ADDC Testing and Protection Section 42608022.xls/IDMT OC-Outgoing 1/2 Setting Calculation Protocol for IDMT Overcurrent Relay Settings Station: Contract: Consultant: Contractor: Feeder ID: Outgoing Feeder (Typical) Relay: Relay Type: Numerical Relay Model: Delta Relay Make: VATECH CT Data: CT Ratio Prim. Current Sec. Current Burden, VA Class Rct 600 1 15 - 10 5P15 - Fault Data: L-L Fault L-G Fault Min. Fault Current, A 11000 8100 Max. Fault Current, A 22000 16200 FAULT SETTING CALCULATION FOR IDMT O/C General Data: Overload Current: 480 (125% of Full load current of Protected Object) PMS (Plug Multiplier Setting): 0.8 Curve Selected: Normal Inverse (NI) 2.17 sec .........Eq. 1 22.92 1.06 .........Eq. 2 0.3 sec Grading Margin (0.3sec) 0 sec 0.139 .........Eq. 3 Final TMS set at: 0.13 0.271 sec 0.433 sec (for Sample) Adopted Settings: PMS: 0.8 TMS: 0.13 10xIn Is settings co-ordinated with downstream side: Yes/No Is settings co-ordinated with upstream side: Yes/No 600 /400/1 Fault Current, If Operating time at TMS 1, sec '=0.14/ [(PSM)0.02 - 1]: PSM (Plus Setting Multiplier): '=[(Ifmin/Prim.Current) * (Sec.Rated Current/PMS)] Assuming Prot. Op. time, sec: (0.3sec) Hence TMS: ('= (0.3+0) / (Result from Eq.1) Operating time at TMS 0.125, sec '=0.14*0.125/[(PSM)0.02 - 1]: Operating time at TMS 0.2, sec '=0.14*0.2/[(PSM)0.02 - 1]: High Set (I>>):

39984912 Setting Calculation Protocol for IDMT Over Current Relay

Embed Size (px)

Citation preview

Page 1: 39984912 Setting Calculation Protocol for IDMT Over Current Relay

ADDC Testing and Protection Section

42608022.xls/IDMT OC-Outgoing 1/2

Setting Calculation Protocol for IDMT Overcurrent Relay Settings

Station:

Contract:

Consultant:

Contractor:

Feeder ID: Outgoing Feeder (Typical)

Relay: Relay Type: Numerical Relay Model: Delta Relay Make: VATECH

CT Data:CT Ratio Prim. Current Sec. Current Burden, VA Class Rct

600 1 15 - 10 5P15 -

Fault Data:

L-L Fault L-G Fault

Min. Fault Current, A 11000 8100

Max. Fault Current, A 22000 16200

FAULT SETTING CALCULATION FOR IDMT O/C

General Data:

Overload Current: 480 (125% of Full load current of Protected Object)

PMS (Plug Multiplier Setting): 0.8

Curve Selected: Normal Inverse (NI)

2.17 sec .........Eq. 1

22.92 1.06 .........Eq. 2

0.3 sec

Grading Margin (0.3sec) 0 sec

0.139 .........Eq. 3

Final TMS set at: 0.13

0.271 sec

0.433 sec (for Sample)

Adopted Settings:

PMS: 0.8

TMS: 0.13

10xIn

Is settings co-ordinated with downstream side: Yes/No

Is settings co-ordinated with upstream side: Yes/No

600/400/1

Fault Current, If

Operating time at TMS 1, sec '=0.14/[(PSM)0.02 - 1]:

PSM (Plus Setting Multiplier): '=[(Ifmin/Prim.Current) * (Sec.Rated Current/PMS)]

Assuming Prot. Op. time, sec: (0.3sec)

Hence TMS: ('= (0.3+0) / (Result from Eq.1)

Operating time at TMS 0.125, sec '=0.14*0.125/[(PSM)0.02 - 1]:

Operating time at TMS 0.2, sec '=0.14*0.2/[(PSM)0.02 - 1]:

High Set (I>>):

Page 2: 39984912 Setting Calculation Protocol for IDMT Over Current Relay

ADDC Testing and Protection Section

42608022.xls/IDMT EF-Outgoing 2/2

Setting Calculation Protocol for IDMT Earth Fault Relay Settings

Station:

Contract:

Consultant:

Contractor:

Feeder ID: Outgoing Feeder (Typical)

Relay: Relay Type: Numerical Relay Model: Delta Relay Make: VATECH

CT Data:CT Ratio Prim. Current Sec. Current Burden, VA Class Rct

600 1 15 - 10 5P15 -

Fault Data:

L-L Fault L-G Fault

Min. Fault Current, A 11000 8100

Max. Fault Current, A 22000 16200

FAULT SETTING CALCULATION FOR IDMT O/C

General Data:

Earth Fault Current: 0.2 (25% of OC PMS)

PMS (Plug Multiplier Setting): 0.2

Curve Selected: Normal Inverse (NI)

1.59 sec .........Eq. 1

67.50 1.09 .........Eq. 2

0.3 sec

Grading Margin (0.3sec) 0 sec

0.188 .........Eq. 3

Final TMS set at: 0.2

0.319 sec

Adopted Settings:

PMS: 0.2

TMS: 0.2

8xIn

Is settings co-ordinated with downstream side: Yes/No

Is settings co-ordinated with upstream side: Yes/No

600/400/1

Fault Current, If

Operating time at TMS 1, sec '=0.14/[(PSM)0.02 - 1]:

PSM (Plus Setting Multiplier): '=[(Ifmin/Prim.Current) * (Sec.Rated Current/PMS)]

Assuming Prot. Op. time, sec: (0.3sec)

Hence TMS: ('= (0.3+0) / (Result from Eq.1)

Operating time at TMS 0.2, sec '=0.14*0.2/[(PSM)0.02 - 1]:

High Set (I0>>):