What is building analytics and why should we care?Daniel Hansen
Salt Lake Community CollegeMarch 23, 2016
Daniel Hansen14 years in Facilities
3 years in PM and HVAC Maintenance (UVU)4 years in HVAC BAS Controls and service (UVU)3 years in HVAC BAS Lead Controls (UVU)3 years Heat Plant Manager (SLCC)1 year Director Plant Operation and Maintenance (SLCC)
B.S. Information Technology
A.A.S Refrigeration and AC Technology
Numerous other certificates
AgendaWhat
What is BAS
What is Analytics
Metering and benefits
How they fit together
Why and How
Challenges
Costs
Benefits
Rules
Value to owner and examples
BASBuilding automation system. AKA BMS, Control system, Johnson, Honeywell, ATC, Struxtureware, etc.
It’s the parent for building systems. Security, HVAC, metering, etc.Controls the equipmentLight trending ability, troubleshootingScheduling
AHUTypical AHUDamper controlFan Speed ControlValve operationEF’s, status incorrectSimple date
Scheduling
Easy slider set upWeekly with multiple options
BAS LimitsMany platforms
Java, HTML5, thin clientsWindows only, Some mac, browser vs. thin clients
SystemsSmall computers, low memory, low storage‐cannot trend high amountsEnterprise server, Automation serverNetworks
Ethernet, N2, R2, BacNet, LonSlow, Fast, a pain.
BMS Questions?
Building AnalyticsBuilding Analytics is like the babysitter for the BAS and Metering.
Pulls data from the Enterprise servers, building controllers or from the unit controllers.
System Network
SkySpark
ADX
NAE NAE
FEC VMA
Meter Server
Building AnalyticsBuilding Analytics is like the babysitter for the BAS and Metering.
Pulls data from the Enterprise servers, building controllers or from the unit controllers.Logs data based off your set criteria.
SkySparkTaggingHistory, COV‐TimeSite Referencing
Building AnalyticsBuilding Analytics is like the babysitter for the BAS and Metering.
Pulls data from the Enterprise servers, building controllers or from the unit controllers.Logs data based off your set criteria.Nice dashboards for displaying
SkySpark
Building AnalyticsBuilding Analytics is like the babysitter for the BAS and Metering.
Pulls data from the Enterprise servers, building controllers or from the unit controllers.Logs data based off your set criteria.Nice dashboards for displayingRules and Sparks
Sparks and Rules
By campus, building and equipment
Time of duration and day
Add Costs if desired
Building AnalyticsBuilding Analytics is like the babysitter for the BAS and Metering.
Pulls data from the Enterprise servers, building controllers or from the unit controllers.Logs data based off your set criteria.Nice dashboards for displayingRules and Sparks
SkySpark, Webs‐AX, Lucid, etcSaas, Local, Remote, Fees, Etc.
Analytics Questions?
Live DemoSLCC Skyspark
MeteringUtility usage
Domestic Water, Irrigation water, Heating Water, Chilled Water, Steam, Condensate, Natural Gas, Electricity
Building ProfilesHow much utility costs per buildingSpace rental costs
System abnormalities
Dashboard
Methodology
METER
BAS
DAS
ARCHIVE
ChallengesWhat do you have? – Will it work for you
What do you want?
Mapping existingSpreadsheets, As‐Builts, walking site
IT networking and communicationSupport for your infrastructure, firewalls, access
Internal Staff capabilities
Money
Costs of MetersElectrical
Meter around $900‐$3000, Install around $1500‐$3000
GasMeter around $2000, Install around $2000‐$3000
BTUMeter around $3000‐$5000, Install around $1500‐$3000
Domestic waterMeter around $1500, Install around $1500‐$3000
Cost of SkySparkAnnual Fee is 18% of License size
Cancel anytime and only lose Weather dataBase purchase with 10,000 caps ~$5900 – Service $1062We use 18,000 a.t.m.
Easy to do in house
Good support
BenefitsThere are many benefits, here are a few
Know how the system is runningBaseline, make changes and compare
Quantify savings from changesIdentify bad buildingsBill by building for utilities accuratelySupport staff with proactive troubleshootingMany more….
RulesAbnormal sensors
DA, Space, vs. set point, other temps
Heating and cooling at same time
Equipment not matching commandAdd costs
Sequence appropriateIDEC, Cooling stages
Equipment sizingOperating 100% for period of time
Short cyclingAC equip, Fans, etc
Jordan CampusWe know there is a problem, but cannot quantify!
Using SkySpark for operation past and present
Have building level metering for verification as well as main meter
Easier way to prove savings
Valve Open?