5
ISO9001 Certified FEATURES DC Energy Management Systems Power Distribution for Telecommunication Room Solar Photovoltaic Systems Wind Power Generation DC Excitation System Industrial DC Control Systems AcuDC 240 Series Metallurgy and Electroanalysis Industries EV Charging Monitoring Data Center Cellular Tower Energy Monitoring DC Power and Energy Meters

AcuDC 240 Series - Accuenergy · External DC Power Vdc dc-+ _ + _ M G I 6 - 5 + _ M G G 3 U-I 6 I-5 + _ M G 3 1 C ur r ent Hall Unit: mm (inch) U-U G G G M 1 I I-I I-U G ±15 External

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: AcuDC 240 Series - Accuenergy · External DC Power Vdc dc-+ _ + _ M G I 6 - 5 + _ M G G 3 U-I 6 I-5 + _ M G 3 1 C ur r ent Hall Unit: mm (inch) U-U G G G M 1 I I-I I-U G ±15 External

ISO9001 Certified

FEATURES DC Energy Management Systems Power Distribution for Telecommunication Room Solar Photovoltaic Systems Wind Power Generation DC Excitation System Industrial DC Control Systems

AcuDC 240 Series

Metallurgy and Electroanalysis Industries EV Charging Monitoring Data Center Cellular Tower Energy Monitoring

DC Power and Energy Meters

Page 2: AcuDC 240 Series - Accuenergy · External DC Power Vdc dc-+ _ + _ M G I 6 - 5 + _ M G G 3 U-I 6 I-5 + _ M G 3 1 C ur r ent Hall Unit: mm (inch) U-U G G G M 1 I I-I I-U G ±15 External

INTRODUCTIONAcuDC 240 series power meter can be used for monitoring and controlling in DC systems. These meters can measure a wide range of parameters such as voltage, current, power and energy. It supports bi-directional current measurement, digital inputs for switch monitor-ing and relay outputs for remote controlling as well as an over-range alarming feature for voltage and current. Large signals, such as voltage and current can be converted to smaller signal using analog output. All data in the meter is accessible via RS485 using open Modbus RTU protocol. The large 3 line LCD display also provides easy to read real-time data directly on the meter front.

AcuDC 240 Series DC Power Meter

APPLICATIONS• DC Energy Management Systems• Power Distribution for Telecommuni-

cation Room• Solar Photovoltaic Systems• Industrial DC Control Systems• Metallurgy and Electroplating Indus-

tries

• Wind Power Generation• DC Excitation Systems• Light Rail Transit Systems• EV Charging Monitoring• Data Center• Cellular Tower Energy Monitoring

FEATURES• DC power system metering• Monitor and control power switches• Alarming and analog output• Standard 72x72mm, allows for drawer type panel installation• Three line high-definition LCD display• Accessible with SCADA, PLC systems• Easy installation, simple wiring• Data Logging: Offers 3 assignable historical logs where the all of the metering parame-

ters can be recorded.• The onboard memory is up to 4 MB and each log size is adjustable.

SPECIFICATIONSFunction AcuDC 241 AcuDC 242 AcuDC 243

METERING

Voltage VCurrent IPower PEnergy E

Ampere-hour Ah

I/O

2DI+2AOSupport DI

count2DI+2RO2DI+2DO

2DI+ ±15Vdc

DATALOGGING

All metering parameters can be recorded (Voltage, Current, Power, Energy, Ampere-hour, DI Count); Interval 1 minute;Can record 4 months

COMMUNICATION RS485 , Modbus RTUDISPLAY LCD

DIMENSIONS 72×72×64.5mm (Cutout: 68×68 mm) / 2.835×2.835×2.539 inch (Cutout: 2.677×2.677 inch)

Note: Standard; Optional Blank: Not Available

Page 3: AcuDC 240 Series - Accuenergy · External DC Power Vdc dc-+ _ + _ M G I 6 - 5 + _ M G G 3 U-I 6 I-5 + _ M G 3 1 C ur r ent Hall Unit: mm (inch) U-U G G G M 1 I I-I I-U G ±15 External

Analog Output4~20mA, R<500Ω

21

AO1-

Analog Output

AcuDC 240

22

AO1+

TYPICAL WIRING

DIMENSIONS

Digital Input

AcuDC 240

DI11Digital Input

DI12DI21

DI2217 18 19 20

(External Power Supply < 250Vacor 30Vdc I<3A)

21

R11

Relay Output

AcuDC 240

Intermediate Relay

External Power Supply

R12R21

R22

2223

24

AC / DC

AC / DC

U+

U -

AcuDC 240

AcuDC 240

Vdc+ Vdc-

1

3

Voltage Direct Wiring

I -

I+

6

5

AcuDC 240

Load

Vdc+ Vdc-

Current Direct Wiring

Voltage & Current Direct Wiring

Load

Vdc+ Vdc-

I -

I+

6

5AcuDC 240

3

1

U-

U+

Voltage & Current Wiring using Shunt

Load

Vdc+ Vdc-

Shunt 75mV

I -

I+5

6AcuDC 240

3

1

U-

U+

Voltage Wiring using

Voltage & Current Wiring using Current Voltage & Current Wiring using Hall

S1

S2

23

AO2-

24

AO2+

External Resistor R

External Resistor R

72.0(2.835)

72.0

(2.8

35)

FRONT PANEL CUTOUT

Unit: mm (inch)

18.0(0.709)

68.0

(2.6

77)

68.0(2.677)

51.7(2.035)

12.8(0.504)

67.0

(2.6

38)

72.0

(2.8

35)

SIDE

65.5(2.579)

51.4

(2.0

24)

51.4

(2.0

24)

I/O Module

Cut-Out

Load

AcuDC 240

Vdc+ Vdc-

3

1

U-

U+

AcuDC 240Current Hall

Load

Vdc+ Vdc-

±15 External DC Power

±15 External DC Power

External DC Power

Vdc+ Vdc-

+_

+_

M

G

I+

I -6

5

+_

MG

U-3G

I+I -6

5

+_

MG 3

1

Current Hall

Unit: mm (inch)

U-U+

GG

G

1M

IN+

IN-

IN+

IN-

U+

G

±15 External DC Power

NOTE: ±15V power supply from the X5 module.

NOTE:±15V power supply from the X5 module.

NOTE:±15V power supply in the X5 module.

NOTE: A physical jumper from terminal 3 to 6 must be connected.

Page 4: AcuDC 240 Series - Accuenergy · External DC Power Vdc dc-+ _ + _ M G I 6 - 5 + _ M G G 3 U-I 6 I-5 + _ M G 3 1 C ur r ent Hall Unit: mm (inch) U-U G G G M 1 I I-I I-U G ±15 External

AcuDC 240 Series DIN Rail Mounting Adapter

4.0(0.157)

7.8(0.275)

7.5 (0.295)

6.8(0.268)

6.8(0.268)

7.8(0.275)

6(0.236)7.8

(0.275)

6.8(0.268)

6.8(0.268)

FRONT SIDE BACK

unit: mm (inch)

DIMENSIONS

AcuDC 240 Series DIN Rails adapter provide easy installation of panel-mount AcuDC 240 series meter on DIN rail in all models and IO options.

Page 5: AcuDC 240 Series - Accuenergy · External DC Power Vdc dc-+ _ + _ M G I 6 - 5 + _ M G G 3 U-I 6 I-5 + _ M G 3 1 C ur r ent Hall Unit: mm (inch) U-U G G G M 1 I I-I I-U G ±15 External

ORDERING INFORMATION AcuDC 240

AcuDC 241:AcuDC 242:AcuDC 243:

Voltage MeterCurrent MeterMultifunction

Model

Power Supply Option P1: 100-240Vac 50/60Hz, 100-300Vdc

P2: 20-60Vdc

Voltage Option

A0: 0~±10AA1: Shunt (50~100mV)

Communication

CommunicationTypeProtocolBaud rateIsolation Voltage

RS485, half duplex, Optical IsolatedModbus-RTU1200~38400bps2500Vac

Parameter Accuracy Resolution RangeVoltage 0.2% 0.001V 0~1200VCurrent 0.2% 0.001A 0~±50000APower* 0.5% 0.001kW 0~±60000kWEnergy* 0.5% 0.01kWh 0~9999999.99kWh

Dri h Temperature <100ppm/˚CStability 0.5‰/year

TECHNICAL SPECIFICATIONS

VoltageInput RangeVoltage Input Impedence Load Accuracy

2MΩ<0.6W 0.2%

CurrentInput Range

Shunt

Power ConsumptionAccuracy

0~±10A(Direct Input, pick up current 0.01A)

programmable range)50~100mV(programmable)0~±5V/0-±4V, 4~20mA/12mA±8mA2W(Max)0.2%

Digital InputTypeIsolation Voltage

Dry Contact2500Vac

Current Option

1000V: Nominal Input Voltage 1000Vdc600V: Nominal Input Voltage 600Vdc300V: Nominal Input Voltage 300Vdc60V: Nominal Input Voltage 60Vdc

Example: AcuDC 243 - 300 - A2 - P1 - X1 - C - D

NC: No CommunicationC: RS485, Modbus RTU

X0: No I/OX1: 2DI+2AO (4~20mA/0~20mA)X2: 2DI+2AO (0~5V/1~5V)X3: 2DI+2ROX4: 2DI+2DOX5: 2DI+ ±15Vdc

I/O Option

Power SupplyInput

Consumption

(P1)100-240Vac, 50/60Hz, 100-300Vdc(P2) 20-60Vdc3W (typical value)

EnvironmentOperation TemperatureStorage TemperatureHumidity

-25°C ~ +70°C-40°C ~ +85°C5%~95%Non-condensing

Standard Compliance

Safety Standard IEC 61010-1EMC Standard IEC 55011,IEC 61000-6-2,IEC 61000-3-2

IEC 61000-3-3

OutputRelay Output (RO)TypeMax Load VoltageMax Load CurrentOn ResistanceIsolation VoltageMechanical Life

Mechanical contact, Form A250Vac/30Vdc3A100mΩ (Max)4000Vac5 × 106 times

Digital Output (Photo-Mos)Load Voltage RangeLoad CurrentMax Output FrequencyIsolation Voltage

0~250Vac/dc100mA(Max) 25Hz, 50% duty cycle2500Vac

Analog Output (AO)RangeAccuracyLoad Capacity

4-20mA/0~20mA; 0~5V/1-5V0.5%Current type, max load resistance: 750 OhmVoltage type, max load current: 20 mA

VOLTAGE HALL EFFECT SENSOR ORDERING INFORMATION (0~5V output)

CURRENT HALL EFFECT SENSOR ORDERING INFORMATION (4~20 mA output)

Note:

When the input voltage is above 1000V, or the system design requires an isolation sensor, the voltage input can be

Special order

0.2% accuracy for Power and Energy

Special Order

Please contact your local Accuenergy representative for further details

Please contact your local AccuenergyRepresentative for further details

Datalogging ND: No DataloggingD: Datalogging (AcuDC 243 Only)

* 0.2% accuracy on Power and Energy available upon request

Make Energy Usage Smarter

Accuenergy Corp.Los Angeles - Toronto - Beijing - PretoriaNorth America Toll Free: 1-877-721-8908Web: www.accuenergy.comEmail: [email protected]

Revision Date: Sep., 2018 | Document #1504 E1112

ORDERING INFORMATIOMModel DC DIN