Public Works Branch Contract Administration 1635 Faraday Avenue Carlsbad, CA 92008 760-602-4677 t August 18, 2020 ADDENDUM NO. 1 RE: New Village Arts Roof and Siding Refurbishment; PWS21-1170FAC Please include the attached addendum in the Notice to Bidder/Request for Bids you have for the above project. This addendum must be acknowledged via PlanetBids or submitted with your cost proposal. JANEAN HAWNEY Contract Administrator I ACKNOWLEDGE RECEIPT OF ADDENDUM NO. 1 __________________________________________________________ Bidder’s Signature

ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

Public Works Branch

Contract Administration 1635 Faraday Avenue Carlsbad, CA 92008 760-602-4677 t

August 18, 2020

ADDENDUM NO. 1

RE: New Village Arts Roof and Siding Refurbishment; PWS21-1170FAC

Please include the attached addendum in the Notice to Bidder/Request for Bids you have for the above project.

This addendum must be acknowledged via PlanetBids or submitted with your cost proposal.

JANEAN HAWNEY

Contract Administrator

I ACKNOWLEDGE RECEIPT OF ADDENDUM NO. 1

__________________________________________________________ Bidder’s Signature

Page 2: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

1 Addendum No. 1

CITY OF CARLSBAD

BID NO. PWS21-1170FAC NEW VILLAGE ARTS ROOF AND SIDING REFURBISHMENT

ADDENDUM NO. 1

From: Janean Hawney, Contract Administrator [email protected] Works Branch1635 Faraday AveCarlsbad, CA 92008

No. of Pages: 13 (including this page)

Date: August 18, 2020

Bid Opening Date: August 31, 2020 at 5 p.m. (no change)

Notice: This Addendum forms a part of the Contract Documents for the above identified project and modifies portions of the original Contract Documents. Documents not specifically mentioned in this Addendum remain in full force.

Consultant must acknowledge receipt of this Addendum via PlanetBids or with documents submitted at the due date and time specified in the bid documents. Failure to do so may subject Consultant to disqualification.

Questions and answers:

Q1. Does bidder require a prequalification before bidding?

A1. No, prequalification is not required for this project.

*Replace page 2 – Table of Contents

*Additional documents added:

Appendix A - Existing Roofing System Details

Appendix B – Electrical Drawing

Page 3: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

APPENDIX A 

The existing roofing system being removed is comprised of three roofing systems. 

Top layer:          Asphalt Fiberglass Shingles over underlayment. 

Middle layer:    Built up roof with cap sheet 

Lower Layer:     Built up roof with gravel surfacing over wood plank decking  

Pictures of the existing roofing systems are shown below: 

PWS21-1170FAC Addendum No. 1

Page 4: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

PWS21-1170FAC Addendum No. 1

Page 5: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

PWS21-1170FAC Addendum No. 1

Page 6: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

PWS21-1170FAC Addendum No. 1

Page 7: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

PWS21-1170FAC Addendum No. 1

Page 8: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

PWS21-1170FAC Addendum No. 1

Page 9: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

PWS21-1170FAC Addendum No. 1

Page 10: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

APPENDIX B 

Contractor shall be responsible for all coordination and permitting with SDG&E, as required, to remove 

and replace the existing electric and gas services affixed to the wall of the structure.    

Attached as reference is a current SDG&E Prearranged Customer Requested Outage form together with 

reference plans intended to generally depict the scope of work associated with removing and replacing 

the electrical services on the building.      

PWS21-1170FAC Addendum No. 1

Page 11: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

PM Forms: PrearrangedCustomerRequestedOutage-NonResidential.dot Revision Date: 9/15/2014

Scope of Work for Non-Residential Prearranged Customer Requested Outage

Customer Name: Date: Address: Telephone: SDG&E Project #: _________________ Outage Requested By (Name of Company): Company Representative: Title: E-Mail: Telephone: Fax: Contact person at job site: Cell Phone: Payment by: Telephone: Company Name

Mailing Address: City: Zip Code: E-mail Address:

Date Requested for De-energize:

Re-energize Date: Alternate Date:

Time Requested for De-energize:

Re-energize Time:

Detailed Scope of Work to be Performed: Additional Questions: 1. Is a permit from the authority having jurisdiction required for the work you are performing? Yes No

If yes, what is your permit number? 2. Are you replacing the existing terminating enclosure (underground pull section)? Yes No

If yes, indicate the size of the new pull section ( amperes), and provide description of work: If adding load, provide new load calculations: If replacing the existing terminating enclosure, electrical contractor to field verify and confirm the following: Height of landing positions on all phases and neutral in NEW pull section are at, or lower than, the existing landing positions. Yes No If no, new utility service lateral conductors will be required and may be at customer’s expense. SDG&E Planner to verify cost responsibilities prior to scheduling the outage.

3. Are you adding new, replacing, or disconnecting/reconnecting any service entrance conductors?

Yes No If yes, explain which conductors are involved and provide description of work: 4. Are you tapping the existing bus in the terminating enclosure? Yes No

If yes, have you submitted your Tap Drawings and received approval from SDG&E? Yes No Comments:

5. Are you adding any new service entrance conductors? Yes No

If yes, please describe where they originate and where they terminate: 6. Are you adding any new service and metering equipment? Yes No

If yes, indicate the number and size of each service you are adding, along with the number and size of each metering section. How will they be addressed?

7. Are you removing any service and metering equipment? Yes No

If yes, indicate SDG&E’s electric meter number(s) to be removed and the size of the metering section:

PWS21-1170FAC Addendum No. 1

Page 12: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

E0.01

COVER SHEET

Team

Project No.

Drawing No.

Construction Documents 2020.05.28

City

of C

arls

bad

- New

Villa

ge A

rts T

heat

er P

artia

l Rer

oofin

g27

87 S

tate

St,

Car

lsba

d, C

A 92

008

Site

Pla

n

1910

350 Pauma PlaceEscondido, CA 92029TEL: 760.658.6098

Electrical Engineers, Inc.1. CONTRACTOR TO OBTAIN PERMISSION FOR ACCESS TO THE SITE FROM THE

OWNER OR DESIGNATED OWNER REPRESENTATIVE TO VISIT THE SITE INCLUDINGALL AREAS OF WORK PRIOR TO BID. CONTRACTOR TO BE FAMILIARIZED WITHEXISTING CONDITIONS, VERIFY SAID CONDITIONS, DIMENSIONS, AND ROUTINGSPRIOR TO START OF CONSTRUCTION. REPORT ANY DISCREPANCIES TO OWNER /ARCHITECT / ENGINEER WITHIN 48 HOURS OF DISCREPANCIES FOUND.

2. CONTRACTOR SHALL CONFIRM ACCURACY OF PANEL BOARD INFORMATIONPRIOR TO START OF WORK. REPORT ANY DISCREPANCIES TO OWNER /ARCHITECT / ENGINEER WITHIN 48 HOURS OF DISCREPANCIES FOUND.

3. ALL WORK SHOWN IS NEW UNLESS OTHERWISE NOTED.

4. ALL AREAS OUTSIDE THE SCOPE OF WORK SHALL BE PROTECTED IN PLACE ANDREMAIN INTACT, U.O.N.

5. CONTRACTOR TO COORDINATE WITH OWNER ANY SHUTDOWN OF ELECTRICALEQUIPMENT WITH 7 DAYS NOTIFICATION. CONTRACTOR TO INCLUDE OFF HOURSIN PRICING FOR THIS WORK.

6. ALL ELECTRICAL MATERIAL AND EQUIPMENT SHALL BE NEW BEARING A ULLISTING OR ACCEPTABLE NRTL LISTING FROM THE LOCAL AREA JURISDICTION.

7. CONTRACTOR SHALL COMPLY WITH THE CURRENT VERSION OF THE CALIFORNIAELECTRICAL CODE 2019, STATE, LOCAL CODES, ORDINANCES, AND REGULATIONS.

8. WORK SHALL BE PERFORMED IN A SAFE MANNER AND NOT DISTURB OR AFFECTEXISTING BUILDING UTILITIES, OCCUPANTS, OR FINISHES WITHOUT PRIOR NOTICEAND APPROVAL FROM OWNER.

9. ALL CONDUIT RUN SHALL BE FIELD COORDINATED, LOCATE CONDUITS CLEAR OFOTHER TRADES, DOOR ACCESS, OR OTHER OBSTRUCTIONS. COORDINATECONDUIT RUNS WITH OTHER TRADES PRIOR TO COMMENCEMENT OF WORK.

10. RUN ALL CONDUITS CONCEALED IN CEILING SPACES, U.O.N. TO BE SURFACEMOUNTED. ALL CONDUIT PATHWAYS MUST MAINTAIN 6 INCHES CLEAR OFSOURCES OF HEAT, SUPPORT CONDUITS FROM STRUCTURE.

11. ALL BRANCH CIRCUITS TO BE PROVIDED WITH SEPARATE GREEN GROUNDINSULATED CONDUCTOR.

12. ALL BRANCH CIRCUITS TO BE PROVIDED WITH SEPARATE WHITE NEUTRALINSULATED CONDUCTOR. SHARED NEUTRAL IS ACCEPTABLE IF COMMON HANDLETIE CIRCUIT BREAKER ARE UTILIZED TO SIMULTANEOUSLY DISCONNECT ALLUNGROUNDED CONDUCTORS PER NEC 210.4(B).

13. PROVIDE IDENTIFICATION TAGS FOR ALL WIRING, INSTALL TAGS AT END OF RUNS,INTERMEDIATE PULL BOXES, JUNCTION BOXES, CABINETS, ETC.

14. BRANCH CIRCUIT VOLTAGE DROP NOT TO EXCEED 3% FROM PANEL BOARDSOURCE.

15. LABEL ALL CIRCUIT BREAKERS IN ALL ELECTRICAL DISTRIBUTION PANELS ANDSWITCHBOARDS. PROVIDE TYPE WRITTEN CIRCUIT DIRECTORY CARDS FOR ANYPANEL BOARD HAVING CIRCUIT MODIFICATIONS.

16. PROVIDE P-TOUCH LABELS ON ALL NEW OUTLETS, RACKS, PLUG MOLD, ANDSWITCHES.

17. ALL CONDUITS PENETRATING ELECTRICAL/MECHANICAL SPACES OF RATEDWALLS SHALL BE SEALED AND FIRE STOPPED.

18. ALL ELECTRICAL PENETRATIONS INTO COOLER OR FREEZER UNITS SHALL BESEALED PER SECTION 300-7 OF THE NEC.

19. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT SHALLBE PERMITTED TO BE LOCATED WITHIN THE DEDICATED SPACE ABOVE THEELECTRICAL EQUIPMENT PER NEC 110.26(E) (1).

20. THE ENGINEER OF RECORD TAKES NO EXCEPTION TO THE USE OF MC CABLEWHERE ALLOWED BY THE CEC 330 AND PROVIDE MC CABLE IS ACCEPTABLE WITHBUILDING OWNERSHIP

GENERAL PROJECT NOTES

ABBREVIATIONS AND DESCRIPTIONSA / AMP AMPERE

ABV ABOVE

ADA AMERICAN WITH DISABILITIES ACT

AF AMPERE FRAME, AMPERE FUSE

AFF / A.F.F. ABOVE FINISH FLOOR

AFG, A.F.G. ABOVE FINISH GRADE

AWG AMERICAN WIRE GAUGE

AIC / A.I.C. AMPERE INTERRUPTING CAPACITY

AS AMPERE SWITCH

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AVG AVERAGE

BKR BREAKER

BLDG BUILDING

BR BRANCH

C CONDUIT

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CBC CALIFORNIA BUILDING CODE

CEC CALIFORNIA ELECTRIC CODE

CFC CALIFORNIA FIRE CODE

CIRC / CKT CIRCUIT

CL CENTER LINE

CLG CEILING

CO / C.O. CONDUIT ONLY

COMM COMMUNICATIONS

CSFM CALIFORNIA STATE FIRE MARSHALL

CT CONTROL TRANSFORMER

CONN CONNECTED

CPT CONTROL POWER TRANSFORMER

CTR CENTER

DET DETAIL

DIST DISTRIBUTION

DP DISTRIBUTION PANEL

(D) DEMOLISH

DISC DISCONNECT

DWG DRAWING

DIA DIAMETER

DIM DIMENSION

EMT ELECTRICAL METALLIC TUBING

EP EXPLOSION PROOF

EM EMERGENCY

EQP EQUIPMENT

(E) EXISTING

ELEC ELECTRICAL

EMS EMERGENCY MANAGEMENT CONTROL SYSTEM

ENT ELECTRICAL NON-METALLIC TUBING

EPO / E.P.O EMERGENCY POWER OFF

EF EXHAUST FAN

EG EQUIPMENT GROUND

EOL END OF LINE RESISTOR

FACP FIRE ALARM CONTROL PANEL

FLR FLOOR

FATC FIRE ALARM TERMINAL CABINET

FA FIRE ALARM

FLA FULL LOAD AMPS

FT / ' FEET

FIN FINISH

G / GND GROUND

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

GEC GROUNDING ELECTRODE CONDUCTOR

H / HGT HEIGHT

HOA HAND OFF AUTO

HP HORSEPOWER

HACR HEATING AIR CONDITIONING REFRIGERATION

HVAC HEATING, VENTILATING AND AIR CONDITIONING

HID HIGH INTENSITY DISCHARGE

IC INTERCOM

IDF INTERMEDIATE DISTRIBUTION FRAME

IN / " INCHES

IMC INTERMEDIATE METAL CONDUIT

IP INTERNET PROTOCOL

IG ISOLATED GROUND

JB / JBOX JUNCTION BOX

KAIC KILOAMPERE INTERRUPTING CAPACITY

KV KILOVOLT

KVA KILOVOLT AMPERE

KW KILOWATT

KWH KILOWATT HOUR

LTG / LTS LIGHTING

LV LOW VOLTAGE

LF LINEAR FEET

KCMIL / MCM THOUSAND CIRCULAR MILS

MAX MAXIMUM

MDF MAIN DISTRIBUTION FRAME

MECH MECHANICAL

MH MANHOLE

MTD MOUNTED

MTG MOUNTING

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT CIRCUIT PROTECTION

MCA MINIMUM CIRCUIT AMPERES

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUGS ONLY

M METER

MV MERCURY VAPOR

MCC MOTOR CONTROL CENTER

MFR MANUFACTURER

NC NORMALLY CLOSED

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NO. / # NUMBER

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MFR ASSOCIATION

NF NON-FUSED

NL NIGHT LIGHT

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISH, CONTRACTOR INSTALLED

P POLE

PB PULL BOX

PF POWER FACTOR

PA PUBLIC ADDRESS

PH / ø PHASE

PNL PANEL

PRIMARY OVER 600 VOLTS

PC PHOTOCELL

PDU POWER DISTRIBUTION UNIT

PROVIDE FURNISH, INSTALL AND/OR CONNECT

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE

REQD REQUIRED

REQT(S) REQUIREMENT(S)

RM ROOM

RMS ROOT MEAN SQUARE

RGS RIGID GALVANIZED STEEL CONDUIT

RECEPT RECEPTACLE

SHT SHEET

SW SWITCH

SWBD SWITCHBOARD

STC SIGNAL TERMINAL CABINET

SCC SHORT CIRCUIT CURRENT

SFD SMOKE FIRE DAMPER

SECONDARY 600 VOLTS AND LESS

SQ SQUARE

TEL TELEPHONE

TYP TYPICAL

TC TIMECLOCK

TEL/DAT TELEPHONE AND DATA

TV TELEVISION

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION

UL UNDERWRITERS LABORATORIES

UON / U.O.N. UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTAGE

VA VOLT AMPERES

VD VOLTAGE DROP

VAV VARIABLE AIR VOLUME

W WATTAGE OR WIRE

WP WEATHERPROOF

WAP WIRELESS ACCESS POINT

XFMR TRANSFORMER

X / (X) EXISTING

XL / (XL) EXISTING TO BE RELOCATED

XR / (XR) EXISTING TO BE REMOVED

XN / (XN) EXISTING NEW LOCATION

%Z PERCENTAGE IMPEDANCE

WT WEIGHT

WH WATER HEATER

VFD VARIABLE FREQUENCY DRIVE

UGPS UNDERGROUND PULL SECTION

TEMP TEMPERATURE OR TEMPORARY

SWGR METAL CLAD SWITCHGEAR

SPEC SPECIFICATIONS

REC RECESSED

REFRIG REFRIGERATOR

QTY QUANTITY

PWR POWER

N / NEUT NEUTRAL

LBS POUNDS

KS KNEE SPACE

HR HOUR OR HOME RUN

HZ HERTZ

GC GENERAL CONTRACTOR

GALV GALVANIZED

CU COPPER

CCTV CLOSED CIRCUIT TELEVISION

AL ALUMINUM

AC ALTERNATING CURRENT

A/C AIR CONDITIONING

DC DIRECT CURRENT

EA EACH

EXO DISCONNECT SWITCH

EC ELECTRICAL CONTRACTOR

ED EXTRA-DUTY

WR WEATHER RESISTANT

CONTROL LEGEND

SURFACE MOUNTED SPST SWITCH MOUNTED AT +48" AFF TO TOP OFBOX U.O.N

FLUSH MOUNTED SINGLE POLE STANDARD TOGGLE SWITCHMOUNTED AT +48" AFF TO TOP OF BOX U.O.N. LETTERING INDICATESQUANTITY OF SWITCHES AND DEVICES TO BE CONTROLLED.

XXD = DIMMING SWITCHK = KEYED SWITCHP = PILOT LIGHT SWITCHR = MOMENTARY CONTACT SWITCHT = TIMER SWITCH3 = THREE WAY SWITCH

FLUSH INFRARED WALL OCCUPANCY SENSOR SINGLE BUTTONMOUNTED AT +48" AFF TO TOP OF BOX U.O.N

OC

FLUSH INFRARED WALL OCCUPANCY SENSOR DUAL BUTTONMOUNTED AT +48" AFF TO TOP OF BOX U.O.NOC

ab

SURFACE INFRARED WALL OCCUPANCY SENSOR SINGLE BUTTONMOUNTED AT +48" AFF TO TOP OF BOX U.O.N

SURFACE INFRARED WALL OCCUPANCY SENSOR DUAL BUTTONMOUNTED AT +48" AFF TO TOP OF BOX U.O.N

ab

OC

OC

XXU = ULTRA SONIC OCCUPANCY SENSORDT = DUAL TECHNOLOGY OCCUPANCY SENSOROC

CEILING MOUNTED INFRARED OCCUPANCY SENSOROC

FLUSH MOUNTED OVERRIDE SWITCH STATION MOUNTED AT +48" AFFTO TOP OF BOX U.O.N. BUTTON CONFIGURATION AS NOTED PERFLOOR PLAN

SURFACE MOUNTED OVERRIDE SWITCH STATION MOUNTED AT +48"AFF TO TOP OF BOX U.O.N. BUTTON CONFIGURATION AS NOTED PERFLOOR PLAN

PHOTOCELL MOUNTED AND ORIENTATED AS NOTED ON FLOOR PLAN

O

O

PC

DL CEILING MOUNTED DAY LIGHT SENSOR

SINGLE LINE LEGEND

ELECTRONIC METERING UNIT

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

DRAWOUT CIRCUIT BREAKERAMP FRAMEAMP TRIPPOLE CONFIGURATIONELECTRONIC TRIP FUNCTIONS

FUSE

TRANSFORMER

100AF100AT3LSIG

FUSED SWITCHAMP SWITCHAMP FUSEPOLE CONFIGURATION

100AS100AF3

CIRCUIT BREAKERAMP FRAMEAMP TRIPPOLE CONFIGURATIONELECTRONIC TRIP FUNCTIONS

100AF100AT3LSIG

GROUNDING ELECTRODE

ENCLOSED CIRCUIT BREAKERAMP FRAMEAMP TRIPPOLE CONFIGURATIONELECTRONIC TRIP FUNCTIONS

100AF100AT3LSIG

C

NORMALLY OPEN CONTACT

NORMALLY CLOSED CONTACT

COIL

SHUNT TRIPST

SOLID STATESS

FEEDER TAGXXXX

AUTOMATIC TRANSFER SWITCH

PACKAGE ENGINE GENERATOR

PANEL BOARDPANEL

HL1

TRANSIENT VOLTAGE SURGE SUPPRESSIONTVSS

M

+-+- STRINGER INVERTER

+

- PHOTOVOLTAIC PANEL (PV PANEL)

FLUSH MOUNTED HALF HOT DUPLEX RECEPTACLE MOUNTED AT +15"AFF TO BOTTOM OF BOX U.O.N

XX

HALF SHADED WIRING INDICATES CONTROLLEDRECEPTACLE PER TITLE 24 SECTION 130.5(d)

POWER LEGEND

FLUSH MOUNTED DUPLEX RECEPTACLE MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N

FLUSH MOUNTED QUAD RECEPTACLE MOUNTING HEIGHT TOBOTTOM OF BOX PER ARCHITECT ELEVATION

SURFACED MOUNTED DUPLEX RECEPTACLE MOUNTED AT +15" AFFTO BOTTOM OF BOX U.O.N

SURFACE MOUNTED QUAD RECEPTACLE MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N

FLUSH MOUNTED SINGLE RECEPTACLE MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N

SURFACE MOUNTED SINGLE RECEPTACLE MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N

CEILING MOUNTED DUPLEX RECEPTACLE

CEILING MOUNTED QUAD RECEPTACLE

FLUSH FLOOR BOX WITH DUPLEX RECEPTACLE

FLUSH FLOOR BOX WITH QUAD RECEPTACLE

FLUSH FLOOR BOX WITH COMBINATION DUPLEX RECEPTACLE ANDDATA OUTLET

FLUSH FLOOR BOX WITH COMBINATION QUAD RECEPTACLE ANDDATA OUTLET

FIRE RATED POKE THRU WITH DUPLEX RECEPTACLE

FIRE RATED POKE THRU WITH QUAD RECEPTACLE

FIRE RATED POKE THRU WITH DUPLEX RECEPTACLE AND DATAOUTLET

FIRE RATED POKE THRU WITH QUAD RECEPTACLE AND DATAOUTLET

XX

FLUSH MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLEMOUNTED AT +15" AFF TO BOTTOM OF BOX U.O.N

SURFACE MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLEMOUNTED AT +15" AFF TO BOTTOM OF BOX U.O.N

XX-XXX

XX-XXX

FLUSH MOUNTED JUNCTION BOX MOUNTED AT +15" AFF TO BOTTOMOF BOX U.O.NSURFACE MOUNTED JUNCTION BOX MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N

FLUSH FLOOR MOUNTED JUNCTION BOX

CEILING MOUNTED JUNCTION BOXJ

J

J

J

GFCIIGSHAC

GROUND FAULT CIRCUIT INTERRUPTERISOLATED GROUNDSURGE SUPPRESSORHORIZONTAL MOUNTEDMOUNT ABOVE COUNTER PERARCHITECT ELEVATIONPROVIDED WITH INTREGRAL USBPORTSRECEPTACLE CONTROLLED PER TITLE24 2013 SECTION 130.5(d)CLOCK TYPE

====

CEILING MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLEXX-XXX

FLOOR MOUNTED SPECIAL NEMA CONFIGURATION RECEPTACLEXX-XXX

=

=RC

=C

FLUSH MOUNTED DUPLEX RECEPTACLE MOUNTING HEIGHT TOBOTTOM OF BOX PER ARCHITECT ELEVATION

SURFACED MOUNTED DUPLEX RECEPTACLE MOUNTED AT COUNTERLEVEL PER ARCHITECT ELEVATION

SURFACE MOUNTED QUAD RECEPTACLE MOUNTING TO BOTTOM OFBOX PER ARCHITECT ELEVATION

FLUSH MOUNTED QUAD RECEPTACLE MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N

=USB

RECEPTACLE POWER PACK MOUNTED IN ACCESSIBLE CEILINGSPACE FOR AUTOMATIC CONTROL OF RECEPTACLE DEVICE

RC

M

EQUIPMENT LEGEND

HEAVY DUTY NON-FUSED DISCONNECT

HEAVY DUTY FUSED DISCONNECT

MOTOR STARTER, HOA, AUX CONTACTS, CPT, PILOT LIGHTS

COMBINATION MOTOR STARTER, HOA, AUX CONTACTS, CPT, PILOTLIGHTS, WITH FUSED DISCONNECT SWITCH

MECHANICAL EQUIPMENT TAG

MOTOR RATED SWITCH

SURFACE MOUNTED PANEL BOARD OR ELECTRICAL CABINET

DISTRIBUTION SWITCHBOARD OR PANEL BOARD

LIGHT FIXTURE DESIGNATIONLIGHTING BRANCH CIRCUITRELAY DESIGNATION IN LIGHTINGCONTROL PANEL

FLUSH MOUNTED PANEL BOARD OR ELECTRICAL CABINET

VARIABLE FREQUENCY DRIVE. CONFIRM INTEGRAL DISCONNECTINGMEANS WITH MECHANICAL

F1HL1-13(R1)

AHU

1

F

VFD

T TRANSFORMER

EMERGENCY POWER OFF BUTTONEPO

SFDSMOKE FIRE DAMPER

MOTOR

SIGNAL LEGEND

FLUSH MOUNTED TELEVISION OUTLET MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N

WIRELESS ACCESS POINT

FLUSH MOUNTED TELECOM OUTLET MOUNTED AT +15" AFF TOBOTTOM OF BOX U.O.N. PROVIDE 1"C. TO ACCESSIBLE CEILINGSPACE WITH PULL STRING, U.O.N.

SURFACE MOUNTED TELECOM OUTLET MOUNTED AT +15" AFF TOBOTTOM OF BOX U.ON. PROVIDE 1"C. TO ACCESSIBLE CEILINGSPACE WITH PULL STRING, U.O.N.

CEILING MOUNTED TELECOM OUTLET

PUSH BUTTON

BUZZER

BELL

WALL MOUNTED SPEAKER

CEILING MOUNTED SPEAKER

TV

WAP

FLUSH FLOOR BOX WITH TELECOM OUTLET

FIRE RATED POKE THRU WITH TELECOM OUTLET

B

B

S

S

FLUSH MOUNTED WALL PHONE OUTLET MOUNTED AT +44" AFF TOTOP OF BOX U.O.NW

SECURITY LEGENDALARM CONTACT

ELECTRIC DOOR STRIKE

DOOR CONTACT

REMOTE DOOR RELEASE

ELECTRONIC LOCK

VIBRATION DETECTOR

CARD READER

KEYPAD

A

CR

KP

GLASS BREAKGB

MOTION SENSORMS

ES

DC

DR

DOOR BREACH ALARM

PANIC BUTTON / DURESS ALARM

REQUEST TO EXITREX

ELECTRONIC HOLD OPENEHO

ELECTRONIC PANIC HARDWAREEPH

ELECTRONIC MAGNETIC LOCKEML

FIXED POSITION VIDEO CAMERA

EL

VD

DA

PB

PAN, TILT, ZOOM VIDEO CAMERAPTZ

PHOTOVOLTAIC LEGENDDC TO AC STRING INVERTER

POTENTIAL INDUCED DEGRATION (PID) ENERGY BALANCER CABINET

PHOTOVOLTAIC MODULE PANEL (PV PANEL)

PID

PHOTOVOLTAIC ARRAY (PV ARRAY)

STRING NUMBER DESIGNATION

INVERTER NUMBER DESIGNATIONS#.#

WIRING LEGEND

RACEWAY EXPOSED

RACEWAY TURNED UP

RACEWAY TURNED DOWN

RACEWAY CAPPED AND STUBBED.PROVIDE PERMANENT GROUNDMARKER FOR UNDERGROUND INSTALLATIONS

BRANCH CIRCUIT RACEWAY CONCEALED IN WALL OR CEILING

BRANCH CIRCUIT RACEWAY CONCEALED IN FLOOR ORUNDERGROUND

BRANCH CIRCUIT RACEWAY HOME RUN BACK TO ELECTRICALEQUIPMENT AS NOTED

L1-1

BRANCH CIRCUIT RACEWAY WITH 3#12, 1#12N, 1#12GND, 3/4"C.MAXIMUM THREE BRANCH CIRCUITS PER HOME RUN, U.O.N.

BRANCH CIRCUIT RACEWAY WITH 3#10, 1#10N, 1#10GND, 3/4"C.MAXIMUM THREE BRANCH CIRCUITS PER HOME RUN, U.O.N.

#10

CABLE TRAY

POINT OF CONNECTION TO EQUIPMENT

BRANCH CIRCUIT RACEWAY TO BE DEMOLISH

SURFACE MOUNTED WIRE MOLD RACEWAY SYSTEM.X = 1, 2 OR 3 CHANNEL RACEWAYWMX

SHEET INDEXSHEET NUMBER SHEET TITLEE0.01 COVER SHEET

E0.06 SITE PLAN

E8.01 SINGLE LINE DIAGRAM

PWS21-1170FAC Addendum No. 1

Page 13: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

Existing Building

TYP02.203

TYP02.203

02.204

02.204

TYP02.205

TYP02.205

TYP02.205

02.20602.206

02.20602.20601.001

Scope of Work

Scop

e of

Wor

k

Stat

e St

reet

Christiansen Way

MSA

KEYNOTES1 CONTRACTOR TO REMOVE EXISTING SDG&E PULL BOX OFF EXTERIOR WALL. CONTRACTOR

TO PROTECT TENANT FEEDER CABLES DURING EXTERIOR WALL IMPROVEMENT PHASE.COORDINATE SDG&E OUTAGE PRIOR TO COMMENCEMENT OF WORK.

AT COMPLETION OF EXTERIOR WALL WORK. REINSTALL NEW PULL BOX OF SAME SIZE ANDTYPE.

CONTRACTOR TO REMOVE EXISTING SDG&E 3-PACK METER SOCKET ASSEMBLIES OFFEXTERIOR WALL. CONTRACTOR TO PROTECT TENANT FEEDER CABLES DURING EXTERIORWALL IMPROVEMENT PHASE. COORDINATE SDG&E OUTAGE PRIOR TO COMMENCEMENT OFWORK.

AT COMPLETION OF EXTERIOR WALL WORK. REINSTALL EXISTING SDG&E 3-PACK METERSOCKET ASSEMBLIES. RECONNECTION EXISTING FEEDER TO TENANT PANELS.

GENERAL NOTES1. ALL ELECTRICAL DEVICES ARE EXISTING TO BE RELOCATED, U.O.N.

2. CONTRACTOR TO FIELD VERIFY BRANCH CIRCUITRY PRIOR TO COMMENCEMENT OFWORK.

3. CONTRACTOR TO MAINTAIN CIRCUITRY CONTINUITY TO EXISTING SPACE OUTSIDE THISSCOPE OF WORK.

4. SEE ARCHITECTURAL SHEETS FOR ADDITIONAL DEMOLITION REQUIREMENTS.

5. ELECTRICAL CONTRACTOR TO MAKE EXISTING ELECTRICAL SYSTEM SAFE FOR DEMOCONTRACTOR. ELECTRICAL CONTRACTOR TO IDENTIFY CONDUIT SYSTEMS THAT ARETO REMAIN AND CAREFULLY WALK WITH DEMO CONTRACTOR EXPLAINING WHAT NEEDSTO STAY. IT IS THE DEMO CONTRACTOR AND GENERAL CONTRACTORS RESPONSIBILITYTO SET THIS MEETING UP AND MAKE SURE THAT THE COMMUNICATION ON WHAT STAYSIS CRYSTAL CLEAR. ITEMS THAT STAY (FEEDERS TO PANELS ETC) SHOULD BE CLEARLYMARKED ON SITE WITH RED PAINT. ANYTHING MARKED RED SHALL NOT BE DEMOED ORREMOVED.

6. SEE SINGLE LINE DIAGRAM ON SHEET E8.01 FOR ADDITIONAL REQUIREMENTS.

2

3

12

4

34

Team

Project No.

Drawing No.

Construction Documents 2020.05.28

City

of C

arls

bad

- New

Villa

ge A

rts T

heat

er P

artia

l Rer

oofin

g27

87 S

tate

St,

Car

lsba

d, C

A 92

008

Site

Pla

n

1910

350 Pauma PlaceEscondido, CA 92029TEL: 760.658.6098

Electrical Engineers, Inc.

SCALE:1 SITE PLAN1/8" = 1'-0" E0.06

SITE PLAN

PWS21-1170FAC Addendum No. 1

Page 14: ADDENDUM NO. 1... · 13. provide identification tags for all wiring, install tags at end of runs, intermediate pull boxes, junction boxes, cabinets, etc. 14. branch circuit voltage

KEYNOTESEXISTING SDG&E PULL BOX TO BE REMOVED PRIOR TO COMMENCEMENT OF EXTERIORWALL WORK. SDG&E CONDUCTORS TO BE PROTECTED IN PLACE.

REPLACE EXISTING SDG&E PULL BOX WITH NEW. NEW PULL BOX TO MATCH EXISTINGTYPE AND SIZE. REINSTALL NEW PULL BOX IN EXISTING LOCATION AT COMPLETION OFEXTERIOR WALL PHASE.

EXISTING SDG&E METER.

EXISTING GROUNDING ELECTRODE SYSTEM TO REMAIN.

EXISTING SDG&E PULL CAN AND METER ASSEMBLIES TO BE REMOVED PRIOR TOCOMMENCEMENT OF EXTERIOR WALL WORK. SDG&E CONDUCTORS TO BE PROTECTEDIN PLACE.

REINSTALL EXISTING SDG&E PULL CAN AND METER ASSEMBLIES IN EXISTINGLOCATION AT COMPLETION OF EXTERIOR WALL PHASE.

GENERAL NOTES1. ALL ELECTRICAL DEVICE SHOWN ARE EXISTING TO REMAIN U.O.N.

2. ALL ELECTRICAL FEEDER CONDUIT AND CONDUCTORS ARE EXISTING TO REMAIN U.O.N.

3. ELECTRICAL PANELS ARE EXISTING TO REMAIN WITH EXISTING LOADS.

1

2

3EXISTING

SDG&EPADMOUNT

TRANSFORMER

SDG&E EXISTING12KV CIRCUIT EXISTING SDG&E CONDUIT AND

CONDUCTORS

EXISTING SDG&E PULL CAN - 400A, 208Y/120V, 3Ø, 4W

M

400A

G N

AFAT

P

2002003

EXISTINGFEEDER

M

AFAT

P

2002003

EXISTINGFEEDER

M

AFAT

P

2001503

EXISTINGFEEDER

EXISTINGGROUNDINGELECTRODE

3 3 3

4

EXISTINGFEEDER

EXISTINGPANEL

A

EXISTINGFEEDER

EXISTINGPANEL

B

12

EXISTINGFEEDER

EXISTINGPANEL

C

4

5

6

56

Team

Project No.

Drawing No.

Construction Documents 2020.05.28

City

of C

arls

bad

- New

Villa

ge A

rts T

heat

er P

artia

l Rer

oofin

g27

87 S

tate

St,

Car

lsba

d, C

A 92

008

Site

Pla

n

1910

350 Pauma PlaceEscondido, CA 92029TEL: 760.658.6098

Electrical Engineers, Inc.

SCALE:1 SINGLE LINE DIAGRAMNONE E8.01

SINGLE LINE DIAGRAM

PWS21-1170FAC Addendum No. 1