74
ACU+ Controller User Manual Version V1.0 Revision date November 16, 2009 BOM 31011743 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Copyright © 2009 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change without notice. Emerson Network Power Co., Ltd. Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China Homepage: www.emersonnetworkpower.com.cn E-mail: [email protected]

31011743_ACU+_User's Manual_V1.0

Embed Size (px)

DESCRIPTION

Emerson ACU user Manual.

Citation preview

  • ACU+ Controller User Manual Version V1.0 Revision date November 16, 2009 BOM 31011743

    Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

    Copyright 2009 by Emerson Network Power Co., Ltd.

    All rights reserved. The contents in this document are subject to change without notice.

    Emerson Network Power Co., Ltd.

    Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China

    Homepage: www.emersonnetworkpower.com.cn

    E-mail: [email protected]

  • The contents of this document are subject to revision without notice due to ongoing progress in methodology, design and manufacturing.

    Revision Log Version Date of Change Description of Change Changed by

    V1.0 2009-02-02 New document David Dai

    V1.1 2009-05-07 Added section 2.4 Using

    with EIB board David

  • Contents

    Chapter 1 Introduction ......................................................................................................................................................... 1

    1.1 Abbreviations ........................................................................................................................................................ 1 1.2 Overview ............................................................................................................................................................... 1 1.3 Look And Feel ....................................................................................................................................................... 1 1.4 Main Components ................................................................................................................................................. 2 1.5 Main Functions...................................................................................................................................................... 2

    1.5.1 Basic Functions ......................................................................................................................................... 2 1.5.2 Communication Functions ......................................................................................................................... 3 1.5.3 Alarm Functions ......................................................................................................................................... 3 1.5.4 Control Functions ...................................................................................................................................... 3

    1.6 Safety Instructions ................................................................................................................................................ 6

    Chapter 2 Installation .......................................................................................................................................................... 7

    2.1 Inspection Before Installation ................................................................................................................................ 7 2.2 Environment .......................................................................................................................................................... 7 2.3 ACU+ Installation In DC Power System ................................................................................................................ 7 2.4 Using With EIB Board ........................................................................................................................................... 8

    Chapter 3 LCD Operation .................................................................................................................................................... 9

    3.1 ACU+ Panel .......................................................................................................................................................... 9 3.2 First Screen ........................................................................................................................................................ 10 3.3 Default Main Screen ........................................................................................................................................... 10 3.4 Overall Menu Structure ....................................................................................................................................... 11 3.5 Main Menu .......................................................................................................................................................... 11 3.6 Status .................................................................................................................................................................. 12 3.7 Manual ................................................................................................................................................................ 14 3.8 Settings ............................................................................................................................................................... 15

    3.8.1 Alarm Setting ........................................................................................................................................... 16 3.8.2 Power System Setting ............................................................................................................................. 20 3.8.3 Rectifier Setting ....................................................................................................................................... 22 3.8.4 Battery Setting ......................................................................................................................................... 22 3.8.5 Parameter Settings Of DC Distri .............................................................................................................. 24 3.8.6 Parameter Setting Of LVD ....................................................................................................................... 24 3.8.7 AC Parameter Settings ............................................................................................................................ 24 3.8.8 Communication Parameter Settings ........................................................................................................ 25 3.8.9 Controller Parameter Settings ................................................................................................................. 25

    3.9 Energy Saving Setting ........................................................................................................................................ 25 3.10 Quick Setting .................................................................................................................................................... 25

  • Chapter 4 Access ACU+ Through Web ............................................................................................................................. 26

    4.1 Overview Of Web Function ................................................................................................................................. 26 4.2 Login ................................................................................................................................................................... 26 4.3 Homepage Introduction ....................................................................................................................................... 28 4.4 Device Explore .................................................................................................................................................... 28

    4.4.1 Data Browse, Control And Parameter Setting Of Rectifier ....................................................................... 29 4.4.2 Data Browse, Control And Parameter Setting Of Battery ........................................................................ 32

    4.5 Alarms ................................................................................................................................................................. 34 4.6 Maintenance ....................................................................................................................................................... 36 4.7 Configurations ..................................................................................................................................................... 43 4.8 Query .................................................................................................................................................................. 48

    Chapter 5 Access ACU+ Through NMS ............................................................................................................................ 51

    5.1 NMS supported By SNMP Agent ........................................................................................................................ 51 5.2 MIB Installation ................................................................................................................................................... 51 5.3 Access ACU+ Through NMS .............................................................................................................................. 52

    5.3.1 Apply Administrative Authority ................................................................................................................. 53 5.4 ESR Configure .................................................................................................................................................... 53

    Chapter 6 Parameter Setting Guidance ............................................................................................................................ 54

    6.1 Battery Management Parameters ....................................................................................................................... 54 6.1.1 Basic Parameters .................................................................................................................................... 54 6.1.2 Charging Parameters .............................................................................................................................. 54 6.1.3 Battery Test Parameters .......................................................................................................................... 55 6.1.4 Temperature Compensation Parameters................................................................................................. 55 6.1.5 Capacity Predicting Parameters .............................................................................................................. 56 6.1.6 Parameters Of Low Voltage Disconnection ............................................................................................. 56

    6.2 Energy Management Parameters ....................................................................................................................... 57 6.2.1 System Energy Saving Parameters ......................................................................................................... 57

    6.3 Power Split Parameters ...................................................................................................................................... 57

    Chapter 7 Application Case ............................................................................................................................................... 58

    7.1 Connecting New Device ...................................................................................................................................... 58 7.2 Connect New Battery .......................................................................................................................................... 58 7.3 Turn Off Audible Alarm Sound ............................................................................................................................ 59 7.4 Shut Down LCD Key-Pressing Sound ................................................................................................................. 59 7.5 Change Alarm Level / Alarm Relay ..................................................................................................................... 59 7.6 Enable DHCP Function ....................................................................................................................................... 60 7.7 Download Configuration Files Through USB ...................................................................................................... 60 7.8 AC Parameter Setting ......................................................................................................................................... 60

  • Appendix 1 List Of Abbreviations ...................................................................................................................................... 61

    Appendix 2 Introduction To EB Boards ............................................................................................................................. 62

    1. Introduction To IB1 Board ..................................................................................................................................... 62 2. Introduction To IB2 ................................................................................................................................................ 62 3. Introduction To EIB Board ..................................................................................................................................... 62 4. Input / Output Signals Of IB1 Board ...................................................................................................................... 63

    4.1 User I/O Signals ......................................................................................................................................... 63 4.2 JTAG Interface ........................................................................................................................................... 63

    5. Input / Output Signals Of IB2 Board ...................................................................................................................... 64 5.1 User I/O Signals Of IB2 Board .................................................................................................................... 64 5.2 Temperature Sensor Interface .................................................................................................................... 65

    6. Input / Output Signals Of EIB Board ..................................................................................................................... 66 6.1 User Interface ............................................................................................................................................. 66 6.2 Temperature Sensor Interface .................................................................................................................... 67 6.3 JTAG INTERFACE ..................................................................................................................................... 67

  • Chapter 1 Introduction 1

    ACU+ Controller User Manual

    Chapter 1 Introduction

    1.1 Abbreviations

    There are many abbreviations used in this user guide in reference to different terms as well as units of measure. A comprehensive list of these abbreviations can be found at the end of this document.

    1.2 Overview

    ACU+ is an easy-to-configure controller with powerful functions. It can control all kinds of GBB rectifiers, LC and SM modules. It can also control a DC power system locally and remotely. In addition, it has a friendly man-machine interface and management and alarm functions. The following figure shows the typical application of ACU+:

    Figure 1-1 Application of ACU+

    1.3 Look And Feel

    198.5

    40.8

    84.6

    40.8

    198.5

    84.8

    84.6

    1U X 2U 2U X 2U

    Figure 1-2 Look and Feel of ACU+

    The look and feel of ACU+ is shown in Figure 1-2. This unit has following two specifications:

    z 1U 2U z 2U 2U

  • 2 Chapter 1 Introduction

    ACU+ Controller User Manual

    1.4 Main Components

    Basic components

    z Mother board: Has various kinds of interfaces such as RS232, RS485, USB, Ethernet and CAN z OB2Connects to system I/Os z LCD panelAn MMI provides a local operation interface

    LCD panel

    A friendly local operation interface that supports the display of 7 languages (English, Chinese, French, Spanish, Portuguese, Italian and Swedish). The ACU+ unit delivered to the customer supports two language, one is English and the other is the customers local language.

    IB2

    Used to connect users I/Os

    EIB

    It is an extended I/O board that connects additional I/O signals.

    Interfaces on ACU+ module

    1) Ethernet Port

    The Ethernet port of ACU+ is used to connect ACU+ to internet. User can access ACU+ remotely in Web mode or Telnet mode through this port.

    2) RS232 (for HLMS)

    ACU+ has a RS232 serial port that talks to HLMS. User can access ACU+ remotely by using HLMS through this port.

    3) USB

    Used to upgrade application software

    4) RS485

    The ACU+ acquires data from SM modules (SM IO, SM BAT and SM AC) through this RS485 port.

    1.5 Main Functions

    1.5.1 Basic Functions

    z Data Acquisition: the controller can acquire and analyze the real time data from Rectifiers, Converters, Inverters, SM-DUs, Large DU, SM-Modules, OB2, IB2/IB1(IB1 and IB2 cannot be connected to ACU+ at the same time) and EIB.

    z Manual Control: the controller can forward the control command from HLMSWeb user or LUI to rectifiers, SM DUs, OB2, IB2 and EIB.

    z Automation Control: the controller can automatically control DC Power system thru rectifiers, SM DUs, OB2, IB2 and EIB.

    z Alarm Callout: when some critical alarm present, ACU+ can dial to HLMS via modem so that HLMS gets the alarm information as soon as possible. This function also depends on related HLMS.

    z Data Local Storage: the controller can provide a local storage to save real time data and alarms/events as history

    z Program Update: the controller can have possibility to update the application locally and remotely z Battery Management: the controller can provide function for battery management, such as current limitation,

    boost charge, battery test, and low voltage disconnection

    z Power Split: The ACU+ provides the function for power split. The power system with the ACU+ can act as a slave system to share load (split output) with an existing master system that needs extension. The ACU+ does not need to communicate with the master system control unit.

    z Alarm Management: the controller can provide function of active alarm list and alarm history

  • Chapter 1 Introduction 3

    ACU+ Controller User Manual

    z Rectifier Redundancy: the controller can provide function for rectifier redundancy z Man Machine Interface: the controller provides a local user interface with a 128 * 128 dot matrix LCD or 128 * 64

    dot matrix LCD, 4 buttons and 3 LEDs. The controller shall also provide a local console interface and a Web based interface

    1.5.2 Communication Functions

    The ACU+ can communicate with MC (Main Computer) or other devices through its 10M/100M Ethernet port. It also provides the alarm dry contacts through IB1/IB2/EIB.

    Communication through 10M/100M Ethernet port

    Communication cable shall be shielded cable.

    Communication through RS232

    RS232 communication is generally used for point-to-point communication. The communication distance shall be less than 15 meters. If ACU+ communicates through RS232, just connect ACU+ RS232 port to the RS232 port of MC.

    Communication through MODEM

    When ACU+ communicates through MODEM, it uses PSTN to realize long-distance monitoring. Power supply cables and communication cables shall be prepared for the communication through MODEM. MODEM communication mode accords with EEM Protocol.

    Dry contacts output

    The ACU+ can connect IB or EIB board, and can provide up to 13 dry contact outputs. Every dry-contact output has NC (normally closed) and NO (normally-open) contacts. Every dry-contact output shall be configured before the alarm event occurs, so that different dry-contact output can trigger different alarms. Once the alarm event occurs, the dry-contact will close or open to generate the alarm.

    If the user has other intelligent equipment to be monitored by ACU+, the user can connect the dry contacts to the interface of the intelligent equipment, and control the intelligent equipment through these dry contacts.

    1.5.3 Alarm Functions

    The alarm events are classified into different alarm categories. Different alarm categories have different visual/audible alarm and alarm-call back activities, as shown in Table 1-1.

    Table 1-1 Alarm categories

    Alarm Category Red LED Yellow LED

    Alarm Buzzer

    Alarm Call-back

    Remark

    Critical Alarm ON ON Yes Call-back function enabled Major Alarm ON ON Yes Call-back function enabled Observation Alarm ON OFF No No Alarm OFF OFF OFF No

    The audible alarm can be silenced if the user presses any key on ACU+. The audible alarm will also be silenced if the fault that triggers the alarm is cleared. The alarm LED is OFF if all the faults that trigger the alarm are cleared.

    1.5.4 Control Functions

    Rectifier control

    The rectifier can be switched on/off by ACU+. The rectifier parameters such as its current limitation point, output voltage and HVSD point can also be set by using ACU+.

    Battery management

    With battery management function, ACU+ can manage the batteries from SCU and SM-BAT, includes

    z Battery test z Boost charge z Temperature compensation

  • 4 Chapter 1 Introduction

    ACU+ Controller User Manual

    z Battery log(maximum 10 logs, maximum 18 strings per log) z Current limitation z LVD(Low-voltage disconnection)

    Battery compensation: ACU+ lowers the system voltage when the battery temperature increases and raise the system voltage when the battery temperature decreases. The system voltage follows the characteristics in the drawing below.

    -5C Nom 40C

    Max

    Max

    T

    UFactor(mV/C)

    NomU

    Figure 1-3 The Principle of Battery Compensation

    Boost charge: When one of the batteries charge current exceed predefined value, that means maybe the batteries need to be recharged faster, the ACU+ can raise the system voltage for the batteries to be recharged faster. The boost charge function can also be used to equalize the difference between the different battery blocks/cells.

    Battery Test: The purpose of a Battery Test is to check the condition of the battery. During a battery test the ACU+ controls the rectifiers by voltage or current and let the batteries take entire or part load. The ACU+ monitors the batteries and save the result in a battery test log. The battery test has three modes, short time test (requires two battery shunts), time test and stable current test. Battery tests can be started either manually or automatically at scheduled times for regular test of battery status. For manual battery tests as well as for cyclic battery tests, the following parameters must be set: End voltage, Test time and Battery capacity discharge limit. Battery test result is shown as follows:

    Figure 1-4 The Principle of Battery Test

    Battery temperature supervision: The battery temperature can be supervised by means of a temperature sensor mounted on one battery cell. Alarms are provided in two steps in case of high temperature. There is also an alarm at low battery temperature.

    Energy management

    Energy management is an advanced function, which can save money for customer, includes

    (1) Energy saving

    z To lower the energy consumption during high tariff z To make the power consumption rate lower than the given limit

  • Chapter 1 Introduction 5

    ACU+ Controller User Manual

    Energy Saving

    Con

    trol

    Input Output

    Current TimeReal power consumption

    External Digital Outputs ControlFlag of Different Time Rates

    Max Allowed Power Consumption

    Different Time Ratesand Max PowerSchedule

    AlarmsBattery Charge Prohibited Alarm

    Over Maximum Power Limit Alarm

    Figure 1-5 Energy saving

    (2) Rectifier redundancy

    z Switch ON/OFF the redundant rectifiers according to maximum and minimum redundancy percent z Rectifier cycling is to make the total work time of the all rectifiers at the average level

    RectifierRedundency

    Con

    trol

    Input Output

    Actual Rectifier LoadUnder Voltage Alarm

    Rectifier Failure Alarm

    Rectifiers Switch On/Offcommand

    Qty of Switch-on rectifiers

    Rectifier Redundancy EnabledMin RedundancyMax RedundancySwitch off delay

    Cycle PeriodCycle Activation Time

    Alarms

    Figure 1-6 Rectifier redundancy

    Diesel management

    The Diesel Management function includes Diesel Test. The Diesel Test supports following functions when SM AC is connected.

    z Planned diesel test z Manual diesel test z Record diesel test result

    Power split

    Power split is an advanced function.

    z Works with an un-known power plan system that acts as a master system z Acts as a slave system to share load(split output) for the master system, without communication with master

  • 6 Chapter 1 Introduction

    ACU+ Controller User Manual

    z Action based on Nominal Voltage, Boost Charge Voltage parameters and other digital signals of battery mgmt state of the master system

    z Default mode is as a master system PLC logic function

    PLC logic is an advanced function. (1) Needs to be regionalized/customized according to customer purpose

    (2) Can combine the equipment analog signal, parameters and alarm to control equipment and replays

    (3) The logical components supported are

    z NOT z OR z AND z XOR z > z < z Delay

    Main switch operation

    Main switch control is an optional function, with this function, ACU+ can automatically turn off a motor operated main switch of AC power supply without manual intervention.

    z Depends on an SM IO module to get the statuses of switch and to control the switch z Will effectively increase the availability of the supplied power

    Management via SM-IO

    The ACU+ can control and supervise different objects like switches, fans, cooling equipment, fire and burglar alarms via the SM-IO unit. See documents for the SM-IO unit.

    1.6 Safety Instructions

    To comply with the published safety standards, the following must be observed when using this built in control unit of ACU+:

    The built in control unit is intended for use as a component part of other equipment. When installing the power supply and marking input and output connections, the relevant safety standards e.g. UL 60950-1; IEC 60950-1/VDE 0805; EN 60950-1; CAN/CSA-22.2NO. 60950-1-03 must be complied with, especially the requirements for creepage distances, clearances and distance through insulation between primary wiring and earth or secondary (SELV) wiring.

    The module should be powered from a source which provides reinforced or double insulation and does not exceed 60Vdc and all signal inputs shall within SELV limits.

    The module is not intended to be repaired by service personnel in case of failure or component defect, failure unit should be sent back to the manufacturer for repair.

    The maximum ambient temperature around the control unit must not exceed 65C. No operator access areas require the use of a tool with ambient temperature up to 50C. Over 50C up to 65C ambient, front panel must be located at Restricted Access Location and hot surface caution symbol (60417-1-IEC-5041) should be marked in end system after installed in end system.

    The built-in control unit has no in-line fuse. For safe operation, an external slow acting 2A/250V fuse must be employed as input line fuse before installation.

    In case of this equipment installed in Restricted Access Location according to standard IEC60950-1: 2001,reasons for the restriction, precaution, and accessibility to the Restricted Access Location must be provided in safety instruction when installed in the end system.

  • Chapter 2 Installation 7

    ACU+ Controller User Manual

    Chapter 2 Installation

    2.1 Inspection Before Installation

    After receiving ACU+, check the package and contact local office of Emerson Network Power for any damage.

    2.2 Environment

    ACU+ Normal Operation Temperature: -10C to +65C

    LCD Operation Temperature: -10C to +50C

    ACU+ installation location shall be away from water, combustible gas, chemical gas, and corrosive gas and liquid.

    2.3 ACU+ Installation In DC Power System

    ACU+ has a connector on its rear panel. The installation process is described below with 1U 2U ACU+ as an example:

    Handle is opened

    Handle is closed

    Figure 2-1 Latch Mechanism of ACU+

    The ACU+ has a latch, when the handle is opened, the latch is retracted, and when the handle is closed, the latch is popped out. Installation process:

    1) Open the handle of the ACU+, and the latch is retracted into the ACU+ enclosure as shown in Figure 2-1;

    2) Insert the ACU+ into the DC power cabinet;

  • 8 Chapter 2 Installation

    ACU+ Controller User Manual

    Close the handle of the ACU+ and the latch is popped out to lock the ACU+ into the DC power cabinet, as shown in Figure 2-1.

    2.4 Using With EIB Board

    ACU+ can have more I/Os when it is used with an EIB board. The EIB board is an enhanced signal extension board. It is installed inside the power system cabinet and outside of the ACU+ controller. It connects to the controller via cables. The functions of EIB board are given in Table 2-1.

    Table 2-1 Functions of EIB Board

    Function Quantity Description DC voltage measurement 8 Measure battery or bus bar voltage to judge the system operating status Shunt current measurement 3 The shunt is used to measure load or battery current Temperature sensor measurement

    2 Measure current-type temperature sensor signal and check the system operating temperature

    Relay output 5 Dry contacts output EIB board can measure 3 currents which can be either load current or battery current:

    Current Sampling of EIB Board as shown in Table 2-2:

    Table 2-2 Current sampling of EIB Board

    Sampling Object Current sampling channels of EIB board

    Sampling 1 Sampling 2 Sampling 3 Battery current Battery 1 current Battery 2 current Battery 3 current Load current Load 3 current Load 2 current Load 3 current

  • Chapter 3 LCD Operation 9

    ACU+ Controller User Manual

    Chapter 3 LCD Operation

    3.1 ACU+ Panel

    ACU+ Panel is illustrated in Figure 3-1:

    86.8

    43

    Panel of 1U 2U ACU+

    87

    86.2

    Panel of 2U 2U ACU+

    Figure 3-1 ACU+ Panel

    Functions of LED indicators are illustrated in Table 3-1.

    Table 3-1 Functions of LED indicators

    LED Normal Status Abnormal Status Cause Operation Indicator (Green) ON OFF No Power Supply Protection Indicator (Yellow)

    OFF ON DC Power has at least an observation alarm

    Alarm Indicator (Red) OFF ON DC Power has at least an major alarm or critical alarm.

  • 10 Chapter 3 LCD Operation

    ACU+ Controller User Manual

    The ACU+ controller has two kinds of LCD: One is a 128 64 dot-matrix LCD unit that can display 4 rows of text and the other is 128 128 dot-matrix LCD that can display 8 rows of text. It has 4 functional keys. Its interface is easy-to-use and supports multi-language display. The panel of the controller is easy-to-remove. The functions of these 4 keys are shown in Table 3-2:

    Table 3-2 Functions of ACU+ keys

    Keys Name of Keys Functions

    ESC Return Key Press this key to back to previous menu or cancel a setting of a parameter .

    Press ESC and ENT together to reset ACU+. ENT Enter Key

    Press this key to go to next menu or highlight editable area for parameter setting, validate the change made to a parameter setting.

    Up

    Press or to scroll through the menus.

    These two arrow keys can be used to change the value of a parameter: Press or to move the cursor to the parameter to be changed and change the value of a parameter.

    Down

    3.2 First Screen

    English

    The first screen is the language-selecting screen. User can select between English and the users local language in

    the screen by pressing and, and press ENT to enter the default main screen after selecting the language. If no key has been pressed for 30 seconds, user will enter the default screen directly.

    3.3 Default Main Screen

    18:15:10

    Float

    53.5V 7.8A

    Auto Alarm

    18:15:10

    Float

    53.5V 7.8A

    Auto Alarm

    2009 -07 -28

    Float

    53.5V 7.8A

    Auto Alarm

    2009 -07 -28

    Float

    53.5V 7.8A

    Auto Alarm

    The first row of the default main screen displays the date and time alternatively (For example, it displays 18:15:10, after a while it displays 2005-06-30, and then displays 18:15:10, and it repeats this cycle continuously). The rest information is dependent on the configuration information such as the equipment Type, signal ID and display location).

    In the default main screen:

    Press ENT++ together to change the contrast of LCD

    Press and and ESC together to log out(The password will be invalid)

    Press ENT and ESC together to reset ACU+

    Press ENT to enter main menu

  • Chapter 3 LCD Operation 11

    ACU+ Controller User Manual

    3.4 Overall Menu Structure

    The overall menu structure is shown in the following figure:

    09:20:20Float53.4V 404AAuto Alarm

    Rect NumRect Group Used

    Batt Curr0A

    MAIN MENUStatusSettingsEnergy SavingManualQuick Settings

    STATUSActive AlarmPower SystemRectifierBattery

    SETTINGSAlarmPower SystemRectifier

    0

    0.0%

    ACDCHistory AlarmSite Inventory

    Batt2

    BATTERYBatt1

    Batt3Batt4

    BatteryDCLVDACEIB DCCommunicationController

    Energy Saving EnableYes

    Off Delay 5 minCycle SwitchOn/Off Period

    168 hourSystem ES Point

    45%Optimist Work

    MANUALMan / Auto SetPower SystemRectifierBattery GroupLVD

    Capacity300 Ah

    RECTIFIERAll Rect CtrlRect1Rect2

    Rect Trim268 V

    Curr Limit121%

    ...

    AC ControlON

    DC ControlOFF

    RECTIFIERAll Rect Ctrl

    AC Over V Value485 V

    AC Low V Value310 V...

    ...

    BATTERYBasicChargeTest...

    LVDLVD GroupSMDU LVD1

    ...

    80%

    Figure 3-2 ACU+ Overall Menu Structure

    3.5 Main Menu

    ID: 03081001311M521BA00

    SW Rev: 11.1

    09:20:20Float53.4V 404AManual Normal

    ENT MAIN MENUStatus

    Manual

    SettingsEnergy Saving

    Quick Setting

    ESC

    Figure 3-3 Main Menu

    Main Menu includes running information, settings, energy saving, manual control and quick setting

  • 12 Chapter 3 LCD Operation

    ACU+ Controller User Manual

    3.6 Status

    In the main menu, move cursor to Status, press ENT to show the status menu as shown in the following figure:

    ENTMAIN MENUStatusSettingsEnergy SavingManualQuick Setting

    StatusActive AlarmPower SystemRectifierBatteryDC DistriACEIBSMDU UnitHistory AlarmSite Inventory

    Figure 3-4 Status Menu

    In the screen of MAINMENU, when cursor is at Status, press ENT to go to the status screen, and when cursor is at Active Alarm, press ENT to show the following screen to check Active Alarm information:

    StatusActive AlarmPower SystemRectifierBatteryDC DistriACEIBSMDU UnitHistory AlarmSite Inventory

    Active AlarmObservation: 1Major: 0Critical: 0

    ENT

    Figure 3-5 Active Alarm Information

    The Active Alarm screen shows the information of the alarms, and the number of the alarms in different alarm levels (Observation, Major and Critical) are displayed, and alarm start time are displayed in the screen. If you want to see the information of other unit, move cursor to this unit and just press ENT. Using the same method, you can browse all the information listed in the following table

    Table 3-3 Device Information

    No. Status Information Description Active Alarm

    1 Observation: Number of observation alarms 2 Major: Number of major alarms 3 Critical: Number of critical alarms

    Power System 1 System Voltage System output voltage 2 System Load System output current

    3 Mtn Time Run

    4 Alarm Status Whether or not the system is in alarming status 5 Power Split Whether this system is master or slave in a power split system 6 SPD Surge protection device

    Rectifier Rect 1 (001)

    1 DC Voltage Rectifier output voltage 2 DC Current Rectifier output current 3 Current Limit Current limit value 4 Temperature Rectifier internal temperature 5 DC Status Whether the DC is on or off 6 Derated by AC Rectifier output power is derated according to input voltage 7 Derated by Temp Rectifier output power is derated according to temperature 8 Walk-in Func Rectifier soft start function

  • Chapter 3 LCD Operation 13

    ACU+ Controller User Manual

    No. Status Information Description 9 Rect Position 10 Rect Phase Whether the rectifier is on Phase A, or Phase B or Phase C? 11 Rectifier SN Rectifier series number 12 Running Time Rectifier operating time 13 AC Voltage Rectifier input AC voltage

    Rect 2 (002): The information of Rect 2 (002) is similar to Rect 1 (001), so is the information of other rectifiers in the system. Battery Battery 1

    1 Batt Current Battery current 2 Batt Voltage Battery voltage 3 Batt Cap (Ah) Battery capacity and the unit is Ah 4 Batt Cap (%) Battery capacity and the unit is %

    Battery 2, SMDU/Batt3 and SMDU/Batt4: The information of these batteries is similar to that of Battery 1. DC Distri

    1 DC Voltage DC output voltage AC Rect1 AC

    1 Phase A Voltage The line-to-neutral voltage of Phase A of rectifier 1 2 Phase B Voltage The line-to-neutral voltage of Phase B of rectifier 1 3 Phase C Voltage The line-to-neutral voltage of Phase C of rectifier 1

    OB AC Unit: The information of OB AC Unit is similar to that of Rect AC. EIB

    1 Bad Battery Blo Bad battery block 2 Load 1 Current Current of load 1 3 Load 2 Current Current of load 2 4 Load 3 Current Current of load 3 5 Voltage 1 Voltage of load 1 6 Voltage 2 Voltage of load 2 7 Voltage 3 Voltage of load 3

    History Alarm 1 Observation: Number of observation alarms 2 Major: Number of major alarms 3 Critical: Number of critical alarms

    Site Inventory Rectifier 1

    1 Device Name Name of the device 2 Product Ver Product version number 3 SW Version Software version number 4 Serial Number Serial number of the device

    The screens give user the information about what devices are available and the device information. The information of SM DU, Controller and IB1 board are similar to the rectifier information that includes the device name, product version, software version and serial number.

  • 14 Chapter 3 LCD Operation

    ACU+ Controller User Manual

    For some devices, there are more than one menu levels, and you need to press ENT more than one time to browse its information. With Rectifier as an example:

    StatusActive AlarmPower SystemRectifierBatteryDC DistriACEIBSMDU UnitHistory AlarmSite Inventory

    ENT RectifierRect 1 (001)Rect 2 (002)

    ENT DC Voltage53.8 V

    DC Current8.5 A

    Curr Limit60 %

    Temperature30 deg C

    DC StatusOff

    Derated by ACNormal

    Derated by TempNormal

    Walk -in FuncDisabled

    Rect Position1

    Rect PhaseA

    Rectifier SN010700213

    Running Time200 h

    AC Voltage224 V

    Figure 3-6 Rectifier Information

    3.7 Manual

    ENTMAIN MENUStatusManualSettingsEnergy SavingQuick Setting

    ManualMan / Auto SetPower SystemRectifierBatt GroupLVD

    Figure 3-7 Manual Operations

    In the Main Menu, move the cursor to the position of Manual, and press ENT to show the Manual operation menus.

    ENTManualMan / Auto SetPower SystemRectifierBatt GroupLVD

    Auto/Man StateAuto

    Figure 3-8 Manual / Auto Control Status

    In the screen as shown in Figure 3-8, you can set the system from Auto control to Manual control. Setting method: When the cursor is beside the Auto, press ENT to highlight the characters of Auto, and then pressand to change the Auto to Manual. After the system is set to Manual control, you can set the system manually.

  • Chapter 3 LCD Operation 15

    ACU+ Controller User Manual

    Move the cursor to Power System, and press ENT, following screen will show up:

    ENTManualMan / Auto SetPower SystemRectifierBatt GroupLVD

    Clr Run TimeYes

    Figure 3-9 Set the Power System Manually

    If you set Clr Run Time to Yes, the system running time record will be cleared.

    Move the cursor to Rectifier, and press ENT, following screen will show up:

    ENTManualMan / Auto SetPower SystemRectifierBatt GroupLVD

    RectifierAll Rect CtrlRect1(001)Rect2(002)

    ENT Rect Trim54.0 V

    Current Limit60 %

    DC On / Off CtrlSwitch on All

    LEDs ControlStop Twinkle

    Fan Speed CtrlAuto Speed

    Clear Rect LoseClear

    Reset OscillClear

    Figure 3-10 Set the Rectifier Manually

    Move the cursor to Batt Group, and press ENT, following screen will show up:

    ENTManualMan / Auto SetPower SystemRectifierBatt GroupLVD

    BC / FC ControlFloat Charge

    Start Batt TestYes

    Stop Batt TestYes

    Reset CapacityYes

    Clear BadBatt AYes

    Clear Abcur AlmYes

    Figure 3-11 Set Battery Group Manually

    Move the cursor to LVD, and press ENT, following screen will show up:

    ENTManualMan / Auto SetPower SystemRectifierBatt GroupLVD

    LVD1 ControlConnected

    LVD2 ControlConnected

    Figure 3-12 Set LVD Manually

    3.8 Settings

    In the submenu of Settings, you can set the parameters of alarm, power system, rectifier, battery, DC distribution, LVD, AC, communication and controller.

  • 16 Chapter 3 LCD Operation

    ACU+ Controller User Manual

    3.8.1 Alarm Setting

    Move cursor to Alarm Setting, press ENT to show the following screen:

    ENTMAIN MENU

    Status

    Manual

    SettingsEnergy Saving

    Quick Setting

    SettingsAlarm SettingPower SystemRectifierBatteryDC DistriLVDACCommunicationController

    Alarm SettingsAlarm SeverityAlarm RelayAlarm Param

    ENT

    Figure 3-13 Alarm Setting

    Alarm severity setting

    Move the cursor to the Alarm Severity, press ENT to pop up the following screen:

    Alarm Settings

    Alarm RelayAlarm Param

    ENTAlarm Severity

    Power SystemRect GroupRectifierBattery GroupBatteryOBBattery FusSMDU Batt FusDCDC Fuse UnitSMDU DC FuseLVDSMDU LVDACOB AC UnitIBEIBSMDU UnitConverter

    ENTSelf Detect Fail

    NoneCAN Comm Fail

    NoneAlarm Blocked

    None.

    Alarm Severity

    .

    Figure 3-14 Alarm Severity Setting of Power System

    In this menu, you can set the severity levels of the alarms of power system, rectifier group, rectifier, battery group, battery, SM DU battery fuse, OB battery fuse, DC distribution, DC fuse, LVD, AC, IB, EIB and converter. Move cursor to Power System, and press ENT, the power system alarm severity setting screen will pop up.

    In the screen as shown in Figure 3-14, the alarms of power system are displayed, such as Self Detect Fail, CAN Comm Fail, Alarm Blocked, etc. The default alarm severities of the alarm are also displayed, such as Critical and Observation. Method of change alarm severity: With the alarm of Self Detect Fail as an example, move the cursor to the alarm severity of Observation, press ENT to highlight the Observation, and then press and to change the severity from Observation to Critical or Major or No Alarm. You can also change the severity of other alarms such as CAN Comm Fail and Alarm Blocked using the same method. In Figure 3-20, move the cursor to Rect Group, you can set the severity levels of the alarms of rectifier group. The ACU+ has 4 alarm severity levels as shown in the following table:

    Table 3-4 Characteristics of 4 alarm categories

    Alarm levels Red alarm indicator

    of controller and system

    Yellow alarm indicator of controller and

    system

    Alarm buzzer

    Alarm call back

    Remark

    CA (critical alarm) On On Yes Alarm call back is enabledMA (major alarm) On On Yes Alarm call back is enabledOA (observation alarm) On Off No No alarm Off Off Off No

  • Chapter 3 LCD Operation 17

    ACU+ Controller User Manual

    The alarm list and the default alarm severity levels of the ACU+ is shown in the following table:

    Table 3-5 List of Alarms and Alarm Severity Levels of ACU+

    No. Alarm Name Alarm Description Default Alarm

    Severity Alarms of power system

    1 Self Detect Fail The system self detection fails. Observation 2 CAN Comm Fail The CAN bus communication fails. Critical 3 Alarm Blocked The alarm is blocked. Observation 4 Maintenance Alrm Maintenance alarm No Alarm 5 Config Error 1 Configuration error 1 Observation 6 Config Error 2 Configuration error 2 Observation 7 Imbalance Curr Current sharing imbalance Critical 8 Over Load The DC power system has overload. Observation 9 SPD Surge protection device Critical 10 EStop/EShutdown Emergent stop or emergent shutdown Critical 11 Temp 1 Not Used Observation 12 Temp 2 Not Used Observation 13 Temp 3 Not Used Observation 14 Temp 4 Not Used Observation 15 Temp 5 Not Used Observation 16 Temp 6 Not Used Observation 17 Temp 7 Not Used Observation 18 T1 Sensor Fault Temperature sensor 1 has fault. Observation 19 T2 Sensor Fault Temperature sensor 2 has fault. Observation 20 T3 Sensor Fault Temperature sensor 3 has fault. Observation 21 T4 Sensor Fault Temperature sensor 4 has fault. Observation 22 T5 Sensor Fault Temperature sensor 5 has fault. Observation 23 T6 Sensor Fault Temperature sensor 6 has fault. Observation 24 T7 Sensor Fault Temperature sensor 7 has fault. Observation 25 Temp1 High2 Temperature 1 higher than high temperature threshold 2 Major 26 Temp2 High2 Temperature 2 higher than high temperature threshold 2 Major 27 .. .. Major 31 Temp7 High2 Temperature 7 higher than high temperature threshold 2 Major 32 Temp1 High1 Temperature 1 higher than high temperature threshold 1 Major 33 Temp2 High1 Temperature 2 higher than high temperature threshold 1 Major 34 .. .. Major 38 Temp7 High1 Temperature 7 higher than high temperature threshold 1 Major 39 Temp1 Low Temperature 1 low Observation 40 Temp2 Low Temperature 2 low Observation 41 .. .. Observation 45 Temp7 Low Temperature 7 low Observation

    46 DHCP Failure The DHCP function is enabled, but effective IP address cannot be acquired.

    Observation

    Alarms of Rect Group 1 Multi-rect Fail More than one rectifier fail Critical 2 Rectifier Lost Rectifier cannot be detected by the controller Critical 3 Redund Active Rectifier redundancy is enabled Observation 4 Rect No Resp The communication of all rectifiers fail. Major

    5 Redund Oscill

    Sometimes, the controller meets the redundancy conditions, sometimes, it does not meet the conditions, if this phenomenon happens more than 5 times, the controller will alarm.

    Observation

    Alarms of Rectifier 1 AC Failure Rectifier AC power fails Major 2 Rect Temp High Rectifier temperature high Major 3 Rect Fault Rectifier fault Major 4 Over Voltage Rectifier over voltage Major 5 Rect Protected Rectifier is protected Major 6 Fan Failure Rectifier fan fails Major

  • 18 Chapter 3 LCD Operation

    ACU+ Controller User Manual

    No. Alarm Name Alarm Description Default Alarm

    Severity 7 Current Limit Rectifier is in current limiting status Major 8 Comm Fail Rectifier communication fails Major 9 Derated Rectifier output power is derated Observation 10 SharingCurr Alm Rectifier has current sharing alarm Observation 11 U-Volt Protect Under voltage protection Major

    Alarms of Batt Group 1 Short Test Battery short time test Observation 2 Boost For Test Boost charge test Observation 3 Manual Test Manual battery discharge test Observation 4 Plan Test Planned battery test Observation

    5 AC Fail Test Switch off AC power to perform the battery discharging test

    Observation

    6 Manual Boost Manually start the boost charging Observation 7 Auto BC Automatic boost charging Observation 8 Cyclic Boost Cyclic boost charging Observation

    9 Master Boost In slave mode, the slave unit starts boost charging with the master unit.

    Observation

    10 Master Test In slave mode, the slave unit starts the test with the master unit.

    Observation

    11 Dis Curr Im Rectifier distribution current alarm Observation 12 Abnorm Batt Curr Battery current is abnormal Observation 13 Temp Comp Activ Temperature compensation is started Observation 14 Batt Curr Lmt Battery current limit Observation 15 Bad Battery Battery block fails Observation 16 Battery Dischar Battery discharging Observation

    Alarms of Battery 1 Exceed Curr Lmt Current limit point is exceeded Observation 2 Over Current Battery over current Observation 3 Low Capacity Battery low capacity Observation

    Alarms of OBBattery Fus 1 Fuse1 Alarm Battery fuse 1 alarm Critical 2 Fuse2 Alarm Battery fuse 2 alarm Critical 3 Fuse3 Alarm Battery fuse 3 alarm Critical 4 Fuse4 Alarm Battery fuse 4 alarm Critical

    Alarms of SMDUBattery Fus 1 Batt Fuse 1 Alm Battery fuse 1 alarm Critical 2 Batt Fuse 2 Alm Battery fuse 2 alarm Critical 3 Batt Fuse 3 Alm Battery fuse 3 alarm Critical 4 Batt Fuse 4 Alm Battery fuse 4 alarm Critical

    Alarms of DC 1 Over Voltage1 DC over voltage 1 Critical 2 Over Voltage2 DC over voltage 2 Critical 3 Under Voltage1 DC under voltage 1 Critical 4 Under Voltage2 DC under voltage 2 Critical

    Alarms of DC Fuse Unit 1 Fuse1 Alarm Fuse 1 alarm Critical 2 Fuse2 Alarm Fuse 2 alarm Critical 3 .. .. Critical 10 Fuse10 Alarm Fuse 10 alarm Critical

    Alarms of SMDU DC Fuse 1 DC Fuse1 Alarm Critical 2 DC Fuse2 Alarm Critical 3 .. Critical 16 DC Fuse16 Alarm Critical

    Alarms of LVD 1 LVD1 Disconnect LVD1 contactor disconnected Critical 2 LVD2 Disconnect LVD2 contactor disconnected Critical 3 LVD1 Failure LVD1 contactor fails Critical

  • Chapter 3 LCD Operation 19

    ACU+ Controller User Manual

    No. Alarm Name Alarm Description Default Alarm

    Severity 4 LVD2 Failure LVD2 contactor fails Critical

    Alarms of SMDU LVD 1 LVD1 Disconnect LVD1 contactor disconnected Critical 2 LVD2 Disconnect LVD2 contactor disconnected Critical 3 LVD1 Failure LVD1 contactor fails Critical 4 LVD2 Failure LVD2 contactor fails Critical

    Alarms of AC 1 L-AB OverVolt1 Line A-to-Line B over voltage 1 Observation 2 L-AB OverVolt2 Line A-to-Line B over voltage 2 Observation 3 L-AB UnderVolt1 Line A-to-Line B under voltage 1 Observation 4 L-AB UnderVolt2 Line A-to-Line B under voltage 2 Observation 5 L-BC OverVolt1 Line B-to-Line C over voltage 1 Observation 6 L-BC OverVolt2 Line B-to-Line C over voltage 2 Observation 7 L-BC UnderVolt1 Line B-to-Line C under voltage 1 Observation 8 L-BC UnderVolt2 Line B-to-Line C under voltage 2 Observation 9 L-CA OverVolt1 Line C-to-Line A over voltage 1 Observation 10 L-CA OverVolt2 Line C-to-Line A over voltage 2 Observation 11 L-CA UnderVolt1 Line C-to-Line A under voltage 1 Observation 12 L-CA UnderVolt2 Line C-to-Line A under voltage 2 Observation 13 PH-A OverVolt1 Phase A over voltage 1 Observation 14 PH-A OverVolt2 Phase A over voltage 2 Observation 15 PH-A UnderVolt1 Phase A under voltage 1 Observation 16 PH-A UnderVolt2 Phase A under voltage 2 Observation 17 PH-B OverVolt1 Phase B over voltage 1 Observation 18 PH-B OverVolt2 Phase B over voltage 2 Observation 19 PH-B UnderVolt1 Phase B under voltage 1 Observation 20 PH-B UnderVolt2 Phase B under voltage 2 Observation 21 PH-C OverVolt1 Phase C over voltage 1 Observation 22 PH-C OverVolt2 Phase C over voltage 2 Observation 23 PH-C UnderVolt1 Phase C under voltage 1 Observation 24 PH-C UnderVolt2 Phase C under voltage 2 Observation 25 Mains Failure AC mains power fails Critical

    Alarms of OB AC Unit 1 PH-A OverVolt1 Phase A over voltage 1 Observation 2 PH-A OverVolt2 Phase A over voltage 2 Observation 3 PH-A UnderVolt1 Phase A under voltage 1 Observation 4 PH-A UnderVolt2 Phase A under voltage 2 Observation 5 PH-B OverVolt1 Phase B over voltage 1 Observation 6 PH-B OverVolt2 Phase B over voltage 2 Observation 7 PH-B UnderVolt1 Phase B under voltage 1 Observation 8 PH-B UnderVolt2 Phase B under voltage 2 Observation 9 PH-C OverVolt1 Phase C over voltage 1 Observation 10 PH-C OverVolt2 Phase C over voltage 2 Observation 11 PH-C UnderVolt1 Phase C under voltage 1 Observation 12 PH-C UnderVolt2 Phase C under voltage 2 Observation 13 Mains Failure AC mains power fails Critical 14 SevereMainsFail AC mains voltage is too low Critical

    Alarms of IB 1 IB Failure Critical 2 DI1 Alarm Digital input 1 alarm Critical 3 DI2 Alarm Digital input 2 alarm Critical 4 .. .. Critical 9 DI8 Alarm Digital input 8 alarm Critical

    Alarms of EIB 1 EIB Failure EIB board fails Critical 2 Bad Batt Block Battery block fails Observation

  • 20 Chapter 3 LCD Operation

    ACU+ Controller User Manual

    No. Alarm Name Alarm Description Default Alarm

    Severity Alarms of SMDU Unit

    1 Under Voltage Observation 2 Over Voltage Observation 3 Comm Interrupt Rectifier communication failure Major

    Alarms of Converter 1 Converter Fail Major

    The Default Alarm Severity of all the alarms in the above table can be changed.

    Alarm relay setting

    Move the cursor to Alarm Relay and press ENT, following screen pop up:

    Alarm Settings

    Alarm RelayAlarm Param

    ENTAlarm RelayPower SystemRect GroupRectifierBattery GroupBatteryOBBattery FusSMDU Batt FusDCDC Fuse UnitSMDU DC FuseLVDSMDU LVDACOB AC UnitIBEIBSMDU UnitConverter

    ENTSelf Detect Fail

    NoneCAN Comm Fail

    NoneAlarm Blocked

    None.

    Alarm Severity

    .

    Figure 3-15 Alarm Relay Setting

    In the screen of Alarm Relay Setting, move cursor to Power System and press ENT to highlight the Power System, and press ENT again to display the alarms of the power system, such as Self Detect Fail, CAN Comm Fail, Alarm Blocked, etc, as well as the alarm relay number. In the screen, the alarm relay number is displayed as None, and you can configure it. For example, if you want to set the alarm relay number for the alarm of Self Detect Fail, move the cursor to None, press ENT to highlight None, and press or continuously to enter the numbers from 0 to 10, this means you set alarm relay 1 to relay 10 for the alarm of Self Detect Fail. You can set the alarm relay for other alarms in the same way.

    Alarm parameter setting

    Move the cursor to Alarm Param and press ENT, following screen shows up:

    ENTAlarm Settings

    Alarm SeverityAlarm RelayAlarm Param

    Alarm VoiceOn

    Block AlarmNormal

    Clear His AlarmYes

    Figure 3-16 Alarm Parameter Setting

    For the menu of Alarm Voice, you can set the alarm voice to Off to turn off the buzzer.

    For the menu of Clear His Alarm, you can set it from Yes to No, which means do not clear the history alarm.

    3.8.2 Power System Setting

    In the Setting screen, move cursor to Power System, press ENT to show the Power System Setting screen. In the Power System Setting screen, you can set the general parameters (General), Power Split parameters and

  • Chapter 3 LCD Operation 21

    ACU+ Controller User Manual

    temperature parameters (Temp Para). Move cursor to General, press ENT, general parameter setting screen will show up

    ENTMAIN MENUStatus

    Manual

    SettingsEnergy Saving

    Quick Setting

    SettingsAlarm SettingPower SystemRectifierBatteryDC DistriLVDACCommunicationController

    Power SystemGeneralPower SplitTemp Para

    ENT Auto / Man StateAuto

    Mtn Time Delay30 days

    Mtn Cycle Time360 days

    ENT

    Figure 3-17 General Parameter Settings of Power System

    The general parameter settings of power system are: Auto / Man State, Mtn Time Delay, Mtn Cycle Time, etc. Method of changing the parameter settings: With Mtn Time Delay as an example, move cursor beside 3 that is in 30 days, press ENT to highlight the character of 3, now you can press or continuously to enter the numbers from 0 to 9 to change the number 3 to other numbers, after the changing, press ENT to validate the change. Then, move cursor beside 0 that is in 30 days, press ENT to highlight the character of 0, and now you can press or continuously to enter the numbers from 0 to 9 to change the number 0 to other numbers. After the changing, press ENT to validate the change

    You can use the same method to change all the other parameters listed in following tables:

    Table 3-6 Parameter Settings of Power System

    No. Parameter Name Parameter Description Default Setting Setting Range General Parameter Settings

    1 Auto / Man State Auto / manual control Auto Auto / manual 2 Mtn Time Delay Delay of maintenance 30 days 3 Mtn Cycle Time Cycle time of maintenance 360 days 4 Over Load Point 70% 5 Imb Protect Current sharing imbalance Enable Enable / disable 6 Relay Report Way Relay report way Fixed Fixed / user defined7 EStop / EShutdown Emergent stop / emergent shutdown Disable Disable / enable

    8 Auto Mode If the region is set to Europe, user can turn on / off the rectifier under auto mode.

    Normal

    9 Alarm Blocked If the alarm is blocked, the alarm information will not be reported under EEM protocol.

    Normal

    Power Split Parameter Settings 1 Slave Curr Lmt 60% 2 Delta Volt 0.5V 3 Proportion Coeff 30.0 4 Interrupt Time 60s

    Temp Para Settings

    1 Temp1 enable Options are disable, environment and battery, which means whether this temperature sensor detects ambient

    Disable Disable / enable

    2 Temp2 enable Same with above Disable Disable / enable 3 Temp3 enable Same with above Disable Disable / enable

    4 Temp1 High1 Temperature 1 higher than high temperature threshold 1

    50 deg.C

    5 Temp2 High1 Temperature 2 higher than high temperature threshold 1

    50 deg.C

    6 Temp3 High1 Temperature 3 higher than high temperature threshold 1

    50 deg.C

    7 Temp1 Low Temperature 1 low 0 deg.C 8 Temp2 Low Temperature 2 low 0 deg.C 9 Temp3 Low Temperature 3 low 0 deg.C

  • 22 Chapter 3 LCD Operation

    ACU+ Controller User Manual

    3.8.3 Rectifier Setting

    Move cursor to Rectifier and press ENT, the rectifier setting screen pops up, then move cursor to All Rect Set, following screen pops up:

    ENT Hi Volt Limit59.0 V

    DCOverVRestartDisable

    OverVRestart300 s

    SettingsAlarm SettingPower SystemRectifierBatteryDC DistriLVDACCommunicationController

    RectifierAll Rect SetRect1(001)Rect2(002)

    ENT

    Figure 3-18 Rectifier Parameter Setting

    In the middle screen of Figure 3-18, there are 3 items: All Rect Set, Rect1(001) and Rect2(002). For All Rect Set, the parameter setting will be effective for all the rectifiers. For Rect1(001), the parameter setting is only effectively for rectifier 1 (001). From the screen, you can see that there are only 2 rectifiers working. If there are 5 rectifiers working, the screen will show all the rectifiers from Rect1(001) to Rect5(005).

    User can configure all the rectifier parameters listed in the following table:

    Table 3-7 List of Rectifier Parameter Settings

    No. Parameter Name Parameter Description Default Setting Setting Range Parameter Settings of All Rect Set

    1 Hi Volt Limit High voltage limit 59.0V 2 DCOverVRestart Restart after DC over voltage Disable Disable / enable 3 OverVRestartT Time after over voltage restart 300s 4 Start Interval Start interval 0s 5 Walk-in Enable Rectifier Walk-in enabled Disable Disable / enable 6 Turn-on ACOverV AC over voltage turn-on No 7 Confirm Posi/PH Confirm rectifier position and phase No 8 Redund Enabled Redundancy enabled Disabled Disabled / enabled

    Rect1 Parameter Settings 1 Rect Position Rectifier position 1 2 Rect Phase Rectifier phase A

    The contents of settings of rect1 (001) are same with those of rect2(002).

    3.8.4 Battery Setting

    Move cursor to Battery, press ENT to show the battery setting screen, you can configure all the battery parameters listed in the following table:

    Table 3-8 List of Battery Parameter Settings

    No. Parameter Name Parameter Description Default Setting Setting Range Basic Battery Parameter Settings

    1 Batt Type No.1 Type of battery string 1 1

    2 Rated Capacity Rated capacity of battery 300.00 Ah

    3 BattVoltSamType Battery voltage sample type 2

    4 Action on VHBT

    Whether to disconnect the LVD contactor or regulate the battery voltage, when battery over temperature happens

    Disabled

    5 Low Cap Point Low capacity threshold 75%

  • Chapter 3 LCD Operation 23

    ACU+ Controller User Manual

    Settings of Charge Para 1 FC Voltage Float charging voltage 53.5V 2 BC Voltage Boost charging voltage 56.4V 3 Batt Curr Lmt Battery charging current limit 0.10 C10 4 Over Current Battery over voltage 0.30 C10

    5 Auto BC Enabled Automatic boost charging test is enabled

    Yes Yes / No

    6 To BC Current Current for transferring boost charging

    0.060C10

    7 To BC Capacity Capacity for transferring boost charging

    80.0%

    8 Stable BC Curr Stable boost charging current 0.010 9 Stable BC delay Stable boost charging delay 100 min 10 BC ProtectTime Boost charging protection time 1000 min 11 CycBC Enabled Cyclic boost charging enabled Yes Yes / No 12 Cyc/BC Interval Cyclic boost charging interval 100 days 13 Cyc/BC Duration Cyclic boost charging duration 720 min

    Settings of Test Para 1 Test Volt Test voltage 45.0V 2 Test End Volt End of test voltage 45.2V 3 Test End Time Test time 100 min 4 Test End Cap End of test capacity 70.0% 5 Record Threshold 0.100V 6 AC Fail Test Enb Disable 7 Planned Test 0 8 ConstCurr Enb Constant current charge is enabled Disable Disable / Enable 9 ShortTestEnable Battery short test is enabled Disable Disable / Enable

    Parameter Settings of Temp Comp 1 TempComp Center Temperature compensation center 25.0 deg.C

    2 TempComp Coeff Temperature compensation coefficient

    72.0 mV/deg.C

    3 Temp No. for TC Number of temperature inputs used for temperature compensation

    None

    Parameter Settings of Capa Cacu 1 Capacity Coef Capacity coefficient 96% 2 Time 0.1C10 10.00 h 3 Time 0.2C10 4.90 h 4 Time 0.3C10 3.00 h 5 Time 0.4C10 2.00 h 6 Time 0.5C10 1.40 h 7 Time 0.6C10 1.20 h 8 Time 0.7C10 1.10 h 9 Time 0.8C10 0.90 h 10 Time 0.9C10 0.70 h 11 Time 1.0C10 0.50 h

    Battery 1

    1 Manage Enable Whether the battery participates the battery management

    Yes

    2 Shunt Current Battery shunt current 500.0A 3 Shunt Voltage Battery shunt voltage 75.0 mV

    The parameter settings of Battery 2 and SMDU Battery are the same with those of Battery 1.

  • 24 Chapter 3 LCD Operation

    ACU+ Controller User Manual

    3.8.5 Parameter Settings Of DC Distri

    Move the cursor to DC Dsitri in the setting screen to configure all the parameters of DC distribution unit listed in the following table:

    Table 3-9 Parameter Settings of DC Distribution

    No. Parameter Name Parameter Description Default Setting Setting Range 1 Over Voltage 1 DC over voltage 1 55.7V 2 Over Voltage 2 DC over voltage 2 58.5V 3 Under Voltage 1 DC Under Voltage 1 45.0V 4 Under Voltage 2 DC Under Voltage 2 42.0V 5 Shunt Current 500.0A 6 Shunt Voltage 75.0mV

    7 Load Exist Whether the load shunt is connected in the system

    Yes

    3.8.6 Parameter Setting Of LVD

    Move cursor to LVD in the setting screen, press ENT to set the LVD parameters listed in the following table:

    Table 3-10 Parameter Setting of LVD

    No. Parameter Name Parameter Description Default Setting Setting Range 1 LVD1 Enabled LVD1 is enabled Enabled Enabled / disabled

    2 LVD1 Mode LVD1 is enabled according to voltage or time

    Voltage Voltage / Time

    3 LVD1 Voltage LVD1 voltage 43.2 V 4 LVD1 Reconn Volt LVD1 reconnection voltage 52.5 V 5 LVD1 Reconn Delay LVD1 reconnection delay time 2 min 6 LVD1 Time 300 min 7 LVD1 Dependency None 8 LVD2 Enabled LVD2 is enabled Enabled Enabled / disabled

    9 LVD2 Mode Whether the LVD2 is activated according to voltage or time

    Voltage Voltage / Time

    10 LVD2 Voltage 43.2 V 11 LVD2 Reconn Volt LVD2 reconnection voltage 52.5 V 12 LVD2 Reconn Delay LVD2 reconnection delay 2 min 13 LVD2 Time 300 min 14 LVD2 Dependency None 15 LVD Type Type of LVD contactor Bistable Bistable / monostable

    3.8.7 AC Parameter Settings

    Move cursor to AC in the setting screen, press ENT to set the AC parameters listed in the following table:

    Table 3-11 AC Parameter Setting

    No. Parameter Name Parameter Description Default Setting Setting Range Rect AC Parameter Settings

    1 Nominal PH-Volt Nominal line-to-neutral voltage 220 V 2 Volt Threshold1 Voltage threshold 1 20.0% 3 Volt Threshold Voltage threshold 25.0%

    OB AC Unit Parameter Settings 1 Nominal PH-Volt Nominal line-to-neutral voltage 220 V 2 Volt Threshold1 Voltage threshold 1 20.0% 3 Volt Threshold Voltage threshold 25.0%

    4 AC Type AC input type None None, Three-Phase, Single-Phase

  • Chapter 3 LCD Operation 25

    ACU+ Controller User Manual

    3.8.8 Communication Parameter Settings

    Move cursor to Communication in the setting screen, press ENT to set the communication parameters listed in the following table:

    Table 3-12 Communication Parameter Setting

    No. Parameter Name Parameter Description Default Setting Setting Range 1 DH CP Close 2 IP Address 10.163.210.205 3 Subnet Mask 255.255.254.0 4 Default Gateway 10.163.210.205

    3.8.9 Controller Parameter Settings

    Move cursor to Controller in the setting screen, press ENT to set the controller parameters listed in the following table:

    Table 3-13 Controller Parameter Setting

    No. Parameter Name Parameter Description Default Setting Setting Range 1 Language Language used in LCD display English English / Chinese 2 Time Zone GMT+00:00 3 Date 2009-01-19 4 Time 11:10:20 5 Keypad Voice On On / Off 6 LCD Rotation 90 deg 0, 90, 180, 270 7 Reload Config Yes Yes / No 8 Download Config Yes Yes / No 9 Auto Config Yes Yes / No

    3.9 Energy Saving Setting

    Move cursor to Energy Saving in the setting screen, press ENT to set the Energy Saving parameters listed in the following table:

    Table 3-14 Rect Standby Parameter Setting

    No. Parameter Name Parameter Description Default Setting Setting Range 1 Redund Enabled Disabled Disabled / Enabled

    3.10 Quick Setting

    Move cursor to Quick Setting in the setting screen, press ENT to set the Quick Setting parameters listed in the following table:

    Table 3-15 Quick Settings

    No. Parameter Name Parameter Description Default Setting Setting Range 1 Rated Capacity 300.0 Ah

  • 26 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    Chapter 4 Access ACU+ Through Web

    4.1 Overview Of Web Function

    Web is a remote user interface, user can

    z Browser the detail status of each equipment such as rectifiers, batteries, and AC unit z Send control command and set parameters to equipment z View the active alarms that can be auto popped up if a new alarm comes. z Query historical alarms, historical signal data and logs(battery test, diesel test, user control, system) z Change system parameters, such as IP address, time, SNMP and EEM protocol settings, user information z Change equipment name, signal name and alarm level z Download/upload configuration files, and update application software and local language package.

    4.2 Login

    To log in ACU+, double-click the icon of IE to run the software, click the menus of ToolsInternet Options and then click the button Connections to pop up the following screen:

    Figure 4-1 LAN Setting (Step 1)

  • Chapter 4 Access ACU+ Through Web 27

    ACU+ Controller User Manual

    In the screen as shown in Figure 4-1, click the button LAN Settings to pop up the following screen:

    Figure 4-2 LAN Setting (Step 2)

    In the above screen, uncheck the proxy screen and click OK to finish the LAN setting. Then input the IP address and press ENT, the following Web interface pops up requiring user to enter username and password.

    Note that user only needs to do the above settings when the ACU+ is connected to an intranet and the user has set that the access to the intranet needs to be made through proxy. If the ACU+ is connected Internet and the user computer is connected to the intranet, the user cannot disable the proxy, otherwise he will have no access to the ACU+.

    Figure 4-3 Log in ACU+

    In the above screen, enter the username and password to log in ACU+, and the homepage screen as shown in Figure 4-4 pops up.

  • 28 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    4.3 Homepage Introduction

    The homepage screen is shown in Figure 4-4.

    Figure 4-4 ACU+ Homepage

    In the main page, the system voltage, load current, management mode and battery management status are displayed at the top.

    The Device Explore, Quick Setting, Query and Modify Configuration are displayed in the left side. Click each kind of menu and the contents will be displayed in the right side.

    The alarm bar is located at the bottom of the screen.

    4.4 Device Explore

    As shown in Figure 4-4, the menu Device explore has the sub-menus of equipment groups such as Power System, RectifierGroup, BatteryGroup, DC Distribution, AC Group, and LVD Group. User can check the sample data of the equipment, set the equipment parameter and control the equipment by operating these sub-menus.

    Every equipment has 3 signals that are data acquisition signals (sampled values), control signal and setting signal.

    The following part introduces the device explore operation with rectifier and battery as examples.

  • Chapter 4 Access ACU+ Through Web 29

    ACU+ Controller User Manual

    4.4.1 Data Browse, Control And Parameter Setting Of Rectifier

    Rectifier group

    In the screen as shown in Figure 4-5, click RectifierGroup, following screen pops up:

    Figure 4-5 Rectifier Screen 1

    The signals in the screen as shown in Figure 4-6 are all the actually sampled values such as Total current, Rectifier Number and so on. In the screen, click the button Control, following screen pops up:

    Figure 4-6 Rectifier Screen 2

  • 30 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    The signals in the screen as shown in Figure 4-6 are all the values used to control the rectifier. For example, in Fan full speed control, user can select Full Speed and click Set to make the rectifier fan run at full speed. The control command is effective for all the rectifiers. Pay attention that the Control button is only active when the ACU+ is in manual status. Therefore, before implementing the Control operation, you have to set the Auto/Man State of the ACU+ System to Man status.

    Click the button Setting, following screen pops up:

    Figure 4-7 Rectifier Screen 3

    The screen as shown in Figure 4-7 lists all the values that can be set. For example, user can select Disabled for the value of Walk-in enabled in the box of Set value, and then click the button Set to make the setting effective. After the setting, the walk-in function of all the rectifiers is disabled.

  • Chapter 4 Access ACU+ Through Web 31

    ACU+ Controller User Manual

    Single rectifier

    Click the submenu Rectifier1 of RectifierGroup, following screen pops up as shown in Figure 4-8:

    Figure 4-8 Sampled Values of Single Rectifier

    The screen as shown in Figure 4-8 shows the sample value of Rectifier1, similar to the operation of RectifierGroup, user can click the button Control to view the values of rectifier 1 that can be controlled, as shown in Figure 4-9.

    Figure 4-9 Control Screen of Rectifier 1

    In the screen as shown in Figure 4-9, user can control the rectifier 1. For example, user can set the AC input of rectifier 1 to on.

  • 32 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    4.4.2 Data Browse, Control And Parameter Setting Of Battery

    Click the icon in the left of Battery Group, all the sampled values of the battery group are displayed as shown in Figure 4-10.

    Figure 4-10 Battery Screen (Sampled Value of Battery)

    In Figure 4-10, the battery voltage is the total battery string voltage. The battery current is the total battery current. Similar to browse the control values of the rectifier, click the button Control to view the control signals of the battery as shown in Figure 4-11:

    Figure 4-11 Control the Battery Group

  • Chapter 4 Access ACU+ Through Web 33

    ACU+ Controller User Manual

    In the screen as shown in Figure 4-11, user can control the battery. For example, in the Set value box of Boost/Float charge control, user can set the Float Charge to Boost Charge, and click the button set to make the setting become effective. Click the button setting to view setting signals of the battery as shown in Figure 4-12.

    Figure 4-12 Setting Values of Battery Group

    In the screen as shown in Figure 4-12, user can set the battery parameters. For example, in the Set value box of Very High Temperature Limit, user can set the temperature limit from 36.00 to 38.00, and click the button set to make the setting become effective.

    Click the submenu of Battery1, the following screen pops up:

    Figure 4-13 Sampled Values of Battery 1

  • 34 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    The screen as shown in Figure 4-13 displays the sampled values of battery 1. In this screen, if you click Control, nothing will be displayed because it is not allowed to control the single battery or set the values of the single battery.

    Click Setting, following screen pops up:

    Figure 4-14 Setting Signals of Battery 1

    Figure 4-14 shows the settable signals of battery 1 and user can set these signal values. For example, user can select whether to enable this string of battery to participate the battery management and whether the shunt coefficient of this battery can be set.

    4.5 Alarms

    The lower part on the right side of the page shows the active alarms of the DC power system.

    When browsing the signals, click the icon to collapse more alarm signal information and you can recover the display of alarm list by clicking again.

  • Chapter 4 Access ACU+ Through Web 35

    ACU+ Controller User Manual

    The active alarms are displayed as shown in Figure 4-15:

    Figure 4-15 Alarm Screen

    Figure 4-15 shows all the default alarms in the current active alarm page. Click Observation Alarm button to display the alarms that are in the category of Observation Alarm:

    Figure 4-16 Only Display Minor Alarms

    Using the same method, click Major Alarm to display all the major alarms, in the same way, click Critical Alarm to display all the critical alarms. All the minor alarms are displayed in yellow color and all the major alarms are displayed in red colors and all the critical alarms are displayed in red color.

  • 36 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    4.6 Maintenance

    Click the icon in the left of Maintenance, and then click the sub-menu of Network configuration, following screen pops up:

    Figure 4-17 Network configuration

    In the screen as shown in Figure 4-17, user can configure the network parameters of ACU+, such as ACU+ IP address, default gateway and Mask. After modifying the network parameters, click Save Parameter to validate the change made to the parameters.

    Click the sub-menu of NMS Configure, following screen pops up:

    Figure 4-18 NMS Configuration

  • Chapter 4 Access ACU+ Through Web 37

    ACU+ Controller User Manual

    In the screen as shown in Figure 4-18, user can configure the NMS IP, authority and trap level. User can also add new NMS, modify NMS information and delete the selected NMS through the interface as shown in Figure 4-18. User can also set the trap level.

    Click the sub-menu of ESR Configure, following screen pops up:

    Figure 4-19 ESR Configuration

    In the screen as shown in Figure 4-19, user can configure the phone number and protocol for communication.

    Click Edit GC PowerSplit submenu, and the following screen shows up:

    Figure 4-20 PowerSplit Configurations

  • 38 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    In this screen, user can configure the PowerSplit parameters.

    Click User Information submenu, the following screen shows up:

    Figure 4-21 Configure User Information

    In the screen as shown in Figure 4-21, user can add a user, and the method is as follows:

    1. Enter the user name in the box at the right side of User name;

    2. Select authority of the user;

    3. Select the user type;

    4. Configure the password for the user;

    5. Finally, click Add button to add the user.

    The method to delete a user is as follows:

    (1) Select the user to be deleted in the user list;

    (2) Click Delete user to delete the user.

    The method to modify a user is as follows:

    (1) Select the user to be deleted in the user list;

    (2) Modify the user information;

    (3) Click Modify the user to validate the modified user information.

    Any user who visits user interfaces of the ACU+, such as LCD, Web interface, Console, shall be assigned with one of the following 5 security levels/user groups:

    Table 4-1 User Security Levels

    Privilege Level User Group User authority Level A Browser All users can browse power information without any writing permission. Level B Operator The operator needs to write one password for control power system

    Level C Engineer

    The engineer needs to write one password to get the following access: browsing, control, modifying parameter, downloading configuration file, but except updating application an OS and modifying, adding, deleting user information (user name, user level, password).

    Level D Administrator The administrator needs to write one password to get full access that include updating application an OS and modifying, adding, deleting user information (user name, user level, password)

    Level E Hardware An H/W switch is set that makes no writing of any kind possible to the product

  • Chapter 4 Access ACU+ Through Web 39

    ACU+ Controller User Manual

    Click the sub-menu of Time synchronization to calibrate the clock as shown in the screen below:

    Figure 4-22 Time Setting Screen

    After changing the time, click Setting to validate the new time.

    Click the submenu of Clear Data to clear the history alarm, history data, control log, battery test log and system operation log.

    Select the data to be deleted, click Clear to clear the corresponding data.

    Figure 4-23 Clear Data

    Click Restore Default Configurations submenu to restore the default configurations and restart the controller.

  • 40 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    Figure 4-24 Restore Default Configurations

    Click Restore Default and click OK, the default configuration files will overwrite the existing configuration files and all the system parameters will be restored to default values.

    Then, click Restart Controller button to restart the controller to make the default settings become effective.

    Note: If the user uses the function of restoring default configurations, the ACU+ will lose its original configurations and existing parameter settings.

    Click Download submenu to upgrade the application programs, upload the current configuration package and language package.

    You need to shut down the controller first:

    Figure 4-25 Download File: Shutdown the Controller

  • Chapter 4 Access ACU+ Through Web 41

    ACU+ Controller User Manual

    Click Shutdown Controller, the following interface shows up:

    Figure 4-26 Download file

    Click Browse. button to file the folder where the file will be downloaded. Select the file to be downloaded and then click Download.

    You can download configuration file package, application file package and language file package through ACU+, but the suffix of the file must be tar or tar.gz. You can also download the file of MonitoringSolution.cfg through ACU+. You cannot download other files through ACU+ except the above files.

    You can upload configuration file package and language package through ACU+. In the screen of Figure 4-26, select Configuration File Package or Language Package, click Upload to save the configuration file package or language package into the computer.

    Click Start Controller to restart the controller so as to validate the updated application program.

    Click the Get Parameter Settings submenu, you can save the parameter settings into the computer and then download the file to other controllers (refer to Download menu), so that the other controllers can have the same parameters.

  • 42 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    Figure 4-27 Restore Default Configurations

    Click Acquire button to save the file of SettingParam.run.

    Click the Site Inventory submenu, you can check the software version, hardware version and serial number information of the intelligent devices (such as rectifier, SMDU and IB board) connected to the ACU+.

    Figure 4-28 Restore Default Configurations

  • Chapter 4 Access ACU+ Through Web 43

    ACU+ Controller User Manual

    4.7 Configurations

    Click the Configuration menu and then select the submenu of Auto Configuration to configure the controller automatically:

    Figure 4-29 Automatic Configuration

    The auto configuration function can detect the intelligent equipment (such as SMDU, IB and EIB) connected to ACU+ and complete relevant configuration.

    Click the menu of Site Information Modification to change the site name as shown below:

    Figure 4-30 Modify Site Name

  • 44 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    After entering the site name, site location or site description, click Set to modify the site information.

    Click the menu of Equipment Information Modification to change the name of the device as shown below:

    Figure 4-31 Modify Equipment Name

    Equipment device has two device names: One is the Device name and another is the Device abbr name. The Device name is displayed in WEB and the Device abbr name is displayed in LCD.

    Enter the new device name in the column of New device name, and select what type of device name will be changed (whether to change the Device name or the Device abbr name), and finally click Set.

    Click the menu of Signal Information Modifcation to modify the signal names as shown below:

    Figure 4-32 Change Information Name

  • Chapter 4 Access ACU+ Through Web 45

    ACU+ Controller User Manual

    Similar to equipment name, each signal has two signal names: Long signal name and short signal name. The long signal name is displayed in WEB and the short signal name is displayed in LCD.

    For example: You can use following procedures to change the System Name to Bus Voltage:

    1. Select the equipment to which this signal belongs: Power system;

    2. Select the signal type to which the signal belongs: Acquisition signal

    3. Enter new signal name: Bus voltage

    4. Select the type of signal name to be changed: Long signal name or short signal name

    5. Click Set button

    For alarm signal, you can also change the alarm level for this alarm signal here:

    Figure 4-33 Change Signal Name

    In the second step in above procedures, select Alarm Signal, then the alarm signal name and alarm level are displayed. Select New alarm level and click Set to change the alarm level of this alarm signal.

    Click the Configuration of Alarm Suppressing menu to modify the shielding relationship of the alarm signal as shown below:

  • 46 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    Figure 4-34 Alarm Shielding Configuration: Select Standard Equipment

    Alarm shielding means: If Alarm A shields Alarm B, when Alarm A happens, Alarm B will not be reported even if the conditions of alarm B are met. For example, AC failure alarm will shield AC low voltage alarm. When AC failure happens, the alarm conditions for both AC failure alarm and AC low voltage alarm are met, and both alarms should be reported. However, since the AC failure alarm shields the AC low voltage alarm, only AC failure alarm is displayed in the alarm list.

    First, select the device to which the alarm signal belongs, all the alarm signals of this device will be displayed.

    Find the alarm signal to be modified, click Modify button, and then set the alarm shield expression, as shown in the Figure below:

    Figure 4-35 Alarm Shield Configurations: Select the signal number

  • Chapter 4 Access ACU+ Through Web 47

    ACU+ Controller User Manual

    After selecting the number of signals in the alarm shield expression (for example, select 2), following screen shows up:

    Figure 4-36 Alarm shield configuration: Select alarm shield expression

    In this screen, user can select the signals in the alarm shield expression and enter the logic relationship before the alarm signal (Logic AND &, Logic OR |, Logic NO !).

    Click Configuration of PLC menu to configure the PLC functions of ACU+, as shown below:

    Figure 4-37 PLC Configurations

    Click Configuration of Alarm Relay menu to configure the relevant relays of the alarm signal, as shown in the following figure:

  • 48 Chapter 4 Access ACU+ Through Web

    ACU+ Controller User Manual

    Figure 4-38 Alarm Relay Configurations

    Select the standard device first, the screen will display all the alarm signals of this device, as well as the related relay number for each alarm signal. If you need to modify the relay number, click Modify button behind the relay number