-002.00

    CONSTRUCTION PLAN31ST FLOOR

    LEGEND/NOTESCONSTRUCTION PLAN

    DETAIL SYMBOL

    SECTION SYMBOL

    ELEVATION SYMBOL

    DETAIL #

    SECTION #

    DRAWING #

    DRAWING #

    DRAWING #

    XX

    ROOM NAME

    ROOM NUMBER

    F&I GYPSUM BOARD PARTITION, SEE PARTITION TYPES FOR DETAILS

    PARTITION TYPE REFERENCE

    ELEVATION #s

    ELEVATION #

    DOOR NUMBER

    EXISTING PARTITION & BUILDING CORE TO REMAIN

    MILLWORK

    TYP.DIM. FROM INSIDEBUCK TO PARTITION

    DRAWING #

    1. G.C. TO LAY OUT PARTITIONS FOR ARCHITECT APPROVAL PRIOR TOCONSTRUCTION2. G.C. TO NOTIFY ARCHITECT AS TO ANY DEVIATIONS IN THE LAYOUT PRIOR TO THEERECTION OF STUDS.3. ALL DIMENSIONS ARE TO BE HELD WITHIN 1"4. DOOR HANDLES SHALL BE LEVER-TYPE CONSISTENT WITH THE REQUIREMENTS OFANSI A117.1-1986 (TYP.)5. G.C. TO REVIEW ALL MECHANICAL ACCESS POINTS WITH BASE BUILDINGMANAGEMENT. PROVIDE AND INSTALL ACCESS DOORS AS REQUIRED.6. FLASH PATCH & LEVEL EXISTING FLOORS AS REQ'D FOR SPECIFIED FLOORING.PROVIDE MIN. 4'-0" OF FLASHING AT ELEVATOR LOBBIES7. ALL PARTITIONS ARE TYPE 1 U.O.N.8. GC TO PATCH ALL WALLS WHERE BASE BUILDING DEVICES, SUCH AS FIREWARDEN STATION, ARE BEING LOWERED,REMOVED OR RELOCATED.9. THE FOLLOWING CONTROLLED INSPECTIONS ARE REQUIRED AND ARE TO BECOMPLETED BY THE CONTRACTOR AND/OR THIRD PARTY????????????????????????????????????????????????????????????????????FIRE ALARM, FIRESTOPPING, AND FINAL INSPECTION . ? IT IS THE RESPONSIBILITY OFTHE OWNER TO HIRE A THIRD PARTY INSPECTOR TO PERFORM AND COMPLETE ALLMECHANICAL, SPRINKLER CONTROLLED INSPECTIONS AND FINAL INSPECTION ASREQUIRED IT IS THE RESPONSIBILITY OF THE CONTRACTOR AND/ORSUBCONTRACTOR TO COORDINATE AND PROVIDE ALL REQUIRED TESTS FOR ALLINSPECTIONS & ASSOCIATED PAPERWORK FOR FILING AND SIGN OFF OF THEWORK INDICATED IN THE CONSTRUCTION DOCUMENTS WITH THE APPROPRIATELOCAL AGENCY AND/OR DEPARTMENT OF BUILDINGS.10. GC TO COORDINATE PARTITION DIMENSIONS AS APPROVED BY THEARCHITECTS AT THE SITE WITH ALL SHOP DRAWINGS.11. LAMINATE ALL UNFINISHED EXPOSED SURFACES W/ 5/8" GYPSUM BOARD.PATCH/REPAIR ALL EXPOSED UNFINISHED SURFACES U.O.N.12. G.C. TO PATCH & PREPARE ALL WALLS AS REQ'D. FOR SPECIFIED FINISH. GC TOCOORD W/MFGR OF FINISHES FOR RECOMMENDED PREPARATION.13. F&I 4'X8' F.R. PLYWOOD PANEL 3/4" THK MOUNTED ON WOOD STUDS FORTELEPHONE HUB CONNECTIONS. CONFIRM LOCATION WITH ARCHITECT IN FIELD.NOT TO BE PAINTED. FIRE RATING TO BE EXPOSED.14. GC TO PUT LASER LINE ON FLOOR & ADVISE ARCHITECT OF DEVIATION OFFLOOR SLAB. GC TO DETERMINE BENCH MARK & ADVISE ARCHITECT ON ALL AREASAFFECTED PRIOR TO RELEASING TRADES AND ORDERING MATERIALS15. ALL PENETRATIONS THROUGH FIRE RATED WALLS, FLOORS, OR PARTITIONSSHALL BE FIRE STOPPED AND SEALED. THE FIRE RATING OF THE SEAL SHALL BE ATLEAST THAT OF THE FLOOR OR WALL INTO WHICH IT IS INSTALLED.16. F&I TYPE 'ABC' FIRE EXT. PER 3,000 SQUARE FEET IN SPRINKLERED BUILDING.MAX. TRAVEL DIST. BETWEEN EXTINGUISHERS TO BE 75 FT. F & I POTTER ROEMERALTA SERIES 7000 RECESSED WHITE FIRE EXTINGUISHER CABINET WITH DUO VERTICALPANEL & 1/8" CLEAR ACRYLIC GLAZING W/ 3010 EXTINGUISHER OR APPROVEDEQUAL. MOUNT 48" AFF TO HANDLE. REFER TO PLANS.17. AT ALL LOCATIONS WHERE AN INSULATED PARTITION (NEW OR EXISTING) MEETSA CONVECTOR, PROVIDE "BEAN BAG" INSULATION IN CONVECTOR AS REQ'D TOOBTAIN THE STC RATING OF THE PARTITION.18. ALL WORK INDICATED IN THE BUILDING RULES & REGULATIONS IS TO BEINCLUDED IN CONTRACTORS SCOPE19. GC TO PROVIDE BUILDING DEPARTMENT SIGN-OFFS & FULL SETS OF AS BUILTDWG'S (HARD COPIES AND ELECTRONIC FORMAT) FOR ALL TRADES PRIOR TOCLIENTS RELEASE OF FINAL PAYMENT.20. SKIMCOAT ALL WALLS WHERE WALLCOVERING WAS REMOVED AND AT AREASNOTED ON PLAN.21. ALL WALLS AT CONFERENCE ROOMS AND RECEPTION AREAS TO BE SKIMCOATED PRIOR TO SPECIFIED FINISH22. GC TO PROVIDE CONTROLLED INSPECTION OF EXISTING FIREPROOFING PERLOCAL LAW 26. GC TO SUBMIT UNIT PRICING FOR ADDITIONAL FIREPROOFING ASREQUIRED. PROOF OF DOB SIGN OFF OF CONTROLLED INSPECTIONS MUST BESUBMITTED PRIOR TO CLIENTS RELEASE OF FINAL PAYMENT.23. CONTRACTOR TO FURNISH AND INSTALL TRUBRO INSULATION AT ALL EXPOSEDPIPING AT BATHROOM AND PANTRIES.

    MULTIPLE ELEVATIONS

    XXX

    A-00X1

    XXX

    GENERAL NOTES:

    1. ALL DIMENSIONS AND CONDITIONS ARE APPROXIMATE ANDSUBJECT TO FIELD VERIFICATION.

    2. ALL EXISTING CORE WALLS AND COLUMNS TO BE LAMINATEDFOR SMOOTH, LEVEL FINISH TO FINISHED CEILING AND PREPPEDFOR SPECIFIED FINISH. FURR WALLS AS REQ'D FOR INSTALLATIONOF DEVICES - COORD. W/ POWER/TEL PLAN, TYP.

    3. ALL FIRE ALARM DEVICES TO BE WHITE. INSTALL PER CODE.

    4. SWINGING DOOR HARDWARE TO BE SCHLAGE ATHENS, BRUSHEDCHROME FINISH, PASSAGE FUNCTION THROUGHOUT, U.O.N.SERVER ROOM DOOR TO BE STOREROOM FUNCTION.

    5. NOTE: DOORS TO IT ROOM, WELLNESS ROOM AND STORAGEROOMS TO HAVE LOCKSETS OF VARYING FUNCTIONALITY. TO BECONFIRMED BY TENANT

    6. F&I FIRE RATED PLYWOOD AT IT ROOM

    TYP. DETAIL @ MULLION/PARTITION NTS

    TYP. DETAIL @ WALL JOGNTS

  • OFFICE3117

    WELLNESS RM3103

    CLOSET3104

    OFFICE3106

    OFFICE3107

    OFFICE3108

    OFFICE3109

    OFFICE3110

    3109

    OFFICE3111

    TEAM ROOM3113

    OPEN AREA3112

    OFFICE3114

    BREAK OUT3115

    STORAGE3102

    RECEPTION3101

    OPEN AREA3134

    MEN'S RM3132A

    AV/IT3132

    ADA BATHROOM3130

    PANTRY3120

    STORAGE3121

    OFFICE3123

    OFFICE3124

    OFFICE3125

    OFFICE3126

    CONF. ROOM3127

    OFFICE3128

    STORAGE3129

    OPEN AREA3131

    OFFICE3105

    OFFICE3119

    OFFICE3118

    CONF. ROOM3116

    J J

    J J

    1

    7

    2

    3

    KP

    42" 42" 42" 42"

    42"42"

    42"42"

    DC

    DC

    5

    R

    R

    EM

    STORAGE3103A

    42"42" 8

    PROVIDE 2" CONDUIT ABOVECEILING FROM TELECOM BUILDING

    CLOSET TO IT ROOM

    PROVIDE DEDICATED 2 AWG WIRE TOBUILDING GROUND BAR AND #6

    INSIDE RUN TO LAN ROOM BUS BAR

    38"38"

    CO

    PIER

    48"

    42"42"

    38"

    48"

    2

    6

    26

    WBK

    W

    B

    K

    OPEN STORAGE3133

    WOMEN'S RM3131A

    42"GFI

    42"GFI

    OFFICE3122

    FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    POWER/TELEPHONE PLAN - 31ST FLOORSCALE: 1/8" = 1'-0" N

    1

    EQUIPMENT LIST SPECIFICATION F.B.T. F.B.C.

    FULL HEIGHT REFRIGERATOR GE #GTZ21GCESS, ST. ST. FINISH, W/ ICE MAKER. GCTO F&I WATER LINE AS REQ'D.

    MICROWAVE GE PROFILE MODEL #PEM31SFSS, ST. ST. FINISH

    COFFEE MAKER FURNISHED BY TENANT. GC TO PROVIDE WATERLINE.

    NOT USED

    COPY MACHINE SPEC TBD BY TENANT

    PRINTER SPEC TBD BY TENANT

    DISHWASHER AVANTI ADA HEIGHT ST. ST. DISHWASHER

    WATER COOLER F&I BY CONTRACTOR WITH ASSOCIATED WATER LINE,SPEC. TBD.

    F.B.T. - FURNISHED BY TENANTF.B.C. - FURNISHED BY CONTRACTORNOTE: GC TO COORD ALL REQ'D OUTLET LOCATIONS W/ MFG. SPEC

    NOTE: FURNITURE SHOWN FOR REFERENCE PURPOSES ONLY. EXACT LOCATIONS TO BE VERIFIED WITH TENANTFURNITURE VENDOR PRICE TO POWER/BACKBOX INSTALLATION. FURNITURE SYSTEMS TO BE 2+2 SYSTEM; GCRESPONSIBLE FOR FINAL WHIP CONNECTION.

    1

    2

    3

    4

    5

    6

    7

    A-003.00

    POWER TELEPHONE PLAN31ST FLOOR

    LEGEND/NOTESPOWER TELEPHONE PLAN

    RECESSED WALL-MTD DUPLEX OUTLET BOX AND STUB-UP

    RECESSED WALL-MTD QUAD OUTLET BOX AND STUB-UP

    CIRCUIT. REFER TO ENGINEERING DRAWINGS FOR DETAILSRECESSED WALL-MOUNTED OUTLET BOX AND STUB-UP ON SEPARATE

    RECESSED OUTLET BOX AND STUB-UP FOR V/D COMBINATION

    RECESSED WALL HUNG PHONE OUTLET BOX/STUB-UP 48" AFF

    RELEASE BUTTON GC TO PROVIDE BACKBOXES AT WALL LOCATIONS

    1. ALL OUTLETS TO BE MTD VERTICALLY CENTERLINE 18" ABOVE FINISHED FLOORU.O.N.2. ALL OUTLETS TO BE LEVITON 'DECORA': COLOR-WHITE3. CONTRACTOR TO TAG ALL OUTLETS4. DIMENSIONS FOR POWER AT PERIMETER OFFICE IS OFF OF THE CONVECTORU.O.N.5. CONTRACTOR TO MODIFY CONVECTORS AS REQUIRED TO F&I CORRECTPOWER, DATA, AND TELEPHONE OUTLETS6. PROVIDE ALL REQ'D. CONNECTIONS FROM ELECTRIFIED DEVICES TO THEASSOCIATED CONTROLS-GC TO COORDINATE W/ CLIENTS' VENDORS AS REQ'D.7. PROVIDE MULTIPLE GANG COVER PLATES FOR ALL ADJACENT OUTLETS &SWITCHES.8. ALL FIRE ALARM DEVICES TO BE WHITE.9. PROVIDE ACOUSTICAL SEALANT AT ALL BACKBOXES IN INSULATED WALLS.10. ALL OUTLETS IN PANTRIES & BATHROOMS AND OTHER WET AREAS TO BE GFITYPE U.O.N.11. GC TO PROVIDE CONDUIT, STUB-UPS, BACK BOXES, AND POWER AS REQ'D.FOR ALL SECURITY DEVICES12. SECURITY VENDOR TO PROVIDE ALL WIRING AND DEVICES NECESSARY TOIMPLEMENT DESIGN INTENT.13. ALL OUTLET DEVICES NOTED FOR COMPUTER TO BE TAGGED, COVER PLATESTO MATCH ALL OTHER PLATES IN COLOR.14. ALL OUTLET DEVICES AND COVERPLATES IN MILLWORK OR ON ACCENT WALLSTO MATCH COLOR OF WALL UON. SUBMIT SAMPLE FOR ARCHITECT APPROVAL.15. COORDINATE OUTLET DEVICE HEIGHTS WITH ELEVATIONS. AT PANTRYCOORDINATE DEVICE LOCATION WITH MANUFACTURER SPECIFICATIONS.16. ALL OUTLETS THAT SHOW FOR LCD TVS TO BE CLOCK OUTLETS17. ALL A/V CONDUIT TO BE 2" DIAMETER UON.18. GC TO PROVIDE GROUNDING FOR SERVER ROOMS WITH STATIC DISSIPATIVETILES, COORD. WITH ENGINEER AND FINISH PLANS19. BOXES IN RATED WALLS TO BE SEALED WITH 3M BARRIER PUDDY OR APPROVEDEQUAL TO MAINTAIN RATING. COORDINATE WITH PARTITION TYPES20. ALL ELECTRIFIED SECURITY DEVICES TO BE TIED INTO CLASS E SYSTEM

    MODULAR RACEWAY POWER/VOICE/DATA SYSTEM COORDRECEPTACLES W/ EQUIPMENT AND ENGINEERING DRAWINGS. GCTO PROVIDE ALL CONNECTIONS FOR POWER AND DATA AS REQ'D.

    INDICATES EQUIPMENT ONLY SEE ENGINEERING DWGS FORSEPARATE CIRCUITS OR SPECIAL OUTLET REQUIREMENTS.

    POWER JUNCTION BOX - LOCATION TO BE DETERMINED IN FIELDW/ FURN. VENDOR

    V/D JUNCTION BOX - LOCATION TO BE DETERMINED IN FIELDW/ FURN. VENDOR

    CIRCUIT. REFER TO ENGINEERING DRAWINGS FOR DETAILSRECESSED WALL-MOUNTED OUTLET BOX AND STUB-UP ON SEPARATE

    8

    CORE DRILL FOR POWER/DATA/AV. COORDINATEREQUIREMENTS W/ CONFERENCE TABLE BOX SPECIFICATIONS

    CORE DRILL FOR FURNITURE IN-FEED POWER/DATA

    KEY PAD - PROVIDE BACKBOX AND STUB-UP

    ELECTRIC MAGNETIC LOCK TIE INTO BUILDING CLASS 'E' SYSTEM

    DOOR CONTACT. ( BY TENANT SELECTED VENDOR)

  • OFFICE3117

    WELLNESS RM3103

    CLOSET3104

    OFFICE3106

    OFFICE3107

    OFFICE3108

    OFFICE3109

    OFFICE3110

    3109

    OFFICE3111

    TEAM ROOM3113

    OPEN AREA3112

    OFFICE3114

    BREAK OUT3115

    STORAGE3102

    RECEPTION3101

    OPEN AREA3134

    MEN'S RM3132A

    AV/IT3132

    ADA BATHROOM3130

    PANTRY3120

    STORAGE3121

    OFFICE3123

    OFFICE3124

    OFFICE3125

    OFFICE3126

    CONF. ROOM3127

    OFFICE3128

    STORAGE3129

    OPEN AREA3131

    OFFICE3105

    OFFICE3119

    OFFICE3118

    CONF. ROOM3116

    VS

    VS

    VS

    VS

    SVS

    VS

    SVS

    S

    VS

    VS

    SVS

    SVS

    VS

    VS

    VS

    VS

    VS

    VS

    SVS

    SSVS

    S

    SMAIN

    L4L4L4L4L4

    L4L4L4L4L4

    VS

    VS

    VS

    SVS

    SM

    9'-0"

    L2a

    VSVS

    L2

    SDb

    9'-0"9'-0"

    9'-0"

    9'-0" 9'-0"

    9'-0"

    9'-0"

    9'-0"

    L7

    9'-0"

    9'-0"9'-0" 9'-0" 9'-0"9'-0"

    8'-2"

    9'-0"

    9'-0"

    8'-2"

    8'-2"

    8'-2"

    8'-2"8'-2"

    8'-2"

    8'-2"

    8'-2"

    8'-2"

    8'-2"8'-2"8'-2"

    8'-2"

    L4b

    (A)

    3Db

    L4b L4b

    L4b

    L4b

    L4b

    L4b

    L4b

    L4b

    L4b L4b

    L4b

    L4b

    L4b

    L4b

    L4b

    L4b

    9'-0"

    9'-0"

    L2a L2a L2a

    L2aL2a

    L2a L2a L2a

    L2aL2aL2a

    L1 L1 L1L1L1L1

    L1L1

    L1L1L1

    S3Da S3Db

    L2L2

    L2

    L2 L2

    L2 L2

    L2 L2

    L2

    L2 L2

    L2L2

    L2

    L2L2

    L2L2

    L2

    L2

    L2 L2

    L2L2

    L2 L2

    L2

    L2

    L1L1

    L1 L1

    L1L1L1L1L1

    L1

    L1

    L1L1

    L1

    L1

    L2L2 L2

    L2L2

    L2L2

    L7

    L1

    L8L8

    STORAGE3103A

    3Da

    L7 L7 L7L7L7

    L4 L4

    L4 L4

    L4

    L4

    L4

    L4

    L4 L4

    L4

    L5

    L6

    L6

    L6

    L1

    L4

    L1

    L4

    L1 L1 L1L1

    L1

    L1

    L1

    L1 L1

    L1 L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L1

    L4

    L4

    L4

    L4

    L4

    L4

    L4

    L7

    L4

    L4

    L4

    L4

    L4

    PROVIDE 350 CFM VARIABLE SPEEDEXHAUST FAN TIED TO THERMOSTAT

    A-003A

    L4

    PROVIDE JUNCTION BOX FORRECESSED ELECTRIFIED PROJECTORSCREEN

    VS

    VS

    OPEN STORAGE3133

    WOMEN'S RM3131A

    L1L1L1

    L1

    L1L1

    OFFICE3122

    EXTEND SOFFIT DOWN TOCONCEAL EXISTING

    DUCTWORK AT LOUVERPENETRATIONS (2), VIF

    L9

    L9

    L9

    L9 L1S

    TEMP. SENSOR

    LC

    STROBESPEAKER

    THERMOSTAT/

    DIMMERSWITCH/

    T

    38" AFF C

    48" AFF TO TOP

    80" AFF C

    COORDINATE LOCATION OF ALL F.A.SPEAKERS AND STROBES WITHARCHITECT AND ENGINEER PRIOR TOINSTALLATION

    NOTE: MODIFY CONDUIT FEEDS TO ALLOW

    STACKED INSTALLATION

    6"

    ACOUSTICAL PANEL CEILINGALIGN

    METAL STUD TRACK

    GYPSUM BOARD

    REFERTO RCP

    SHADOW MOLDING

    SUSPENSION SYSTEM

    HANGER ROD

    CARRYING CHANNEL

    METAL STUD

    CORNER BEAD

    REFER TORCP

    ?????

    REFER TO RCP

    (TYPICAL)

    2-1/2" METAL STUDSAND RUNNERS

    5/8" GYP. BD.

    EXISTING SLAB

    EXTRUDED METALWINDOW POCKET

    EXISTING WINDOW

    ALIGN W/ CONVECTOR BELOW

    ????

    EXISTING FIREPROOFINGPATCH AS REQUIRED

    FINISH CEILING

    ALIGN

    BOTTOM OF MULION

    WT/01

    WT/02 ADDITIONAL BLACKOUT SHADE ALT. AT CONF.

    RM. 3215 ON LIP

    N

    FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    REFLECTED CEILING PLAN - 31ST FLOORSCALE: 1/8" = 1'-0" SCALE: NTS

    TYPICAL ELEV.1 2

    A-004.00

    REFLECTED CEILING PLAN31ST FLOOR

    LEGEND/NOTESREFLECTED CEILING PLAN

    GC TO FURNISH AND INSTALL ACOUSTICALLY LINED TILES TO

    LIGHT SWITCH, SUBSCRIPT INDICATES CIRCUIT

    DIMMER SWITCH3 WAY LIGHT SWITCHS3

    S#

    SD

    1. ALL CLGS TO BE ACOUSTICAL TILE U.O.N.2. ALL LIGHT SWITCH CENTERLINE HEIGHTS TO BE 38" A.F.F. U.O.N.3. ALL SWITCHES AND DIMMERS TO BE LEVITON 'DECORA' COLOR: WHITEVACANCY SENSORS TO BE LEVITON PIR/MULTI TECH OR APPROVED EQUAL.COORDINATE WITH ENGINEERS DRAWINGS4. ALL INCANDESCENT LIGHTS TO BE ON DIMMERS.5. COORDINATE EXIT SIGN LOCATIONS W/ ARCHITECT IN FIELD6. V.A.V. BOXES SHALL NOT BE PLACED IN GYP. BD. CLGS.7. PROVIDE CUT OUTS IN CEILING AS REQ'D FOR ALL PAGING AND SECURITYDEVICES.8. REFER TO ENGINEERING DWGS FOR EMERGENCY LIGHTING AND NIGHT LIGHTS9. TIMECLOCK SWITCH TO COORDINATED WITH ENGINEERING DRAWINGS10. CEILING CONTRACTOR TO INCLUDE SCOPE OF WORK INVOLVING REMOVALAND REINSTALLATION OF EXISTING CEILINGS AS REQ'D TO COMPLETE WORKINDICATED ON ALL CONTRACT DOCUMENTS11. GC TO SUBMIT ALL LIGHT CUTS, STEEL SHOPS & ALL OTHER ITEMS THE ARE TO BEINSTALLED ABOVE CEILING TO HVAC SKETCHER. ALL ITEMS & CONFLICTS TO BECLEARLY IDENTIFIED TO THE ARCHITECT & ENGINEER IN SHOP DRAWINGS FORCOORDINATION PRIOR TO FABRICATION AND INSTALLATION12.F&I INTEX FORMS-INTEX A-PANEL FIBERGLASS ACCESS PANELS AS REQ'D G.C.TO COORD. W/ ARCH. & ENGINEERING DWGS. FOR LOCATION & SIZE13. CEILING CONTRACTOR TO COORD. SCOPE OF WORK INVOLVING FLOORBELOW W/ ELECTRICIAN & ALL OTHER TRADES BIDS. TO INCLUDE ALL NECESSARYPATCHING & MODIFICATION TO FLOOR BELOW ON OVERTIME.14. ALL GYPSUM BOARD CEILINGS AT CONFERENCE ROOMS AND RECEPTIONAREAS TO BE SKIM COATED PRIOR TO SPECIFIED FINISH15. MODIFY EXISTING WINDOW POCKET AS REQUIRED TO ACCOMMODATECEILING HEIGHT AS NOTED ON REFLECTED CEILING PLAN. PROVIDE CONTINUOUSMETAL PAN TO CONNECT EXISTING POCKET FACE TO CEILING. PATCH LENGTH OFPOCKET AS REQUIRED FOR CONTINUOUS HORIZONTAL RUN AT POCKET.16. ANY EXPOSED DUCTWORK FOR FRESH AIR INTAKE CANNOT BE INTERIOR LINED.LINING MUST BE ON EXTERIOR (PAINTED) TO MATCH. COORDINATE WITHENGINEERS.17. ARCHITECT TO BE NOTIFIED IF ACOUSTICAL TILES WILL BE LESS THAN 4" CUTS18. ALL CUT EDGES OF CEILING TILE TO BE PAINTED TO MATCH TILE COLOR

    GYPSUM BOARD CEILING

    SMAINMAIN SWITCH BANK WITH TIMECLOCK FOR RECEPTION, OPENAREA AND CORRIDOR LTG. REFER TO ENGINEERING DWGS.FOR QUANTITY.

    GRID SPEC: ARMSTRONG SUPRAFINE EXPOSED TEE 9/16" GRID

    2' x 2' ACOUSTICAL CEILING TILE SPEC: ARMSTRONG ULTIMA 1912

    MATCH SPECIFIED TILES AT OFFICES ADJACENT TOMECHANICAL ROOMS, REFER TO PLANS

    SVS

    CEILING MOUNTED VACANCY SENSOR TIED TO WALL SWITCH

    2'X2' CENTER BASKET RECESSED FLUORESCENT FIXTURE: ZENITHSERIES ZBS: ZBS-22G-317-BIAX-ELB-FLXL12'X4' CENTER BASKET RECESSED FLUORESCENT FIXTURE: ZENITH ISERIES ZBS: ZBS-24G-232-OCT-ELB-FLXL2

    CEILING RECESSED DOWN LIGHTLIGHTOLIER, 4X4 1000 LUMEN C4XC4L10DL, 40K CL, OR EQUIV.L4

    L5 CEILING RECESSED WALLWASHERLIGHTOLIER, 4X4 1000 LUMEN, FRAME: C4X4L10NUVBZ10V, TRIM:C4X4L10DL35KCLWVB

    L6 PENDANT LIGHT, TBD. PROVIDE ALLOWANCE OF $550/FIXTURE

    CONTINUOUS UNDERCABINET LIGHTING - ALKCO "ARIS" LEDLIGHT - FIXTURES TO BE MTD END TO END AS REQ'D. REFER TOPLAN FOR RUN LENGTH, ARIS-[PER PLAN]-2700-120-PRL-HWC

    L8

    EXIT SIGN: ATLITE LED EDGE LIT EXIT SERIES - MARATHON (BATTERYBACK UP)- CLEAR BACKGROUND. LETTER COLOR: RED.

    LIGHT SWITCH VACANCY SENSOR, TYP. REFER TO ENG. DWGSFOR SPECIFICATIONS

    SUBSCRIPT INDICATES MOTORIZED SCREEN SWITCHSM

    CEILING TRANSITION SCALE: 3" = 1'-0"

    A

    ASSUME 70% 2X4 FIXTURES INDICATED TO BE SALVAGED FROMEXISTING BUILD-OUT. GC TO RE-LAMP FIXTURES

    ALTERNATE: PROVIDE ALTERNATE PRICING TO F & I NEWBUILDING STANDARD 2X4 BASKET FIXTURES TO MATCH 2X2FIXTURES IN LIEU OF SALVAGING & RE-USE.

    CEILING RECESSED LINEAR FLUOR. LIGHT, REFER TO PLAN FORLENGTH, CORONET, LSR4-4FT-2-T8-(VOLT)- FLAMP: (2) DOWN, 3500K

    L7

    WINDOW POCKET DETAIL (TYP.)

    MARK LIGHTING MP - SERIES #MP-120-EBB-2T8-32W LAMPFIXTURE. CUSTOM LENGTH - VERIFIY IN FIELDL9

  • OFFICE3117

    WELLNESS RM3103

    CLOSET3104

    OFFICE3106

    OFFICE3107

    OFFICE3108

    OFFICE3109

    OFFICE3110

    3109

    OFFICE3111

    TEAM ROOM3113

    OPEN AREA3112

    OFFICE3114

    BREAK OUT3115

    STORAGE3102

    RECEPTION3101

    OPEN AREA3134

    MEN'S RM3132A

    AV/IT3132

    ADA BATHROOM3130

    PANTRY3120

    STORAGE3121

    OFFICE3123

    OFFICE3124

    OFFICE3125

    OFFICE3126

    CONF. ROOM3127

    OFFICE3128

    STORAGE3129

    OPEN AREA3131

    OFFICE3105

    OFFICE3119

    OFFICE3118

    CONF. ROOM3116

    01PT

    CP01

    LV-02

    CP-01

    RB01

    01PT

    RB01

    01PT

    RB01

    01PT

    RB01

    01PT

    RB01

    01PT

    RB01

    01PT RB

    01

    RB01

    01PT RB

    01

    01PT RB

    01

    01PT

    RB01

    01PT

    RB01

    01PT

    RB01

    01PT

    RB01

    01PT

    RB01

    01PT

    RB02

    01PT

    VT01

    RB03

    01PT RB

    01

    01PT

    VT01

    RB03

    01PT

    VT01

    RB03

    01PT CP

    01RB

    01

    CP01

    CP01

    01PT

    VT01

    RB03

    RB01

    01PT

    01PT

    CP01

    RB01

    LV-02

    CP-01

    CP-01

    LV-02

    L

    V

    -

    0

    2

    C

    P

    -

    0

    1

    C

    P

    -

    0

    1

    V

    T

    -

    0

    1

    C

    P

    -

    0

    1

    V

    T

    -

    0

    1

    VT-01

    CP-01

    LV01

    RB02

    01PT

    LV-01

    CP-01

    CP-01

    LV-01

    VT-01

    CP-01

    CP02

    01PT RB

    02LV

    01

    04PT

    01WP

    03PT

    04PT RB

    02LV

    01

    CP01

    CP01

    CP01

    CP01

    CP01

    CP01

    CP02

    CP01

    CP01

    CP01

    CP01

    CP01

    CP01

    CP01

    02PT

    STORAGE3103A

    03PT

    02PT

    02PT

    02PT

    02PT

    02PT

    02PT

    02PT

    02PT

    02PT

    02PT

    02PT

    02PT

    02PT

    04PT

    04PT

    02PT

    01PT RB

    01CP

    01

    02PT

    01PT RB

    01CP

    01

    02PT

    04PT

    01WP

    05PT

    05PT

    06PT

    01WP

    01PT

    VT01

    RB03

    V

    T

    -

    0

    1

    C

    P

    -

    0

    1

    C

    P

    -

    0

    1

    V

    T

    -

    0

    1

    01PT

    VT01

    RB03

    CO

    PIER

    01PT

    VT01

    RB03

    OPEN STORAGE3133

    WOMEN'S RM3131A

    CP-

    01

    PS-0

    1

    02PS

    01ST

    03PS

    PS01

    02PS

    03PSPS

    01

    01ST

    02PS

    03PSPS

    01

    02PS

    03PSPS

    01

    CP-

    01

    PS-0

    1

    01PTPS

    01

    CP-

    01

    PS-0

    1

    PROVIDE 6"COVE BASE ATJ.C. TO MATCHFLOORING

    OFFICE3122

    N

    FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    FINISH PLAN - 31ST FLOORSCALE: 1/8" = 1'-0"

    1

    A-005.00

    FINISH PLAN31ST FLOOR

    5

    LEGEND/NOTESFINISH PLAN

    1. NOT USED2. ALL CLOSET FLOORING TO BE SAME AS ADJACENT AREA U.O.N.3. VINYL BASE THROUGHOUT SPACE U.O.N. ALL VINYLBASE TO BE ROLL GOODS U.O.N.

    4. ALL AREAS TO BE U.O.N.

    5. WALLS TO BE IN EGGSHELL, DOORS & FRAMES IN SEMI-GLOSS6. ALL PAINT GRADE WOOD TO BE POPLAR (U.O.N.)7. PROVIDE REDUCER STRIPS AS NECESSARY8. FLASH PATCH ALL FLOORS AND PREP FOR SPECIFIED FINISH9. ELEVATOR DOORS TO BE SANDED, BONDO'D & PREPPED TO RECEIVE ROLL ONPAINT10. VINYL BASE OVER 4" HIGH IS TO BE 1/8" THICK-TYP. INSTALLER TO INSPECT WALLS& FLOORS 3 DAYS PRIOR TO INSTALLATION AND CONFIRM ACCEPTABILITYTHROUGHOUT11. SEAMING DIAGRAMS MUST BE SUBMITTED TO ARCHITECT & APPROVED PRIORTO INSTALLATION OF CARPET12. ALL GYP BOARD CEILINGS AND WINDOW POCKETS TO BE PAINTED13. PROVIDE TRACKS FOR ALL BLACK OUT SHADES14. PROVIDE FASCIA/VALENCE FOR ALL WINDOW TREATMENTS15. SKIMCOAT ALL WALLS WHERE WALLCOVERING IS REMOVED AND AS NOTED ONPLAN.16. PAINT ALL EXPOSED RADIATORS AND RADIATOR PIPING WHITE17. PAINT ALL EXPOSED CONDUIT, SPRINKLERS AND DUCTWORK WHITE.18. GC TO PROVIDE 5% ATTIC STOCK UON FOR SPECIFIED FINISHES INCLUDINGPAINT, CARPET, BASE, WALLCOVERING AND ACOUSTICAL CEILING TILE.COORDINATE WITH ARCHITECT19. F & I STATIC DISSIPATIVE VINYL TILE AT COMPUTER ROOMS. REFER TO PLANSAND SPECIFICATIONS20. EXISTING WINDOW TREATMENT TO REMAIN. REMOVE, CLEAN AND RE-INSTALLTHROUGHOUT. PROVIDE NEW SHADES TO MATCH EXISTING AS REQUIRED DUE TONEW WALL LOCATIONS.2Q. ALL COLOR SELECTIONS SUBJECT TO TENANT APPROVAL.21. ALL EXISTING CONVECTOR COVERS SHALL BE PAINTED PER BUILDINGSTANDARD4. ALL HM DOOR AND FRAMES SHALL BE PAINTED, COLOR: TBD5. ALL SOFFIT AND GYP. BD. CEILINGS, WINDOW POCKETS TO BE PAINTED FLATWHITE5. ALL WALLS TO BE EGGSHELL. HM DOORS, FRAMES & CONVECTOR COVERS TOBE SEMI-GLOSS. ALL CEILINGS TO BE FLAT6. ELEVATOR DOORS TO RECEIVE STANDARD PREP AND ROLLED PAINT

    PAINT - SHERWIN WILLIAMS TBD

    PAINT - SHERWIN WILLIAMS TBD

    CARPET - BOLYU - SHIFT, 24 X 24, SHF57 COMMAND

    CARPET - BOLYU - CUSTOM, 24 X 24, HV84-1

    01PT

    CP01

    02PT

    CP02

    PAINT - SHERWIN WILLIAMS TBD03PT

    PAINT - SHERWIN WILLIAMS TBD04PT

    PAINT - SHERWIN WILLIAMS TBD, EGGSHELL AT WALLS05PT

    PAINT - SHERWIN WILLIAMS IDEA PAINT TBD EGGSHELL ATWALLS, SEMI GLOSS AT TRIMS06

    PT

    WALL PANEL - CARNEGIE XOREL - HAVANA 6249 01WP

    01PL PLASTIC LAMINATE (PANTRY): ABET LAMINATI, 1385 GROOVE,

    RAILROADED

    01LB FULL HEIGHT LAMINATE BACKSPLASH (PANTRY): SPEC. TBD

    LUXURY VINYL TILE - KARNDEAN FLOORING - SYLVA WP417(PANTRY, ELEVATOR LOBBY AND RECEPTION)

    LV01

    VINYL TILE - ARMSTRONG STRIATIONS -12X24 T308 WARM GREYPOLISHED (STORAGE ROOMS AND IT)

    VT01

    RB01

    RB02

    RB03

    PAINT - BENJAMIN MOORE MURESCO - WHITE. FINISH: FLAT ALLSHEETROCK CEILINGS, PIPING, SOFFITS AND WINDOW POCKETS.07

    PT

    PAINT AT ELEVATOR DOORS AND FRAMES - BENJAMIN MOORE,ROLLED APPLICATION, COLOR TBD.08

    PT

    FLOOR TILE: DALTILE D014: 2" X 2" DESERT GRAY - UNGLAZEDMATTE. GROUT COLOR: 1/8" LATICRETE SPECTRALOCK PRO SILVERSHADOW (CORE BATHROOMS)

    WALL TILE: DALTILE D014: DESERT GRAY: 2" X 2" - WITH COVEBASE. GLAZED. (CORE BATHROOMS) (FULL HEIGHT). GROUT: 1/8"LATICRETE SPECTRALOCK PRO SILVER SHADOW

    BORDER TILE: BORDER TILE (2 COURSES LOCATED 34 COURSESABOVE TILED FLOOR): DALTILE D182: 2" X 2" SUEDE GRAY - GLAZED.GROUT: 1/8" LATICRETE SPECTRALOCK PRO SILVER SHADOW

    STONE TOP - BIANCO ROMANO POLISHED GRANITE,3/4" THICK (VANITY FINISH @ CORE BATHROOMS).

    LEGEND/NOTESCORE BATHROOM FINISHES

    01SS SOLID SURFACE COUNTERTOP (PANTRY): ICE STONE, COLOR:

    SNOW FLURRY

    RUBBER WALL BASE - JOHNSONITE 4" RUBBER BASE. COLOR TBD.PROVIDE STRAIGHT AT CARPET AND COVE AT VCT/TILE.

    RUBBER WALL BASE - JOHNSONITE 4" RUBBER BASE. COLOR TBD.PROVIDE STRAIGHT AT CARPET AND COVE AT VCT/TILE.

    RUBBER WALL BASE - JOHNSONITE 4" RUBBER BASE. COLOR TBD.PROVIDE STRAIGHT AT CARPET AND COVE AT VCT/TILE.

    ADD/ALTERNATE: IN LIEU OF REGULAR 4" BASE, PROVIDEJOHNSONITE MILLWORK REVEAL MW-4" BASE- COLOR: TBD.MITERED AT CORNERS- INSTALLED PER MANUFACTURERRECOMMENDATIONS (ALL AREAS U.O.N)

    LEGEND/NOTES CONT.FINISH PLAN

    INDICATES FLOORING TRANSITION:- AT CARPET/VCT OR CARPET/EXISTING BASE BUILDING, F&IRUBBER REDUCER STRIP, COLOR TO MATCH CARPET- AT TILE TO CARPET OR TILE/EXISTING BASE BUILDING, F&I ST.ST. SCHLUTER TRANSITION STRIP OR RENO RAMP AS REQ'D.

    02PL PLASTIC LAMINATE (STORAGE 3121 & ADJUSTABLE SHELVING):

    TBD

  • OFFICE3117

    WELLNESS RM3103

    CLOSET3104

    OFFICE3106

    OFFICE3107

    OFFICE3108

    OFFICE3109

    OFFICE3110

    3109

    OFFICE3111

    TEAM ROOM3113

    OPEN AREA3112

    OFFICE3114

    BREAK OUT3115

    STORAGE3102

    RECEPTION3101

    OPEN AREA3134

    MEN'S RM3132A

    AV/IT3132

    ADA BATHROOM3130

    PANTRY3120

    STORAGE3121

    OFFICE3123

    OFFICE3124

    OFFICE3125

    OFFICE3126

    CONF. ROOM3127

    OFFICE3128

    STORAGE3129

    OPEN AREA3131

    OFFICE3105

    OFFICE3119

    OFFICE3118

    CONF. ROOM3116

    STORAGE3103A

    CO

    PIER

    2

    6

    26

    WBK

    W

    B

    K

    OPEN STORAGE3133

    WOMEN'S RM3131A

    OFFICE3122

    N

    FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    FURNITURE PLAN - 31ST FLOORSCALE: 1/8" = 1'-0"

    1

    A-006.00

    FURNITURE PLAN31ST FLOOR

    6

    FURNITURE IS FOR REFERENCE PURPOSES. G.C. RESPONSIBLE FOR ALL FINALELECTRICAL CONNECTIONS FOR FURNITURE SYSTEMS, TABLE BOXES, ETC. COOR'DBLOCKING REQUIREMENTS FOR FURNITURE RELATED ITEMS WITH VENDOR PRIORTO INSTALLATION. COOR'D ELECTRICAL LOCATIONS WITH FURNITURE VENDORPRIOR TO INSTALLATION.

    LEGEND/NOTESFURNITURE PLAN

  • AS

    NO

    TED

    334"

    BASE AS PERFINISH PLAN

    EXISTING SLAB PROVIDE SEALANTAT BOTH SIDESOF PARTITION

    6"

    EXISTING SLABBRACE TO SLAB

    AS REQ'D.

    SUSPENDED CEILING

    1 LAYER5/8" THK. GYP. BD.

    (TYPE X)

    2-1/2" METALSTUDS PLACED

    16" O.C.

    NOTE: ALL METAL STUDSTO BE 25 GA. U.O.N.

    AS

    NO

    TED

    334"

    BASE AS PERFINISH PLAN

    EXISTING SLAB PROVIDE SEALANTAT BOTH SIDESOF PARTITION

    EXISTING SLABBRACE TO SLAB

    AS REQ'D.

    SUSPENDED CEILING

    1 LAYER5/8" THK. GYP. BD.

    (TYPE X)2-1/2" METAL

    STUDS PLACED16" O.C.

    PROVIDE SEALANTAT BOTH SIDESOF PARTITION

    PROVIDE SEALANTAT BOTH SIDESOF PARTITION

    2" SAFB INSULATION

    VARIES

    CHECK CLEARANCES

    SUSPENDED CEILING SUSPENDED CEILING

    VA

    RIES

    EXISTING SLABBRACE TO SLAB

    AS REQ'D.

    5/8" THK.CEMENT BD.

    2-1/2" METALSTUDS PLACED

    16" O.C.

    2-1/2" METALSTUDS PLACED

    16" O.C.

    PROVIDE SEALANTAT BOTH SIDESOF PARTITION

    PROVIDE SEALANTAT BOTH SIDESOF PARTITION

    EXISTING SLAB

    PROVIDE SEALANTAT BOTH SIDESOF PARTITION

    PROVIDE SEALANTAT BOTH SIDESOF PARTITION

    5/8" THK. CEMENT BD.

    WATERPROOFMEMBRANE

    FLOOR FIN. VARIESWATERPROOF

    MEMBRANE

    FLOOR FIN. VARIES

    WATERPROOFMEMBRANE

    BASE AS PERFINISH PLAN

    EXISTING SLAB

    EXISTING SLAB

    SUSPENDED CEILING

    1 LAYER5/8" THK. GREEN BD.

    FLOOR FIN. VARIES

    PROVIDE SEALANT

    VA

    RIES

    FINISHED FLOOR

    3 34"

    EXISTING SLAB

    AS REQUIREDBRACE TO SLAB

    5/8" THICKGYPSUM BOARD

    GC TO PROVIDELEVEL FLOOR PERMANUFACTURERSRECOMMENDEDTOLERANCES FORINSTALL OF GLASSWALL SYSTEM.

    OFFICE SIDECORRIDOR SIDE

    5/8" THK.GYPSUM BOARD

    TAG WALLSYSTEM BY GC.

    CONTINUOUSBLOCKING ASREQ'D.

    6"

    SUSPENDED CEILING

    C

    FINISHED CEILING

    L

    F&I REMOVABLE POLEON ESCUTCHEONSAT ADA HEIGHT

    EQ. EQ.

    4'-0

    "

    5'-6

    "

    A-008E

    GYP. BOARD FASCIA

    H.M. FRAME

    2'-2" MIN.

    1'-0"

    STAINED 3/4" BIRCH

    POLISHED CHROME POLEON ESCUTCHEON

    4'-0

    "

    5'-6

    "

    DOORSEE SCHEDULE

    ADDITIONAL SET OF CLEATSFOR SHELF & ESCUTCHEON FOR

    POLE TO BE INSTALLED @HANDICAP HT. FOR FUTURE USE

    INSTALL DIVIDER PANEL INCLOSETS EXCEEDING 4'-0"

    WIDTH. F&I (1) POLE AT ADAAPPROVED HT. ON (1) SIDE

    OF DIVIDER. OTHERS AT 5'-6".

    FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    PARTITION TYPE 1

    PARTITION TYPESSCALE: 1-1/2" = 1'-0"

    PARTITION TYPE 2 PARTITION TYPE 3 PARTITION TYPE 4 PARTITION TYPE 5

    1. IN WALLS THAT HAVE SIGNAGE, SHELVING, COUNTERS, CHAIR RAILS,CABINETS, CROWN MOULDINGS, BASE MOULDING, LIGHT FIXTURES,HEAVY MIRRORS, ETC... PROVIDE WOOD BLOCKING.

    2. ALL WALLS GREATER THAN 12'-6" TO BE 20 GAUGE WITHCONTINUOUS METAL STRAPPING EVERY 4'-0" HORIZONTALLY. GC TONOTIFY ARCHITECT PRIOR TO INSTALLATION AND LAYOUT APPROVALFOR EXACT STUD SIZE

    3. ALL METAL STUDS TO BE 25 GAUGE, U.O.N.

    NOTES

    1

    A-007.00

    PARTITION TYPES

    TAG WALL GLASS PARTITION

    CLOSET ELEVATIONSCALE: 1" = 1'-0"

    CLOSET SECTIONSCALE: 1" = 1'-0"

  • 3'-2

    "

    3'-2

    "

    A B C D

    7'-1

    0"

    8'-0

    "

    8'-0

    "

    TAGWALLSYSTEM SLIDINGGLASS DOOR

    12" TEMPERED

    GLASS

    CRL TOP AND BOTTOM PATCHFITTINGS

    TAGWALLSTANDARDLADDER PULL

    3'-2

    "

    4'-0

    " EQ

    .4'

    -0" E

    Q.

    12" TEMPERED

    GLASS

    4" TOP AND BOTTOMST. STL. RAILS

    E

    4'-0

    " EQ

    .4'

    -0" E

    Q.

    CHOP FLOOR AS REQUIREDFOR FLOOR CLOSERS, TYP

    DEADBOLTS &DUSTPROOF STRIKES

    3'-2

    "

    F&I LOUVERPAINTED TO MATCHDOOR

    7'-1

    0"

    F

    FLOOR TILE

    SLAB

    CARPET PER PLANS

    EXISTING WATERPROOFING

    PER FINISH PLAN

    MUD SET

    1/4" MAX

    BUILDING STANDARD WHITECARRERA MARBLE SADDLE

    FLASH PATCH AND FEATHERFLOOR AS REQUIRED

    FOR LEVEL TRANSITION

    DOOR JAMB

    DOOR TYPESNTS

    FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    NOTES

    1

    DOOR SCHEDULEDOOR FRAME HARD

    WARESET

    SADDLEREMARKSFL. NO. TYPE SIZE MAT. JAMB HEAD MAT. TYPE MAT.

    FLO

    OR

    31

    1 - EXISTING - - - - - - - SAND, BONDO & REPAINT

    2 - EXISTING - - - - - - - SAND, BONDO & REPAINT

    3 - EXISTING - - - - 1 - - SAND, BONDO & REPAINT

    4 A 3'-0" x 7'-10" HM A B HM 2 - - -

    5 B (2) 2'-6" x 8'-0" HM - - - 3 - - FRAMELESS CLOSET DOORS

    6 C TAGWALL DOOR - - - - - - - -

    7 D 3'-0" x 8'-0" GL - - - 4 - - -

    8 C TAGWALL DOOR - - - - - - - -

    9 C TAGWALL DOOR - - - - - - - -

    10 C TAGWALL DOOR - - - - - - - -

    11 C TAGWALL DOOR - - - - - - - -

    12 C TAGWALL DOOR - - - - - - - -

    13 C TAGWALL DOOR - - - - - - - -

    14 C TAGWALL DOOR - - - - - - - -

    15 D 3'-0" x 8'-0" GL - - - 4 - - -

    16 D 3'-0" x 8'-0" GL - - - 4 - - -

    17 C TAGWALL DOOR - - - - - - - -

    18 C TAGWALL DOOR - - - - - - - -

    19 D 3'-0" x 8'-0" GL - - - - - - -

    20 C TAGWALL DOOR - - - - - - - -

    21 D 3'-0" x 8'-0" GL - - - - - - -

    22 - 3'-0" x 8'-0" - C C HM - - - F & I HM FRAME FOR TRIMMED OPENING

    23 C TAGWALL DOOR - - - - - - - -

    24 C TAGWALL DOOR - - - - - - - -

    25 C TAGWALL DOOR - - - - - - - -

    26 C TAGWALL DOOR - - - - - - - -

    27 C TAGWALL DOOR - - - - - - - -

    28 F 3'-0" x 7'-10" HM A B HM - - - -

    29 D 3'-0" x 8'-0" GL - - - - - - -

    30 C TAGWALL DOOR - - - - - - - -

    31 A 3'-0" x 7'-10" HM A B HM 2 - - -

    32 - EXISTING - - - - - - - SAND, BONDO, & REPAINT

    33 A 3'-0" x 7'-10" HM A B HM 2 - - -

    34 - EXISTING - - - - - - - SAND, BONDO, & REPAINT

    35 E (2) 3'-0" x 7'-10" GL - - - 5 - - -

    36 - EXISTING - - - - - E MBL MEN'S RESTROOM DOOR: SAND, BONDO, & PAINT

    37 - EXISTING - - - - - - - MEN'S VESTIBULE DOOR: SAND, BOND, & PAINT

    38 - EXISTING - - - - - E MBL WOMEN'S RESTROOM DOOR: SAND, BONDO, & PAINT

    39 - EXISTING - - - - - - - WOMEN'S VESTIBULE DOOR: SAND, BONDO, & PAINT-

    40 - EXISTING - - - - - E MBL SAND, BOND, & REPAINT

    HARDWARE SCHEDULE

    A-008.00

    DOOR & HARDWARE SCHEDULEFLOOR XX

    FRAME DETAILNTS

    KNOCK-DOWN

    12"

    VARIES

    VARIES

    A= 1-9/16" STD. FOR A 1-3/8" DOORA= 1-15/16" STD. FOR A 1-3/4" DOOR

    VARIESA

    DOOR

    5 8"

    2" M

    ATC

    HEX

    ISTIN

    G

    2" M

    ATC

    HEX

    ISTIN

    G

    BONDO AND FINISH ALL SEAMS AT DOOR

    2"(or 1.5"

    if specified)

    A= 1-9/16" STD. FOR A 1-3/8" DOORA= 1-15/16" STD. FOR A 1-3/4" DOOR

    2"

    1 2"1 2"

    A

    58"

    VA

    RIES

    DOOR

    VA

    RIES

    VA

    RIES

    CARPET

    REDUCER STRIP, COLOR: TBD

    VINYL TILE

    VINYL CARPET

    DOOR

    JAMB

    TRIMMED OPENINGNTS

    NTS

    FINISH & STYLE:1. ALL WOOD DOORS TO BE SOLID CORE WITH BIRCH VENEER STAINED TOMATCH EXISTING. PLAIN SLICED VENEER 15% OPENNESS.2. ALL HARDWARE FINISHES TO BE US26D AND/OR 626 U.O.N.3. ALL LEVERS TO BE SCHLAGE ATHENS SERIES U.O.N.4. ALL HOLLOW METAL DOOR FINISHES TO BE: PAINTED SEMIGLOSS TO MATCHWALL (IF WALL NOT PAINTED, PAINT PT-01 U.O.N.)

    NOTES:1. USE 3 HINGES PER LEAF FOR DOORS 7'-6" OR LESS. USE 4 HINGES PER LEAFFOR DOORS 7'-6" OR HIGHER.2. ALL RATED DOORS TO HAVE AUTOMATIC CLOSERS WITH "NO-HOLD OPEN."& WELDED FRAMES3. ALL HARDWARE SETS SHALL BE MTD. @ 3'-2"4. CONTRACTOR TO KEY PREMISES TO BUILDING MASTER SYSTEM. PROVIDEBITTING LIST UPON COMPLETION OF PROJECT KEYING. PROVIDE 2 KEYS PERLOCK. KEYS ARE TO BE LABELED BY ROOM/DOOR NUMBER. GC TOCOORDINATE MASTER KEYING REQUIREMENTS WITH BUILDING MANAGEMENTAND TENANT.5. ALL HM FRAMES TO BE KNOCK DOWN UON6. ALL WOOD DOORS TO BE SOLID CORE 1-3/4" UON7. ALL HOLLOW METAL DOORS TO TO BE SEAMLESS WITH ROLLED EDGES. ALLHOLLOW METAL FRAMES TO BE WELDED UNLESS OTHERWISE NOTED INSCHEDULE.8. GC TO PROVIDE ENTRY DOOR MASTER KEY, OFFICE DOOR MASTER KEY, ITDOOR MASTER KEY AND GRAND MASTER. ALL LOCKS TO BE KEYED TOBUILDING MASTER - COORD. W/ BUILDING AS REQ'D PRIOR TO ORDERING.9. ALL ASTRAGALS PAINTED TO MATCH DOOR10. ALL SIDELITES 18" OR LESS TO BE 3/8", ALL GLASS PANLES GREATER THAN 18"WIDE TO BE 12" CLEAR TEMPERED GLASS.11. G.C. TO VERIFY ALL THROAT SIZES AT EXISTING & SCHEDULED PARTITIONS12. ALL GLASS DOORS OR GLASS PANES WIDER THAN 20" SHALL HAVEDISTRACTION STRIPS (BY OTHERS) ACROSS FULL WIDTH AT 33" AND 66" A.F.F.DISTRACTION STRIPS TO BE 1-1/2" TALL ADHESIVE FILM BANDS, 3M ORAPPROVED EQUAL.

    DOOR BUCKNTS

    KNOCK-DOWN

    TYP. CARPET-LVTTRANSITION

    NTS

    TYP. CARPET-LVTTRANSITION

    ROCKWOOD RM 3300 (5'-0" LENGTH) - BRUSHED ST. ST.

    TOP & BOTTOM PIVOT

    PULLS

    1 PAIR

    SET

    # 4

    SET

    # 2

    SILENCERS

    HINGES

    LOCKSETFLOOR STOP

    SCHLAGE ATHENS D SERIES-STOREROOM FUNCTION

    GLYNN JOHNSON #GJ 64 3IVES #438

    2 PAIR

    11

    CHOP FLOOR AS REQUIRED

    STANLEY #CB191 5 KNUCKLE FULL MORTISE HINGESCONCEALED BEARING

    1 PAIR

    ALL KEYING TO BE ON GRANDMASTERKEY/ CORE- COORDINATE W/ PROPERTY MANAGEMENT

    DORMA #BTS SERIES (WITH CLOSER, 90 DEGREEHOLD OPEN)

    SET

    # 1

    SILENCERS

    HINGES

    LOCKSETFLOOR STOP

    KABA / SIMPLEX - 5021XSWL

    GLYNN JOHNSON #GJ 64 3IVES #438

    2 PAIR

    11

    STANLEY #CB191 5 KNUCKLE FULL MORTISE HINGESCONCEALED BEARING

    CLOSER 1 DORMA 8900 NO HOLD OPENDEADBOLT 1 SCHLAGE B571 W/ VACANCY INDICATOR

    DUMMY TRIMPIVOTS 2 PAIR

    2

    SET

    # 3

    OVERHEAD STOP 2SCHLAGE ATHENS D SERIES-DUMMY TRIMIVES

    MAGNETIC CATCH 2 IVES #327 SUPER MIGHT HEAVY DUTY MAGNET

    RIXON TOP & BOTTOM PIVOT HINGES

    CONCEALED

    CR LAURENCE TOP & BOTTOM PATCH FITTINGSPATCH FITTINGS 1 PAIR

    SET

    # 1

    CRL BOTTOM RAIL LOCKS WITH THUMBTURN ON INSIDE

    TOP & BOTTOM PIVOT 2 PAIR CHOP FLOOR AS REQUIREDDORMA #BTS SERIES (WITH CLOSER, 90 DEGREEHOLD OPEN)DYNALOCK 2280 SERIES SLIM LINE 1200 LLBS DOUBLEMAGLOCK AT TYPE B AND SINGLE AT TYPE C.COORDINATE WITH DOOR SWINGS AND SECURITYVENDOR OR LOCKNETICS M400 SERIES WITH BRUSHEDCHROME COVER

    ELECTRIC MAGLOCKSLIMLINE COORDINATE MAGLOCK WITH WEIGHT OFDOORS. INCLUDE CLASS 'E' TIE-IN

    1 PAIR

    ROCKWOOD RM 3300 (5'-0" LENGTH) - BRUSHED ST. ST.PULLS 2 PAIR

    TOP & BOTTOM RAILS CRL 4" TOP AND BOTTOM RAILS2 PAIR

    CR LAURENCE OVERHEAD ANGLE STOP 1

    CR LAURENCE OVERHEAD ANGLE STOP 1 PAIR

    BOTTOM LOCKS WITHDUSTRPOOF STRIKES

    1 PAIR

  • EQ.EQ.??????COORD. W/

    MANUF.SPECIFICATIONS

    ??????

    CO

    ORD

    INA

    TE W

    /M

    AN

    UFA

    CTU

    RER

    SPE

    ALIGN

    ??????

    30" MIN INOPEN POSITION

    ??????COORD. W/

    MANUF.SPECIFICATIONS

    ??????

    4"

    ??????

    ??????

    2 EQ. PANELS

    3'-0

    "2'

    -10"

    2'-0

    "

    ???????COORD. W/ MANUF.

    SPECIFICATIONS

    ??????

    ????????????

    ???????????2 EQ. PANELS

    ????????????2 EQ. PANELS

    ?????? ??????

    N

    FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    A-009.00

    PANTRY DETAILS

    PANTRY ELEVATIONSCALE: 1/2" = 1'-0"

    PANTRY SECTION SCALE: 1" = 1'-0"

    SCALE: 1" = 1'-0"SCALE: 1" = 1'-0"

    PANTRY SECTION PANTRY SECTION

    PANTRY SECTION SCALE: 1" = 1'-0"SCALE: 1" = 1'-0"

    PANTRY SECTION

  • 87

    6

    9

    2

    53

    8

    6

    A-010

    2

    4

    A-010

    6

    A-010

    6

    A-010

    4

    42"GFI

    42"GFI

    S

    4'-0

    "

    4" SIDE SPLASH

    A-011A

    COVE BASE (TYP).

    4" SIDE SPLASH

    S.S. URINALPARTITION

    TYP. ON VESTIBULEWALLS

    A-011A

    TYP. ON VESTIBULEWALLS

    5'-0

    3 4"

    5'-0

    3 4"

    2'-3

    1/2

    "

    1'-6

    "

    5'-0"

    5'-0

    3 4"

    4'-6"

    4'-2

    "

    4'-6"

    5'-0

    3 4"

    1'-0"

    2'-3

    1/2

    "

    1'-6

    "5'-0"

    2'-1

    0"

    14" MIRROR LAMINATED TO 14" PLYWOOD

    SUPPORTED ON WOOD CLEATS TO BEFULL WIDTH OF COUNTER. EXTEND FROM

    BACKSPLASH TO FINISHED CEILING.PROVIDE SILCONE ALONG ALL EDGES

    STONE TOP - BIANCO ROMANOPOLISHED GRANITE, 3/4" THICK

    STONE BACKSPLASH - BIANCO ROMANOPOLISHED GRANITE, 3/4" THICK

    2'-1"

    4"

    6"

    6"2'

    -4"

    8" 1'-2" 4"

    1'-0

    "

    4" SIDESPLASHAT WALLS ONLY

    34" PLAYWOOD FASTENED

    TO STUDS

    CAULK, GASKET, SECURESINK AS REQUIRED

    STEEL CHANNEL SUPPORT ATCOUNTERTOP. PROVIDEBLOCKING IN WALLS AS

    REQ'D

    N

    FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    A-010.00

    CORE BATHROOMELEVATIONS

    PLAN AT CORE BATHROOMSNTS

    WOMEN'S ROOM ELEVATIONNTS

    WOMEN'S ROOM ELEVATIONNTS

    WOMEN'S ROOM ELEVATION1/2" = 1'-0"

    WOMEN'S ROOM ELEVATION1/2" = 1'-0"

    MEN'S ROOM ELEVATION1/2" = 1'-0"

    MEN'S ROOM ELEVATION1/2" = 1'-0"

    MEN'S ROOM ELEVATION1/2" = 1'-0"

    MEN'S ROOM ELEVATION1/2" = 1'-0"

    SECTION AT COUNTERTOP1/2" = 1'-0"

    1

    2

    3

    4

    5

    6

    7

    9

    TOILET ACCESSORIES

    TOILET - FLOOR MTD

    URINAL

    LAVATORY

    SOAP DISPENSER

    GRAB BAR

    ANCHOR PLATE

    SANITARY NAPKIN DISPENSER

    TOWEL DISPENSER/DISPOSAL

    I.D. TYPE SPECIFICATION REMARKSSLOAN - WETS2020.1201-1.28 SOLIS

    BOBRICK B-822

    BOBRICK

    BOBRICK B-2800-25

    BOBRICK B-38032

    BOBRICK 256 SERIES

    SLOAN -WEUS-1005.1401-0.5 G2

    KOHLER - CAXTONUNDERCOUNTER -K-2210SLOAN EBF-85

    FLUSH OMETER:SLOAN #8111 - SATINCHROME

    SLOAN #8111

    FAUCET

    PROVIDE (1) PER SINK

    MOUNTED 2'-10" AFFCONCEALED MOUNT

    SECURE TO STUDS

    SURFACE MOUNTED

    SEMI RECESSEDMOUNTED @ 59 34" AFF(ADA)

    MEN'S BATH

    TOILET PARTITIONSROOM PARTITION

    S.S TOILETPARTITION

    S.S URINALPARTITION

    WOMAN'SBATH

    MFGKNICKERBOCKER'NEW YORKER'STAINLESS STEEL

    REMARKSFLOOR MTD.PROVIDE ADA COMPLIANTHARDWARE. SEE MFG INSTALLGUIDE FOR ELEV'S & DETAILS

    KNICKERBOCKERSTAINLESS STEEL

    STAINLESS STEEL #4 FINISH

    FLOOR MTD.PROVIDE ADA COMPLIANTHARDWARE. SEE MFG INSTALLGUIDE FOR ELEV'S & DETAILS

    10 BOBRICK - B-2888 SURFACE MOUNTED2'-3" TO TOP OFDISPENSER

    8 TOILET SEAT COVERDISPENSER

    BOBRICK B-221 SURFACE MOUNTED48" MAX AFF

    TOLIET PAPER DISPENSER

    F & I WATERPROOFING MEMBRANE AT FLOOR: LATICRETE#9235 INSTALL AS PER ANSIO A118.10 (TURN UP WALL 6")

    S.S TOILETPARTITION

    KNICKERBOCKER'NEW YORKER'STAINLESS STEEL

    CORE BATHROOM FINISHES

    PROVIDE (1) #160 COAT HOOK PER STALL

    FLOOR TILE: DALTILE D014: 2" X 2" DESERT GRAY - UNGLAZEDMATTE. GROUT COLOR: 1/8" LATICRETE SPECTRALOCK PRO SILVERSHADOW (CORE BATHROOMS)

    WALL TILE: DALTILE D014: DESERT GRAY: 2" X 2" - WITH COVEBASE. GLAZED. (CORE BATHROOMS) (FULL HEIGHT). GROUT: 1/8"LATICRETE SPECTRALOCK PRO SILVER SHADOW

    BORDER TILE: BORDER TILE (2 COURSES LOCATED 34 COURSESABOVE TILED FLOOR): DALTILE D182: 2" X 2" SUEDE GRAY - GLAZED.GROUT: 1/8" LATICRETE SPECTRALOCK PRO SILVER SHADOW

    STONE TOP - BIANCO ROMANO POLISHED GRANITE,3/4" THICK (VANITY FINISH @ CORE BATHROOMS).

  • 8'-2

    "

    8'-2

    "

    2'-1

    0"A

    DA

    CO

    UNTE

    R

    3'-0

    "2'

    -0"

    3'-0

    "

    3'-0

    "2'

    -0"

    3'-0

    "

    ????????????(12) EQ. SPACES

    ????????????

    3'-0

    "2'

    -0"

    3'-0

    "

    2'-8" 1'-0"

    HOLD

    (13) EQ. SPACES

    PLASTIC LAMINATEUPPER AND LOWERCABINETS

    PLASTIC LAMINATECOUNTERTOP AND 4" HIGHBACKSPLASH

    PLASTIC LAMINATEUPPER AND LOWERCABINETS

    PLASTIC LAMINATECOUNTERTOP AND 4" HIGHBACKSPLASH

    HAFELE PULLS, TYP. 1" FILLERPANELS, TYP.1" FILLER PANELS, TYP.

    2'-1"2'-8"

    1'-6"1'-6"

    (2) ADJUSTABLESHELVES PERCABINET, TYP.

    (2) ADJUSTABLESHELVES PERCABINET, TYP.

    4" H x 3" DTOE KICK,TYP.

    4" H X 3" DTOE KICK, TYP.

    8'-2

    "

    2'-1

    0"A

    DA

    CO

    UNTE

    R

    6'-0"

    (2) EQ. SPACES 2'-8"

    3'-0

    "2'

    -0"

    3'-0

    "

    ALI

    GN

    FINISHED ENDPANELS, TYP.

    PLASTIC LAMINATEUPPER AND LOWERCABINETS

    PLASTIC LAMINATECOUNTERTOP AND 4" HIGH

    BACKSPLASH

    CONTINUEBACKSPLASH OVER

    ADA COUNTERHEIGHT

    1" FILLER PANELS, TYP.

    4" H X 3" DTOE KICK, TYP.

    N

    FILE: CONDOCS.DWG

    SCALE: AS NOTED

    DWG NO.

    PROJ MGR. MR

    CHECKED BY OT

    DRAWN BY LL

    SEAL & SIGNATURE PROJ NO. 10295.00

    DRAWINGTITLE

    NEW YORK, NEW YORK

    3ST FLOOR

    750 THIRD AVENUE

    JOB TITLE SL GREEN REALTYCORPORATION

    NO. DATE ISSUE/REVISION BY

    - 11.20.15 ISSUE FOR BID OT

    A-011.00

    MILLWORK ELEVATIONS

    ELEVATIONSCALE: 1/2" = 1'-0"

    1ELEVATIONSCALE: 1/2" = 1'-0"

    2

    ELEVATIONSCALE: 1/2" = 1'-0"

    3

  • SLG-750 3rd Ave-31st Fl-Arch IFB_112015MEPS Combined384854M001-Layout1.pdf384854M101-Layout1.pdf384854M201-Layout1.pdf384854M501-Layout1.pdf384854M502-Layout1.pdf384854M503-Layout1.pdf384854M801-Layout1.pdf384854M802-Layout1.pdf384854M803-Layout1.pdf384854M901-Layout1.pdf384854E001-Layout1.pdf384854E002-Layout1.pdf384854E101-Layout1.pdf384854E201-Layout1.pdf384854E301-Layout1.pdf384854E501-Layout1.pdf384854E502-Layout1.pdf384854E503-Layout1.pdf384854E504-Layout1.pdf384854E601-Layout1.pdf384854E701-Layout1.pdf384854E801-Layout1.pdf384854E802-Layout1.pdf384854E803-Layout1.pdf384854EN001-Layout1.pdf384854EN002-Layout1.pdf384854FA101-36X24.pdf384854FA601-Layout1.pdf384854P001-Layout1.pdf384854P101-Layout1.pdf384854P801-Layout1.pdf384854SP001-Layout1.pdf384854SP101-Layout1.pdf384854SP501-Layout1.pdf384854SP601-Layout1.pdf384854SP801-Layout1.pdf384854SP901-Layout1.pdf