20 feet Containerized Solution

Specifications

CSCU 3024635

Version Date: August 2019

Sample

Page 2: 20 feet Containerized Solution Specifications CSCU 3024635

2

Legal Provisions No part of this User Manual (“Manual”) may be reproduced, or transmitted, in any form or by any means, without the prior written permission of Kilowatt Labs, Inc. (“Kilowatt” or the “Company”). Specifications in this Manual are subject to change without notice. While every attempt has been made to make the Manual accurate and up-to-date, users are cautioned that product improvements may cause the Company to make changes to specifications without advance notice. Users are encouraged to consult the Company or its Resellers before using the Manual. Neither the Company nor its Resellers shall be liable for any indirect, incidental, or consequential damages under any circumstances caused by reliance on the material presented, including, but not limited to, omissions, typographical errors, arithmetical errors or listing errors in the content material. The content of this manual shall not be modified without the written authorization of the Company. Trademarks All trademarks are recognized, even if not explicitly identified as such. Kilowatt Labs® is a registered trademark of the Company. Warning Selling and installation of this product is only through the Company’s Resellers who are

trained on installation, operation and maintenance of the Sirius modules.

Sample

Page 3: 20 feet Containerized Solution Specifications CSCU 3024635

3

Container Overview:

Sample

Page 4: 20 feet Containerized Solution Specifications CSCU 3024635

4

Electrical Drawing:

Mechanical Drawing:

Sample

Page 5: 20 feet Containerized Solution Specifications CSCU 3024635

5

Module Rack:

1. 30 Module Rack:

2. 20 Module Rack:

Sample

Page 6: 20 feet Containerized Solution Specifications CSCU 3024635

6

Container Description:

ITEM NAME DESCRIPTION MU

1 Energy Server 20kW Capacity, 380V-3P input 1 Set

2 Sirius Capacitor Module 1.36kWh, 2.4V 150 PCS

3 Monitoring Machine

LCD w/ Mouse and keyboard 1 PC

UPS (600VA) & Battery (465Wh) 1 Set

CPU 1 PC

4

DC Breaker ELCB 250, CNS 250 4P 1 PC

MAIN Distribution Panel

MCCB ABS104c, 125 Ah 1 PC

Switch SBN440, 4P 40 A 1 PC

Switch CEC441J, 4P 40 A 1 PC

MCB MCN116A, 1P 6kVA C-16A 1M 3 PCS

MCB MCN132A, 1P 6kVA C-32A 1M 3 PCS

Output DB Panel MCCB, ABS104c, 125 Ah 1 PC

Generator Panel MCCB, ABS104c, 125Ah 1 PC

5 Isolator Switch 1P, 35 A, 250V 1 PC

6 Fire Extinguisher Automatic Dry Power Fire

Extinguisher 2 PC

7 Camera DS-2CD1121-1 2 PC

8 Embedded NVR DS-7600 Series NVR 1 PC

9 Module Sensor PBAT 802 150 PCS

10 Sensor Combiner PBAT 600 3 PCS

11 Communication Gate Way

PBAT GATE 1 PC

12 Power Supply 24 V 1 PC

13 Protocol Converter Protocol Converter 1 PC

14 Motion Sensor 1 Set

Sample

Page 7: 20 feet Containerized Solution Specifications CSCU 3024635

7

Storage Bank Specifications:

CSCU 3024635

PERFORMANCE SPECIFICATIONS

Voltage (Nominal) 360 Vdc

Maximum Charge Voltage 405 Vdc

Discharge Cut-Off Voltage 325 Vdc

Total Energy 204600 Wh

Maximum Charge Rate 60 A

Maximum Discharge Rate 60 A

ENVIRONMENTAL SPECIFICATIONS

Cell Operating Temperature3 -30 OC to 80 OC

Operating Humidity Non-Condensing

SMART FEATURES

Monitoring Data Temperature, Total Voltage, individual

cell monitoring, Current and Energy

Remote control (optional) Via Sirius Remote Control

Communication and Connectivity Ethernet/RS 485

Alarm Audible alarm in the event of

Over/under-Voltage, Over-Current, Over Temperature

CENTAURI VIEW SOFTWARE

Module Monitoring Current, Voltage, Temperatures,

Graphs, Daily reports and data logging

System Monitoring

Instant Generator Solar Power, Daily Generated Solar Energy, Daily

Consumption Solar Energy, Total Generated Solar energy from the start,

Daily Consumption Energy

SAFETY PERFORMANCE

Over/under voltage Hardware protection, Module shut

down

Over Current Hardware protection, Module shut

down

Over temperature Hardware protection, Module shut

down

Additional Safety DC circuit breaker

COMPLIANCE8

INFORMATION

EN55032:2015, EN55024:2010, EN61000-4-2:2009, EN61000

EN61000:2008+A2:2010

PRECAUTIONS

Alarm In case of alarm, immediately rectify/attend to the cause of the alarm.

Physical Damage In case the Module is physically damaged due to any event, do not install and energize the Module under any circumstances and contact your Reseller.

Short Circuit Ensure precautions to prevent short-circuit under all circumstances.

Galvanic isolation When connecting to external devices ensure that galvanic isolation does not exceed 1000V.

15 Recessed box

16 Ethernet Switch 8 port-Ethernet Switch 1 PC

17 Sockets Standard Socket 2 Set

18 Lights Fluorescent Light Tube 3 PCS

19 Exit Light 2 PC

Sample

Page 8: 20 feet Containerized Solution Specifications CSCU 3024635

8

Charge/Discharge Current

Under no circumstances must the charge/discharge current exceed 60A.

Charging Voltage Under no circumstances must the charging voltage exceed 405 Vdc for more than 60 seconds.

Charge Cycle During charge cycle ensure never to exceed constant voltage of 405 Vdc and constant current of 60A.

1Self-discharge is the natural decay of the Module total voltage over time. Module self-discharge is 2% in Sleep Mode (switched off) and 9.6% in Switched-On Mode. 2The Module C-Rate refers to the rate at which a Module is charged or discharged. A 1C rate means that the current will charge or discharge the entire Module in 1 hour. 3The temperature range indicates the range in which the supercapacitor cells can operate. The performance of the cells may vary if they are continuously operated outside a temperature range of -10⁰C to 55⁰C, and/or at C-rates higher than the maximum charge/discharge rate specified in this spec sheet. The operating temperature range of the Module varies based on the application. If the Module is to be operated continuously outside a temperature range of -10oC to 55oC, and/or at C-rates higher than the maximum charge/discharge rate specified in the spec sheet, please consult Kilowatt Labs or its Reseller prior to deploying. 4Projected life of supercapacitor cells. Cycle life will vary if cycled more than 4 times a day. 5Additional terms and conditions, including a limited warranty, will apply at the time of purchase. 6Projected Calendar life of supercapacitor cells from the date of first operation. 7Shelf life is the life of the Module (in years) from the date it is manufactured to the time it is first operated. 8CE certification is completed for supercapacitor cells. Product dimensions are for reference only unless otherwise identified and may change without notice. For critical applications, please contact your Reseller.

Sample

Page 9: 20 feet Containerized Solution Specifications CSCU 3024635

9

1.Centauri Energy Server

Rated power 20 kW

Rated current 45 A

Output power factor 1

Rated input voltage 380 Vac ± 20%

Rated output voltage 380 Vac ± 1%

Battery voltage 360 Vdc

Operating mode AC and PV complementation

PV INPUT

Max. voltage (Voc) 750 Vdc

Optimum operating voltage (Vamp) 450 ~ 550 Vdc

Max. conversion efficiency ≥ 98%

Floating charge voltage (25℃) 414 Vdc ± 1%

Equalizing charge voltage (25℃) 428 Vdc ± 1%

MPPT Max. current 120 A

Max. PV power 2 * 25 KW

Number of PV input 2 + 1 (reserve)

MPPT modules 2 + 1 (reserve)

AC RECTIFIER

Input voltage range 380 V ± 20% three-phase

Rated frequency 50 Hz / 60 Hz ± 5 Hz (settable)

Power factor 0.8

Floating charge voltage (25℃) 410 V ± 1%

Equalizing charge voltage (25℃) 415 V ± 1%

Max. charging current 38 A

INVERTER

Inverter voltage 380 Vac three-phase + N+PE

Phase voltage 220 / 230 / 240 Vac (settable)

Sample

Page 10: 20 feet Containerized Solution Specifications CSCU 3024635

10

Output voltage precision ± 1%

Transient voltage range ± 5%

Transient recovery time 20 ms

Rated frequency 50 Hz / 60 Hz ± 1 Hz (settable)

Frequency tracking range 50 Hz / 60 Hz ± 3 Hz

Peak factor 3: 1

Waveform Sinusoidal

Waveform distortion ≤ 3% (linear load)

Voltage unbalance ± 3% (100% unbalanced load)

Overload

≥ 105% ~ 110% for 1 hr: ≥ 110% ~ 125% for 10 mins; ≥ 125% ~ 150% for 1 min; ≥ 150% shut down in 10 s;

≥ 200% shut down immediately;

Short circuit Current-limiting, shut down immediately until the user

start up

Max. efficiency ≥ 92%

BYPASS

Rated voltage 380 Vac three-phase + N+PE

Voltage range ± 20%

Rated frequency 50 Hz / 60 Hz ± 5 Hz

Max. current 57 A

TRANSFER TIME

Inverter– Bypass 0 ms

Bypass – Inverter 0 ms

COMMUNICATIONS

Remote control Energy server startup, shutdown, abnormal clearance,

EPO, battery self-test

Communication interface RS232, RS485, SNMP (optional)

Dry contacts output Bypass input abnormal, rectifier input abnormal, system

fault, system alarm, low battery, output overload, fan fault, generator ON / OFF

Load Handling Curve

OTHERS

Operating temperature 0℃ ~ 40℃

Max. relative humidity 90% (non-condensing)

Max. altitude 1000 m at rated power (derating 1% for each additional

100 m); Max. 4000 m

Sample

Page 11: 20 feet Containerized Solution Specifications CSCU 3024635

11

Noise level at 1 m ≤ 65 dB (varies with loads and temperature)

IP rating IP20

Dimensions (W × D × H) (mm) 600 × 700 × 1750

Packaged dimensions (W ×D × H) (mm) 690 × 790 × 1850

Weight (kg) 380

2. Sirius Module 1364Wh 2.4VDC:

Part No. 1364-2.4-B-0.53C-TM-SD-A-CS

PERFORMANCE SPECIFICATIONS

Voltage (Nominal) 2.4 Vdc

Maximum Charge Voltage 2.7 Vdc

Discharge Cut-Off Voltage 2.2 Vdc

Total Energy 1364 Wh

Maximum Charge Rate 300 A

Maximum Discharge Rate 300 A

Fuse Breaking Amps 800 A

ENVIRONMENTAL SPECIFICATIONS

Cell Operating Temperature3 -30 OC to 80 OC

Operating Humidity Non-Condensing

Module Casing Material Aluminum

Terminal Type F12

SMART FEATURES

Monitoring Data Temperature, Total Voltage, Current

and Energy Remote control (optional) Via Sirius Remote Control

Communication and Connectivity Ethernet

Alarm Audible alarm in the event of

Over/under-Voltage, Over-Current, Over Temperature

SIRIUSVEIW SOFTWARE

Module Monitoring Current, Voltage, SOC, Temperatures,

Total Energy delivered, Graphs

System Monitoring Modules Monitoring (connected in

parallel or series)

MODULE SERVICE LIFE

Projected Cycle Life4,5 1 million cycles

Projected Calendar Life5,6 45 years

Shelf Life7 10 years

Warehousing Can be stored at any SOC without

affecting cycle life

Sample

Page 12: 20 feet Containerized Solution Specifications CSCU 3024635

12

SAFETY PERFORMANCE

Over/under voltage Hardware protection, Module shut

down

Over Current Hardware protection, Module shut

down

Over temperature Hardware protection, Module shut

down

Additional Safety Fuse

COMPLIANCE8

INFORMATION

EN55032:2015, EN55024:2010, EN61000-4-2:2009, EN61000

EN61000:2008+A2:2010

PRECAUTIONS

Alarm In case of alarm, immediately rectify/attend to the cause of the alarm.

Physical Damage In case the Module is physically damaged due to any event, do not install and energize the Module under any circumstances and contact your Reseller.

Short Circuit Ensure precautions to prevent short-circuit under all circumstances.

Galvanic isolation When connecting to external devices ensure that galvanic isolation does not exceed 1000V.

Charge/Discharge Current

Under no circumstances must the charge/discharge current exceed 300A.

Charging Voltage Under no circumstances must the charging voltage exceed 2.7 Vdc for more than 60 seconds.

Charge Cycle During charge cycle ensure never to exceed constant voltage of 2.7 Vdc and constant current of 300A.

1Self-discharge is the natural decay of the Module total voltage over time. Module self-discharge is 2% in Sleep Mode (switched off) and 9.6% in Switched-On Mode. 2The Module C-Rate refers to the rate at which a Module is charged or discharged. A 1C rate means that the current will charge or discharge the entire Module in 1 hour. 3The temperature range indicates the range in which the supercapacitor cells can operate. The performance of the cells may vary if they are continuously operated outside a temperature range of -10⁰C to 55⁰C, and/or at C-rates higher than the maximum charge/discharge rate specified in this spec sheet. The operating temperature range of the Module varies based on the application. If the Module is to be operated continuously outside a temperature range of -10oC to 55oC, and/or at C-rates higher than the maximum charge/discharge rate specified in the spec sheet, please consult Kilowatt Labs or its Reseller prior to deploying. 4Projected life of supercapacitor cells. Cycle life will vary if cycled more than 4 times a day. 5Additional terms and conditions, including a limited warranty, will apply at the time of purchase. 6Projected Calendar life of supercapacitor cells from the date of first operation. 7Shelf life is the life of the Module (in years) from the date it is manufactured to the time it is first operated. 8CE certification is completed for supercapacitor cells. Product dimensions are for reference only unless otherwise identified and may change without notice. For critical applications, please contact your Reseller.

Sample

Page 13: 20 feet Containerized Solution Specifications CSCU 3024635

13

3. Centauri View Monitoring:

3.1 Auxiliary Supply UPS with 465Wh12V Module:

Auxiliary Supply UPS Model 600VA

Input mode Inverter mode BLU mode

Rated values

Input voltage 220VAC

Input frequency

50Hz

Number of input phases

Single phase

Input voltage range 120~300VAC 145~285VAC

Input frequency range 38~70Hz

Output voltage Mains mode

BLU mode : 198V~242V / INV mode : 175V~255V

ESD mode 220V±5% (resistive load)

Output frequency

Mains mode Synchronous with grid power

ESD mode 50HZ±1Hz

Waveform Mains mode Tracking mains power ESD mode Sine wave

Output power factor 0.8 Output power 600VA/480W

Protection

Over temperature protection

When heatsink temperature exceeds 90ºC: Shut down charger in mains mode, and shut down inverter in ESD

mode Over voltage protection

Shut down output when the voltage is above 285+/-10V

Under voltage protection

Shut down output when the voltage is below 120+/-10V

LCD Monitor

Monitoring CPU

Auxiliary Supply UPS

DC Circuit Breaker

Sample

Page 14: 20 feet Containerized Solution Specifications CSCU 3024635

14

Short circuit protection

Shut down output

Audible noise ≤55dB(1m) Insulation resistance > 2MΩ(500Vdc)

Dielectric strength 2820Vdc

Overload capacity (precision: +/-10%)

1. Mains mode: 1) 100% load, long term operation. 2) 100~120% shut down output after 3min, re-startup automatically after 30s, after re-startup 3 times, if the overload still exists, then enter failure mode and the unit needs to be started up manually. 3) 120~130% shut down output after 30s, re-startup automatically after 30s, after re-startup 3 times, if the overload still exists, then enter failure mode and the unit needs to be started up manually. 4) ≥130% shut down output immediately, re-startup automatically after 30s, after re-startup 3 times, if the overload still exists, then enter failure mode and the unit needs to be started up manually. 2. ESD mode: 1) 100% load, long term operation. 2) 100~110% shut down output after 10s, re-startup automatically after 30s (with soft startup), after re-startup 3 times, if the overload still exists, then enter failure mode and the unit needs to be started up manually. 3) ≥110% shut down output immediately, re-startup automatically after 30s (with soft startup), after re-startup 3 times, if the overload still exists, then enter failure mode and the unit needs to be started up manually.

Rated ESD voltage

12V

Charging voltage 13.8V±0.3V

Charging current 10A/20A optional

Extension port 1M Cable

Red: to ESD positive Black: to ESD negative

Mechanical Specifications

Unit Dimensions

272*285*165 mm

Package Dimensions

380*375*255 mm

Net Weight (KG)

11.4

Gross Weight (KG)

12.7

Environmental Specifications

Operating Temperature

0°C-40°C

Storage Temperature

-25°C-55°C

Relative Humidity

20%-95% (no condensation)

Elevation <1000m, for elevation above 1000m, de-rate with

reference to GB7260.3-2003 4.1.1

Sample

Page 15: 20 feet Containerized Solution Specifications CSCU 3024635

15

Cooling Mode Air cooling

Sirius Module 465Wh12V:

Part No. 465-12-B-1.7C-CS

PERFORMANCE SPECIFICATIONS

Voltage (Nominal) 12 Vdc

Maximum Charge Voltage 13.5 Vdc

Discharge Cut-Off Voltage 11 Vdc

Total Energy 465 Wh

Maximum Charge Rate 70 A

Maximum Discharge Rate 70 A

ENVIRONMENTAL SPECIFICATIONS

Cell Operating Temperature3 -30 OC to 80 OC

Operating Humidity Non-Condensing

Module Casing Material Aluminum

Terminal Type Anderson Connectors

MODULE SERVICE LIFE

Projected Cycle Life4,5 1 million cycles

Projected Calendar Life5,6 45 years

Shelf Life7 10 years

Warehousing Can be stored at any SOC without

affecting cycle life

COMPLIANCE8

INFORMATION

EN55032:2015, EN55024:2010, EN61000-4-2:2009, EN61000

EN61000:2008+A2:2010

PRECAUTIONS

Physical Damage In case the Module is physically damaged due to any event, do not install and energize the Module under any circumstances and contact your Reseller.

Short Circuit Ensure precautions to prevent short-circuit under all circumstances.

Galvanic isolation When connecting to external devices ensure that galvanic isolation does not exceed 1000V.

Charge/Discharge Current

Under no circumstances must the charge/discharge current exceed 70A.

Charging Voltage Under no circumstances must the charging voltage exceed 13.5 Vdc for more than 60 seconds.

Charge Cycle During charge cycle ensure never to exceed constant voltage of 13.5 Vdc and constant current of 70 A.

3.2 Monitoring CPU:

PERFORMANCE

Processor Up to 7th generation Intel® Core™ i7

Operating System Windows 10 Pro

Memory Up to 32 GB 2 DDR4 UDIMM 2400MHz

Storage

• 2280 M.2 PCIe SSD (up to 256 GB)

• 3.5" HDD (up to 1 TB) • 2.5" SSD (up to 128 GB)

• Slim ODD

Graphics • Intel Integrated HD Graphics 630

• Intel Integrated HD Graphics 610

Sample

Page 16: 20 feet Containerized Solution Specifications CSCU 3024635

16

• Optional NVIDIA® GT730 2G GDDR3

• Optional NVIDIA® GT730 1G GDDR5

PSU 180W/210W PSU

SECURITY Security • Smart USB Protection • TPM 2.0

CONNECTIVITY

Front I/O Ports • 4 x USB 3.0

• Card reader (optional)

• 2 x audio

Rear I/O Ports

• 2 x USB 3.0

• 2 x USB 2.0

• VGA

• HDMI

• DP

• 1 x serial, 1 x optional serial • Optional parallel port

• LAN

• 2 x audio

Wireless Connection 1×1802.1 1b/g/n/ac

CERTIFICATIONS Green Certifications

• Energy Star 6.1

• GREENGUARD®

• EPEAT® Gold

• RoHS/WEEE/REACH

DESIGN Dimensions (W x D x H) 92.5 mm × 290.9 mm × 343.5 mm / 3.64" x 11.45" x 13.52"

SOFTWARE Preloaded Software • Lenovo App Explorer

• Lenovo Companion 3.0

• Microsoft Office 2016 (Trial)

3.3 LCD Monitor:

PANNEL

Size 17" (43.3cm)

Type TN

Color Gamut 72% NTSC

Color Depth (Number of Colors) 16.7M

Aspect Ratio 5: 4

Pixel Pitch(mm) 0.264 x 0.264

Resolution 1280 x 1024

Brightness 250cd/m2

Contrast Ratio (Type) 5000000: 1(DFC), 1,000:1(Native)

Response Time 5ms (On/Off)

Viewing Angle 170°/160° (CR≥10)

Surface Treatment Non glare

PHYSICAL FEATURES

Set (with Stand, W x D x H, mm) 370 x 95 x 315

Set (without Stand, W x D x H, mm) 370 x 62 x 315

Box (W x D x H, mm) 429 x 159 x 377

Sample

Page 17: 20 feet Containerized Solution Specifications CSCU 3024635

17

Wall Mount VESA Compatible (75mmx75mm)

Weight (kg, with Stand) 3.3

Weight (kg, without Stand) 2.9

Box(kg) 4.5

Set (with Stand, W x D x H, mm) 370 x 95 x 315

SPECIAL FEATURES

USB Yes (1)

General Function

sRGB, DDC/CI, Intelligent Auto (Auto Resolution), Plug & Play

STAND

Base Detachable -

Tilt (Angle) 15° (forwards) ~ 68°(backwards)

Swivel (Angle) -

Pivot -

Base Detachable -

CONNECTIVITY

Signal Input D-Sub

Others USB (Touch Screen connection)

ENERGY RATINGS

Comparative Energy Consumption 60kWh/Year

Star Rating 5 Stars

Active Standby 0.2W

GENERAL

Accessories Power Cord, D-sub, USB Cable

Regulation Compliance TUV-Type, FCC-B, CE, C-Tick, CB, MEPS VESA Mount,

Windows7

4. Circuit Breakers:

MODEL POLES RATED

AMPERAGE QUANTITY

DC Breaker CB ELCB 4P 250 A 1PC

MCCB ABS104c - - 1 PC

Sample

Page 18: 20 feet Containerized Solution Specifications CSCU 3024635

18

Main distribution Panel

Switch SBN440 4P 40A 1 PC

Switch CEC441J 4P 40A 1 PC

MCB MCV116A 1P 16A 3 PC

MCB MCV132A 1P 32A 3 PC

Output DB Panel

MCCB ABS104c - - 1 PC

Generator Panel

MCCB ABS104c - - 1 PC

5. Isolator Switch:

Application Current rating 35A

Standard BSEN 60947-3

Number of Poles 1

Function O-I

Rated Operational Current 20 35 63

Rated operational Voltage 250 V

Rated Insulation Voltage 250 V

Rated Impulse-withstand Voltage (Uimp) 2.5 KV

Frequency 50 / 60 Hz

Utilization Category AC23A

Rated making capacity 10Ie

Rated Breaking Capacity 8Ie

Rated short - time withstand current 15 Ie for 1s

Pollution Degree 3

Degree of Protection IP56

Tightening Torque 1

Terminal Capacity Flexible Type mm² 1.5-2.5

Terminal Capacity rigid Type mm² 1.5-2.5

Contact Opening Type Normal Gap

Switch Actuating Method Manual Operation

Method of mounting Surface

Type of Terminal Screw Type

Type of Enclosure Enclosed

Material Engg. Plastic

Quality Management System ISO 9001: 2008

Sample

Page 19: 20 feet Containerized Solution Specifications CSCU 3024635

19

6. FE36 FIRE EXTINGUISHER:

7. IR Fixed Dome Network Camera (DS-2CD1121-I)

SPECIFICATION MODEL FE36

Capacity (kg) 6

Fire rating 21a

144b

Diameter (mm) 275

Breadth (mm) n/a

Height (mm) 210

Discharge range (m) 8

Discharge time (sec) 7.9 9.11 18-20

Empty weight (kg) 6

Total weight (kg) 15

Packing final volume (m3) 0.03

Cylinder wall thickness (mm) 2

Hose automatic type

Class of fire a,b,c &e

Extinguishing agent hfc-236fa

Operating pressure (bar) 15

Testing pressure (bar) -

Nozzle -

Valve -

Bottom base -

Rising pipe plastic /aluminum

Temperature range -20°c to +60°c

Cylinder material cold rolled steel

Painting super finished electro plastic polyester

epoxy resin

Printing clear attractive silk screen printing

Mounting ceiling mounted

Sample

Page 20: 20 feet Containerized Solution Specifications CSCU 3024635

20

Key Features:

1/2.8″ progressive scan CMOS Up to 2.0 megapixel 2.8mm/4mm/6mm fixed focal lens Up to 30 m IR range Dual stream Digital WDR (Wide Dynamic Range) 3D DNR (Digital Noise Reduction) PoE (Power over Ethernet) IP67, IK10 Mobile monitoring via Hik-Conn

Sensor CMOS Image Sensor

Horizontal Resolution 2MP

Signal system PAL/NTSC

Effective pixels 1920 x 1080

S/N Ratio >62dB

Lens 2.8mm

Minimum illumination Color: 0.01 Lux @ (F1.2, AGC ON), 0 Lux

with IR

IR LED EXIR

IR LED Range 30 μέτρα

Shutter Speed 1/3 s to 1/100, 000 s, support slow

shutter

Video output 1RJ-45

Power supply 12 VDC ± 25%, PoE (802.3af)

Power Consumption Max. 5 W/6.5 W (PoE)

Working temperature -30 °C to 60 °C

Dimensions 69.1 mm × 66 mm × 172.7 mm

Weight 500g

8. Embedded NVR (DS-7600 Series NVR):

Sample

Page 21: 20 feet Containerized Solution Specifications CSCU 3024635

21

Key Features

- 4 Channel PoE IP Camera Ports - Support for up to 8MP recording and playback - Support for 4k video output - H.264/H.264+/H.265 video codecs - 1 SATA interface to connect 1 x 10TB hard drive - Support for VCA detection alarm - Compatible with third-party IP cameras - Supports Hikvision's ANPR solutions

Number of Channels 4

Number of PoE Ports 4

Incoming Bandwidth 40 Mbps

Outgoing Bandwidth 80 Mbps

Number of Bays 1

ANPR Ready Yes

HDD Capacity Supplied 0GB

Maximum Memory Capacity 10TB

9. Module Sensors:

10. Sensor Combiner:

Sample

Page 22: 20 feet Containerized Solution Specifications CSCU 3024635

22

11. Communication Gate Way:

12. Power Supply(24V):

13. Protocol Converter:

Sample

Page 23: 20 feet Containerized Solution Specifications CSCU 3024635

23

14. Motion Sensor:

15. Recessed box: 1 Recessed Box with 63A Industrial socket and Plug(5-pin) and 6 number of 50mm dia holes for cable entry.

16. Double Sockets:

Sample

Page 24: 20 feet Containerized Solution Specifications CSCU 3024635

24

2 double sockets of 13A

17. Double LED light:

4’ double LED light fittings (2nos), emergency exit light(2nos)

18. Exit Light (ROBUS R8MLED-01):

Power Consumption (W) 2.6

Batteries (NiCad) 3.6v 1.5Ah

Discharge duration >3hrs after 24 hr charge

Light output in emergency (lm) 60

Ambient Temperature Range (0C) 0 ≤ Ta ≤ +25

IP Rating 65

Weight (Kg) 0.57