Modulens EN
Gas fired floor-standing condensing boiler
AGC 1015AGC 15AGC 25AGC 35
User Guide
300026080-001-07
Contents
1 Safety instructions 411 General safety instructions 4
12 Recommendations 5
13 Liabilities 6131 Manufacturerrsquos liability 6132 Installerrsquos liability 7133 Userrsquos liability 7
2 About this manual 821 Symbols used 8
211 Symbols used in the manual 8212 Symbols used on the equipment 8
22 Abbreviations 9
3 Technical specifications 1031 Certifications 10
32 Technical specifications 10
4 Description 1241 Operating principle 12
411 Gasair setting 12412 Combustion 12
42 Main parts 13
43 Control panel 14431 Description of the keys 14432 Description of the display 15433 Browsing in the menus 17
5 Operating the appliance 1951 Putting the appliance into operation 19
52 Reading out measured values 19
53 Changing the settings 21531 Setting the set point temperatures 21532 Selecting the operating mode 21533 Forcing domestic hot water production 22534 Setting the contrast and lighting on the
display 23
1 15032016 - 300026080-001-07
535 Setting the time and date 23536 Selecting a timer programme 24537 Customising a timer programme 24
54 Installation shutdown 26
55 Antifreeze protection 26
6 Checking and maintenance 2861 General instructions 28
62 Periodic checks 28
7 Troubleshooting 3071 Anti-hunting 30
72 Messages (Code type Bxx or Mxx) 30
73 Faults (Code type Lxx or Dxx) 32
8 Energy savings 3881 Energy-saving advice 38
82 Recommendations 38
9 Warranty 3991 General 39
92 Warranty terms 39
10 Appendix ndash Information on the Ecodesign and Energy LabellingDirectives 40
Contents
2 15032016 - 300026080-001-07
3 15032016 - 300026080-001-07
1 Safety instructions
11 General safety instructions
DANGER
This appliance can be used by children agedfrom 8 years and above and persons withreduced physical sensory or mental capabilitiesor lack of experience and knowledge if they havebeen given supervision or instruction concerninguse of the appliance in a safe way andunderstand the hazards involved Children shallnot play with the appliance Cleaning and usermaintenance shall not be made by childrenwithout supervision
CAUTION
4 The use of the boiler and system by you asthe end-user must be limited to theoperations described in this User ManualAll other actions may only be undertaken bya qualified fitterengineer
4 Only qualified persons are authorised toassemble install and maintain theinstallation
DANGER
If you smell gas1 Do not use a naked flame do not smoke do
not operate electrical contacts or switches( doorbell light motor lift etc)
2 Shut off the gas supply3 Open the windows4 Evacuate the premises5 Call your fitter
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 4
DANGER
If you smell flue gases1 Switch the appliance off2 Open the windows3 Evacuate the premises4 Call your fitter
DANGER
The installation and maintenance of the boilermust be undertaken by a qualified fitterengineerin accordance with the information in thesupplied Installation and Service Manual doingotherwise may result in dangerous situationsandor bodily injury
WARNING
Depending on the settings of the appliance4 The temperature of the flue gas conduits
may exceed 60degC4 The temperature of the radiators may reach
85degC4 The temperature of the domestic hot water
may reach 65degC
CAUTION
Do not neglect to service the appliance4 For completely safe and optimum operation
you must have your boiler regularly servicedby an approved installer
12 Recommendations
WARNING
Only qualified professionals are authorised towork on the appliance and the installation
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
5 15032016 - 300026080-001-07
DANGER
For safety reasons we recommended fittingsmoke and CO alarms at suitable places in yourhome
4Regularly check the water pressure in the installation(minimum pressure 08 bar recommended pressurebetween 08 and 15 bar)
4Keep the appliance accessible at all times4Never remove or cover labels and rating plates affixed
to the appliance Labels and rating plates must belegible throughout the entire lifetime of the appliance
4The appliance should be on Summer or Antrifreezemode rather than switched off to guarantee thefollowing functions- Anti blocking of pumps- Antifreeze protection
13 Liabilities
131 Manufacturerrsquos liability
Our products are manufactured in compliance with therequirements of the various applicable European
Directives They are therefore delivered with [ markingand all relevant documentationIn the interest of customers we are continuouslyendeavouring to make improvements in product qualityAll the specifications stated in this document are thereforesubject to change without notice
Our liability as the manufacturer may not be invoked in thefollowing cases4Failure to abide by the instructions on using the
appliance4Faulty or insufficient maintenance of the appliance4Failure to abide by the instructions on installing the
appliance
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 6
132 Installerrsquos liability
The installer is responsible for the installation andcommissioning of the appliance The installer mustrespect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Carry out installation in compliance with the prevailing
legislation and standards4Perform the initial start up and carry out any checks
necessary4Explain the installation to the user4 If a maintenance is necessary warn the user of the
obligation to check the appliance and maintain it ingood working order
4Give all the instruction manuals to the user
133 Userrsquos liability
To guarantee optimum operation of the appliance theuser must respect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Call on qualified professionals to carry out installation
and initial start up4Get your installer to explain your installation to you4Ensure the Appliance is serviced in accordance with
the manufacturerrsquos instructions by a suitable qualifiedperson
4Keep the instruction manuals in good condition closeto the appliance
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
7 15032016 - 300026080-001-07
2 About this manual
21 Symbols used
211 Symbols used in the manual
In these instructions various danger levels are employed to draw theuserrsquos attention to particular information In so doing we wish tosafeguard the userrsquos safety highlight hazards and guarantee correctoperation of the appliance
DANGER
Risk of a dangerous situation causing serious physicalinjury
WARNING
Risk of a dangerous situation causing slight physicalinjury
CAUTION
Risk of material damage
Signals important information
frac14Signals a referral to other instructions or other pages in theinstructions
212 Symbols used on the equipment
4 Protective earthing~ Alternating current
Before installing and commissioning the device readcarefully the instruction manuals provided
Dispose of the used products in an appropriate recoveryand recycling structure
This appliance must be connected to the protective earth
D000241-C
AGC 1015 AGC 15 AGC 25 AGC 35 2 About this manual
15032016 - 300026080-001-07 8
Caution danger live partsDisconnect the mains power prior to any operations
22 Abbreviations
4 3CE Collective conduit for sealed boiler4 DHW Domestic hot water4 Interscenario switch Home automation switch that can be used
to centralise and control several scenarios4 Hi Lower heating value LHV (Nett)4 Hs Higher heating value HHV (Gross)4 PPS Polypropylene hardly inflammable4 PCU Primary Control Unit - PCB for managing burner operation4 PSU Parameter Storage Unit - Parameter storage for PCBs
PCU and SU4 SCU Secondary Control Unit - control panel PCB4 SU Safety Unit - Safety PCB4 3WV 3-way valve4 HL High Load - DHW tank with plate exchanger4 SL Standard Load - DHW tank with coil4 SHL Solar High Load - Solar DHW tank with plate exchanger4 SSL Solar Standard Load - Solar DHW tank with coil
1 2
M002628-A
2 About this manual AGC 1015 AGC 15 AGC 25 AGC 35
9 15032016 - 300026080-001-07
3 Technical specifications
31 Certifications
CE identification no CE-0085CM0178NOx classification 5 (EN 15502-1 EN 15502-2-1)Type of connection Chimney B23 B33
Flue gas outlet C13(x) C33(x) C43(x) C53 C83(x)C93(x)
32 Technical specifications
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35GeneralNominal output (Pn)Heating System (8060 degC)
minimum-maximum
kW 30 - 104 30 - 149 50 - 248 63 - 348
Nominal output (Pn)Heating System (5030 degC)
minimum-maximum
kW 34 - 112 34 - 158 56 - 255 70 - 359
Nominal output (Pn)Heating System (4030 degC)
minimum-maximum
kW 34 - 160 34 - 160 56 - 259 70 - 364
Nominal input (Qn)Heating System (Hi)
minimum-maximum
kW 31 - 105 31 - 150 52 - 250 65 - 351
Nominal input(Qn)Heating System (Hs)
minimum-maximum
kW 34 - 117 34 - 167 58 - 278 72 - 390
Nominal input (Qnw)DHW System (Hi)
minimum-maximum
kW 31 - 150 31 - 150 52 - 293 65 - 351
Nominal input (Qnw)DHW System (Hs)
minimum-maximum
kW 34 - 167 34 - 167 58 - 326 72 - 390
Heating efficiency under full load (Hi)(8060 degC)
- 993 993 992 991
Heating efficiency under full load (Hi)(5030 degC)
- 1070 1053 1020 1022
Heating efficiency under partial load(Hi) (Return temperature 60degC)
- 949 949 961 963
Heating efficiency under partial load(EN 9242) (Return temperature30degC)
- 1102 1102 1101 1106
Data on the gases and combustion gasesGas consumption - Natural gas H(G20)
minimum-maximum
m3h 033 - 159 033 - 159 055 - 310 069 - 371
Gas consumption - Natural gas L(G25)
minimum-maximum
m3h 038 - 185 038 - 185 064 - 361 080 - 432
Gas consumption - Propane G31 minimum-maximum
m3h 013 - 061 013 - 061 021 - 120 027 - 144
Mass flue gas flow rate minimum-maximum
kgh 53 - 252 53 - 252 89 - 493 111 - 573
AGC 1015 AGC 15 AGC 25 AGC 35 3 Technical specifications
15032016 - 300026080-001-07 10
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
Contents
1 Safety instructions 411 General safety instructions 4
12 Recommendations 5
13 Liabilities 6131 Manufacturerrsquos liability 6132 Installerrsquos liability 7133 Userrsquos liability 7
2 About this manual 821 Symbols used 8
211 Symbols used in the manual 8212 Symbols used on the equipment 8
22 Abbreviations 9
3 Technical specifications 1031 Certifications 10
32 Technical specifications 10
4 Description 1241 Operating principle 12
411 Gasair setting 12412 Combustion 12
42 Main parts 13
43 Control panel 14431 Description of the keys 14432 Description of the display 15433 Browsing in the menus 17
5 Operating the appliance 1951 Putting the appliance into operation 19
52 Reading out measured values 19
53 Changing the settings 21531 Setting the set point temperatures 21532 Selecting the operating mode 21533 Forcing domestic hot water production 22534 Setting the contrast and lighting on the
display 23
1 15032016 - 300026080-001-07
535 Setting the time and date 23536 Selecting a timer programme 24537 Customising a timer programme 24
54 Installation shutdown 26
55 Antifreeze protection 26
6 Checking and maintenance 2861 General instructions 28
62 Periodic checks 28
7 Troubleshooting 3071 Anti-hunting 30
72 Messages (Code type Bxx or Mxx) 30
73 Faults (Code type Lxx or Dxx) 32
8 Energy savings 3881 Energy-saving advice 38
82 Recommendations 38
9 Warranty 3991 General 39
92 Warranty terms 39
10 Appendix ndash Information on the Ecodesign and Energy LabellingDirectives 40
Contents
2 15032016 - 300026080-001-07
3 15032016 - 300026080-001-07
1 Safety instructions
11 General safety instructions
DANGER
This appliance can be used by children agedfrom 8 years and above and persons withreduced physical sensory or mental capabilitiesor lack of experience and knowledge if they havebeen given supervision or instruction concerninguse of the appliance in a safe way andunderstand the hazards involved Children shallnot play with the appliance Cleaning and usermaintenance shall not be made by childrenwithout supervision
CAUTION
4 The use of the boiler and system by you asthe end-user must be limited to theoperations described in this User ManualAll other actions may only be undertaken bya qualified fitterengineer
4 Only qualified persons are authorised toassemble install and maintain theinstallation
DANGER
If you smell gas1 Do not use a naked flame do not smoke do
not operate electrical contacts or switches( doorbell light motor lift etc)
2 Shut off the gas supply3 Open the windows4 Evacuate the premises5 Call your fitter
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 4
DANGER
If you smell flue gases1 Switch the appliance off2 Open the windows3 Evacuate the premises4 Call your fitter
DANGER
The installation and maintenance of the boilermust be undertaken by a qualified fitterengineerin accordance with the information in thesupplied Installation and Service Manual doingotherwise may result in dangerous situationsandor bodily injury
WARNING
Depending on the settings of the appliance4 The temperature of the flue gas conduits
may exceed 60degC4 The temperature of the radiators may reach
85degC4 The temperature of the domestic hot water
may reach 65degC
CAUTION
Do not neglect to service the appliance4 For completely safe and optimum operation
you must have your boiler regularly servicedby an approved installer
12 Recommendations
WARNING
Only qualified professionals are authorised towork on the appliance and the installation
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
5 15032016 - 300026080-001-07
DANGER
For safety reasons we recommended fittingsmoke and CO alarms at suitable places in yourhome
4Regularly check the water pressure in the installation(minimum pressure 08 bar recommended pressurebetween 08 and 15 bar)
4Keep the appliance accessible at all times4Never remove or cover labels and rating plates affixed
to the appliance Labels and rating plates must belegible throughout the entire lifetime of the appliance
4The appliance should be on Summer or Antrifreezemode rather than switched off to guarantee thefollowing functions- Anti blocking of pumps- Antifreeze protection
13 Liabilities
131 Manufacturerrsquos liability
Our products are manufactured in compliance with therequirements of the various applicable European
Directives They are therefore delivered with [ markingand all relevant documentationIn the interest of customers we are continuouslyendeavouring to make improvements in product qualityAll the specifications stated in this document are thereforesubject to change without notice
Our liability as the manufacturer may not be invoked in thefollowing cases4Failure to abide by the instructions on using the
appliance4Faulty or insufficient maintenance of the appliance4Failure to abide by the instructions on installing the
appliance
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 6
132 Installerrsquos liability
The installer is responsible for the installation andcommissioning of the appliance The installer mustrespect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Carry out installation in compliance with the prevailing
legislation and standards4Perform the initial start up and carry out any checks
necessary4Explain the installation to the user4 If a maintenance is necessary warn the user of the
obligation to check the appliance and maintain it ingood working order
4Give all the instruction manuals to the user
133 Userrsquos liability
To guarantee optimum operation of the appliance theuser must respect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Call on qualified professionals to carry out installation
and initial start up4Get your installer to explain your installation to you4Ensure the Appliance is serviced in accordance with
the manufacturerrsquos instructions by a suitable qualifiedperson
4Keep the instruction manuals in good condition closeto the appliance
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
7 15032016 - 300026080-001-07
2 About this manual
21 Symbols used
211 Symbols used in the manual
In these instructions various danger levels are employed to draw theuserrsquos attention to particular information In so doing we wish tosafeguard the userrsquos safety highlight hazards and guarantee correctoperation of the appliance
DANGER
Risk of a dangerous situation causing serious physicalinjury
WARNING
Risk of a dangerous situation causing slight physicalinjury
CAUTION
Risk of material damage
Signals important information
frac14Signals a referral to other instructions or other pages in theinstructions
212 Symbols used on the equipment
4 Protective earthing~ Alternating current
Before installing and commissioning the device readcarefully the instruction manuals provided
Dispose of the used products in an appropriate recoveryand recycling structure
This appliance must be connected to the protective earth
D000241-C
AGC 1015 AGC 15 AGC 25 AGC 35 2 About this manual
15032016 - 300026080-001-07 8
Caution danger live partsDisconnect the mains power prior to any operations
22 Abbreviations
4 3CE Collective conduit for sealed boiler4 DHW Domestic hot water4 Interscenario switch Home automation switch that can be used
to centralise and control several scenarios4 Hi Lower heating value LHV (Nett)4 Hs Higher heating value HHV (Gross)4 PPS Polypropylene hardly inflammable4 PCU Primary Control Unit - PCB for managing burner operation4 PSU Parameter Storage Unit - Parameter storage for PCBs
PCU and SU4 SCU Secondary Control Unit - control panel PCB4 SU Safety Unit - Safety PCB4 3WV 3-way valve4 HL High Load - DHW tank with plate exchanger4 SL Standard Load - DHW tank with coil4 SHL Solar High Load - Solar DHW tank with plate exchanger4 SSL Solar Standard Load - Solar DHW tank with coil
1 2
M002628-A
2 About this manual AGC 1015 AGC 15 AGC 25 AGC 35
9 15032016 - 300026080-001-07
3 Technical specifications
31 Certifications
CE identification no CE-0085CM0178NOx classification 5 (EN 15502-1 EN 15502-2-1)Type of connection Chimney B23 B33
Flue gas outlet C13(x) C33(x) C43(x) C53 C83(x)C93(x)
32 Technical specifications
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35GeneralNominal output (Pn)Heating System (8060 degC)
minimum-maximum
kW 30 - 104 30 - 149 50 - 248 63 - 348
Nominal output (Pn)Heating System (5030 degC)
minimum-maximum
kW 34 - 112 34 - 158 56 - 255 70 - 359
Nominal output (Pn)Heating System (4030 degC)
minimum-maximum
kW 34 - 160 34 - 160 56 - 259 70 - 364
Nominal input (Qn)Heating System (Hi)
minimum-maximum
kW 31 - 105 31 - 150 52 - 250 65 - 351
Nominal input(Qn)Heating System (Hs)
minimum-maximum
kW 34 - 117 34 - 167 58 - 278 72 - 390
Nominal input (Qnw)DHW System (Hi)
minimum-maximum
kW 31 - 150 31 - 150 52 - 293 65 - 351
Nominal input (Qnw)DHW System (Hs)
minimum-maximum
kW 34 - 167 34 - 167 58 - 326 72 - 390
Heating efficiency under full load (Hi)(8060 degC)
- 993 993 992 991
Heating efficiency under full load (Hi)(5030 degC)
- 1070 1053 1020 1022
Heating efficiency under partial load(Hi) (Return temperature 60degC)
- 949 949 961 963
Heating efficiency under partial load(EN 9242) (Return temperature30degC)
- 1102 1102 1101 1106
Data on the gases and combustion gasesGas consumption - Natural gas H(G20)
minimum-maximum
m3h 033 - 159 033 - 159 055 - 310 069 - 371
Gas consumption - Natural gas L(G25)
minimum-maximum
m3h 038 - 185 038 - 185 064 - 361 080 - 432
Gas consumption - Propane G31 minimum-maximum
m3h 013 - 061 013 - 061 021 - 120 027 - 144
Mass flue gas flow rate minimum-maximum
kgh 53 - 252 53 - 252 89 - 493 111 - 573
AGC 1015 AGC 15 AGC 25 AGC 35 3 Technical specifications
15032016 - 300026080-001-07 10
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
535 Setting the time and date 23536 Selecting a timer programme 24537 Customising a timer programme 24
54 Installation shutdown 26
55 Antifreeze protection 26
6 Checking and maintenance 2861 General instructions 28
62 Periodic checks 28
7 Troubleshooting 3071 Anti-hunting 30
72 Messages (Code type Bxx or Mxx) 30
73 Faults (Code type Lxx or Dxx) 32
8 Energy savings 3881 Energy-saving advice 38
82 Recommendations 38
9 Warranty 3991 General 39
92 Warranty terms 39
10 Appendix ndash Information on the Ecodesign and Energy LabellingDirectives 40
Contents
2 15032016 - 300026080-001-07
3 15032016 - 300026080-001-07
1 Safety instructions
11 General safety instructions
DANGER
This appliance can be used by children agedfrom 8 years and above and persons withreduced physical sensory or mental capabilitiesor lack of experience and knowledge if they havebeen given supervision or instruction concerninguse of the appliance in a safe way andunderstand the hazards involved Children shallnot play with the appliance Cleaning and usermaintenance shall not be made by childrenwithout supervision
CAUTION
4 The use of the boiler and system by you asthe end-user must be limited to theoperations described in this User ManualAll other actions may only be undertaken bya qualified fitterengineer
4 Only qualified persons are authorised toassemble install and maintain theinstallation
DANGER
If you smell gas1 Do not use a naked flame do not smoke do
not operate electrical contacts or switches( doorbell light motor lift etc)
2 Shut off the gas supply3 Open the windows4 Evacuate the premises5 Call your fitter
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 4
DANGER
If you smell flue gases1 Switch the appliance off2 Open the windows3 Evacuate the premises4 Call your fitter
DANGER
The installation and maintenance of the boilermust be undertaken by a qualified fitterengineerin accordance with the information in thesupplied Installation and Service Manual doingotherwise may result in dangerous situationsandor bodily injury
WARNING
Depending on the settings of the appliance4 The temperature of the flue gas conduits
may exceed 60degC4 The temperature of the radiators may reach
85degC4 The temperature of the domestic hot water
may reach 65degC
CAUTION
Do not neglect to service the appliance4 For completely safe and optimum operation
you must have your boiler regularly servicedby an approved installer
12 Recommendations
WARNING
Only qualified professionals are authorised towork on the appliance and the installation
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
5 15032016 - 300026080-001-07
DANGER
For safety reasons we recommended fittingsmoke and CO alarms at suitable places in yourhome
4Regularly check the water pressure in the installation(minimum pressure 08 bar recommended pressurebetween 08 and 15 bar)
4Keep the appliance accessible at all times4Never remove or cover labels and rating plates affixed
to the appliance Labels and rating plates must belegible throughout the entire lifetime of the appliance
4The appliance should be on Summer or Antrifreezemode rather than switched off to guarantee thefollowing functions- Anti blocking of pumps- Antifreeze protection
13 Liabilities
131 Manufacturerrsquos liability
Our products are manufactured in compliance with therequirements of the various applicable European
Directives They are therefore delivered with [ markingand all relevant documentationIn the interest of customers we are continuouslyendeavouring to make improvements in product qualityAll the specifications stated in this document are thereforesubject to change without notice
Our liability as the manufacturer may not be invoked in thefollowing cases4Failure to abide by the instructions on using the
appliance4Faulty or insufficient maintenance of the appliance4Failure to abide by the instructions on installing the
appliance
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 6
132 Installerrsquos liability
The installer is responsible for the installation andcommissioning of the appliance The installer mustrespect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Carry out installation in compliance with the prevailing
legislation and standards4Perform the initial start up and carry out any checks
necessary4Explain the installation to the user4 If a maintenance is necessary warn the user of the
obligation to check the appliance and maintain it ingood working order
4Give all the instruction manuals to the user
133 Userrsquos liability
To guarantee optimum operation of the appliance theuser must respect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Call on qualified professionals to carry out installation
and initial start up4Get your installer to explain your installation to you4Ensure the Appliance is serviced in accordance with
the manufacturerrsquos instructions by a suitable qualifiedperson
4Keep the instruction manuals in good condition closeto the appliance
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
7 15032016 - 300026080-001-07
2 About this manual
21 Symbols used
211 Symbols used in the manual
In these instructions various danger levels are employed to draw theuserrsquos attention to particular information In so doing we wish tosafeguard the userrsquos safety highlight hazards and guarantee correctoperation of the appliance
DANGER
Risk of a dangerous situation causing serious physicalinjury
WARNING
Risk of a dangerous situation causing slight physicalinjury
CAUTION
Risk of material damage
Signals important information
frac14Signals a referral to other instructions or other pages in theinstructions
212 Symbols used on the equipment
4 Protective earthing~ Alternating current
Before installing and commissioning the device readcarefully the instruction manuals provided
Dispose of the used products in an appropriate recoveryand recycling structure
This appliance must be connected to the protective earth
D000241-C
AGC 1015 AGC 15 AGC 25 AGC 35 2 About this manual
15032016 - 300026080-001-07 8
Caution danger live partsDisconnect the mains power prior to any operations
22 Abbreviations
4 3CE Collective conduit for sealed boiler4 DHW Domestic hot water4 Interscenario switch Home automation switch that can be used
to centralise and control several scenarios4 Hi Lower heating value LHV (Nett)4 Hs Higher heating value HHV (Gross)4 PPS Polypropylene hardly inflammable4 PCU Primary Control Unit - PCB for managing burner operation4 PSU Parameter Storage Unit - Parameter storage for PCBs
PCU and SU4 SCU Secondary Control Unit - control panel PCB4 SU Safety Unit - Safety PCB4 3WV 3-way valve4 HL High Load - DHW tank with plate exchanger4 SL Standard Load - DHW tank with coil4 SHL Solar High Load - Solar DHW tank with plate exchanger4 SSL Solar Standard Load - Solar DHW tank with coil
1 2
M002628-A
2 About this manual AGC 1015 AGC 15 AGC 25 AGC 35
9 15032016 - 300026080-001-07
3 Technical specifications
31 Certifications
CE identification no CE-0085CM0178NOx classification 5 (EN 15502-1 EN 15502-2-1)Type of connection Chimney B23 B33
Flue gas outlet C13(x) C33(x) C43(x) C53 C83(x)C93(x)
32 Technical specifications
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35GeneralNominal output (Pn)Heating System (8060 degC)
minimum-maximum
kW 30 - 104 30 - 149 50 - 248 63 - 348
Nominal output (Pn)Heating System (5030 degC)
minimum-maximum
kW 34 - 112 34 - 158 56 - 255 70 - 359
Nominal output (Pn)Heating System (4030 degC)
minimum-maximum
kW 34 - 160 34 - 160 56 - 259 70 - 364
Nominal input (Qn)Heating System (Hi)
minimum-maximum
kW 31 - 105 31 - 150 52 - 250 65 - 351
Nominal input(Qn)Heating System (Hs)
minimum-maximum
kW 34 - 117 34 - 167 58 - 278 72 - 390
Nominal input (Qnw)DHW System (Hi)
minimum-maximum
kW 31 - 150 31 - 150 52 - 293 65 - 351
Nominal input (Qnw)DHW System (Hs)
minimum-maximum
kW 34 - 167 34 - 167 58 - 326 72 - 390
Heating efficiency under full load (Hi)(8060 degC)
- 993 993 992 991
Heating efficiency under full load (Hi)(5030 degC)
- 1070 1053 1020 1022
Heating efficiency under partial load(Hi) (Return temperature 60degC)
- 949 949 961 963
Heating efficiency under partial load(EN 9242) (Return temperature30degC)
- 1102 1102 1101 1106
Data on the gases and combustion gasesGas consumption - Natural gas H(G20)
minimum-maximum
m3h 033 - 159 033 - 159 055 - 310 069 - 371
Gas consumption - Natural gas L(G25)
minimum-maximum
m3h 038 - 185 038 - 185 064 - 361 080 - 432
Gas consumption - Propane G31 minimum-maximum
m3h 013 - 061 013 - 061 021 - 120 027 - 144
Mass flue gas flow rate minimum-maximum
kgh 53 - 252 53 - 252 89 - 493 111 - 573
AGC 1015 AGC 15 AGC 25 AGC 35 3 Technical specifications
15032016 - 300026080-001-07 10
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
3 15032016 - 300026080-001-07
1 Safety instructions
11 General safety instructions
DANGER
This appliance can be used by children agedfrom 8 years and above and persons withreduced physical sensory or mental capabilitiesor lack of experience and knowledge if they havebeen given supervision or instruction concerninguse of the appliance in a safe way andunderstand the hazards involved Children shallnot play with the appliance Cleaning and usermaintenance shall not be made by childrenwithout supervision
CAUTION
4 The use of the boiler and system by you asthe end-user must be limited to theoperations described in this User ManualAll other actions may only be undertaken bya qualified fitterengineer
4 Only qualified persons are authorised toassemble install and maintain theinstallation
DANGER
If you smell gas1 Do not use a naked flame do not smoke do
not operate electrical contacts or switches( doorbell light motor lift etc)
2 Shut off the gas supply3 Open the windows4 Evacuate the premises5 Call your fitter
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 4
DANGER
If you smell flue gases1 Switch the appliance off2 Open the windows3 Evacuate the premises4 Call your fitter
DANGER
The installation and maintenance of the boilermust be undertaken by a qualified fitterengineerin accordance with the information in thesupplied Installation and Service Manual doingotherwise may result in dangerous situationsandor bodily injury
WARNING
Depending on the settings of the appliance4 The temperature of the flue gas conduits
may exceed 60degC4 The temperature of the radiators may reach
85degC4 The temperature of the domestic hot water
may reach 65degC
CAUTION
Do not neglect to service the appliance4 For completely safe and optimum operation
you must have your boiler regularly servicedby an approved installer
12 Recommendations
WARNING
Only qualified professionals are authorised towork on the appliance and the installation
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
5 15032016 - 300026080-001-07
DANGER
For safety reasons we recommended fittingsmoke and CO alarms at suitable places in yourhome
4Regularly check the water pressure in the installation(minimum pressure 08 bar recommended pressurebetween 08 and 15 bar)
4Keep the appliance accessible at all times4Never remove or cover labels and rating plates affixed
to the appliance Labels and rating plates must belegible throughout the entire lifetime of the appliance
4The appliance should be on Summer or Antrifreezemode rather than switched off to guarantee thefollowing functions- Anti blocking of pumps- Antifreeze protection
13 Liabilities
131 Manufacturerrsquos liability
Our products are manufactured in compliance with therequirements of the various applicable European
Directives They are therefore delivered with [ markingand all relevant documentationIn the interest of customers we are continuouslyendeavouring to make improvements in product qualityAll the specifications stated in this document are thereforesubject to change without notice
Our liability as the manufacturer may not be invoked in thefollowing cases4Failure to abide by the instructions on using the
appliance4Faulty or insufficient maintenance of the appliance4Failure to abide by the instructions on installing the
appliance
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 6
132 Installerrsquos liability
The installer is responsible for the installation andcommissioning of the appliance The installer mustrespect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Carry out installation in compliance with the prevailing
legislation and standards4Perform the initial start up and carry out any checks
necessary4Explain the installation to the user4 If a maintenance is necessary warn the user of the
obligation to check the appliance and maintain it ingood working order
4Give all the instruction manuals to the user
133 Userrsquos liability
To guarantee optimum operation of the appliance theuser must respect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Call on qualified professionals to carry out installation
and initial start up4Get your installer to explain your installation to you4Ensure the Appliance is serviced in accordance with
the manufacturerrsquos instructions by a suitable qualifiedperson
4Keep the instruction manuals in good condition closeto the appliance
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
7 15032016 - 300026080-001-07
2 About this manual
21 Symbols used
211 Symbols used in the manual
In these instructions various danger levels are employed to draw theuserrsquos attention to particular information In so doing we wish tosafeguard the userrsquos safety highlight hazards and guarantee correctoperation of the appliance
DANGER
Risk of a dangerous situation causing serious physicalinjury
WARNING
Risk of a dangerous situation causing slight physicalinjury
CAUTION
Risk of material damage
Signals important information
frac14Signals a referral to other instructions or other pages in theinstructions
212 Symbols used on the equipment
4 Protective earthing~ Alternating current
Before installing and commissioning the device readcarefully the instruction manuals provided
Dispose of the used products in an appropriate recoveryand recycling structure
This appliance must be connected to the protective earth
D000241-C
AGC 1015 AGC 15 AGC 25 AGC 35 2 About this manual
15032016 - 300026080-001-07 8
Caution danger live partsDisconnect the mains power prior to any operations
22 Abbreviations
4 3CE Collective conduit for sealed boiler4 DHW Domestic hot water4 Interscenario switch Home automation switch that can be used
to centralise and control several scenarios4 Hi Lower heating value LHV (Nett)4 Hs Higher heating value HHV (Gross)4 PPS Polypropylene hardly inflammable4 PCU Primary Control Unit - PCB for managing burner operation4 PSU Parameter Storage Unit - Parameter storage for PCBs
PCU and SU4 SCU Secondary Control Unit - control panel PCB4 SU Safety Unit - Safety PCB4 3WV 3-way valve4 HL High Load - DHW tank with plate exchanger4 SL Standard Load - DHW tank with coil4 SHL Solar High Load - Solar DHW tank with plate exchanger4 SSL Solar Standard Load - Solar DHW tank with coil
1 2
M002628-A
2 About this manual AGC 1015 AGC 15 AGC 25 AGC 35
9 15032016 - 300026080-001-07
3 Technical specifications
31 Certifications
CE identification no CE-0085CM0178NOx classification 5 (EN 15502-1 EN 15502-2-1)Type of connection Chimney B23 B33
Flue gas outlet C13(x) C33(x) C43(x) C53 C83(x)C93(x)
32 Technical specifications
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35GeneralNominal output (Pn)Heating System (8060 degC)
minimum-maximum
kW 30 - 104 30 - 149 50 - 248 63 - 348
Nominal output (Pn)Heating System (5030 degC)
minimum-maximum
kW 34 - 112 34 - 158 56 - 255 70 - 359
Nominal output (Pn)Heating System (4030 degC)
minimum-maximum
kW 34 - 160 34 - 160 56 - 259 70 - 364
Nominal input (Qn)Heating System (Hi)
minimum-maximum
kW 31 - 105 31 - 150 52 - 250 65 - 351
Nominal input(Qn)Heating System (Hs)
minimum-maximum
kW 34 - 117 34 - 167 58 - 278 72 - 390
Nominal input (Qnw)DHW System (Hi)
minimum-maximum
kW 31 - 150 31 - 150 52 - 293 65 - 351
Nominal input (Qnw)DHW System (Hs)
minimum-maximum
kW 34 - 167 34 - 167 58 - 326 72 - 390
Heating efficiency under full load (Hi)(8060 degC)
- 993 993 992 991
Heating efficiency under full load (Hi)(5030 degC)
- 1070 1053 1020 1022
Heating efficiency under partial load(Hi) (Return temperature 60degC)
- 949 949 961 963
Heating efficiency under partial load(EN 9242) (Return temperature30degC)
- 1102 1102 1101 1106
Data on the gases and combustion gasesGas consumption - Natural gas H(G20)
minimum-maximum
m3h 033 - 159 033 - 159 055 - 310 069 - 371
Gas consumption - Natural gas L(G25)
minimum-maximum
m3h 038 - 185 038 - 185 064 - 361 080 - 432
Gas consumption - Propane G31 minimum-maximum
m3h 013 - 061 013 - 061 021 - 120 027 - 144
Mass flue gas flow rate minimum-maximum
kgh 53 - 252 53 - 252 89 - 493 111 - 573
AGC 1015 AGC 15 AGC 25 AGC 35 3 Technical specifications
15032016 - 300026080-001-07 10
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
1 Safety instructions
11 General safety instructions
DANGER
This appliance can be used by children agedfrom 8 years and above and persons withreduced physical sensory or mental capabilitiesor lack of experience and knowledge if they havebeen given supervision or instruction concerninguse of the appliance in a safe way andunderstand the hazards involved Children shallnot play with the appliance Cleaning and usermaintenance shall not be made by childrenwithout supervision
CAUTION
4 The use of the boiler and system by you asthe end-user must be limited to theoperations described in this User ManualAll other actions may only be undertaken bya qualified fitterengineer
4 Only qualified persons are authorised toassemble install and maintain theinstallation
DANGER
If you smell gas1 Do not use a naked flame do not smoke do
not operate electrical contacts or switches( doorbell light motor lift etc)
2 Shut off the gas supply3 Open the windows4 Evacuate the premises5 Call your fitter
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 4
DANGER
If you smell flue gases1 Switch the appliance off2 Open the windows3 Evacuate the premises4 Call your fitter
DANGER
The installation and maintenance of the boilermust be undertaken by a qualified fitterengineerin accordance with the information in thesupplied Installation and Service Manual doingotherwise may result in dangerous situationsandor bodily injury
WARNING
Depending on the settings of the appliance4 The temperature of the flue gas conduits
may exceed 60degC4 The temperature of the radiators may reach
85degC4 The temperature of the domestic hot water
may reach 65degC
CAUTION
Do not neglect to service the appliance4 For completely safe and optimum operation
you must have your boiler regularly servicedby an approved installer
12 Recommendations
WARNING
Only qualified professionals are authorised towork on the appliance and the installation
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
5 15032016 - 300026080-001-07
DANGER
For safety reasons we recommended fittingsmoke and CO alarms at suitable places in yourhome
4Regularly check the water pressure in the installation(minimum pressure 08 bar recommended pressurebetween 08 and 15 bar)
4Keep the appliance accessible at all times4Never remove or cover labels and rating plates affixed
to the appliance Labels and rating plates must belegible throughout the entire lifetime of the appliance
4The appliance should be on Summer or Antrifreezemode rather than switched off to guarantee thefollowing functions- Anti blocking of pumps- Antifreeze protection
13 Liabilities
131 Manufacturerrsquos liability
Our products are manufactured in compliance with therequirements of the various applicable European
Directives They are therefore delivered with [ markingand all relevant documentationIn the interest of customers we are continuouslyendeavouring to make improvements in product qualityAll the specifications stated in this document are thereforesubject to change without notice
Our liability as the manufacturer may not be invoked in thefollowing cases4Failure to abide by the instructions on using the
appliance4Faulty or insufficient maintenance of the appliance4Failure to abide by the instructions on installing the
appliance
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 6
132 Installerrsquos liability
The installer is responsible for the installation andcommissioning of the appliance The installer mustrespect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Carry out installation in compliance with the prevailing
legislation and standards4Perform the initial start up and carry out any checks
necessary4Explain the installation to the user4 If a maintenance is necessary warn the user of the
obligation to check the appliance and maintain it ingood working order
4Give all the instruction manuals to the user
133 Userrsquos liability
To guarantee optimum operation of the appliance theuser must respect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Call on qualified professionals to carry out installation
and initial start up4Get your installer to explain your installation to you4Ensure the Appliance is serviced in accordance with
the manufacturerrsquos instructions by a suitable qualifiedperson
4Keep the instruction manuals in good condition closeto the appliance
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
7 15032016 - 300026080-001-07
2 About this manual
21 Symbols used
211 Symbols used in the manual
In these instructions various danger levels are employed to draw theuserrsquos attention to particular information In so doing we wish tosafeguard the userrsquos safety highlight hazards and guarantee correctoperation of the appliance
DANGER
Risk of a dangerous situation causing serious physicalinjury
WARNING
Risk of a dangerous situation causing slight physicalinjury
CAUTION
Risk of material damage
Signals important information
frac14Signals a referral to other instructions or other pages in theinstructions
212 Symbols used on the equipment
4 Protective earthing~ Alternating current
Before installing and commissioning the device readcarefully the instruction manuals provided
Dispose of the used products in an appropriate recoveryand recycling structure
This appliance must be connected to the protective earth
D000241-C
AGC 1015 AGC 15 AGC 25 AGC 35 2 About this manual
15032016 - 300026080-001-07 8
Caution danger live partsDisconnect the mains power prior to any operations
22 Abbreviations
4 3CE Collective conduit for sealed boiler4 DHW Domestic hot water4 Interscenario switch Home automation switch that can be used
to centralise and control several scenarios4 Hi Lower heating value LHV (Nett)4 Hs Higher heating value HHV (Gross)4 PPS Polypropylene hardly inflammable4 PCU Primary Control Unit - PCB for managing burner operation4 PSU Parameter Storage Unit - Parameter storage for PCBs
PCU and SU4 SCU Secondary Control Unit - control panel PCB4 SU Safety Unit - Safety PCB4 3WV 3-way valve4 HL High Load - DHW tank with plate exchanger4 SL Standard Load - DHW tank with coil4 SHL Solar High Load - Solar DHW tank with plate exchanger4 SSL Solar Standard Load - Solar DHW tank with coil
1 2
M002628-A
2 About this manual AGC 1015 AGC 15 AGC 25 AGC 35
9 15032016 - 300026080-001-07
3 Technical specifications
31 Certifications
CE identification no CE-0085CM0178NOx classification 5 (EN 15502-1 EN 15502-2-1)Type of connection Chimney B23 B33
Flue gas outlet C13(x) C33(x) C43(x) C53 C83(x)C93(x)
32 Technical specifications
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35GeneralNominal output (Pn)Heating System (8060 degC)
minimum-maximum
kW 30 - 104 30 - 149 50 - 248 63 - 348
Nominal output (Pn)Heating System (5030 degC)
minimum-maximum
kW 34 - 112 34 - 158 56 - 255 70 - 359
Nominal output (Pn)Heating System (4030 degC)
minimum-maximum
kW 34 - 160 34 - 160 56 - 259 70 - 364
Nominal input (Qn)Heating System (Hi)
minimum-maximum
kW 31 - 105 31 - 150 52 - 250 65 - 351
Nominal input(Qn)Heating System (Hs)
minimum-maximum
kW 34 - 117 34 - 167 58 - 278 72 - 390
Nominal input (Qnw)DHW System (Hi)
minimum-maximum
kW 31 - 150 31 - 150 52 - 293 65 - 351
Nominal input (Qnw)DHW System (Hs)
minimum-maximum
kW 34 - 167 34 - 167 58 - 326 72 - 390
Heating efficiency under full load (Hi)(8060 degC)
- 993 993 992 991
Heating efficiency under full load (Hi)(5030 degC)
- 1070 1053 1020 1022
Heating efficiency under partial load(Hi) (Return temperature 60degC)
- 949 949 961 963
Heating efficiency under partial load(EN 9242) (Return temperature30degC)
- 1102 1102 1101 1106
Data on the gases and combustion gasesGas consumption - Natural gas H(G20)
minimum-maximum
m3h 033 - 159 033 - 159 055 - 310 069 - 371
Gas consumption - Natural gas L(G25)
minimum-maximum
m3h 038 - 185 038 - 185 064 - 361 080 - 432
Gas consumption - Propane G31 minimum-maximum
m3h 013 - 061 013 - 061 021 - 120 027 - 144
Mass flue gas flow rate minimum-maximum
kgh 53 - 252 53 - 252 89 - 493 111 - 573
AGC 1015 AGC 15 AGC 25 AGC 35 3 Technical specifications
15032016 - 300026080-001-07 10
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
DANGER
If you smell flue gases1 Switch the appliance off2 Open the windows3 Evacuate the premises4 Call your fitter
DANGER
The installation and maintenance of the boilermust be undertaken by a qualified fitterengineerin accordance with the information in thesupplied Installation and Service Manual doingotherwise may result in dangerous situationsandor bodily injury
WARNING
Depending on the settings of the appliance4 The temperature of the flue gas conduits
may exceed 60degC4 The temperature of the radiators may reach
85degC4 The temperature of the domestic hot water
may reach 65degC
CAUTION
Do not neglect to service the appliance4 For completely safe and optimum operation
you must have your boiler regularly servicedby an approved installer
12 Recommendations
WARNING
Only qualified professionals are authorised towork on the appliance and the installation
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
5 15032016 - 300026080-001-07
DANGER
For safety reasons we recommended fittingsmoke and CO alarms at suitable places in yourhome
4Regularly check the water pressure in the installation(minimum pressure 08 bar recommended pressurebetween 08 and 15 bar)
4Keep the appliance accessible at all times4Never remove or cover labels and rating plates affixed
to the appliance Labels and rating plates must belegible throughout the entire lifetime of the appliance
4The appliance should be on Summer or Antrifreezemode rather than switched off to guarantee thefollowing functions- Anti blocking of pumps- Antifreeze protection
13 Liabilities
131 Manufacturerrsquos liability
Our products are manufactured in compliance with therequirements of the various applicable European
Directives They are therefore delivered with [ markingand all relevant documentationIn the interest of customers we are continuouslyendeavouring to make improvements in product qualityAll the specifications stated in this document are thereforesubject to change without notice
Our liability as the manufacturer may not be invoked in thefollowing cases4Failure to abide by the instructions on using the
appliance4Faulty or insufficient maintenance of the appliance4Failure to abide by the instructions on installing the
appliance
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 6
132 Installerrsquos liability
The installer is responsible for the installation andcommissioning of the appliance The installer mustrespect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Carry out installation in compliance with the prevailing
legislation and standards4Perform the initial start up and carry out any checks
necessary4Explain the installation to the user4 If a maintenance is necessary warn the user of the
obligation to check the appliance and maintain it ingood working order
4Give all the instruction manuals to the user
133 Userrsquos liability
To guarantee optimum operation of the appliance theuser must respect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Call on qualified professionals to carry out installation
and initial start up4Get your installer to explain your installation to you4Ensure the Appliance is serviced in accordance with
the manufacturerrsquos instructions by a suitable qualifiedperson
4Keep the instruction manuals in good condition closeto the appliance
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
7 15032016 - 300026080-001-07
2 About this manual
21 Symbols used
211 Symbols used in the manual
In these instructions various danger levels are employed to draw theuserrsquos attention to particular information In so doing we wish tosafeguard the userrsquos safety highlight hazards and guarantee correctoperation of the appliance
DANGER
Risk of a dangerous situation causing serious physicalinjury
WARNING
Risk of a dangerous situation causing slight physicalinjury
CAUTION
Risk of material damage
Signals important information
frac14Signals a referral to other instructions or other pages in theinstructions
212 Symbols used on the equipment
4 Protective earthing~ Alternating current
Before installing and commissioning the device readcarefully the instruction manuals provided
Dispose of the used products in an appropriate recoveryand recycling structure
This appliance must be connected to the protective earth
D000241-C
AGC 1015 AGC 15 AGC 25 AGC 35 2 About this manual
15032016 - 300026080-001-07 8
Caution danger live partsDisconnect the mains power prior to any operations
22 Abbreviations
4 3CE Collective conduit for sealed boiler4 DHW Domestic hot water4 Interscenario switch Home automation switch that can be used
to centralise and control several scenarios4 Hi Lower heating value LHV (Nett)4 Hs Higher heating value HHV (Gross)4 PPS Polypropylene hardly inflammable4 PCU Primary Control Unit - PCB for managing burner operation4 PSU Parameter Storage Unit - Parameter storage for PCBs
PCU and SU4 SCU Secondary Control Unit - control panel PCB4 SU Safety Unit - Safety PCB4 3WV 3-way valve4 HL High Load - DHW tank with plate exchanger4 SL Standard Load - DHW tank with coil4 SHL Solar High Load - Solar DHW tank with plate exchanger4 SSL Solar Standard Load - Solar DHW tank with coil
1 2
M002628-A
2 About this manual AGC 1015 AGC 15 AGC 25 AGC 35
9 15032016 - 300026080-001-07
3 Technical specifications
31 Certifications
CE identification no CE-0085CM0178NOx classification 5 (EN 15502-1 EN 15502-2-1)Type of connection Chimney B23 B33
Flue gas outlet C13(x) C33(x) C43(x) C53 C83(x)C93(x)
32 Technical specifications
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35GeneralNominal output (Pn)Heating System (8060 degC)
minimum-maximum
kW 30 - 104 30 - 149 50 - 248 63 - 348
Nominal output (Pn)Heating System (5030 degC)
minimum-maximum
kW 34 - 112 34 - 158 56 - 255 70 - 359
Nominal output (Pn)Heating System (4030 degC)
minimum-maximum
kW 34 - 160 34 - 160 56 - 259 70 - 364
Nominal input (Qn)Heating System (Hi)
minimum-maximum
kW 31 - 105 31 - 150 52 - 250 65 - 351
Nominal input(Qn)Heating System (Hs)
minimum-maximum
kW 34 - 117 34 - 167 58 - 278 72 - 390
Nominal input (Qnw)DHW System (Hi)
minimum-maximum
kW 31 - 150 31 - 150 52 - 293 65 - 351
Nominal input (Qnw)DHW System (Hs)
minimum-maximum
kW 34 - 167 34 - 167 58 - 326 72 - 390
Heating efficiency under full load (Hi)(8060 degC)
- 993 993 992 991
Heating efficiency under full load (Hi)(5030 degC)
- 1070 1053 1020 1022
Heating efficiency under partial load(Hi) (Return temperature 60degC)
- 949 949 961 963
Heating efficiency under partial load(EN 9242) (Return temperature30degC)
- 1102 1102 1101 1106
Data on the gases and combustion gasesGas consumption - Natural gas H(G20)
minimum-maximum
m3h 033 - 159 033 - 159 055 - 310 069 - 371
Gas consumption - Natural gas L(G25)
minimum-maximum
m3h 038 - 185 038 - 185 064 - 361 080 - 432
Gas consumption - Propane G31 minimum-maximum
m3h 013 - 061 013 - 061 021 - 120 027 - 144
Mass flue gas flow rate minimum-maximum
kgh 53 - 252 53 - 252 89 - 493 111 - 573
AGC 1015 AGC 15 AGC 25 AGC 35 3 Technical specifications
15032016 - 300026080-001-07 10
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
DANGER
For safety reasons we recommended fittingsmoke and CO alarms at suitable places in yourhome
4Regularly check the water pressure in the installation(minimum pressure 08 bar recommended pressurebetween 08 and 15 bar)
4Keep the appliance accessible at all times4Never remove or cover labels and rating plates affixed
to the appliance Labels and rating plates must belegible throughout the entire lifetime of the appliance
4The appliance should be on Summer or Antrifreezemode rather than switched off to guarantee thefollowing functions- Anti blocking of pumps- Antifreeze protection
13 Liabilities
131 Manufacturerrsquos liability
Our products are manufactured in compliance with therequirements of the various applicable European
Directives They are therefore delivered with [ markingand all relevant documentationIn the interest of customers we are continuouslyendeavouring to make improvements in product qualityAll the specifications stated in this document are thereforesubject to change without notice
Our liability as the manufacturer may not be invoked in thefollowing cases4Failure to abide by the instructions on using the
appliance4Faulty or insufficient maintenance of the appliance4Failure to abide by the instructions on installing the
appliance
AGC 1015 AGC 15 AGC 25 AGC 35 1 Safety instructions
15032016 - 300026080-001-07 6
132 Installerrsquos liability
The installer is responsible for the installation andcommissioning of the appliance The installer mustrespect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Carry out installation in compliance with the prevailing
legislation and standards4Perform the initial start up and carry out any checks
necessary4Explain the installation to the user4 If a maintenance is necessary warn the user of the
obligation to check the appliance and maintain it ingood working order
4Give all the instruction manuals to the user
133 Userrsquos liability
To guarantee optimum operation of the appliance theuser must respect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Call on qualified professionals to carry out installation
and initial start up4Get your installer to explain your installation to you4Ensure the Appliance is serviced in accordance with
the manufacturerrsquos instructions by a suitable qualifiedperson
4Keep the instruction manuals in good condition closeto the appliance
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
7 15032016 - 300026080-001-07
2 About this manual
21 Symbols used
211 Symbols used in the manual
In these instructions various danger levels are employed to draw theuserrsquos attention to particular information In so doing we wish tosafeguard the userrsquos safety highlight hazards and guarantee correctoperation of the appliance
DANGER
Risk of a dangerous situation causing serious physicalinjury
WARNING
Risk of a dangerous situation causing slight physicalinjury
CAUTION
Risk of material damage
Signals important information
frac14Signals a referral to other instructions or other pages in theinstructions
212 Symbols used on the equipment
4 Protective earthing~ Alternating current
Before installing and commissioning the device readcarefully the instruction manuals provided
Dispose of the used products in an appropriate recoveryand recycling structure
This appliance must be connected to the protective earth
D000241-C
AGC 1015 AGC 15 AGC 25 AGC 35 2 About this manual
15032016 - 300026080-001-07 8
Caution danger live partsDisconnect the mains power prior to any operations
22 Abbreviations
4 3CE Collective conduit for sealed boiler4 DHW Domestic hot water4 Interscenario switch Home automation switch that can be used
to centralise and control several scenarios4 Hi Lower heating value LHV (Nett)4 Hs Higher heating value HHV (Gross)4 PPS Polypropylene hardly inflammable4 PCU Primary Control Unit - PCB for managing burner operation4 PSU Parameter Storage Unit - Parameter storage for PCBs
PCU and SU4 SCU Secondary Control Unit - control panel PCB4 SU Safety Unit - Safety PCB4 3WV 3-way valve4 HL High Load - DHW tank with plate exchanger4 SL Standard Load - DHW tank with coil4 SHL Solar High Load - Solar DHW tank with plate exchanger4 SSL Solar Standard Load - Solar DHW tank with coil
1 2
M002628-A
2 About this manual AGC 1015 AGC 15 AGC 25 AGC 35
9 15032016 - 300026080-001-07
3 Technical specifications
31 Certifications
CE identification no CE-0085CM0178NOx classification 5 (EN 15502-1 EN 15502-2-1)Type of connection Chimney B23 B33
Flue gas outlet C13(x) C33(x) C43(x) C53 C83(x)C93(x)
32 Technical specifications
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35GeneralNominal output (Pn)Heating System (8060 degC)
minimum-maximum
kW 30 - 104 30 - 149 50 - 248 63 - 348
Nominal output (Pn)Heating System (5030 degC)
minimum-maximum
kW 34 - 112 34 - 158 56 - 255 70 - 359
Nominal output (Pn)Heating System (4030 degC)
minimum-maximum
kW 34 - 160 34 - 160 56 - 259 70 - 364
Nominal input (Qn)Heating System (Hi)
minimum-maximum
kW 31 - 105 31 - 150 52 - 250 65 - 351
Nominal input(Qn)Heating System (Hs)
minimum-maximum
kW 34 - 117 34 - 167 58 - 278 72 - 390
Nominal input (Qnw)DHW System (Hi)
minimum-maximum
kW 31 - 150 31 - 150 52 - 293 65 - 351
Nominal input (Qnw)DHW System (Hs)
minimum-maximum
kW 34 - 167 34 - 167 58 - 326 72 - 390
Heating efficiency under full load (Hi)(8060 degC)
- 993 993 992 991
Heating efficiency under full load (Hi)(5030 degC)
- 1070 1053 1020 1022
Heating efficiency under partial load(Hi) (Return temperature 60degC)
- 949 949 961 963
Heating efficiency under partial load(EN 9242) (Return temperature30degC)
- 1102 1102 1101 1106
Data on the gases and combustion gasesGas consumption - Natural gas H(G20)
minimum-maximum
m3h 033 - 159 033 - 159 055 - 310 069 - 371
Gas consumption - Natural gas L(G25)
minimum-maximum
m3h 038 - 185 038 - 185 064 - 361 080 - 432
Gas consumption - Propane G31 minimum-maximum
m3h 013 - 061 013 - 061 021 - 120 027 - 144
Mass flue gas flow rate minimum-maximum
kgh 53 - 252 53 - 252 89 - 493 111 - 573
AGC 1015 AGC 15 AGC 25 AGC 35 3 Technical specifications
15032016 - 300026080-001-07 10
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
132 Installerrsquos liability
The installer is responsible for the installation andcommissioning of the appliance The installer mustrespect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Carry out installation in compliance with the prevailing
legislation and standards4Perform the initial start up and carry out any checks
necessary4Explain the installation to the user4 If a maintenance is necessary warn the user of the
obligation to check the appliance and maintain it ingood working order
4Give all the instruction manuals to the user
133 Userrsquos liability
To guarantee optimum operation of the appliance theuser must respect the following instructions4Read and follow the instructions given in the manuals
provided with the appliance4Call on qualified professionals to carry out installation
and initial start up4Get your installer to explain your installation to you4Ensure the Appliance is serviced in accordance with
the manufacturerrsquos instructions by a suitable qualifiedperson
4Keep the instruction manuals in good condition closeto the appliance
1 Safety instructions AGC 1015 AGC 15 AGC 25 AGC 35
7 15032016 - 300026080-001-07
2 About this manual
21 Symbols used
211 Symbols used in the manual
In these instructions various danger levels are employed to draw theuserrsquos attention to particular information In so doing we wish tosafeguard the userrsquos safety highlight hazards and guarantee correctoperation of the appliance
DANGER
Risk of a dangerous situation causing serious physicalinjury
WARNING
Risk of a dangerous situation causing slight physicalinjury
CAUTION
Risk of material damage
Signals important information
frac14Signals a referral to other instructions or other pages in theinstructions
212 Symbols used on the equipment
4 Protective earthing~ Alternating current
Before installing and commissioning the device readcarefully the instruction manuals provided
Dispose of the used products in an appropriate recoveryand recycling structure
This appliance must be connected to the protective earth
D000241-C
AGC 1015 AGC 15 AGC 25 AGC 35 2 About this manual
15032016 - 300026080-001-07 8
Caution danger live partsDisconnect the mains power prior to any operations
22 Abbreviations
4 3CE Collective conduit for sealed boiler4 DHW Domestic hot water4 Interscenario switch Home automation switch that can be used
to centralise and control several scenarios4 Hi Lower heating value LHV (Nett)4 Hs Higher heating value HHV (Gross)4 PPS Polypropylene hardly inflammable4 PCU Primary Control Unit - PCB for managing burner operation4 PSU Parameter Storage Unit - Parameter storage for PCBs
PCU and SU4 SCU Secondary Control Unit - control panel PCB4 SU Safety Unit - Safety PCB4 3WV 3-way valve4 HL High Load - DHW tank with plate exchanger4 SL Standard Load - DHW tank with coil4 SHL Solar High Load - Solar DHW tank with plate exchanger4 SSL Solar Standard Load - Solar DHW tank with coil
1 2
M002628-A
2 About this manual AGC 1015 AGC 15 AGC 25 AGC 35
9 15032016 - 300026080-001-07
3 Technical specifications
31 Certifications
CE identification no CE-0085CM0178NOx classification 5 (EN 15502-1 EN 15502-2-1)Type of connection Chimney B23 B33
Flue gas outlet C13(x) C33(x) C43(x) C53 C83(x)C93(x)
32 Technical specifications
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35GeneralNominal output (Pn)Heating System (8060 degC)
minimum-maximum
kW 30 - 104 30 - 149 50 - 248 63 - 348
Nominal output (Pn)Heating System (5030 degC)
minimum-maximum
kW 34 - 112 34 - 158 56 - 255 70 - 359
Nominal output (Pn)Heating System (4030 degC)
minimum-maximum
kW 34 - 160 34 - 160 56 - 259 70 - 364
Nominal input (Qn)Heating System (Hi)
minimum-maximum
kW 31 - 105 31 - 150 52 - 250 65 - 351
Nominal input(Qn)Heating System (Hs)
minimum-maximum
kW 34 - 117 34 - 167 58 - 278 72 - 390
Nominal input (Qnw)DHW System (Hi)
minimum-maximum
kW 31 - 150 31 - 150 52 - 293 65 - 351
Nominal input (Qnw)DHW System (Hs)
minimum-maximum
kW 34 - 167 34 - 167 58 - 326 72 - 390
Heating efficiency under full load (Hi)(8060 degC)
- 993 993 992 991
Heating efficiency under full load (Hi)(5030 degC)
- 1070 1053 1020 1022
Heating efficiency under partial load(Hi) (Return temperature 60degC)
- 949 949 961 963
Heating efficiency under partial load(EN 9242) (Return temperature30degC)
- 1102 1102 1101 1106
Data on the gases and combustion gasesGas consumption - Natural gas H(G20)
minimum-maximum
m3h 033 - 159 033 - 159 055 - 310 069 - 371
Gas consumption - Natural gas L(G25)
minimum-maximum
m3h 038 - 185 038 - 185 064 - 361 080 - 432
Gas consumption - Propane G31 minimum-maximum
m3h 013 - 061 013 - 061 021 - 120 027 - 144
Mass flue gas flow rate minimum-maximum
kgh 53 - 252 53 - 252 89 - 493 111 - 573
AGC 1015 AGC 15 AGC 25 AGC 35 3 Technical specifications
15032016 - 300026080-001-07 10
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
2 About this manual
21 Symbols used
211 Symbols used in the manual
In these instructions various danger levels are employed to draw theuserrsquos attention to particular information In so doing we wish tosafeguard the userrsquos safety highlight hazards and guarantee correctoperation of the appliance
DANGER
Risk of a dangerous situation causing serious physicalinjury
WARNING
Risk of a dangerous situation causing slight physicalinjury
CAUTION
Risk of material damage
Signals important information
frac14Signals a referral to other instructions or other pages in theinstructions
212 Symbols used on the equipment
4 Protective earthing~ Alternating current
Before installing and commissioning the device readcarefully the instruction manuals provided
Dispose of the used products in an appropriate recoveryand recycling structure
This appliance must be connected to the protective earth
D000241-C
AGC 1015 AGC 15 AGC 25 AGC 35 2 About this manual
15032016 - 300026080-001-07 8
Caution danger live partsDisconnect the mains power prior to any operations
22 Abbreviations
4 3CE Collective conduit for sealed boiler4 DHW Domestic hot water4 Interscenario switch Home automation switch that can be used
to centralise and control several scenarios4 Hi Lower heating value LHV (Nett)4 Hs Higher heating value HHV (Gross)4 PPS Polypropylene hardly inflammable4 PCU Primary Control Unit - PCB for managing burner operation4 PSU Parameter Storage Unit - Parameter storage for PCBs
PCU and SU4 SCU Secondary Control Unit - control panel PCB4 SU Safety Unit - Safety PCB4 3WV 3-way valve4 HL High Load - DHW tank with plate exchanger4 SL Standard Load - DHW tank with coil4 SHL Solar High Load - Solar DHW tank with plate exchanger4 SSL Solar Standard Load - Solar DHW tank with coil
1 2
M002628-A
2 About this manual AGC 1015 AGC 15 AGC 25 AGC 35
9 15032016 - 300026080-001-07
3 Technical specifications
31 Certifications
CE identification no CE-0085CM0178NOx classification 5 (EN 15502-1 EN 15502-2-1)Type of connection Chimney B23 B33
Flue gas outlet C13(x) C33(x) C43(x) C53 C83(x)C93(x)
32 Technical specifications
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35GeneralNominal output (Pn)Heating System (8060 degC)
minimum-maximum
kW 30 - 104 30 - 149 50 - 248 63 - 348
Nominal output (Pn)Heating System (5030 degC)
minimum-maximum
kW 34 - 112 34 - 158 56 - 255 70 - 359
Nominal output (Pn)Heating System (4030 degC)
minimum-maximum
kW 34 - 160 34 - 160 56 - 259 70 - 364
Nominal input (Qn)Heating System (Hi)
minimum-maximum
kW 31 - 105 31 - 150 52 - 250 65 - 351
Nominal input(Qn)Heating System (Hs)
minimum-maximum
kW 34 - 117 34 - 167 58 - 278 72 - 390
Nominal input (Qnw)DHW System (Hi)
minimum-maximum
kW 31 - 150 31 - 150 52 - 293 65 - 351
Nominal input (Qnw)DHW System (Hs)
minimum-maximum
kW 34 - 167 34 - 167 58 - 326 72 - 390
Heating efficiency under full load (Hi)(8060 degC)
- 993 993 992 991
Heating efficiency under full load (Hi)(5030 degC)
- 1070 1053 1020 1022
Heating efficiency under partial load(Hi) (Return temperature 60degC)
- 949 949 961 963
Heating efficiency under partial load(EN 9242) (Return temperature30degC)
- 1102 1102 1101 1106
Data on the gases and combustion gasesGas consumption - Natural gas H(G20)
minimum-maximum
m3h 033 - 159 033 - 159 055 - 310 069 - 371
Gas consumption - Natural gas L(G25)
minimum-maximum
m3h 038 - 185 038 - 185 064 - 361 080 - 432
Gas consumption - Propane G31 minimum-maximum
m3h 013 - 061 013 - 061 021 - 120 027 - 144
Mass flue gas flow rate minimum-maximum
kgh 53 - 252 53 - 252 89 - 493 111 - 573
AGC 1015 AGC 15 AGC 25 AGC 35 3 Technical specifications
15032016 - 300026080-001-07 10
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
Caution danger live partsDisconnect the mains power prior to any operations
22 Abbreviations
4 3CE Collective conduit for sealed boiler4 DHW Domestic hot water4 Interscenario switch Home automation switch that can be used
to centralise and control several scenarios4 Hi Lower heating value LHV (Nett)4 Hs Higher heating value HHV (Gross)4 PPS Polypropylene hardly inflammable4 PCU Primary Control Unit - PCB for managing burner operation4 PSU Parameter Storage Unit - Parameter storage for PCBs
PCU and SU4 SCU Secondary Control Unit - control panel PCB4 SU Safety Unit - Safety PCB4 3WV 3-way valve4 HL High Load - DHW tank with plate exchanger4 SL Standard Load - DHW tank with coil4 SHL Solar High Load - Solar DHW tank with plate exchanger4 SSL Solar Standard Load - Solar DHW tank with coil
1 2
M002628-A
2 About this manual AGC 1015 AGC 15 AGC 25 AGC 35
9 15032016 - 300026080-001-07
3 Technical specifications
31 Certifications
CE identification no CE-0085CM0178NOx classification 5 (EN 15502-1 EN 15502-2-1)Type of connection Chimney B23 B33
Flue gas outlet C13(x) C33(x) C43(x) C53 C83(x)C93(x)
32 Technical specifications
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35GeneralNominal output (Pn)Heating System (8060 degC)
minimum-maximum
kW 30 - 104 30 - 149 50 - 248 63 - 348
Nominal output (Pn)Heating System (5030 degC)
minimum-maximum
kW 34 - 112 34 - 158 56 - 255 70 - 359
Nominal output (Pn)Heating System (4030 degC)
minimum-maximum
kW 34 - 160 34 - 160 56 - 259 70 - 364
Nominal input (Qn)Heating System (Hi)
minimum-maximum
kW 31 - 105 31 - 150 52 - 250 65 - 351
Nominal input(Qn)Heating System (Hs)
minimum-maximum
kW 34 - 117 34 - 167 58 - 278 72 - 390
Nominal input (Qnw)DHW System (Hi)
minimum-maximum
kW 31 - 150 31 - 150 52 - 293 65 - 351
Nominal input (Qnw)DHW System (Hs)
minimum-maximum
kW 34 - 167 34 - 167 58 - 326 72 - 390
Heating efficiency under full load (Hi)(8060 degC)
- 993 993 992 991
Heating efficiency under full load (Hi)(5030 degC)
- 1070 1053 1020 1022
Heating efficiency under partial load(Hi) (Return temperature 60degC)
- 949 949 961 963
Heating efficiency under partial load(EN 9242) (Return temperature30degC)
- 1102 1102 1101 1106
Data on the gases and combustion gasesGas consumption - Natural gas H(G20)
minimum-maximum
m3h 033 - 159 033 - 159 055 - 310 069 - 371
Gas consumption - Natural gas L(G25)
minimum-maximum
m3h 038 - 185 038 - 185 064 - 361 080 - 432
Gas consumption - Propane G31 minimum-maximum
m3h 013 - 061 013 - 061 021 - 120 027 - 144
Mass flue gas flow rate minimum-maximum
kgh 53 - 252 53 - 252 89 - 493 111 - 573
AGC 1015 AGC 15 AGC 25 AGC 35 3 Technical specifications
15032016 - 300026080-001-07 10
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
3 Technical specifications
31 Certifications
CE identification no CE-0085CM0178NOx classification 5 (EN 15502-1 EN 15502-2-1)Type of connection Chimney B23 B33
Flue gas outlet C13(x) C33(x) C43(x) C53 C83(x)C93(x)
32 Technical specifications
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35GeneralNominal output (Pn)Heating System (8060 degC)
minimum-maximum
kW 30 - 104 30 - 149 50 - 248 63 - 348
Nominal output (Pn)Heating System (5030 degC)
minimum-maximum
kW 34 - 112 34 - 158 56 - 255 70 - 359
Nominal output (Pn)Heating System (4030 degC)
minimum-maximum
kW 34 - 160 34 - 160 56 - 259 70 - 364
Nominal input (Qn)Heating System (Hi)
minimum-maximum
kW 31 - 105 31 - 150 52 - 250 65 - 351
Nominal input(Qn)Heating System (Hs)
minimum-maximum
kW 34 - 117 34 - 167 58 - 278 72 - 390
Nominal input (Qnw)DHW System (Hi)
minimum-maximum
kW 31 - 150 31 - 150 52 - 293 65 - 351
Nominal input (Qnw)DHW System (Hs)
minimum-maximum
kW 34 - 167 34 - 167 58 - 326 72 - 390
Heating efficiency under full load (Hi)(8060 degC)
- 993 993 992 991
Heating efficiency under full load (Hi)(5030 degC)
- 1070 1053 1020 1022
Heating efficiency under partial load(Hi) (Return temperature 60degC)
- 949 949 961 963
Heating efficiency under partial load(EN 9242) (Return temperature30degC)
- 1102 1102 1101 1106
Data on the gases and combustion gasesGas consumption - Natural gas H(G20)
minimum-maximum
m3h 033 - 159 033 - 159 055 - 310 069 - 371
Gas consumption - Natural gas L(G25)
minimum-maximum
m3h 038 - 185 038 - 185 064 - 361 080 - 432
Gas consumption - Propane G31 minimum-maximum
m3h 013 - 061 013 - 061 021 - 120 027 - 144
Mass flue gas flow rate minimum-maximum
kgh 53 - 252 53 - 252 89 - 493 111 - 573
AGC 1015 AGC 15 AGC 25 AGC 35 3 Technical specifications
15032016 - 300026080-001-07 10
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
Boiler type AGC 1015 AGC 15 AGC 25 AGC 35Flue gas temperature minimum-
maximumdegC 30 - 65 30 - 65 30 - 80 30 - 75
Maximum counter pressure Pa 80 80 130 140Characteristics of the heating circuitWater content (ex expansion vessel) l 19 19 19 25Water operating pressure minimum kPa (bar (MPa)) 80 (08) 80 (08) 80 (08) 80 (08)Water operating pressure (PMS) maximum kPa (bar (MPa)) 300 (30) 300 (30) 300 (30) 300 (30)Water temperature maximum degC 110 110 110 110Operating temperature maximum degC 90 90 90 90Electrical characteristicsPower supply voltage VAC 230 230 230 230Power consumption - Full load maximum W 101 101 116 132Electrical protection index IP21 IP21 IP21 IP21Other characteristicsWeight (empty) kg 56 56 56 50
3 Technical specifications AGC 1015 AGC 15 AGC 25 AGC 35
11 15032016 - 300026080-001-07
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
4 Description
41 Operating principle
411 Gasair setting
Air is sucked in by the fan and the gas injected into the venturiattached to the fan inlet The fan rotation speed modulates and adaptsto thermal energy requirements thanks to the temperatures measuredby the various sensors The gas and air are mixed in the venturi whichenables operation at a constant ratio The noise of the venturi isabsorbed by a silencer attached to its inlet The gasair mixture iscarried to the burner in the top of the exchanger guided by the pre-mix channel
412 Combustion
The burner heats the heating water circulating in the heatexchanger At a return temperature lower than around 55degC the fluegases cool down to a temperature lower than the dew point thuscausing the condensation of the water vapour contained in the fluegases in the lower section of the heat exchanger The heat releasedduring this condensation process (the latent heat or condensing heat)is also transferred to the heating water The cooled combustion gasesare evacuated via the combustion gas outlet flue The condensationwater is evacuated via a condensate trap
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 12
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
42 Main parts
1 Flue gas discharge pipe2 Flue gas measuring point3 Heat exchanger4 Ignitionionization electrode5 Box for the control PCBs6 Control panel7 Command module8 Water pressure sensor9 Circulation pump10 Hydroblock11 3-way valve12 Safety valve13 Casing14 Expansion vessel15 Combined venturi and gas valve unit16 Fan17 Air intake silencer18 Mixer pipe19 Automatic air vent
C003072-C
18
19
16
17
15
14
13
12
11
1234
10
9
5
6
7
8
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
13 15032016 - 300026080-001-07
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
43 Control panel
431 Description of the keys
A Temperature setting key (heating DHW swimming pool)B Operating mode selection keyC DHW override keyD Key to access the parameters reserved for the installerE Keys on which the function varies as and when selections
are madeF Rotary setting button
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
A0
00
86
6-A
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
A
B
C
D E F
(
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 14
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
432 Description of the display
n Key functions
gt Access to the various menus
( Used to scroll through the menus
rsquo Used to scroll through the parameters The symbol is displayed when help is available
f Used to display the curve of the parameter selectedSTD Reset of the time programmes
b Selection of comfort mode or selection of the days to beprogrammed
v Selection of reduced mode or deselection of the days tobe programmed
j Back to the previous levelESC Back to the previous level without saving the
modifications made
t Manual reset
n Flame output level
C002705-A
The whole symbol flashes The burner starts up but theflame is not yet present
C002704-A
Part of the symbol flashes Output is increasing
C002703-A
Steady symbol The required output has been reached
C002702-A
Part of the symbol flashes Output is dropping
bar
r
STD( t
0 2 4 6 8 10 12 14 16 18 22 2420
C002696-A
pb AUTOx c rjLg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002701-B
pb AUTOx c rjMg m
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
15 15032016 - 300026080-001-07
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
n Solar (If connected)
u The solar load pump is running
L000200-A The top part of the tank is reheated to the tank set point
L000201-A The entire tank is reheated to the tank set point
L000198-A The entire tank is reheated to the solar tank set point
L000199-A The tank is not loaded - Presence of the solar control
system
n Operating modes
p Summer mode The heating is off Domestic hot watercontinues to be produced
b WINTER mode Heating and domestic hot water working
AUTO Operation in automatic mode according to the timerprogramme
x Comfort mode The symbol is displayed when a DAYoverride (comfort) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
m Reduced mode The symbol is displayed when a NIGHToverride (reduced) is activated
4 Flashing symbol Temporary override4 Steady symbol Permanent override
g Holiday mode The symbol is displayed when a HOLIDAYoverride (antifreeze) is activated
4 Flashing symbol Holiday mode programmed4 Steady symbol Holiday mode active
m Manual mode The boiler operates with the displayed setpoint All of the pumps operate The 3-way valves are notcontrolled
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
L000197-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002697-B
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002698-B
pb AUTOx c rjMg m
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 16
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
n System pressure
bar Pressure indicator The symbol is displayed when a waterpressure sensor is connected
4 Flashing symbol The water pressure is insufficient4 Steady symbol The water pressure is sufficient
l Water pressure level
4 R 09 to 11 bar4 E 12 to 15 bar4 Z 16 to 19 bar4 A 20 to 23 bar4 l gt 24 bar
n Domestic Hot Water override
A bar is displayed when a DHW override is activated
4 Flashing bar Temporary override4 Steady bar Permanent override
n Other information
433 Browsing in the menus
1 To select the desired menu turn the rotary button2 To access the menu press the rotary button
To go back to the previous display press the key j
3 To select the desired parameter turn the rotary button4 To modify the parameter press the rotary button
To go back to the previous display press the key j
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002708-A
pb AUTOx c rjMg m
bar
STD t
0 2 4 6 8 10 12 14 16 18 22 2420
C002707-A
pb AUTOx c rjMg m
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
MEASURES
CHOICE TIME PROG
TIME PROGRAM
SETTING
TIME DAYa
C002220-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGB
CURRENT PROGC
P2
P3
a
C002221-C-04
4 Description AGC 1015 AGC 15 AGC 25 AGC 35
17 15032016 - 300026080-001-07
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
5 To modify the parameter turn the rotary button6 To confirm press the rotary button
To cancel press key h
7 To go back to the main display press key j2 times
It is possible to use the ( and rsquo keys instead of the rotarybutton
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
CURRENT PROGCChoice of the timeprogram applied C
P4
a
C002222-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
LUNDI 1145
C002224-D-04
2x
AGC 1015 AGC 15 AGC 25 AGC 35 4 Description
15032016 - 300026080-001-07 18
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
5 Operating the appliance
51 Putting the appliance into operation
1 Turn on the boiler using the onoff switch
2 The first time the boiler is powered up the LANGUAGE menu isdisplayed Select the desired language by turning the rotarybutton
3 To confirm press the rotary buttonThe boiler will begin an automatic venting-programme (which lastsapprox 3 minutes) and will do this every time the power supply isisolated If there is a problem the error is displayed on the screen
4 Check the water pressure in the installation shown on the controlpanel display
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
52 Reading out measured values
The various values measured by the appliance are displayed in theMEASURES menu
1 To access user level Press the gt key2 Select the menu MEASURES
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
8 22 2420
l
0
C003159-B
Franccedilais - Deutsch - English - Italiano - Espanol - Nederlands- Pycck - Polski - Tuumlrk -
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb x c rg m
yumlLANGUE FRANCAIS
C002286-C
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
19 15032016 - 300026080-001-07
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
User level - MEASURES Menu
Parameter Description UnitOUTSIDE TEMP Outside temperature degCROOMTEMPA (1) Room temperature of circuit A degC
ROOMTEMPB (1) Room temperature of circuit B degC
ROOMTEMPC (1) Room temperature of circuit C degCBOILER TEMP Water temperature in the boiler degCPRESSURE Water pressure in the installation bar (MPa)WATER TEMP (1) Water temperature in the DHW tank degC
TEMP DHW INST (1) Instant hot water temperature degCSTORTANKTEMP(1)
Water temperature in the storage tank degC
SWIMMING PTB (1) Water temperature of the swimming pool on circuit B degC
SWIMMING PTC (1) Water temperature of the swimming pool on circuit C degC
OUTLET TEMPB (1) Temperature of the flow water in circuit B degC
OUTLET TEMPC (1) Temperature of the flow water in circuit C degC
TEMPSYSTEM (1) Temperature of the system flow water if multi-generator degC
TDHW BOTTOM (1) Water temperature in the bottom of the DHW tank degC
TEMPTANK AUX (1) Water temperature in the second DHW tank connected to the AUX circuit degC
DHW A TEMP (1) Water temperature in the second DHW tank connected to circuit A degC
TEMPSOLTANK (1) Temperature of the hot water produced by solar power (TS) degC
SOLARCOLLT (1) Solar panel temperature (TC) degC
SOLAENERGY (1) Solar energy accumulated in the tank kWhBACK TEMP Temperature of the boiler return water degCFAN SPEED Fan rotation speed rpmPOWER Instantaneous boiler output (0 Burner off or running at minimum output) CURRENT (microA) Ionization current microAHEATCONS (2) Energy consumed by the boiler in heating mode (estimated value) kWh
DHW CONS (2) Energy consumed by the boiler in DHW mode (estimated value) kWhNB IMPULS Number of burner starts (not restartable)
The meter is incremented by 8 every 8 start-ups
RUNTIME Number of burner operation hours (not restartable)The meter is incremented by 2 every 2 hours
h
IN 0-10V (1) Voltage at input 0-10 V VSEQUENCE Control system sequence CTRL Software control number (1) The parameter is only displayed for the options circuits or sensors actually connected(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the CONFIGURATION menu)
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 20
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
53 Changing the settings
531 Setting the set point temperatures
C Menu
Parameter Adjustment range Description Factory settingDAY TEMPA 5 to 30 degC Desired room temperature in comfort periods on circuit A 20 degCNIGHT TEMPA 5 to 30 degC Desired room temperature in reduced periods on circuit A 16 degCDAY TEMPB (1) 5 to 30 degC Desired room temperature in comfort periods on circuit B 20 degCNIGHT TEMPB (1) 5 to 30 degC Desired room temperature in reduced periods on circuit B 16 degCDAY TEMPC (1) 5 to 30 degC Desired room temperature in comfort periods on circuit C 20 degCNIGHT TEMPC (1) 5 to 30 degC Desired room temperature in reduced periods on circuit C 16 degCDHW TEMP (1) 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 55 degCTEMPTANK AUX (1) 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 55 degCDHW A TEMP (1) 10 to 90 degC Desired domestic hot water temperature in circuit A 55 degCTEMPSOLTANK (1)
(2) 20 to 80 degC Maximum load temperature of the tankrsquos solar zone 65 degC
SWIMMING PTB (1) HG 05 to 39 degC Desired temperature for swimming pool B 20 degCSWIMMING PTC (1) HG 05 to 39 degC Desired temperature for swimming pool C 20 degCWATER TNIGHT 10 to 80 degC Desired domestic hot water temperature in the DHW circuit 10 degCWATER TNIGHTAUX 10 to 90 degC Desired domestic hot water temperature in the auxiliary circuit 10 degCWATER TNIGHTA 10 to 90 degC Desired domestic hot water temperature in circuit A 10 degC(1) The parameter is only displayed for the options circuits or sensors actually connected(2) The menu is only displayed if the solar control system is connected
532 Selecting the operating mode
To select an operating mode proceed as follows
1 Press the MODE key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
MODE
C002267-A
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
21 15032016 - 300026080-001-07
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
MODE MenuParameter Adjustment range Description Factory settingAUTOMATIQUE The comfort ranges are determined by the timer programmeDAY 77 xxxx Comfort mode is forced until the time indicated or all the time (77) Present time + 1
hourNIGHT 77 xxxx Reduced mode is forced until the time indicated or all the time
(77)Present time + 1hour
HOLIDAYS 77 1 to 364 The antifreeze mode is active on all boiler circuitsNumber of daysrsquo holiday xx (1)
heating OFF xxxx (1)
Restarting xxxx (1)
Present date + 1day
SUMMER The heating is offDomestic hot water continues to be produced
MANUEL The generator operates according to the set point setting All ofthe pumps operate Option of setting the set point by simplyturning the rotary button
FORCE AUTO (2) YES NO An operating mode override is activated on the remote control(option)To force all circuits to run on AUTOMATIQUE mode selectYES
(1) The start and end days and the number of days are calculated in relation to each other(2) The parameter is only displayed if a room sensor is connected
533 Forcing domestic hot water production
To force domestic hot water production proceed as follows
1 Press the r key2 To select the desired parameter turn the rotary button3 To modify the parameter press the rotary button
To go back to the previous display press the key j4 To modify the parameter turn the rotary button5 To confirm press the rotary button
To cancel press key h
r MenuParameter Description Factory settingAUTOMATIQUE The domestic hot water comfort ranges are determined by the timer programme COMFORT Domestic hot water comfort mode is forced until the time indicated or all the time (77) Present time + 1 hour
MODE
C002268-A
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 22
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
534 Setting the contrast and lighting on thedisplay
1 To access user level Press the gt key2 Select the menu SETTING
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - SETTING Menu
Parameter Adjustment range Description Factory setting Customer settingCONTRAST DISP Adjusting the display contrast BACK LIGHT COMFORT The screen is illuminated continuously in
daytime periodsECO
ECO The screen is illuminated for 2 minuteswhenever pressed
535 Setting the time and date
1 To access user level Press the gt key2 Select the menu TIME DAY
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 Set the following parameters
User level - TIME DAY Menu (1)
Parameter Adjustment range Description Factory setting Customer settingHOURS 0 to 23 Hours setting MINUTE 0 to 59 Minutes setting DAY Monday to Sunday Setting the day of the week DATE 1 to 31 Day setting MONTH January to December Month setting YEAR 2008 to 2099 Year setting SUMTIME AUTO automatic switch to summer time on the last Sunday
in March and back to winter time on the last Sundayin October
AUTO
MANU for countries where the time change is done on otherdates or is not in use
(1) According to the configuration
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
23 15032016 - 300026080-001-07
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
536 Selecting a timer programme
1 To access user level Press the gt key2 Select the menu CHOICE TIME PROG
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter4 Assign the desired timer programme (P1 to P4) to the circuit with
the rotary button
User level - CHOICE TIME PROG Menu
Parameter Adjustment range DescriptionCURRENT PROGA P1 P2 P3 P4 Comfort programme activated
(Circuit A)CURRENT PROGB P1 P2 P3 P4 Comfort programme activated
(Circuit B)CURRENT PROGC P1 P2 P3 P4 Comfort programme activated
(Circuit C)
537 Customising a timer programme
1 To access user level Press the gt key2 Select the menu TIME PROGRAM
4 Turn the rotary button to scroll through the menus ormodify a value
4 Press the rotary button to access the selected menuor confirm a value modification
frac14For a detailed explanation of menu browsing refer tothe chapter Browsing in the menus page 17
3 To select the desired parameter
User level - TIME PROGRAM Menu
Parameter Time schedule DescriptionTIME PROGA PROG P2 A
PROG P3 APROG P4 A
Timer programme for circuit A
TIME PROGB PROG P2 BPROG P3 BPROG P4 B
Timer programme for circuit B
TIME PROGC PROG P2 CPROG P3 CPROG P4 C
Timer programme for circuit C
TIME PROGDHW DHW circuit timer programmeTIME PROGAUX Auxiliary circuit timer programme
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
C002219-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 24
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
4 To select a timer programme to be modified5 To select to days for which the timer programme is to be
modifiedTurn the rotary button to the left until you reach the day desiredTo confirm press the rotary button
6 b Day selectionPress key b v until the symbol b is displayedTurn the rotary button to the right to select the day(s) desiredv Cancelling the day selectionPress key b v until the symbol v is displayedTurn the rotary button to the right to cancel selection of the relevantday(s)
7 When the days desired for the programme have been selectedpress the rotary button to confirm
8 To define the timer ranges for the comfort mode and reducedmodeTurn the rotary button to the left until 000 is displayed The firstsegment of the graphic bar for the timer programme flashes
9 b Comfort mode selectionPress key b v until the symbol b is displayedTo select a comfort time range turn the rotary button to the rightv Reduced mode selectionPress key b v until the symbol v is displayedTo select a reduced time range turn the rotary button to the right
10When the times for the comfort mode have been selected pressthe rotary button to confirm
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGA Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuDisplay of the timeprogram To continuepush on the button a
C002228-B-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSelect the days toprogram a
C002229-C-04
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjLg m
PROG P2 C Mo Tu We Th Fr Sa SuSet the time program a
C002230-E-04
0600
0600
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
25 15032016 - 300026080-001-07
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
User level - TIME PROGRAM Menu
Day Comfort periods Filling enabledP1_______________
P2 _______________ P3 _______________ P4 _______________
TIME PROGB Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGC Monday 600 to 2200 Tuesday 600 to 2200 Wednesday 600 to 2200 Thursday 600 to 2200 Friday 600 to 2200 Saturday 600 to 2200 Sunday 600 to 2200
TIME PROGDHW Monday Tuesday Wednesday Thursday Friday Saturday Sunday
TIME PROGAUX Monday Tuesday Wednesday Thursday Friday Saturday Sunday
54 Installation shutdown
CAUTION
Do not switch off the mains supply to the appliance If thecentral heating system is not used for a long period werecommend activating the HOLIDAYS mode (to ensurethe anti-grip of the heating pump)
55 Antifreeze protection
When the heating water temperature in the boiler is too low theintegrated boiler protection system starts up This protection functionsas follows
4 If the water temperature is lower than 7degC the heating pump startsup
AGC 1015 AGC 15 AGC 25 AGC 35 5 Operating the appliance
15032016 - 300026080-001-07 26
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
4 If the water temperature is lower than 4degC the boiler starts up4 If the water temperature is higher than 10degC the boiler shuts down
and the circulation pump continues to run for a short time4 If the water temperature in the storage tank is less than 4degC it is
reheated to its set point
CAUTION
4 The antifreeze protection does not function if theappliance is switched off
4 The integrated protection system only protects theboiler not the installation To protect the installationset the appliance to HOLIDAYS mode
The HOLIDAYS mode protects
4 The installation if the outside temperature is lower than 3degC(factory setting)
4 The room temperature if a remote control is connected and theroom temperature is lower than 6 degC (factory setting)
4 The domestic hot water tank if the tank temperature is lowerthan 4 degC (the water is reheated to 10 degC)
To configure the holidays mode frac14See chapter Selecting theoperating mode page 21
5 Operating the appliance AGC 1015 AGC 15 AGC 25 AGC 35
27 15032016 - 300026080-001-07
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
6 Checking and maintenance
61 General instructions
The boiler does not require a lot of maintenance Nevertheless werecommend having the boiler inspected and serviced at regularintervals
4 Maintenance and cleaning of the boiler must be carried out at leastonce a year by a qualified technician
4 Have the flues swept at least once a year or more depending onthe regulations in force in your country
CAUTION
4 Maintenance operations must be done by a qualifiedengineer
4 We recommend taking out a maintenance contract4 Only original spare parts must be used4 Make certain that the flues and chimneys are
connected in good condition and not blocked4 Do not modify nor block the condensate outlet(s)4 If a neutralisation system is installed follow the
instructions delivered with the neutralisation systemfor cleaning and servicing of this system
The boiler displays a message whenever maintenance is necessary
1 When the message REVISION is displayed press to displaythe installerrsquos telephone number (only if the installer has input thisparameter)
2 Contact the fitter3 Ensure the Appliance is serviced in accordance with the
manufacturerrsquos instructions by a suitable qualified person
62 Periodic checks
4 Check the water pressure in the installation (MEASURE mode)
If the water pressure is lower than 08 bar more watershould be added If necessary top up the water level in theheating system (recommended hydraulic pressurebetween 15 and 20 bar)
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
AGC 1015 AGC 15 AGC 25 AGC 35 6 Checking and maintenance
15032016 - 300026080-001-07 28
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
4 Carry out a visual check for the presence of any water leaks
4 Open and close the radiator valves several times a year (thisprevents the valves from seizing up)
4 Clean the outside of the boiler using a damp cloth and a lightdetergent
CAUTION
Only a qualified professional is authorised to clean theinside of the boiler
T001507-B
1
2
3
4
T000181-B
6 Checking and maintenance AGC 1015 AGC 15 AGC 25 AGC 35
29 15032016 - 300026080-001-07
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
7 Troubleshooting
71 Anti-hunting
When the boiler is in Anti-short-cycle operating mode the symbol flashes
1 Press the keyThe message Operation assured when the restart temperaturewill be reached is displayed
This message is not an error message but an item ofinformation
72 Messages (Code type Bxx or Mxx)
In the case of failure the control panel displays a message and acorresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Switch the boiler off and switch back onThe boiler starts up again automatically when the reason for theblocking has been removed
3 If the code is displayed again correct the problem by following theinstructions in the table below
Code Messages Description Checking solutionB00 BLPSU ERROR The PSU PCB is incorrectly
configuredParameter error on the PSU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B01 BLBOILER MAX Maximum flow temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)B02 BLHEATING SPEED The increase in flow temperature
has exceeded its maximum limitThe water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
B07 BLDT OUTL RET Maximum difference betweenthe flow and return temperatureexceeded
The water flow in the installation is insufficient
4 Check the circulation (direction pump valves)4 Check the water pressureSensor error
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
Code Messages Description Checking solutionB08 BLRL OPEN The RL inlet on the PCU PCB
terminal block is openParameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B09 BLINVLN 4 Contact the professional who takes care of maintenance of the applianceB10B11
BLSCINOPEN The BL inlet on the PCU PCBterminal block is open
The contact connected to the BL inlet is open
4 Contact the professional who takes care ofmaintenance of the appliance
Parameter error
4 Contact the professional who takes care ofmaintenance of the appliance
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B13 BL PCU COM Communication error with theSCU PCB
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
SCU PCB not installed in the boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B14 BLWATER MIS The water pressure is lower than08 bar
Not enough water in the circuit
4 Top up the installation with waterB15 BLGAS PRESS Gas pressure too low Incorrect setting of the gas pressure switch on the SCU
PCB
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB16 BLBAD SU The SU PCB is not recognised Wrong SU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B17 BLBAD PSU The parameters saved on thePCU PCB are impaired
Parameter error on the PCU PCB
4 Contact the professional who takes care ofmaintenance of the appliance
B18 BLBAD PSU The PSU PCB is not recognised Wrong PSU PCB for this boiler
4 Contact the professional who takes care ofmaintenance of the appliance
B19 BLNO CONFIG The boiler has not beenconfigured
The PSU PCB has been changed
4 Contact the professional who takes care ofmaintenance of the appliance
B21 BLCOM SU Communication error betweenthe PCU and SU PCBs
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
B22 BLFLAME LOS No flame during operation No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceB25 BLSU ERROR Internal error on the SU PCB 4 Contact the professional who takes care of
maintenance of the applianceB26 BLDHW S The DHW tank sensor is
disconnected or short circuited4 Contact the professional who takes care of
maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
31 15032016 - 300026080-001-07
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
Code Messages Description Checking solutionB27 BLDHW INST The sensor on the plate
exchanger outlet is disconnectedor short circuited
4 Contact the professional who takes care ofmaintenance of the appliance
B28 BLBADCONFIG An HL tank is detected whilst theboiler cannot control itThis message disappears after10 seconds if the boiler cancontrol the HL tank
4 Wait for 10 seconds to see whether the error persists4 Contact the professional who takes care of
maintenance of the appliance
B29 toB34
BLUNKNOWN Bxx Incorrect configuration of thePCU
4 Contact the professional who takes care ofmaintenance of the appliance
M04 REVISION A service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M05 REVISION A An A B or C service is required The date programmed for the service has been reached
4 If the symbol flashes press key The installerrsquoscontact details are displayed
4 Contact the professional who takes care ofmaintenance of the appliance
M06 REVISION BM07 REVISION C
M20 DISGAS A boiler vent cycle is underway Switching the boiler on
4 Wait 3 minutes FLDRYB XX DAYS Floor drying is active
XX DAYS = Number of daysrsquofloor drying remaining
Floor drying is underway Heating on the circuits notconcerned is shut down
4 Contact the professional who takes care ofmaintenance of the appliance
FLDRYC XX DAYSFLDRYB+C XXDAYS
M23 CHANGE OUTSIS The outside temperature sensoris defective
Change the outside radio temperature sensor
M30 BLSYSTEMNETWORK
No communication with themaster regulation through theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
M31 BLCOM MODBUS Incorrect configuration of theMODBUS network
4 Contact the professional who takes care ofmaintenance of the appliance
73 Faults (Code type Lxx or Dxx)
In the event of operational failure the control panel flashes anddisplays an error message and a corresponding code
1 Make a note of the code displayedThe code is important for the correct and rapid diagnosis of thetype of failure and for any technical assistance that may beneeded
2 Press the t key If the code is displayed again switch off the boilerand then switch it back on
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COM FAIL D27
C002604-B-04
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 32
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
3 Press the key Follow the instructions displayed to solve theproblem
4 Consult the meaning of the codes in the table below
Code Faults Causeof thefault
Description Checking solution
L00 PSU FAIL PCU PSU PCB not connected Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L01 PSU PARAM FAIL PCU The safety parameters are incorrect Bad connectionPSU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L02 DEFOUTLET S PCU The boiler flow sensor has short-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L03 DEFOUTLET S PCU The boiler flow sensor is on an opencircuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L04 DEFOUTLET S PCU Boiler temp too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L05 STB OUTLET PCU Boiler temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L06 BACK SFAILURE PCU The return temperature sensor hasshort-circuited
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
bar
1
1
2
2
rc
STD( t
v
0 2 4 6 8 10 12 14 16 18 22 2420
pb AUTOx c rjMg m
SUNDAY 1145
TEMP 68deg
PCU COMFAIL D27
C002302-D-04
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
33 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
Code Faults Causeof thefault
Description Checking solution
L07 BACK SFAILURE PCU The return temperature sensor is onan open circuit
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
L08 BACK SFAILURE PCU Return temperature too low Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L09 STB BACK PCU Return temperature too high Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L10 DT RET-DEPgtMAX PCU Difference between the flow andreturn temperatures insufficient
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L11 DEP-RETgtMAX PCU Difference between the flow andreturn temperatures too great
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
L12 STB OPEN PCU Maximum boiler temperatureexceeded (STB thermostatmaximum)
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
No water circulation
4 Vent the air in the heating system4 Check the circulation (direction pump
valves)4 Check the water pressure
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 34
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
Code Faults Causeof thefault
Description Checking solution
L14 BURNER FAILURE PCU 5 burner start-up failures No ignition
4 Contact the professional who takes care ofmaintenance of the appliance
Ignition arc but no flame formation
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the appliancePresence of the flame but insufficient ionization(lt3 microA)
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL16 PARASIT FLAME PCU Detection of a parasite flame Ionization current present even though there is no
flameIgnition transformer defectiveGas valve defectThe burner remains very hot O2 too low
4 Contact the professional who takes care ofmaintenance of the appliance
L17 VALVE FAIL PCU Problem on the gas valve SU PCB faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L34 FAN FAILURE PCU The fan is not running at the rightspeed
Bad connectionFan defective
4 Contact the professional who takes care ofmaintenance of the appliance
L35 BACKgtBOIL FAIL PCU Flow and return reversed Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
Water circulation direction reversed
4 Check the circulation (direction pumpvalves)
L36 I-CURRENT FAIL PCU The flame went out more than 5times in 24 hours while the burnerwas operating
No ionization current
4 Check that the gas valve is fully opened4 Contact the professional who takes care of
maintenance of the applianceL37 SU COMFAIL PCU Communication failure with the SU
PCBBad connection
4 Contact the professional who takes care ofmaintenance of the appliance
L38 PCU COMFAIL PCU Communication failure between thePCU and SCU PCBs
Bad connectionSCU PCB not connected or faulty
4 Contact the professional who takes care ofmaintenance of the appliance
L39 BL OPEN FAIL PCU The BL inlet opened for a short time Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
35 15032016 - 300026080-001-07
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
Code Faults Causeof thefault
Description Checking solution
L40 TESTHRUFAIL PCU HRUURC unit test error Bad connectionExternal causeParameter incorrectly set
4 Contact the professional who takes care ofmaintenance of the appliance
L250 DEFWATER MIS PCU The water pressure is too low Hydraulic circuit incorrectly ventedWater leakMeasurement error
4 Top up with more water if necessary4 Reset the boiler
L251 MANOMETRE FAIL PCU Fault on the water pressure sensor Wiring problemThe manometer is defectSensor pcb defect
4 Contact the professional who takes care ofmaintenance of the appliance
D03D04
OUTL SB FAILOUTL SC FAIL
SCU Circuit B flow sensor faultCircuit C flow sensor faultRemarksThe circuit pump is runningThe 3-way valve motor on the circuitis no longer powered and can beadjusted manually
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D05 OUTSISFAIL SCU Outside temperature sensor faultRemarksThe boiler operates on BOILERMAX temperatureThe valve setting is no longerensured but monitoring themaximum temperature of the circuitafter the valve is ensuredValves may be manually operatedReheating the domestic hot waterremains ensured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D07 AUXSENSFAIL SCU Auxiliary sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D09 DHW SFAILURE SCU Domestic hot water sensor faultRemarksHeating of domestic hot water is nolonger ensuredThe load pump operatesThe load temperature of the dhwtank is the same as the boiler
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D11D12D13
ROOM SA FAILROOM SB FAILROOM SC FAIL
SCU A room temperature sensor faultB room temperature sensor faultC room temperature sensor faultNoteThe circuit concerned operateswithout any influence from the roomsensor
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D14 MC COMFAIL SCU Communication failure between theSCU PCB and the boiler radiomodule
Bad connection
4 Contact the professional who takes care ofmaintenance of the appliance
Boiler module failure
4 Contact the professional who takes care ofmaintenance of the appliance
AGC 1015 AGC 15 AGC 25 AGC 35 7 Troubleshooting
15032016 - 300026080-001-07 36
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
Code Faults Causeof thefault
Description Checking solution
D15 STTANK SFAIL SCU Storage tank sensor faultNoteThe hot water storage tank reheatingoperation is no longer assured
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D16D16
SWIMB SFAILSWIMC SFAIL
SCU Swimming pool sensor fault circuit BSwimming pool sensor fault circuit CNoteSwimming pool reheating is alwaysdone during the circuitrsquos comfortperiod
Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D17 DHW 2 SFAIL SCU Sensor fault tank 2 Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D18 STTANK SFAIL SCU Solar tank sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D19 SOLCOLSFAIL SCU Header sensor fault Bad connectionSensor fault
4 Contact the professional who takes care ofmaintenance of the appliance
D20 SOL COMFAIL SCU Interruption in communication between the SCU PCB and the solar control system
4 Contact the professional who takes care of maintenance of the applianceD27 PCU COM FAIL SCU Communication failure between the SCU and PCU PCBs
4 Contact the professional who takes care of maintenance of the applianceD32 5 RESETONOFF SCU 5 resets done in less than an hour
4 Switch the boiler off and switch back on4 If the boiler does not start after several resets (5 attempts possible) contact your
heating engineer and inform him of the error message displayedD37 TA-S SHORT-CIR SCU The Titan Active Systemreg is short-circuited
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D38 TA-S DISCONNEC SCU The Titan Active Systemreg is on an open circuit
4 Contact the professional who takes care of maintenance of the applianceRemarksDomestic hot water production has stopped but can nonetheless be restarted using keyrThe tank is no longer protectedIf a tank without Titan Active Systemreg is connected to the boilercheck that the TASsimulation connector (delivered with package AD212) is fitted to the sensor card
D99 DEFBAD PCU SCU The SCU software version does not recognise the PCU connected
4 Contact the professional who takes care of maintenance of the appliance
7 Troubleshooting AGC 1015 AGC 15 AGC 25 AGC 35
37 15032016 - 300026080-001-07
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
8 Energy savings
81 Energy-saving advice
4 Keep the room in which the boiler is installed well ventilated4 Do not block ventilation outlets4 Do not cover the radiators Do not hang curtains in front of the
radiators4 Install reflective panels behind the radiators to prevent heat
losses4 Insulate the pipes in rooms that are not heated (cellars and lofts)4 Close the radiators in rooms not in use4 Do not run hot (or cold) water pointlessly4 Install a water-saving shower head to save up to 40 energy4 Take showers rather than baths A bath consumes twice as much
water and energy
82 Recommendations
The remote control is available in the following versions
4 Wire4 Radio
The setting of the control panel andor of the remote control has aconsiderable influence on energy consumption
A few tips
4 In the room in which the room thermostat is installed itrsquos advisednot to use thermostatic valve radiators If a thermostatic valve isused the valve must be fully opened
4 Completely closing and opening thermostatic valve radiatorscauses undesirable temperature fluctuations Open and closethermostatic valves in small steps
4 Lower the temperature to around 20degC This reduces heating costsand energy consumption
4 Lower the temperature when you air the rooms4 When setting a time schedule bear days when you are absent
and holidays in mind
AGC 1015 AGC 15 AGC 25 AGC 35 8 Energy savings
15032016 - 300026080-001-07 38
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
9 Warranty
91 General
You have just purchased one of our appliances and we thank you forthe trust you have placed in our products
Please note that your appliance will provide good service for a longerperiod of time if it is regularly checked and maintained
Your installer and our customer support network are at your disposalat all times
92 Warranty terms
The following provisions are not exclusive of the buyer being ablebenefit from the legal provisions applicable regarding hidden defectsin the buyerrsquos country
Starting from the purchase date shown on the original installerrsquosinvoice your appliance has a contractual guarantee against anymanufacturing defect
The length of the guarantee is mentioned in the price catalogueThe manufacturer is not liable for any improper use of the applianceor failure to maintain or install the unit correctly (the user shall takecare to ensure that the system is installed by a qualified engineer)
In particular the manufacturer shall not be held responsible for anydamage loss or injury caused by installations which do not complywith the following
4 applicable local laws and regulations4 specific requirements relating to the installation such as national
andor local regulations4 the manufacturerrsquos instructions in particular those relating to the
regular maintenance of the unit4 the rules of the profession
The warranty is limited to the exchange or repair of such parts as havebeen recognised to be faulty by our technical department and doesnot cover labour travel and carriage costs
The warranty shall not apply to the replacement or repair of partsdamaged by normal wear and tear negligence repairs by unqualifiedparties faulty or insufficient monitoring and maintenance faultypower supply or the use of unsuitable fuel
Sub-assemblies such as motors pumps electric valves etc areguaranteed only if they have never been dismantled
The legislation laid down by european directive 9944EECtransposed by legislative decree No 24 of 2 February 2002 publishedin OJ No 57 of 8 March 2002 continues to apply
9 Warranty AGC 1015 AGC 15 AGC 25 AGC 35
39 15032016 - 300026080-001-07
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
en
Appendix
Information on the ecodesign and energy labelling directives
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
Contents1 Specific information 3
11 Recommendations 312 Ecodesign Directive 313 Technical data 314 Circulation pump 415 Disposal and Recycling 416 Product fiche - Boiler space heaters 417 Product data sheet - Temperature controls 418 Package fiche - Boilers 5
Contents
2 300026080 - ErP03 - 29032016
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
1 Specific information
11 Recommendations
NoteOnly qualified persons are authorised to assemble install and maintain the installation
12 Ecodesign Directive
This product conforms to the requirements of European Directive 2009125EC on the ecodesign of energy-related products
13 Technical data
Tab1 Technical parameters for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Condensing boiler Yes Yes Yes YesLow-temperature boiler(1) No No No NoB1 boiler No No No NoCogeneration space heater No No No NoCombination heater No No No NoRated heat output Prated kW 10 15 25 35
Useful heat output at rated heat output and high temperature regime(2)
P4 kW 104 149 248 348
Useful heat output at 30 of rated heat output and low temperature regime(1)
P1 kW 35 50 83 116
Seasonal space heating energy efficiency ƞs 93 94 94 94
Useful efficiency at rated heat output and high temperature regime(2)
ƞ4 895 895 894 893
Useful efficiency at 30 of rated heat output and low temperature regime(1)
ƞ1 993 993 992 996
Auxiliary electricity consumption Full load elmax kW 0024 0031 0045 0062Part load elmin kW 0020 0021 0019 0021Stand-by PSB kW 0004 0004 0004 0004
Other characteristics Standby heat loss Pstby kW 0078 0078 0078 0085
Ignition burner power consumption Pign kW - - - -
Annual energy consumption QHE GJ 31 46 77 107
Sound power level indoors LWA dB 37 46 51 53
Emissions of nitrogen oxides NOX mgkWh 28 30 34 38
(1) Low temperature means for condensing boilers 30degC for low temperature boilers 37degC and for other heaters 50degC return temperature (at heater inlet)
(2) High temperature regime means 60degC return temperature at heater inlet and 80degC feed temperature at heater outlet
1 Specific information
300026080 - ErP03 - 29032016 3
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
SeeThe back cover for contact details
14 Circulation pump
NoteThe benchmark for the most efficient circulators is EEI le 020
15 Disposal and Recycling
WarningRemoval and disposal of the boiler must be carried out by a qualishyfied installer in accordance with local and national regulations
If you need to remove the boiler proceed as follows1 Switch off the boiler2 Cut the electrical power to the boiler3 Close the main gas valve4 Close the water mains5 Close the gas valve on the boiler6 Drain the installation7 Remove the air vent hose above the siphon8 Remove the siphon9 Remove the airflue gas pipes
10 Disconnect all pipes on the underside of the boiler11 Dismantle the boiler
16 Product fiche - Boiler space heaters
Tab2 Product fiche for boiler space heatersProduct name AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency class A A A A
Rated heat output (Prated or Psup) kW 10 15 25 35Seasonal space heating energy efficiency 93 94 94 94Annual energy consumption GJ 31 46 77 107Sound power level LWA indoors dB 37 46 51 53
SeeFor specific precautions on assembly installation and mainteshynance see the chapter on Safety Instructions
17 Product data sheet - Temperature controls
Tab3 Product data sheet for the Temperature controls DIEMATIC iSystemClass IIContribution to space heating energy efficiency 2
Fig1 Recycling
MW-3000179-03
1 Specific information
4 300026080 - ErP03 - 29032016
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
18 Package fiche - Boilers
Fig2 Package fiche for boilers indicating the space heating energy efficiency of the package
AD-3000743-01
1
lsquoIrsquo
2
+
3
( - lsquoIrsquo ) x 01 = plusmn
4
(lsquoIIIrsquo x + lsquoIVrsquo x ) x 09 x ( 100) x = +
(1)
A = 095 A = 091
B = 086 C = 083
D - G = 081
5
( - lsquoIrsquo ) x lsquoIIrsquo = +
6
05 x 05 x = -
54
lt30
G F E D C B A A+
A++
A+++
+ (50 x lsquoIIrsquo) =
7
7
from fi che of solar device
Solar contribution AND Supplementary heat pump
Solar contribution
The energy effi ciency of the package of products provided for in this fi che may not correspond to its actual energy effi ciency once installed
in a building as this effi ciency is infl uenced by further factors such as heat loss in the distribution system and the dimensioning of the
products in relation to building size and characteristics
Boiler and supplementary heat pump installed with low temperature heat emitters at 35degC
Seasonal space heating energy effi ciency class of package
Seasonal space heating energy effi ciency of package
OR
Seasonal space heating energy effi ciency (in ) Supplementary heat pump
Tank rating
Collector effi ciency (in
)
Tank volume (in msup3) Collector size (in msup2)
Seasonal space heating energy effi ciency (in ) Supplementary boiler
Class I = 1 Class II = 2 Class III = 15
Class IV = 2 Class V = 3 Class VI = 4
Class VII = 35 Class VIII = 5
Temperature control
Seasonal space heating energy effi ciency of boiler
(1) If tank rating is above A use 095
select smaller value
from fi che of heat pump
from fi che of heat pump
from fi che of boiler
from fi che of temperature control
I The value of the seasonal space heating energy efficiency of the preferential space heater expressed in
1 Specific information
300026080 - ErP03 - 29032016 5
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
II The factor for weighting the heat output of preferential and suppleshymentary heaters of a package as set out in the following table
III The value of the mathematical expression 294(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
IV The value of the mathematical expression 115(11 Prated) whereby lsquoPratedrsquo is related to the preferential space heater
Tab4 Weighting of boilersPsup (Prated + Psup)(1)(2) II package without hot water storage tank II package with hot water storage tank0 0 001 03 03702 055 07003 075 08504 085 09405 095 09806 098 100ge 07 100 100(1) The intermediate values are calculated by linear interpolation between the two adjacent values(2) Prated is related to the preferential space heater or combination heater
Tab5 Package efficiencyDe Dietrich - AGC AGC 1015 AGC 15 AGC 25 AGC 35Seasonal space heating energy efficiency of boiler 93 94 94 94Temperature control + 2 + 2 + 2 + 2Seasonal space heating energy efficiency of package 95 96 96 96
1 Specific information
6 300026080 - ErP03 - 29032016
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30
AD
001N
U-A
J
DUEDI Srl
DE DIETRICH SERVICE
BDR Thermea (Czech republic) sro
wwwduediclimait
wwwdedietrichcz
Distributore Ufficiale EsclusivoDe Dietrich-Thermique Italia
wwwdedietrich-heiztechnikcom
Freecall 0800 201608
Jeseniova 277056130 00 Praha 3
+49 (0)25 72 9161-0+49 (0)25 72 9161-102
inforemehade
Via Passatore 12 - 12010San Defendente di CervascaCUNEO
+39 0171 857170+39 0171 687875infoduediclimait
+420 271 001 627dedietrichbdrthermeacz
IT
DE DIETRICH THERMIQUE Iberia SLUwwwdedietrich-calefacciones
CSalvador Espriu 1108908 LrsquoHOSPITALET de LLOBREGAT
+34 935 475 850infodedietrich-calefacciones
ES
129164 Россия г МоскваЗубарев переулок д 151
Бизнес-центр laquoЧайка Плазаraquo офис 309
+7 (495) 221-31-51
CZ
DE DIETRICH THERMIQUE SAS
infodedietrichru
copy CopyrightAll technical and technological information contained in these technical instructionsas well as any drawings and technical descriptions supplied remain our propertyand shall not be multiplied without our prior consent in writing
15032016
300026080-001-07
DE DIETRICH THERMIQUE
57 rue de la Gare F- 67580 MERTZWILLER - BP 30