ADVAC Technical Guide 1VAL050501-TG Rev A

Embed Size (px)

Citation preview

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    1/20

    ADVACTM technical guideAdvanced design vacuum circuit breakers

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    2/202 ADVAC circuit breaker | Technical guide

    ADVAC

    Universal applications:

    Medium voltage motor starting applications

    Capacitor switching

    Retrofit applications to replace existing circuit breakers in

    repetitive duty applications

    ADVAC circuit breakers have been fully tested to the most

    recent versions of ANSI C37.04, C37.06,and C37.09. Using "k"

    factor equals 1 as the test criteria.

    Available for 5, 8.25, and 15 kVapplications, in stationary and drawoutforms.

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    3/20Technical guide | ADVAC circuit breaker

    The new ADVAC circuit breaker continues to improve upon pre-

    vious designs. Although some aspects remain unchanged, the

    differences set this generation of circuit breakers apart from the

    rest. The operating mechanism was refreshed with the EL me-

    chanism featuring quick and easy accessory installations. New

    programmable smart coils provide close, open, and under-

    voltage actuation of the breaker. All models feature embedded

    poles that attain excellent dielectric and thermal capabilities as

    well as provide superior protection against outside influences.

    ADVAC. The circuit breaker.

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    4/204 ADVAC circuit breaker | Technical guide

    ADVAC

    A sturdy metal frame provides the support for the operating me-

    chanism and the poles. This frame also allows for the breaker

    to be mounted as a fixed version. The operating mechanism

    harnesses stored energy and free trip allowing the opening

    and closing operations to be independent of the operator. Theoperating mechanism is a simple module containing the electric

    motor and gears necessary to provide charging of the closing

    spring. This construction allows for simple removal of the me-

    chanism as a complete assembly and greatly increases the relia-

    bility of the apparatus. The mechanism can also be customized

    with various accessories that are quick and easy to install. The

    new smart coils integrate all necessary components required for

    electrical operation of the breaker. The smart coils are simple to

    install due to their modular design.

    Smart coils

    Auxiliary contacts

    Charging motor

    Manual charging leverEL mechanism

    Summary of benefits:

    Manual provisions to charge, close, and open the breaker

    Built in charging lever

    EL mechanism features extremely limited and simple

    maintenance

    Mechanical anti-pumping device supplies as standard

    Quick and easy smart coil installation

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    5/20Technical guide | ADVAC circuit breaker

    The vacuum interrupter assembly consists of the interrupter and

    the current carrying parts completely embedded in a proprietary

    epoxy resin. Thermal performance of the interrupter is improved

    as the epoxy resin draws heat away from the hot spots for a

    more even heat distribution. Moreover, the interrupter pole as-

    sembly is fully skirted so that push rod and other moving parts

    of the current transfer area are isolated and protected from

    external influences. As a result, accumulations of dust, dirt, and

    condensation do not increase tracking and partial discharge as

    they do in non-embedded designs.

    AMVAC. Qualities that convince.

    Maintenance free vacuum interrupterand current carrying parts in oneembedded assembly

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    6/206 ADVAC circuit breaker | Technical guide

    Smart coils provide electrical control of the mechanical func-

    tions of the circuit breaker. One open and one close coil are

    installed as standard parts for basic circuit breaker operation.

    An additional open coil can be easily installed and wired to a

    circuit completely separate from the first open coil. An under-

    voltage release can also be easily installed to provide circuit

    breaker opening if there is a notable drop in voltage. The coils

    can both operate in direct and alternating current. Installationof these coils only involves securing the coil with a couple of

    screws and connecting a wire plug. The coils are programmed

    at the factory and ready to install upon arrival.

    ADVAC. Smart coils.

    Open, close, and undervoltage coilsallow remote operation of circuit breakerfunctions.

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    7/20Technical guide | ADVAC circuit breaker

    ADVAC. Stored energy operating mechanism.

    ADVAC uses a simple, front-accessible stored energy operating

    mechanism designed specifically for use with vacuum technolo-

    gy. This provides the benefits of dependable vacuum interrup-

    ters with advanced contact design and proven reliability, without

    the complexity of mechanisms and linkages found in previous

    generation circuit breakers.

    The EL mechanism can be charged manually using the spring

    charging lever or electrically by the spring charging gear motor

    While activating one of the above mentioned methods, the cam

    (2) on the rotating operating shaft (1) move the closing lever

    assembly (3) to charge the closing spring.

    A part of the closing springs force works on the closing hook

    through the closing lever assembly and the pin of the cam/tog

    le assembly (1). The closing hook remains locked by the closin

    shaft (2) and the opening hook reaches its position where it

    receives the central hook of the cam/toggle assembly (3). The

    breaker signals that it is charged.

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    8/208 ADVAC circuit breaker | Technical guide

    Activating the closing push button rotates the closing shaft and

    releases the closing hook (1). The stored energy of the closing

    spring is transferred to the closing lever assembly (2) which pu-

    shes the long levers of the cam/toggle assembly connected by

    a pin (3). The long levers move the main shaft counter-clock-

    wise (4) which transfers the motion to the push rods connected

    to the contacts in the vacuum interrupters. The breaker signals

    that it is closed

    The long levers reach their settled position (1) once the breaker

    is closed and are held by the central hook of the cam/toggle

    assembly (3). The contact springs inside the poles and the ope-

    ning spring inside the frame are charged. The contact springs

    maintain contact pressure while the breaker is in the closedposition. The central hook applies force to the opening hook (4)

    which is locked by the opening shaft (5).

    The charging motor (if present) automatically rotates the opera-

    ting mechanism. The closing spring is now charged again and

    ready for the next closing operation.

    Activating the opening push button rotates the opening shaft

    and releases the opening hook (1). This action releases the

    central hook of the cam/toggle assembly (2) allowing the con-

    tact and opening springs to transfer their energy to the long

    levers (3). The main shaft rotates clockwise (4) and the breaker

    signals that it is open.

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    9/20Technical guide | ADVAC circuit breaker

    ADVAC. Technical data.

    Table 1. Short circuit ratings

    Voltage

    Class

    FLC

    (Amps)

    Isc (kA) Type/Rating Max. Wave volta-

    ge (kV, rms)

    Max. Sym. Inter-

    rupt & STC (kA,

    rms)

    Close & Latch

    (kA, rms)

    Lightning Impulse

    Withstand (BIL) (kV,

    Crest)

    Low Frequenc

    Withstand (H

    Pot) (kV, rms

    5

    1200

    25 ADVAC 05.12.25 4.76 25 65 60 19

    31.5 ADVAC 05.12.31 4.76 31.5 82 60 19

    40 ADVAC 05.12.40 4.76 40 104 60 19

    50 ADVAC 05.12.50 4.76 50 130 60 19

    2000

    25 ADVAC 05.20.25 4.76 25 65 60 19

    31.5 ADVAC 05.20.31 4.76 31.5 82 60 19

    40 ADVAC 05.20.40 4.76 40 104 60 19

    50 ADVAC 05.20.50 4.76 50 130 60 19

    3000

    25 ADVAC 05.30.25 4.76 25 65 60 19

    31.5 ADVAC 05.30.31 4.76 31.5 82 60 19

    40 ADVAC 05.30.40 4.76 40 104 60 19

    50 ADVAC 05.30.50 4.76 50 130 60 19

    8.25

    1200

    40

    ADVAC 08.12.40 8.25 40 104 95 36

    2000 ADVAC 08.20.40 8.25 40 104 95 36

    3000 ADVAC 08.30.40 8.25 40 104 95 36

    15

    1200

    20 ADVAC 15.12.20 15 20 52 95 36

    25 ADVAC 15.12.25 15 25 65 95 36

    31.5 ADVAC 15.12.31 15 31.5 82 95 36

    40 ADVAC 15.12.40 15 40 104 95 36

    50 ADVAC 15.12.50 15 50 130 95 36

    2000

    20 ADVAC 15.20.20 15 20 52 95 36

    25 ADVAC 15.20.25 15 25 65 95 36

    31.5 ADVAC 15.20.31 15 31.5 82 95 36

    40 ADVAC 15.20.40 15 40 104 95 36

    50 ADVAC 15.20.50 15 50 130 95 36

    3000

    20 ADVAC 15.30.20 15 20 52 95 36

    25 ADVAC 15.30.25 15 25 65 95 36

    31.5 ADVAC 15.30.31 15 31.5 82 95 36

    40 ADVAC 15.30.40 15 40 104 95 36

    50 ADVAC 15.30.50 15 50 130 95 36

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    10/2010 ADVAC circuit breaker | Technical guide

    Table 2. Capacitor bank switching ratings

    Voltage

    Class

    FLC (Amps) Isc (kA) Type/Rating Max. Sym. Interrupt

    & STC (kA, rms)

    Capacitor Switching Ratings

    5

    1200

    25 ADVAC 05.12.25 25 C2 630A C2 rated 15kA Peak 2.0 Khz

    31.5 ADVAC 05.12.31 31.5 C1 Rated cable charging current 10A

    40 ADVAC 05.12.40 40 C1 Rated cable charging current 10A

    50 ADVAC 05.12.50 50 C2 630A C2 rated 15kA Peak 2.0 Khz

    2000

    25 ADVAC 05.20.25 25 C1 Rated cable charging current 10A

    31.5 ADVAC 05.20.31 31.5 C1 Rated cable charging current 10A

    40 ADVAC 05.20.40 40 C2 1200A C2 rated 15kA Peak 2.0 Khz

    50 ADVAC 05.20.50 50 C2 1200A C2 rated 15kA Peak 2.0 Khz

    3000

    25 ADVAC 05.30.25 25 C2 1200A C2 rated 15kA Peak 2.0 Khz

    31.5 ADVAC 05.30.31 31.5 C2 1200A C2 rated 15kA Peak 2.0 Khz

    40 ADVAC 05.30.40 40 C2 1200A C2 rated 15kA Peak 2.0 Khz

    50 ADVAC 05.30.50 50 C2 1000A C2 rated 15kA Peak 2.0 Khz

    8.25

    1200

    40

    ADVAC 08.12.40 40 C2 1200A C2 rated 15kA Peak 2.0 Khz

    2000 ADVAC 08.20.40 40 C2 1200A C2 rated 15kA Peak 2.0 Khz

    3000 ADVAC 08.30.40 40 C2 1200A C2 rated 15kA Peak 2.0 Khz

    15

    1200

    20 ADVAC 15.12.20 20 C2 630A C2 rated 15kA Peak 2.0 Khz

    25 ADVAC 15.12.25 25 C2 630A C2 rated 15kA Peak 2.0 Khz

    31.5 ADVAC 15.12.31 31.5 C1 Rated cable charging current 10A

    40 ADVAC 15.12.40 40 C2 630A C2 rated 15kA Peak 2.0 Khz

    50 ADVAC 15.12.50 50 C2 630A C2 rated 15kA Peak 2.0 Khz

    2000

    20 ADVAC 15.20.20 20 C1 Rated cable charging current 25A

    25 ADVAC 15.20.25 25 C1 Rated cable charging current 25A

    31.5 ADVAC 15.20.31 31.5 C1 Rated cable charging current 25A 40 ADVAC 15.20.40 40 C2 1200A C2 rated 15kA Peak 2.0 Khz

    50 ADVAC 15.20.50 50 C2 1000A C2 rated 15kA Peak 2.0 Khz

    3000

    20 ADVAC 15.30.20 20 C2 1200A C2 rated 15kA Peak 2.0 Khz

    25 ADVAC 15.30.25 25 C2 1200A C2 rated 15kA Peak 2.0 Khz

    31.5 ADVAC 15.30.31 31.5 C2 1200A C2 rated 15kA Peak 2.0 Khz

    40 ADVAC 15.30.40 40 C2 1000A C2 rated 15kA Peak 2.0 Khz

    50 ADVAC 15.30.50 50 C2 1000A C2 rated 15kA Peak 2.0 Khz

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    11/20Technical guide | ADVAC circuit breaker

    Table 3. Timing characteristics

    Voltage

    Class

    FLC

    (Amps) Isc (kA) Type/Rating

    Max. Sym.

    Interrupt & STC

    (kA, rms)

    Interrupt Time

    (cycles)

    Opening time

    (ms) 3 cycles

    Opening time

    (ms) 5 cyc les Clos ing time

    5

    1200

    25 ADVAC 05.12.25 25 3 27.5-33 N.A. 30-60

    31.5 ADVAC 05.12.31 31.5 3 22.9-34 N.A. 30-60

    40 ADVAC 05.12.40 40 5 NA 60-70.9 50-80

    50 ADVAC 05.12.50 50 5 NA 57.5-70.3 50-80

    2000

    25 ADVAC 05.20.25 25 3 22.9-34 N.A. 30-60

    31.5 ADVAC 05.20.31 31.5 3 22.9-34 N.A. 30-60

    40 ADVAC 05.20.40 40 3 26.4-34.3 N.A. 50-80

    50 ADVAC 05.20.50 50 5 NA 57.5-70.3 50-80

    3000

    25 ADVAC 05.30.25 25 3 26.4-34.3 N.A. 50-80

    31.5 ADVAC 05.30.31 31.5 3 26.4-34.3 N.A. 50-80

    40 ADVAC 05.30.40 40 3 26.4-34.3 N.A. 50-80

    50 ADVAC 05.30.50 50 5 NA 57.5-70.3 50-80

    8.25

    1200

    40

    ADVAC 08.12.40 40 3 26.4-34.3 N.A. 50-80

    2000 ADVAC 08.20.40 40 3 26.4-34.3 N.A. 50-80

    3000 ADVAC 08.30.40 40 3 26.4-34.3 N.A. 50-80

    15

    1200

    20 ADVAC 15.12.20 20 3 27.5-33 N.A. 30-60

    25 ADVAC 15.12.25 25 3 27.5-33 N.A. 30-60

    31.5 ADVAC 15.12.31 31.5 3 22.9-34 N.A. 30-60

    40 ADVAC 15.12.40 40 3 26.4-34.3 N.A. 50-80

    50 ADVAC 15.12.50 50 3 26.3-38.6 N.A. 50-80

    2000

    20 ADVAC 15.20.20 20 3 22.9-34 N.A. 30-60

    25 ADVAC 15.20.25 25 3 22.9-34 N.A. 30-6031.5 ADVAC 15.20.31 31.5 3 22.9-34 N.A. 30-60

    40 ADVAC 15.20.40 40 3 26.4-34.3 N.A. 50-80

    50 ADVAC 15.20.50 50 3 26.3-38.6 N.A. 50-80

    3000

    20 ADVAC 15.30.20 20 3 26.4-34.3 N.A. 50-80

    25 ADVAC 15.30.25 25 3 26.4-34.3 N.A. 50-80

    31.5 ADVAC 15.30.31 31.5 3 26.4-34.3 N.A. 50-80

    40 ADVAC 15.30.40 40 3 26.4-34.3 N.A. 50-80

    50 ADVAC 15.30.50 50 3 26.3-38.6 N.A. 50-80

    Table 4: Mechanical details:Parameter 5 kV 7.5 kV 15 kV

    No load mechanical operations 5,000-10,000 10,000 5,000-10,000

    Operations between servicing 1,000-2,000 2,000 1,000-2,000

    Operations at full load current 500-1,000 1,000 500-1,000

    Height (draw out) (mm) 27.88 (708) 27.88 (708) 27.88 (708)

    Depth (draw out) (mm) 24.17 (614) 24.17 (614) 24.17 (614)

    Width (frame) (mm) 27.56 (700) 27.56 (700) 27.56 (700)

    29.53 (750) [50 kA] NA 29.53 (750) [50 kA]

    Weight (drawout) (min/max) lbs (kg) 132.5 (60.1) 132.5 (60.1) 132.5 (60.1)

    218.6 (99.2) 218.6 (99.2) 218.6 (99.2)

    *Total interrupting time consists of opening time plus the time required for arc interruption. Total interrupt time is 50 ms or less for 3 cycle breakers and 83 ms or less for 5 cycle breake

    Opening time is defined as the time from when the trip signal is received until primary contacts begin to part.

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    12/2012 ADVAC circuit breaker | Technical guide

    Table 5. Open (MO1, MO2) and Close (MC) coils

    Parameter

    Un 24-48-125-250 VDC

    120-240 VAC

    Operating limits 70-110% Un

    Power on inrush (Ps) DC: 200 W

    AC : 200 VA

    Inrush duration approx. 100 ms

    Continuous power (Pc) DC: 5 W

    AC: 5 VA

    Opening time * 40-60 ms

    Closing time ** 40-80 ms

    Insulation voltage 2000 V 50 Hz (for 1 min)

    Table 6. Undervoltage (MU) coil

    Parameter

    Un 24-48-125-250 VDC

    120-240 VAC

    Operating limits CB opeining: 35-70% Un

    CB closing: 85-110% Un

    Power on inrush (Ps) DC: 200 W

    AC: 200 VA

    Inrush duration approx. 100 ms

    Continuous power (Pc) DC: 5 W

    AC: 5 VA

    Opening time 60-80 ms

    Insulation voltage 2000 V 50 Hz (for 1 min)

    * Valid for MO1 and MO2

    ** Valid for MC

    Table 7. Gear motors (MS)

    Parameter

    Un 24-48-125-250 VDC

    120-240 VAC

    Operating limits 85-110% Un

    Power on inrush (Pa)

    40 kA 50 kA

    DC: 600 W DC: 900 W

    AC: 600 VA AC: 900 VA Rated power (Pn) DC: 200 W DC: 350 W

    AC: 200 VA AC: 350 VA

    Charging time 6-7 s 6-7 s

    Insulating voltage 2000 V 50 Hz

    (for 1 min)

    Table 8. Auxiliary switch ratings

    Un Rated current (A) Breaking capacity (A)

    220 VAC 2.5 25

    24 VDC

    1 ms 10 12

    15 ms 10 12

    50 ms 8 10

    200 ms 6 7.7

    60 VDC1 ms 8 10

    15 ms 6 8

    50 ms 5 6

    200 ms 4 5.4

    110 VDC

    1 ms 6 8

    15 ms 4 5

    50 ms 2 4.6

    200 ms 1 2.2

    220 VDC

    1 ms 1.5 2

    15 ms 1 1.4

    50 ms 0.75 1.2

    200 ms 0.5 1

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    13/20Technical guide | ADVAC circuit breaker

    Table 9. Contact resistance

    Voltage

    Class

    FLC (Amps) Isc (kA) Type/Rating Contact

    Resistance

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    14/2014 ADVAC circuit breaker | Technical guide

    ADVAC. Circuit breaker specifiers guide.

    General

    The circuit breaker shall be an ABB ADVAC or approved equal

    three-pole drawout (or stationary) type breaker, electrically ope-

    rated, with manual or electric motor charging of a spring type

    stored energy operating mechanism. The breaker is intended

    for use as a General Purpose device in accordance with appli-

    cable ANSI standards applying to 5, 8.25, or 15 kV applications:

    ANSI C37.04, C37.06, and C37.09. The circuit breaker shall

    also conform to the general purpose capacitor switching ratings

    referenced in the ANSI standards.

    Option:

    Definite purpose capacitor switching ratings are optionallyoffered for single and back-to-back applications. Details of

    these applications are required at the time of quotation to insure

    conformance to specific applications.

    Drawout circuit breaker racking system and interlocks

    The circuit breaker shall be inserted and withdrawn by means of

    a racking system, which can be operated with the compartment

    door open or closed. The racking system shall provide smooth

    consistent racking, and shall secure the breaker from both sides

    of the cell in all racking positions. During racking, the breaker

    shall automatically open and close cell-mounted safety shutters

    to cover stationary primary contacts when the breaker is not inthe Connected position.

    The racking system shall have three distinct positions. In addi-

    tion to the withdrawn position (free movement): Disconnected

    (both primary and secondary contacts disengaged), Test (sec-

    ondary contacts engaged, primary contacts disconnected, and

    shutter closed), and Connected (shutter open, primary and

    secondary contacts engaged). Positive stops shall be provided

    for all three positions, with deliberate operator intervention re-

    quired to enable continued insertion or withdrawal of the circuit

    breaker from any position.

    The racking system and all moving parts of the breaker-cell

    interface, including the secondary disconnects, shutter actuator

    and ground contact, shall be capable of 500 complete rack-in/

    rack-out operations without maintenance.

    It shall not be possible to insert or withdraw a closed breaker,

    and the breaker shall not be allowed to close within a cell un-

    less it is in the Connected, Test, or Disconnected position.

    Electrical and mechanical blocking means shall be employed

    to preclude breaker contact closure in any position other then

    Connected, Test, or Disconnected. The springs in the

    stored energy device operating mechanism shall be automati-

    cally discharged prior to removing a circuit breaker from a com-

    partment (other than spring preload charges which do not have

    the capacity to operate the circuit breaker).

    Controls

    Opening and closing speed shall be independent of the opera-

    tor or of control voltage within the rated control voltage range.

    Circuit breaker charge, close and trip circuits shall be electrically

    separate, and control voltages for each circuit shall be indepen-

    dently selectable from the full range of ANSI preferred control

    voltages. Manual provisions shall be provided for closing,

    tripping and charging the breaker. These provisions shall beinstalled and easily accessible at the front of the breaker.

    All control components shall be front accessible for quick

    inspection after easy removal of the circuit breaker front cover.

    Mechanism operated cell switches shall not be allowed; the cir-

    cuit breaker shall include eight on-board auxiliary contacts (four

    normally open a and four normally closed b) for customer

    use, wired through the secondary disconnects. All breaker-

    mounted contacts shall operate in both the Connected and

    Test positions.

    Option:Nine additional contacts (for a total of nine normally open a

    and eight normally closed b) shall be installed on the circuit

    breaker and wired through the secondary disconnect, for a total

    of 17 on-board contacts.

    The breaker shall have flags to indicate open or closed posi-

    tion, and spring charge status. Only the correct status flag for

    any single function shall be visible. Pointer systems shall not be

    used to indicate status. Additionally, the breaker shall have a

    five-digit, non-resetting operation counter clearly visible from the

    front of the breaker. The operation counter shall advance when

    the breaker closes.All control devices shall be universal AC/DC, for AC or DC ap-

    plication flexibility with standard parts. All control components

    shall be front-accessible for inspections and easily removable

    for maintenance.

    Option:

    Dual open coils shall be supplied for breakers as noted on data

    sheets, and wired through separate secondary control sources

    for complete redundancy.

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    15/20Technical guide | ADVAC circuit breaker

    Option:

    A direct-acting undervoltage trip shall be supplied for breakers

    as noted on data sheets. The undervoltage trip shall operate

    when the control voltage drops to a predetermined value below

    the nominal control voltage.

    The EL actuator shall have a mechanical anti-pumping device

    mounted to prevent a continuous succession of close-open op-

    erations. The anti-pumping device allows the breaker to close

    if the operating mechanism spring is fully charged, the opening

    push button and/or shunt opening release are not activated,

    and the circuit breaker is open simultaneously.

    Current path

    Each primary lead assembly shall consist of a vacuum inter-

    rupter completely embedded in an epoxy resin casting. The

    epoxy casting shall encapsulate not only the vacuum interrupter,

    but also the upper and lower current carrying parts and current

    transfer assembly. The epoxy casting shall limit access to any

    moving parts, protecting them from dirt and debris. Epoxy en-

    capsulation shall be used on all 1200 and 2000 ampere circuit

    breakers. The 3000 ampere circuit breakers shall use individual

    ventilated pole assemblies that shield and protect the vacuum

    interrupters. Connecting directly to the pole pads, silver-plated

    copper upper and lower leads shall use tulip type self-aligningprimary disconnects. A dedicated ground contact shall be

    provided to engage the stationary ground contact in the circuit

    breaker compartment to ground the circuit breaker in all posi-

    tions from Disconnected through Connected.

    Maintenance and handling

    The operating mechanism shall be front accessible, and all

    routine maintenance shall be performed with the breaker in

    an upright position. Circuit breakers shall have self-contained

    wheels designed for easy insertion, removal and transport on

    flat indoor surfaces.

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    16/2016 ADVAC circuit breaker | Technical guide

    ADVAC. Outline drawings.

    493.2 [19.42]

    27 [1.06]

    [11.32]287.6

    [14.21]360.9

    82.9

    12.20

    [3.26]

    1.00ROLLER

    310

    25.4

    636.2 25.05

    587 23.11

    10.83275

    29.92760

    700 27.56

    275 10.83

    788 31.02

    OPEN "0"

    CLOSING

    OPENINGBUTTON

    COUNTER

    BUTTON

    CLOSE "I"

    MANUAL CLOSING

    INDICATOR

    SPRING CHARGELEVER

    SPRINGCHARGE

    INDICATOR

    27.88708

    31.10790

    772 30.39

    786 30.94

    PRIMARYCONTACTSTUD

    50.8 2.00

    287.6[11.32]

    587 23.11

    651.7 25.66

    760 29.92

    788 31.02[1.06]

    1.00

    360.9 [14.21]

    27

    25.4

    [3.26]82.9

    ROLLER

    493.2 [19.42]

    310 12.20

    INDICATOR

    SPRING CHARGE LEVER

    BUTTONOPENING

    BUTTONCLOSING

    MECHANICAL CLOSING

    CLOSE "I"OPEN "O"INDICATOR

    SPRING CHARGECOUNTER

    790 31.10

    [27.88]708

    30.94]786

    772 30.39PRIMARYCONTACTSTUD

    50.8 2.00 10.83275 275 10.83

    FRAME WIDTH

    U (kV) Ir (A) Isc (kA)

    4.76 1200 25-31.5

    15 1200 20-25-31.5

    U (kV) Ir (A) Isc (kA)

    4.76 2000 25-31.5-40

    8.25 2000 40

    15 2000 20-25-31.5-40

    15 2000 50

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    17/20Technical guide | ADVAC circuit breaker

    760 29.92

    69.8 2.75PRIMARY CONTACT

    STUD10.83275

    FRAME WIDTH

    275 10.83

    788 31.02

    12.20

    82.9

    [27.00]

    11.32

    [3.26]

    ROLLER

    287.6

    360.9 [14.21]

    1.0025.427 [1.06]

    686

    310

    587 23.11

    CLOSE "I"

    BUTTONOPENING

    BUTTON

    LEVER

    INDICATOR

    CLOSING

    COUNTER

    SPRING CHARGEMANUAL CLOSING

    CHARGESPRING

    OPEN "O"

    INDICATOR

    772 30.39

    708 27.88

    786 30.94

    790 31.10

    [11.32]287.6

    638.4 25.13

    760 29.92

    PRIMARYCONTACTSTUD50.8 2.00

    360.9 [14.21]

    23.11

    25.4

    493.2 [19.42]

    1.00

    82.9[3.26]

    27 [1.06]ROLLER

    587

    310 12.20

    OPENING

    BUTTON

    COUNTER

    SPRINGCHARGEINDICATOR

    OPEN "0"CLOSE "I"

    CLOSING

    BUTTON

    LEVER

    MANUAL CLOSINGSPRING CHARGE

    INDICATOR

    30.94786

    27.88708

    790 31.10

    772 30.39

    27.56700

    31.02788

    275 10.83275 10.83

    U (kV) Ir (A) Isc (kA)

    4.76 3000 25-31.5-40

    4.76 3000 50

    8.25 3000 40

    15 3000 20-25-31.5-40

    15 3000 50

    U (kV) Ir (A) Isc (kA)

    4.76 1200 40

    8.25 1200 40

    15 1200 40

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    18/2018 ADVAC circuit breaker | Technical guide

    644.16 25.36

    50.8 2.00PRIMARYCONTACTSTUD

    [11.32]287.6

    [3.26]82.9

    760 29.92

    493.2 [19.42]

    23.11587

    310

    ROLLER

    360.9 [14.21]

    12.20

    25.4 1.00

    27 [1.06]

    10.83275 10.83275

    750 29.53

    788 31.02

    CLOSING

    BUTTONOPENING

    OPEN "0"INDICATOR

    SPRING

    CLOSE "I"

    BUTTON

    CHARGEINDICATOR

    MANUAL CLOSINGSPRING CHARGELEVER

    COUNTER

    30.39772

    31.10790

    786[30.94]

    708.1 27.88

    50.8 2.00PRIMARY

    CONTACTSTUD

    788 31.02

    760 29.92

    [11.32]287.6

    CLOSINGBUTTON

    INDICATOR

    INDICATOR

    COUNTER

    LEVERSPRING CHARGEMANUAL CLOSING

    CLOSE "I"OPEN "O"

    BUTTONOPENING

    SPRINGCHARGE

    30.39772

    27.88

    786[30.94]

    708

    790 31.10

    10.83275

    750 29.53

    275 10.83

    493.2 [19.42]

    [14.21]360.9

    ROLLER

    23.11

    25.4 1.00

    587

    310 12.20

    27 [1.06]

    U (kV) Ir (A) Isc (kA)

    4.76 1200 50

    U (kV) Ir (A) Isc (kA)

    15 1200-2000 50

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    19/20Technical guide | ADVAC circuit breaker

    760 29.92

    [3.26]82.9

    685 26.97

    287.3 11.31

    OPEN "I"

    CHARGE

    COUNTER

    MANUAL CLOSINGSPRING CHARGELEVER

    OPENINGBUTTON

    CLOSINGBUTTON

    SPRING

    INDICATOR

    INDICATORCLOSE "0"

    27.88708

    30.39772

    786 30.94

    790 31.10

    10.83275

    29.53750

    275 10.83

    788 31.02

    PRIMARYCONTACT

    STUD69.9 2.75

    23.11587

    493.2 [19.42]

    310 12.20

    360.9 14.21

    27 [1.06]

    U (kV) Ir (A) Isc (kA)

    15 3000 50

  • 8/2/2019 ADVAC Technical Guide 1VAL050501-TG Rev A

    20/20

    Contact us

    ABB Inc.

    Medium Voltage OEM Apparatus

    655 Century Point

    Lake Mary, FL 32746

    Phone: +1 407 732 2000

    Customer service: +1 800 929 7947 ext. 5

    +1 407 732 2000 ext. 2510

    E-Mail: [email protected]

    ABB Inc.

    Low and Medium Voltage Service

    Florence, South Carolina

    Phone: +1 800 HELP 365 (option 7)+1 407 732 2000

    www.abb.com/mediumvoltage

    www.abb.us/mvservice

    Note:

    We reserve the right to make technical changes

    or modify the contents of this document without

    prior notice. With regard to purchase orders, the

    agreed particulars shall prevail. ABB does not

    accept any responsibility whatsoever for potential

    errors or possible lack of information in this docu-

    ment. We reserve all rights in this document and

    in the subject matter and illustrations contained

    therein. Any reproduction in whole or in parts

    is forbidden without ABBs prior written consent.

    Copyright 2011 ABB.

    All rights reserved.