MFC-8000
138
Control Module Card
M o d e l C h a r t
S p e c i f i c a t i o n s
This card acts as a plug-in module for theMF-63123 Floating Valve Actuator. It allows theactuator to accept proportional voltage Vdc
signals.
Features:
Acceptance of all commonly used proportional Vdc input
signals (0 to 10 Vdc and 6 to 9 Vdc).
Factory set at 6 to 9 Vdc for System 8000 applications.
Switch-selectable control input signal extend point and
span for quick, accurate field setup.
MF-63123 actuator plug-in for quick, easy installation.
Field-selectable for direct or reverse action, for maximum
application flexibility.
Model No.
Power Input
Actuator Part NumberVoltage(+20%/ -15%)
Hz Amps Watts
MFC-8000 24 (Class 2 Power Supply)50 0.085 1.2 MF-63123
MF-63123-50060 0.080 1.1
Inputs
Control signal
Factory setting: 6 to 9 Vdc.
Maximum input signal: 22 Vdc to maintain specified performance. 30 Vdc to avoid componentdamage.
Operating span: 2 to 10 Vdc adjustable by DIP switch.
Start point: 0 to 12 Vdc adjustable by DIP switch.
Hysteresis: Hysteresis switch settings selectable using 9 and 10 of the 10-position DIP switch. Referto General Instructions. Factory setting: 2.3% of span (3 Vdc control signal input span). Adjustable:hysteresis switch selection settings for control signal input spans. Refer to General Instructions.
Impedance: Minimum of 10k .
Power required Refer to Model Chart.
Connections
Control module to actuator: Uses the pin connections on the actuator circuit board to interface withcontrol module.
Field wiring for control signal: Uses the screw terminals on the circuit board and accepts 14 to 20gage wire.
Outputs
Electrical Control module plugs into MF-63123 Actuator.
Timing Refer to MF-63123 Actuator General Instructions F-24732.
EXTEND POINT SPAN
MFC-8000
CONTROL MODULE
CAUTION:
DO NOT INSTALL CONTROL
MODULE WHILE ACTUATOR IS
POWERED. DAMAGE TO MODULE
MAY OCCUR.
J4 J5
J6 J7
8/12/2019 a_mfc8000
2/2
MFC-8000
139
T y p i c a l A p p l i c a t i o n s
Figure 1 Switch and Adjustment Locations Showing Wiring Designations,Typical Factory Switch, and Shorting Block Settings.
S p e c i f i c a t i o n s ( C o n t i n u e d )Environment
Ambient temperature limitsShipping and storage: -40 to 160F (-40 to 71C).
Operating: 0to 140F (-17.78 to 60C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA Type 1 (When mounted in MF-63123).
Dimensions 1-7/8 H x 4-9/16 L x 4-13/16 D in. (47.6 x 115.9 x 20.6 mm).
Dip Switches
Extend PointSpan(1-8)
Top
Direct/Reverse ActionShorting Blocks
Not Used 123
(+) Positive Vdc Input(-) Vdc Input (Common)
Mounting PinBrackets
WiringTerminal
Hysteresis (9, 10)