F I R E S Y S T E M S
Self DiagnosticIntelligentFire Detectors
PREVENTING FALSE ALARMS
Self Diagnostics
Each detector in the 700 seriescon- tinually monitors its ownsensitivity and operationalstatus. Once a day, it performsa full diagnostic test whichincludes dynamically testing thesensing chamber and internalelectronics. If a detector driftsout of its sensitivity range orfails internal diagnostics, theyellow trouble LED will indicate.
Background drift is dailycompensated to maintain theoriginally calibrated sensitivity.The thresholds are not compensatedbeyond EN 54 limits for sensitivity.A failure of the sensing chamberis reported back per zone to theFP 800 series panels.
MAINTENANCE FRIENDLY
Sensitivity level test mode
The photoelectric detectorincludes a sensitivity test modethat is activated by holding amagnet near the integral reedswitch. This initiates the selfdiagnostic routine and providesvisual indication if service isrequired.This test mode allows fieldsensitivity testing without therequirement for external meters.
Field cleaning and service
The photoelectric sensing chamberunsnaps from the detector foreasy field cleaning and service.Once a year (or more in dustyenvironments), one should openthe detector cover, snap off andthrow away the optical chamber.Vacuum and/or filtered com-pressed air can be used to removedirt from the optical base. Thensnap a new optical chamber backin place and re-check the sensi-tivity.
THE RIGHT DETECTOR FOR THE RIGHT JOB
The 700 Series comprises a vastrange of sensors : optical and heatsensor. The detectors are alsoavailable with onboard C/O relay.
For a truly fast and broad spec-trum detection, there is themulticriteria optical/heat sensor.The interaction of both thesmoke and heat algorithms ensurea quick response to both flamingand smouldering fires.
The universal bases are availablein 2 sizes to suit your applica-tion. All bases are provided withan integral locking tab for extrasecurity reasons if required.They are also equipped with ashorting bar between IN and OUTwhich opens when the head isinstalled and can be manuallyrestored when removing the head.
nnnnn Automatic SelfDiagnostics- Dynamic full detector
test- Sensitivity test
nnnnn Manual Self Diagnosticroutine with visualsensitivity indication
nnnnn Field sensitivity testingwithout external meters
nnnnn Field exchangeable anddisposable opticalchamber
nnnnn High false alarmimmunity
nnnnn Floating backgroundwith drift compensation
nnnnn Separate fire andtrouble LED
nnnnn 12 - 24 V dc operationnnnnn Polarity insensitivennnnn Full range : optical and
heat sensorsnnnnn Multi criteria sensor :
optical/heatnnnnn Fully compliant with
EN 54
700 Series
SLC Technologies Europe & AfricaHeadquartersExcelsiorlaan 28B-1930 ZaventemTel. : ++ 32 2 725 11 20Fax : ++ 32 2 721 40 47
How to order
F I R E S Y S T E M S
DP 700 DT 700
Operating voltage 8.5 - 33 V dc FWR
Current consumptionQuiescent at 24 V dc 100 µA; Max. 70 µA averageIn alarm at 24 V dc 60 mA
Alarm indication White LED Red LED(red alarm)
Fault indication Yellow LED
Remote alarm output 30 mA
RY contact rating 2 A @ 30 V dc;1 A @ 120 V ac
Humidity 0-95% Non condensing
IP rating IP 43
Heat specificationMax. - 57º C ± 1.5º CR.O.R. - 8º C/min and > 40° C
Sensitivity 10%/m(+1.6% - 3.3%)
Reset voltage 2,5 V max
Reset time 1 sec
Dimensions 10 cm Ø, H = 5 cm
DP 721 .... Photoelectric smokedetector head
DP 721 I .... Photoelectric smokedetector head withremote alarm LED output
DP 721 T ..... Photoelectric smokedetector and heatdetector head withremote alarm LED output
DP 721 R ..... Photoelectric smokedetector head with C/Orelay output
DP 721 RT .. Photoelectric smokedetector and heatdetector headwith relay output
DP 721 RTA Photoelectric smokedetector and heatdetector head with relayoutput, autoreset
DT 713-5R . 57º C fixed andrate-of-rise heatdetector
DT 713-5 .. 57º C fixed and R.O.Rheat detector,with relay output
DT 713-7 .. 70º C fixed and R.O.Rheat detector
DB 701 .... 10 cm diameter base- 3 terminals
DB 701 U . 15 cm diameter base- 3 terminals
DB 702 .... 10 cm diameter base- 6 terminals
DB 702 U . 15 cm diameter base- 6 terminals
DB 703 .... Transition base600 series to 700 series
211 ......... Set of 10 fieldexchangeable opticalblocks
Technical data
The 700 Series complies with the essential requirementsof the EMC directive 89/336/EMC