Electrical systems for SCES#10 and 11 TECHNICAL ANNEXURES AND BOM Annexure-1(A) SUPPLY OF LT POWER CABLE: -1100V RATED (Sl no. 1 and 2 of Table-I) GENERAL TERMS: A. Compliance for Tender Specification shall be clearly mentioned. LT POWER CABLE: 1100V RATED, XLPE INSULATED , ALUMINIUM CONDUCOR & STEEL STRIP ARMOURED. Sn Technical Specification 1. Type LT - XLPE Power Cable (Cable code :- A2XFY) 2. Voltage grade 1100 V 3. Size As per (Table-I –BOM- Sl no.1& 2) of the tender (3.5Core X 240 sqmm ) (3.5CoreX 185 sqmm ) 4. Conductor Stranded aluminum wires confirming to IS 8130 with latest amendments. 5 Core Identificatio n As per IS 7098 / Part -1,1988 with latest amendments. Red, Yellow, Blue for phase and Black for ½ core (neutral) 6. Insulation Cross linked polyethylene XLPE 7. Inner Sheath Insulating material of Vulcanized or unvulcanized rubber or Thermoplastic materials. 8. Armour flat Steel strip 9. Outer sheath Overall extruded PVC as per IS 5831-1984 with latest amendments. 10. Standards The cable shall confirm to IS 7098 / Part -1,1988 with latest amendments. 11 Embossing on the cable outer sheath Following details to be printed on the outer sheath for every one meter of cable 1100V, ,No. of Core & Size of Cable' sequential Length and manufacturer’s name. 12. Inspection Cable shall be offered for inspection at works before dispatch. All the routine and acceptance tests as per the relevant IS are to be conducted. Also type test reports to be submitted for verification

A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

Electrical systems for SCES#10 and 11 TECHNICAL ANNEXURES AND BOM

Annexure-1(A)

SUPPLY OF LT POWER CABLE: -1100V RATED

(Sl no. 1 and 2 of Table-I)

GENERAL TERMS:

A. Compliance for Tender Specification shall be clearly mentioned.

LT POWER CABLE: 1100V RATED, XLPE INSULATED , ALUMINIUM CONDUCOR & STEEL STRIP ARMOURED.

Sn Technical Specification

1. Type LT - XLPE Power Cable (Cable code :- A2XFY)

2. Voltage grade

1100 V

3. Size As per (Table-I –BOM- Sl no.1& 2) of the tender (3.5Core X 240 sqmm ) (3.5CoreX 185 sqmm )

4. Conductor Stranded aluminum wires confirming to IS 8130 with latest amendments.

5 Core Identification

As per IS 7098 / Part -1,1988 with latest amendments. Red, Yellow, Blue for phase and Black for ½ core (neutral)

6. Insulation Cross linked polyethylene XLPE

7. Inner Sheath

Insulating material of Vulcanized or unvulcanized rubber or Thermoplastic materials.

8. Armour flat Steel strip

9. Outer sheath

Overall extruded PVC as per IS 5831-1984 with latest amendments.

10. Standards The cable shall confirm to IS 7098 / Part -1,1988 with latest amendments.

11 Embossing on the cable outer sheath

Following details to be printed on the outer sheath for every one meter of cable 1100V, ,No. of Core & Size of Cable' sequential Length and manufacturer’s name.

12. Inspection Cable shall be offered for inspection at works before dispatch. All the routine and acceptance tests as per the relevant IS are to be conducted. Also type test reports to be submitted for verification

Page 2: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

2

13. Make As per annexure-A

14. Quantity tolerance

± 5%

Annexure-1(B)

Laying of LT UG cable in ground (Sl no. 3 of Table-I)

Sl NO. Description of work 1 LT CABLE LAYING IN GROUND;; Laying of following sizes 1.1kV rated,

3.5 Core /4 core, aluminum conductor XLPE insulated cables in ground in all kinds of soil , at 750mm below ground level including transportation of cable to site, excavation, refilling with river sand and baked bricks on sides and on top, providing cable route / joint markers complete and as per drawing no. MCF_TSF_ES:10&11/2 and MCF_TSF_ES:10&11/3

Annexure-1(C)

Laying of LT UG cable in existing Trench / cable tray (Sl no. 4, 5, 14 20 and 33 of Table-I)

Sl NO. Description of work 1 LAYING OF LT CABLE IN EXISTING TRENCH/PIPE: Laying of

following sizes , 1.1kV rated, 3/4/5/3.5 Core , aluminum /copper conductor XLPE insulated /PVC insulated , armoured /unarmoured/ shielded cables in existing concrete trench / on cable tray / on wall / floor / ceiling / above false ceiling / existing hume pipe / existing HDPE pipe including transportation of cable to site, removing of trench /false ceiling covers and reclosing the covers after laying the cables in good condition with supply of all necessary materials such as brackets, clamps , MS spacers, cable ties complete as required and as directed by Engineer-in-charge

1.1 Single/ two/ three runs of cables from 1.5 sqmm to 240 sqmm size cables

Page 3: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

3

Annexure-1(D)

Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I)

1 End termination of LT cables:- Providing end terminations for following sizes, 3/4/5/3.5 /Core X 1.1 KV grade XLPE/PVC insulated armoured / unarmoured/shielded, copper / Aluminium conductor cables including supply of flange type cable gland/PVC cable gland, copper heavy duty , long barrel lugs, neoprene bushes and other materials and tools required for completing the terminal connections, earthing of gland as required and as directed by EIC. Type of gland will be selected by the Engineer-in-charge.

1.1 1.5/2.5/4/6/10/16/50/95/185/240 sqmm cables of all types as mentioned above

Page 4: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

4

Annexure-2(A) POWER CONTROL CENTRE – SCES#10, SCES#11and SCES11 UPS INPUT PANEL Sl no.7,8,9,15, 17 and 22 of Table-I.

1. Instructions

1. GA drawing of the PCC panel to be furnished with super imposed SLD and bus bar configuration and dimension of the offered panel to be furnished.

2. Make for all the items in BOM shall be furnished. Also the make shall be one among the approved brands enclosed

2. Scope of work

1. Design, manufacture, testing, supply, installation & commissioning of the PCC as per the SLD considering applicable mechanical & electrical safety standards.

2. Panel fabrication and integration of switchgears shall be as per the approved General Assembly drawing.

3. Routine test of the panels at works prior to dispatch as per IS. 4. Input & output switchgears is also included in the scope of the Vendor as

per the details mentioned in the BOM 5. Panel shall be suitable for indoor applications.

3. General requirements

1. Make

a. Anyone make of switchgear among specified in bill of material only to be selected and used in the panel.

b. Make of switchgear should be same, i.e., make of SDFUs, ACB, Fuses etc of all ratings should be same

c. Any left out or additional requirements of switchgears, spares and control accessories shall be included.

2. Calibration

a. Protective devices, Relays & Current Transformers calibration to be carried out by NABL accredited party other than manufacturer

4. Technical specifications

1. Designs standards complies to

a. National Electrical Code (NEC)/IS b. Latest IE rules.

5. Electrical requirements

1. Rating: 400 KVA, Bus bar continuous current carrying capacity shall be 120% of the rated kVA at 380 VAC.

2. Input: 360 to 440VAC at 50 Hz, 3-phase, four-wire-plus-ground. 3. Output: 415 / 230 VAC 3-phase, four-wire-plus-ground, wye

configuration. 4. Operating PF: From 0.5 lead to 0.5 lagging. 5. Short time rating: Short time withstand current more than 36 kA RMS for

1 sec.

Page 5: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

5

6. Environmental requirements

1. Storage temperature range shall be 0° to + 60°C 2. Operating temperature range shall be 0° to 50°C 3. Operation shall be reliable in an environment with 0% to 95% non-

condensing RH.

7. Fabrication

1. Panel design

a. Free standing, floor mounting and suitable for indoor installation. b. Profile should have holes of standard size punched at standard pitch

throughout the length. c. All the external face of the panels and doors shall be made of minimum

2mm thick MS sheet . Inside partitions shall be with minimum1.6mm thick d. Mounting plate’s -Mild steel, 2 mm, epoxy polyester powder coated. e. The panel shall have easily removable and interchangeable sections. f. Horizontal busbars are to be located at the top of the panel. g. High tensile strength fasteners shall be used for panel, consisting of

hexagonal bolt –1 no, flat washers –2 nos, spring washers –1 no and hexagonal nut –1 no) shall be provided for each termination point.

h. The length of the hexagonal bolt shall be adequate for insertion of 3 lugs of requisite rating.

i. Required service clearances shall be provided to carry out preventive and remedial maintenance from front and rear side.

j. The panel shall be naturally convection-cooled & shall allow continuous full-load operation, maintaining the temperatures within tolerance level of components.

k. Each bus bar compartment should have a barrier with 1.6 mm (or more)thick.

l. All other external covers/ doors/ all the six sides etc shall be with 2mm thick.

m. Proper fixing arrangement shall be made for mounting metering & protection current transformers.

n. The degree of protection for the panel shall be IP 31. o. ISMC 100 base channel to be provided on all the four sides.

2. Panel dimension

Width : As per design requirement. Depth : Shall not be more than 900 mm Height : Shall not be more than 2200 mm (including plinth) Plinth : Shall be 100 mm height with ISMC100 MS channel

a. Ground clearance: Minimum ground clearance for switchgear mounting shall be 350 mm including plinth.

b. Switchgears operation: Switchgears are to be mounted in such a way its handle operation shall confirm to per IS 4237 a. ON Closing –Clockwise i.e., Vertically upward b. OFF Opening –Anti-clockwise i.e., Vertically down ward

c. Plinth: The panel shall be supplied along with base plinth of 100 mm height for each transportable modular section and shall be made of C –

Page 6: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

6

channel forming sectional ‘Box’.

3. Door

a. Doors shall be with concealed hinges and flush type locks. b. Doors that are bolted for busbar chambers should be flush in design

such that the bolt head and the door surface are in one level. c. High quality door gasket should be used for dust and vermin proof. d. Each bolt shall have plastic washers on the inner side of the door such

that the bolt will remain with the door on removal of the door. e. The switch handle shall be interlocked such that the door of enclosure

cannot be opened unless the switch is in OFF position, however, mechanical interlock defeat mechanism has to be provided.

f. All rear doors shall be of hinged type with locking arrangement at three places (top, middle and bottom) and with 2mm thick sheet

g. All horizontal and vertical bus bars chamber covers shall be of bolted type.

h. Hinged doors shall be provided for all switchgear compartments. i. Stiffeners are to be provided for all rear doors for mechanical strength.

4. Cable compartment

a. Cable entry gland plates shall be provided at the bottom. b. Each gland plate shall be of GI with 3mm thickness & adequately

supported. c. Independent, detachable gland plates for each cable considering 2 cables

/ outlet shall be provided at the cable compartments & terminal chamber.

d. Liberal space shall be provided in the cable compartment as well as switch compartment to facilitate termination of cables.

e. Provision shall be made for proper clamping of the cables above the glands and cable clamps to avoid weight of cables acting directly on the termination.

f. Wide cable alley shall be provided for easy bending and termination of cables. Space shall be sufficient for minimum three runs of 3.5C X 300sqmm ,Aluminium conductor, XLPE insulated armoured cable.

g. All the incoming and outgoing bus bars are to be brought up to the cable chamber for easy termination. Also for the lesser rated output switches(<63A rated) , output cables are to be brought up to cable chamber and terminated in the suitable rated/size screw less type TB’s.

5. Painting

a. Surface treatment: Seven tank process to be done as per standards. b. Type: Epoxy polyester powder coated c. External Finish: Mat or Gloss d. Color: Outer surface of the panel –Siemens gray. (color code IS: 952) e. Plinth –Black

6. Bus bar System

Page 7: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

7

a. Material: High-purity electrolytic Aluminium complying to IS 5082-1981, 63401-WP

b. Electrical Conductivity shall be 100% c. Main bus bar rating shall be 120 % of 400 kVA, continuous current

rating d. Distribution bus bar rating shall be 120 % of the switchgear rating

connected e. N –busbar rating shall be 50% of the phase busbar rating f. Busbar system shall be TPN-E g. Phase sequence arrangement shall be N-R-Y-B from rear to front. h. Should not raise 400C above ambient temperature as per IS 4237 i. Bus duct for Main PCC of SCES#10 and 11 ( Sl no. 7 & 8 of BOM)

External Bus ducts with TPN aluminium bus bars are to be provided for connecting Q3 to Q2 / Q6 and Q7 to Q6. PCC to be split in to two sections for connecting feeder 1 and feeder2 input power supply and connected through two nos. of bus ducts as mentioned above. As per as possible, size of the two sections are to be matched. Two sections are planned to install in “L” shape or as per requirement.

7. Bus bars supporting insulators

a. Material shall be self-extinguishing moulded fiberglass reinforced thermosetting plastic or equivalent.

b. Higher mechanical strength, High dielectric strength, High temperature with stand capability, Nonflammable, Non hygroscopic & Ribbed construction to prevent tracking

8. Bus bars protection

a. Horizontal and vertical bus bar should be enclosed in a separate chamber.

b. Horizontal bus bars, vertical bus bars, switchgear input bus bars and switchgears output bus bar are to be totally sleeved with color coded heat shrunk PVC to protect against accidental contact and tracking caused by dust, humidity and vermin.

9. Cabling / Bus bar extension

a. Separate chamber for the cabling shall be at the rear side of the panel. b. It should be separated from the bus bar zone and switchgear

compartment. c. The control cables and terminals are to be mounted in a separate

compartment. d. All the outgoing bus bars are to be brought up to cable chamber for

proper terminations. Also for smaller size switchgear, out goings terminals are to be extended by using suitable single core copper cable and terminated in the screw less type TB’s

10. Safety interlock

a. The door cannot be opened unless the breaker is in ‘Isolated position’.

Page 8: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

8

b. The door cannot be opened unless MCCB / SDFU is in OFF position. c. Defeat facility shall be provided to facilitate testing / inspection for all

switchgears. d. Also interlock between Q1,Q2and Q3 and Q5,Q6 and Q7 are to be

provided (Only for main PCC under sl No.7 and 8 of the BOM)

11. Wiring

a. Cable shall be FRLS, single core multi strand electrolyte grade, annealed copper cable, confirming to IS: 694 / 1990

b. Size & Rating shall be 1.5 sq-mm, 1.1 kV grade for all control / interlock wiring & 2.5 sq-mm, for all CT related wiring.

c. Power cable of suitable size for SDFUs / MCBs of rating up to 63 A. d. Color of the cable shall be Gray for control wiring. e. Cage clamp type din rail mounting, cage clamp terminal connectors

shall be used for all control and power wiring up to 63A. f. Standard ferruling concept shall be followed for clear identification of

control circuit. wiring as per IS 375

12. Name plates / stickers

a. Nameplates for each incomer and outgoing feeder outlets shall be provided.

b. Each nameplate shall contain feeder no, switchgear rating and nomenclature.

c. Nameplates size, design, and color combination and nomenclature for each output feeder will be furnished during approval of drawing.

d. The approved SLD of the panel shall be screen-printed / computerized print over an A3 size 2 mm thick aluminum sheet or foam board. It shall be fixed at top-center of the panel.

e. Laminated stickers of suitable size with good quality adhesive shall be fixed at each terminal blocks, meters, relays on the inner side for clear identification.

f. Panel specification plate shall have the specification plate as per the IS reference standard 2675

13. Grounding / Earthing

a. Two-point ground in accordance with the recommendations of IEEE Standard and the requirements of the NEC.

b. Panel earth bus of high-purity electrolyte copper of size 50x6 mm should be run all along the width of the panel at front or rear bottom surface.

c. All ACBs and switchgears body shall be earthed by 25x3 mm copper strip.

d. Panel doors shall be earthed, if electrical equipment (meters / relays / lamps) mounted by a yellow green 2.5 Sq. mm wire lugged at both ends.

e. All meters / relays shall be earthed to the profile by a yellow green 2.5 Sq. mm wire lugged at both ends.

Page 9: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

9

14. Inspection / Testing

a. First stage inspection Mechanical -structural fabrication after approval of GA drawing. Verification of components as per PO bill of material. Minor modifications in mechanical / electrical changes pointed out by MCF inspecting officer shall be carried out, if necessary, without additional cost.

b. Final inspection & testing After integration of switchgears and wiring. Inspection and testing as per checklist. Calibrated testing & measuring instruments are to be used for routine

test. Any deviations from the specifications or in testing shall be attended & offered for re-inspection.

15. Documentation shall comprise

a. Party to submit the PDR document for approval within 15 days after receiving the purchase order.

b. PDR document shall contain –SLD, GA drawing with superimposed busbar configuration, Structural details of PCC, Make and Catalogue number of switchgears & accessories, Control circuit drawing and Delivery schedule.

c. As built GA, SLD, Control drawing &busbar layout configuration in A3 size.

d. Meters / Protective Relays operating manuals, test & calibration certificates.

e. Metering / Protection CT’s calibration certificates f. Bill of actual material used with make, catalog no and quantity. g. Routine / Acceptance test results as per standard. h. Specific instructions for installation and operation / maintenance

procedures. i. Document shall be supplied in duplicate with hardbound cover having

printed title. j. The entire document is to be copied & supplied in CD.

16. General requirements.

a. Control power supply to Meters, Relays, interposing relays & shall be taken through modular fuse holder with HRC fuse links.

b. Change over contacts, aux. contacts wiring of shall be terminated to separate terminal blocks with cage clamp TBs no for clear identification.

c. Each terminal connector to be numbered and their input & output details to be provided.

d. All auxiliary contacts of Switchgears Relays, ACBs and CT outputs shall be brought to cage clamp type TBs.

Page 10: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

10

e. Emergency Power OFF (EPO) switch shall shut down the unit by activating the shunt trip of the ACBs in local & remote operation.

f. Potential free contacts for ON and OFF positions of all the incoming switches with necessary contacts based on switch position are to be provided (NO & NC contacts). Also Close and open (ON and OFF) remote command (From SCADA) interface provision to be provided (Required only for incoming ACB/SDFU/MCCB).

Page 11: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

11

BOM for Main Power control Centre for SCES#10- BOM-2A (Sl no.7 of Table-I) NOTE:- Refer Drawing No. MCF_TSF_ES 10: DRG4(1)&4(2) and technical annexure-2(A)

S/n Description Qty

1

Air Circuit Breakers -ACB (For F # 1 & # 2 Incomers) Rated operational voltage -415V 50Hz AC, Rated current -630A, 3 Poles, EDO type, Type of closing: Stored energy type (Motor operated), Motor voltage: 240 VAC, Closing electromagnet: 240 VAC, Wiring scheme: 3Ph, 4 wire, Auto reset, Door interlock, Castle lock with key, Rated insulation voltage: 690 VAC, Utilization category -B Breaking capacity (Ics) at 415V, 50Hz –minimum 36 kA, , Making capacity (Icm) at 415V, 50Hz -105 kA peak. Confirming to IS 13947 (Part 2) / IEC 60947-2. Accessories: Auxiliary contacts: 4NO+4NC, Safety shutters / Inter phase barriers, Shunt release: 240 VAC/24V DC, Operation counter, Terminal orientation / adopters, protection release of microprocessor based:

2

2

Switch Disconnector Fuse Units (SDFU) Triple Pole with isolable Neutral (TPN), 415V, 50 Hz, Panel mounting type interior version with operating mechanism and handle without HRC fuse links. Confirming to IS 13947 (Part 3), Accessories: Terminal shrouds, Fuse shrouds, Fuse barriers

2a Rating: 630A 5 2b Rating: 400A 8 2c Rating: 200A 4 2d Rating: 125A 4 2e Rating:63A 4

3

DIN TYPE HRC Fuse Links (For 2a to 2d) Rated Voltage: 415V, 50 Hz, DIN fuse Type -HN, Confirming to IS 13703, Low let through energy, High breaking Capacity of 100 kA at 415V with blown indication. Make shall be of SDFU selected or recommended by the SDFU manufacturer.

3a Suitable for 630A SDFU, Rating: 630A 15 3b Suitable for 400A SDFU, Rating: 400A 24 3c Suitable for 200A SDFU, Rating: 160A 12 3d Suitable for 125A SDFU, Rating: 100A 12 3e Suitable for 63A SDFU, Rating: 40A 12

4 Mechanical Castle key Interlock kit for 630A ACB /SDFU Q1 and Q2 and B/C-Q3 with key(Three locks with two keys) and interlock between Q5, Q6 and Q7

6

Page 12: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

12

5

Miniature Circuit Breakers (MCB's) Breaking capacity: 10 kA, Type C Tripping characteristics confirming to IEC 8828-1996, Din rail mounting type, Rated voltage 415 V 50 Hz, Class 3 let through energy, Should give protection against over load and short circuit, Make: CEPO approved brands

5a No of poles: 4, Rating: 63 Amps, 6 5b No of poles: 4, Rating: 32 Amps, 8 5c No of poles: 2, Rating: 16 Amps, 6 5d No of poles: 2, Rating: 10 Amps, 6

6 Insulated Copper Busbars Type: Fork, Rating: 63 Amps, including end caps for bus bars, Make: Shall be same as that of MCB.

6a 4 pole 4 mod step, 8 mod As required

6b 2 pole 2 mod step, 12 mod or as per requirement

7

Modular Fuse Holders: Suitable for 14x51 mm cylindrical HRC fuse, Din rail mounting, 600 VAC, 50 Hz, 3 Pole, No. of moduls 4.5 (18 mm / module), Finger safe protection, With neon indication for blown fuse, Material –Self extinguishable polyester, Confirming to IEC 60269. Make: Cooper Bussmann / Ferraz Shawmut / Siemens / CII or equivalent / better (For 63 A MCB out goings)

6

8

Modular Fuse Holders: Suitable for 10x38 mm cylindrical HRC fuse, Din rail mounting, 600 VAC, 50 Hz, 3 Pole & 1 Pole, No. of moduls 3 & 1 (18 mm / module), Finger safe protection, With neon indication for blown fuse, Material –Self extinguishable polyester, Confirming to IEC 60269.

8a 3 Pole (For 32 A and below MCB's three phase voltage to Meter, protections relays etc)

17

8b 1 Pole (For auxiliary supply to meter, protection relay, ELR, single phase MCB's) 22

HRC Fuse Links

Nominal Voltage: 415 V 50 Hz, Breaking Capacity: 80 kA at 415 V 50 Hz P.F. of 0.15, Confirming to IS: 9224 1979. Cylindrical type of size 14 x 51 mm, Make: CEPO approved

9

9a Rating: 50 Amps 18

10

HRC Fuse Links Nominal Voltage: 415 V 50 Hz, Breaking Capacity: 80 kA at 415 V 50 Hz P.F. of 0.15, Confirming to IS: 9224 1979. Cylindrical type of size 10 x 38 mm, Make: CEPO approved or MFH make

10a Rating: 20/25 Amps 24 10b Rating: 10 Amps 6 10c Rating: 16 Amps 6 10d Rating: 2/4 Amps 24

Page 13: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

13

11

Digital Trivector Meter True RMS measuring meter to read L-L/L-N voltage, Current per phase / neutral current, Frequency, Phase rotation / Vmax. and current demand per phase, Vmin. per phase, %age of load circular bar graph. Capable of measuring power parameters viz., kW & kWh, kVA &kVAh, kVAr&kVARh, import & export etc., The meter shall be capable of reading the voltage as well as current (THD) Harmonic, Three phase at once, bright LED display. Communication port –RS 485 and Industrial standard communication protocol – MODBUS, Auxiliary power supply: 24 VDC.

2

12

Current Transformers (Metering) Resin cast Current Transformer, Burden: 10 VA, Accuracy class: 1, Ratio: 800/5. Suitable arrangement for fixing CT’s to busbar shall be provided. Calibration / test certificate shall be supplied for each CT.

6

13

3 Phase OC + EFR + High Set Micro Controller, LS OC (20-200 % step 5 %) HS O/C (0.2 to 40) in step of 0.2 In or disable & LS EF (5-80 % step 5 %), HS EF (0.1 to 20) on step of 0.1 On or disable, HS delay (0.1 to 2 Sec) step 0.01 sec or instantaneous, Draw out type, Auto doubling of HS, relay co-ordination, self testing& display of parameters, Site selectable trip time characteristics (NI, VI, EI & Definite Time), TMS 0.1-1.6 step 0.05, Auxiliary contacts 2 NO + 2 NC, Auxiliary supply: 88-264V AC/DC, CT Rating: 5A, Make:

2

14

Current Transformers (Protection) Resin cast Current Transformer, Burden: 10 VA, Accuracy class: 5P10, Ratio: 800/5. Suitable arrangement for fixing CT’s to busbar shall be provided, Calibration certificate shall done for each CT.

8

15

ELR & CBCT Input auxiliary voltage: 220 V AC, 50 Hz, Sensitivity: Primary 1–8 Amps, Secondary 30–300 mA adjustable, Tripping time: Variable 0.15 to 3 Seconds, Potential free 1 NO+1 NC contacts, Contact rating: 6 A, 230 V AC, Mounting: Flush 96x96 mm, Export model Confirming to IS 8686, 3231, Resin cast CBCT, Size ID: 150 mm circular: 2 Nos,

2

16

Power Capacitor Rating: 15 kVAr at 415 V, 3 phase, 50 Hz delta connected, Type: Metallised Polypropylene capacitor, Dry type, Self healing with pressure sensitive disconnector, Low watt loss, High inrush current withstand capability, Discharge resistor as per IEC 831-1, Burst proof.

1

17

Power Contactor for Power Capacitor switching. Utilization category 6b AC at 415 V, 50 Hz, 3 Phase delta connected, Auxiliary contact 2 NO + 2 NC, Coil voltage: 240 V AC, With suitable damping resistor to limit inrush current, Capacitor switching rating: 15 kVAr.

1

Page 14: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

14

18

Electronic ON Delay Timers for capacitor Supply voltage; 240VAC, Contact: 2 delayed c/o 240VAC, Timing ranges; 3,6,12,30,60,120 Sec/minutes, Din mounting type, Make: CEPO approved brands

1

19

TBs for CT circuit with two conductor longitudinal switching disconnect -Type -CAGE CLAMP terminal connector, 600 VAC, Colour -Grey, Din rail mounting, Front entry, Material -polyamide, Continuous operating temperature -105 deg C, Electrolytic copper, end plate, lock out, coupling device, jumper complete as required. Suitable for 0.2-6.0 Sq. mm cable. Wago: / equivalent

12

20 Toggle Switch Rating: 5 A,

2

21 Copper Control Cable, single core, multi strand, Halogen Free Fire Retardant (HFFR), 1.5 and 2.5 sqmm cables as per IS: 694 / 1990.

As required

22

Power Cable Halogen Free Fire Retardant (HFFR), single core multi strand electrolytic grade, annealed copper cable, Voltage grade: 1100 Volts, as per IS: 694 / 1990, Size &colour of the cable should be selected according to the MCB/Switch-gear rating & standard RYBB colour,

As required

23

Din Rail / Terminal Connectors / Cable Tray Mounting Rails: C-channel shaped, steel zinc passivated / plated Length: as required, Terminal connectors:, Suitable for 2.5 Sq. mm control cable, Color: Red, Yellow, Blue, Black and Grey, End cover:, End clamp: as per requirement,

As required

24

LED Indication lamps -For RYB indication & ON, OFF & Trip indication -Type: LED, Ribbed lens with trim collar anodised bright, 230VAC, Flush head. Colour Red, Yellow/Amber, Blue & Green.

As required

25

Control Accessories:- (For capacitor ) Illuminated Actuators -LED type, 230 VAC, including contacts, legend plate & guard ring for remote operation purpose with 1NO+1NC auxiliary contacts & in green/red colour. Mush room push button type. Make:

As required

26

Emergency Push button The local EPO shall include a non-illuminated "Emergency Power Off" pushbutton. Pressing the EPO switch shall immediately shut down the unit by activating the shunt trip of the all main input and bus coupler circuit breakers.

1

27

Auto Manual Selector Switch ( For street light control) Cam operated, Operating angle 60 degree,Three position for Auto-OFF-Manual indication, two pole, contact rating: 10 A with all fixing accessories complete set.

1

Page 15: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

15

28

Power Contactor for Street light circuit -Air break type power contactor without enclosure in open execution suitable for 415V, 50Hz, AC 3 duty with 3 main contacts and 2NO+2NC auxiliary contacts and coil rated for 220/230 V, 50 Hz, AC Supply with 32A current rating confirming to IS / IECC 60947-4-1.

1

29

Illumination level based switch (For street light control) Switching lux range 10 to 60 lux, Waiting time 30 to 90 seconds, Automatic switch on at dusk, Automatic switch off at dawn, Auxiliary supply voltage 150-280 VAC, Switch off selection from 4 to 8 hours or at dawn. (To be kept outside and wired)

Outdoor 1

30

Terminal Connectors -Type -CAGE CLAMP terminal connector, 600 VAC 50 Hz grade, Colour - Grey for phases, Blue for neutral

and Yellow-Green for earth, Including end plate, Din rail mounting type, Front entry, Material -modified Nylon,

Continuous operating temperature 0 to 5O C, Electrolytic copper Ecu, Make: Wago / Connectwell / Phoenix / Salzer/ Equivalent

30a Suitable for termination of cable from 0.2 to 16 sq mm, Rating -76 A (For 63A outlets)

As per requirement

30b Suitable for termination of cable from 0.2 to 10 sq mm, Rating -41 A (For 32A outlets)

30c Suitable for termination of cable from 0.2 to 4 sq mm, (For control wiring)

31

Breaker Control Switch (TNC) with lever handle, shall be lockable in neutral position, Front mounting with grey colour, handle black colour, Engraved 'Trip', Neutral' & 'Close', IP 40 protection.

2

32

Industrial plug in Relays 3 C/O contacts, 11 pin, circular pin arrangement, Continuous duty, Silver cadmium alloy Contacts, Contact rating 5A continuous @ 240 VAC, Contact min. power rating 1000 VA, Relay assembly shall be completely sealed in transparent enclosure, Led indication across coil while on relay pick up, Arc barriers shall be provided between the pole contacts, Mechanical test to push button shall be provided, Mechanical flag indication on relay status, Din rail mounted plug in socket for 11 pin relay. Make: PLA / Paramount / OEN / BCH / Siemens / ABB/Equivalent

As per requirement

33 Aluminim bus bars of sufficient size as per standards As per requirement

34 Bus duct between the two sections with minimum 500mm gap to be considered. Also Both the sections are planned to place in L- shape

As per requirement

35 Any other materials required for completing the work as per relevant IS standards and not mentioned here are to be considered and mentioned in the BOM along with technical bid.

As per requirement

Page 16: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

16

36 Potential free contacts for ON and OFF positions of all the incoming switches are to be provided (NO & NC contacts). Also provision for ON/OFF commands to be made.

As per requirement

Functional requirements 1. Mechanical interlock between Input feeder ACB’s Q1, Q2 and Bus coupler Q3 shall be provided 2. mechanical interlock between AVR output (Q5) & AVR bypass (Q6) and load side bus coupler (Q7) shall be provided. (reference Drawing for PCC MCF_TSF_ES 10: DRG4(1) & 4(2) 3. PCC Panel shall be of two sections separated between bus couplers and will be placed separately. Minimum distance between the two sections is 500mm and bus duct with suitable size aluminium bus bar to be considered for inter connection (reference Drawing for PCC MCF_TSF_ES 10: DRG4(1) & 4(2 4. Capacitor control circuit shall be wired for Auto / Manual mode of operation using timer and contactor with bypass arrangement. Illuminated push buttons to be provided for manual operation. 5. Street light control circuit shall be wired for auto / manual mode of operation using Illumination level based switch & contactor with bypass arrangement. Illuminated push buttons to be provided for manual operation. (Illumination level based sensor to be fixed in a separate weather proof box with all the control switches and fixed outside the building. Also required interface cable between the Illumination sensor and contactor in the PCC to be supplied and interfaced)

Page 17: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

17

BOM for SCES#11 Main Power control Centre- BOM-2(A1) Sl no.8 of Table-I NOTE:-Refer Drawing No. MCF_TSF_ES 11: DRG4(3)&4(4)and technical annexure-2(A)

S/n Description Qty

1

Air Circuit Breakers -ACB (For F # 1 & # 2 Incomers) Rated operational voltage -415V 50Hz AC, Rated current -630A, 3 Poles, EDO type, Type of closing: Stored energy type (Motor operated), Motor voltage: 240 VAC, Closing electromagnet: 240 VAC, Wiring scheme: 3Ph, 4 wire, Auto reset, Door interlock, Castle lock with key, Rated insulation voltage: 690 VAC, Utilization category -B Breaking capacity (Ics) at 415V, 50Hz –minimum 36 kA, , Making capacity (Icm) at 415V, 50Hz -105 kA peak. Confirming to IS 13947 (Part 2) / IEC 60947-2. Accessories: Auxiliary contacts: 4NO+4NC, Safety shutters / Inter phase barriers, Shunt release: 240 VAC/24V DC, Operation counter, Terminal orientation / adopters, protection release of microprocessor based

2

2

Switch Disconnector Fuse Units (SDFU) Triple Pole with isolable Neutral (TPN), 415V, 50 Hz, Panel mounting type interior version with operating mechanism and handle without HRC fuse links. Confirming to IS 13947 (Part 3), Accessories: Terminal shrouds, Fuse shrouds, Fuse barriers

2a Rating: 630A 5 2b Rating :400A 4 2c Rating: 160A 2 2d Rating: 125A 4 2e Rating: 100A 4 2f Rating:63A 4

3

DIN TYPE HRC Fuse Links (For 2a to 2e) Rated Voltage: 415V, 50 Hz, DIN fuse Type -HN, Confirming to IS 13703, Low let through energy, High breaking Capacity of 100 kA at 415V with blown indication. Make shall be of SDFU selected or recommended by the SDFU manufacturer.

3a Suitable for 630A SDFU, Rating: 630A 15 3b Suitable for 400A SDFU, Rating: 400A 12 3c Suitable for 160A SDFU, Rating: 125A 6 3d Suitable for 125A SDFU, Rating: 100A 12 3e Suitable for 100A SDFU, Rating: 63A 12 3f Suitable for 63A SDFU, Rating: 40A 12

4 Mechanical Castle key Interlock kit for 630A MCCB Q1 and Q2 and B/C-Q3 with key(Three locks with two keys) and interlock between Q5, Q6 and Q7

6

Page 18: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

18

5

Miniature Circuit Breakers (MCB's) Breaking capacity: 10 kA, Type C Tripping characteristics confirming to IEC 8828-1996, Din rail mounting type, Rated voltage 415 V 50 Hz, Class 3 let through energy, Should give protection against over load and short circuit,

5a No of poles: 4, Rating: 63 Amps, 7 5b No of poles: 4, Rating: 32 Amps, 7 5c No of poles: 2, Rating: 16 Amps, 6 5d No of poles: 2, Rating: 10 Amps, 6

6 Insulated Copper Bus bars Type: Fork, Rating: 63 Amps, including end caps for bus bars, Make: Shall be same as MCB make .

6a 4 pole 4 mod step, 8 mod As required

6b 2 pole 2 mod step, 12 mod or as per requirement

7

Modular Fuse Holders: Suitable for 14x51 mm cylindrical HRC fuse, Din rail mounting, 600 VAC, 50 Hz, 3 Pole, No. of modules 4.5 (18 mm / module), Finger safe protection, With neon indication for blown fuse, Material –Self extinguishable polyester, Confirming to IEC 60269. Make: Cooper Bussmann / Ferraz Shawmut / Siemens / CII or equivalent (For 63 A MCB out goings)

7

8

Modular Fuse Holders: Suitable for 10x38 mm cylindrical HRC fuse, Din rail mounting, 600 VAC, 50 Hz, 3 Pole & 1 Pole, No. of moduls 3 & 1 (18 mm / module), Finger safe protection, With neon indication for blown fuse, Material –Self extinguishable polyester, Confirming to IEC 60269. Make: Cooper Bussmann / Ferraz Shawmut / Siemens / CII or equivalent

8a 3 Pole (For 32 A and below MCB's three phase voltage to Meter, protections relays etc) 15

8b 1 Pole (For auxiliary supply to meter, protection relay, ELR, 22

9

HRC Fuse Links Nominal Voltage: 415 V 50 Hz, Breaking Capacity: 80 kA at 415 V 50 Hz P.F. of 0.15, Confirming to IS: 9224 1979. Cylindrical type of size 14 x 51 mm,

9a Rating: 50 Amps 21

10

HRC Fuse Links Nominal Voltage: 415 V 50 Hz, Breaking Capacity: 80 kA at 415 V 50 Hz P.F. of 0.15, Confirming to IS: 9224 1979. Cylindrical type of size 10 x 38 mm,

10a Rating: 25-32 Amps 21 10b Rating: 10 Amps 6 10c Rating: 16 Amps 6 10d Rating-2-6A 24

Page 19: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

19

11

Digital Multi function Meter True RMS measuring meter to read L-L/L-N voltage, Current per phase / neutral current, Frequency, Phase rotation / Vmax. and current demand per phase, Vmin. per phase, %age of load circular bar graph. Capable of measuring power parameters viz., kW & kWh, kVA &kVAh, kVAr&kVARh, import & export etc., The meter shall be capable of reading the voltage as well as current (THD) Harmonic, Three phase at once, bright LED display. Communication port –RS 485 and Industrial standard communication protocol – MODBUS, Auxiliary power supply: 24 VDC.

2

12

Current Transformers (Metering) Resin cast Current Transformer, Burden: 10 VA, Accuracy class: 1, Ratio: 800/5. Suitable arrangement for fixing CT’s to busbar shall be provided. Calibration / test certificate shall be supplied for each CT.

6

13

3 Phase OC + EFR + High Set Micro Controller, LS OC (20-200 % step 5 %) HS O/C (0.2 to 40) in step of 0.2 In or disable & LS EF (5-80 % step 5 %), HS EF (0.1 to 20) on step of 0.1 On or disable, HS delay (0.1 to 2 Sec) step 0.01 sec or instantaneous, Draw out type, Auto doubling of HS, relay co-ordination, self testing& display of parameters, Site selectable trip time characteristics (NI, VI, EI & Definite Time), TMS 0.1-1.6 step 0.05, Auxiliary contacts 2 NO + 2 NC, Auxiliary supply: 88-264V AC/DC, CT Rating: 5A,

2

14

Current Transformers (Protection) Resin cast Current Transformer, Burden: 10 VA, Accuracy class: 5P10, Ratio: 800/5. Suitable arrangement for fixing CT’s to busbar shall be provided, Calibration certificated shall done for each CT.

8

15

ELR & CBCT Input auxiliary voltage: 220 V AC, 50 Hz, Sensitivity: Primary 1–8 Amps, Secondary 30–300 mA adjustable, Tripping time: Variable 0.15 to 3 Seconds, Potential free 1 NO+1 NC contacts, Contact rating: 6 A, 230 V AC, Mounting: Flush 96x96 mm, Export model Confirming to IS 8686, 3231, Resin cast CBCT, Size ID: 150 mm circular: 2 Nos,

2

16

Power Capacitor Rating: 15 kVAr at 415 V, 3 phase, 50 Hz delta connected, Type: Metallised Polypropylene capacitor, Dry type, Self healing with pressure sensitive disconnector, Low watt loss, High inrush current withstand capability, Discharge resistor as per IEC 831-1, Burst proof.

1

17

Power Contactor for Power Capacitor switching. Utilization category 6b AC at 415 V, 50 Hz, 3 Phase delta connected, Auxiliary contact 2 NO + 2 NC, Coil voltage: 240 V AC, With suitable damping resistor to limit inrush current, Capacitor switching rating: 15 kVAr.

1

Page 20: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

20

18 Electronic ON Delay Timers Supply voltage; 240VAC, Contact: 2 delayed c/o 240VAC, Timing ranges; 3,6,12,30,60,120 Sec/minutes, Din mounting type,

1

19

TBs for CT circuit with two conductor longitudinal switching disconnect -Type -CAGE CLAMP terminal connector, 600 VAC, Colour -Grey, Din rail mounting, Front entry, Material -polyamide, Continuous operating temperature -105 deg C, Electrolytic copper, end plate, lock out, coupling device, jumper complete as required. Suitable for 0.2-6.0 Sq. mm cable. Wago/ equivalent

12

20 Toggle Switch Rating: 5 A, 2

21

Control Cable Halogen Free Fire Retardant (HFFR), single core multi strand electrolytic grade, annealed copper cable, Size: 0.75 sq. mm, No. & size of wire: 24/0.2 for control wiring, 2.5 Sq. mm cable for CT wiring, Voltage grade: 1100 V, Current rating: 7A, as per IS: 694 / 1990.

As required

22

Power Cable Halogen Free Fire Retardant (HFFR), single core multi strand electrolytic grade, annealed copper cable, Voltage grade: 1100 Volts, as per IS: 694 / 1990, Size &colour of the cable should be selected according to the MCB/Switch-gear rating & standard RYBB colour,

As required

23

Din Rail / Terminal Connectors / Cable Tray Mounting Rails: C-channel shaped, steel zinc passivated / plated Length: as required, Terminal connectors:, Suitable for 2.5 Sq. mm control cable, Color: Red, Yellow, Blue, Black and Grey, End cover: End clamp:, as per requirement, Busbar type Terminal connector should be used for 32 Amps & above for output termination,

As required

24

LED Indication lamps -For RYB indication & ON, OFF & Trip indication -Type: LED, Ribbed lens with trim collar anodised bright, 230VAC, Flush head. Colour Red, Yellow/Amber, Blue & Green.

As per requirement

25

Control Accessories:- (For capacitor ) Illuminated Actuators -LED type, 230 VAC, including contacts, legend plate & guard ring for remote operation purpose with 1NO+1NC auxiliary contacts & in green/red colour. Mush room push button type.

As per requirement

26

Emergency Push button The local EPO shall include a non-illuminated "Emergency Power Off" pushbutton. Pressing the EPO switch shall immediately shut down the unit by activating the shunt trip of the all main input and bus coupler circuit breakers.

1

27

Auto Manual Selector Switch ( For street light contro) Cam operated, Operating angle 60 degree, Three position for Auto-OFF-Manual indication, two pole, contact rating: 10 A with all fixing accessories complete set.

1

Page 21: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

21

28

Power Contactor for Street light circuit -Air break type power contactor without enclosure in open execution suitable for 415V, 50Hz, AC 3 duty with 3 main contacts and 2NO+2NC auxiliary contacts and coil rated for 220/230 V, 50 Hz, AC Supply with 32A current rating confirming to IS / IECC 60947-4-1.

1

29

Illumination level based switch (For street light control)Switching lux range 10 to 160 lux, Waiting time 30 to 90 seconds, Automatic switch on at dusk, Automatic switch off at dawn, Auxiliary supply voltage 150-280 VAC, Switch off selection from 4 to 8 hours or at dawn.

1

30

Terminal Connectors -Type -CAGE CLAMP terminal connector, 600 VAC 50 Hz grade, Colour - Grey for phases, Blue for neutral and Yellow-Green for earth, Including end plate, Din rail mounting type, Front entry, Material -modified Nylon, Continuous operating temperature -105O C, Electrolytic copper Ecu, Make: Wago / Connectwell / Phoenix / Salzer/Equivalent

30a Suitable for termination of cable from 0.2 to 16 sq mm, Rating -76 A (For 63A outlets)

As per requirement

30b Suitable for termination of cable from 0.2 to 10 sq mm, Rating -41 A (For 32A outlets)

30c Suitable for termination of cable from 0.2 to 4 sq mm, (For control wiring)

31

Breaker Control Switch (TNC) Frame size - 88 mm, Lever handle, shall be lockable in neutral position, Front mounting with grey colour, handle black colour, Engraved 'Trip', Neutral' & 'Close',

2

32

Industrial plug in Relays 3 C/O contacts, 11 pin, circular pin arrangement, Continuous duty, Silver cadmium alloy Contacts, Contact rating 5A continuous @ 240 VDC, Contact min. power rating 1000 VA, Relay assembly shall be completely sealed in transparent enclosure, Led indication across coil while on relay pick up, Arc barriers shall be provided between the pole contacts, Mechanical test to push button shall be provided, Mechanical flag indication on relay status, Din rail mounted plug in socket for 11 pin relay.

As per requirement

33 Aluminim bus bars of sufficient size as per standards As per

requirement

34 Bus duct between the two sections with minimum 500mm gap to be considered. Also Both the sections are planned to place in L- shape

As per requirement

35 Any other materials required for completing the work as per relevant IS standards and not mentioned here are to be considered and mentioned in the BOM along with technical bid.

As per requirement

36 Potential free contacts for ON and OFF positions of all the incoming switches are to be provided (NO & NC contacts)

As per requirement

Page 22: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

22

Functional requirements

1. Mechanical interlock between Input feeder ACB’s Q1, Q2 and Bus coupler Q3 shall be provided

2. mechanical interlock between AVR output (Q5) & AVR bypass (Q6) and load side bus coupler (Q7) shall be provided. (reference Drawing for PCC. MCF_TSF_ES 11: DRG4(3) & 4(4)

3. PCC Panel shall be of two sections separated between bus

couplers and will be placed separately. Minimum distance between the two sections is 500mm and bus duct with suitable size aluminium bus bar to be considered for inter connection (reference Drawing for PCC. MCF_TSF_ES 11: DRG4(3) & 4(4)

4. Capacitor control circuit shall be wired for Auto / Manual mode of operation using timer and contactor with bypass arrangement. Illuminated push buttons to be provided for manual operation.

5. Street light control circuit shall be wired for auto / manual mode of operation using Illumination level based switch & contactor with bypass arrangement. Illuminated push buttons to be provided for manual operation. (Illumination level based sensor to be fixed in a separate weather proof box with all the control switches and fixed outside the building. Also required interface cable between the Illumination sensor and contactor in the PCC to be supplied and interfaced)

Page 23: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

23

BOM for SCES#11 UPS INPUT PANEL- BOM:2A (2)

(Sl no.9 of Table-I)

NOTE:- Refer Drawing No. MCF_TSF_ES 11: DRG4(5) and technical annexure-2(A)

S/n Description Qty

1

Switch Disconnector Fuse Units (SDFU) Triple Pole with isolatable Neutral (TPN), 415V, 50 Hz, Panel mounting type interrior version with operating mechanism and handle without HRC fuse links. Confirming to IS 13947 (Part 3), Accessories: Terminal shrouds, Fuse shrouds, Fuse barriers

1a Rating: 400A (Incomming) 2

1b Rating: 400A (Out going) 7

1c Rating: 100A (Out going) 1

2

DIN TYPE HRC Fuse Links (For 2a to 2b) Rated Voltage: 415V, 50 Hz, DIN fuse Type -HN, Confirming to IS 13703, Low let through energy, High breaking Capacity of 100 kA at 415V with blown indication. Make shall be of SDFU selected or recommended by the SDFU manufacturer.

2a Suitable for 400A SDFU, Rating: 400A 27

2b Suitable for 100A SDFU, Rating: 100A 3

3 Mechanical Castle key Interlock kit 2

4

Modular Fuse Holders: Suitable for 10x38 mm cylindrical HRC fuse, Din rail mounting, 600 VAC, 50 Hz, 3 Pole & 1 Pole, No. of modules 3 /1 (18 mm / module), Finger safe protection, With neon indication for blown fuse, Material –Self extinguishable polyester, Confirming to IEC 60269.

4

5

HRC `Fuse Links Nominal Voltage: 415 V 50 Hz, Breaking Capacity: 80 kA at 415 V 50 Hz P.F. of 0.15, Confirming to IS: 9224 1979. Cylindrical type of size 10 x 38 mm,

5a Rating: 2 Amps 8

6 Multi-function Meter True RMS measuring meter to read L-L/L-N voltage, Current per phase / neutral current, Frequency, Phase rotation / Vmax. and current demand per phase, Vmin. per phase,

Page 24: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

24

%age of load circular bar graph. Capable of measuring power parameters viz., kW & kWh, kVA &kVAh, kVAr&kVARh, import & export etc., The meter shall be capable of reading the voltage as well as current (THD) Harmonic, Three phase at once, bright LED display. Communication port –RS 485 and Industrial standard communication protocol – MODBUS, Auxiliary power supply: 24 VDC.

7

Current Transformers (Metering) Resin cast Current Transformer, Burden: 10 VA, Accuracy class: 1, Ratio: 800/5. Suitable arrangement for fixing CT’s to busbar shall be provided. Calibration / test certificate shall be supplied for each CT.

8

Control Cable Halogen Free Fire Retardant (HFFR), single core multi strand electrolytic grade, annealed copper cable, Size: 0.75 sq. mm, No. & size of wire: 24/0.2 for control wiring, 2.5 Sq. mm cable for CT wiring, Voltage grade: 1100 V, Current rating: 7A, as per IS: 694 / 1990.

As per requirement

9

Din Rail / Terminal Connectors / Cable Tray Mounting Rails: C-channel shaped STD 32 mm, steel zinc passivated / plated. Length: as required, Terminal connectors: STB – 02, Suitable for 2.5 Sq. mm control cable, Color: Red, Yellow, Blue, Black and Grey, End cover: STEC – 02, End clamp: STEL 35, as per requirement, Busbar type Terminal connector should be used for 32 Amps & above for output termination,

As per requirement

10

LED Indication lamps -For RYB indication & ON, OFF & Trip indication -Type: LED, Ribbed lens with trim collar anodised bright, 230VAC, Flush head. Colour Red, Yellow/Amber, Blue & Green. Make: CEPO approved. Required for phase indications of incomers and ON/OFF indications for incommers

As per requirement

11

Terminal Connectors -Type -CAGE CLAMP terminal connector, 600 VAC 50 Hz grade, Colour - Grey for phases, Blue for neutral and Yellow-Green for earth, Including end plate, Din rail mounting type, Front entry, Material -modified Nylon, Continuous operating temperature -105O C, Electrolytic copper Ecu, Make: Wago / Connectwell / Phoenix / Salzer/equivalent

11a Suitable for termination of cable from 0.2 to 4 sq mm, (For control wiring)

As per requirement

12 Aluminim bus bars of sufficient size as per standards. As per requirement

13 Any other materials required for completing the work as per relevant IS standards and not mentioned here are to be considered

Page 25: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

25

and mentioned in the BOM along with technical bid.

14 Potential free contacts for ON and OFF positions of all the incoming switches are to be provided (NO & NC contacts)

Page 26: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

26

Annexure-3 (A) (Sl no.13 of Table-I) LT POWER CABLE: 1100V RATED SUPPLY OF LT POWER CABLE, PVC INSULATED, COPPER CONDUCTOR, UNARMOURED AND PVC OUTER SHEATH(Sl no. 13 of Table-I-BOM). GENERAL TERMS:

A. Compliance for Tender Specification shall be clearly mentioned. . Annexure-4 (A)

LT POWER CABLE: 1100V RATED PVC INSULATED , COPPER CONDUCOR , UNARMOURED AND PVC OUTER SHEATH.

Sn Technical Specification

1. Type LT - PVC insulated, Power Cable (Cable code :- YY)

2. Voltage grade

1100 V

3. Size (Single core X 95 sqmm )

4. Conductor Electrolytic grade multi stand, flexible, Annealed Bare Copper (ABC) and Flexibility -Class 5 of IS 8130, Double insulated and sheathed,

5 Core Identification

Single core- Black

6. Insulation Core Insulation: HRPVC as per IS 5831

9. Outer sheath

PVC /FRLS PVC as per IS 5831

11 Embossing on the cable outer sheath

Following details to be printed on the outer sheath for every one meter of cable Voltage rating, Core & Size of Cable' sequential Length and manufacturer’s name.

12. Inspection Cable shall be offered for inspection at works before dispatch. All the routine and acceptance tests as per the relevant IS are to be conducted. Also type test reports to be submitted for verification

14. Quantity As mentioned in BOM

15. Quantity tolerance

± 5%

Page 27: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

27

Annexure-4(A) (Sl no.15 of Table-I) BOM:2 (A3) UPS OUTPUT PANEL– SCES#10, SCES#11

Instructions

1. All the technical specifications mentioned in Annexure-2(A) for power control center are applicable (Which ever related to this panel are to be considered).

2. Single line diagram enclosed to be used for reference. drawing MCF_ TSF_ELF_ES 10&11 :5

S/n Description Qty

Switch Disconnector Fuse Units (SDFU) Triple Pole with isolable Neutral (TPN), 415V, 50 Hz, Panel mounting type interior version with operating mechanism and handle without HRC fuse links. Confirming to IS 13947 (Part 3), Accessories: Terminal shrouds, Fuse shrouds, Fuse barriers (switches shall be with auxiliary contacts). Make: As per approved list

1a Incommer:- Rating: 400A 2

1b Outgoing:- Rating: 200A 5 1c Outgoing:- Rating: 250A 1 1d Outgoing:- Rating: 125A 1

2

DIN TYPE HRC Fuse Links Rated Voltage: 415V, 50 Hz, DIN fuse Type -HN, Confirming to IS 13703, Low let through energy, High breaking Capacity of 100 kA at 415V with blown indication. Make shall be of SDFU selected or recommended by the SDFU manufacturer.

2a Suitable for 400A SDFU, Rating: 360A 6 2b Suitable for 200A SDFU, Rating: 160A 15 2c Suitable for 250A SDFU, Rating: 200A 3 2d Suitable for 125A SDFU, Rating: 100A 3

3

LED Indication lamps -For RYB indication & ON, OFF indication for incommers -Type: LED, Ribbed lens with trim collar anodised bright, 230VAC, Flush head. Colour Red, Yellow, Blue for phases and & Green and Red for ON/OFF. Make: Department approved ( Phase indicators for incommers and ON/OFF indicators for incomer and outgoing SDFU)

As per requirement

4

Terminal Connectors -Type -CAGE CLAMP terminal connector, 600 VAC 50 Hz grade, Colour - Grey for phases, Blue for neutral and Yellow-Green for earth, Including end plate, Din

As per requirement

Page 28: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

28

rail mounting type, Front entry, Material -modified Nylon, Continuous operating temperature -105OC, Electrolytic copper Ecu,

5

Miniature Circuit Breakers (MCB's) Breaking capacity: 10 kA, Type C Tripping characteristics confirming to IEC 8828-1996, Din rail mounting type, Rated voltage 415 V 50 Hz, Class 3 let through energy, Should give protection against over load and short circuit,

5a No of poles: 4, Rating: 63 Amps, 4 5b No of poles: 4, Rating: 32 Amps, 2

6 Insulated Copper Busbars Type: Fork, Rating: 63 Amps, including end caps for bus bars, Make: Shall be MCB.

6a 4 pole 4 mod step, 8 mod or as required As per requirement

6b 2 pole 2 mod step, or as per requirement As per

requirement

7

Modular Fuse Holders: Suitable for 14x51 mm cylindrical HRC fuse, Din rail mounting, 600 VAC, 50 Hz, 3 Pole, No. of modules 4.5 (18 mm / module), Finger safe protection, With neon indication for blown fuse, Material –Self extinguishable polyester, Confirming to IEC 60269. (For 63 A MCB out goings)

2

8

Modular Fuse Holders: Suitable for 10x38 mm cylindrical HRC fuse, Din rail mounting, 600 VAC, 50 Hz, 3 Pole & 1 Pole, No. of moduls 3 & 1 (18 mm / module), Finger safe protection, With neon indication for blown fuse, Material –Self extinguishable polyester, Confirming to IEC 60269.

8a 3 Pole (For 32 A and below MCB's three phase and for indicator)

4

9

HRC Fuse Links Nominal Voltage: 415 V 50 Hz, Breaking Capacity: 80 kA at 415 V 50 Hz P.F. of 0.15, Confirming to IS: 9224 1979. Cylindrical type of size 14 x 51 mm,

9a Rating: 50 Amps 6

10

HRC Fuse Links Nominal Voltage: 415 V 50 Hz, Breaking Capacity: 80 kA at 415 V 50 Hz P.F. of 0.15, Confirming to IS: 9224 1979. Cylindrical type of size 10 x 38 mm, Make: Department approved make

10a Rating: 25-32 Amps 6 10b Rating 16/10Amps 6 10d Rating-2-4A 6

Page 29: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

29

11 RCBO Two pole 10/16A rating with 100mA sensitivity 6

12 Control /power cables of sufficient size As per

requirement

13 Aluminim bus bars of sufficient size as per standards

As per requirement

14

Any other materials required for completing the work as per relevant IS standards and not mentioned here are to be considered and mentioned in the BOM along with technical bid.

As per requirement

15 Potential free contacts for ON and OFF positions of all the incoming switches are to be provided (NO & NC contacts)

Reference. drawing MCF_ TSF_ES 10&11 :5

1. All incoming and outgoing bus bars are to be brought up to the cable chamber with required length of bus bars for easily terminating the cables. Also space shall be considered liberally for easy termination

2. Output cables of the smaller rating MCB’s (below 63A MCB’s) are to be brought up to cable chamber and terminated with suitable copper cables and screw less type TB’s

3. All the items mentioned in the BOM shall be of department approved only. List of approved makes enclosed.

4. All the SDFU’s are to be kept in the separate compartment with required fire barriers

Page 30: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

30

Annexure-5(A) BOM:2 (A4)

CHANGE OVER PANEL– SCES#10, SCES#11(Sl No. 17 of BOM)

Instructions

1. All the technical specifications mentioned in Annexure-2(A) for power control center are applicable (Which ever related to this panel are to be considered).

2. Single line diagram enclosed to be used for reference. (drawing no. MCF_ TSF_ELF_ES 10&11 :6)

BOM for CHANGE OVER PANEL

S/n Description Qty

1

Switch Disconnector Fuse Units (SDFU) 200A, Triple Pole with isolable Neutral (TPN), 415V, 50 Hz, Panel mounting type interior version with operating mechanism and handle without HRC fuse links. Confirming to IS 13947 (Part 3), Accessories: Terminal shrouds, Fuse shrouds, Fuse barriers. Make: As per approved list. Scheme to be designed to have two inputs through SDFU with single common output

8

2 LED Indication lamps -For RYB phase indication with required fuse protection. Make: Department approved brands

As per requirement

3

Terminal Connectors -Type -CAGE CLAMP terminal connector, 600 VAC 50 Hz grade, Colour - Grey for phases, Blue for neutral and Yellow-Green for earth, Including end plate, Din rail mounting type, Front entry, Material -modified Nylon, Continuous operating temperature -105O C,

As per requirement

4 Control and power cables As per

requirement

5 Potential free contacts for ON and OFF positions of the (SDFU) switches are to be provided (NO & NC contacts)

1. All the SDFU are to be kept in the separate compartment with required fire barriers

2. All incoming and outgoing bus bars are to be brought up to the cable chamber with required length of bus bars for easily terminating the cables. Also space shall be considered liberally for easy termination

Page 31: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

31

Annexure-6 (A)

LT POWER CABLE: 1100V RATED SUPPLY OF LT POWER CABLE, PVC INSULATED, COPPER CONDUCTOR, UNARMOURED AND PVC OUTER SHEATH, COPPER SHEILDED CABLE (Sl no. 19, 26,27,28,29,30, 31 and 32of Table-I-BOM) .

GENERAL TERMS:

A. The Cables offered should be restricted only to the department approved brands/make list enclosed with the tender (Annexure-A).

B. Compliance for Tender Specification shall be clearly mentioned.

LT POWER CABLE: 1100V RATED SUPPLY OF LT POWER CABLE, PVC INSULATED, COPPER CONDUCTOR, UNARMOURED AND PVC OUTER SHEATH, COPER SHEILDED CABLE (Sl no. 19, 26,27,28,29,30, 31 and 32of Table-I-BOM) .

Sn Technical Specification

1. Type LT - PVC insulated, Power Cable (Cable code :- YY)

2. Voltage grade 1100 V

3. Size Four core X 50sqmm ,Four coreX95 sqmm , Four Core X4 sqmm, 5core X 10/ 16sqmm, , Three core X1.5/2.5/4 sqmm (All Screened, Copper conductor PVC insulated cables)

4. Conductor Electrolytic grade multi stand, flexible, Annealed Copper (ABC) and Flexibility -Class 5 of IS 8130, Doubly insulated / sheathed,

5 Core Identification

As per standards

6. Insulation Core Insulation: HRPVC as per IS 5831

7 Inner sheath PVC per IS 5831

8. Outer sheath PVC FRLS PVC as per IS 5831

9 Screening /shielding

Copper (ATC-Annealed tinned copper) screening /shielding with more than 65 % covering to be provided

10. Embossing on the cable outer sheath

Following details to be printed on the outer sheath for every one meter of cable Voltage rating, Core & Size of Cable' sequential Length and manufacturer’s name.

Page 32: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

32

11 Inspection Cable shall be offered for inspection at works before dispatch. All the routine and acceptance tests as per the relevant IS are to be conducted. Also type test reports to be submitted for verification

12 Make As per Annexure-A.

13 Quantity Standard lengths to meet the required quantity

14 Quantity tolerance

± 5%

15 Warranty

Not less than 18 months from the date of receipt of material at MCF OR 12 months from the date of commissioning whichever is earlier.

16 IS standards Apart from the IS standards mentioned above, other applicable IS standards are to be followed.

Page 33: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

33

Annexure-7(A) (Sl no.22 of Table-I) BOM:2(A5)

STS OUTPUT PANEL– SCES#10, SCES#11

Instructions

1. All the technical specifications mentioned in Annexure-2(A) are applicable (Which ever related to this panel are to be considered).

2. Single line diagram enclosed to be used for reference. drawing MCF_ TSF_ES 10&11 :7

S/n Description Qty

Switch Disconnector Fuse Units (SDFU) Triple Pole with isolable Neutral (TPN), 415V, 50 Hz, Panel mounting type interrior version with operating mechanism and handle without HRC fuse links. Confirming to IS 13947 (Part 3), Accessories: Terminal shrouds, Fuse shrouds, Fuse barriers. Make: As per approved list

1a Incommer:- Rating: 200A 2

1b Outgoing:- Rating: 125A 6

2

DIN TYPE HRC Fuse Links Rated Voltage: 415V, 50 Hz, DIN fuse Type -HN, Confirming to IS 13703, Low let through energy, High breaking Capacity of 100 kA at 415V with blown indication. Make shall be of SDFU selected or recommended by the SDFU manufacturer.

2a Suitable for200A SDFU, Rating: 160A 6 2b Suitable for 125A SDFU, Rating: 100A 18

3

LED Indication lamps -For RYB indication of incommers -Type: LED, Ribbed lens with trim collar anodised bright, 230VAC, Flush head. Colour Red, Yellow, Blue for phases and & Green and Red for ON/OFF. Make: MCF approved

As per requirement and as per

SLD

4

Terminal Connectors -Type -CAGE CLAMP terminal connector, 600 VAC 50 Hz grade, Colour - Grey for phases, Blue for neutral and Yellow-Green for earth, Including end plate, Din rail mounting type, Front entry, Material -modified Nylon, Continuous operating temperature -105O C, Electrolytic copper Ecu,

As per requirement

5

Modular Fuse Holders: Suitable for 10x38 mm cylindrical HRC fuse, Din rail mounting, 600 VAC, 50 Hz, 3 Pole Pole, No. of moduls 3 & 1 (18 mm / module), Finger safe protection, With

Page 34: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

34

neon indication for blown fuse, Material –Self extinguishable polyester, Confirming to IEC 60269.

5a 3 Pole (For 32 A and below MCB's three phase voltage to Meter, protections relays etc)

2

6

HRC Fuse Links Nominal Voltage: 415 V 50 Hz, Breaking Capacity: 80 kA at 415 V 50 Hz P.F. of 0.15, Confirming to IS: 9224 1979. Cylindrical type of size 10 x 38 mm,

6a Rating: 2-4 Amps 6

7 Aluminium bus bars of sufficient rating As per requirement

8 Control and power Cables As per requirement

9 Potential free contacts for ON and OFF positions of all the incoming switches are to be provided (NO & NC contacts)

1. GA drawing of the STS panel to be furnished with super imposed SLD and bus bar configuration or proposed dimension of the panel to be furnished.

2. All incoming and outgoing bus bars are to be brought up to the cable chamber with required length of bus bars for easily terminating the cables. Also space shall be considered liberally for easy termination

3. The offer will not be considered if the submittals are not as per the above instructions.

4. All the SDFU’s are to be kept in the separate compartment with required fire barriers

Page 35: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

35

Annexure-8( A) (Sl no.24 of Table-I)

UPS/ Technical Power Distribution Boards

(Drawing no. MCF_TSF_ES10&11:8 and 8/1)

Only Schneider, / Rittal enclosures or equivalent will be accepted. For make of switch gears refer enclosed Annexure-A. All the items used shall be of cataloged items and make and model to be mentioned in the BOM. Also the distribution board shall be floor mounting type. Enclosure of the UPS DB shall be of Schneider or Rittal or equivalent. These makes with standard cataloged items are to be offered for enclosure and all the panel accessories. All the panel accessories of the UPS DB also from the same make. Also detailed catalog with model Nos. for enclosure and all the items of the DB are to submitted along with technical bid. A. Instructions

1. The make of the switchgears shall be any one among the MCF approved / specified makes in the bill of material. Make, model number and photocopy highlighting suitable catalogue number of the offered make should be provided.

2. Any left out or additional requirements of switchgears / enclosures accessories shall be included in the BOM with proper justification to meet the specification. No additional accessories are allowed after the order because of financial implications.

3. Clause by clause technical specification and bill of material compliance should be furnished.

4. The offer will not be considered if the submittals are not as per the above instructions.

5. Panels shall be supplied within delivery date of Purchase Order including approval of drawing.

B. Scope of work 1 Assembly, testing & supply of UPS power distribution boards as per

the SLD, GA drawing & bill of material considering applicable mechanical & electrical safety standards.

2 Routine & functional testing of UPS power distribution boards shall be carried out at works prior to dispatch as per the relevant IS.

3 UPS power distribution boards shall be supplied to MCF –Hassan, Karnataka.

C. General Technical specifications -The panel design standards shall comply to,

1. National Electrical Code (NEC). 2. IS & latest IE rules.

D. Electrical requirements

Page 36: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

36

1. Rating of the panel shall be 100A at 400 VAC, 3 Phase 2. Input to the panel will be 415 VAC at 50 Hz, 3-phase, four-wire-

plus-ground. 3. Short time withstand current rating of the panel should be 25 kA

RMS for 1 sec. E. Environmental requirements

1. Storage temperature range should be 0° to + 45°C 2. Operating temperature range should be 0° to 50°C 3. Operation should be reliable in an environment with 0 to 95% non-

condensing RH F. Panel Technical Specification –

1 Fabrication

1.1 Vendor to consider Schneider Electric, /Rittal enclosure or equivalent enclosure and accessories for floor mounted power distribution boards. Vendor to provide the make, model no and photocopy of catalog highlighting the item for compliance.

1.2 Power distribution boards shall be of floor mounting with mounting MS channels and brackets and suitable for indoor installation

1.3 The panel shall be naturally convection-cooled & should allow continuous full-load operation, maintaining the temperatures within tolerance level of components.

1.4 Panel shall be suitable for indoor application.

1.5 Contact hazard protection covers of standard cut out size shall be used to cover switchgears and terminal connector areas.

1.6 Provision shall be made to clamp / tie / fix the cables before connecting them to the cage clamp terminal blocks.

1.7 Cable entry provision shall be at the bottom.

1.8 Sheet steel cable entry plates shall be provided at the bottom for cable entry as per the requirement

1.9 Adjustable modular device rail for mounting RCBOs, Modular fuse holders and cage clamp terminal blocks shall be used.

1.10. Dummy cover strips shall be provided wherever left blank

2 Panel dimension

2.1 To be designed as per the input and output switch gears/ BOM. Also it shall be of floor mounting type and minimum depth of the enclosure shall be 600mm to mount the STS and other accessories.

3 Panel doors

3.1 Plain front door shall be provided along with proper fixing arrangement & standard handle system

4 Painting

4.1 Triple surface treatment -Phosphating, Electrophoretic dip coat priming and Powder coating technique / 7 tank processes shall be

Page 37: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

37

employed.

4.2 Epoxy polyester powder coating should be provided.

4.3 Color of the panel should be smoke gray

5 Wiring

5.1 FRLS, single core multi strand electrolytic grade, annealed copper cable confirming to: IS: 694 / 1990 shall be used.

5.2 Power cable of suitable size shall be used as per RCBO & MCBs current rating. Proper ferruling shall be provided for each cable at termination point for clear identification.

5.3 Cage clamp terminal connectors shall be used for all input and output power terminations.

6 Name plates / stickers

6.1 Standard identification labels shall be used for each output feeder.

6.2 Panel specification plate should be per the IS reference standard 2675.

6.3 Type of panel, Rated voltage AC or DC, Hz, Total number of outgoing ways / feeders, rated current of each outgoing feeders, Number of poles, Manufacturer name / Trade mark / Address, Customer PO reference and date, Year of manufacturing.

7 Grounding / Earthing

7.1 Two-point ground in accordance with recommendations of IEEE Standard and the requirements of the NEC shall be provided.

7.2 Panel earth bus of pure electrolyte Copper bus bar of suitable size shall be used.

8 Inspection / Testing

8.1 Panel shall be offered for inspection at factory after completion of all works and same shall be dispatched only after issue of dispatch clearance by MCF engineer.

8.2 Verification of switchgear components as per purchase order bill of material.

8.3 Minor modifications in mechanical / electrical changes pointed out by MCF inspecting officer shall be carried out, if necessary, without any additional cost

8.4 Routine inspection and testing as per the norms / checklist will be carried out.

8.5 Calibrated testing & measuring instruments are to be used for routine test.

8.6 Any deviations from the specifications or in testing shall be attended & offered for re-inspection if required.

9 Documentation shall contain the following information

9.1 As built General Assembly, Single Line Diagram, layout configuration

Page 38: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

38

in A3 size.

9.2 Bill of actual material used with make, catalogue number and quantity.

9.3 Routine / Acceptance test results / reports as per standard.

9.4 Document shall be supplied in duplicate with hardbound cover having printed title.

10 11

All incoming and outgoing terminals are to be wired up to the suitable screw less type Terminal blocks. Sufficient space shall be provided in the cable chamber for easy termination of cables. All the panel accessories like TB’s, coper bus bars, cable ducts etc shall be as per the standards from the enclosure/panel manufacturer only. Drawing shall be submitted from the manufacturer for MCF approval

Page 39: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

39

BOM FOR UPS /Technical power distribution boards. For SCES #10 and SCES#11, (Annexure-10( A) (Sl no.24 of Table-I) All the items shall be cataloged items suitable to fix in the standard enclosures mentioned in the BOM table below.

Sn Item Description Unit Qty

1

Miniature Circuit Breakers (MCB) Tripping Characteristic –C, Breaking capacity – 9/10 kA, 4 Pole, Touch proof terminals – IP20, Positive contact indicator, Bi-connect facility –Cable & Bus bar, Din rail mounting, Confirming to IS 60898 Part-1, 2002.

1.1 Rating: 100A, Number of modules –6, (18 mm / module) (Q1) Each 1

1.2 Rating: 63A, Number of modules – 4 (18 mm / module) (Q2 to Q3) Each 2

1.3 Rating: 40A, Number of modules –4 (18 mm / module) (Q4to Q6) Each 3

2

RCBO (Single Phase Two pole ):- Protection –OC, SC & EL, Suitable for AC, Tripping characteristic –C, Breaking capacity – >9 kA, Two pole, Touch proof terminals –IP20, Number of modules –2 (18 mm / module), Positive contact indicator, Bi-connect facility –Cable & Bus bar, Din rail mounting, Confirming to IS/IEC 61009. Make: CEPO approved brands.

2.1 Rating -16A, 100 mA Sensitivity (Q7 to Q16) Each 10 2.2 Rating -10A, 100 mA Sensitivity (Q17 to Q31) Each 15 2.3 Rating -06A, 100 mA Sensitivity ( Q32 to Q40) Each 9

3 Insulated Fork Copper Bus bars including end caps Make: Same as RCBO make.

As per requirement

3.1 Copper bus bar rating –40/ 63A, 4 Pole,, Including end caps

Each As per

requirement 3.2

Copper bus bar rating –32A, 2 Pole, Including end caps Each

4

Ultra Safe Modular Fuse Holders Type –Suitable for 14/51 and 10x38 cylindrical HRC fuse links, Mounting –Din rail, Voltage –600 VAC, 50 Hz, Contineous current rating -62/40A, Finger safe protection, With neon indication for blown fuse, Material –Self extinguishable polyester, Confirming to IEC 60269.

4.1 No of Poles -Three, (3 Module) 14X51(63A) Each 2 4.2 No of Poles -Three, (3 Module-10x38)) (40A) Each 3 4.3 No of Poles -Single, (1 Module-10 x38) (32A) Each 34

Page 40: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

40

5

Fuse link -HRC, HF type Size -14X51/ 10x38 mm cylindrical, Class of operation –General gG/gL, Fuse link with blown fuse indicator, Rated voltage – 400 to 690 VAC, Breaking capacity at 415 VAC: 80 kA, Low let through energy, Confirming to IS –13703 (part I & II)

5.2 Current Rating -63 A Each 6 5.3 Current Rating -40 A Each 9 5.4 Current Rating -16 A Each 10 5.5 Current Rating -10 A Each 15 5.6 Current Rating -6 A Each 9

6

Indicating Lights LED type, Voltage –230 VAC, 50 Hz, Din rail mounting type, Single pole, Number of module –1 (18 mm / module)

6.1 Colour -Red

As per requirement 6.2 Colour -Yellow

6.3 Colour -Blue

7

Terminal connector Type -Cage clamp, Rated voltage -800VAC, Din rail mounting Front Entry, Material -modified nylon 6.6 free of halogens, flurocarbons etc., Continuous operating temperature -1050C, Electrolytic copper Ecu.

As per requirement

7.1 Terminal connectors with rated current -80A/63A, Suitable for terminating the cables sufficient to the switch gears including end plate

7.1.1 Red

As per requirement

7.1.2 Yellow 7.1.3 Blue 7.1.4 Black 7.1.5 Green-yellow

7.2 Rated current -41A, Suitable for cable from 0.2 - 6 sq mm, Grey for phases, Blue for neutral & Yellow-Green for earth including end plates

7.2.1 Grey: As per

requirement 7.2.2 Blue 7.2.3 Green-yellow

7.3 Rated current -125A, Suitable for cable from 6 - 35 sq mm Grey for phases, Blue for neutral & Yellow-Green for earth including end plates.

7.3.1 Grey As per requirement 7.3.2 Blue

Page 41: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

41

7.3.3 Green-yellow

8

Cage clamp type Distribution terminal blocks Type -Cage clamp, Rated voltage -800VAC, Din rail mounting Front Entry, Material -modified nylon 6.6 free of halogens, flurocarbons etc., Continuous operating temperature -1050C, Electrolytic copper Ecu. Suitable for 1 x 6 - 35 Sq.

As per requirement

9

Power / Control Cable -FRLS, Smoke free, non toxic, non corrosive, single core un-sheathed, copper cable with compact circular uni-lay conductors, Voltage grade: 1.1 kV AC, The cable shall confirming to IS: 694-1990, The colour of the cable shall be Red / Yellow / Blue / Black for phase and Neutral and Green-Yellow stripe for earthing, Size of the cable selected according to the MCB / RCBO rating.

As per

requirement

10

Cable Ducts -Manufactured from high impact rigid PVC, should not peel, chip or break, non inflammable, warp proof, non-britle, high di-electric strength (36 kV / mm), Temperature withstand capacity up to 70 degree C, Colour: Grey, Type B locking, width &deapth of the duct should be selected according to the requirement and should be uniform in size. Make: Salzer / L&T / Kaycee / Klemson / Wago or equivalent / better

As per requirement

11

MS Enclosure ( structure, side enclosure, door , base channels, mounting supporting devices etc) shall be of Schneider / Rittal enclosures or equivalent. All the devices are to be mounted properly on suitable mounting rails as per standards. All the safety based the standards are to be considered.

As per requirement

12 Enclosures & accessories Schneider / Rittal enclosures or equivalent / better Sets

As per requirement

Page 42: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

42

Annexure-9A (Sl no.37 of Table-I)

SUPPLY AND FIXING OF STEEL WIRE MESH CABLE TRAY

Cable tray manufactured from steel wires, welded together and bent into final shape prior to surface treatment Hot dipped Galvanized to EN ISO 1461(formally BS 729 since 1999). Cable Tray dimensions are all internal. Steel wire Cable Tray will be produced from lateral and longitudinal sidewall steel wires, with minimum diameters of 4 mm for trays of width up to 100 mm, 4.5 mm for trays of width of 300mm, 6.0 mm for trays of widths of 400mm, 450mm, 500mm, and 600 mm. Trays will be manufactured with a longitudinal ‘T – Welded ‘safety edge along the top wire of the sidewall (excluding 30X50). Trays will be constructed with a 50mm x 100 mm mesh configuration. All tray fittings (e.g. changes in direction, level and size) shall be constructed on site, to the manufactures instruction, using side action bolt croppers and fastened using 25 mm and 30mm counters clamps with M6 bolts and nuts, all surface treated as the tray. Trays will be coupled together using either a fast spring coupler or a 25mm/30mm counter clamp combination with supporting lateral splice plate on trays over 300mm width. The coupling will have the same surface finish as the tray. Trays are to be supplied with cover and suitable cover clips. Trays shell be supported at maximum span of 2.5mm by the trapeze ,wall ,floor or channel mounting methods and will not exceed maximum loads as specified by the manufacturer. The fixture of the cable trays to the supported system shall be fast fixing type bolt free system. Traditional nuts and bolts shall not be used in coupling and fixture of cable baskets to the support systems. Fire test certification should be submitted in accordance with the E30/E90 standard. Loading and deflection characteristic of the tray should be tested and the results published in accordance with the European standard IEC 615357. All the fixtures like supporting structures, bends, tees etc are to be supplied along with the cable tray. Cable tray shall have the covers on the top with proper fixing arrangement.

Page 43: A. LT POWER CABLE: 1100V RATED, XLPE INSULATED ......3 Annexure-1(D) Termination of LT Power cable (Sl no. 6, 12, 21 and 34 of Table-I) 1 End termination of LT cables:- Providing end

43

GENERAL NOTE TO TENDER:-

1. Quantity for some of the items/ equipment’s are mentioned in the Table -1. Items /equipment’s which needs detailed specifications are enclosed above along with technical annexure /specifications. Also relevant drawings mentioned in the Table-1 are to be referred for more clarity.

2. All the works are to be carried out as per applicable IS/IEC standards.

3. Any of the items /specifications not mentioned in the BOM /technical annexures, but they are required to complete the work are to be considered adequately and mentioned in the detailed BOM in the technical bid. Also cost of additional items are to be considered while submitting price bid. Additional items requirement after the technical bid are not considered for any extra payment.

4. Payment for all the items or equipment’s mentioned in the table-1 will be

made as per the quantity utilization at site.

5. Only Department (ISRO) approved make of items will be accepted (List of approved make is enclosed as Annexure-A)

6. Warranty for the whole system as per tender specifications is compulsory.

7. Compliance for the points and all the systems as per Annexure-B are to be

provided along with the technical bid

8. All the installation and commissioning works are to be done as per the relevant IE rules.

9. All the panels are to be fabricated by the panel fabricators approved by the

ISRO (As per annexure-D)