Upload
brianna-hoover
View
215
Download
1
Tags:
Embed Size (px)
Citation preview
Active beams versus VAV with ReheatAnalysis of May 2013 ASHRAE Journal article
Ken Loudermilk
Vice President, Technology & Developement
Pre-treated Primary Air
Entrained Room Air
Supply Air to Room
1 Part
3 to 5 Parts2 to 4 Parts
Air handling unit
0.4 to 0.7 in. SP
Active Chilled Beams
Cost to transport cooling with water 15 to 20% that of air
1“ Dia. Water Pipe
14“ x 14“
Air Duct
Comparison of water to air as a heat transfer medium
Primary airflow requirement is the greater of:
• Volume flow rate needed to maintain mandated ventilation to space • Volume flow rate needed to offset space sensible heat gains
• Sensible cooling contribution• Drive induction of room air through coil
• Volume flow rate needed to maintain space dew point temperature
Pre-treated primary air
Typical active beam cooling operation
Typical active beam cooling operation
67% of space sensible heat removal by water
33% of space sensible heat removed by primary air
ACB with 55˚F primary air
• Office/classroom building at UC Davis• 56,500 ft2 building
• Sensible loads average 19.5 Btu/h-ft2
• Occupancy is one person per 275 ft2
• Compares VAV + reheat to ACB system with DOAS
• Analyzes and compares• System first cost
• System energy use
• Other benefits of VAV + R
Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013
Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013
• Sensible design (outdoor air)•100˚F DB/70˚F WB (54˚F dew point)
•Humidity ratio W = 62.2 grains/lbm-DA
•Enthalpy h = 33.8 Btu/h-lbm
• Off peak operation (outside air)•50% indoor sensible load
•77˚F DB/59˚F WB (46˚F dew point)
•Humidity ratio W = 46.3 grains/lbm-DA
•Enthalpy h = 25.8 Btu/h-lbm
Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013
• 100% OA (DOAS) air handling unit•No energy recovery!
•Primary air 63˚F, 54˚ DP (W = 2.7 grains)
•0.15 CFM/ft2 for ventilation
•0.53 CFM/ft2 for latent cooling!!
•Primary airflow • 30,000 CFM (0.53 CFM/ft2)
• Constant air volume, no set back
• No DCV provisions
• Mixing AHU with VFD•Equipped with airside economizer
•Primary air 55˚F, 52˚ DP (ΔW = 8 grains)
•0.15 CFM/ft2 for ventilation
•0.18 CFM/ft2 for latent cooling
• Primary airflow• 50,000 CFM (0.88 CFM/ft2)
•Normal VAV turndown ratio of 6:1
• Interior terminals DCV (allows shut off)
VAV + reheat systemACB system
Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013
Performance comparison of systems as described
Ventilation 0.15 0.15 0.15 0.15
Dehumidification 0.18 0.18 0.53 0.53
Sensible Cooling 0.60 1.75 0.22 0.53
Design airflow rates in CFMPA per square foot
Primary air conditions and flow rates as described by authors
Resultant Airflow 0.60 1.75
Avg. 0.88 CFM/ft2
0.53 0.53
Avg. 0.53 CFM/ft2
VAV System
Interior Space Perimeter Space
ΔW = 7.9 grains55˚ DB/52˚ DP
ACB System
Interior Space Perimeter Space
ΔW = 2.7 grains63˚ DB/54˚ DP
Air handling unit configurations as described
VFD 30,000 CFM30,000 CFM
8,300 CFMRelief
Fan
8,475 to 50,000 CFM0 to 41,700
CFM recirculation
Bypass Damper
Fan Array
Cooling Coil
Heating Coil
OA Filters
30,000 CFM 30,000 CFM
(0.53 CFM/Ft2)
63⁰F
Fan Array
Cooling CoilFilters
8,300 CFM
8,475 to 50,000 CFM
(0.15 to 0.88 CFM/Ft2)
55⁰F
Note: 100% OA, no energy recovery! Note: OA requirement only 0.15 CFM/Ft2, 16% of design airflow rate!
Authors‘ performance conclusions
Energy use comparable
ACB system more than
double
˚F CFM CFM % kW kW BHP BHP kW
VAVR system as described 55 8,475 41,525 17% 49.9 0.0 45.6 5.5 88.0
ACB system as described 63 30,000 0 100% 40.5 23.5 26.0 8.7 89.9
Sensible design conditions (100% sensible & latent space loads)
SAT OARAOAAHU
coolingBeam
coolingFan Pumps
Total energy
˚F CFM CFM % kW kW BHP BHP kW
VAVR system as described 55 8,475 16,525 34% 13.0 0.0 6.6 2.0 19.4
ACB system as described 63 30,000 0 100% 15.6 5.1 26.0 1.4 41.2
Shoulder season operation (50% sensible, 80% latent space load)
SAT OA RA OAAHU
coolingBeam
coolingFan Pumps
Total energy
Authors‘ performance conclusions
30
25
20
15
5
0
kBtu
/ft2 -y
ear
10
2.30.1
17.9
5.1
12.8
1.51.0
District coolingHeatingFansPumps
ACB Design as Described
VAV Reheat
0.0
Authors‘ performance conclusions
Energy use comparable
ACB system more than
double
˚F CFM CFM % kW kW BHP BHP kW
VAVR system as described 55 8,475 41,525 17% 49.9 0.0 45.6 5.5 88.0
ACB system as described 63 30,000 0 100% 40.5 23.5 26.0 8.7 89.9
Sensible design conditions (100% sensible & latent space loads)
SAT OARAOAAHU
coolingBeam
coolingFan Pumps
Total energy
˚F CFM CFM % kW kW BHP BHP kW
VAVR system as described 55 8,475 16,525 34% 13.0 0.0 6.6 2.0 19.4
ACB system as described 63 30,000 0 100% 15.6 5.1 26.0 1.4 41.2
Shoulder season operation (50% sensible, 80% latent space load)
SAT OA RA OAAHU
coolingBeam
coolingFan Pumps
Total energy
Actual performance comparisons
Operation
al Energy use,
kW
100
90
80
70
60
50
40
30
20
10
0
Sensible Design Performance Latent Design Performance Shoulder Season Performance
52.0
VAVR
sys
tem
79.2
ACB
syst
em
as d
esig
ned
41.2
19.4
VAVR
sys
tem
ACB
syst
em
as d
esig
ned
88.0
VAVR
sys
tem
89.9
ACB
syst
em
as d
esig
ned
What’s wrong with this picture?
• ACB system primary airflow rate as designed is driven by space latent load combined with low ΔW
• Primary airflow rate is 75% greater than that typically required by properly designed ACB systems
• Beam water side cooling capacities (23.6 Btu-h-CFM) as designed are far lower than those (40 to 50 Btu/h-CFM) in properly designed ACB systems
Ventilation
System Design TPA (˚F) Btu/h-ft2 Btu/h-CFM CFM/ft2
% Space Sensible Cooling
Btu/h-CFM
% Space Sensible Cooling
Btu/h-ft2
ΔW grains
Btu/h-CFM CFM/ft2 CFM/ft2
0.15
0.150.307.5NA19.5
63.0 19.5 13.2 0.53 36% 23.6
VAVR system as described
ACB system described
55.0 22.0
Latent Cooling Requirement (all airside)
Waterside sensible cooling
Primary Air Sensible Cooling
11.0
6.0
0.89
64% 2.2
100% 2.2
4.1 0.53
NA
Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013
Performance comparison with properly designed ACB system
Air handling unit modifications for ACB system
8,300 CFM
VFD16,667 CFM16,667 CFM
Fan Array
Cooling Coil
Heating Coil
OA Filters
Bypass Damper
30,000 CFM16.667 CFM
(0.3 CFM/Ft2)
55⁰F
Fan Array
Cooling CoilFilters
Relief Fan
8,475 CFM
16.667 CFM
16,667 CFM8,192 CFM
recirculation
(0.3 CFM/Ft2)
55⁰F
Reduce SAT to 55˚FLower PA dew point allows primary airflow
reduction of 45% and an associated fan energy reduction of 70%!
Introduce mixing at AHUMixing results in an additional 30%
reduction in chiller energy!
Leveling the playing field
• Same primary air conditions used for both systems
• ACB system primary airflow rate reduced from 30,000 CFM to 16,950 CFM!
• Beam water side cooling capacity (44 Btu-h-CFM) increased by 86%
Ventilation
System Design TPA (˚F) Btu/h-ft2 Btu/h-CFM CFM/ft2
% Space Sensible Cooling
Btu/h-CFM
% Space Sensible Cooling
Btu/h-ft2
ΔW grains
Btu/h-CFM CFM/ft2 CFM/ft2
0.15
0.150.307.5NA19.5
63.0 19.5 13.2 0.53 36% 23.6
VAVR system as described
ACB system described
55.0 22.0
Latent Cooling Requirement (all airside)
Waterside sensible cooling
Primary Air Sensible Cooling
11.0
6.0
0.89
64% 2.2
100% 2.2
4.1 0.53
NA
0.30 0.1533% 44.0 67% 2.2 7.5 0.3011.0Properly designed ACB system
55.0 19.5 22.0
0.15 0.15
0.18 0.18
0.20 0.60
Design airflow rates in CFMPA per square foot
Primary air conditions and flow rates for modified ACB system
0.20 0.60
Avg. 0.30 CFM/ft2
Ventilation 0.15 0.15
Dehumidification 0.18 0.18
Sensible Cooling 0.60 1.75
Resultant Airflow 0.60 1.75
Avg. 0.88 CFM/ft2
VAV System
Interior Space Perimeter Space
ΔW = 7.9 grains55˚ DB/52˚ DP
ACB System
Interior Space Perimeter Space
ΔW = 2.7 grains55˚ DB/52˚ DP
Actual performance calculations
˚F CFM CFM % kW kW BHP BHP kW
VAVR system as described 55 8,475 41,525 17% 49.9 0.0 45.6 5.5 88.0ACB system as described 63 30,000 0 100% 40.5 23.5 26.0 8.7 89.9
Sensible design conditions (100% sensible & latent space loads)
SAT OARAOAAHU
coolingBeam
coolingFan Pumps
Total energy
30% less than VAVRPrimary air @ 55 ˚ F DB , 53 ˚F DP 55 16,667 0 100% 28.7 24.4 4.5 7.6 62.1
Modified ACB system
38% less than VAVRMixing at air handling unit 55 8,475 8,192 51% 21.6 24.4 4.5 6.8 54.5
˚F CFM CFM % kW kW BHP BHP kW
VAVR system as described 55 8,475 29,025 23% 26.6 0.0 26.0 2.9 48.2ACB system as described 63 30,000 0 100% 40.2 14.3 26.0 7.0 79.2
Beam cooling
Fan PumpsTotal
energyLatent design conditions (75% sensible, 90% latent space load)
SAT OA RA OAAHU
cooling
˚F CFM CFM % kW kW BHP BHP kW
VAVR system as described 55 8,475 16,525 34% 13.0 0.0 6.6 2.0 19.4ACB system as described 63 30,000 0 100% 15.6 5.1 26.0 1.4 41.2
Shoulder season operation (50% sensible, 80% latent space load)
SAT OA RA OAAHU
coolingBeam
coolingFan Pumps
Total energy
Same as VAVRPrimary air @ 55 ˚ F DB , 53 ˚F DP 55 16,667 0 100% 8.4 6.1 4.5 2.0 19.3
Modified ACB system
Was more than doubleMixing at air handling unit 55 16,667 0 100% 8.4 6.1 4.5 2.0 19.3* Air handling unit operating in economizer mode
Primary air @ 55 ˚ F DB , 53 ˚F DP 55 16,667 0 100% 28.5 15.3 4.5 5.9 51.5
Modified ACB system
6% more than VAVRMixing at air handling unit 55 8,475 8,192 51% 10.3 15.3 4.5 3.9 31.8 34% less than VAVR
Actual performance comparisons using modified ACB system
Operation
al Energy use,
kW
100
90
80
70
60
50
40
30
20
10
0
Sensible Design Performance Latent Design Performance Shoulder Season Performance
62.1
ACB
syst
em,
55˚F
PA
54.5 AC
B sy
stem
,
AHU
mix
ing
51.5
ACB
syst
em,
55˚F
PA
31.8
ACB
syst
em,
AHU
mix
ing
22.0
ACB
syst
em,
55˚F
PA
22.0
ACB
syst
em,
AHU
mix
ing
52.0
VAVR
sys
tem
79.2
ACB
syst
em
as d
esig
ned
41.2
19.4
VAVR
sys
tem
ACB
syst
em
as d
esig
ned
88.0
VAVR
sys
tem
89.9
ACB
syst
em
as d
esig
ned
Active beams with a DOAS vs. VAV with reheat ASHRAE Journal, May 2013
System cost comparisons
Authors’ installed cost comparison of the systems as designed
Cost or Qty. Cost/CFM Cost or Qty. Cost/CFM$215,179 $4.30 $576,496 $19.22$584,058 $11.68 $1,509,349 $50.31$319,695 $6.39 $608,349 $20.28$252,067 $5.04 $647,037 $21.57
38,000 28,612310 10,244
2,085 9,630
$1,370,999 $3,341,231
$25 $27 $62 $111
Equipment cost ($)Labor cost ($)
Material cost ($)
VAV system as designed
Lbs. of ductwork (lbs.)Chilled water piping (LF)
Hot water piping (LF)
Total HVAC cost ($)
HVAC cost ($/ft2)
Subcontractors ($)
ACB system as designed
System ductwork configuration
900 FPM
0.53 CFM/Ft2
2,000 FPM @ 0.9 CFM/Ft2
ACB System MainsAEFF = 30,000/900 = 33.3
VAV System MainsAEFF = 50,000/2,000 = 25.0
Authors’ conclusion: Average duct cross sectional area 33% greater for the ACB system
Two supply risers
One supply riser
Ductwork configuration
2,000 FPM2,000 FPM
ACB System MainsAEFF = 16,667/2,000 = 8.3
VAV System MainsAEFF = 50,000/2,000 = 25
VAVR system average duct cross sectional area is triple that of the ACB system when sized for the same maximum velocity
Beam requirements
• Number of beams reduced by 63% by modifying ACB system
• 63% reduction in beam piping and insulation costs
Area served, ft2 38,922 17,578 56,500 38,922 17,578 56,500
BTU/H-ft2 13.4 33.0 19.5 13.4 33.0 19.5
CFMPA 23,634 26,367 50,000 13,123 16,877 30,000
CFMPA/ft2 0.61 1.50 0.88 0.34 0.96 0.53
BTU/H-CFMPA 22.0 22.0 22.0 39.6 34.4 38.0
305 550 398
7.7 16.0 10.9
1,706 1,055 2,761
ACB Btu/h-LFACB CFM PA /LF
Linear feet of ACB required
All zones
VAV system as described ACB system as described
Interior zones
Perimeter zones
Interior zones
Perimeter zones
All zones
38,922 17,578 56,500
13.4 33.0 19.5
7,878 8,789 16,667
0.20 0.50 0.29
66.0 66.0 66.0
1,056 1,056 1,056
16.0 16.0 16.0
492 549 1,042
Modified ACB system
Interior zones
Perimeter zones
All zones
Remedies for other cost inequities
• Perimeter VAV terminals serve multiple offices
• Interior VAV terminals have no reheat provisions
• Perimeter VAV terminals require only one HW connection per zone
• No indication of thermal zoning or condensation prevention in ACB system
• Four pipe configuration of interior space beams
• Remedy: Eliminate heating provision on interior beams
• Eliminates HW piping/insulation and connection to interior beams
• Perimeter beams require individual HW connections
• Accomplish perimeter heating by heating primary air
• Reduces HW piping/insulation and connections to one per perimeter zone
Cost or Qty.$320,282$838,544$337,978$359,472
15,8965,6915,350
$1,856,277
$33
Modified ACB system
Cost comparison using modified ACB system
Cost or Qty. Cost/CFM Cost or Qty. Cost/CFM$215,179 $4.30 $576,496 $19.22$584,058 $11.68 $1,509,349 $50.31$319,695 $6.39 $608,349 $20.28$252,067 $5.04 $647,037 $21.57
38,000 28,612310 10,244
2,085 9,630
$1,370,999 $3,341,231
$25 $27 $62 $111
Equipment cost ($)Labor cost ($)
Material cost ($)
VAV system as designed
Lbs. of ductwork (lbs.)Chilled water piping (LF)
Hot water piping (LF)
Total HVAC cost ($)
HVAC cost ($/ft2)
Subcontractors ($)
ACB system as designed
Modified ACB system cost assumes the cost per CFM for the ACB system remains constant and thus system costs are proportional to the reduced primary airflow requirements. These costs also do not include any possible reheat piping reduction opportunities discussed before.
Total $ $/ft2 Total $ $/ft2
Central Equipment Costs $554,608 $9.83 $467,782 $8.29
Air handling units and exhaust fans $196,642 $137,201
Chillers $223,253 $169,152
Boilers $37,384 $66,204
Pumps $97,329 $95,225
Air and water distribution costs $851,323 $15.09 $1,060,439 $18.80
Ductwork and insulation $389,350 $237,025
Piping and insulation $91,944 $460,106 $8.16
Air terminal units $150,109 $0
Supply/return grilles and diffusers $92,610 $19,824
Active beams $0 $263,000
Zone controls $127,310 $80,485
Other costs $197,400 $3.50 $206,400 $3.66
Fire and life safety $84,600 $84,600
Commissioning $112,800 $112,800
Condensation prevention $9,000
TOTAL INSTALLED COST OF HVAC SYSTEM $1,603,332 $28.43 $1,734,621 $30.76
All-air system
Mixing type without energy recovery
Beam system (pulldown menu)
Mixing type without energy recovery
Beam system (pulldown menu)
2 pipe beams, primary air heating coil
All air system (pulldown menu)
Single duct VAV with reheat
Specify perimeter heat method
Condensation prevention (pulldown menu)
SYSTEM TYPE
Gray cells require user input
All air VAV Active Beams
Summary Table Specify AHU configuration
Reset each floor chilled water supply temperature
Installed cost comparison (ACB system with mixing AHU, no ER)
Article in winter 2013 High Performance Buildings
• UC Davis Health and Wellness Center•73,112 ft2 of conditioned space
•LEED-NC Gold
•Occupied since March 2010
•DOAS air handling strategy
• Energy performance•Projected 35% better than LEED baseline
•Actual 31% better than projected
•70% less primary air than VAV system
Chilled beams!
And the hands down winner is………
Questions?
Active beams versus VAV with ReheatAnalysis of May 2013 ASHRAE Journal article