Acceptance processNoSite NameSite Code1st ATP visit date2nd ATP visit date3rd ATP visit date4th ATP visit dateATP PowerPower comment (Task description No.)ATP BSSBSS comment (Task description No.)ATP TRTR Comment (Task description No.)ATP RFRF Comment (Task description No.)Status of visit1Al- AswadDY285917-Mar-1519-Apr-1528-Apr-157-May-15Minor1-Ubnormal sound in G2.2-All metal Tray cable without stand and not grounded .3-Aviation light working abnormally.4-surge arrestor need to directly connection to the base bar.5-Fuel tank need to cover lock.
Civil snags are Korek responsibility:1-External tray need more fixations and need to be grounded to bus bar.2-Safety ladder cage need more fixation.3-Sectors & MW support screws need to be tightened(double net).4- Tray must have a rubber glands to avoid any sharp edge.5-Tray cover need more fixation.Minor1-External alarm cable bad quality type.2-Roxtic must be replaced (without any silicon on it).3-Check all feeders and jumpers (VSWR, DTF).4-External alarm aviation light must be activated (always not activated).Minor1-IF cable need more systemization (Must be the lack of any increases in the cable near the MW).2-TN most be grounded (ground cable exist but not connected to AMM2p).3-MW need label 24 mm in middle also need label on IF cable.4-Re systemize ICF Cable .5- Alignment screw is damaged & soldered most be replaced.Minor1-Feeder jumpers to antenna need more isolation (most isolated with electrical tape then water proof then with electrical tape).2-Need label on all outdoor jumpers, feeders, three sectors.3-Indoor jumpers need label especially for RUS 1800.4-Earth kit need to fix on bus bar in right way.5-Cell A 1800 jumpers too short inside RBS cabinet.6-Cell A DX1 jumper damage must be replaced Minor