8
Thru-The-Wall THDC Series R-410A Condensing Units 3-4-5 Ton Series

3-4-5 Ton Series

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 3-4-5 Ton Series

Thru-The-Wall THDC Series R-410A Condensing Units 3-4-5 Ton Series

Page 2: 3-4-5 Ton Series

M-SE RI ES FRONT V IE W

M-Series Cabinet Available In 3 / 4 / 5 Ton

Model Wide High Deep EER BTU THDC-36MG Standard or LX 42 23 18-1/2 12.1 36,800 THDC-48MG Standard or LX 42 23 18-1/2 12.1 49,300 THDC-60MG Standard or LX 42 23 18-1/2 12.1 60,900

Electrical Voltage AWG Wire

Motor FLA MCA Max Fuse

THDC-36MG21 208-230/1/60 10 4.3 26.7 40 AMP THDC-36MG23 208/3/60 12 4.3 20.8 30 AMP THDC-36MG43 460/3/60 14 3.4 11.7 15 AMP THDC-48MG21 208-230/1/60 10 4.3 31.6 50 AMP THDC-48MG23 208/3/60 10 4.3 21.4 35 AMP THDC-48MG43 460/3/60 14 3.4 11.2 15 AMP THDC-60MG21 208-230/1/60 8 4.3 39.7 65 AMP THDC-60MG23 208/3/60 10 4.3 28.3 45 AMP

THDC-60MG43 460/3/60 14 3.4 15.5 25 AMP

STANDARD DESIGN • High Efficiency Scroll Compressor • Advanced Coil Design • Over Sized Direct Drive Blowers • Two Screw Blower Slide Out • CNC Punched Safety Screen / Powder Coat • Non Corrosive Hardware • Powder Coated Cabinet

Standard / LX Series

M-SE RI ES I NSI DE V IE W

CHE CK Y OUR STATE AND LOCAL BUILDI NG CODES BE FORE E VE RY I NS TALL ATI ON FOR E LE CTRI CAL RE QUI RE ME NTS.

Vibration Eliminators Included
Page 3: 3-4-5 Ton Series

LX SERIES ADDED FEATURES

• High / Low Pressure Switches

• Low Ambient Speed Control (Down To 20⁰)

• 4 lbs. Acoustical ArmaFlex Lined Cabinet

• Vibration Eliminators (Liquid & Suction)

• Heavy Duty Compressor Sound Blanket

Model Blower

Discharge Weight Compressor Liquid / Vapor

THDC-36MG Top 300 lbs. Scroll 1/2" / 3/4" THDC-48MG Top 300 lbs. Scroll 1/2" / 3/4" THDC-60MG Top 325 lbs. Scroll 1/2" / 7/8"

Electrical

Motor Amps

Motor HP

Compressor RLA

Compressor LRA

THDC-36MG21 4.3 1/2 17.9 112 THDC-36MG23 4.3 1/2 13.2 88 THDC-36MG43 3.4 1/2 6.0 44 THDC-48MG21 4.3 1/2 21.8 117 THDC-48MG23 4.3 1/2 13.7 83.1 THDC-48MG43 3.4 1/2 6.2 41 THDC-60MG21 4.3 1/2 30.1 158 THDC-60MG23 4.3 1/2 20.5 155 THDC-60MG43 3.4 1/2 9.6 75

*AeroSys THDC series units are compatible with most indoor air handlers. All specifications are subject to change without notice.

Standard / LX Series

M-SE RI ES LX I NSI DE V IE W

M-SE RI ES LOUVE R WITH ATTACHE D WALL SLEEV E

Page 4: 3-4-5 Ton Series

AeroSys Cross Reference List

Brand Model Wide High Type AeroSys

Model Dunham-Bush WCR-18/24/30 30 24 Condensing R Size Dunham-Bush VCR-24 30-5/8 29-1/2 Condensing R Size Dunham-Bush VCR-30 36-1/4 29-1/2 Condensing R Size

Dunkirk DRCU-018/024/030-4010 29-1/2 23 Condensing R Size First Company WCU-18/24/30-CB 29-1/2 23 Condensing R Size First Company WCX-18/24/30-CB 29-1/2 23 Condensing R Size

Hydro Therm / Space Pack WCR-18/24/30 30 24 Condensing R Size Johnson / Aire Ease CW-18/24-PR 30 23 Condensing R Size

Luxaire ECD-018/024/030-FNA 29 26 Condensing R Size National Comfort Products NCPB-018/024/030-4010 29-1/2 23 Condensing R Size National Comfort Products NCPC-018/024/030-4010 29-1/2 23 Condensing R Size National Comfort Products NCPC-418/424/230-4010 29-1/2 23 Condensing R Size National Comfort Products DSHP-018/024/030-4010 29-1/2 23 Heat Pump R Size

Westinghouse SLO-018-024-030 29-1/2 23 Condensing R Size York H1DC-018/024/030 29-1/2 23 Condensing R Size

Bryant/Day & Night/Payne 566C-014/018/024/030 26 28-5/8 Condensing S Size Bryant/Day & Night/Payne 566D-014/018/024/030 26 28-5/8 Condensing S Size Bryant/Day & Night/Payne 566E-014/018/024/030 26 28-5/8 Condensing S Size

Carrier 38GK-014/018/024/030 26 28-5/8 Condensing S Size Dunham-Bush VCR-24 30-5/8 29-1/2 Condensing S Size Dunham-Bush VCR-30 36-1/4 29-1/2 Condensing S Size

Dunkirk DRCU-018/024/030-1010 26 28-5/8 Condensing S Size Dunkirk DSHP-018/024/030-1019 26 28-5/8 Heat Pump S Size

First Company WCU-18/24/30-BB 25-3/4 28-5/8 Condensing S Size First Company WCX-18/24/30-BB 25-3/4 28-5/8 Condensing S Size

National Comfort Products NCPB-018/024/030-1010 26 28-5/8 Condensing S Size National Comfort Products NCPC-018/024/030-1010 26 28-5/8 Condensing S Size National Comfort Products NCPC-418/424/230-1010 26 28-5/8 Condensing S Size National Comfort Products DSHP-018/024/030-1010 26 28-5/8 Heat Pump S Size National Comfort Products NCHP-018-1019 26 28-5/8 Heat Pump S Size

Dunkirk DRCU-018/024/030-3010 23-3/4 32 Condensing T Size EMI VCH-018/024/030 22-3/8 32 Condensing T Size EMI VHH-018/024/030 22-3/8 32 Heat Pump T Size

Fedders CWC-018/24B7C 24 32 Condensing T Size Fedders CWC-028-B3C 24 32 Condensing T Size

First Company WCU-18/24/30-AB 24 32 Condensing T Size First Company WCX-18/24/30-AB 24 32 Condensing T Size

Goodman TWC-18/24/30-1 24 32 Condensing T Size Lennox HWS2A-21-2-FFC 24 34 Condensing T Size Lennox HSW4-24/26/31-FFC 29 34-1/2 Condensing T Size

Magic Chef CBW-18/24/30-PRI 24 32 Condensing T Size National Comfort Products NCPB-018/024/030-3010 23-3/4 32 Condensing T Size National Comfort Products NCPC-018/024/030-3010 23-3/4 32 Condensing T Size National Comfort Products NCPC-418/424/230-3010 23-3/4 32 Condensing T Size National Comfort Products DSHP-018/024/030-3010 23-3/4 32 Heat Pump T Size National Comfort Products NCHP-018/024/030-3019 23-3/4 32 Heat Pump T Size

Rheem CBW-18/24/28-B1Q 24 32 Condensing T Size Rheem CBW-18/24/28-B1C 24 32 Condensing T Size

929 Eldridge Drive Hagerstown, MD 21740 P; 301.620.0002 F: 301.620.0685 www.aerosysinc.com e-mail: [email protected]

Listing # 4008574 Complies with

UL 1995 Heating & Cooling

Equipment THDC-M R090214

Accepted For Use City of New York

Department of Buildings MEA 85-04-E

Page 5: 3-4-5 Ton Series
Page 6: 3-4-5 Ton Series
Page 7: 3-4-5 Ton Series

Bulletin 20-25 / April 2011

© Copyright 2011 Unico, Inc.

Electric Furnace

Features

x Galvanized insulated sheet metal cabinet enclosure x Can be converted to a duct heater x Magnetic de-energizing contactors for each element x Line level auto limit primary safety set @ 165ºF (74ºC) x Line level fuse link back-up safety x Fan interlock control, fan signal proving switch x Low air flow pressure switch x Circuit breakers on all units x Time delay sequencers for a gradual “stepped” power draw

(softer start) x Low voltage terminal strip (24 volt control) x Specially designed tight cabinet for small duct, high

velocity systems x Single Supply (all units) or dual supply (15 and 20kW)

General

The electric furnaces are designed to provide primary heating or auxiliary heating in a heat pump system. The model numbers, kW, and Unico System match-ups are shown in Table 1 below:

Table 1. Electric Furnaces

Model Number

Nominal kW Rating

Unico System Match-up

Min. Airflow, CFM (m3/s)

WON0202-B 2

All sizes

200 (0.10)

WON0502-B

WON0504-B 5 250 (0.12)

WON0752-B

WON0754-B 7.5 300 (0.14)

WON1002-B

WON1004-B 10

2430, 3642 and 4860

500 (0.24)

WON1502-B

WON1504-B 15 600 (0.28)

WON2002-B 20 3642 and 4860 800 (0.38)

Specifications

WON0502-BRevision level

2 - Single-Phase, 240V4- 3-Phase, 240V

Nominal kWRating(050=5kW)

All Unico System furnaces include a 10-inch (254-mm) round plenum adapter and a 9½ × 9½-inch (241 × 241-mm) square plenum adapter.

81037

CONFORMS TO UL STD 181CERTIFIED TO

CAN/ULC STD S110-M86

Other plenum adapter sizes are available separately. See the electric furnace installation instructions Bulletin 30-34 for a list of plenum adapter part numbers. See Figure 1 and Table 1 for the dimensions on all furnaces.

AIRFLOW

Ø 10.0 in

12.0 in

L

4.0 in

12.0 in

SIDE VIEWEND VIEW

TOP VIEW

10.0 in. Round plenum adapter shown attached (Supplied). Optional: 9.5 in. x 9.5 in.square plenum adapter (Supplied) is shipped loose. IL00002(Rev D).cvx

Figure 1. Electric Furnace dimensions.

The electric duct furnace is approved for attic, closet, or alcove installation, with “0” clearance to combustible materials. It can

Table 1. Electric Furnace dimensions & specifications

Model L

inch Rated Capacity

kW @240V Amperage@ 240V

WON0202-B

WON0502-B

13

13

2.0

4.8

8.30

20.00 WON0752-B 16 7.2 31.25 WON1002-B 16 9.6 40.00 WON1502-B 21 14.4 60.00 WON2002-B 24 19.2 80.00

WON0504-B 21 4.8 11.54

WON0754-B 21 7.2 18.04

WON1004-B 21 9.6 23.09

WON1504-B 21 14.4 34.64

Page 8: 3-4-5 Ton Series

Bulletin 20-25 — Page 2

© Copyright 2011 Unico, Inc.

be mounted either directly to the blower module or in the main duct. See Figure 2.

AIRFLOW

Electric HeaterMain Plenum Blower module

24.0"

Electric furnace application

Min.

AIRFLOW

Electric HeaterMain Plenum Blower module

24.0" 48.0"

Main Plenum

Duct heater application

Min. Min.

IL00491.cvx

Figure 2. Minimum duct clearance for electric heater applications.

Allow at least 25-inches (610-mm) in front of the control for servicing. For high humidity applications and other important information, see the electric furnace installation instructions Bulletin 30-34.

For limits and set points, see Table 2. For further specifications,

see Table 3. The 15 and 20 kW single phase furnaces contain two supply circuits. Supply wires can be run separately for each circuit, which is the default configuration. Using two supply circuits allows the use of smaller gauge wires. In some cases, it is necessary to use smaller gauge wire to comply with building codes that limit the maximum wire size that can be used for a single circuit. The required wire size for each electric furnace is shown in Table 3. The two circuits can also be joined together with a jumper bar. This is included with all dual circuit furnaces. The jumper bar allows the use of one pair of larger gauge wire, as opposed to two pairs of smaller gauge wire.

Note: Circuit breakers installed in this device are for short-circuit protection of internal wiring and to serve as a service disconnect. Circuit breakers installed within this device DO NOT provide over current protection of the supply wiring.

Specifications Maximum Outlet Temperature, oF (oC) 160 (70)

Maximum External Static Pressure, in. wc (Pa) 3 (745)

Auto Limit set point, oF (oC) 165 (74)

Fuse Link Setting, oF (oC) 250 (121)

Table 2. Limits and set points

Table 3. Furnace Specifications

Model Nom.

Capacity, kW

Rated Output*,

kW Power Supply

No. of Supply Circuits

No. Steps

Control Power (VA) Overall Dimensions, inch

WON0202-B 2 2.0 1 ph – 60 Hz – 240V 1 1 20.5 12 H x 16 W x 13 L WON0502-B 5 4.8 1 ph – 60 Hz – 240V 1 1 20.5 12 H x 16 W x 13 L WON0752-B 7.5 7.5 1 ph – 60 Hz – 240V 1 2 31.0 12 H x 16 W x 16 LWON1002-B 10 9.6 1 ph – 60 Hz – 240V 1 2 31.0 12 H x 16 W x 16 LWON1502-B 15 14.4 1 ph – 60 Hz – 240V 1 or 2 3 42.5 12 H x 16 W x 21 LWON2002-B 20 19.2 1 ph – 60 Hz – 240V 1 or 2 3 42.5 12 H x 16 W x 24 L

WON0504-B 5 4.8 3 ph – 60 Hz – 240V 1 1 20.5 12 H x 16 W x 21 LWON0754-B 7.5 7.5 3 ph – 60 Hz – 240V 1 1 20.5 12 H x 16 W x 21 LWON1004-B 10 10 3 ph – 60 Hz – 240V 1 1 20.5 12 H x 16 W x 21 LWON1504-B 15 15 3 ph – 60 Hz – 240V 1 2 31.0 12 H x 16 W x 21 L

Model Single Supply Dual Supply (1 Circuit/ 2 Circuit)

Heater Amps

Max. Fan Amps

Min. Circuit

Ampacity

Max. Overcurrent Protection †

Req’d Wire

Size ††

Heater Amps

Max. Fan

Amps

Min. Circuit

Ampacity

Max. Overcurrent Protection

Req’d Wire Size

WON0202-B 8.3 6.5 18.5 20 12 WON0502-B 20 6.5 33.1 35 10 WON0752-B 31.25 6.5 47.2 50 8 WON1002-B 40 6.5 58.1 60 6 WON1502-B 60 6.5 83.1 90 3 40/20 ---/6.5 50/33.1 50/35 6/8 WON2002-B 80 6.5 108.1 110 2 40/40 6.5/--- 58.1/50 60/50 6/6

WON0504-B 11.54 6.5 22.6 25 10 WON0754-B 18.04 6.5 30.7 35 8 WON1004-B 23.09 6.5 37 40 8 WON1504-B 34.6 6.5 51.4 60 6

*at rated voltage † FUSE or “HACR TYPE” Circuit Breaker †† Based on 75°C copper. For other wire types reference NEC