a_mfc8000

Embed Size (px)

Citation preview

  • 8/12/2019 a_mfc8000

    1/2

    MFC-8000

    138

    Control Module Card

    M o d e l C h a r t

    S p e c i f i c a t i o n s

    This card acts as a plug-in module for theMF-63123 Floating Valve Actuator. It allows theactuator to accept proportional voltage Vdc

    signals.

    Features:

    Acceptance of all commonly used proportional Vdc input

    signals (0 to 10 Vdc and 6 to 9 Vdc).

    Factory set at 6 to 9 Vdc for System 8000 applications.

    Switch-selectable control input signal extend point and

    span for quick, accurate field setup.

    MF-63123 actuator plug-in for quick, easy installation.

    Field-selectable for direct or reverse action, for maximum

    application flexibility.

    Model No.

    Power Input

    Actuator Part NumberVoltage(+20%/ -15%)

    Hz Amps Watts

    MFC-8000 24 (Class 2 Power Supply)50 0.085 1.2 MF-63123

    MF-63123-50060 0.080 1.1

    Inputs

    Control signal

    Factory setting: 6 to 9 Vdc.

    Maximum input signal: 22 Vdc to maintain specified performance. 30 Vdc to avoid componentdamage.

    Operating span: 2 to 10 Vdc adjustable by DIP switch.

    Start point: 0 to 12 Vdc adjustable by DIP switch.

    Hysteresis: Hysteresis switch settings selectable using 9 and 10 of the 10-position DIP switch. Referto General Instructions. Factory setting: 2.3% of span (3 Vdc control signal input span). Adjustable:hysteresis switch selection settings for control signal input spans. Refer to General Instructions.

    Impedance: Minimum of 10k .

    Power required Refer to Model Chart.

    Connections

    Control module to actuator: Uses the pin connections on the actuator circuit board to interface withcontrol module.

    Field wiring for control signal: Uses the screw terminals on the circuit board and accepts 14 to 20gage wire.

    Outputs

    Electrical Control module plugs into MF-63123 Actuator.

    Timing Refer to MF-63123 Actuator General Instructions F-24732.

    EXTEND POINT SPAN

    MFC-8000

    CONTROL MODULE

    CAUTION:

    DO NOT INSTALL CONTROL

    MODULE WHILE ACTUATOR IS

    POWERED. DAMAGE TO MODULE

    MAY OCCUR.

    J4 J5

    J6 J7

  • 8/12/2019 a_mfc8000

    2/2

    MFC-8000

    139

    T y p i c a l A p p l i c a t i o n s

    Figure 1 Switch and Adjustment Locations Showing Wiring Designations,Typical Factory Switch, and Shorting Block Settings.

    S p e c i f i c a t i o n s ( C o n t i n u e d )Environment

    Ambient temperature limitsShipping and storage: -40 to 160F (-40 to 71C).

    Operating: 0to 140F (-17.78 to 60C).

    Humidity 5 to 95% RH, non-condensing.

    Locations NEMA Type 1 (When mounted in MF-63123).

    Dimensions 1-7/8 H x 4-9/16 L x 4-13/16 D in. (47.6 x 115.9 x 20.6 mm).

    Dip Switches

    Extend PointSpan(1-8)

    Top

    Direct/Reverse ActionShorting Blocks

    Not Used 123

    (+) Positive Vdc Input(-) Vdc Input (Common)

    Mounting PinBrackets

    WiringTerminal

    Hysteresis (9, 10)