713.487.3400 Energyarch.com 2777 Allen Parkway, Suite 460 Houston, TX 77019
Addendum 01 1/1 RELLIS Administration Complex Extension 1555 Ave D Bryan, TX 77807 Energy Architecture Project #: 19114 Date: 18 January 2021 This addendum issued pursuant to Article 1.1.1 of the AIA General Conditions of the Contract for Construction (A201) in connection with the revisions of Permit Documents dated 01/04/2021 which have been previously issued. This document shall become attached to and part of the Construction Documents for the above mentioned project, as though it had been issued at the same time and incorporated integrally therewith. DOCUMENTS: BID Request For Information - Responses SPECIFICATIONS: 00 21 00 – Competitive Sealed Proposals • Remove “Day 2” from Paragraph 5.2.3
01 25 00 – Substitution Procedures • Substitution Request Forms DRAWINGS: A-001 – ASSEMBLY AND PARTITION TYPES • Added ROOF-1 Detail A-102 – MEZZANINE FLOOR PLAN • Note 15 has been updated to remove overlapping notes End of Addendum 01
01/18/2021
713.487.3400 Energyarch.com 2777 Allen Parkway, Suite 460 Houston, TX 77019
BID REQUEST FOR INFORMATION – ADDENDUM 1 1/2 RELLIS Administration Complex Extension 1555 Ave D Bryan, TX 77807 Energy Architecture Project #: 19114 Date: 18 January 2021 BID QUESTIONS:
1. Section 01 91 00 references Special Procedure – LEED Certification. Please confirm LEED certification is not required. Response: LEED certification is not required on this project.
2. Section 12 24 00 only lists Lutron as the shade manufacturer. Is Hunter Douglass an acceptable manufacturer also? If so, please provide an acceptable window shade management system for the alternate for Hunter Douglas. Response: Refer to specification section 01 25 00 Substitution Procedures for any substitutions to be reviewed by Design Team. Please use attached Substitution Request form.
3. Specifications for the rubber base and static dissipative floor tile is not provided. Please advise. Response: Refer to drawing A-105 for rubber base and dissipative floor tile manufacturer, types, and sizes.
4. Substitution Request: Window Systems - Sierra Pacific Windows Response: GENERAL NOTE: Bidders to price specified products included in bid documents. Qualified substitutions are to be priced as a voluntary alternate to be reviewed after bid date. Refer to specification section 01 25 00 Substitution Procedures for any substitutions to be reviewed by Design Team. Please use attached Substitution Request form.
5. Substitution Request: Air Barrier – Dörken Systems, Inc. Response: GENERAL NOTE: Bidders to price specified products included in bid documents. Qualified substitutions are to be priced as a voluntary alternate to be reviewed after bid date. Refer to specification section 01 25 00 Substitution Procedures for any substitutions to be reviewed by Design Team. Please use attached Substitution Request form.
6. Remove “Day 2” from Paragraph 5.2.3 of Section 00 21 00 – Competitive Sealed Proposals.
7. Confirm UPS Panels are required for the BAS on this project per 23 09 00 1.2.N? UES’s previous communication was that if there is no backup power, UPSes are not required.
2/2
2 | 2
Response: Confirmed, UPS Panels are not required because the building does not have backup power.
8. IR2 lists a flow meter requirement. Typically this flow meter is provided by BAS and is to be by the manufacturers listed in 23 09 00. Please confirm if the BAS contractor is to provide the flow meter and if by a manufacturer listed in 23 09 00. Response: Confirmed, BAS Contractor to provide flow meter per spec.
9. IR2 lists a flow meter requirement. Is the flow to be monitored and on graphics of the BAS front end? Response: Yes, flow shall be monitored on the BAS front end.
10. P1.1 Keyed Note 2 lists a 2” flow meter for domestic water. Is the BAS contractor to provide this scope as it is typical at TAMU? Response: Yes, BAS to provide flow meter for domestic water. Refer to P1.1 Note 14 for flow meter spec
11. P1.1 Keyed Note 2 lists a 2” flow meter for domestic water? Is the flow to be monitored and on the graphics of the BAS front end? Response: Yes, flow shall be monitored on BAS front end.
2777 Allen Parkway, Suite 460Houston, TX 77019713.487.3400www.energyarch.com
ASSEMBLY ANDPARTITION TYPES
A-001
RELL
IS A
dmin
istra
tion
Com
plex
Ext
ensio
nRE
LLIS
Cam
pus
1555
Ave
DBr
yan,
TX 7
7807
EA PROJECT NUMBER: 19114
REV DATE DESCRIPTION
NOT FORREGULATORYAPPROVAL,
PERMITTING ORCONSTRUCTION
0 01/04/2021 ISSUED FOR CONSTRUCTION
ARCHITECT : BRIAN TODD ARENZLICENSE #: 18478
5/8" THICK FIBER-CEMENT LAP SIDINGASPHALT SHINGLES
ICE & WATER BARRIER
81/4" THICK STRUCTURAL INSULATED PANEL, RE: STRUCT
GALVANIZED STEEL FURRING CHANNELS@ 24" O.C., RE: STRUCT
FIBERGLASS REINFORCED PLASTIC "Z" GIRTS @ 16" O.C.
MINERAL WOOL INSULATION
AIR BARRIER
PRESSURE TREATED PLYWOOD
CFMF, RE: STRUCT
THERMAL BATT INSULATION
GYP BOARD OR WOOD PANELING, RE: INTERIOR ELEVATIONS
5/8" THICK FIBER-CEMENT LAP SIDING
FIBERGLASS REINFORCED PLASTIC "Z" GIRTS @ 16" O.C.
AIR BARRIER
PRESSURE TREATED PLYWOOD
CFMF, RE: STRUCT
GYP BOARD
GALVANIZED STEEL FURRING CHANNELS@ 24" O.C., RE: STRUCT
10 3/4"
1 5/16"
7/8" 1 1/2"7/16"
6"5/8"
10 3/4"
1 5/16"
7/8" 1 1/2"7/16"
6"5/8"
1
2
4
1
3
5
6
2
1
3
1
2
3
3
2
3
4
5
6
9
7
8
8
9
1
2
4
1
3
5
6
2
3
4
5
7
7
7
EXTERIOR WALL ASSEMBLIESEXTERIOR WALL ASSEMBLIES
6.5"
12"
EXTERIOR WALL ASSEMBLIES
XWA-1ROOF-1 XWA-2
6
45° MAX
PARTITION GENERAL NOTES
3. REFER TO FLOOR PLANS FOR LOCATION AND EXTENTS OF PARTITIONS. PARTITION TYPES ARE INDICATED WITH THE SYMBOL DESCRIBED
BELOW:
C3INS
PARTITION TYPE:REFER TO DETAILS ON THIS SHEET
FRAMING MEMBER SIZE NUMBER
ACOUSTIC INSUL DESIGNATION
2. REFER TO SPECIFICATIONS FOR ADDITIONAL REFERENCE STANDARDS,PRODUCT INFORMATION, AND EXECUTION REQUIREMENTS.
1. AT CONDITIONS WHERE A PARTITION EXCEEDS THE LIMITING HEIGHTLISTED FOR THAT TYPE, REDUCE STUD SPACING OR PROVIDE HEAVIERGAUGE FRAMING MEMBERS PER TABLE BELOW, OR APPLICABLE LOCALCODES, WHICHEVER IS MORE STRINGENT.
ALTERNATELY, PROVIDE DIAGONAL BRACING TO STRUCTURE AT ORBELOW THE LIMITING HEIGHT, PER PARTITION ATTACHMENT DETAILS.
2. L/240 AND L/360 VALUES ARE FOR 5 PSF LATERAL LOAD. VERIFY AND
COMPLY WITH LOCAL CODE REQUIREMENTS.
3. TYPICAL ALLOWABLE DEFLECTION DESIGN CRITERIA RATIO IS L/240.USE L/360 WHERE BRITTLE FINISHES WILL BE APPLIED SUCH ASPLASTER OR TILE.
4. TABLE VALUES ARE FROM SSMA (STEEL STUD MANUFACTURERSASSOCIATION) TECHNICAL GUIDE (EFFECTIVE 9/5/2014) COMPLYINGWITH 2009 AND 2012 IBC, AND ARE PROVIDED FOR REFERENCE ONLY.VERIFY AND COMPLY WITH LOCAL CODE REQUIREMENTS.
4. NOT ALL PARTITION TYPES INDICATED ON THIS SHEET MAY BE USEDON THIS SPECIFIC PHASE OF THE PROJECT.
1. PROVIDE COMPLETE CONSTRUCTION ASSEMBLIES COMPLYING WITHAPPLICABLE LOCAL CODES, ASTM C645, ASTM C754, AND OTHERSTANDARDS AS REFERENCED BY THE CONTRACT DOCUMENTS.
NON-COMPOSITEFULLY BRACED
≤ Lu
≤ Lu
≤ Lu
BRACING SPACING ABOVEGYP BOARD IS LESS THAN Lu
UNBRACED LENGTHLESS THAN Lu
COMPOSITE
GYP BOARD FULLHEIGHT BOTH SIDES
NON-COMPOSITEBRACED @ 48" O.C.
48" O
.C. M
AX
GYP BOARD FULLHEIGHT ONE SIDE
LIMITING HEIGHTS
212CH25-18 24 10' 7" 9' 4" 400CH25-18 24 14' 5" 12' 9" 600CH20-34 24 15' 2" 14' 8"
212CH25-18 24 11' 2" 9' 10" 400CH25-18 24 15' 7" 13' 11" 600CH20-34 24 21' 9" 20' 0"
SHAFT WALL - 1 HR
SHAFT WALL - 2 HR
5. IDENTIFY FIRE AND SMOKE PARTITIONS WITHIN ACCESSIBLECONCEALED SPACES PER APPLICABLE LOCAL CODES.
SECTION SP L/240 L/360 L/240 L/360 L/240 L/360 Lu (in)FRAMING MEMBER
162S125-18 12 11' 1" 9' 10" 7' 10" 6' 11" 7' 8" 6' 8" (1 5/8") 16 10' 1" 8' 11" 7' 1" 6' 3" 6' 11" 6' 1" 29.0 24 8' 9" 7' 9" 5' 11" 5' 5" 6' 1" 5' 4"162S125-27 12 11' 8" 10' 2" 9' 0" 7' 10" 8' 11" 7' 10" 16 10' 7" 9' 1" 8' 2" 7' 2" 8' 2" 7' 1" 29.1 24 9' 1" -- 7' 1" 6' 3" 7' 1" 6' 3"162S125-30 12 11' 10" 10' 4" 9' 3" 8'1" 9' 3" 8' 1" 16 10' 9" 9' 4" 8' 5" 7' 4" 8' 5" 7' 4" 29.2 24 9' 4" 7' 11" 7' 4" 6' 5" 7' 4" 6' 5"250S125-18 12 14' 2" 12' 9" 10' 9" 9' 6" 10' 6" 9' 2" (2 1/2") 16 12' 10" 11' 7" 9' 8" 8' 7" 9' 7" 8' 4" 29.0 24 11' 3" 10' 2" 8' 2" 7' 6" 8' 3" 7' 4"250S125-27 12 15' 4" 13' 9" 12' 5" 10' 10" 12' 4" 10' 10" 16 13' 11" 12' 5" 11' 3" 9' 11" 11' 3" 9' 10" 28.9 24 12' 2" 10' 11" 9' 10" 8' 7" 9' 10" 8' 7"
362S125-18 12 16' 8" 14' 7" 13' 1" 12' 7" 14' 0" 12' 6" (3 5/8") 16 15' 2" 13' 3" 11' 4" 11' 4" 12' 2" 11' 4" 28.8 24 13' 2" 11' 6" 9' 3" 9' 3" 9' 11" 9' 11"
250S125-30 12 15' 10" 14' 1" 12' 10" 11' 3" 12' 9" 11' 2" 16 14' 5" 12' 10" 11' 8" 10' 2" 11' 7" 10' 2" 28.9 24 12' 7" 11' 2" 10' 2" 8' 11" 10' 2" 8' 10"
362S125-27 12 18'-2" 15'-10" 16' 6" 14' 6" 16' 6" 14' 5" 16 16'-6" 14'-5" 15' 0" 13' 2" 15' 0" 13' 1" 28.6 24 14'-5" 12'-6" 12' 5" 11' 5" 13' 1" 11' 5"362S125-30 12 18' 3" 16' 4" 17' 1" 14' 11" 17' 0" 14' 10" 16 16' 7" 14' 10" 15' 6" 13' 7" 15' 6" 13' 6" 28.6 24 14' 6" 12' 11" 13' 4" 11' 10" 13' 6" 11' 10"400S125-18 12 17' 6" 15' 4" 13' 9" 13' 7" 14' 9" 13' 6" (4") 16 15' 11" 13' 11" 11' 11" 11' 11" 12' 10" 12' 3" 28.7 24 13' 8" 12' 2" 9' 9" 9' 9" 10' 5" 10' 5"400S125-27 12 19' 5" 17' 0" 17' 10" 15' 8" 17' 10" 15' 7" 16 17' 8" 15' 5" 16' 1" 14' 2" 16' 2" 14' 2" 28.5 24 15' 5" 13' 6" 13' 1" 12' 4" 14' 1" 12' 4"400S125-30 12 19' 5" 17' 0" 18' 5" 16' 2" 18' 5" 16' 1" 16 17' 8" 15' 5" 16' 9" 14' 8" 16' 8" 14' 7" 28.5 24 15' 5" 13' 6" 14' 1" 12' 10" 14' 7" 12' 9"600S125-18 12 22' 9" 19' 11" (6") 16 20' 1" 18' 1" 24 16' 4" 15' 10"600S125-27 12 26' 9" 23' 5" 24' 5" 21' 6" 24' 4" 21' 3" 16 24' 4" 21' 3" 21' 5" 19' 6" 21' 6" 19' 4" 27.7 24 21' 3" 18' 7" 17' 6" 17' 0" 17' 7 16' 10"600S125-30 12 27' 1" 23' 8" 25' 4" 22' 4" 25' 2" 22' 0" 16 24' 7" 21' 6" 23' 0" 20' 3" 22' 11" 20' 0" 27.6 24 21' 6" 18' 9" 18' 10" 17' 7" 18' 11" 17' 6"
COMPOSITE
NON-COMPOSITE
BRACED @ 48"
NON-COMPOSITE
FULLY BRACED
PARTITION LIMITING HEIGHTS TABLE
AS
FULL DEPTH ACOUSTIC BATT INSULATIONAND CONT ACOUSTICAL SEALANT BOTHSIDES AT STRUCTURE AND FLOORWHERE DESIGNATED 'INS'
TYPE FRAMING MEMBER PARTITION WIDTH STC (INSULATED)AS6
PLAN
FLOOR
CEILING
STRUCTURE
MIN. 16 GAUGE METAL STUDS AT 16" O.C. MAX. TO UNDERSIDEOF STRUCTURE WITH ONE LAYER OF 7/16" PLYWOODSHEATHING AND ONE LAYER OF 5/8" GYP BOARD EACH SIDE
RE: STRUCT (6") 7 11/16" 43 (48)
LIMITING HEIGHTS: RE: STRUCT
BTYPE FRAMING MEMBER PARTITION WIDTH STC (INSULATED)
LIMITING HEIGHTS: USE COMPOSITE VALUES
B2B3B4B6
PLAN
FLOOR
CEILING
STRUCTURE
250S125-18 (2 1/2")362S125-18 (3 5/8")400S125-18 (4")600S125-18 (6")
3 3/4"4 7/8"5 1/4"7 1/4"
38 (45)43 (48)43 (48)43 (48)
MIN. 18 MIL (25 GAUGE) METAL STUDS AT 16" O.C. MAX.TO 6" ABOVE CEILING WITHONE LAYER OF 5/8" GYPSUM BOARD EACH SIDE
MIN 18 MIL (25 GAUGE) RIGID BRACE ATMAX 8'-0" O.C. AT ALTERNATE SIDES.A PERPENDICULAR INTERSECTING WALLMAY SUBSTITUTE FOR A RIGID BRACE.
JTYPE FRAMING MEMBER PARTITION WIDTH STC (INSULATED)J
PLAN
FLOOR
CEILING
STRUCTURE
087F125-18 (7/8") 1 1/2" N/A
7/8" MTL FURRING CHANNELS AT 24" O.C. TO 6" ABOVE CEILINGANCHORED TO SUBSTRATE WITHONE LAYER OF 5/8" GYPSUM BOARD ON FINISHED SIDEN
TYPE FRAMING MEMBER PARTITION WIDTH STC (INSULATED)N2N3N4N6
PLAN
FLOOR
CEILING
STRUCTURE
250S125-18 (2 1/2")362S125-18 (3 5/8")400S125-18 (4")600S125-27 (6")
3 1/8"4 1/4"4 5/8"6 5/8"
N/A
MIN. 18 MIL (25 GAUGE) METAL STUDS AT 16" O.C. MAX.TO UNDERSIDE OF STRUCTURE WITHONE LAYER OF 5/8" GYPSUM BOARD FINISHED SIDE
BRIDGING AT 48" O.C. MAX
LIMITING HEIGHTS: USE NON-COMPOSITE BRACED AT 48" VALUES
A
FULL DEPTH ACOUSTIC BATT INSULATIONAND CONT ACOUSTICAL SEALANT BOTHSIDES AT STRUCTURE AND FLOORWHERE DESIGNATED 'INS'
TYPE FRAMING MEMBER PARTITION WIDTH STC (INSULATED)A2A3A4A6
PLAN
FLOOR
CEILING
STRUCTURE
MIN. 25 GAUGE METAL STUDS AT 16" O.C. MAX.TO UNDERSIDE OF STRUCTURE WITHONE LAYER OF 5/8" GYP BOARD EACH SIDE
250S125-18 (2 1/2")362S125-18 (3 5/8")400S125-18 (4")600S125-18 (6")
3 3/4"4 7/8"5 1/4"7 1/4"
38 (45)43 (48)43 (48)43 (48)
LIMITING HEIGHTS: USE COMPOSITE VALUES
1 01/18/2021 ADDENDUM 01
1
01/18/2021
2777 Allen Parkway, Suite 460Houston, TX 77019713.487.3400www.energyarch.com
MEZZANINE FLOOR PLAN
A-102
RELL
IS A
dmin
istra
tion
Com
plex
Ext
ensio
nRE
LLIS
Cam
pus
1555
Ave
DBr
yan,
TX 7
7807
EA PROJECT NUMBER: 19114
REV DATE DESCRIPTION
NOT FORREGULATORYAPPROVAL,
PERMITTING ORCONSTRUCTION
0 01/04/2021 ISSUED FOR CONSTRUCTION
ARCHITECT : BRIAN TODD ARENZLICENSE #: 18478
C2/A
-302
C2/A
-302
A2/A
-553
A3
INS
A3 INS
A6 INS
37'-1
"
3'-0"
4'-7"
6 5/8"
12'-1
"2'-
9 3/4"
2'-9 1
/8"
5
5
3
9
PLUMBING / HVACCHASE
N3 INS
(NO CEILING)
OPEN TO BELOW
BALCONY
200
G
G
F
F
E
E
D
D
C
C
B
B
A
A
J
J
1 1
2 2
3 3
4 4
H
H
A.1
A.1
1.1
3.2
1.1
3.1
A1/A-301A1/A-301
A2/A
-302
A2/A
-302
A2/A
-302
A2/A
-302
A2/A
-303
A2/A
-303
C4/A
-302
C4/A
-302
A1/A
-303
A1/A
-303
C1/A-301C1/A-301
A1/A-201
B1/A
-201
A1/A-202
B2/A
-202
AS6 INS
A6 INS
AS6 INS
9'-0"
7'-8 1
/2"11
'-4 1/
2"9'-
0"
6 5/8" 5'-4 3/8" 8'-1 1/2"
37'-1
"
12
16
16
MECH MEZZANINE200
A
1
2
3
4
5
6
7
8
91011
12
13
14
15
16
17
18
RECESSED FLOOR SLAB, RE: STRUCTURAL
CONCRETE VAULT, RE: MEP
MECH ACCESS LADDER
SCHEDULED WOOD STAIR WITH SSTL GUARD RAIL
PLUMBING/ HVAC CHASE
FLOOR DIFFUSER, RE: MECHANICAL
MOP SINK, RE: PLUMBING
IT RACK, RE: TELECOM
PROJECTION WALL, LEVEL 5 FINISH
DOUBLE COMPARTMENT SINK, RE: PLUMBING
A. ALL DIMENSIONS ARE TAKEN FROM OUTSIDE FACE TO OUTSIDE FACE OF GYPSUM BOARD. UNLESS NOTED OTHERWISE.
B. ALL PARTITIONS ARE FULL HEIGHT WITH SOUND ATTENUATION UNLESS NOTED OTHERWISE.
C. REFER TO MEP FOR A/C UNITS EQUIPMENT LOCATIONS
D. REFER TO CEILING PLAN FOR MOTORIZED WINDOW SHADES ATNAVE WINDOWS
E. REFER TO A-603 FOR RESTROOM ACCESSORIES
FEC FIRE EXTINGUISHER CABINET
DESIGNATES INTERIOR & EXTERIOR WINDOW
FLOOR PLAN GENERAL NOTES
SYMBOLS LEGEND
FLOOR PLAN KEY NOTES
MECH ACCESS DOOR
FIRE EXTINGUISHER CABINET
FLOOR DRAIN, RE: PLUMBING
FLOOR SINK, RE: PLUMBING
TWO-WAY COMMUNICATION FOR AREA OF ASSISTEDRESCUE
SPEAKERBOX, RE: AV AND B2/A-553
FIRE ALARM ANNUNCIATOR PANEL
AED CABINET
MILLWORK HATCH. REFER TO MILLWORK DRAWINGS
RECESSED SLAB, REFER TO STRUCTURAL DRAWINGS
1 01/18/2021 ADDENDUM 01
N
1
0 2' 4' 8'SCALE: 1/4" = 1'-0"A1 MEZZANINE
01/18/2021
NOTE: REFER TO 1ST FLOOR PLAN FOR KEYNOTES NOT ON THIS PLAN