APC® by Schneider Electric Solutions for Cisco® Unified Computing System (UCS) The Cisco Unified Computing System is a next-generation data center platform that unites compute, network, storage access, and virtualization into a cohesive system designed to reduce TCO and increase business agility. The system integrates a low-latency, lossless 10GE unified network fabric with enterprise-class, x86-architecture servers. The system is an integrated, scalable, multi-chassis platform in which all resources participate in a unified management domain. Blade server applications present unique challenges in terms of rack level power distribution, cable management and physical access space requirements for hot-swappable blade components. This application guide provides recommendations for enclosures, rack power distribution, and cable management to best address the specific physical infrastructure needs of the Cisco UCS 5108 Blade Server Chassis. The recommended solutions in this guide are based on physical verification and testing of an actual Cisco UCS 5108 Blade Server Chassis mounted in APC enclosures.

APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

  • Upload
    others

  • View
    33

  • Download
    1

Embed Size (px)

Citation preview

Page 1: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

APC® by Schneider Electric Solutions for Cisco® Unified Computing System (UCS) Blade Applications

The Cisco Unified Computing System is a next-generation data center platform that unites compute, network, storage access, and virtualization into a cohesive system designed to reduce TCO and increase business agility. The system integrates a low-latency, lossless 10GE unified network fabric with enterprise-class, x86-architecture servers. The system is an integrated, scalable, multi-chassis platform in which all resources participate in a unified management domain.

Blade server applications present unique challenges in terms of rack level power distribution, cable management and physical access space requirements for hot-swappable blade components.

This application guide provides recommendations for enclosures, rack power distribution, and cable management to best address the specific physical infrastructure needs of the Cisco UCS 5108 Blade Server Chassis. The recommended solutions in this guide are based on physical verification and testing of an actual Cisco UCS 5108 Blade Server Chassis mounted in APC enclosures.

APC Solutions for Cisco®

Catalyst® SwitchesThe Cisco / APC relationship began in 1998 with a focus on non-stop networking and has since grown to include the integration of various platforms, the sharing of intellectual property for white papers and design specifications as well as joint field engagements.

Power protection is a crucial component of VoIP & IP Telephony networks and helps to ensure that they meet the demands for “always available” systems. To achieve the highest levels of availability, it is essential that Layer 0 solutions support VoIP & IP Telephony networks, in line with your business requirements. This document discusses the power needs of Cisco® Catalyst® Switches and appropriate APC UPS solutions.

APC’s Smart-UPS® is Ideal for Protecting and Supporting Cisco Catalyst Family Switches Which Cisco equipment needs APC Smart-UPS?

> Catalyst 2950 Series, Catalyst 3750 Series, Catalyst 3550 Series, Catalyst 4500 Series

> Catalyst 6500/6500E Series

www.apc.com> Cisco Partnership Information: www.apc.com/techpartners> Wiring Closet Design Tool: configurator.apcc.com> Wiring Closet Solutions: http://apc.com/products/family/index.cfm?id

On Demand trainings at www. Datacenteruniversity.com

APC White Papers> White Paper #88: Power and Cooling Considerations for Power over Ethernet (PoE)

APC Application Notes> Application Note #50: APC Power Protection for Cisco VoIP and IP Telephony Solutions

Resources Available from APC

©2008 American Power Conversion Corporation. All rights reserved. O/ther trademarks are property of their respective owners. /Specifications are subject to change without notice. Last Updated on 8/18/08132 Fairgrounds Rd. West Kingston, RI 02892 USA • Call: 800-800-4APC • Fax: 401-789-3710 • e-mail: [email protected]

APC Smart-UPS® support for Cisco®

CallManager®:APC Smart-UPS supports Cisco CallManager 6.x out-of-the-box with exclusive built-in UPS support. This Cisco Compatible integration provides for graceful unattended shutdown of CallManager in the event of an extended power outage, thus preventing data corruption and improving time-to-recovery. In this application, Smart-UPS communicates serially or over the network.

APC Smart-UPS® support for Cisco®

Unity Express® and CUCM 6.x:APC Smart-UPS supports Cisco Unity Express with exclusive built-in UPS support. This Cisco Compatible integration provides for graceful unattended shutdown of voicemail and automated attendant services in the event of an extended power outage, thus preventing data corruption and improving time-to-recovery. In this application, Smart-UPS communicates serially and requires the APC Unity Express UPS Simple Signaling Cable (APC Part#AP9840)

Additionally, APC Smart-UPS 750XL and Smart-UPS 1500/1500RM gracefully shutdown Cisco Unified Communications Manager versions 6.x via a point-to-point direct Universal Serial Bus (USB) connection in the event of an extended power outage.

Choose Smart-UPS® RT or Symmetra®

RM/LX for Catalyst 6500 and High Density Environments:Smart-UPS RT, double conversion online family of UPSs offers performance for high density voice and data networks. Supports up to 20kVA in a 12U rack or stack form factor.

Symmetra offers scalability and the additional protection of N+1 redundancy. Symmetra supports from 2-6kVA (RM) in a rack-optimized form or up to 16kVA (LX) in a rack or tower form.

How to choose the right APC Smart-UPS® for a Cisco® Catalyst®

Family Switch?

Step 1: Consider Your Application> What model Cisco Catalyst Switch will the Smart-UPS support?> What is the input voltage for the switch?> Will the Cisco Catalyst Switch support PoE devices? If so, how many and what PoE class?> What is the plug type for the Cisco Catalyst Switch?> How many power supplies does the switch have?> What will be the total loading on the UPS VA and Watts, both initially and in the future?> How much runtime is required if the power goes out?

Step 2: Use the UPS Selector or Call APC for Assistancewww.apc.com/tools/ups_selector/ or 1-800-800-4272 in North America. In other countries, please contact your local APC office from the list provided on APC.com.

Step 3: Purchase an APC Smart-UPS®

> APC Smart-UPS® is the best solution for the Cisco Catalyst Switch family in the wiring closet. > For mission-critical or remote closets, you may also consider the NetBotz® family of accessories which provide real-time environmental monitoring and visibility to your wiring closet environment. > For dense closet and server room environments, consider InRow® RD.> All of these components are InfraStruXure® Certified to integrate seamlessly with the APC InfraStruXure® system.

APC Smart-UPS® and Smart-UPS® XLThe Smart-UPS & Smart-UPS XL use Line-interactive topology offering high reliability and efficiency with good voltage regulation.

> Smart-UPS series offers power outputs from 750VA to 5kVA (480W to 4kW)

> Smart-UPS XL units are available that allow connection of additional battery strings to increase the system run time.

Page 2: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

APC Advanced PDUs• Integrates power management capabilities with

other APC products including Symmetra® PX UPS, row and room PDUs, InRow cooling, NetShelter®

SX enclosures, and InfraStruXure® Central, Capacity and Change Manager

• Features zero U, low profile design, optimized for high-density rack power solutions to minimize interference between the PDU and hot-swap blade components

• Superior current monitoring protection including active monitoring of 3 phases for upstream panel breaker and on-board input breakers

APC Full Featured Enclosures• APC NetShelter® SX enclosures offer the most

standard, out-of-box features to ease installation and speed deployment

• Single enclosure design is flexible enough to accommodate various networking and server applications.

• Sizes Available: 42U & 48U heights, 600mm (24”) & 750mm (30”) widths, and 1070mm (42”) & 1200mm (47.2”) depths.

APC Rack Enclosures and Rack Mount Power Distributions Units (PDUs)

APC is a world leader in data center infrastructure - cooling, UPS, power distribution, racks and management.

Page 3: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

Power Requirements for Cisco UCS 5108

Source “A”(2) C20

Connectors

Source “B”(2) C20

Connectors

The UCS 5108 Blade Server Chassis includes four, single phase, hot- swappable redundant power supplies with IEC C20 Inlet connections.

In a typical power configuration, two IEC C20 inlets on the UCS 5108 are connected to each power source.

The total power consumption per chassis for typical enterprise applications is 2.0 – 2.5 kW; while a typical peak power consumption is 2.8 – 3.0 kW. In order to allow for loss of one power source, each power source should be sized and provisioned for approximately 3.0kW per chassis loading scenario as indicated below.

Note: High performance computing applications with extremely heavy loading conditions have been tested and measured to draw a peak power consumption of 3.2kW per chassis. Under these conditions, users should provision 3.2kW per chassis.

Rack Enclosures with up to two UCS 6100 Series Fabric Internconnects

AND

"A" Power Source Total Req'd Receptacles (per

Source/Rack PDU)

"B" Power Source Total Req'd Receptacles (per

Source/Rack PDU)

Total Power Provision Recommendation*

(1) UCS 5108 Chassis (2) C19, (2) C13 (2) C19, (2) C13 3.5 kW(2) UCS 5108 Chassis (4) C19, (2) C13 (4) C19, (2) C13 6.5 kW(3) UCS 5108 Chassis (6) C19, (2) C13 (6) C19, (2) C13 9.5 kW(4) UCS 5108 Chassis (8) C19, (2) C13 (8) C19, (2) C13 12.5 kW(5) UCS 5108 Chassis (10) C19, (2) C13 (10) C19, (2) C13 15.5 kW(6) UCS 5108 Chassis (12) C19, (2) C13 (12) C19, (2) C13 18.5 kW

* Each Rack Power Distribution Unit should be provisioned to this Total Power Provision Recommendation in order to account for potential source redundancy loss; Total Power Provision recommendations include power for up to two UCS 6100 Series Fabric Interconnects

Page 4: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

Rack PDU Selection Tables

415V 3-phase

1 to 3 2 to 5 6 1 to 3

9.5 15.5 18.5 9.5

45.7 74.5 88.9 39.6

50A, 3-phase 60A, 3-phase (2x) 50A, 3-ph 20A, 3-phase

(1)AP7898 (1)AP7866 or (1)AP7866A (2)AP7567A (1)AP7557NA

60A (12.5kW)

77.9A (16.2kW)

138.6A (28.8kW)

48A (11.5kW)

Max Power Required (kW)*

Rack PDU Model

Total Rack PDU Rating(single phase amps)

* Total power and amps required includes power provision for up to two UCS 6100 Series Fabric Interconnects

Number of UCS 5108 Blade Chassis per Enclosure

208V 3-phase

Max Amps Required (1ph output)*

Recommended Branch Circuit

STEP 2 ---->

STEP 3 ---->

North America Solutions

International Solutions (230/400V 3-phase Power)

Steps to select the correct rack PDU to match site/application requirements:

1. Select your region; choose North America or International (for any location outside North America)

2. If North America, select 3-phase power system (208V 3-phase or 415V 3-phase)

3. Select the desired number of UCS 5108 chassis per rack

Table Results Indicate:

• Recommended total amps (single phase output) required to power the selected number of UCS 5108 chassis plus up to two UCS 6100 Series Fabric Interconnects

• Recommended branch circuit type and size

• Recommended APC rack PDU (metered rack PDUs are recommended to actively monitor and provide alarm warnings to protect critical power circuits from accidental overloads)

• Total rack PDU rated output (total max single phase amps output)

1 to 3 4 to 6

9.5 18.5

41.3 80.4

16A, 3-phase 32A, 3-phase

(1)AP7857 (1)AP7856 or (1)AP7856A

48A (11kW)

96A (22kW)

Total Rack PDU Rating (single phase amps)

Max Power Required (kW)*

Max Amps Required (1ph output)*

Recommended Branch Circuit

Rack PDU Model

STEP 2 ---->

STEP 3 ---->

400V 3-phaseNumber of UCS 5108 Blade

Chassis per Enclosure

* Total power and amps required includes power provision for up to two UCS 6100 Series Fabric Interconnects

Page 5: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

Rack Enclosure Recommendation

Steps to select the correct enclosure to match site/application requirements:

1. Choose Region and Density: Select the number of chassis expected per enclosure

2. Choose enclosure width: Wider enclosures offer the best use of cable management space and access to blade modules, however site specific limitations may require standard 600mm width enclosure

3. Choose enclosure depth: Deeper enclosures are an alternative to wider enclosures for increased cable management and PDU space

4. Choose the Configuration: Reference the diagrams in this document for configuration recommendations and planning considerations

5. Choose Enclosure and Cable Management from the reference diagrams

The clearance access space required to access the hot swap blade chassis modules require special consideration in the selection and configuration of a proper rack enclosure to match the space requirements for access, power distribution, and data cabling. The specific selection of a properly sized rack enclosure depends upon your site specific data, cabling and rack power positioning preferences.

Step 1 Step 2 Step 3 Step 4

Choose Region & Density

Choose Enclosure Width

Choose Enclosure Depth

Verify Configuration (as shown in diagrams)

1070mm deep (~42 in) Diagram A(note limited available space)

1200mm deep (~47 in) Diagram B1 or B2

1070mm deep (~42 in) Diagram C1 or C2

1200mm deep (~47 in) Diagram C1 or C2

600mm wide(24 in) 1200mm deep (~47 in) Diagram D

1070mm deep (~42 in) Diagram E

1200mm deep (~47 in) Diagram E

1070mm deep (~42 in) Diagram A(note limited available space)

1200mm deep (~47 in) Diagram B1 or B2

1070mm deep (~42 in) Diagram C1 or C2

1200mm deep (~47 in) Diagram C1 or C2

750mm wide(30 in)

600mm wide(24 in)

750mm wide(30 in)

750mm wide(30 in)

600mm wide(24 in)

International(1 to 6 chassis)

North America(1 to 5 chassis)

North America(6 chassis)

Page 6: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

Chassis hot swap component access

CiscoUCS 5108Chassis

1070

mm

600 mm

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

Diagram “A” 600mm wide x 1070mm deep

TOP VIEWPROFILE VIEWREAR OF ENCLOSURE

In this configuration, data cabling space is very limited; use AR8621 tool-less hook & loop cable managers and fasten to vertical mounting rails (small space cavity between the rack PDU and UCS chassis is shown in yellow)

Place rack PDUs on each side of the enclosure with receptacles facing the rear door to allow access to hot swap blade components (outlet direction shown by arrow)

AP7866 rack PDU shown in illustration; however, configuration would be common for any PDU selection and number of UCS 5108 blade server chassis

ORDER ITEMS

• Rack enclosure 42U (AR3100) or 48U (AR3107)

• Rack PDU (from selection table)

• Bracket kit AR7711 (one per rack PDU)

• Cable management AR8621 (2 each)

• Power cords (C19 to C20 type)

Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)

Use AR7711 bracket (one per side) to orient rack PDUs 90°

(receptacles facing enclosure rear door)

Page 7: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

CiscoUCS 5108Chassis

Chassis hot swap component access

600 mm

1200

mm

Diagram “B1” 600mm wide x 1200mm deep

In this configuration, data cabling space is abundant; users can select 1 to 3 cable management kits (AR7710) depending on expected volume of data cables.

Place rack PDUs as shown in this image to allow for hot swap component access; note: PDUs cannot be located the opposite side due to interference with fan component access space

In this configuration, hot swap component access is tight, but has been tested to properly work.

TOP VIEWPROFILE VIEWREAR OF ENCLOSURE

AP7866 rack PDU shown in illustration; however, configuration would be common for any PDU selection and number of UCS 5108 blade server chassis

ORDER ITEMS

• Rack enclosure 42U (AR3300) or 48U (AR3307)

• Rack PDU (from selection table)

• Cable Management kit(s) AR7710 (order 1 to 3 units)

• Power cords (C19 to C20 type)

Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)

Page 8: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

CiscoUCS 5108Chassis

Chassis hot swap component access

1200

mm

600 mm

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

ON

OFF

20

Diagram “B2” 600mm wide x 1200mm deep

In this configuration, data cabling space is abundant; users can select 1 or 2 cable management kits (AR7710) depending on expected volume of data cables.

Place rack PDUs on each side of the enclosure with receptacles facing the rear door to allow access to hot swap blade components (outlet direction shown by arrow)

TOP VIEWPROFILE VIEWREAR OF ENCLOSURE

AP7866 rack PDU shown in illustration; however, configuration would be common for any PDU selection and number of UCS 5108 blade server chassis

ORDER ITEMS

• Rack enclosure 42U (AR3300) or 48U (AR3307)

• Rack PDU (from selection table)

• Bracket kit AR771 (one per rack PDU)

• Cable Management kit(s) AR7710 (order 1 to 3 units)

• Power cords (C19 to C20 type)

Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)

Use AR7711 bracket (one per side) to orient rack PDUs 90°

(receptacles facing enclosure rear door)

Page 9: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

Diagram “C1” 750mm wide x 1070mm and 1200mm deep

Chassis hot swap component access

CiscoUCS 5108Chassis

1070

mm

750 mm

Data cabling can be managed by use of either (1) AR7710 or (2)AR8442 (for more capacity)

Rack PDUs can be placed on either side of rack enclosure

TOP VIEWPROFILE VIEWREAR OF ENCLOSURE

AP7866 rack PDU shown in illustration; however, configuration would be common for any PDU selection and number of UCS 5108 blade server chassis

ORDER ITEMS

• Rack enclosure 1070mm: 42U (AR3150) or 48U (AR3157) 1200mm: 42U (AR3350) or 48U (AR3357)

• Rack PDU (from selection table)

• Cable Management kit(s) 1070mm: either (1 or 2) AR8442 or (1)

AR7710 1200mm: either (1 to 3) AR7710 or (1 to 6)

AR8442

• Power cords (C19 to C20 type)

Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)

Chassis hot swap component access

1200

mm

1200mm enclosure has additional space for access and cable management (can use additional AR8442 kits or AR7710 kits)

Page 10: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

Diagram “C2” 750mm wide x 1070mm and 1200mm deep

Chassis hot swap component access

CiscoUCS 5108Chassis

750 mm

1070

mmData cabling can be

managed by use of AR8442 (1 or 2 units)

Rack PDUs placed on both sides of the rack enclosure

AP7866 rack PDU shown in illustration; however, configuration would be common for any PDU selection and number of UCS 5108 blade server chassis

ORDER ITEMS

• Rack enclosure 1070mm: 42U (AR3150) or 48U (AR3157) 1200mm: 42U (AR3350) or 48U (AR3357)

• Rack PDU (from selection table)

• Cable Management kit(s) 1070mm: either (1 or 2) AR8442 1200mm: either (1 or 2) AR7710 or (1 to 6)

AR8442

• Power cords (C19 to C20 type)

TOP VIEWPROFILE VIEWREAR OF ENCLOSURE

Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)

Chassis hot swap component access

1200

mm

1200mm enclosure has additional space for access and cable management (can use additional AR8442 kits or AR7710 kits)

Page 11: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

CiscoUCS 5108Chassis

Chassis hot swap component access

600 mm

1200

mm

Diagram “D” 600mm wide x 1200mm deep

TOP VIEWPROFILE VIEWREAR OF ENCLOSURE

ORDER ITEMS

• Rack enclosure 42U (AR3300) or 48U (AR3307)

• Rack PDU (from selection table)

• Cable Management kit(s) AR7710 (order 1 to 3 units)

• Power cords (C19 to C20 type)

Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)

Space is extremely limited in this configuration; hot swap modules must be removed at an angle to avoid interference with PDU

Place rack PDUs as shown in this image to allow for hot swap component access

Note: PDUs cannot be located on the opposite side due to interference with fan component access space

In this configuration, data cabling space is abundant; users can select 1 to 3 cable management kits (AR7710) depending on expected volume of data cables.

Page 12: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

Diagram “E” 750mm wide x 1070mm and 1200mm deep

Chassis hot swap component access

CiscoUCS 5108Chassis

1070

mm

750 mm

Data cabling can be managed by use of either (1) AR7710 or (2)AR8442 (for more capacity)

Rack PDUs can be placed on either side of rack enclosure

PDUs are ½ enclosure height; place 4 units on the same rack side to reduce interference from incoming power cords

ORDER ITEMS

• Rack enclosure 1070mm: 42U (AR3150) or 48U (AR3157) 1200mm: 42U (AR3350) or 48U (AR3357)

• Rack PDU (from selection table)

• Cable Management kit(s) 1070mm: either (1 or 2) AR8442 1200mm: either (1 to 3) AR7710 or (1 to 6)

AR8442

• Power cords (C19 to C20 type)

Optional UCS 6100 Series Fabric Interconnects(can be positioned to customer preference)

TOP VIEWPROFILE VIEWREAR OF ENCLOSURE

Chassis hot swap component access

1200

mm

1200mm enclosure has additional space for access and cable management (can use additional AR8442 kits or AR7710 kits)

Page 13: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

Cable Management Accessories

AR8442Toolless Vertical Cable Organizer

AR7710 Toolless, Low-Profile

Vertical Cable Organizer

AR8621 Toolless Hook and Loop

Cable Managers

AR8443A & AR8444Fiber Spool Kits

AR7580 High Density Cable Manager

(for wide racks)

AR7711Zero U Accessory Bracket

All trademarks are property of their owners.

For more information visit: www.apc.com or www.thedcofthefuture.com

Call APC at: 800-272-2722

Page 14: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

AP

C b

y S

chne

ider

Ele

ctric

–N

ame

–D

ate

Net

She

lter N

exus

701

8 S

olut

ion

Ext

erna

l Exp

ansi

on D

ucts

for S

ide

Airf

low

●Nex

us 7

018

switc

h cl

eara

nce

requ

irem

ents

to

supp

ort s

ide-

to-s

ide

airf

low

resu

lt in

a 4

0”

wid

e en

clos

ure

●APC

AR

3350

Enc

losu

re :

42U

x 3

0”W

x 4

7”D

●A

dd 2

AR

7580

ver

tical

cab

le m

anag

ers

●O

ptio

nal A

R77

16 n

etw

orki

ng ro

of a

vaila

ble

for l

arge

bun

dles

of c

able

rout

ing

over

hear

d

●5”

wid

e si

de e

xter

nal e

xpan

sion

duc

ts

●P

art n

umbe

r for

kit:

QR

AC

K-Q

SV

O46

270

●R

ever

sibl

e -m

ount

ed o

n rig

ht s

ide

as in

take

, m

ount

ed o

n le

ft si

de a

s ex

haus

t

●P

rodu

ct is

cur

rent

ly u

nder

eva

luat

ion

by

Cis

co

●AR

3340

dee

p ne

twor

king

enc

losu

re a

vaila

ble

in

fall

2010

with

inte

grat

ed v

ertic

al c

able

man

ager

s,

pre-

set r

ails

for N

exus

, and

net

wor

king

roof

.

Per

fora

ted

front

to m

atch

doo

rs

Page 15: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

AP

C b

y S

chne

ider

Ele

ctric

–N

ame

–D

ate

Net

She

lter N

exus

701

8 S

olut

ion

Ext

erna

l Exp

ansi

on D

ucts

for S

ide

Airf

low

Rea

r ver

tical

baf

fle to

bl

ock

re-c

irc a

ir ac

ross

bac

k of

sw

itch

Fron

t ver

tical

baf

fle

to b

lock

exh

aust

air

Hor

izon

tal t

op b

affle

to

bloc

k re

-circ

air

acro

ss

top

of s

witc

hH

oriz

onta

l top

baf

fle to

is

olat

e ex

haus

t air

acro

ss to

p of

sw

itch

Sid

e ex

tens

ions

are

re

vers

ible

–sa

me

parts

le

ft an

d rig

ht

Page 16: APC by Schneider Electric Solutions for Cisco Unified ... · ® by Schneider Electric Solutions for Cisco ® Unified Computing System (UCS) Blade Applications The Cisco Unified Computing

APC Solutions for Cisco®

Catalyst® SwitchesThe Cisco / APC relationship began in 1998 with a focus on non-stop networking and has since grown to include the integration of various platforms, the sharing of intellectual property for white papers and design specifications as well as joint field engagements.

Power protection is a crucial component of VoIP & IP Telephony networks and helps to ensure that they meet the demands for “always available” systems. To achieve the highest levels of availability, it is essential that Layer 0 solutions support VoIP & IP Telephony networks, in line with your business requirements. This document discusses the power needs of Cisco® Catalyst® Switches and appropriate APC UPS solutions.

APC’s Smart-UPS® is Ideal for Protecting and Supporting Cisco Catalyst Family Switches Which Cisco equipment needs APC Smart-UPS?

> Catalyst 2950 Series, Catalyst 3750 Series, Catalyst 3550 Series, Catalyst 4500 Series

> Catalyst 6500/6500E Series

www.apc.com> Cisco Partnership Information: www.apc.com/techpartners> Wiring Closet Design Tool: configurator.apcc.com> Wiring Closet Solutions: http://apc.com/products/family/index.cfm?id

On Demand trainings at www. Datacenteruniversity.com

APC White Papers> White Paper #88: Power and Cooling Considerations for Power over Ethernet (PoE)

APC Application Notes> Application Note #50: APC Power Protection for Cisco VoIP and IP Telephony Solutions

Resources Available from APC

©2008 American Power Conversion Corporation. All rights reserved. O/ther trademarks are property of their respective owners. /Specifications are subject to change without notice. Last Updated on 8/18/08132 Fairgrounds Rd. West Kingston, RI 02892 USA • Call: 800-800-4APC • Fax: 401-789-3710 • e-mail: [email protected]

APC Smart-UPS® support for Cisco®

CallManager®:APC Smart-UPS supports Cisco CallManager 6.x out-of-the-box with exclusive built-in UPS support. This Cisco Compatible integration provides for graceful unattended shutdown of CallManager in the event of an extended power outage, thus preventing data corruption and improving time-to-recovery. In this application, Smart-UPS communicates serially or over the network.

APC Smart-UPS® support for Cisco®

Unity Express® and CUCM 6.x:APC Smart-UPS supports Cisco Unity Express with exclusive built-in UPS support. This Cisco Compatible integration provides for graceful unattended shutdown of voicemail and automated attendant services in the event of an extended power outage, thus preventing data corruption and improving time-to-recovery. In this application, Smart-UPS communicates serially and requires the APC Unity Express UPS Simple Signaling Cable (APC Part#AP9840)

Additionally, APC Smart-UPS 750XL and Smart-UPS 1500/1500RM gracefully shutdown Cisco Unified Communications Manager versions 6.x via a point-to-point direct Universal Serial Bus (USB) connection in the event of an extended power outage.

Choose Smart-UPS® RT or Symmetra®

RM/LX for Catalyst 6500 and High Density Environments:Smart-UPS RT, double conversion online family of UPSs offers performance for high density voice and data networks. Supports up to 20kVA in a 12U rack or stack form factor.

Symmetra offers scalability and the additional protection of N+1 redundancy. Symmetra supports from 2-6kVA (RM) in a rack-optimized form or up to 16kVA (LX) in a rack or tower form.

How to choose the right APC Smart-UPS® for a Cisco® Catalyst®

Family Switch?

Step 1: Consider Your Application> What model Cisco Catalyst Switch will the Smart-UPS support?> What is the input voltage for the switch?> Will the Cisco Catalyst Switch support PoE devices? If so, how many and what PoE class?> What is the plug type for the Cisco Catalyst Switch?> How many power supplies does the switch have?> What will be the total loading on the UPS VA and Watts, both initially and in the future?> How much runtime is required if the power goes out?

Step 2: Use the UPS Selector or Call APC for Assistancewww.apc.com/tools/ups_selector/ or 1-800-800-4272 in North America. In other countries, please contact your local APC office from the list provided on APC.com.

Step 3: Purchase an APC Smart-UPS®

> APC Smart-UPS® is the best solution for the Cisco Catalyst Switch family in the wiring closet. > For mission-critical or remote closets, you may also consider the NetBotz® family of accessories which provide real-time environmental monitoring and visibility to your wiring closet environment. > For dense closet and server room environments, consider InRow® RD.> All of these components are InfraStruXure® Certified to integrate seamlessly with the APC InfraStruXure® system.

APC Smart-UPS® and Smart-UPS® XLThe Smart-UPS & Smart-UPS XL use Line-interactive topology offering high reliability and efficiency with good voltage regulation.

> Smart-UPS series offers power outputs from 750VA to 5kVA (480W to 4kW)

> Smart-UPS XL units are available that allow connection of additional battery strings to increase the system run time.