36
 © AGI/FORUM, 2011 Oktober / October 2011  AGI  Arbeitsblatt Working Document Q 154 Dämmarbei ten an betriebstechnischen Anlagen Trag- und Stützkonstruk tionen Insulation Work at Industrial Installations Support- and Spacer-ring Constructions Bestell-Nr. / Order No. 51558  Arbeitsgemeinschaft Indu striebau e.V . (AGI) Neuhofstr. 9 · 64625 Bensheim Tel. 06251-9845296 · Fax 06251-9845297 E-mail: [email protected] · www.agi-on line.de Bezug durch / To be ordered by: FORUM Zeitschriften und Spezialmedien GmbH Mandichostraße 18 · 86504 Merching Tel. +49 8233 381129 · E-Mail: agi-blaetter@forum-zei tschriften.de Inhalt: 1 Allgemeines 1.1 Geltungsbereich 1.2 Lieferumfang des Auftragnehmers 1.3 Lieferumfang des Auftraggebers 1.4 Schweißarbeiten 1.5 Begriffe 1.6 Normen, Arbeitsblätter 2 Stoffe 2.1 Allgemeines 2.2 Stähle 2.3 Holz 2.4 Kunststoffe 2.5 Keramische Stoffe 2.6 Dämmstoffe 2.7 Stoffe für Trennschichten 3 Unterkonstruktions-Systeme 3.1 Allgemeines 3.2 Ausführungsmöglichkeiten 3.2.1 Befestigung am Objekt 3.2.2 Befestigung der Komponenten einer Unterkonstruktion untereinander 4 Trag- und Stützkonstru ktionen 4.1 Allgemeines 4.2 Tragkonstruktionen 4.2.1 Funktion 4.2.2 Arten 4.2.3 Anordnung und Dimensionen 4.2.4 Tragkonstruktion für Wärmedämmungen 4.2.4.1 Allgemeines 4.2.4.2 Ausführung 4.2.5 Tragkonstruktionen für Kältedämmung 4.2.5.1 Allgemeines 4.2.5.2 Ausführung 4.3 Stützkonstruktionen 4.3.1 Funktion 4.3.2 Arten 4.3.3 Erfordernis von Stützkonstruktionen 4.3.3.1 Betrachtung nach Anwendungsfällen 4.3.4 Anordnung und Dimensionen 4.3.5 Stützkonstruktionen für Wärmedämmungen 4.3.6 Stützkonstruktionen für Kältedämmungen 5 Anordnungsbeispiele 5.1 Beispiele für die Anordnung von Tragkonstruktionen 5.2 Bespiele für die Anordnung von Stützkonstruktionen 5.3 Beachtung der Dehnungsdifferenzen Contents: 1 General 1.1 Scope 1.2 Supply obligations of the contractor 1.3 Supply obligations of the client 1.4 Welding 1.5 Terms 1.6 Standards, Working Documents 2 Materials 2.1 General 2.2 Steels 2.3 Wood 2.4 Plastics 2.5 Ceramic Materials 2.6 Insulation Materials 2.7 Materials for Separating Layers 3 Sub-construc tion Systems 3.1 General 3.2 Execution Possibilities 3.2.1 Fastening at the Objekt 3.2.2 Connecting the Components of a Sub-construction with each other 4 Supporting- and Spacer-ring Constructio ns 4.1 General 4.2 Supporting Constructions 4.2.1 Function 4.2.2 Types 4.2.3 Positioning and Dimensions 4.2.4 Supporting Constructions for Hot Insulations 4.2.4.1 General 4.2.4.2 Execution 4.2.5 Supporting Constructions for Cold Insulations 4.2.5.1 General 4.2.5.2 Execution 4.3 Spacer-ring Constructions 4.3.1 Function 4.3.2 Types 4.3.3 Requirement of Spacer-ring Constructions 4.3.3.1 Discussion of Application Examples 4.3.4 Positioning and Dimensions 4.3.5 Spacer-ring Constructions for Hot Insulations 4.3.6 Spacer-ring Constructions for Cold Insulations 5 Positioning Examples 5.1 Positioning Examples for Support Constructions 5.2 Positioning Examples for Spacer-ring Constructions 5.3 Consideration of Expansion Differences

AGI Q 154 2011-10

Embed Size (px)

DESCRIPTION

Thermal insulation support and spacer ring construction for piping

Citation preview

  • AGI/FORUM, 2011

    Oktober / October 2011

    AGIArbeitsblatt

    Working Document

    Q 154Dmmarbeiten an betriebstechnischen Anlagen

    Trag- und SttzkonstruktionenInsulation Work at Industrial Installations

    Support- and Spacer-ring Constructions

    Bestell-Nr. / Order No. 51558

    Arbeitsgemeinschaft Industriebau e.V. (AGI) Neuhofstr. 9 64625 Bensheim

    Tel. 06251-9845296 Fax 06251-9845297 E-mail: [email protected] www.agi-online.de

    Bezug durch / To be ordered by:FORUM Zeitschriften und Spezialmedien GmbH

    Mandichostrae 18 86504 MerchingTel. +49 8233 381129 E-Mail: [email protected]

    Inhalt:

    1 Allgemeines

    1.1 Geltungsbereich

    1.2 Lieferumfang des Auftragnehmers

    1.3 Lieferumfang des Auftraggebers

    1.4 Schweiarbeiten

    1.5 Begriffe

    1.6 Normen, Arbeitsbltter

    2 Stoffe

    2.1 Allgemeines

    2.2 Sthle

    2.3 Holz

    2.4 Kunststoffe

    2.5 Keramische Stoffe

    2.6 Dmmstoffe

    2.7 Stoffe fr Trennschichten

    3 Unterkonstruktions-Systeme

    3.1 Allgemeines

    3.2 Ausfhrungsmglichkeiten

    3.2.1 Befestigung am Objekt

    3.2.2 Befestigung der Komponenten einer Unterkonstruktion untereinander

    4 Trag- und Sttzkonstruktionen

    4.1 Allgemeines

    4.2 Tragkonstruktionen

    4.2.1 Funktion

    4.2.2 Arten

    4.2.3 Anordnung und Dimensionen

    4.2.4 Tragkonstruktion fr Wrmedmmungen

    4.2.4.1 Allgemeines

    4.2.4.2 Ausfhrung

    4.2.5 Tragkonstruktionen fr Kltedmmung

    4.2.5.1 Allgemeines

    4.2.5.2 Ausfhrung

    4.3 Sttzkonstruktionen

    4.3.1 Funktion

    4.3.2 Arten

    4.3.3 Erfordernis von Sttzkonstruktionen

    4.3.3.1 Betrachtung nach Anwendungsfllen

    4.3.4 Anordnung und Dimensionen

    4.3.5 Sttzkonstruktionen fr Wrmedmmungen

    4.3.6 Sttzkonstruktionen fr Kltedmmungen

    5 Anordnungsbeispiele

    5.1 Beispiele fr die Anordnung von Tragkonstruktionen

    5.2 Bespiele fr die Anordnung von Sttzkonstruktionen

    5.3 Beachtung der Dehnungsdifferenzen

    Contents:

    1 General

    1.1 Scope

    1.2 Supply obligations of the contractor

    1.3 Supply obligations of the client

    1.4 Welding

    1.5 Terms

    1.6 Standards, Working Documents

    2 Materials

    2.1 General

    2.2 Steels

    2.3 Wood

    2.4 Plastics

    2.5 Ceramic Materials

    2.6 Insulation Materials

    2.7 Materials for Separating Layers

    3 Sub-construction Systems

    3.1 General

    3.2 Execution Possibilities

    3.2.1 Fastening at the Objekt

    3.2.2 Connecting the Components of a Sub-construction with each other

    4 Supporting- and Spacer-ring Constructions

    4.1 General

    4.2 Supporting Constructions

    4.2.1 Function

    4.2.2 Types

    4.2.3 Positioning and Dimensions

    4.2.4 Supporting Constructions for Hot Insulations

    4.2.4.1 General

    4.2.4.2 Execution

    4.2.5 Supporting Constructions for Cold Insulations

    4.2.5.1 General

    4.2.5.2 Execution

    4.3 Spacer-ring Constructions

    4.3.1 Function

    4.3.2 Types

    4.3.3 Requirement of Spacer-ring Constructions

    4.3.3.1 Discussion of Application Examples

    4.3.4 Positioning and Dimensions

    4.3.5 Spacer-ring Constructions for Hot Insulations

    4.3.6 Spacer-ring Constructions for Cold Insulations

    5 Positioning Examples

    5.1 Positioning Examples for Support Constructions

    5.2 Positioning Examples for Spacer-ring Constructions

    5.3 Consideration of Expansion Differences

  • Seite 2 / Page 2 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

    1 Allgemeines

    1.1 Geltungsbereich

    Das AGI-Arbeitsblatt Q 154 gilt fr Trag- und Sttzkonstruktionen bei Wrme- und Kltedmmungen an betriebstechnischen Anla-gen in der Industrie und in der technischen Gebudeausrstung. Sonderkonstruktionen sind nicht aufgefhrt. Das Arbeitsblatt gilt nicht fr Luftzerlegungsanlagen. Fr Anwendungsflle mit PUR-Ortschaum siehe AGI-Arbeitsblatt Q 138.

    1.2 Lieferumfang des Auftragnehmers

    Trag- und Sttzkonstruktionen gehren zur Leistung des Dm-munternehmens.

    1.3 Lieferumfang des Auftraggebers

    Der Auftraggeber hat die erforderlichen Betriebsdaten und Rand-bedingungen anzugeben. Dies knnen sein: Isometrien Lage der Festpunkte Fundamentierungen Behlterzeichnungen Verformungen, Dehnungen, Vibrationen whrend des

    Betriebes Temperaturen Materialien

    Er hat Stoffe und Bauteile, die er selbst beistellt, nach Anfor-derung durch den Auftragnehmer rechtzeitig anzuliefern, sowie Schwei- und Metallklebearbeiten am Objekt auszufhren.

    Halterungen am Objekt zur Anbringung der Tragkonstruktionen gehren zum Lieferumfang des Auftraggebers.

    1.4 Schweiarbeiten

    1.4.1 Am Objekt

    Schweiarbeiten am Objekt drfen nur mit Zustimmung des Auf-traggebers von qualifizierten Schweiern ausgefhrt werden. Die Schweivorschriften sind zu beachten.

    1.4.2 An Trag- und Sttzkonstruktionen

    Schweiarbeiten an Trag- und Sttzkonstruktionen drfen nur von qualifizierten Schweiern ausgefhrt werden. Werden diese Arbeiten auf der Baustelle durchgefhrt, muss eine Schweier-laubnis des Auftraggebers vorliegen. Die Schweivorschriften sind zu beachten.

    1.5 Begriffe

    1.5.1 Abstandshalter

    Abstandshalter sind Teile der Sttzkonstruktion, z. B. Stege aus Metall, Holz oder Keramik oder Formteile aus Dmmstoffen, die sich in der Regel auf dem Objekt absttzen.

    Bei Dmmsystemen mit Luftspalt und ausreichender Druckfestig-keit des Dmmstoffes knnen sie sich auch auf diesem absttzen.

    1.5.2 Ausdehnung

    Es wird die thermische Ausdehnung und die Ausdehnung durch Spannungen unterschieden.

    1.5.3 Dehnungskompensation

    Die Dehnungskompensation nimmt Dehnungen innerhalb des Systems auf und verhindert dadurch die Entstehung von Schden.

    1.5.4 Dehnungsdifferenz

    Unter Dehnungsdifferenz versteht man die Verlagerung zwei-er Bauteile zueinander auf Grund unterschiedlicher Tem-

    1 General

    1.1 Scope

    The AGI-Working Document Q 154 is applicable for supporting and spacer-ring constructions in hot and cold insulations at technical installations in the industry and in the technical building equipment. Special constructions have not been mentioned. The Working Document does not apply to air separation plants. For applications with PUR in-situ foam see AGI Working Document Q 138.

    1.2 Supply obligations of the contractor

    Support- and spacer-ring constructions are part of the insulation contractors assignment.

    1.3 Supply obligations of the client

    The client has to declare the operation data and the boundary conditions.These could be: isometric drawings positions of anchor points foundation structures container drawings deformations, expansions and vibrations

    during operation temperatures materials

    He shall supply in time upon request of the contractor materials and components provided by him. He is responsible for the exe-cution of welding and metal-gluing tasks at the object.

    Mounting supports at the object for fixing the support construc-tions are the clients responsibility.

    1.4 Welding

    1.4.1 At the object

    Welding at the object may only be done by qualified welders and only with explicit agreement of the client. Welding regulations shall be heeded.

    1.4.2 At support- and spacer-ring constructions

    Welding at support- and spacer-ring constructions may only be done by qualified welders. In case this labour is executed at the building site, a welding permit by the client is required. Welding regulations shall be heeded.

    1.5 Terms

    1.5.1 Distancer, Spacer

    Distancers are part of the spacer-ring construction, e.g. cross-pieces of metal, wood, or ceramic, or insulation material form-pieces. They are normally supported by the object.

    In insulation systems with air space and sufficient compressive strength of the insulant, they may also be supported by the in-sulant.

    1.5.2 Expansion

    A distinction is made between thermal expansion and the expan-sion through stress.

    1.5.3 Expansion compensation

    Expansion compensation absorbs expansions within the system, thus preventing the generation of damages.

    1.5.4 Expansion difference

    Expansion difference is understood to be the displacement of two building components opposite each other because of different

  • AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 3 / Seite 3

    peraturen bei Montage und Betrieb und unterschiedlicher Ausdehnungskoeffizienten bei den gewhlten Materialien. Auch der unterschiedliche Fllstand von Behltern kann ein Grund fr das Auftreten von Dehnungsdifferenzen sein.

    1.5.5 Distanzstcke

    Distanzstcke sind Bestandteile von Trag- und Sttzkonstrukti-onen, z. B. Stege aus Stahl oder Hartschaumformteile.

    1.5.6 Federelement

    Federelemente sind Bestandteile von Abstandshaltern. Sie kn-nen thermisch bedingte Abstandsnderung zwischen Objekt und Ummantelung kompensieren. Sie knnen auch die Funktion von Losstegen bernehmen und zur Minderung von Krperschall-bertragungen beitragen.

    1.5.7 Festschiene

    Festschienen sind mit einem Feststeg und mehreren Losstegen mit dem Objekt verbunden.

    1.5.8 Feststeg

    Feststege sind Stege, die in allen Richtungen starr sind.

    1.5.9 Gleitschuh

    Gleitschuhe sind Verbindungsstcke zwischen Schiene und Steg. Sie weisen einen Bewegungsfreiheitsgrad in Richtung der Schiene auf.

    1.5.10 Halterungen

    Halterungen sind angeschweite oder angeschraubte Bestand-teile des Objekts. Sie dienen der Befestigung von Tragkonstruk-tionen und bertragen die Lasten aus dem Dmmsystem auf das Objekt.

    1.5.11 Klemmvorrichtungen

    Klemmvorrichtungen (auch Spannvorrichtungen genannt) sind Tragkonstruktionen, die in Ausnahmefllen eingesetzt werden, wenn Halterungen nicht vorhanden und Schwei- arbeiten nicht zugelassen sind. Klemmvorrichtungen sind Kon-struktionen, ber die Lasten ber Reibung auf die Konstruktion bertragen werden.

    1.5.12 Koppelelement

    Koppelelemente sind Verbindungsstcke zwischen Schiene und Steg. Sie knnen einen oder mehrere Bewegungsfreiheitsgrade aufweisen.

    1.5.13 Losschiene

    Losschienen sind nur mit Losstegen mit dem Objekt verbunden.

    1.5.14 Lossteg

    Losstege sind Stege, die in mindestens einer Richtung beweglich sind.

    1.5.15 Nocken

    Nocken sind am Objekt angeschweite Halterungen zur Auflage-rung der Tragkonstruktion.

    1.5.16 Ring

    Ringe sind ein- oder mehrteilige Bauteile, die im montierten Zu-stand eine kreisrunde oder kreishnliche Form annehmen. Sie knnen Bestandteil einer Trag- oder Sttzkonstruktion sein und bestehen aus Flachstahl (Bandstahl), Blech- oder Stahlprofilen.

    TragringTragringe sind Bestandteil einer Tragkonstruktion. Sie knnen als Auenring und/oder Innenring montiert werden. Innenringe sind um das Objekt gespannt oder liegen auf Halterungen auf. Auenringe sind ber Stege mit dem Objekt oder dem Innenring verbunden.

    temperatures at mounting and operation and different thermal ex-pansion coefficients of the materials chosen. Different filling levels of containers, too, may be the cause of expansion differences.

    1.5.5 Distancers

    Distancers are parts of support- and spacer-ring constructions, e.g. webs of steel or rigid foam form-pieces.

    1.5.6 Spring Element

    Spring elements are parts of distancers. They are able to compen-sate the distance change between object and cladding caused by thermal expansion. They can also function as movable webs and contribute to the reduction of structure-born sound trans-mission.

    1.5.7 Fixed bars

    Fixed bars are connected with the object through one fixed and several sliding webs.

    1.5.8 Fixed webs

    Fixed webs are rigid in all directions.

    1.5.9 Sliding block

    Sliding blocks are connections between bar and web. They have a certain degree of freedom of movement in the direction of the bar.

    1.5.10 Mounting supports

    Mounting supports are welded or screwed components of the object. They serve the fastening of support constructions and convey the loads out of the insulation system onto the object.

    1.5.11 Clamping devices

    Clamping devices (also called chucking devices) are support constructions employed in exceptional cases, when mounting supports are missing and welding is not permitted. Clamping de-vices are constructuions with which loads are conveyed onto the object by friction.

    1.5.12 Coupling element

    Coupling elements are connecting devices between bar and web. They may have one or several degrees of freedom of movement.

    1.5.13 Sliding bars

    Sliding bars are connected to the object only through webs.

    1.5.14 Sliding webs

    Sliding webs are webs with a freedom of movement in at least one direction.

    1.5.15 Supports

    Supports are fixtures welded to the object to attach the support construction.

    1.5.16 Ring

    Rings are building components in one or several parts, which when mounted assume a circular or almost circular form. They can be parts of a support- or a spacer-ring construction and are made of flat steel (band steel), sheet- or steel profiles.

    Thrust collarThrust collars are parts of a support construction. They can be mounted as inner and/or external ring. Inner rings are clamped around the object or resting on mounting supports. External rings are connected with the object or with the inner ring by webs.

  • SttzringSttzringe sind Bestandteil einer Sttzkonstruktion. Sie halten die Ummantelung im vorgesehenen Abstand vom Objekt und sttzen sich ber Abstandshalter auf dem Objekt oder bei Dmmstoffen ausreichender Druckfestigkeit auf dem Dmmstoff ab.

    Doppelspannring/KlemmringDoppelspannringe/Klemmringe sind eine Sonderform der Trag-ringe. Sie bestehen aus einem Auenring und einem Innenring, die ber Stege miteinander verbunden sind.

    1.5.17 Schiebenaht

    Die Schiebenaht in der Ummantelung ist eine berlappung ohne mechanische Verbindung der berlappenden Bleche. Sie wird auch Dehnungsnaht genannt.

    1.5.18 Schiene/Blech-Profil

    Schienen/Blech-Profile sind Bestandteile einer Trag- oder Sttz-konstruktion an flchigen Bauteilen. Sie sind ber Abstandshal-ter/Stege mit dem Objekt verbunden.

    Je nach Querschnittsform unterscheidet man U-, Z-, C-, Hut- oder Winkel-Schienen.

    Losschiene (siehe 1.5.13) Festschiene (siehe 1.5.7)

    1.5.19 Sttzkonstruktion

    Sttzkonstruktionen sind Konstruktionen, die die Ummantelung im vorgegebenen Abstand vom Objekt halten, wenn der Dmm-stoff diese Aufgaben nicht bernehmen kann.

    Sttzkonstruktionen knnen nur senkrecht zur Objekt- bzw. Dm-moberflche wirkende Krfte bertragen. Sie sind Wrmebr-cken, soweit sie nicht aus Dmmstoffen mit annhernd gleicher Dmmwirkung hergestellt werden knnen oder sich nicht auf den Dmmstoff absttzen.

    1.5.20 Tragkonstruktion

    Tragkonstruktionen sind Konstruktionen, die die Lasten der Dm-mung und die auf die Dmmung einwirkenden Krfte direkt oder ber Halterungen auf das Objekt bertragen. Sie sind dmmtech-nisch bedingte Wrmebrcken.

    Sonderformen tragen ausschlielich den Dmmstoff.

    1.5.21 Trennstellen bei Ringen

    Trennstellen bei Ringen sind dadurch gekennzeichnet, dass hier die Endstellen der Ringsegmente entweder nicht miteinander ver-bunden sind oder so, dass trotz eingesetzter Verbindungsmittel Dehnungsdifferenzen aufgenommen werden knnen.

    1.5.22 Trennschichten

    Thermische Trennschichten bei Trag- und Sttzkonstruktionen sind Stoffe mit geringer Wrmeleitfhigkeit, die in der Regel zwi-schen Steg und Ring oder Schiene angeordnet sind.

    Trennschichten zur Vermeidung von Kontaktkorrosion sind elek-trisch nicht leitende Schichten zwischen Metallen unterschied-lichen elektrischen Potentials.

    1.5.23 Unterkonstruktion

    Unterkonstruktion ist der Oberbegriff fr Trag- und Sttzkon-struktionen.

    1.5.24 Wrmebrcken

    Wrmebrcken sind Bereiche, in denen die Wrmestromdichte grer ist als in angrenzenden Bereichen. Trag- und Sttzkon-struktionen aus Metall sind Wrmebrcken.

    Spacer ringsSpacer rings are parts of the spacer-ring construction. They keep the cladding in the intended distance from the object and are sup-ported via distancers by the object, or where the insulant has sufficient compressive strength by the insulation material.

    Double locking ring /Clamping ringDouble locking rings / clamping rings are a special form of thrust collars. They consist of an external and an inner ring, which are connected with each other by webs.

    1.5.17 Sliding seam

    The sliding seam in the cladding is an overlap without any mecha-nical connection between the overlapping sheets. It is also called expansion seam.

    1.5.18 Bar/Sheet metal profile

    Bars/sheet metal profiles are components of a support- or a spacer-ring construction at plane building components. They are connected with the object by distancers / webs.

    Dependent upon the form of the cross-section, one discerns U-, Z-, C-, hat- or angle bars.

    Sliding bar ( see 1.5.13 ) Fixed bar ( see 1.5.7 )

    1.5.19 Spacer-ring construction

    Spacer-ring constructions are structures to keep the cladding in the intended distance from the object where the insulation material cant do this.

    Spacer-ring constructions can only transfer loads that are effec-tive perpendicularly to the surface of the object or of the insu-lation material. They are thermal bridges as long as they cant be made of insulation material of roughly similar performance or cant be supported by the insulant.

    1.5.20 Support construction

    Support constructions are structures to transfer the loads of the insulation and the forces effective on the insulation directly or via mounting supports onto the object. They are insulation system related thermal bridges.

    Special types support only the insulation material.

    1.5.21 Separation points in rings

    Separation points in rings are characterised by the fact that here the ends of the ring sections are either not connected with each other or connected in a fashion to accommodate expansion diffe-rences despite the connection means employed.

    1.5.22 Separating layers

    Thermally separating layers in support- and spacer-ring construc-tions are materials with a low thermal conductivity, which are nor-mally employed between web and ring, respectively bar.

    Separating layers to prevent contact corrosion are electrically nonconductive materials between metals of different electrical potential.

    1.5.23 Sub-construction

    Sub-construction is a general term for support- and spacer-ring constructions.

    1.5.24 Thermal bridges

    Thermal bridges are regions, where the heat flow rate is higher than in adjacent areas. Metal support- and spacer-ring construc-tions are thermal bridges.

    Seite 4 / Page 4 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

  • Bild 1: Beispiele fr die Ausfhrung von Feststegen und Losstegen / Figure 1: Examples for the execution of fixed and sliding webs

    1.5.25 Steg

    FeststegFeststege sind Stege, die in allen Richtungen starr und stets mit dem Objekt fest verbunden sind.

    LosstegLosstege zeichnen sich dadurch aus, dass bei ihnen Kopf- und Fupunkt gegeneinander verschiebbar sind.

    Losstege sind in mindestens einer Richtung biegsam. Sie sind bei ebenen Objektflchen vorzugsweise fest mit dem Objekt ver-bunden, bei Rohrleitungen dagegen vorzugsweise fest mit dem Ring oder der Schiene.

    1.6 Normen, Arbeitsbltter

    DIN 4140 Dmmarbeiten an betriebstechnischen Anlagen in der Industrie und in der Technischen Gebu-deausstattung Ausfhrung von Wrme- und Kltedmmungen

    VDI 2055 Wrme- und Klteschutz fr betriebstechnische Anlagen in der Industrie und in der technischen Gebudeausrstung

    AGI-ArbeitsbltterQ 02 Dmmarbeiten an betriebstechnischen Anlagen;

    BegriffeQ 03 Dmmarbeiten an betriebstechnischen Anlagen;

    Ausfhrung von Wrme- und Kltedmmungen

    Q 05 Konstruktion betriebstechnischer Anlagen

    Q 153 Halterungen fr Tragkonstruktionen

    Beispiel: Winkelsteg mit angenieteter U-Schiene Example: Angle web with riveted U-rail

    Beispiel: Winkelsteg mit Koppelelement und C-Schiene Koppelelement an C-Schiene fixiert Example: Angle web with coupling element and C-rail; coupling element fixed to C-rail

    Beispiel: Winkelsteg mit Gleitschuh und C-Schiene, Gleitschuh an C-Schiene fixiert Fixierte C-Schiene mit Gleitschuh; Gleitschuh an Schiene fixiert Example: Angle web with sliding block and C-rail; sliding box fixed to C-rail

    Beispiel: Flachstahl mit angenieteter U-Schiene Example: Flat steel riveted to U-rail

    Beispiel: Flachstahl mit C-Schiene und Koppelelement; Koppelelement in Schiene verschiebbar Example: Flat steel with C-rail and coupling element; coupling element sliding in rail

    Festschiene an Feststeg / Fixed rail on fixed web

    Festschiene an Lossteg (aus Flachstahl) / Fixed rail on sliding web (made of flat steel)

    1.5.25 Web

    Fixed webFixed webs are rigid in all directions and always firmly connected to the object.

    Sliding webSliding webs are characterised by the fact that head- and foot point are traversable against each other.

    Sliding webs can be bent in at least one direction. At plane sur-faces they are preferably firmly connected to the object, at pipes on the contrary, they are preferably firmly connected to the ring or the bar.

    1.6 Standards, Working Documents

    DIN 4140 Insulation work on operational installations in industry and in the technical building equipment Execution of thermal and cold insulations.

    VDI 2055 Thermal insulation of heated and refrigerated operational installations in industry and in the technical building equipment.

    AGI Working DocumentsQ 02 Insulation on industrial installations;

    Terminology Q 03 Thermal insulation; Execution of thermal and

    cold insulations; Insulation work on industrial installations

    Q 05 Design of industrial installations; Principles, de-sign, requirements for the intersection between installation components and insulation

    Q 153 Mountings for support constructions

    AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 5 / Seite 5

  • 2 Stoffe

    2.1 Allgemeines

    Die Stoffe mssen den zu erwartenden Beanspruchungen gen-gen. Wichtige Kriterien bei der Auswahl der Stoffe sind z. B. die mechanischen Eigenschaften unter Einwirkung von Temperatur, chemischen Einflssen und/oder Feuchte.

    2.2 Sthle

    Fr Trag- und Sttzkonstruktionen sind bei Temperaturen ber 300 C warmfeste bzw. hitzebestndige Sthle einzusetzen.

    2.3 Holz

    Fr Trag- und Sttzkonstruktionen aus Holz muss Hartholz Gte-klasse I nach DIN 68368 verwendet werden.

    2.4 Kunststoffe

    Fr Sttzkonstruktionen aus Kunststoffen knnen Hartschu-me, z. B. aus Polyurethan oder Polystyrol, verwendet werden. PE-Kunststoffe mit hoher Dichte finden in Form von Noppen-bahnen als Abstandshalter Anwendung.

    2.5 Keramische Stoffe

    Keramische Stoffe knnen nur Druckkrfte bertragen. Sie sind nur fr Sttzkonstruktionen geeignet.

    2.6 Dmmstoffe

    Fr Tragkonstruktionen sind Dmmstoffe im Allgemeinen nicht geeignet.

    Dmmstoffe, die Druckkrfte ausreichend aufnehmen knnen, z. B. Formstcke aus Mineralwolle, Calciumsilikat, Schaumglas, Kunststoff-Hartschumen, erbrigen eine Sttzkonstruktion, wenn kein Luftspalt erforderlich ist.

    2.7 Stoffe fr Trennschichten

    Als Trennschichten werden z. B. Glasgewebe, gebundene orga-nische Stoffe, Aluminiumsilikate und Kunststoffe eingesetzt.

    3 Unterkonstruktions-Systeme

    3.1 Allgemeines

    Im nachfolgenden Bild 2 ist die prinzipielle Funktion der Trag- und der Sttzkonstruktion dargestellt.

    Im oberen Teil des Bildes ist eine Sttzkonstruktion dargestellt. Dort ist ein Steg als Abstandshalter und ein formgebendes Ele-ment (Ring, Schiene) montiert, mit dem die Ummantelung ver-bunden sein kann.

    Im unteren Teil des Bildes ist eine Tragkonstruktion dargestellt. Dort ist eine an der Objektwand angeschweite Halterung nach AGI-Arbeitsblatt Q 153 angebracht. Damit kraftschlssig verbun-den ist ein Steg als Abstandshalter und ein formgebendes Ele-ment (Ring, Schiene), mit dem die Ummantelung verbunden ist.

    Die Bilder 3 a bis 3c zeigen schematische Darstellungen der An-ordnung von Unterkonstruktionen bei unterschiedlichen Objekt-geometrien.

    3.2 Ausfhrungsmglichkeiten

    Nachfolgend sind Ausfhrungsmglichkeiten der Einzelkom-ponenten von Trag- und Sttzkonstruktionen dargestellt. Da es viele Ausfhrungsvarianten gibt, sind hier gngige Anwendungen aufgefhrt. Im Anwendungsfall werden diese Komponenten zu einem System kombiniert.

    Schalldmmungen mssen hinsichtlich der Schallquellen, Fre-quenzen, Schallarten etc. gesondert betrachtet werden.

    Seite 6 / Page 6 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

    2 Materials

    2.1 General

    Materials shall satisfy the expected requirements. Important crite-ria when choosing materials are e.g. mechanical properties under the influences of temperature, chemicals, and/or moisture.

    2.2 Steels

    Heat-resistant respectively heat-proof steels shall be employed for support- and spacer-ring constructions where temperatures exceed 300 C.

    2.3 Wood

    For wooden support- and spacer-ring constructions hardwood of Quality class I acc. to DIN 68368 shall be used.

    2.4 Plastics

    For plastic spacer-ring constructions, rigid foams may be used, e.g. made of polyurethane or polystyrene. PE-plastics with elevated densities in the form of knob-foils are being used as distancers.

    2.5 Ceramic Material

    Ceramic materials can only transfer pressure loads. They are fit only for spacer-ring constructions.

    2.6 Insulation materials

    In general, insulation materials are not suitable for support constructions.

    Insulants with sufficient compressive strength, e.g. form pieces of mineral wool, calcium silicate, cellular glass, rigid plastic foam allow for the dispensation of spacer-ring constructions where no air space is required.

    2.7 Materials for separating layers

    To serve as separating layers, e.g. glass tissue, bonded organic materials, aluminium silicate, and plastics are being employed.

    3 Subconstruction systems

    3.1 General

    In Figure 2 below, the fundamental functions of support and spacer-ring constructions have been presented.

    In the upper portion of the figure, a spacer-ring construction is shown. There, a web is mounted as distancer, and a shaping ele-ment (ring, bar) with which the cladding may be connected.

    In the lower portion of the figure, a support construction is shown. A mounting support acc. to AGI Working Document Q 153, is welded to the object wall. Force-closed connected to it is a web as distancer and a shaping element ( ring, bar) with which the cladding is connected.

    The figures 3a through 3c show schematic drawings of the placing of subconstructions at different object geometries.

    3.2 Execution Possibilities

    Below, possible designs of the individual components of support and spacer-ring constructions are shown. Since a large variety of designs exists, only generally applicable executions have been presented. For operational installations, these components are being combined to a system.

    Acoustic insulations must be considered separately concerning sources of sound, frequencies, types of noise etc.

  • Bild 3a: Tragschienen / Figure 3a: Supporting bars

    Bild 2: Funktion der Trag- und Sttzkonstruktion / Figure 2: Functioning of support- and spacer-ring constructions

    08 Nocke/Halterung / Support

    07 Ummantelungsblech / Cladding (steel)

    05 Trennschicht / Separating layer

    04 Auenring / External ring

    03 Innenring / Inner ring

    02 Steg / Web

    01 Objektwand / Object

    Pos. Benennung / Designation

    F = Kraft / ForceFG = Gewicht der Dmmung (Dmmstoff, Ummantelung, Unterkonstruktion) / Weight of insulation system (insulant, cladding, sub-construction)

    AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 7 / Seite 7

    formgebendes Element, Pos. 04 formgiving element, pos. 04

    Stege am Objekt angeschweit Webs welded to the object

    Sttzkonstruktion Spacer-ring construction

    Tragkonstruktion Support construction

    geschweit welded

    Verbindung Schiene mit Steg Fixing bar to web

    Trennstelle der Schienen Separation points in bars

    Tragschiene Supporting bar

  • 3.2.1 Befestigung am Objekt

    Die wesentlichen Mglichkeiten fr die Befestigung von Ringen und Stegen am Objekt sind:

    Anschrauben an Halterungen nach AGI-Arbeitsblatt Q 153

    Auflegen auf Halterungen nach AGI-Arbeitsblatt Q 153

    Anschweien am Objekt Auflegen auf vorhandene Konstruktionsteile

    wie z. B. Versteifungsringe

    3.2.2 Verbindung der Komponenten einer Unter- konstruktion

    Die Verbindungsstellen der Stege untereinander und der Stege sind meistens verschraubt oder genietet. Gleiches gilt fr die Ver-bindung der Stege aus Flachstahl und Ringen; sie knnen auch verschweit werden. Bei Stegen aus rundem Material werden sie hufig in die Ringe eingeklemmt.

    Die Endstellen der Ringsegmente werden meist miteinander verschraubt, mit oder ohne Federelement. Sie knnen auch mit Rdeldraht verbunden werden. Diese Verbindungen drfen nur hergestellt werden, wenn hier fr die Ummantelung keine Schie-benhte vorgesehen sind.

    Sollen Endstellen von Schienen miteinander verbunden werden, erfolgt dies in der Regel durch Verschraubung. Diese Verbin-dungen drfen nur hergestellt werden, wenn hier fr die Umman-telung keine Schiebenhte vorgesehen sind.

    Bild 3b: Trag- und Sttzring Figure 3b: Thrust collars and backing rings

    Bild 3c: Tragschiene am horizontalen Objekt Figure 3c: Supporting bar at horizontal object

    Seite 8 / Page 8 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

    Sttzring Backing ring

    Tragschiene Supporting bar

    Tragkonstruktion mittels Doppelspann-ring auf Halterungen gelegt Support construction as double locking ring put on mounting supports

    Nocken Supports

    Fertigung je nach Objektumfang in zwei oder mehreren Teilen manufacturing depending on object circumference in two or several pieces

    Mit entsprechender Verbindung der Ringendstellen With connection at the ends of the rings

    3.2.1 Fastening at the object

    The principal possibilities to fix rings and webs at the object are:

    screwing to mounting supports acc. to AGI Working Document Q 153

    putting on mounting supports acc. to AGI Working Document Q 153

    welding to the object putting on existing construction components

    such as stiffening rings

    3.2.2 Fastening the components of a sub construction to Each other

    The connection points of the webs with each other are commonly be screwed or riveted. The same applies to the connection of flat-steel webs with rings, they may also be welded. Round profile webs are frequently clamped into the rings.

    The ends of ring sections are most frequently screwed to each other, with or without a suspension element. They may also be connected with tie wire. These connections may only be made where no sliding seam is foreseen in the cladding.

    Where the ends of bars are to be connected, this is normally done by screwing. These connections may only be made where no sliding seam is foreseen in the cladding.

  • Bild 4: Befestigungsmglichkeiten am Objekt / Figure 4: Fastening possibilities at the object

    AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 9 / Seite 9

    Seitenansicht / side view

    Draufsicht / top view

    Seitenansicht / side view

    Draufsicht / top view

    Seitenansicht / side view

    Draufsicht / top view

    Seitenansicht / side view

    Draufsicht / top view

    Seitenansicht / side view

    Draufsicht / top view

    12 Versteifungsring / Vacuum ring

    11 Winkelstck / Angle bar

    10 Z-Bgel / Z-handle

    09 Dehnungsbgel / Expansion handle

    08 Nocke/Halterung / Support

    07 Ummantelungsblech / Cladding (steel)

    06 U-Profil/Schiene / U-rail

    05 Trennschicht / Separating layer

    04 Auenring / External ring

    03 Innenring / Inner ring

    02 Steg / Web

    01 Objektwand / Object wall

    Pos. Benennung / Designation

  • 4 Trag- und Sttzkonstruktionen

    4.1 Allgemeines

    Trag- und Sttzkonstruktionen aus metallischen Werkstoffen ha-ben auf Grund ihrer hohen Wrmeleitfhigkeit Auswirkungen auf die Oberflchentemperatur:

    a) an der Ummantelung rtlich hhere Oberflchentemperaturen (Berhrungsschutz).

    b) von der Objektwand mit z. B. der Gefahr der Taupunktunter-schreitung bei Rauchgasen durch lokale Temperaturabsen-kung.

    Siehe hierzu auch VDI 2055 Blatt 3.

    Die Anforderungen hinsichtlich trittfester Dmmung sind nicht allein mit dem Vorhandensein einer Trag- oder Sttzkonstruktion zu erfllen. Lsungen hierzu bieten sich an durch den Einsatz von z. B. druckfesten Dmmstoffen oder druckverteilenden Verble-chungen.

    4.2 Tragkonstruktionen

    4.2.1 Funktion

    Tragkonstruktionen bertragen die Eigenlast des Dmm-systems und die auf das Dmmsystem einwirkenden Krf-te ber Halterungen oder direkt auf das Objekt. Sie sind in der Regel aus metallischen Werkstoffen und stellen dmm-technisch bedingte Wrmebrcken im Dmmsystem dar. Tragkonstruktionen knnen auch aus anderen Materialien wie Holz, Kunststoff oder druckfesten Dmmstoffen gefertigt werden.

    Stoffe und Konstruktionen mssen die statischen und dyna-mischen Anforderungen erfllen und unter wirtschaftlichen As-pekten den Wrmestrom so gering wie mglich halten.

    4.2.2 Arten

    Tragkonstruktionen knnen direkt an das Objekt ange-schweit, an Halterungen angeschraubt/angenietet bzw. da-rauf aufgelegt werden oder sind auf das Objekt geklemmt. Entsprechende Darstellungen sind den Bildern 6 bis 13 zu ent-nehmen.

    4.2.3 Anordnung und Dimensionen

    Anordnung und Dimensionen von Tragkonstruktionen sind vom Objekt, den zu bertragenden Krften, der Dmmschichtdicke, dem Dmmstoff, dem gewhlten Werkstoff und den Betriebsbe-dingungen abhngig. Dabei mssen neben den statischen und dynamischen Krften, z. B. Windlasten, auch die temperaturbe-dingten Formnderungen des Objektes und der Tragkonstruktion bercksichtigt werden. Ferner knnen betriebsbedingte Formn-derungen auftreten, z. B. beim Befllen von Tanks.

    Die Anordnung der Tragkonstruktion richtet sich auerdem nach der Form des Objektes, den auftretenden Lngennderungen, den am Objekt vorhandenen Halterungen (siehe Q 153) und dem gewhlten Ummantelungsmaterial. Planungsseitig ist eine Anordnung anzustreben, bei der Kollisionen mit Anbauteilen, z. B. Mannlchern oder Stutzen des Objektes vermieden werden.

    Zur Optimierung sind sowohl Kombinationen unterschiedlicher Arten von Tragkonstruktionen als auch Kombinationen von Trag- und Sttzkonstruktionen mglich.

    Fr die Lastannahmen gelten neben der Eigenlast des Dmmsy-stems die DIN EN 1991. Bei profilierten Ummantelungsblechen sind die zulssigen Sttzweiten aus den Tabellen der Hersteller zu entnehmen.

    Ringe und Stege sind aus Bandstahl von mindestens 30 mm x 3 mm anzufertigen, Blech-Profile mit mindestens 1 mm Dicke bei Stahlblechen sowie 0,8 mm bei nichtrostenden austenitischen Stahlblechen. Bei geringeren Dicken ist ein statischer Nachweis zu fhren.

    Doppelspannringe als Klemmringe sind eine Sonderform der Tragringe, die nur in Ausnahmefllen bei Nichtvorhandensein von Halterungen nach Q 153 zur Ausfhrung kommen. Dabei ist zu

    4 Support and spacer-ring constructions

    4.1 General

    Support and spacer-ring constructions made of metal materials, because of their high thermal conductivity, effect the surface tem-perature:

    a) at the cladding locally elevated surface temperatures (person-nel protection)

    b) at the object wall, causing e.g. the danger of local tempera-tures below dew-point of flue gases through local temperature decrease.

    See also VDI 2055 Part 3.

    The requirements regarding walk-on insulation cannot be met alone with the presence of a support or spacer-ring construction. Solutions are possible with the employment of e.g. compression resistant insulants or pressure distributing sheet metal.

    4.2 Support constructions

    4.2.1 Function

    Supporting constructions transfer the weight of the insulation system and the loads bearing on it via mounting supports or di-rectly onto the object. Generally they are made of metallic ma-terials and constitute insulation related thermal bridges in the insulation system. Support constructions can also be made of other materials, such as wood, plastic material or compression resistant insulation materials.

    Materials and designs must meet the static and dynamic requi-rements and keep the heat flow rate under economic aspects as low as possible.

    4.2.2 Types

    Supporting constructions may be directly welded to the object, screwed or riveted to mounting supports, respectively put on them, or they are clamped to the object. Related presentations are given in Figures 6 through 13.

    4.2.3 Positioning and Dimensions

    Positioning and dimensions of supporting constructions are de-pendent upon the object, the loads that need to be transferred, the insulation layer thickness, the insulation material, and the operating conditions. Here, next to the static and dynamic forces, e.g. wind loads, temperature dependent changes in the shape of the object and the support construction must be considered too. Additionally, shape changes may be operation-related, e.g. the filling of tanks.

    The positioning of the supporting construction is also governed by the shape of the object, occurring changes in its length, the mounting supports that exist on the object (see Q 153), and the cladding material chosen. The design must aim at a positioning that avoids collisions with fixings, e.g. man-holes, or taps at the object.

    For optimization purposes, combinations of different types of support constructions are possible as well as combinations of supporting and spacer-ring constructions.

    For the loading assumptions, next to the weight of the system itself, DIN EN 1991 apply. For profiled cladding sheet metal the support distance given in the manufacturers literature shall be heeded.

    Rings and webs shall be made of strip steel of at least 30 mm x 3 mm; sheet profiles have a minimum thickness of 1 mm for steel and 0,8 mm for stainless austenitic steel sheets. At lower thick-nesses, a static proof shall always be provided.

    Double locking rings/clamping rings are a special form of sup-porting rings, which shall only be employed in exceptional cases in the absence of mounting supports acc, to Q 153. It shall be

    Seite 10 / Page 10 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

  • AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 11 / Seite 11

    beachten, dass der Kraftschluss zum Objekt bei allen Betriebszu-stnden gewhrleistet ist, um ein Abrutschen zu vermeiden.

    Bei Temperaturen ber 300 C sind warmfeste bzw. hitzebestn-dige Sthle einzusetzen.

    4.2.4 Tragkonstruktionen fr Wrmedmmung

    4.2.4.1 Allgemeines

    Tragkonstruktionen fr Wrmedmmungen bestehen aus metallischen Tragringen oder Schienen und Stegen. Tragkonstruktionen mit einem Ring werden im allgemeinen an Halterungen befestigt oder aufgelegt oder unmittelbar an das Objekt geschweit (siehe Punkt 1.4.1). Tragkonstrukti-onen mit Doppelspannring werden auf Halterungen gelegt. Schienen werden im Allgemeinen ber Stege an Halterungen befestigt. Die Stege knnen auch unmittelbar an das Objekt ge-schweit sein.

    4.2.4.2 Ausfhrung

    Die Ausfhrung richtet sich nach einer Vielzahl von Bedingungen. Wesentliche Bedingungen und Fragen sind:

    a) Art, Geometrie und Lage des Objektesb) Sind Schweiarbeiten am Objekt erlaubt?c) Sind Halterungen nach Arbeitsblatt Q 153 vorhanden?

    d) Wie gro ist die Differenzdehnung zwischen Objekt und Ummantelung?

    e) Welche aufzunehmenden Lasten aus dem Dmmsystem treten auf?

    f) Welche auf die Dmmung einwirkenden Lasten treten auf?g) Art des Dmmsystems und der Ummantelungh) Gibt es Anforderungen z. B. hinsichtlich des Schallschutzes?

    i) Ist der Schutz der Tragkonstruktion gegen Korrosion erforder-lich?

    j) Kann Kontaktkorrosion auftreten?

    Stege knnen an die Tragringe oder Tragschienen geschweit, geschraubt, genietet, geklemmt oder formschlssig verbunden werden.

    Zwischen Auftraggeber und Auftragnehmer ist zu vereinbaren, ob und wie Tragkonstruktionen gegen Korrosion zu schtzen sind. Siehe hierzu AGI-Arbeitsblatt Q 151.

    Die Bilder 6 bis 13 zeigen Ausfhrungsvarianten fr Objekte, die berwiegend die Bedingungen a), b), c) und d) bercksichtigen.

    Fr flchige Objekte ist in den Bildern 17 und 18 eine schema-tische Anordnung der Schienen einer Tragkonstruktion darge-stellt, mit Bezeichnung der Steg- und Schienenart in Los- oder Festausfhrung, zur Aufnahme der Dehnungsdifferenzen. Das Bild 19 ergnzt letzteres mit Ausfhrungsbeispielen.

    Bei groen Durchmessern kann es erforderlich sein, zwischen den vorhandenen Tragkonstruktionen Sttzkonstruktionen unter den Rundnhten anzuordnen.

    4.2.5 Tragkonstruktion fr Kltedmmungen

    4.2.5.1 Allgemeines

    Tragkonstruktionen fr Kltedmmungen knnen je nach sta-tischen Erfordernissen aus Holz, Kunststoff, Dmmstoff, Metall oder aus Kombinationen dieser Werkstoffe hergestellt werden. Die Distanzstcke sollten aus Materialien mit niedriger Wrme-leitfhigkeit bestehen und umlaufend angebracht werden.

    4.2.5.2 Ausfhrung

    Es gilt Abschnitt 4.2.4.2 sinngem, jedoch mssen die Trag-konstruktionen gegen Korrosion geschtzt werden. Beispiele zeigen das nachfolgende Bild 5.

    Der Vermeidung von Wrmebrcken kommt hier eine noch gr-ere Bedeutung zu als bei Wrmedmmungen, besonders we-gen der Gefahr der Eisbildung.

    observed that the the frictional connection to the object is gu-aranteed under all operational conditions, so that a downward sliding is avoided.

    Heat-resistant respectively heat-proof steels shall be employed where temperatures exceed 300 C.

    4.2.4 Support constructions for hot insulations

    4.2.4.1 General

    Support constructions for hot insulations consist of metal support rings or bars and webs. Supporting constructions with a ring are generally fastened or put onto mounting supports, or welded di-rectly to the object ( see Chapter 1.4.1 ). Supporting constructions with double campling rings are being put on mounting supports. Bars are generally fastened to mounting supports with webs. The webs may also be welded directly to the object.

    4.2.4.2 Execution

    The execution is dependent upon a variety of conditions. Crucial conditions and questions are:

    a) type, geometry and position of the objectb) is welding at the object permitted?c) are mounting supports acc. to Working Document Q 153

    available?d) how large is the expansion difference between the object and

    the cladding?e) which loads from the insulation system need to be borne?

    f) which loads come to bear onto the insulation system?g) type of the insulation system and the claddingh) are there any requirements, e.g. concerning acoustic protec-

    tion?i) does the supporting construction require corrosion protec-

    tion?j) could contact corrosion occur?

    Webs may be welded, screwed, riveted, clamped or positively connected to the support rings or bars.

    It must be agreed between client and contractor, if and how sup-porting constructions shall be protected against corrosion. See in this context AGI Working Document Q 151.

    Figures 6 through 13 show execution examples for objects which are predominantly geared to conditions b), c), and d).

    For plane objects, a schematic positioning of the bars of a sup-porting construction is shown on Figures 17 and 18, giving also the terms for the types of webs and bars as fixed and sliding, to accommodate expansion differences. Figure 19 completes the latter with execution examples.

    For large diameters it can be required, to position spacer-ring constructions under the circular seams between the existing sup-porting constructions.

    4.2.5 Support constructions for cold insulations

    4.2.5.1 General

    Support constructions for cold insulations may be made of wood, plastic material, insulation material, or a combination of these, dependent upon the static requirements. The distance pieces should be made of materials with a low thermal conductivity and be mounted all around.

    4.2.5.2 Execution

    Section 4.2.4.2 applies analogously, however, support construc- tions must be protected against corrosion. Examples are given in Figure 5 below.

    Avoiding thermal bridges is even more important than in hot Insu-lations, specifically because of ice formation danger.

  • Luftspalt / air space

    Luftspalt / air space

    Luftspalt / air space

    Luftspalt / air space

    Luftspalt / air space

    berdeckung des Tragringes z. B. mit 1/3 der Dmmstrke covering of the thrust collars for example with 1/3 of the thickness of the insulation

    umlaufend, vollflchig verklebt circulating full-laminar sticked

    berdeckung des Tragringes z. B. mit 1/3 der Dmmstrke covering of the thrust collars for example with 1/3 of the thickness of the insulation

    berdeckung des Tragringes z. B. mit 1/3 der Dmmstrke covering of the thrust collars for example with 1/3 of the thickness of the insulation

    Bild 5: Beispiele fr die Ausfhrung von Tragkonstruktionen bei Kltedmmungen Figure 5: Examples for the execution of support constructions in cold insulations

    Seite 12 / Page 12 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

    06 Dampfbremse / Vapour retarder

    05 Dmmstoff / Insulation material

    04 Auenring / External ring

    03 Innenring / Inner ring

    02 Steg / Web

    01 Objektwand / Object wall

    Pos. Benennung / Designation

    12 Noppenfolie / Knob foil strip

    11 Kleber / Glue

    10 Hartschaum / Rigid foam

    09 Druckverteilungsblech / Pressure distribution sheet metal

    08 Nocke/Halterung / Support

    07 Ummantelungsblech / Cladding (steel)

    Pos. Benennung / Designation

  • AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 13 / Seite 13

    4.3 Sttzkonstruktionen

    4.3.1 Funktion

    Sttzkonstruktionen halten die Ummantelung im vorgesehenen Abstand vom Objekt, wenn der Dmmstoff diese Aufgabe nicht bernehmen kann. Sie sind nicht zu vermeidende dmmtech-nisch bedingte Wrmebrcken und knnen zu rtlich abwei-chenden Oberflchentemperaturen fhren, soweit sie nicht aus Dmmstoffen mit annhernd gleicher Dmmwirkung herge-stellt werden oder sie sich nicht auf dem Dmmstoff absttzen. Sie knnen nur senkrecht zur Objekt- bzw. Dmmoberflche wir-kende Krfte bertragen.

    Sttzkonstruktionen sind erforderlich bei Dmmstoffen mit ge-ringer Druckbelastbarkeit, z. B. bei Mineralwollematten. Bei klei-neren Nennweiten- und Dmmschichtdicken kann auf die Sttz-konstruktion verzichtet werden. Entsprechende Hinweise sind den Tabellen 2 bis 12 zu entnehmen.

    Bei Dmmsystemen mit Luftspalt sind immer Sttzkonstruk-tionen erforderlich. In Abhngigkeit vom eingesetzten Dmm-stoffes knnen sich die Abstandshalter auf einem Dmmstoff mit gengender Festigkeit absttzen. Entsprechende Hinweise sind den Anwendungsfllen in den nachfolgenden Abschnitten zu entnehmen.

    Bei besonderen Betriebsbedingungen, z. B. Vibrationen, knnen Sttzkonstruktionen auch bei druckfesten Dmmstoffen erfor-derlich sein.

    4.3.2 Arten

    Sttzkonstruktionen sttzen in der Regel direkt auf das Objekt ab. Beim Einsatz druckfester Dmmstoffe kommt als Sonderform ein Abstandshalter zur Ausfhrung, der auf dem Dmmstoff ab-sttzt.

    Sttzkonstruktionen werden meist ber den gesamten Umfang montiert. Zur Kostenoptimierung sind auch Teillsungen mg-lich, z. B. als sogenannte Drittellsung bei waagerechten Lei-tungen, im oberen Drittel als Auflager angebracht.

    4.3.3 Erfordernis von Sttzkonstruktionen

    Zur wrmetechnischen Optimierung der Dmmsysteme und zur Kostenoptimierung ist der Einsatz von Sttzkonstruktionen nur dort einzuplanen und auszufhren, wo er unbedingt erforderlich ist.

    Um hier Planungshilfen bzw. Ausfhrungsempfehlungen zu geben, sind auf Basis vorliegender Erfahrungen und unterstt-zender Versuchsmontagen nachfolgend Anwendungen genannt, bei denen auf die Sttzkonstruktion verzichtet werden kann. Be-rcksichtigt sind die blichen Lastannahmen wie Gewicht der Ummantelung und Windlasten.

    4.3.3.1 Betrachtung nach Anwendungsfllen

    Zur besseren Darstellung sind die Anwendungen wie folgt grup-piert. Die unterschiedlichen Dmmstoffe sind in den nachfol-genden Tabellen bercksichtigt.

    4.3 Spacer-ring constructions

    4.3.1 Function

    Spacer-ring constructions keep the cladding in the intended dis-tancefrom the object, where the insulant cannot do this. They are unavoidable insulation related thermal bridges, and may lead to local deviations of the surface temperature unless they are made of insulation material of almost equal performance or are sup-ported by the insulation material. They can only transfer loads vertically to the object respectively the insulation material surface.

    Spacer-ring constructions are required where insulants possess a low compressive strength, e.g. mineral wool mats. At lower dia-meters and insulation layer thicknesses even here spacer-ring constructions may be dispensed with. Related advice is given in Tables 2 through 12.

    Spacer-ring constructions are always required in insulation systems with an air space. Dependent upon the insulation ma-terial employed, distancers (by definition part of a spacer-ring construction) may be supported by an insulation material of suffi-cient strength. Related advice is given in the execution examples in the subsequent chapters.

    Where special operation conditions prevail, e.g. vibrations, spacer-ring constructions may even be required with compressi-on resistant insulation materials.

    4.3.2 Types

    Spacer-ring constructions are normally directly supported by the object. Where compression resistant insulation material is being used, a special form of distancer is executed, which is supported by the insulation material.

    Spacer-ring constructions are generally mounted around the en-tire perimeter. For reasons of cost optimization partial solutions are also possible, e.g. so-called one-third solutions at horizontal pipes, mounted at the upper third of the perimeter as bearing.

    4.3.3 Requirement of spacer-ring constructions

    To ensure optimal thermal performance of insulation systems and to minimize expenditure, the employment of spacer-ring constructions shall only be planned and executed, where abso-lutely required.

    To provide planning aids, respectively recommendations for the execution, usages have been determined hereafter on the basis of existing experience and supporting trials, where spacer-ring constructions may be dispensed with. Standard load assump-tions have been used, i.e. weight of the cladding and wind loads.

    4.3.3.1 Discussion of application examples

    For better representation, the applications have been grouped as follows. The different insulation materials are considered in the tables below.

  • Anwendungsfall Application examples

    Wrme/Klte / Heat/Cold

    Verlauf / Process

    Form / Form

    Umfang/Kantenlnge / Perimeter/side length

    Luftspalt / Air gap

    1a

    Wrme / Heat

    o 2000 mm nein / no

    1b I o 2000 mm nein / no

    2a o 2000 mm ja / yes

    2b I o 2000 mm ja / yes

    3 o + > 2000/> 500 mm nein / no

    4 I o + > 2000/> 500 mm nein / no

    5a o > 2000 mm ja / yes

    5b I o > 2000 mm ja / yes

    5c > 500 mm ja / yes

    6

    Klte / Cold

    + I o 2000 mm nein / no

    7 + I o 2000 mm ja / yes

    8 + I o + > 2000/> 500 mm nein / no

    9 + I o + > 2000/> 500 mm ja / yes

    Tabelle 1: bersicht der Anwendungsflle zur Betrachtung der Erfordernis von Sttzkonstruktionen Table 1: Overview of application examples to consider the requirement of spacer-ring constructions

    Seite 14 / Page 14 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

  • AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 15 / Seite 15

    In bestimmten Nennweiten- und Dmmschichtdickenbereichen knnen auch nicht druckfeste Dmmstoffe durch ihre Steifigkeit, Faseranordnung und Rohdichte die Funktion der Sttzkonstruk-tion bernehmen. Dies ist in den nachfolgenden Tabellen darge-stellt.

    Wrme Runde Leitungen, runde Kanle, Behlter U 2000 mm waagerecht ohne Luftspalt Heat Round pipes, round ducts, vessels: diameter 2000 mm horizontal without air gap

    In certain ranges of diameters and insulation layer thicknesses, even insulants that are not compression resistant, can function as spacer-ring constructions because of their stiffness, fibre ori-entation and apparent density. This is shown in the tables below.

    4.3.3.1.1 Anwendungsfall 1a 4.3.3.1.1 Application example 1a

    Tabelle 2: Verzicht auf die Sttzkonstruktion beim Anwendungsfall 1a, Dmmstoff Mineralwolle-Drahtnetzmatte nach AGI-Arbeitsblatt Q 132 Table 2: Managing without spacer-ring constructions in the application example 1a, insulation material mineral wool wired mat acc. to AGI Working document Q 132

    Nennweite Diameter

    Dmmschichtdicke s in mm Insulation layer thickness s in mm

    DN 30 40 50 60 70 80 90 100 >100

    25 200 X X X X X X X X

    250 X X X X X X X

    300 X X X X X X

    350 X X X X

    400 X X X

    Tabelle 3: Verzicht auf die Sttzkonstruktion beim Anwendungsfall 1a, Dmmstoff Mineralwolle-Lamellenmatte nach AGI-Arbeitsblatt Q 132 Table 3: Managing without spacer-ring constructions in the application example 1a, insulation material mineral wool lamella mat acc. to AGI Working document Q 132

    Nennweite Diameter

    Dmmschichtdicke s in mm Insulation layer thickness s in mm

    DN 30 40 50 60 70 80 90 100 >100

    25 200 X X X X X X X X

    250 X X X X X X X X

    300 X X X X X X X X

    350 X X X X X X X X

    400 X X X X X X

    Tabelle 4: Verzicht auf die Sttzkonstruktion beim Anwendungsfall 1a, Dmmstoff Mineralwolle-Lamellenmatte druckfest nach AGI-Arbeitsblatt Q 132 Table 4: Managing without spacer-ring constructions in the application example 1a, insulation material mineral wool lamella mat compression resistant acc. to AGI Working document Q 132

    Nennweite Diameter

    Dmmschichtdicke s in mm Insulation layer thickness s in mm

    DN 30 40 50 60 70 80 90 100 >100

    400 X X X X X X X X X

    At smaller diameters the compression resistant lamella mat cannot be applied because of its stiffness.

    Bei kleinen Nennweiten ist die druckfeste Lamellenmatte auf Grund ihrer Steifigkeit nicht montierbar.

    Tabelle 5: Verzicht auf die Sttzkonstruktion beim Anwendungsfall 1a, Rohrschale aus Mineralwolle mit Ausnahme der Mineralwolle-Rohrschalen mit Rohdichten < 75 kg/m3 bei Betriebstemperaturen > 200 C Table 5: Managing without spacer-ring constructions in the application example 1a, insulation material mineral wool pipe sections, excepting mineral wool pipe sections with apparent densities < 75kg/m at operating temperatures > 200 C

    Nennweite Diameter

    Dmmschichtdicke s in mm Insulation layer thickness s in mm

    DN 30 40 50 60 70 80 90 100 >100

    400 X X X X X X X X X

    X = Verzicht auf die Sttzkonstruktion X = Managing without spacer-ring constructions

  • Seite 16 / Page 16 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

    4.3.3.1.2 Application example 1b4.3.3.1.2 Anwendungsfall 1b

    Wrme Runde Leitungen, runde Kanle, Behlter U 2000 mm senkrecht ohne Luftspalt Heat Round pipes, round ducts, vessels: diameter 2000 mm vertical without air gap

    For the products

    mineral wool wired mats acc. to AGI Working Document Q 132, mineral wool lamella mats acc. to AGI Working Document

    Q 132, compression resistant mineral wool lamella mats acc. to

    AGI Working Document Q 132, mineral wool pipe sections acc. to

    AGI Working Document Q 132

    Spacer-ring constructions can generally be dispensed with.

    Bei den Produkten

    Mineralwolle-Drahtnetzmatte nach AGI-Arbeitsblatt Q 132 Mineralwolle-Lamellenmatte nach AGI-Arbeitsblatt

    Q 132 Mineralwolle-Lamellenmatte druckfest nach AGI-Arbeitsblatt

    Q 132 Rohrschalen aus Mineralwolle nach AGI-Arbeitsblatt

    Q 132

    kann auf die Sttzkonstruktion verzichtet werden.

  • AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 17 / Seite 17

    4.3.3.1.3 Anwendungsfall 2a 4.3.3.1.3 Application example 2a

    Wrme Runde Leitungen, runde Kanle, Behlter U 2000 mm waagerecht mit Luftspalt Heat Round pipes, round ducts, vessels: diameter 2000 mm horizontal with air gap

    In certain ranges of diameters and insulation layer thicknesses, even insulants that are by definition not compression resistant, can function as spacer-ring constructions because of their stiff-ness, fibre orientation and apparent density.

    In this application example, therefore, a distancer supported by the object can be dispensed with. The air space is created through different types of distancers, supported by the insulation material. This is shown in the tables below.

    In bestimmten Nennweiten- und Dmmschichtdickenbereichen knnen auch nicht druckfeste Dmmstoffe durch ihre Steifigkeit, Faseranordnung und Rohdichte die Funktion der Sttzkonstruk-tion bernehmen.

    Deshalb kann in diesem Anwendungsfall auf den Abstands-halter zum Objekt verzichtet werden. Der Luftspalt wird durch Abstandshalter unterschiedlicher Art zum Dmmstoff erzeugt. Dies ist in den nachfolgenden Tabellen dargestellt.

    Tabelle 6: Verzicht auf Abstandshalter zum Objekt beim Anwendungsfall 2a, Dmmstoff Mineralwolle-Drahtnetzmatte nach AGI-Arbeitsblatt Q 132, Art der Abstandshalter zum Dmmstoff: Noppenfolie vollflchig Table 6: Managing without spacer-ring constructions in the application example 2a, insulation material mineral wool wired mat acc. to AGI Working Document Q132, type of distancer to the insulant: nap foil full surface.

    Nennweite Diameter

    Dmmschichtdicke s in mm Insulation layer thickness s in mm

    DN 30 40 50 60 70 80 90 100 >100

    25 200 X X X X X X X X

    250 X X X X X X X

    300 X X X X X X

    350 X X X X

    400 X X X

    Nennweite Diameter

    Dmmschichtdicke s in mm Insulation layer thickness s in mm

    DN 30 40 50 60 70 80 90 100 >100

    400 X X X X X X X X

    Tabelle 7: Verzicht auf Sttzkonstruktion beim Anwendungsfall 2a, Dmmstoff Mineralwolle-Lamellenmatte, Art der Abstandshalter zum Dmmstoff: Noppenfolie vollflchig Table 7: Managing without spacer-ring constructions in the application example 2a, insulation material mineral wool lamella mat, type of distancer to the insulant: nap foil full surface

    Nennweite Diameter

    Dmmschichtdicke s in mm Insulation layer thickness s in mm

    DN 30 40 50 60 70 80 90 100 >100

    400 X X X X X X X X X

    Tabelle 8: Verzicht auf Sttzkonstruktion beim Anwendungsfall 2a, Dmmstoff Mineralwolle-Lamellenmatte druckfest, Art der Abstandshalter zum Dmmstoff: Blechstreifen mit Wellenband oder Noppenfolienstreifen Table 8: Managing without spacer-ring constructions in the application example 2a, insulation material mineral wool lamella mat, type of distancer to the insulant: corrugated band on sheet metal strip or nap foil strips.

    Nennweite Diameter

    Dmmschichtdicke s in mm Insulation layer thickness s in mm

    DN 30 40 50 60 70 80 90 100 >100

    400 X X X X X X X X X

    Tabelle 9: Verzicht auf Sttzkonstruktion beim Anwendungsfall 2a, Rohrschale aus Mineralwolle mit Ausnahme der Mineralwolle- Rohrschalen mit Rohdichten < 75 kg/m3 bei Betriebstemperaturen > 200 C Art der Abstandshalter zum Dmmstoff: Wellenband auf Blechstreifen oder Noppenfolienstreifen Table 9: Managing without spacer-ring constructions in the application example 2a, insulation material mineral wool pipe sections, excepting mineral wool pipe sections with apparent densities < 75 kg/m at operating temperatures >200C. Type of distancer to the insulant: corrugated band on sheet metal strip or knob foil strips.

    At smaller diameters the compression resistant lamella mat cannot be applied because of its stiffness.

    Bei kleineren Nennweiten ist die druckfeste Lamellenmatte auf Grund ihrer Steifigkeit nicht montierbar.

  • Seite 18 / Page 18 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

    4.3.3.1.4 Application example 2b

    Wrme Runde Leitungen, Kanle, Behlter U 2000 mm senkrecht mit Luftspalt Heat Round pipes, ducts, vessels: diameter 2000 mm vertical with air gap

    4.3.3.1.4 Anwendungsfall 2b

    In certain ranges of diameters and insulation layer thicknesses, even insulants that are by definition not compression resistant, can function as spacer-ring constructions because of their stiff-ness, fibre orientation and apparent density. In this application example, therefore, a distancer supported by the object can be dispensed with. The air space is created through different types of distancers, supported by the insulation material.

    For the products

    mineral wool wired mats with a minimum apparent density of 80 kg/m3 acc. to AGI Working Document Q 132

    mineral wool lamella mats acc. to AGI Working Document Q 132

    compression resistant mineral wool lamella mats acc. to AGI Working Document Q 132

    mineral wool pipe sections acc. to AGI Working Document Q 132

    distancers supported by the object can generally be dispensed with. As distancers to he insulant, e.g. knob foil or corrugated sheet metal strips can be used.

    In bestimmten Nennweiten- und Dmmschichtdickenbereichen knnen auch nicht druckfeste Dmmstoffe durch ihre Steifigkeit, Faseranordnung und Rohdichte die Funktion der Sttzkonstruk-tion bernehmen. Deshalb kann in diesem Anwendungsfall auf den Abstandshalter zum Objekt verzichtet werden. Der Luftspalt wird durch Abstandshalter unterschiedlicher Art zum Dmmstoff erzeugt.

    Bei den Produkten

    Mineralwolle-Drahtnetzmatte mit mindestens 80 kg/m3 nach AGI-Arbeitsblatt Q 132

    Mineralwolle-Lamellenmatte nach AGI-Arbeitsblatt Q 132 Mineralwolle-Lamellenmatte druckfest nach AGI-Arbeitsblatt

    Q 132 Rohrschalen aus Mineralwolle nach AGI-Arbeitsblatt

    Q 132

    kann auf die Abstandshalter zum Objekt verzichtet werden. Als Abstandshalter zum Dmmstoff kommen z. B. Noppenfolie oder Wellblechstreifen in Frage.

  • AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 19 / Seite 19

    Wrme Runde Leitungen, runde Kanle, Behlter U > 2000 mm waagerecht ohne Luftspalt Heat Round pipes, round ducts, vessels: diameter > 2000 mm horizontal without air gap

    4.3.3.1.5 Application example 34.3.3.1.5 Anwendungsfall 3

    Wrme Eckige Leitungen und Kanle, U > 2000 mm waagerecht ohne Luftspalt Heat Angular pipes and ducts, diameter > 2000 mm horizontal without air gap

    Bei den gedmmten Anlagenteilen mit greren Umfngen ist in Abhngigkeit des eingesetzten Dmmstoffproduktes definiert, ob eine Sttzkonstruktion erforderlich ist oder nicht.

    For insulated installation components of larger diameters, it is defined in dependence upon the insulation product employed, whether or not a spacer-ring construction is required.

    Dmmstoffprodukt Insulation product

    Sttzkonstruktion erforderlich Spacer-ring construction required

    Mineralwolle-Drahtnetzmatte / mineralwool wired mat ja / yes

    Mineralwolle-Lamellenmatte / mineralwool lamella mat ja / yes

    Mineralwolle-Lamellenmatte druckfest / mineralwool lamella mat compression resistent nein / no

    Rohrschalen (ausgenommen Mineralwolle-Rohrschalen mit Rohdichten < 75 kg/m3 und bei Betriebstemperaturen > 200 C) / Pipe section excluded mineralwool pipe sections with apparent density < 75 kg/m3 and at operating temperatur > 200 C

    nein / no

    Tabelle 10: Erfordernis Sttzkonstruktion fr Anwendungsfall 3 Table 10: Requirement of spacer-ring construction for application example 3

    4.3.3.1.6 Application example 44.3.3.1.6 Anwendungsfall 4

    Wrme Runde Leitungen, runde Kanle, Behlter U > 2000 mm senkrecht ohne Luftspalt Heat Round pipes, round ducts, vessels: diameter > 2000 mm vertical without air gap

    Wrme Eckige Leitungen und Kanle, U > 2000 mm senkrecht ohne Luftspalt Heat Angular pipes and ducts, diameter > 2000 mm vertical without air gap

    Unabhngig vom eingesetzten Dmmstoffprodukt ist keine Sttz-konstruktion erforderlich, da bei der senkrechten Verlegung Trag-konstruktionen vorhanden sind.

    Bei groen Durchmessern kann es erforderlich sein, zwischen den vorhandenen Tragkonstruktionen Sttzkonstruktionen unter den Rundnhten anzuordnen.

    Independent of the insulation product employed no spacer-ring constructions are required, since support constructions are mounted in vertical applications.

    At larger diameters it may be required to place spacer-ring constructions under the circular seams between the support constructions.

  • Seite 20 / Page 20 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

    Wrme Runde Leitungen, runde Kanle, Behlter U > 2000 mm waagerecht mit Luftspalt Heat Round pipes, round ducts, vessels: diameter > 2000 mm horizontal with air gap

    4.3.3.1.7 Anwendungsfall 5a

    In bestimmten Nennweiten- und Dmmschichtdickenbereichen knnen druckfeste Dmmstoffe durch ihre Steifigkeit, Faser-anordnung und Rohdichte die Funktion der Sttzkonstruktion bernehmen. Deshalb kann in diesem Anwendungsfall auf den Abstandshalter zum Objekt verzichtet werden. Der Luftspalt wird durch Abstandshalter zum Dmmstoff erzeugt.

    Dies ist in den nachfolgenden Tabellen dargestellt.

    Tabelle 11: Verzicht auf die Sttzkonstruktion beim Anwendungsfall 5a, Dmmstoff Mineralwolle-Lamellenmatte druckfest. Art der Abstandshalter zum Dmmstoff: Blechstreifen mit Wellenband oder Noppenfolienstreifen Table 11: Managing without spacer-ring constructions in the application example 5a, insulation material mineral wool lamella mat, compression resistant. Type of distancer to the insulant: corrugated band on sheet metal strip or knob foil strips.

    Nennweite Diameter

    Dmmschichtdicke s in mm Insulation layer thickness s in mm

    DN 30 40 50 60 70 80 90 100

    400 X

    500 X X X X X X

    600 X X X X X X X X

    700 X X X X X X X X

    800 X X X X X X X X

    1000 X X X X X X X X

    2500 X X X X X X X X

    U 2000 mm

    Bei greren Nennweiten und/oder Dmmschichtdicken muss fr den Einzelfall entschieden werden, ob auf die Sttzkonstruk-tion zum Objekt verzichtet werden kann.

    In certain ranges of diameters and insulation layer thicknesses, compression resistant insulants can function as spacer-ring constructions because of their stiffness, fibre orientation and apparent density. In this application example, therefore, a distancer supported by the object can be dispensed with. The air space is created through distancers, supported by the insu-lation material.

    This is shown in the tables below.

    At larger diameters and/or insulation layer thicknesses, it must be decided dependent upon the individual case, whether a spacer-ring construction to the object may be dispensed with

    Tabelle 12: Verzicht auf die Sttzkonstruktion beim Anwendungsfall 5a, Rohrschale aus unterschiedlichen Dmmstoffen (Ausnahmen untenstehend), Art der Abstandshalter zum Dmmstoff: Blechstreifen mit Wellenband oder Noppen- folienstreifen ausgenommen: Mineralwolle-Rohrschalen mit Rohdichten < 75 kg/m3 und bei Betriebstemperaturen > 200 C Table 12: Managing without spacer-ring constructions in the application example 5a pipe sections made of different insulation materials. (Exceptions below) Type of distancer to the insulant: corrugated band on sheet metal strip or knob foil strips. Excepting: mineral wool pipe sections with apparent densities < 75 kg/m3 at operating temperatures > 200 C.

    Nennweite Diameter

    Dmmschichtdicke s in mm Insulation layer thickness s in mm

    DN 30 40 50 60 70 80 90 100

    400 X

    500 X X X X X X

    600 X X X X X X X X

    700 X X X X X X X X

    800 X X X X X X X X

    1000 X X X X X X X X

    U 2000 mm

    Bei greren Nennweiten und/oder Dmmschichtdicken muss fr den Einzelfall entschieden werden, ob auf die Sttzkonstruk-tion zum Objekt verzichtet werden kann.

    At larger diameters and/or insulation layer thicknesses, it must be decided dependent upon the individual case, whether a spacer-ring construction to the object may be dispensed with

    4.3.3.1.7 Application example 5a

  • Wrme Runde Leitungen, runde Kanle, Behlter U > 2000 mm senkrecht mit Luftspalt Heat Round pipes, round ducts, vessels: diameter > 2000 mm vertical with air gap

    4.3.3.1.8 Anwendungsfall 5b 4.3.3.1.8 Application example 5b

    AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 21 / Seite 21

    Unabhngig vom eingesetzten Dmmstoffprodukt ist keine Sttz-konstruktion erforderlich, da bei der senkrechten Verlegung Trag-konstruktionen vorhanden sind.

    Bei groen Durchmessern kann es erforderlich sein, zwischen den vorhandenen Tragkonstruktionen Sttzkonstruktionen unter den Rundnhten anzuordnen.

    Independent of the insulation product employed no spacer-ring constructions are required, since support constructions are mounted in vertical applications.

    At larger diameters it may be required to place spacer-ring constructions under the circular seams between the support constructions.

    Auf Grund der vielfltigen Anwendungen durch unterschiedliche Querschnitte, Ummantelungsarten, etc. lsst sich eine generelle Empfehlung nicht treffen. Hier muss die Sttzkonstruktion im Ein-zelfall spezifiziert werden.

    4.3.3.1.9 Anwendungsfall 5c

    waagerecht Wrme Eckige Leitungen und Kanle, U > 2000 mm oder senkrecht mit Luftspalt Heat Angular pipes and ducts, diameter > 2000 mm horizontal with air gap or vertical

    4.3.3.1.9 Application example 5c

    Because of the manifold applications through differing diameters, types of claddings, etc, a general advice cannot be given. The spacer ring construction must be specified for the individual case.

  • Seite 22 / Page 22 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

    4.3.3.1.10 Anwendungsfall 6

    waagerecht Klte Runde Leitungen, Runde Kanle, Behlter, U 2000 mm oder senkrecht ohne Luftspalt Cold Round pipes, round ducts, vessels diameter 2000 mm horizontal without air gap or vertical

    4.3.3.1.10 Application example 6

    In general, spacer-ring constructions are not required, with soft foams e.g. FEF, they may be needed.

    Sttzkonstruktionen sind im Allgemeinen nicht erforderlich; bei weichen Schaumstoffen z.B. FEF knnen sie notwendig werden.

    4.3.3.1.11 Anwendungsfall 7

    waagerecht Klte Runde Leitungen, Runde Kanle, Behlter, U 2000 mm oder senkrecht mit Luftspalt Cold Round pipes, round ducts, vessels diameter 2000 mm horizontal with air gap or vertical

    4.3.3.1.11 Application example 7

    A distancer supported by the insulant is required; full-surface applied nap foils or strip-shaped distancers are being used, e.g. closed cellular insulation material, corrugated sheet metal strips or knob foil.

    Ein Abstandshalter zum Dmmstoff ist erforderlich; zur Ausfh-rung kommen vollflchig verlegte Noppenfolie oder streifenfr-mige Abstandshalter z.B. geschlossenzelliger Dmmstoff, Well-blechstreifen oder Noppenfolie.

  • AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 23 / Seite 23

    4.3.3.1.12 Anwendungsfall 8 4.3.3.1.12 Application example 8

    waagerecht Klte Runde Leitungen, Runde Kanle, Behlter, U > 2000 mm oder senkrecht ohne Luftspalt Cold Round pipes, round ducts, vessels diameter > 2000 mm horizontal without air gap or vertical

    oder Kantenlnge > 500 mm or side length > 500 mm

    In general, spacer-ring constructions are not required, with soft foams e.g. FEF, they may be needed.

    Sttzkonstruktionen sind im Allgemeinen nicht erforderlich; bei weichen Schaumstoffen z.B. FEF knnen sie notwendig werden.

    4.3.3.1.13 Application example 94.3.3.1.13 Anwendungsfall 9

    waagerecht Klte Runde Leitungen, Runde Kanle, Behlter, U > 2000 mm oder senkrecht mit Luftspalt Cold Round pipes, round ducts, vessels diameter > 2000 mm horizontal with air gap or vertical

    oder Kantenlnge > 500 mm or side length > 500 mm

    Ein Abstandshalter zum Dmmstoff ist erforderlich; zur Ausfh-rung kommen vollflchig verlegte Noppenfolie oder streifenfr-mige Abstandshalter z.B. geschlossenzelliger Dmmstoff, Well-blech oder Noppenfolie.

    A distancer supported by the insulant is required; full-surface applied nap foils or strip-shaped distancers are being used, e.g. closed cellular insulation material, corrugated sheet metal strips or knob foil.

  • Seite 24 / Page 24 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

    4.3.4 Positioning and Dimensions

    Positioning and dimensions of spacer-ring constructions are dependent upon the object, the insulation layer thickness, the insulant, and the operating conditions. Next to dynamic loads, shape changes of the object and the spacer-ring construction caused by changing temperatures, too, must be heeded. Additio-nally, operation dependent shape changes may occur, e.g. when filling a tank.

    Support constructions resting on the object consist of rings or bars with webs as distancers, made of e.g. metal. Webs may be rigid, but may also be equipped with suspension elements. Spacer-ring constructions can also consist of compression resis- tant insulation material strips.

    Distancers resting on the insulation material in insulation systems with air space could be e.g. plastic knob foil, corrugated sheet on sheet metal strips, or insulation material strips.

    The positioning of the spacer-ring construction is dependent upon the casing material chosen. An related to the perimeter un-disturbed application must be aimed at. Hampering elements at vessels might be e.g. taps and man-holes, at pipes e.g. branches and pipe fittings.

    At installation components with insulation perimeters up to 1000 mm rings ad webs have to be made of band steel of at least 30 mm x 2 mm, at insulation perimeters > 1000 mm of at least 30 mm x 3 mm. Bars are at least 1 mm thick.

    Distancers resting on the insulation material must be so dimen-sioned that loads from the cladding and forces effective on the cladding (wind etc.) do not lead to a thickness decrease of the insulation material.

    Where at objects with a circular diameters spacer-ring construc-tions are being required, they shall be positioned under the circu-lar seams of the cladding. At elbows and pipe fittings spacer-ring constructions are required at the beginning and the end. Where at elbows the distance between the spacer-ring constructions ex-ceeds 700 mm, additional spacer-ring constructions are required.

    The insulation systems with spacer-ring constructions discussed do not meet the requirements of a step-on insulation.

    Materials and constructions shall keep the heat flow rate as low as possible under economic conditions.

    4.3.5 Spacer-ring constructions for hot insulations

    At round objects, the support rings shall be closed at the ends with machine screws or self tapping screws, diameter at least 6 mm.

    Webs may be made of band steel of the same thickness as for the rings, of profiled sheet or round steel of sufficient stiffness, or of ceramic cylinders with a 16 mm diameter.

    Thermally insulating separating layers in the web or between web and ring are generally not required for heat protection, since their effect is limited. A separating layer may, however, be required when connecting metals of different electrical potential to prevent contact corrosion.

    At least three webs are required. Their maximum distance, measured at the outer perimeter, is 400 mm. When using ceramic webs, at least 4 are required and their maximum distance at the outer ring is 250 mm.

    At plane surfaces, the distancer construction consists of webs and bars. The number, type, and positioning of webs and bars is determined by static considerations as well as by the thermal expansion and the dimensions of cladding sheets and object sur-face.

    Spacer-ring constructions of insulation material are secured by gluing, binding, stapling, screwing, or clamping.

    4.3.4 Anordnung und Dimensionen

    Anordnung und Dimensionen von Sttzkonstruktionen sind vom Objekt, der Dmmschichtdicke, dem Dmmstoff, dem gewhl-ten Werkstoff und den Betriebsbedingungen abhngig. Dabei mssen neben den statischen und dynamischen Krften, den wrmetechnischen Auswirkungen auch die temperaturbedingten Formnderungen des Objektes und der Sttzkonstruktion be-rcksichtigt werden. Ferner knnen betriebsbedingte Formnde-rungen auftreten, z.B. beim Befllen von Tanks.

    Auf das Objekt absttzende Sttzkonstruktionen beste-hen aus Ringen oder Schienen mit Stegen als Abstands- halter, z. B. aus Metall. Die Stege knnen starrr oder auch mit Federelementen versehen sein. Die Sttzkonstruktionen knnen auch aus druckfesten Dmmstoffstreifen bestehen.

    Auf den Dmmstoff absttzende Abstandshalter bei Dmmsys-temen mit Luftspalt knnen z. B. Noppenfolien aus Kunststoff, Wellblech mit untergelegten Blechstreifen oder Dmmstoff- streifen sein.

    Die Anordnung der Sttzkonstruktion richtet sich nach dem ge-whlten Ummantelungsmaterial. Dabei ist eine ungestrte Aus-fhrung auf den Umfang bezogen anzustreben. Strende Ele-mente knnen bei Behltern z. B. Stutzen und Mannlcher, bei Rohrleitungen z. B. Abzweige und Armaturen sein.

    Bei Anlagenteilen bis 1000 mm Dmmungsumfang sind die Ringe und Stege aus Bandstahl von mindestens 30 mm x 2 mm anzu-fertigen, bei Umfngen > 1000 mm aus Bandstahl von mindes-tens 30 mm x 3 mm. Schienen haben mindestens 1 mm Dicke.

    Auf dem Dmmstoff absttzende Abstandshalter mssen so bemessen sein, dass die Lasten aus der Ummantelung und die darauf einwirkenden Krfte (Windlast etc.) nicht zur Dicken- minderung des Dmmstoffes fhren.

    Sind bei Objekten mit rundem Querschnitt Sttzkonstruktionen erforderlich, so sind sie unter den Rundnhten der Ummantelung anzuordnen. Bei Bgen und Einbauten sind Sttzkonstruktionen am Anfang und am Ende erforderlich. berschreitet bei Bgen der Abstand der Sttzkonstruktionen 700 mm, so sind weitere Sttzkonstruktionen erforderlich.

    Die beschriebenen Dmmsysteme mit Sttzkonstruktionen erfl-len nicht die Ansprche an eine trittfeste Dmmung.

    Stoffe und Konstruktionen mssen unter wirtschaftlichen As-pekten den Wrmestrom so gering wie mglich halten.

    4.3.5 Sttzkonstruktionen fr Wrmedmmungen

    Bei runden Objekten werden die Sttzringe an den Enden mit Maschinenschrauben oder Senkschneidschrauben, Durchmes-ser mindestens 6 mm, geschlossen.

    Stege knnen aus Bandstahl gleicher Dicke wie bei den Ringen, aus profiliertem Blech oder Rundstahl ausreichender Steifigkeit oder keramischen Zylindern von 16 mm Durchmesser bestehen.

    Wrmedmmende Zwischenlagen im Steg und zwischen Ring und Steg sind fr den Wrmeschutz in der Regel nicht erforder-lich, da ihre Wirkung gering ist. Eine Zwischenlage kann jedoch bei Zusammenfgen von verschiedenen Metallen zur Vermei-dung von Kontaktkorrosion erforderlich sein.

    Es sind mindestens 3 Stege erforderlich. Der Abstand der Stege am ueren Ring gemessen, darf hchstens 400 mm betragen. Bei Verwendung keramischer Stege sind mindestens 4 Stck erforderlich und ein Hchstabstand von 250 mm am ueren Ring zulssig.

    Bei ebenen Flchen bestehen die Sttzkonstruktionen aus Stegen und Schienen. Die Anzahl, Art und Anordnung der Stege und Schienen ergibt sich aus Gesichtspunkten der Statik, der Wrmedehnung, der Abmessungen der Ummantelungsbleche und der Objektoberflche.

    Sttzkonstruktionen aus Dmmstoffen werden durch Kleben, Aufbinden, Tackern, Schrauben oder Einspannen gesichert.

  • AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 25 / Seite 25

    4.3.6 Sttzkonstruktion fr Kltedmmungen

    Als Sttzkonstruktionen werden bei Kltedmmungen vorwie-gend Schalen, Segmente und sonstige Formstcke aus Stoffen nach Tabelle 13 verwendet. Ansonsten gilt der Abschnitt 4.2.5 sinngem, jedoch mssen die Stege/Distanzstcke aus Dmm-stoff, Kunststoff oder Holz bestehen und alle metallischen Teile korrosionsgeschtzt oder korrosionsbestndig sein.

    4.3.6 Spacer-ring constructions for cold insulations

    For spacer-ring constructions in cold insulations predominantly pipe sections, segments, or otherform pieces made of materials acc. toTable 13 are being used. Apart from this, chapter 4.2.5 in general sense, however, webs/distancers must consist of insulation material, plastic or wood and all metal parts must be corrosion protected.

    Tabelle 13: Stoffe fr Sttzkonstruktionen bei Kltedmmungen (Anhaltswerte)a Table 13: Materials for spacer-ring constructions in cold insulation systems (typical values)a

    Zeile Line

    Stoffeb Materialsb

    Mindestrohdichte Minimum apparent density

    kg/m3

    Wrmeleitfhigkeit bei m = 10 C Thermal conductivity at m = 10 C

    W/(m K)

    Zulssige Druckspannungen bei statisch aufgebrachter Dauerlastc Acceptable compression stress at static applied permanent loadc

    N/mm2

    1Polystyrol(EPS)-Partikelschaum expanded polystyrene foam (EPS)

    20 0,040 0,020 0,025

    2Polystyrol(EPS)-Partikelschaum expanded polystyrene foam (EPS)

    30 0,040 0,035 0,045

    3Polystyrol(XPS)-Extruderschaum extruded polystyrene foam (XPS)

    30 0,040 0,040 0,050

    4Polystyrol(XPS)-Extruderschaum extruded polystyrene foam (XPS)

    40 0,040 0,060 0,075

    5Polystyrol(XPS)-Extruderschaum extruded polystyrene foam (XPS)

    50 0,040 0,140 0,175

    6Polyurethan(PUR)-Hartschaum polyurethane rigid foam (PUR)

    50 0,035 0,020 0,030

    7Polyurethan(PUR)-Hartschaum polyurethane rigid foam (PUR)

    80 0,035 0,080 0,100

    8Polyurethan(PUR)-Hartschaum polyurethane rigid foam (PUR)

    120 0,040 0,200 0,300

    9Presskork CC press cork (CC)

    300 0,065 0,120 0,150

    10Schaumglas CG cellular glass (CG)

    120 0,045 0,17d

    11Schaumglas CG cellular glass (CG)

    125 0,050 0,27d

    12Schaumglas CG cellular glass (CG)

    160 0,055 0,40d

    13Hartholz , Gteklasse 1 hard wood , quality class 1

    650 0,205 4,0d

    14Hartholz II, Gteklasse 1 hard wood II, quality class 1

    650 0,320 10,0d

    a Festigkeitswerte gelten fr Temperaturen < +20 C Compression-strength values in this table apply to temperatures < +20 C

    b Herstellerangaben sind zu beachten. Manufacturer information to be taken into account.

    c Die Werte der Zeilen 1 bis 14 entsprechen etwa 20% der gemessenen Werte nach DIN EN 826. The values given in lines 1 through 14 represent roughly 20% of the measured values according to DIN EN 826.

    d Stauchungsfrei without deformation

  • Seite 26 / Page 26 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

    5 Positioning Examples

    5.1 Examples for the Positioning of Support Constructions

    Figures 6 through 13 show examples for the positioning of support constructions.

    In Figures 6 through 9, no fixtures acc. to AGI Working Docu- ment 153 have been mounted on the object. Where these fixtures exist, positioning according to Figures 10 through 13 is possible.

    Additionally, different connections between webs and/or rings respectively bars have been shown.

    5 Anordnungsbeispiele

    5.1 Beispiele fr die Anordnung von Tragkonstruktionen

    Beispiele fr die Anordnung von Tragkonstruktionen zeigen die Bilder 6 bis 13.

    In den Bildern 6 bis 9 sind am Objekt keine Halterungen nach dem AGI-Arbeitsblatt Q 153 angebracht. Sind diese Halterungen vorhanden, sind Anordnungen der Bilder 10 bis 13 mglich.

    Zudem sind unterschiedliche Verbindungen zwischen Stegen und/oder Ringen bzw. Schienen dargestellt.

    geschweit / welded

    11 Winkelstck / Angle bar

    10 Z-Bgel / Z-handle

    09 Dehnungsbgel / Expansion handle

    08 Nocke/Halterung / Support

    07 Ummantelungsblech / Cladding (steel)

    06 U-Profil/Schiene / U-rail

    05 Trennschicht / Separating layer

    04 Auenring / External ring

    03 Innenring / Inner ring

    02 Steg / Web

    01 Objektwand / Object wall

    Pos. Benennung / Designation

    angenietet ohne thermische Trennung / riveted without thermal separating

    angenietet mit thermischer Trennung / riveted with thermal separating

    Bild 6: Tragkonstruktion am runden Objekt angeschweit mit unterschiedlichen Steg/Ring-Verbindungen Figure 6: Support construction, welded to a round object, with different web/ring connection

  • AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 27 / Seite 27

    Bild 7: Tragkonstruktion am ebenen Objekt angeschweit mit unterschiedlichen Steg/Schienen-Verbindungen Figure 7: Support construction, welded to a plane object, with different web/ring connections

    angeschweit / welded

    Ab

    stan

    d g

    egeb

    enen

    falls

    na

    ch B

    elas

    tung

    /

    Dis

    tanc

    e if

    nece

    ssar

    y

    follo

    win

    g th

    e lo

    ad

    geschweit / welded

    geschweit / welded

    angenietet ohne thermische Trennung / riveted without thermal separating

    angenietet mit thermischer Trennung / riveted with thermal separating

    11 Winkelstck / Angle bar

    10 Z-Bgel / Z-handle

    09 Dehnungsbgel / Expansion handle

    08 Nocke/Halterung / Support

    07 Ummantelungsblech / Cladding (steel)

    06 U-Profil/Schiene / U-rail

    05 Trennschicht / Separating layer

    04 Auenring / External ring

    03 Innenring / Inner ring

    02 Steg / Web

    01 Objektwand / Object wall

    Pos. Benennung / Designation

  • Seite 28 / Page 28 AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154

    Bild 8: Tragkonstruktion am runden Objekt angeschweit mit Dehnungsbgel Figure 8: Support construction, welded to a round object, with expansion handle

    Bild 9: Tragkonstruktion am runden, stehenden Objekt angeschweit Figure 9: Support construction, welded to a round, standing object

    angenietet mit thermischer Trennung /riveted with thermal separating

    direkt geschweit directly welded

    Winkelstck / angle bar

    Z-Bgel / Z-handle

    direkt vernietet directly riveted

    mit Trennschicht vernietet riveted with separating layer

    11 Winkelstck / Angle bar

    10 Z-Bgel / Z-handle

    09 Dehnungsbgel / Expansion handle

    08 Nocke/Halterung / Support

    07 Ummantelungsblech / Cladding (steel)

    06 U-Profil/Schiene / U-rail

    05 Trennschicht / Separating layer

    04 Auenring / External ring

    03 Innenring / Inner ring

    02 Steg / Web

    01 Objektwand / Object wall

    Pos. Benennung / Designation

    11 Winkelstck / Angle bar

    10 Z-Bgel / Z-handle

    09 Dehnungsbgel / Expansion handle

    08 Nocke/Halterung / Support

    07 Ummantelungsblech / Cladding (steel)

    06 U-Profil/Schiene / U-rail

    05 Trennschicht / Separating layer

    04 Auenring / External ring

    03 Innenring / Inner ring

    02 Steg / Web

    01 Objektwand / Object wall

    Pos. Benennung / Designation

  • AGI-Arbeitsblatt Q 154 / AGI-Working document Q 154 / Page 29 / Seite 29

    Bild 10: Tragkonstruktion mit an Halterungen befestigten Stegen Figure 10: Support construction with webs, mounted on fixtures

    geschweit welded

    geschraubt od