6 Dimensions and Weights The Senvion MM92 is generally designed for easy transport and erection. The values given in the following clauses may differ from the actual values. 6.1 Weights Weights Rotor blade approx. 8.1 t Rotor hub (incl. pitch system) approx. 18.7 t Nacelle (excl. rotor) approx. 69.2 t 6.2 Dimensions Dimensions Rotor Blade Length approx. 45.2 m Height approx. 5.0 m Dimensions Rotor Hub Diameter approx. 4.5 m Height approx. 3.4 m Dimensions Nacelle Length approx. 10.3 m Depth approx. 3.8 m Height (hood demounted) approx. 3.9 m Dimensions Drive Train (rotor, shaft and gearbox) Length approx. 4.9 m Depth approx. 3.0 m Height approx. 2.4 m Senvion MM92 [50Hz/2050kW] Dimensions and Weights PD-2.9-WT.WT.01-B-I-EN -ISO 16016 Protection Notice to be attended- Page 21 / 21

6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

6 Dimensions and Weights

The Senvion MM92 is generally designed for easy transport and erection. The values given in the followingclauses may differ from the actual values.

6.1 Weights

WeightsRotor blade approx. 8.1 tRotor hub (incl. pitch system) approx. 18.7 tNacelle (excl. rotor) approx. 69.2 t

6.2 Dimensions

Dimensions Rotor BladeLength approx. 45.2 mHeight approx. 5.0 m

Dimensions Rotor HubDiameter approx. 4.5 mHeight approx. 3.4 m

Dimensions NacelleLength approx. 10.3 mDepth approx. 3.8 mHeight (hood demounted) approx. 3.9 m

Dimensions Drive Train (rotor, shaft and gearbox)Length approx. 4.9 mDepth approx. 3.0 mHeight approx. 2.4 m

Senvion MM92 [50Hz/2050kW]Dimensions and Weights

PD-2.9-WT.WT.01-B-I-EN -ISO 16016 Protection Notice to be attended- Page 21 / 21

Page 2: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

Power Curve & Sound Power Level

[MM92/2050kW/50Hz]

Doc. no.: SD-2.9-WT.PC.03-B-H-EN2016-02-29

Page 3: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

Disclaimer [European Market]Senvion GmbH

Überseering 10D-22297 Hamburg Germany

Phone: +49 - 40 - 5555090 - 0 Fax: +49 - 40 - 5555090 - 3999

www.senvion.com

Copyright © 2015 Senvion GmbH

All rights reserved.

Protection Notice DIN ISO 16016: The reproduction, distribution and use of this document as well as thecommunication of its contents to others without explicit authorization in writing by Senvion GmbH is strict-ly prohibited. Offenders will be held liable for the payment of damages. Furthermore, all rights reserved inthe event of the grant of a patent or industrial design. Please ensure the latest versions of the applicablespecifications are used. Images do not necessarily reflect the exact scope of supply, specifications, sizeor materials and are subject to technical alterations at any time. Please note that this document may notcorrespond with project-specific requirements.

Possible work procedures described in this product description comply with German, and Senvion’s, safe-ty provisions and regulations The laws of other countries may provide for additional safety specifications.

It is essential that all safety measures, both project- and country-specific, be strictly complied with. It isthe duty of each customer to inform itself, implement and comply with these measures.

The applicability and validity of relevant legal and/or contractual provisions, technical guidelines, DINstandards and other comparable regulations are not excluded by the content or examples contained inthis product description. Moreover, such contractual provisions and regulations shall continue to applywithout any limitation.

All information contained in this product description is subject to change at any time without notice to, orapproval by, the customer. Senvion GmbH and/or its affiliates assume no liability for any errors or omis-sions in the content of this product description. Legal claims against Senvion GmbH and/or its affiliatesbased on damage or injury caused by the use or non-use of the information included herein or the use oferroneous or incomplete information are excluded.

Although Senvion GmbH strives to provide information which is accurate and makes this informationavailable to customers in good faith, no representation or warranty is made or guarantee given as to itsaccuracy or completeness. The sole applicable warranties in respect of the products described hereinshall be those provided in a contract executed by an authorized representative of Senvion GmbH. EX-CEPT AS PROVIDED IN SUCH EXECUTED CONTRACT, Senvion MAKES NO WARRANTIES, EX-PRESS OR IMPLIED, AS TO THE PRODUCT SPECIFICATIONS, PRODUCT DESCRIPTIONS OR THEPRODUCTS HEREIN DESCRIBED. TO THE EXTENT PERMITTED BY LAW, Senvion EXPRESSLYDISCLAIMS ALL IMPLIED WARRANTIES, INCLUDING THE IMPLIED WARRANTIES OF MERCHANT-ABILITY, FITNESS FOR A PARTICULAR PURPOSE, TITLE AND NONINFRINGEMENT.

All brands, trade-marks or product names mentioned in this document are the exclusive property of theirrespective owners.

Power Curve & Sound Power Level [MM92/2050kW/50Hz]Disclaimer [European Market]

Page 2 / 10-ISO 16016 Protection Notice to be attended-

SD-2.9-WT.PC.03-B-H-EN

Page 4: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

Table of contents

1 Introduction .................................................................................................... 5

2 Conditions for the measurement and scope of the power curve and soundpower level ..................................................................................................... 6

2.1 General information ................................................................................................... 6 2.2 Conditions for the measurement and scope of the power curve ............................... 6 2.3 Conditions for the measurement and scope of the sound power level ..................... 7

3 Electrical power curve and sound power level ............................................... 8 3.1 Electrical power curve ................................................................................................ 8 3.2 Sound power level according to IEC .......................................................................... 9 3.3 Sound power level according to FGW Guideline at 95 % of rated power .................. 10

Power Curve & Sound Power Level [MM92/2050kW/50Hz]Table of contents

SD-2.9-WT.PC.03-B-H-EN-ISO 16016 Protection Notice to be attended- Page 3 / 10

Page 5: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

Applicable Documents

The documents referred to in the table below are included for information only. Reference to them in thisproduct description does not make them part of the contract.

Title Document-No.

* If the products referred to in the table above are to be included within the project, the relevant productdescriptions in their current version will be amended to the contract.

List of Abbreviations and Units

Abbreviations/Units DescriptioncP Power coefficientcT Thrust coefficienthh Hub heightLWA Sound power levelΔLa,k Tonal audibilityFGW Fördergesellschaft Windenergie e.V.IEC International Electrotechnical Commissionv Wind speed at hub heightv10 Wind speed at 10 m heightvout Cut-out wind speedWTG Wind turbine generator

Power Curve & Sound Power Level [MM92/2050kW/50Hz]

Page 4 / 10-ISO 16016 Protection Notice to be attended-

SD-2.9-WT.PC.03-B-H-EN

Page 6: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

1 Introduction

This document shows the power curve and sound power level of the Senvion MM92/50 Hz and the corre-sponding measurement conditions.

Power Curve & Sound Power Level [MM92/2050kW/50Hz]Introduction

SD-2.9-WT.PC.03-B-H-EN-ISO 16016 Protection Notice to be attended- Page 5 / 10

Page 7: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

2 Conditions for the measurement and scope of the powercurve and sound power level

2.1 General informationRotor diameter: 92.5 m

Cut in wind speed: 3.0 m/s

Cut out wind speed: 24.0 m/s

Wind speed at hub height: 10 min. mean value

2.2 Conditions for the measurement and scope of the power curve Verification according to IEC 61400-12-1: 2005

Turbulence intensity: 6 to 20 %

Terrain: not complex acc. to IEC 61400-12-1: 2005

Vertical wind shear coefficient (measured betweenhub height and lower blade tip):

0 to 0.3

Air density at location (10 min. mean value): ≥ 1.13 kg/m3

Temperature range: acc. to related standard conditions of use

Anemometer type: Thies First Class Advanced

Blades: clean, without ice or snow formation

For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure“Power Performance Measurement Procedure – Version 5, December 2009” chapter 3.9 has to be fol-lowed. In addition, no obstacles with a height greater than 1/3 of the distance between the ground and thelowest blade tip position shall exist in the measurement sector within 0-4 rotor diameters of the WTG ormet mast.

Fig. 2.2 - 1: Arrangement of a measuring unit for the power curve measurement

Power Curve & Sound Power Level [MM92/2050kW/50Hz]Conditions for the measurement and scope of the power curve and sound power level

Page 6 / 10-ISO 16016 Protection Notice to be attended-

SD-2.9-WT.PC.03-B-H-EN

Page 8: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

2.3 Conditions for the measurement and scope of the sound powerlevel

Verification acc. to IEC 61400-11: 2002 + A1: 2006, orTechnische Richtlinie für Windenergieanlagen Teil1: Rev. 18 der FGW

Roughness length (average peak): 0.05 m

To determine the wind speed during the sound measurement of the operating turbine, Method 1, as out-lined in 7.3.1.1 of the IEC standard 61400-11, shall be applied.

Power Curve & Sound Power Level [MM92/2050kW/50Hz]Conditions for the measurement and scope of the power curve and sound power level

SD-2.9-WT.PC.03-B-H-EN-ISO 16016 Protection Notice to be attended- Page 7 / 10

Page 9: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

3 Electrical power curve and sound power level

3.1 Electrical power curve

Values related to an air density of 1.225 kg/m3

Wind speedv [m/s]

PowerP [kW]

Thrust coefficientcT [-]

Power coefficientcP [-]

3.0 20 0.98 0.1804.0 94 0.87 0.3575.0 205 0.79 0.3986.0 391 0.79 0.4407.0 645 0.79 0.4578.0 979 0.79 0.4659.0 1375 0.74 0.45810.0 1795 0.69 0.43611.0 2000 0.54 0.36512.0 2040 0.39 0.28713.0 2050 0.29 0.22714.0 2050 0.23 0.18215.0 2050 0.19 0.14816.0 2050 0.15 0.12217.0 2050 0.13 0.10118.0 2050 0.11 0.08519.0 2050 0.09 0.07320.0 2050 0.08 0.06221.0 2050 0.07 0.05422.0 2050 0.06 0.04723.0 2050 0.06 0.04124.0 2050 0.05 0.036

The electrical power is valid for pure active power set points.

The electrical power is valid for the low-voltage side of the transformer.

Power Curve & Sound Power Level [MM92/2050kW/50Hz]Electrical power curve and sound power level

Page 8 / 10-ISO 16016 Protection Notice to be attended-

SD-2.9-WT.PC.03-B-H-EN

Page 10: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

3.2 Sound power level according to IEC

The sound power levels given below exclude measurement uncertainty. With the established soundmeasurement methods (see chapter 2.3) there might be deviations of around +/- 1 dB(A) due to themeasurement uncertainty.

In case an approving authority or an external consultant does not consider uncertainty or considers anuncertainty of less than 1 dB(A) for the sound propagation modelling, a measurement uncertainty of atleast 1 dB(A) shall be added instead to the sound power levels provided below. The measurement uncer-tainty has to be taken into account for the maximum sound power level within permits.

There is no tonal audibility ΔLa.k > 0 dB (for v10 ≥ 6 m/s).

Sound Power Level according to IEC for wind speed at hub height

Wind speedv [m/s]

Sound Power LevelLWA [dB(A)]

5.0 90.15.5 92.86.0 96.06.5 98.57.0 100.57.5 101.58.0 102.08.5 102.59.0 102.89.5 103.1

10.0 - 24.0 103.2

Sound Power Level according to IEC for wind speed at 10m height

Wind speedv10 [m/s]

Sound Power Level LWA [dB(A)]63.75 - 64.75m 68 - 68.5m 78 - 80m 98 - 100m

3.0 89.2 89.2 89.2 89.23.5 89.5 89.5 89.7 90.24.0 92.5 92.5 93.3 94.44.5 96.7 96.7 97.4 98.35.0 99.9 99.9 100.4 100.95.5 101.5 101.5 101.7 101.96.0 102.2 102.2 102.4 102.56.5 102.7 102.7 102.8 103.07.0 103.1 103.1 103.1 103.2

7.5 - vout 103.2 103.2 103.2 103.2

Power Curve & Sound Power Level [MM92/2050kW/50Hz]Electrical power curve and sound power level

SD-2.9-WT.PC.03-B-H-EN-ISO 16016 Protection Notice to be attended- Page 9 / 10

Page 11: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

3.3 Sound power level according to FGW Guideline at 95 % of ratedpower

Independently of the hub height, the sound power level, measured according to the "Technische Richtli-nie für Windenergieanlagen Teil1: Rev. 18 der FGW" at 95 % of the rated power is:

LWA,95 % = 103.2 dB(A)

This sound power level excludes measurement uncertainty. With the established sound measurementmethods (see chapter 2.3) there might be deviations of around +/- 1 dB(A) due to the measurement un-certainty.

In case an approving authority or an external consultant does not consider uncertainty or considers anuncertainty of less than 1 dB(A) for the sound propagation modelling, a measurement uncertainty of atleast 1 dB(A) shall be added instead to the sound power level provided above. The measurement uncer-tainty has to be taken into account for the maximum sound power level within permits.

Power Curve & Sound Power Level [MM92/2050kW/50Hz]Electrical power curve and sound power level

Page 10 / 10-ISO 16016 Protection Notice to be attended-

SD-2.9-WT.PC.03-B-H-EN

Page 12: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure
Page 13: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure
Page 14: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure
DT&S
Senvion_Schrift_regular
DT&S
Drafting Stamp new
DT&S
Drawing Alternate DinA3-DiA0
DT&S
Senvion_Schrift_regular
Page 15: 6 Dimensions and Weights - Windpark Ferrum...For obstacle assessment, IEC 61400-12-1: 2005 Annex A.2 together with the MEASNET procedure “Power Performance Measurement Procedure

10280

3864

x

(3140)

5303

y

8 x 100/160 kNAnschlagpunkt /lash point

zb

Transportgewicht incl. Transportgestell: 50 Hz = 69 t / 60 Hz = 72 ttransport weight incl. transport cradle: 50 Hz = 69 ton / 60 Hz = 72 ton

every data in mmAlle Angaben in mm

2 x 160/240 kNAnschlagpunkt /lash point

Zurrkraftangaben: Seetransport/Strassentransportdata of lashing forces: shipping/road transport

3725

2500

(a)

gesamte Auflagefläche hinteresTransportgestell 0,5 m²

gesamte Auflagefläche vorderesTransportgestell 1,3 m²total bearing area front transport cradle 1,3 m²

total bearing area back transport cradle 0,5 m²

max 10 x 300 kNAnschlagpunkt / lash point

8765

F

E

D

C

B

A

4321

1 2 3 4 5 6 7 8

F

E

D

C

B

A

Weitergabe sowie Vervielfältigungdieses Dokuments, Verwertung undMitteilung seines Inhalts sindverboten, soweit nicht ausdrücklichgestattet. Zuwiderhandlungenverpflichten zu Schadenersatz.Alle Rechte für den Fall derPatent-, Gebrauchsmuster- oderGeschmacksmustereintragungvorbehalten.

The reproduction, distribution andutilization of this document as wellas the communication of itscontents to others without explicidauthorization is prohibited.Offenders will be held liable forthe payment of damages. All rightsreserved in the event of the grantof a patent, utility model or design.

PDM Dok ID

A3

Plot:

Stückzahl proAnlage/ No. ofPieces per Turbine:

.

..

R. Rieckenberg08.03.2007

M. Brückner08.03.2007

J. Lütjen08.03.2007

. .1:50

MM 92 - 50/60 Hznacelle - COG, transportGondel, Schwerpkt. Transport

BD-2.9-GP.MA.19-B

F:\2.9_ _MM92\GesamtProjekt\Mass_Abmessg_transp\Untersuchung\D-2.9-GP.MA.19-B-B..

1/1

08.03.2007

ToleranceDIN ISO 8015

DIN ISO 2768-mHH

DIN ISO13715

+-

Schutzvermerk DIN ISO 16016

Protection Mark DIN ISO 16016SAP-No.: Pos.-Nr.: (Ers.d. / repl.by:)(Ers.f. / repl.for:)

Unterbennung / subtitle

DIN-Blatt/DIN-Sheet

Datum/date

be strictly observed!Indicated Specification has to zwingend zu beachten!Angegebene Spezifikation ist

freigegeben/released:

geprüft / checked:

gezeichnet / drawn:

Version / Revision

Workflow Status

Zeichnungsnummer / Drawing Number

Benennung / Title

Werkstoff / Material:

Name/name

Gewicht / Weight:Maßstab / Scale:

EDP NO.

Blatt/Sheet

D&TS
Document Stamp