ZS/S 1.1 Meter Interface Module ETS Parameter settingsfor EQ Energy Meters (A-/B-Series)

ABB i-bus® KNX, STO/G

Page 2: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 2

ZS/S 1.1 Meter Interface ModuleETS Parameter settings (A-/B-Series)

In the ETS application program ZS/S, the connected meter must be parameterized. The features and

functions of the meter must be taken into account, even if they are not used.

Example: A meter of type A43 311 -100 has 4 tariffs. These must be set in the ETS parameter Tariffs

(parameter option: yes), even if tariffs are not used or read.

The red LED of the Meter Interface Module flashes when the connected meter does not meet the

parameter settings in the ETS! The energy and measured values are still transmitted correctly. The

LED is permanently on if the IR communication is disrupted.

A-Series B-Series

Click on meter series which shall be read out via ZS/S:

Page 3: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 3

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A-Series

Steel ■ Bronce ■ Silver ■ Gold ■ Platinum ■

A41 11x - 100 A41 21x - 100 A41 31x - 100 A41 41x - 100 A41 51x - 100

A42 11x - 100 A42 21x - 100 A42 31x - 100 A42 41x - 100 A42 55x - 100

A43 1xx - 100 A43 21x - 100 A43 31x - 100 A43 41x - 100 A43 51x - 100

A44 11x - 100 A44 21x - 100 A44 3xx - 100 A44 45x - 100 A44 55x – 100

Click on meter type which shall be read out via ZS/S:

Page 4: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 4

ZS/S 1.1 Meter Interface ModuleETS Parameter settings B-Series

Steel ■ Bronce ■ Silver ■

B21 11x - 100 B21 21x - 100 B21 31x - 100

B23 1xx - 100 B23 21x - 100 B23 31x - 100

B24 11x - 100 B24 21x - 100 B24 3xx - 100

Click on meter type which shall be read out via ZS/S:

Page 5: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 5

A41

Page 6: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 6

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A41 Steel

Page 7: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 7

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A41 Bronce

Page 8: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 8

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A41 Silver, Gold, Platinum

Page 9: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 9

A42

Page 10: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 10

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A42 Steel

* freely adjustable

*

*

Page 11: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 11

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A42 Bronce

* freely adjustable

*

*

Page 12: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 12

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A42 Silver, Gold, Platinum

* freely adjustable

*

*

Page 13: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 13

A43

Page 14: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 14

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A43 Steel

* NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

*

Page 15: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 15

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A43 Bronce

* NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

*

Page 16: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 16

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A43 Silver, Gold, Platinum

*

* NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

Page 17: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 17

A44

Page 18: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 18

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A44 Steel

* freely adjustable

** NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

**

*

*

Page 19: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 19

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A44 Bronce

**

* freely adjustable

** NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

*

*

Page 20: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 20

ZS/S 1.1 Meter Interface ModuleETS Parameter settings A44 Silver, Gold, Platinum

**

* freely adjustable

** NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

*

*

Page 21: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 21

B21

Page 22: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 22

ZS/S 1.1 Meter Interface ModuleETS Parameter settings B21 Steel

Page 23: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 23

ZS/S 1.1 Meter Interface ModuleETS Parameter settings B21 Bronce

Page 24: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 24

ZS/S 1.1 Meter Interface ModuleETS Parameter settings B21 Silver

Page 25: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 25

B23

Page 26: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 26

ZS/S 1.1 Meter Interface ModuleETS Parameter settings B23 Steel

* NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

*

Page 27: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 27

ZS/S 1.1 Meter Interface ModuleETS Parameter settings B23 Bronce

* NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

*

Page 28: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 28

ZS/S 1.1 Meter Interface ModuleETS Parameter settings B23 Silver

*

* NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

Page 29: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 29

B24

Page 30: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 30

ZS/S 1.1 Meter Interface ModuleETS Parameter settings B24 Steel

**

* freely adjustable

** NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

*

*

Page 31: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 31

ZS/S 1.1 Meter Interface ModuleETS Parameter settings B24 Bronce

* freely adjustable

** NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

**

*

*

Page 32: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized

© ABBMrz-14 STO/G | 32

ZS/S 1.1 Meter Interface ModuleETS Parameter settings B24 Silver

* freely adjustable

** NOTE:

Settings in ETS parameter Voltage network (4-wire or 3-wire) must be identical

with voltage network settings in the meter.

**

*

*

Page 33: ABB i-bus® KNX, STO/G ZS/S 1.1 Meter Interface Module ETS ......ETS Parameter settings (A-/B-Series) In the ETS application program ZS/S, the connected meter must be parameterized