Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
Public Works Branch
Contract Administration 1635 Faraday Avenue Carlsbad, CA 92008 760-602-4677 t
August 18, 2020
ADDENDUM NO. 1
RE: New Village Arts Roof and Siding Refurbishment; PWS21-1170FAC
Please include the attached addendum in the Notice to Bidder/Request for Bids you have for the above project.
This addendum must be acknowledged via PlanetBids or submitted with your cost proposal.
JANEAN HAWNEY
Contract Administrator
I ACKNOWLEDGE RECEIPT OF ADDENDUM NO. 1
__________________________________________________________ Bidder’s Signature
1 Addendum No. 1
CITY OF CARLSBAD
BID NO. PWS21-1170FAC NEW VILLAGE ARTS ROOF AND SIDING REFURBISHMENT
ADDENDUM NO. 1
From: Janean Hawney, Contract Administrator [email protected] Works Branch1635 Faraday AveCarlsbad, CA 92008
No. of Pages: 13 (including this page)
Date: August 18, 2020
Bid Opening Date: August 31, 2020 at 5 p.m. (no change)
Notice: This Addendum forms a part of the Contract Documents for the above identified project and modifies portions of the original Contract Documents. Documents not specifically mentioned in this Addendum remain in full force.
Consultant must acknowledge receipt of this Addendum via PlanetBids or with documents submitted at the due date and time specified in the bid documents. Failure to do so may subject Consultant to disqualification.
Questions and answers:
Q1. Does bidder require a prequalification before bidding?
A1. No, prequalification is not required for this project.
*Replace page 2 – Table of Contents
*Additional documents added:
Appendix A - Existing Roofing System Details
Appendix B – Electrical Drawing
APPENDIX A
The existing roofing system being removed is comprised of three roofing systems.
Top layer: Asphalt Fiberglass Shingles over underlayment.
Middle layer: Built up roof with cap sheet
Lower Layer: Built up roof with gravel surfacing over wood plank decking
Pictures of the existing roofing systems are shown below:
PWS21-1170FAC Addendum No. 1
PWS21-1170FAC Addendum No. 1
PWS21-1170FAC Addendum No. 1
PWS21-1170FAC Addendum No. 1
PWS21-1170FAC Addendum No. 1
PWS21-1170FAC Addendum No. 1
PWS21-1170FAC Addendum No. 1
APPENDIX B
Contractor shall be responsible for all coordination and permitting with SDG&E, as required, to remove
and replace the existing electric and gas services affixed to the wall of the structure.
Attached as reference is a current SDG&E Prearranged Customer Requested Outage form together with
reference plans intended to generally depict the scope of work associated with removing and replacing
the electrical services on the building.
PWS21-1170FAC Addendum No. 1
PM Forms: PrearrangedCustomerRequestedOutage-NonResidential.dot Revision Date: 9/15/2014
Scope of Work for Non-Residential Prearranged Customer Requested Outage
Customer Name: Date: Address: Telephone: SDG&E Project #: _________________ Outage Requested By (Name of Company): Company Representative: Title: E-Mail: Telephone: Fax: Contact person at job site: Cell Phone: Payment by: Telephone: Company Name
Mailing Address: City: Zip Code: E-mail Address:
Date Requested for De-energize:
Re-energize Date: Alternate Date:
Time Requested for De-energize:
Re-energize Time:
Detailed Scope of Work to be Performed: Additional Questions: 1. Is a permit from the authority having jurisdiction required for the work you are performing? Yes No
If yes, what is your permit number? 2. Are you replacing the existing terminating enclosure (underground pull section)? Yes No
If yes, indicate the size of the new pull section ( amperes), and provide description of work: If adding load, provide new load calculations: If replacing the existing terminating enclosure, electrical contractor to field verify and confirm the following: Height of landing positions on all phases and neutral in NEW pull section are at, or lower than, the existing landing positions. Yes No If no, new utility service lateral conductors will be required and may be at customer’s expense. SDG&E Planner to verify cost responsibilities prior to scheduling the outage.
3. Are you adding new, replacing, or disconnecting/reconnecting any service entrance conductors?
Yes No If yes, explain which conductors are involved and provide description of work: 4. Are you tapping the existing bus in the terminating enclosure? Yes No
If yes, have you submitted your Tap Drawings and received approval from SDG&E? Yes No Comments:
5. Are you adding any new service entrance conductors? Yes No
If yes, please describe where they originate and where they terminate: 6. Are you adding any new service and metering equipment? Yes No
If yes, indicate the number and size of each service you are adding, along with the number and size of each metering section. How will they be addressed?
7. Are you removing any service and metering equipment? Yes No
If yes, indicate SDG&E’s electric meter number(s) to be removed and the size of the metering section:
PWS21-1170FAC Addendum No. 1
E0.01
COVER SHEET
Team
Project No.
Drawing No.
Construction Documents 2020.05.28
City
of C
arls
bad
- New
Villa
ge A
rts T
heat
er P
artia
l Rer
oofin
g27
87 S
tate
St,
Car
lsba
d, C
A 92
008
Site
Pla
n
1910
350 Pauma PlaceEscondido, CA 92029TEL: 760.658.6098
Electrical Engineers, Inc.1. CONTRACTOR TO OBTAIN PERMISSION FOR ACCESS TO THE SITE FROM THE
OWNER OR DESIGNATED OWNER REPRESENTATIVE TO VISIT THE SITE INCLUDINGALL AREAS OF WORK PRIOR TO BID. CONTRACTOR TO BE FAMILIARIZED WITHEXISTING CONDITIONS, VERIFY SAID CONDITIONS, DIMENSIONS, AND ROUTINGSPRIOR TO START OF CONSTRUCTION. REPORT ANY DISCREPANCIES TO OWNER /ARCHITECT / ENGINEER WITHIN 48 HOURS OF DISCREPANCIES FOUND.
2. CONTRACTOR SHALL CONFIRM ACCURACY OF PANEL BOARD INFORMATIONPRIOR TO START OF WORK. REPORT ANY DISCREPANCIES TO OWNER /ARCHITECT / ENGINEER WITHIN 48 HOURS OF DISCREPANCIES FOUND.
3. ALL WORK SHOWN IS NEW UNLESS OTHERWISE NOTED.
4. ALL AREAS OUTSIDE THE SCOPE OF WORK SHALL BE PROTECTED IN PLACE ANDREMAIN INTACT, U.O.N.
5. CONTRACTOR TO COORDINATE WITH OWNER ANY SHUTDOWN OF ELECTRICALEQUIPMENT WITH 7 DAYS NOTIFICATION. CONTRACTOR TO INCLUDE OFF HOURSIN PRICING FOR THIS WORK.
6. ALL ELECTRICAL MATERIAL AND EQUIPMENT SHALL BE NEW BEARING A ULLISTING OR ACCEPTABLE NRTL LISTING FROM THE LOCAL AREA JURISDICTION.
7. CONTRACTOR SHALL COMPLY WITH THE CURRENT VERSION OF THE CALIFORNIAELECTRICAL CODE 2019, STATE, LOCAL CODES, ORDINANCES, AND REGULATIONS.
8. WORK SHALL BE PERFORMED IN A SAFE MANNER AND NOT DISTURB OR AFFECTEXISTING BUILDING UTILITIES, OCCUPANTS, OR FINISHES WITHOUT PRIOR NOTICEAND APPROVAL FROM OWNER.
9. ALL CONDUIT RUN SHALL BE FIELD COORDINATED, LOCATE CONDUITS CLEAR OFOTHER TRADES, DOOR ACCESS, OR OTHER OBSTRUCTIONS. COORDINATECONDUIT RUNS WITH OTHER TRADES PRIOR TO COMMENCEMENT OF WORK.
10. RUN ALL CONDUITS CONCEALED IN CEILING SPACES, U.O.N. TO BE SURFACEMOUNTED. ALL CONDUIT PATHWAYS MUST MAINTAIN 6 INCHES CLEAR OFSOURCES OF HEAT, SUPPORT CONDUITS FROM STRUCTURE.
11. ALL BRANCH CIRCUITS TO BE PROVIDED WITH SEPARATE GREEN GROUNDINSULATED CONDUCTOR.
12. ALL BRANCH CIRCUITS TO BE PROVIDED WITH SEPARATE WHITE NEUTRALINSULATED CONDUCTOR. SHARED NEUTRAL IS ACCEPTABLE IF COMMON HANDLETIE CIRCUIT BREAKER ARE UTILIZED TO SIMULTANEOUSLY DISCONNECT ALLUNGROUNDED CONDUCTORS PER NEC 210.4(B).
13. PROVIDE IDENTIFICATION TAGS FOR ALL WIRING, INSTALL TAGS AT END OF RUNS,INTERMEDIATE PULL BOXES, JUNCTION BOXES, CABINETS, ETC.
14. BRANCH CIRCUIT VOLTAGE DROP NOT TO EXCEED 3% FROM PANEL BOARDSOURCE.
15. LABEL ALL CIRCUIT BREAKERS IN ALL ELECTRICAL DISTRIBUTION PANELS ANDSWITCHBOARDS. PROVIDE TYPE WRITTEN CIRCUIT DIRECTORY CARDS FOR ANYPANEL BOARD HAVING CIRCUIT MODIFICATIONS.
16. PROVIDE P-TOUCH LABELS ON ALL NEW OUTLETS, RACKS, PLUG MOLD, ANDSWITCHES.
17. ALL CONDUITS PENETRATING ELECTRICAL/MECHANICAL SPACES OF RATEDWALLS SHALL BE SEALED AND FIRE STOPPED.
18. ALL ELECTRICAL PENETRATIONS INTO COOLER OR FREEZER UNITS SHALL BESEALED PER SECTION 300-7 OF THE NEC.
19. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALLBE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE THEELECTRICAL EQUIPMENT PER NEC 110.26(E) (1).
20. THE ENGINEER OF RECORD TAKES NO EXCEPTION TO THE USE OF MC CABLEWHERE ALLOWED BY THE CEC 330 AND PROVIDE MC CABLE IS ACCEPTABLE WITHBUILDING OWNERSHIP
GENERAL PROJECT NOTES
ABBREVIATIONS AND DESCRIPTIONSA / AMP AMPERE
ABV ABOVE
ADA AMERICAN WITH DISABILITIES ACT
AF AMPERE FRAME, AMPERE FUSE
AFF / A.F.F. ABOVE FINISH FLOOR
AFG, A.F.G. ABOVE FINISH GRADE
AWG AMERICAN WIRE GAUGE
AIC / A.I.C. AMPERE INTERRUPTING CAPACITY
AS AMPERE SWITCH
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AVG AVERAGE
BKR BREAKER
BLDG BUILDING
BR BRANCH
C CONDUIT
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CBC CALIFORNIA BUILDING CODE
CEC CALIFORNIA ELECTRIC CODE
CFC CALIFORNIA FIRE CODE
CIRC / CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CO / C.O. CONDUIT ONLY
COMM COMMUNICATIONS
CSFM CALIFORNIA STATE FIRE MARSHALL
CT CONTROL TRANSFORMER
CONN CONNECTED
CPT CONTROL POWER TRANSFORMER
CTR CENTER
DET DETAIL
DIST DISTRIBUTION
DP DISTRIBUTION PANEL
(D) DEMOLISH
DISC DISCONNECT
DWG DRAWING
DIA DIAMETER
DIM DIMENSION
EMT ELECTRICAL METALLIC TUBING
EP EXPLOSION PROOF
EM EMERGENCY
EQP EQUIPMENT
(E) EXISTING
ELEC ELECTRICAL
EMS EMERGENCY MANAGEMENT CONTROL SYSTEM
ENT ELECTRICAL NON-METALLIC TUBING
EPO / E.P.O EMERGENCY POWER OFF
EF EXHAUST FAN
EG EQUIPMENT GROUND
EOL END OF LINE RESISTOR
FACP FIRE ALARM CONTROL PANEL
FLR FLOOR
FATC FIRE ALARM TERMINAL CABINET
FA FIRE ALARM
FLA FULL LOAD AMPS
FT / ' FEET
FIN FINISH
G / GND GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GEC GROUNDING ELECTRODE CONDUCTOR
H / HGT HEIGHT
HOA HAND OFF AUTO
HP HORSEPOWER
HACR HEATING AIR CONDITIONING REFRIGERATION
HVAC HEATING, VENTILATING AND AIR CONDITIONING
HID HIGH INTENSITY DISCHARGE
IC INTERCOM
IDF INTERMEDIATE DISTRIBUTION FRAME
IN / " INCHES
IMC INTERMEDIATE METAL CONDUIT
IP INTERNET PROTOCOL
IG ISOLATED GROUND
JB / JBOX JUNCTION BOX
KAIC KILOAMPERE INTERRUPTING CAPACITY
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATT
KWH KILOWATT HOUR
LTG / LTS LIGHTING
LV LOW VOLTAGE
LF LINEAR FEET
KCMIL / MCM THOUSAND CIRCULAR MILS
MAX MAXIMUM
MDF MAIN DISTRIBUTION FRAME
MECH MECHANICAL
MH MANHOLE
MTD MOUNTED
MTG MOUNTING
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT CIRCUIT PROTECTION
MCA MINIMUM CIRCUIT AMPERES
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
M METER
MV MERCURY VAPOR
MCC MOTOR CONTROL CENTER
MFR MANUFACTURER
NC NORMALLY CLOSED
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO. / # NUMBER
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MFR ASSOCIATION
NF NON-FUSED
NL NIGHT LIGHT
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISH, CONTRACTOR INSTALLED
P POLE
PB PULL BOX
PF POWER FACTOR
PA PUBLIC ADDRESS
PH / ø PHASE
PNL PANEL
PRIMARY OVER 600 VOLTS
PC PHOTOCELL
PDU POWER DISTRIBUTION UNIT
PROVIDE FURNISH, INSTALL AND/OR CONNECT
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
REQD REQUIRED
REQT(S) REQUIREMENT(S)
RM ROOM
RMS ROOT MEAN SQUARE
RGS RIGID GALVANIZED STEEL CONDUIT
RECEPT RECEPTACLE
SHT SHEET
SW SWITCH
SWBD SWITCHBOARD
STC SIGNAL TERMINAL CABINET
SCC SHORT CIRCUIT CURRENT
SFD SMOKE FIRE DAMPER
SECONDARY 600 VOLTS AND LESS
SQ SQUARE
TEL TELEPHONE
TYP TYPICAL
TC TIMECLOCK
TEL/DAT TELEPHONE AND DATA
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
UL UNDERWRITERS LABORATORIES
UON / U.O.N. UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTAGE
VA VOLT AMPERES
VD VOLTAGE DROP
VAV VARIABLE AIR VOLUME
W WATTAGE OR WIRE
WP WEATHERPROOF
WAP WIRELESS ACCESS POINT
XFMR TRANSFORMER
X / (X) EXISTING
XL / (XL) EXISTING TO BE RELOCATED
XR / (XR) EXISTING TO BE REMOVED
XN / (XN) EXISTING NEW LOCATION
%Z PERCENTAGE IMPEDANCE
WT WEIGHT
WH WATER HEATER
VFD VARIABLE FREQUENCY DRIVE
UGPS UNDERGROUND PULL SECTION
TEMP TEMPERATURE OR TEMPORARY
SWGR METAL CLAD SWITCHGEAR
SPEC SPECIFICATIONS
REC RECESSED
REFRIG REFRIGERATOR
QTY QUANTITY
PWR POWER
N / NEUT NEUTRAL
LBS POUNDS
KS KNEE SPACE
HR HOUR OR HOME RUN
HZ HERTZ
GC GENERAL CONTRACTOR
GALV GALVANIZED
CU COPPER
CCTV CLOSED CIRCUIT TELEVISION
AL ALUMINUM
AC ALTERNATING CURRENT
A/C AIR CONDITIONING
DC DIRECT CURRENT
EA EACH
EXO DISCONNECT SWITCH
EC ELECTRICAL CONTRACTOR
ED EXTRA-DUTY
WR WEATHER RESISTANT
CONTROL LEGEND
SURFACE MOUNTED SPST SWITCH MOUNTED AT +48" AFF TO TOP OFBOX U.O.N
FLUSH MOUNTED SINGLE POLE STANDARD TOGGLE SWITCHMOUNTED AT +48" AFF TO TOP OF BOX U.O.N. LETTERING INDICATESQUANTITY OF SWITCHES AND DEVICES TO BE CONTROLLED.
XXD = DIMMING SWITCHK = KEYED SWITCHP = PILOT LIGHT SWITCHR = MOMENTARY CONTACT SWITCHT = TIMER SWITCH3 = THREE WAY SWITCH
FLUSH INFRARED WALL OCCUPANCY SENSOR SINGLE BUTTONMOUNTED AT +48" AFF TO TOP OF BOX U.O.N
OC
FLUSH INFRARED WALL OCCUPANCY SENSOR DUAL BUTTONMOUNTED AT +48" AFF TO TOP OF BOX U.O.NOC
ab
SURFACE INFRARED WALL OCCUPANCY SENSOR SINGLE BUTTONMOUNTED AT +48" AFF TO TOP OF BOX U.O.N
SURFACE INFRARED WALL OCCUPANCY SENSOR DUAL BUTTONMOUNTED AT +48" AFF TO TOP OF BOX U.O.N
ab
OC
OC
XXU = ULTRA SONIC OCCUPANCY SENSORDT = DUAL TECHNOLOGY OCCUPANCY SENSOROC
CEILING MOUNTED INFRARED OCCUPANCY SENSOROC
FLUSH MOUNTED OVERRIDE SWITCH STATION MOUNTED AT +48" AFFTO TOP OF BOX U.O.N. BUTTON CONFIGURATION AS NOTED PERFLOOR PLAN
SURFACE MOUNTED OVERRIDE SWITCH STATION MOUNTED AT +48"AFF TO TOP OF BOX U.O.N. BUTTON CONFIGURATION AS NOTED PERFLOOR PLAN
PHOTOCELL MOUNTED AND ORIENTATED AS NOTED ON FLOOR PLAN
O
O
PC
DL CEILING MOUNTED DAY LIGHT SENSOR
SINGLE LINE LEGEND
ELECTRONIC METERING UNIT
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
DRAWOUT CIRCUIT BREAKERAMP FRAMEAMP TRIPPOLE CONFIGURATIONELECTRONIC TRIP FUNCTIONS
FUSE
TRANSFORMER
100AF100AT3LSIG
FUSED SWITCHAMP SWITCHAMP FUSEPOLE CONFIGURATION
100AS100AF3
CIRCUIT BREAKERAMP FRAMEAMP TRIPPOLE CONFIGURATIONELECTRONIC TRIP FUNCTIONS
100AF100AT3LSIG
GROUNDING ELECTRODE
ENCLOSED CIRCUIT BREAKERAMP FRAMEAMP TRIPPOLE CONFIGURATIONELECTRONIC TRIP FUNCTIONS
100AF100AT3LSIG
C
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
COIL
SHUNT TRIPST
SOLID STATESS
FEEDER TAGXXXX
AUTOMATIC TRANSFER SWITCH
PACKAGE ENGINE GENERATOR
PANEL BOARDPANEL
HL1
TRANSIENT VOLTAGE SURGE SUPPRESSIONTVSS
M
+-+- STRINGER INVERTER
+
- PHOTOVOLTAIC PANEL (PV PANEL)
FLUSH MOUNTED HALF HOT DUPLEX RECEPTACLE MOUNTED AT +15"AFF TO BOTTOM OF BOX U.O.N
XX
HALF SHADED WIRING INDICATES CONTROLLEDRECEPTACLE PER TITLE 24 SECTION 130.5(d)
POWER LEGEND
FLUSH MOUNTED DUPLEX RECEPTACLE MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N
FLUSH MOUNTED QUAD RECEPTACLE MOUNTING HEIGHT TOBOTTOM OF BOX PER ARCHITECT ELEVATION
SURFACED MOUNTED DUPLEX RECEPTACLE MOUNTED AT +15" AFFTO BOTTOM OF BOX U.O.N
SURFACE MOUNTED QUAD RECEPTACLE MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N
FLUSH MOUNTED SINGLE RECEPTACLE MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N
SURFACE MOUNTED SINGLE RECEPTACLE MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N
CEILING MOUNTED DUPLEX RECEPTACLE
CEILING MOUNTED QUAD RECEPTACLE
FLUSH FLOOR BOX WITH DUPLEX RECEPTACLE
FLUSH FLOOR BOX WITH QUAD RECEPTACLE
FLUSH FLOOR BOX WITH COMBINATION DUPLEX RECEPTACLE ANDDATA OUTLET
FLUSH FLOOR BOX WITH COMBINATION QUAD RECEPTACLE ANDDATA OUTLET
FIRE RATED POKE THRU WITH DUPLEX RECEPTACLE
FIRE RATED POKE THRU WITH QUAD RECEPTACLE
FIRE RATED POKE THRU WITH DUPLEX RECEPTACLE AND DATAOUTLET
FIRE RATED POKE THRU WITH QUAD RECEPTACLE AND DATAOUTLET
XX
FLUSH MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLEMOUNTED AT +15" AFF TO BOTTOM OF BOX U.O.N
SURFACE MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLEMOUNTED AT +15" AFF TO BOTTOM OF BOX U.O.N
XX-XXX
XX-XXX
FLUSH MOUNTED JUNCTION BOX MOUNTED AT +15" AFF TO BOTTOMOF BOX U.O.NSURFACE MOUNTED JUNCTION BOX MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N
FLUSH FLOOR MOUNTED JUNCTION BOX
CEILING MOUNTED JUNCTION BOXJ
J
J
J
GFCIIGSHAC
GROUND FAULT CIRCUIT INTERRUPTERISOLATED GROUNDSURGE SUPPRESSORHORIZONTAL MOUNTEDMOUNT ABOVE COUNTER PERARCHITECT ELEVATIONPROVIDED WITH INTREGRAL USBPORTSRECEPTACLE CONTROLLED PER TITLE24 2013 SECTION 130.5(d)CLOCK TYPE
====
CEILING MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLEXX-XXX
FLOOR MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLEXX-XXX
=
=RC
=C
FLUSH MOUNTED DUPLEX RECEPTACLE MOUNTING HEIGHT TOBOTTOM OF BOX PER ARCHITECT ELEVATION
SURFACED MOUNTED DUPLEX RECEPTACLE MOUNTED AT COUNTERLEVEL PER ARCHITECT ELEVATION
SURFACE MOUNTED QUAD RECEPTACLE MOUNTING TO BOTTOM OFBOX PER ARCHITECT ELEVATION
FLUSH MOUNTED QUAD RECEPTACLE MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N
=USB
RECEPTACLE POWER PACK MOUNTED IN ACCESSIBLE CEILINGSPACE FOR AUTOMATIC CONTROL OF RECEPTACLE DEVICE
RC
M
EQUIPMENT LEGEND
HEAVY DUTY NON-FUSED DISCONNECT
HEAVY DUTY FUSED DISCONNECT
MOTOR STARTER, HOA, AUX CONTACTS, CPT, PILOT LIGHTS
COMBINATION MOTOR STARTER, HOA, AUX CONTACTS, CPT, PILOTLIGHTS, WITH FUSED DISCONNECT SWITCH
MECHANICAL EQUIPMENT TAG
MOTOR RATED SWITCH
SURFACE MOUNTED PANEL BOARD OR ELECTRICAL CABINET
DISTRIBUTION SWITCHBOARD OR PANEL BOARD
LIGHT FIXTURE DESIGNATIONLIGHTING BRANCH CIRCUITRELAY DESIGNATION IN LIGHTINGCONTROL PANEL
FLUSH MOUNTED PANEL BOARD OR ELECTRICAL CABINET
VARIABLE FREQUENCY DRIVE. CONFIRM INTEGRAL DISCONNECTINGMEANS WITH MECHANICAL
F1HL1-13(R1)
AHU
1
F
VFD
T TRANSFORMER
EMERGENCY POWER OFF BUTTONEPO
SFDSMOKE FIRE DAMPER
MOTOR
SIGNAL LEGEND
FLUSH MOUNTED TELEVISION OUTLET MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N
WIRELESS ACCESS POINT
FLUSH MOUNTED TELECOM OUTLET MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N. PROVIDE 1"C. TO ACCESSIBLE CEILINGSPACE WITH PULL STRING, U.O.N.
SURFACE MOUNTED TELECOM OUTLET MOUNTED AT +15" AFF TOBOTTOM OF BOX U.ON. PROVIDE 1"C. TO ACCESSIBLE CEILINGSPACE WITH PULL STRING, U.O.N.
CEILING MOUNTED TELECOM OUTLET
PUSH BUTTON
BUZZER
BELL
WALL MOUNTED SPEAKER
CEILING MOUNTED SPEAKER
TV
WAP
FLUSH FLOOR BOX WITH TELECOM OUTLET
FIRE RATED POKE THRU WITH TELECOM OUTLET
B
B
S
S
FLUSH MOUNTED WALL PHONE OUTLET MOUNTED AT +44" AFF TOTOP OF BOX U.O.NW
SECURITY LEGENDALARM CONTACT
ELECTRIC DOOR STRIKE
DOOR CONTACT
REMOTE DOOR RELEASE
ELECTRONIC LOCK
VIBRATION DETECTOR
CARD READER
KEYPAD
A
CR
KP
GLASS BREAKGB
MOTION SENSORMS
ES
DC
DR
DOOR BREACH ALARM
PANIC BUTTON / DURESS ALARM
REQUEST TO EXITREX
ELECTRONIC HOLD OPENEHO
ELECTRONIC PANIC HARDWAREEPH
ELECTRONIC MAGNETIC LOCKEML
FIXED POSITION VIDEO CAMERA
EL
VD
DA
PB
PAN, TILT, ZOOM VIDEO CAMERAPTZ
PHOTOVOLTAIC LEGENDDC TO AC STRING INVERTER
POTENTIAL INDUCED DEGRATION (PID) ENERGY BALANCER CABINET
PHOTOVOLTAIC MODULE PANEL (PV PANEL)
PID
PHOTOVOLTAIC ARRAY (PV ARRAY)
STRING NUMBER DESIGNATION
INVERTER NUMBER DESIGNATIONS#.#
WIRING LEGEND
RACEWAY EXPOSED
RACEWAY TURNED UP
RACEWAY TURNED DOWN
RACEWAY CAPPED AND STUBBED.PROVIDE PERMANENT GROUNDMARKER FOR UNDERGROUND INSTALLATIONS
BRANCH CIRCUIT RACEWAY CONCEALED IN WALL OR CEILING
BRANCH CIRCUIT RACEWAY CONCEALED IN FLOOR ORUNDERGROUND
BRANCH CIRCUIT RACEWAY HOME RUN BACK TO ELECTRICALEQUIPMENT AS NOTED
L1-1
BRANCH CIRCUIT RACEWAY WITH 3#12, 1#12N, 1#12GND, 3/4"C.MAXIMUM THREE BRANCH CIRCUITS PER HOME RUN, U.O.N.
BRANCH CIRCUIT RACEWAY WITH 3#10, 1#10N, 1#10GND, 3/4"C.MAXIMUM THREE BRANCH CIRCUITS PER HOME RUN, U.O.N.
#10
CABLE TRAY
POINT OF CONNECTION TO EQUIPMENT
BRANCH CIRCUIT RACEWAY TO BE DEMOLISH
SURFACE MOUNTED WIRE MOLD RACEWAY SYSTEM.X = 1, 2 OR 3 CHANNEL RACEWAYWMX
SHEET INDEXSHEET NUMBER SHEET TITLEE0.01 COVER SHEET
E0.06 SITE PLAN
E8.01 SINGLE LINE DIAGRAM
PWS21-1170FAC Addendum No. 1
Existing Building
TYP02.203
TYP02.203
02.204
02.204
TYP02.205
TYP02.205
TYP02.205
02.20602.206
02.20602.20601.001
Scope of Work
Scop
e of
Wor
k
Stat
e St
reet
Christiansen Way
MSA
KEYNOTES1 CONTRACTOR TO REMOVE EXISTING SDG&E PULL BOX OFF EXTERIOR WALL. CONTRACTOR
TO PROTECT TENANT FEEDER CABLES DURING EXTERIOR WALL IMPROVEMENT PHASE.COORDINATE SDG&E OUTAGE PRIOR TO COMMENCEMENT OF WORK.
AT COMPLETION OF EXTERIOR WALL WORK. REINSTALL NEW PULL BOX OF SAME SIZE ANDTYPE.
CONTRACTOR TO REMOVE EXISTING SDG&E 3-PACK METER SOCKET ASSEMBLIES OFFEXTERIOR WALL. CONTRACTOR TO PROTECT TENANT FEEDER CABLES DURING EXTERIORWALL IMPROVEMENT PHASE. COORDINATE SDG&E OUTAGE PRIOR TO COMMENCEMENT OFWORK.
AT COMPLETION OF EXTERIOR WALL WORK. REINSTALL EXISTING SDG&E 3-PACK METERSOCKET ASSEMBLIES. RECONNECTION EXISTING FEEDER TO TENANT PANELS.
GENERAL NOTES1. ALL ELECTRICAL DEVICES ARE EXISTING TO BE RELOCATED, U.O.N.
2. CONTRACTOR TO FIELD VERIFY BRANCH CIRCUITRY PRIOR TO COMMENCEMENT OFWORK.
3. CONTRACTOR TO MAINTAIN CIRCUITRY CONTINUITY TO EXISTING SPACE OUTSIDE THISSCOPE OF WORK.
4. SEE ARCHITECTURAL SHEETS FOR ADDITIONAL DEMOLITION REQUIREMENTS.
5. ELECTRICAL CONTRACTOR TO MAKE EXISTING ELECTRICAL SYSTEM SAFE FOR DEMOCONTRACTOR. ELECTRICAL CONTRACTOR TO IDENTIFY CONDUIT SYSTEMS THAT ARETO REMAIN AND CAREFULLY WALK WITH DEMO CONTRACTOR EXPLAINING WHAT NEEDSTO STAY. IT IS THE DEMO CONTRACTOR AND GENERAL CONTRACTORS RESPONSIBILITYTO SET THIS MEETING UP AND MAKE SURE THAT THE COMMUNICATION ON WHAT STAYSIS CRYSTAL CLEAR. ITEMS THAT STAY (FEEDERS TO PANELS ETC) SHOULD BE CLEARLYMARKED ON SITE WITH RED PAINT. ANYTHING MARKED RED SHALL NOT BE DEMOED ORREMOVED.
6. SEE SINGLE LINE DIAGRAM ON SHEET E8.01 FOR ADDITIONAL REQUIREMENTS.
2
3
12
4
34
Team
Project No.
Drawing No.
Construction Documents 2020.05.28
City
of C
arls
bad
- New
Villa
ge A
rts T
heat
er P
artia
l Rer
oofin
g27
87 S
tate
St,
Car
lsba
d, C
A 92
008
Site
Pla
n
1910
350 Pauma PlaceEscondido, CA 92029TEL: 760.658.6098
Electrical Engineers, Inc.
SCALE:1 SITE PLAN1/8" = 1'-0" E0.06
SITE PLAN
PWS21-1170FAC Addendum No. 1
KEYNOTESEXISTING SDG&E PULL BOX TO BE REMOVED PRIOR TO COMMENCEMENT OF EXTERIORWALL WORK. SDG&E CONDUCTORS TO BE PROTECTED IN PLACE.
REPLACE EXISTING SDG&E PULL BOX WITH NEW. NEW PULL BOX TO MATCH EXISTINGTYPE AND SIZE. REINSTALL NEW PULL BOX IN EXISTING LOCATION AT COMPLETION OFEXTERIOR WALL PHASE.
EXISTING SDG&E METER.
EXISTING GROUNDING ELECTRODE SYSTEM TO REMAIN.
EXISTING SDG&E PULL CAN AND METER ASSEMBLIES TO BE REMOVED PRIOR TOCOMMENCEMENT OF EXTERIOR WALL WORK. SDG&E CONDUCTORS TO BE PROTECTEDIN PLACE.
REINSTALL EXISTING SDG&E PULL CAN AND METER ASSEMBLIES IN EXISTINGLOCATION AT COMPLETION OF EXTERIOR WALL PHASE.
GENERAL NOTES1. ALL ELECTRICAL DEVICE SHOWN ARE EXISTING TO REMAIN U.O.N.
2. ALL ELECTRICAL FEEDER CONDUIT AND CONDUCTORS ARE EXISTING TO REMAIN U.O.N.
3. ELECTRICAL PANELS ARE EXISTING TO REMAIN WITH EXISTING LOADS.
1
2
3EXISTING
SDG&EPADMOUNT
TRANSFORMER
SDG&E EXISTING12KV CIRCUIT EXISTING SDG&E CONDUIT AND
CONDUCTORS
EXISTING SDG&E PULL CAN - 400A, 208Y/120V, 3Ø, 4W
M
400A
G N
AFAT
P
2002003
EXISTINGFEEDER
M
AFAT
P
2002003
EXISTINGFEEDER
M
AFAT
P
2001503
EXISTINGFEEDER
EXISTINGGROUNDINGELECTRODE
3 3 3
4
EXISTINGFEEDER
EXISTINGPANEL
A
EXISTINGFEEDER
EXISTINGPANEL
B
12
EXISTINGFEEDER
EXISTINGPANEL
C
4
5
6
56
Team
Project No.
Drawing No.
Construction Documents 2020.05.28
City
of C
arls
bad
- New
Villa
ge A
rts T
heat
er P
artia
l Rer
oofin
g27
87 S
tate
St,
Car
lsba
d, C
A 92
008
Site
Pla
n
1910
350 Pauma PlaceEscondido, CA 92029TEL: 760.658.6098
Electrical Engineers, Inc.
SCALE:1 SINGLE LINE DIAGRAMNONE E8.01
SINGLE LINE DIAGRAM
PWS21-1170FAC Addendum No. 1