Upload
rodger-moody
View
220
Download
0
Tags:
Embed Size (px)
Citation preview
2008 Code Drills
(C) Copyright 2008 Ted "Smitty" Smith1
Smitty’s Speed Drills
Instructions
(C) Copyright 2008 Ted "Smitty" Smith2
Click on the slide show ICON in the lower left hand corner of this screen to start the slide show.
A question will appear and stay on the screen for 2 minutes. The question will then be replaced with the correct answer and code reference. This process will repeat until you reach a slide with a stop sign. You can then click on the slides and the questions and answers will be repeated without the timer so you can look up the answers or take notes.
Do not worry about writing down the answers until after the timed portion of the program.
Concentrate on finding the answer and improving your speed using the NEC. This drill is focused on changes to the 2008 NEC.
(C) Copyright 2008 Ted "Smitty" Smith3
Where raceways are installed in wet locations above grade, the interior of these raceways shall be considered to be a __________location.
(C) Copyright 2008 Ted "Smitty" Smith4
Wet location 300.9
(C) Copyright 2008 Ted "Smitty" Smith
5
Where 1” liquid tight flexible metal conduit is used to provide necessary flexibility after installation, the LFMC must be support within ________ inches of the termination.
(C) Copyright 2008 Ted "Smitty" Smith6
36 inches 350.30(A) Exception 2 (1)
(C) Copyright 2008 Ted "Smitty" Smith7
In a class I, division 2 area, flexible metal conduit and liquidtight flexible metal conduit shall not be used as the sole ground fault current path.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith8
True 501.30(B)
(C) Copyright 2008 Ted "Smitty" Smith9
The required disconnecting means for a hot tub must be located within sight from the hot tub and shall be located at least _______ feet away from the waters edge, measured from the waters edge, horizontally along the shortest path required to reach the disconnect.
(C) Copyright 2008 Ted "Smitty" Smith10
5 feet 680.12
(C) Copyright 2008 Ted "Smitty" Smith11
Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit shall be identified by ________ or ___________ and system at all terminations, connection and splice points.
(C) Copyright 2008 Ted "Smitty" Smith12
Phase or line 210.5(C)
(C) Copyright 2008 Ted "Smitty" Smith13
No circuit shall be described in a manner that depends on ____________ conditions of occupancy in a panelboard circuit directory.
(C) Copyright 2008 Ted "Smitty" Smith14
Transient 408.4
(C) Copyright 2008 Ted "Smitty" Smith15
A raceway type wiring method installed in exposed or concealed locations under metal corrugated sheet roof decking, shall be installed and supported so the nearest outside surface of the raceway is at least _______ inches from the nearest surface of the roof decking.
(C) Copyright 2008 Ted "Smitty" Smith16
1 ½ inches 300.4(E)
(C) Copyright 2008 Ted "Smitty" Smith17
AFCI protection of a branch circuit in a dwelling unit living room can be accomplished with an AFCI device installed in the first outlet box of the circuit if the homerun wiring is done with a type AC cable and a metal outlet box is used and the system is grounded in accordance with 250.118.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith18
True 210.12 Exception 1
(C) Copyright 2008 Ted "Smitty" Smith19
Special purpose and dedicated receptacles used for specific purposes only, such as garage door opener power shall not be required to be GFCI protected in a dwelling unit.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith20
False 210.8(A) The exception that allowed this practice in
the past has been removed.
(C) Copyright 2008 Ted "Smitty" Smith21
Flexible metal conduit is not permitted in wet locations unless the conductors are approved for the specific conditions and the installation is such that liquid is not likely to enter raceways or enclosures to which the conduit is connected.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith22
False 348.12(1) New wording now prohibits use of FMC in all wet locations without conditions.
(C) Copyright 2008 Ted "Smitty" Smith23
In a dwelling unit, a switched receptacle used to meet the requirements of a wall switch controlled lighting source shall not be considered a receptacle for meeting the requirements of having a receptacle within 6 feet of any unbroken wall space.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith24
True 210.52 New wording now prohibits using switched receptacles for meeting spacing requirements of receptacles in dwelling units. Note: A duplex receptacle is two receptacles so a duplex that is half switched can still be used to meet the spacing requirements.
(C) Copyright 2008 Ted "Smitty" Smith25
A junction box installed in a fountain overflow basin is expected to be completely submerged for short periods of time. Which of the following NEMA enclosures will need to be used in this application?
NEMA 3RNEMA 12XNEMA 6NEMA 11
(C) Copyright 2008 Ted "Smitty" Smith26
NEMA 6 110.20
(C) Copyright 2008 Ted "Smitty" Smith27
Electrically controlled drinking fountains installed in other than dwelling units shall be AFCI and GFCI protected.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith28
False GFCI protected only. 422.52
(C) Copyright 2008 Ted "Smitty" Smith29
A double ended florescent fixture with a ballast that can be serviced in place installed in a dwelling unit shall have a means of disconnect installed in the fixture or external to the fixture.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith30
False 410.130(G) Required for non-dwelling units only
(C) Copyright 2008 Ted "Smitty" Smith31
All non-locking 15- and 20-ampere, 125- and 250-volt receptacles installed in damp locations shall be listed ________________ type.
(C) Copyright 2008 Ted "Smitty" Smith32
Weather resistant 406.8
End of Drill
(C) Copyright 2008 Ted "Smitty" Smith33
This is the end of the timed portion of the drill.
You can now click on each slide and take your time reviewing the questions and answers.
(C) Copyright 2008 Ted "Smitty" Smith34
Where raceways are installed in wet locations above grade, the interior of these raceways shall be considered to be a __________location.
(C) Copyright 2008 Ted "Smitty" Smith35
Wet location 300.9
(C) Copyright 2008 Ted "Smitty" Smith
36
Where 1” liquid tight flexible metal conduit is used to provide necessary flexibility after installation, the LFMC must be support within ________ inches of the termination.
(C) Copyright 2008 Ted "Smitty" Smith37
36 inches 350.30(A) Exception 2 (1)
(C) Copyright 2008 Ted "Smitty" Smith38
In a class I, division 2 area, flexible metal conduit and liquidtight flexible metal conduit shall not be used as the sole ground fault current path.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith39
True 501.30(B)
(C) Copyright 2008 Ted "Smitty" Smith40
The required disconnecting means for a hot tub must be located within sight from the hot tub and shall be located at least _______ feet away from the waters edge, measured from the waters edge, horizontally along the shortest path required to reach the disconnect.
(C) Copyright 2008 Ted "Smitty" Smith41
5 feet 680.12
(C) Copyright 2008 Ted "Smitty" Smith42
Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit shall be identified by ________ or ___________ and system at all terminations, connection and splice points.
(C) Copyright 2008 Ted "Smitty" Smith43
Phase or line 210.5(C)
(C) Copyright 2008 Ted "Smitty" Smith44
No circuit shall be described in a manner that depends on ____________ conditions of occupancy in a panelboard circuit directory.
(C) Copyright 2008 Ted "Smitty" Smith45
Transient 408.4
(C) Copyright 2008 Ted "Smitty" Smith46
A raceway type wiring method installed in exposed or concealed locations under metal corrugated sheet roof decking, shall be installed and supported so the nearest outside surface of the raceway is at least _______ inches from the nearest surface of the roof decking.
(C) Copyright 2008 Ted "Smitty" Smith47
1 ½ inches 300.4(E)
(C) Copyright 2008 Ted "Smitty" Smith48
AFCI protection of a branch circuit in a dwelling unit living room can be accomplished with an AFCI device installed in the first outlet box of the circuit if the homerun wiring is done with a type AC cable and a metal outlet box is used and the system is grounded in accordance with 250.118.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith49
True 210.12 Exception 1
(C) Copyright 2008 Ted "Smitty" Smith50
Special purpose and dedicated receptacles used for specific purposes only, such as garage door opener power shall not be required to be GFCI protected in a dwelling unit.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith51
False 210.8(A) The exception that allowed this practice in
the past has been removed.
(C) Copyright 2008 Ted "Smitty" Smith52
Flexible metal conduit is not permitted in wet locations unless the conductors are approved for the specific conditions and the installation is such that liquid is not likely to enter raceways or enclosures to which the conduit is connected.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith53
False 348.12(1) New wording now prohibits use of FMC in all wet locations without conditions.
(C) Copyright 2008 Ted "Smitty" Smith54
In a dwelling unit, a switched receptacle used to meet the requirements of a wall switch controlled lighting source shall not be considered a receptacle for meeting the requirements of having a receptacle within 6 feet of any unbroken wall space.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith55
True 210.52 New wording now prohibits using switched receptacles for meeting spacing requirements of receptacles in dwelling units. Note: A duplex receptacle is two receptacles so a duplex that is half switched can still be used to meet the spacing requirements.
(C) Copyright 2008 Ted "Smitty" Smith56
A junction box installed in a fountain overflow basin is expected to be completely submerged for short periods of time. Which of the following NEMA enclosures will need to be used in this application?
NEMA 3RNEMA 12XNEMA 6NEMA 11
(C) Copyright 2008 Ted "Smitty" Smith57
NEMA 6 110.20
(C) Copyright 2008 Ted "Smitty" Smith58
Electrically controlled drinking fountains installed in other than dwelling units shall be AFCI and GFCI protected.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith59
False GFCI protected only. 422.52
(C) Copyright 2008 Ted "Smitty" Smith60
A double ended florescent fixture with a ballast that can be serviced in place installed in a dwelling unit shall have a means of disconnect installed in the fixture or external to the fixture.
TrueFalse
(C) Copyright 2008 Ted "Smitty" Smith61
False 410.130(G) Required for non-dwelling units only
(C) Copyright 2008 Ted "Smitty" Smith62
All non-locking 15- and 20-ampere, 125- and 250-volt receptacles installed in damp locations shall be listed ________________ type.
(C) Copyright 2008 Ted "Smitty" Smith63
Weather resistant 406.8