Click here to load reader
Upload
sudipto-majumder
View
215
Download
1
Embed Size (px)
Citation preview
5320J 1 93 9 ENABL ED
AUT O MAI NSF AIL URE MO DUL E
F EAT URES
CANBus option to connectto the industry standard SAEJ1939 ‘Eco friendly’ enginemanagement systems providingengine protection andinstrumentation without requiringadditional senders.
Comprehensive remotecommunication via optionalRS232 port. Provides RS232Modem link to PC via either PSTNline or GSM network (using asuitable modem). The module canalso signal Engineers via their cellphones using the GSM SMSmessaging system to advise ofsystem alarms.
Optional RS485 ‘Modbus’ output.Using industry standardcommunication protocol allowsfull system integration into newand existing buildingmanagement and controlschemes.
Engine diagnostic informationremoves the need for both serviceequipment and cryptic diagnosticlamp (when using J1939 optionwith J1939 engines).
LCD 4-line text based display toprovide ‘at-a-glance’ diagnosis offault conditions, instrumentationand operating state.
Comprehensive PC configurationand status monitoring using 5xxxPC software.
PIN number protected front panelprogramming of selected trippoints and timers, allows fieldchanges to be made to themodule settings.
Built in exercise timer.
‘Sleep mode’ to ensure very lowbattery power usage when in“Off” mode.
Multiple LCD languages (English,French, Spanish, German etc.)possible.
Automatic and Manual operationmodes.
Six configurable auxiliary inputsfor connection to external faultdetection equipment.
Three configurable outputs tohelp produce complexapplications.
Integral load switch controlcapability.
DESCRI PT IO N
The Model 5320 is an Automatic MainsFailure Control Module. The module isused to monitor a mains supply andautomatically start a standby generator set.The module also provides indication ofoperational status and fault conditions,automatically shutting down the genset andindicating failures by means of an LCDdisplay, and appropriate flashing LED onthe front panel.Selected timers and alarms can be alteredby the customer from the front panel.Alterations to the system are made usingthe 810 interface and a PC. This interfacealso provides real time diagnostic facilities.It is also possible to monitor the operationof the system either locally or remotely.(Optional: Remote Communications outputversions only).Easy push button controlOperation of the module is via pushbuttoncontrols (with security locking facility)mounted on the front panel withSTOP/RESET, AUTO, MANUAL andSTART pushbuttons. The first threepushbuttons feature LED ‘selected’indications. Further pushbuttons provideLCD DISPLAY SCROLL, LAMP TEST andMUTE functions.
Microprocessor controlThe module features 16-Bit microprocessorcontrol and a comprehensive list of timersand pre-configured sequences. Thisallows demanding specifications to beachieved.
The 5320 module provides a four-line textLCD display with the followinginstrumentation displays, accessed via theLCD DISPLAY SCROLL push-buttons:
Generator Instruments:Volts, Hz, Amps, kW, kVA, cosθEngine Instruments:RPM, Oil Pressure, Coolant Temperature,Hours Run, Charging voltage, batteryVolts.SAE J1939: Enhanced instrumentationand Engine ECU diagnostics via industrystandard SAE J1939 interface when usedin conjunction with J1939 engine ECU.Mains/Utility Instruments:Volts, Frequency.
Issue 102/12/03 AM
SPECIF ICATI ON
DC Supply:8 to 35 V Continuous.
Cranking Dropouts:Able to survive 0 V for 50 mS, providingsupply was at least 10 V before dropoutand supply recovers to 5V. This isachieved without the need for internalbatteries.
Max. Operating Current:12V – 400mA24V – 200mA
Sleep Mode Current:12V – 70mA24V – 45mA
Standby Current (when in auto):12V – 230mA24V – 120mA
Auxiliary Outputs 1-3:Relay outputs -5A DC at supply voltage.Switches to battery negative when active.
Auxiliary Outputs 4 & 5:8 Amp AC rated volts-free relay
Dimensions:220mm x 160mm x 49mm(8.7’’ x 6.3’’ x 2’’)
Operating Temperature Range:-30 to +70°C
Engine ECU interface:
SAE J1939 CANbus
Deep Sea Electronics Plc.Highfield House, Hunmanby Industrial Estate,
North Yorkshire. YO14 0PH.ENGLAND
Tel:+44 (0)1723 890099.Fax: +44 (0)1723 893303.
Email: [email protected]: www.deepseaplc.com
Deep Sea Electronics inc.5301 E. State St. – Suite 202
Rockford, Illinois 61108U.S.A.
Phone: +1 (815) 316-8706Fax: +1 (815) 316-8708
Email: [email protected]: www.deepseausa.com
Deep Sea Electronics reserve the rightto change specification without notice.
UL508pending
DEEP SEA EL ECT RONI CS
T YPI CAL CO NNECT I ONS
DI MENSI ONS
57mm [2 1/4"] 240mm [9 1/2"]
172mm
[63/4"]
Panelcutout 220mm x 160mm (8.7” x 6.3”)