National Institutes of Health Building 37 Modernization Bethesda, Maryland Katie L. McGimpsey Mechanical Option APPENDIX I HAP OUTPUT

APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

  • Upload
    leliem

  • View
    223

  • Download
    0

Embed Size (px)

Citation preview

Page 1: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

National Institutes of Health Building 37 Modernization

Bethesda, Maryland

Katie L. McGimpsey

Mechanical Option

APPENDIX I – HAP OUTPUT

Page 2: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Sizing Summary for AHU 1Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

Air System Information Air System Name AHU 1 Equipment Class CW AHU Air System Type VAV

Number of zones 22Floor Area 11840.3 ft²Location Washington, Dist. of Columbia

Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads

Calculation Months Jan to DecSizing Data Calculated

Central Cooling Coil Sizing Data Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at Sep 1500 62210 CFM Sum of peak zone CFM 62363 CFM Sensible heat ratio 0.943 ft²/Ton 67.8 BTU/(hr-ft²) 177.0 Water flow @ 10.0 °F rise 419.29 gpm

Load occurs at Oct 1500OA DB / WB 83.0 / 70.0 °FEntering DB / WB 82.7 / 62.0 °FLeaving DB / WB 49.9 / 48.1 °FCoil ADP 46.3 °FBypass Factor 0.100Resulting RH 34 %Design supply temp. 55.0 °FZone T-stat Check 22 of 22 OKMax zone temperature deviation 0.0 °F

Precool Coil Sizing Data Total coil load 21.3 Tons Total coil load 255.9 MBH Sensible coil load 145.3 MBH Coil CFM at Jul 1500 2996 CFM Max coil CFM 2996 CFM Sensible heat ratio 0.568 Water flow @ 10.0 °F rise 51.20 gpm

Load occurs at Jul 1500OA DB / WB 95.0 / 76.0 °FEntering DB / WB 95.0 / 76.0 °FLeaving DB / WB 50.0 / 49.1 °FBypass Factor 0.100

Preheat Coil Sizing Data Max coil load 145.3 MBH Coil CFM at Des Htg 2996 CFM Max coil CFM 2996 CFM Water flow @ 20.0 °F drop N/A

Load occurs at Des HtgEnt. DB / Lvg DB 15.0 / 60.0 °F

Humidifier Sizing Data Max steam flow at Des Htg 45.87 lb/hr Airflow Rate 10645 CFM

Air mass flow 47789.64 lb/hrMoisture gain .00096 lb/lb

Supply Fan Sizing Data Actual max CFM at Sep 1500 62210 CFM Standard CFM 62062 CFM Actual max CFM/ft² 5.25 CFM/ft²

Fan motor BHP 163.49 BHPFan motor kW 121.91 kWFan static 9.02 in wg

Return Fan Sizing Data Actual max CFM at Sep 1500 62210 CFM Standard CFM 62062 CFM Actual max CFM/ft² 5.25 CFM/ft²

Fan motor BHP 163.49 BHPFan motor kW 121.91 kWFan static 9.02 in wg

Outdoor Ventilation Air Data Design airflow CFM 2996 CFM CFM/ft² 0.25 CFM/ft²

CFM/person 26.19 CFM/person

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I1 of 48

Page 3: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Design Load Summary for AHU 1Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 83.0 °F / 70.0 °F HEATING OA DB / WB 15.0 °F / 12.2 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 1119 ft² 87939 - 1119 ft² - -

Wall Transmission 3261 ft² 15594 - 3261 ft² 18926 -

Roof Transmission 0 ft² 0 - 0 ft² 0 -

Window Transmission 1119 ft² 3309 - 1119 ft² 36203 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 0 ft² 0 - 0 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 22465 W 67713 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 98130 W 306907 - 0 0 -

People 114 21486 23452 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 361687 0 - 0 0

Safety Factor 50% / 50% 432318 11726 50% 27565 0

>> Total Zone Loads - 1296953 35178 - 82694 0

Zone Conditioning - 1360468 35178 - 79378 0

Plenum Wall Load 0% 0 - 0 0 -

Plenum Roof Load 0% 0 - 0 0 -

Plenum Lighting Load 0% 0 - 0 0 -

Return Fan Load 55924 CFM 307078 - 10645 CFM -124794 -

Ventilation Load 2996 CFM 1048 84381 2996 CFM 204406 48388

Supply Fan Load 55924 CFM 307078 - 10645 CFM -124794 -

Space Fan Coil Fans - 0 - - 0 -

Duct Heat Gain / Loss 0% 0 - 0% 0 -

>> Total System Loads - 1975672 119559 - 34197 48388

Central Cooling Coil - 1975671 119638 - -333136 0

Precool Coil - 0 0 - 0 0

Preheat Coil - 0 - - 145263 -

Humidification Load - - 0 - - 48388

Terminal Reheat Coils - 0 - - 222070 -

>> Total Conditioning - 1975671 119638 - 34197 48388

Key: Positive values are clg loads Positive values are htg loads

Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I2 of 48

Page 4: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Simulation Results for AHU 1Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:20PM

Air System Simulation Results (Table 1) :

Month

Precool Coil Load

(kBTU)

Preheat Coil Load

(kBTU)

Central Cooling Coil

Load(kBTU)

Terminal Heating Coil

Load(kBTU)

Humidifier Load

(kBTU)Supply Fan

(kWh)Return Fan

(kWh)

January 0 70562 462291 10721 12237 28008 28008

February 0 58479 419650 8699 9418 25331 25331

March 0 41759 479632 5084 4332 28199 28199

April 0 18332 482924 2554 1540 27419 27419

May 49907 0 475837 1266 761 28410 28410

June 91269 0 475489 622 0 27581 27581

July 131274 0 496906 136 0 28573 28573

August 114581 0 494909 183 0 28574 28574

September 89976 0 475698 738 0 27590 27590

October 0 13793 518898 2510 532 28362 28362

November 0 33033 468240 5475 2740 27278 27278

December 0 55514 464011 9216 9150 28035 28035

Total 477007 291472 5714485 47205 40709 333360 333360

Air System Simulation Results (Table 2) :

MonthLighting(kWh)

Electric Equipment

(kWh)

January 19989 33559

February 18054 30311

March 19989 33559

April 19344 32476

May 19989 33559

June 19344 32476

July 19989 33559

August 19989 33559

September 19344 32476

October 19989 33559

November 19344 32476

December 19989 33559

Total 235349 395126

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I3 of 48

Page 5: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Sizing Summary for AHU 2Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

Air System Information Air System Name AHU 2 Equipment Class CW AHU Air System Type VAV

Number of zones 22Floor Area 13950.0 ft²Location Washington, Dist. of Columbia

Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads

Calculation Months Jan to DecSizing Data Calculated

Central Cooling Coil Sizing Data Total coil load 195.1 Tons Total coil load 2340.8 MBH Sensible coil load 2208.6 MBH Coil CFM at Oct 1500 62531 CFM Max block CFM at Aug 1500 69951 CFM Sum of peak zone CFM 70068 CFM Sensible heat ratio 0.944 ft²/Ton 71.5 BTU/(hr-ft²) 167.8 Water flow @ 10.0 °F rise 468.41 gpm

Load occurs at Oct 1500OA DB / WB 83.0 / 70.0 °FEntering DB / WB 82.7 / 62.0 °FLeaving DB / WB 49.9 / 48.1 °FCoil ADP 46.3 °FBypass Factor 0.100Resulting RH 34 %Design supply temp. 55.0 °FZone T-stat Check 22 of 22 OKMax zone temperature deviation 0.0 °F

Precool Coil Sizing Data Total coil load 16.8 Tons Total coil load 201.0 MBH Sensible coil load 125.0 MBH Coil CFM at Jul 1500 3314 CFM Max coil CFM 3314 CFM Sensible heat ratio 0.622 Water flow @ 10.0 °F rise 40.22 gpm

Load occurs at Jul 1500OA DB / WB 95.0 / 76.0 °FEntering DB / WB 95.0 / 76.0 °FLeaving DB / WB 60.0 / 58.5 °FBypass Factor 0.100

Preheat Coil Sizing Data Max coil load 26.4 MBH Coil CFM at Des Htg 701 CFM Max coil CFM 3314 CFM Water flow @ 20.0 °F drop N/A

Load occurs at Des HtgEnt. DB / Lvg DB 15.0 / 50.0 °F

Humidifier Sizing Data Max steam flow at Des Htg 12.96 lb/hr Airflow Rate 701 CFM

Air mass flow 3145.55 lb/hrMoisture gain .00412 lb/lb

Supply Fan Sizing Data Actual max CFM at Aug 1500 69951 CFM Standard CFM 69784 CFM Actual max CFM/ft² 5.01 CFM/ft²

Fan motor BHP 183.83 BHPFan motor kW 137.08 kWFan static 9.02 in wg

Return Fan Sizing Data Actual max CFM at Aug 1500 69951 CFM Standard CFM 69784 CFM Actual max CFM/ft² 5.01 CFM/ft²

Fan motor BHP 183.83 BHPFan motor kW 137.08 kWFan static 9.02 in wg

Outdoor Ventilation Air Data Design airflow CFM 3314 CFM CFM/ft² 0.24 CFM/ft²

CFM/person 26.22 CFM/person

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I4 of 48

Page 6: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Design Load Summary for AHU 2Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 83.0 °F / 70.0 °F HEATING OA DB / WB 15.0 °F / 12.2 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 883 ft² 57633 - 883 ft² - -

Wall Transmission 2734 ft² 11971 - 2734 ft² 15866 -

Roof Transmission 0 ft² 0 - 0 ft² 0 -

Window Transmission 883 ft² 2609 - 883 ft² 28545 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 0 ft² 0 - 0 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 27649 W 83564 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 116862 W 365493 - 0 0 -

People 126 23739 25912 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 419693 0 - 0 0

Safety Factor 50% / 50% 482351 12956 50% 22205 0

>> Total Zone Loads - 1447053 38868 - 66616 0

Zone Conditioning - 1524961 38868 - 56579 0

Plenum Wall Load 0% 0 - 0 0 -

Plenum Roof Load 0% 0 - 0 0 -

Plenum Lighting Load 0% 0 - 0 0 -

Return Fan Load 62531 CFM 341301 - 701 CFM -140322 -

Ventilation Load 3314 CFM 1070 93244 701 CFM 179621 11129

Supply Fan Load 62531 CFM 341301 - 701 CFM -140322 -

Space Fan Coil Fans - 0 - - 0 -

Duct Heat Gain / Loss 0% 0 - 0% 0 -

>> Total System Loads - 2208632 132113 - -44444 11129

Central Cooling Coil - 2208632 132144 - -136547 -2539

Precool Coil - 0 0 - 0 0

Preheat Coil - 0 - - 26423 -

Humidification Load - - 0 - - 13668

Terminal Reheat Coils - 0 - - 65681 -

>> Total Conditioning - 2208632 132144 - -44444 11129

Key: Positive values are clg loads Positive values are htg loads

Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I5 of 48

Page 7: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Simulation Results for AHU 2Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:20PM

Air System Simulation Results (Table 1) :

Month

Precool Coil Load

(kBTU)

Preheat Coil Load

(kBTU)

Central Cooling Coil

Load(kBTU)

Terminal Heating Coil

Load(kBTU)

Humidifier Load

(kBTU)Supply Fan

(kWh)Return Fan

(kWh)

January 0 52197 498558 2374 15828 31877 31877

February 0 41348 453559 1593 12485 28839 28839

March 0 23829 524590 179 6067 32083 32083

April 0 6097 538939 10 2204 31197 31197

May 21135 0 582456 0 1025 32325 32325

June 48328 0 599702 0 0 31366 31366

July 82888 0 633506 0 0 32471 32471

August 68262 0 625630 0 0 32443 32443

September 46864 0 596298 0 0 31315 31315

October 0 4292 579159 0 698 32200 32200

November 0 17079 512863 336 3896 31005 31005

December 0 35485 501772 1558 11888 31914 31914

Total 267477 180328 6647031 6051 54092 379033 379033

Air System Simulation Results (Table 2) :

MonthLighting(kWh)

Electric Equipment

(kWh)

January 24809 39656

February 22408 35818

March 24809 39656

April 24009 38377

May 24809 39656

June 24009 38377

July 24809 39656

August 24809 39656

September 24009 38377

October 24809 39656

November 24009 38377

December 24809 39656

Total 292110 466914

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I6 of 48

Page 8: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Sizing Summary for AHU 3Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

Air System Information Air System Name AHU 3 Equipment Class CW AHU Air System Type VAV

Number of zones 22Floor Area 11840.3 ft²Location Washington, Dist. of Columbia

Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads

Calculation Months Jan to DecSizing Data Calculated

Central Cooling Coil Sizing Data Total coil load 164.7 Tons Total coil load 1976.9 MBH Sensible coil load 1857.9 MBH Coil CFM at Oct 1500 52900 CFM Max block CFM at Jul 1500 60037 CFM Sum of peak zone CFM 60037 CFM Sensible heat ratio 0.940 ft²/Ton 71.9 BTU/(hr-ft²) 167.0 Water flow @ 10.0 °F rise 395.58 gpm

Load occurs at Oct 1500OA DB / WB 83.0 / 70.0 °FEntering DB / WB 82.6 / 62.1 °FLeaving DB / WB 50.0 / 48.2 °FCoil ADP 46.4 °FBypass Factor 0.100Resulting RH 34 %Design supply temp. 55.0 °FZone T-stat Check 22 of 22 OKMax zone temperature deviation 0.0 °F

Precool Coil Sizing Data Total coil load 15.1 Tons Total coil load 181.7 MBH Sensible coil load 113.0 MBH Coil CFM at Jul 1500 2996 CFM Max coil CFM 2996 CFM Sensible heat ratio 0.622 Water flow @ 10.0 °F rise 36.36 gpm

Load occurs at Jul 1500OA DB / WB 95.0 / 76.0 °FEntering DB / WB 95.0 / 76.0 °FLeaving DB / WB 60.0 / 58.5 °FBypass Factor 0.100

Preheat Coil Sizing Data Max coil load 22.6 MBH Coil CFM at Des Htg 600 CFM Max coil CFM 2996 CFM Water flow @ 20.0 °F drop N/A

Load occurs at Des HtgEnt. DB / Lvg DB 15.0 / 50.0 °F

Humidifier Sizing Data Max steam flow at Des Htg 11.03 lb/hr Airflow Rate 600 CFM

Air mass flow 2695.23 lb/hrMoisture gain .00409 lb/lb

Supply Fan Sizing Data Actual max CFM at Jul 1500 60037 CFM Standard CFM 59894 CFM Actual max CFM/ft² 5.07 CFM/ft²

Fan motor BHP 157.78 BHPFan motor kW 117.65 kWFan static 9.02 in wg

Return Fan Sizing Data Actual max CFM at Jul 1500 60037 CFM Standard CFM 59894 CFM Actual max CFM/ft² 5.07 CFM/ft²

Fan motor BHP 157.78 BHPFan motor kW 117.65 kWFan static 9.02 in wg

Outdoor Ventilation Air Data Design airflow CFM 2996 CFM CFM/ft² 0.25 CFM/ft²

CFM/person 26.19 CFM/person

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I7 of 48

Page 9: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Design Load Summary for AHU 3Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 83.0 °F / 70.0 °F HEATING OA DB / WB 15.0 °F / 12.2 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 820 ft² 43301 - 820 ft² - -

Wall Transmission 3561 ft² 12688 - 3561 ft² 20664 -

Roof Transmission 0 ft² 0 - 0 ft² 0 -

Window Transmission 820 ft² 2424 - 820 ft² 26519 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 0 ft² 0 - 0 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 22465 W 67713 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 98130 W 306907 - 0 0 -

People 114 21486 23452 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 361687 0 - 0 0

Safety Factor 50% / 50% 408103 11726 50% 23592 0

>> Total Zone Loads - 1224308 35178 - 70775 0

Zone Conditioning - 1288177 35178 - 62109 0

Plenum Wall Load 0% 0 - 0 0 -

Plenum Roof Load 0% 0 - 0 0 -

Plenum Lighting Load 0% 0 - 0 0 -

Return Fan Load 52900 CFM 284183 - 600 CFM -120434 -

Ventilation Load 2996 CFM 1332 83763 600 CFM 153981 9455

Supply Fan Load 52900 CFM 284183 - 600 CFM -120434 -

Space Fan Coil Fans - 0 - - 0 -

Duct Heat Gain / Loss 0% 0 - 0% 0 -

>> Total System Loads - 1857874 118942 - -24778 9455

Central Cooling Coil - 1857873 118979 - -117200 -2176

Precool Coil - 0 0 - 0 0

Preheat Coil - 0 - - 22640 -

Humidification Load - - 0 - - 11631

Terminal Reheat Coils - 0 - - 69782 -

>> Total Conditioning - 1857873 118979 - -24778 9455

Key: Positive values are clg loads Positive values are htg loads

Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I8 of 48

Page 10: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Simulation Results for AHU 3Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:20PM

Air System Simulation Results (Table 1) :

Month

Precool Coil Load

(kBTU)

Preheat Coil Load

(kBTU)

Central Cooling Coil

Load(kBTU)

Terminal Heating Coil

Load(kBTU)

Humidifier Load

(kBTU)Supply Fan

(kWh)Return Fan

(kWh)

January 0 47191 411108 2573 14273 27168 27168

February 0 37383 374702 1592 11254 24589 24589

March 0 21544 436826 155 5461 27384 27384

April 0 5513 453272 6 1982 26669 26669

May 19108 0 493361 0 923 27662 27662

June 43693 0 510871 0 0 26860 26860

July 74939 0 541128 0 0 27817 27817

August 61716 0 532976 0 0 27778 27778

September 42369 0 505962 0 0 26787 26787

October 0 3881 486975 0 628 27498 27498

November 0 15441 426919 325 3506 26450 26450

December 0 32082 414714 1670 10716 27209 27209

Total 241824 163033 5588815 6320 48742 323870 323870

Air System Simulation Results (Table 2) :

MonthLighting(kWh)

Electric Equipment

(kWh)

January 19989 33559

February 18054 30311

March 19989 33559

April 19344 32476

May 19989 33559

June 19344 32476

July 19989 33559

August 19989 33559

September 19344 32476

October 19989 33559

November 19344 32476

December 19989 33559

Total 235349 395126

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I9 of 48

Page 11: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Sizing Summary for AHU 4Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

Air System Information Air System Name AHU 4 Equipment Class CW AHU Air System Type VAV

Number of zones 22Floor Area 11840.3 ft²Location Washington, Dist. of Columbia

Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads

Calculation Months Jan to DecSizing Data Calculated

Central Cooling Coil Sizing Data Total coil load 157.8 Tons Total coil load 1893.9 MBH Sensible coil load 1775.2 MBH Coil CFM at Oct 1500 50581 CFM Max block CFM at Jul 1500 57525 CFM Sum of peak zone CFM 57527 CFM Sensible heat ratio 0.937 ft²/Ton 75.0 BTU/(hr-ft²) 160.0 Water flow @ 10.0 °F rise 378.99 gpm

Load occurs at Oct 1500OA DB / WB 83.0 / 70.0 °FEntering DB / WB 82.6 / 62.1 °FLeaving DB / WB 50.0 / 48.2 °FCoil ADP 46.4 °FBypass Factor 0.100Resulting RH 34 %Design supply temp. 55.0 °FZone T-stat Check 22 of 22 OKMax zone temperature deviation 0.0 °F

Precool Coil Sizing Data Total coil load 15.1 Tons Total coil load 181.7 MBH Sensible coil load 113.0 MBH Coil CFM at Jul 1500 2996 CFM Max coil CFM 2996 CFM Sensible heat ratio 0.622 Water flow @ 10.0 °F rise 36.36 gpm

Load occurs at Jul 1500OA DB / WB 95.0 / 76.0 °FEntering DB / WB 95.0 / 76.0 °FLeaving DB / WB 60.0 / 58.5 °FBypass Factor 0.100

Preheat Coil Sizing Data Max coil load 21.7 MBH Coil CFM at Des Htg 575 CFM Max coil CFM 2996 CFM Water flow @ 20.0 °F drop N/A

Load occurs at Des HtgEnt. DB / Lvg DB 15.0 / 50.0 °F

Humidifier Sizing Data Max steam flow at Des Htg 10.56 lb/hr Airflow Rate 575 CFM

Air mass flow 2582.57 lb/hrMoisture gain .00409 lb/lb

Supply Fan Sizing Data Actual max CFM at Jul 1500 57525 CFM Standard CFM 57388 CFM Actual max CFM/ft² 4.86 CFM/ft²

Fan motor BHP 151.17 BHPFan motor kW 112.73 kWFan static 9.02 in wg

Return Fan Sizing Data Actual max CFM at Jul 1500 57525 CFM Standard CFM 57388 CFM Actual max CFM/ft² 4.86 CFM/ft²

Fan motor BHP 151.17 BHPFan motor kW 112.73 kWFan static 9.02 in wg

Outdoor Ventilation Air Data Design airflow CFM 2996 CFM CFM/ft² 0.25 CFM/ft²

CFM/person 26.19 CFM/person

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I10 of 48

Page 12: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Design Load Summary for AHU 4Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 83.0 °F / 70.0 °F HEATING OA DB / WB 15.0 °F / 12.2 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 427 ft² 13868 - 427 ft² - -

Wall Transmission 3954 ft² 6944 - 3954 ft² 22944 -

Roof Transmission 0 ft² 0 - 0 ft² 0 -

Window Transmission 427 ft² 1263 - 427 ft² 13816 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 0 ft² 0 - 0 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 22465 W 67713 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 98130 W 306907 - 0 0 -

People 114 21486 23452 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 361687 0 - 0 0

Safety Factor 50% / 50% 389934 11726 50% 18380 0

>> Total Zone Loads - 1169802 35178 - 55140 0

Zone Conditioning - 1231601 35178 - 46952 0

Plenum Wall Load 0% 0 - 0 0 -

Plenum Roof Load 0% 0 - 0 0 -

Plenum Lighting Load 0% 0 - 0 0 -

Return Fan Load 50581 CFM 271093 - 575 CFM -115395 -

Ventilation Load 2996 CFM 1375 83588 575 CFM 147533 9055

Supply Fan Load 50581 CFM 271093 - 575 CFM -115395 -

Space Fan Coil Fans - 0 - - 0 -

Duct Heat Gain / Loss 0% 0 - 0% 0 -

>> Total System Loads - 1775162 118767 - -36304 9055

Central Cooling Coil - 1775162 118785 - -112296 -2085

Precool Coil - 0 0 - 0 0

Preheat Coil - 0 - - 21694 -

Humidification Load - - 0 - - 11140

Terminal Reheat Coils - 0 - - 54298 -

>> Total Conditioning - 1775162 118785 - -36304 9055

Key: Positive values are clg loads Positive values are htg loads

Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I11 of 48

Page 13: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Simulation Results for AHU 4Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:20PM

Air System Simulation Results (Table 1) :

Month

Precool Coil Load

(kBTU)

Preheat Coil Load

(kBTU)

Central Cooling Coil

Load(kBTU)

Terminal Heating Coil

Load(kBTU)

Humidifier Load

(kBTU)Supply Fan

(kWh)Return Fan

(kWh)

January 0 47191 408917 1479 14301 26409 26409

February 0 37383 371600 925 11280 23886 23886

March 0 21544 429762 46 5477 26561 26561

April 0 5513 443379 1 1989 25833 25833

May 19108 0 481226 0 926 26776 26776

June 43693 0 498165 0 0 25985 25985

July 74939 0 526455 0 0 26899 26899

August 61716 0 519333 0 0 26870 26870

September 42369 0 494806 0 0 25931 25931

October 0 3881 478370 0 630 26658 26658

November 0 15441 421763 125 3519 25680 25680

December 0 32082 411827 879 10742 26443 26443

Total 241824 163033 5485602 3455 48864 313932 313932

Air System Simulation Results (Table 2) :

MonthLighting(kWh)

Electric Equipment

(kWh)

January 19989 33559

February 18054 30311

March 19989 33559

April 19344 32476

May 19989 33559

June 19344 32476

July 19989 33559

August 19989 33559

September 19344 32476

October 19989 33559

November 19344 32476

December 19989 33559

Total 235349 395126

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I12 of 48

Page 14: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Sizing Summary for AHU 5Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

Air System Information Air System Name AHU 5 Equipment Class CW AHU Air System Type VAV

Number of zones 22Floor Area 11840.3 ft²Location Washington, Dist. of Columbia

Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Peak zone sensible load Space CFM Individual peak space loads

Calculation Months Jan to DecSizing Data Calculated

Central Cooling Coil Sizing Data Total coil load 162.4 Tons Total coil load 1948.5 MBH Sensible coil load 1828.5 MBH Coil CFM at Oct 1100 51659 CFM Max block CFM at Aug 1500 56453 CFM Sum of peak zone CFM 57437 CFM Sensible heat ratio 0.938 ft²/Ton 72.9 BTU/(hr-ft²) 164.6 Water flow @ 10.0 °F rise 389.91 gpm

Load occurs at Oct 1100OA DB / WB 76.5 / 68.0 °FEntering DB / WB 82.6 / 61.9 °FLeaving DB / WB 49.7 / 47.9 °FCoil ADP 46.1 °FBypass Factor 0.100Resulting RH 34 %Design supply temp. 55.0 °FZone T-stat Check 22 of 22 OKMax zone temperature deviation 0.0 °F

Precool Coil Sizing Data Total coil load 15.1 Tons Total coil load 181.7 MBH Sensible coil load 113.0 MBH Coil CFM at Jul 1500 2996 CFM Max coil CFM 2996 CFM Sensible heat ratio 0.622 Water flow @ 10.0 °F rise 36.36 gpm

Load occurs at Jul 1500OA DB / WB 95.0 / 76.0 °FEntering DB / WB 95.0 / 76.0 °FLeaving DB / WB 60.0 / 58.5 °FBypass Factor 0.100

Preheat Coil Sizing Data Max coil load 21.7 MBH Coil CFM at Des Htg 574 CFM Max coil CFM 2996 CFM Water flow @ 20.0 °F drop N/A

Load occurs at Des HtgEnt. DB / Lvg DB 15.0 / 50.0 °F

Humidifier Sizing Data Max steam flow at Des Htg 10.54 lb/hr Airflow Rate 574 CFM

Air mass flow 2578.49 lb/hrMoisture gain .00409 lb/lb

Supply Fan Sizing Data Actual max CFM at Aug 1500 56453 CFM Standard CFM 56319 CFM Actual max CFM/ft² 4.77 CFM/ft²

Fan motor BHP 148.36 BHPFan motor kW 110.63 kWFan static 9.02 in wg

Return Fan Sizing Data Actual max CFM at Aug 1500 56453 CFM Standard CFM 56319 CFM Actual max CFM/ft² 4.77 CFM/ft²

Fan motor BHP 148.36 BHPFan motor kW 110.63 kWFan static 9.02 in wg

Outdoor Ventilation Air Data Design airflow CFM 2996 CFM CFM/ft² 0.25 CFM/ft²

CFM/person 26.19 CFM/person

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I13 of 48

Page 15: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Design Load Summary for AHU 5Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Oct 1100 HEATING DATA AT DES HTG

COOLING OA DB / WB 76.5 °F / 68.0 °F HEATING OA DB / WB 15.0 °F / 12.2 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 315 ft² 20351 - 315 ft² - -

Wall Transmission 4066 ft² 19637 - 4066 ft² 21941 -

Roof Transmission 0 ft² 0 - 0 ft² 0 -

Window Transmission 315 ft² -3 - 315 ft² 10187 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 0 ft² 0 - 0 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 22465 W 64921 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 98130 W 298186 - 0 0 -

People 114 19441 23452 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 361687 0 - 0 0

Safety Factor 50% / 50% 392111 11726 50% 16064 0

>> Total Zone Loads - 1176333 35178 - 48192 0

Zone Conditioning - 1260975 35178 - 40199 0

Plenum Wall Load 0% 0 - 0 0 -

Plenum Roof Load 0% 0 - 0 0 -

Plenum Lighting Load 0% 0 - 0 0 -

Return Fan Load 51659 CFM 294126 - 574 CFM -113245 -

Ventilation Load 2996 CFM -20705 84890 574 CFM 145331 9040

Supply Fan Load 51659 CFM 294126 - 574 CFM -113245 -

Space Fan Coil Fans - 0 - - 0 -

Duct Heat Gain / Loss 0% 0 - 0% 0 -

>> Total System Loads - 1828522 120069 - -40961 9040

Central Cooling Coil - 1828522 119988 - -110151 -2081

Precool Coil - 0 0 - 0 0

Preheat Coil - 0 - - 21659 -

Humidification Load - - 0 - - 11121

Terminal Reheat Coils - 0 - - 47531 -

>> Total Conditioning - 1828522 119988 - -40961 9040

Key: Positive values are clg loads Positive values are htg loads

Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I14 of 48

Page 16: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Simulation Results for AHU 5Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:20PM

Air System Simulation Results (Table 1) :

Month

Precool Coil Load

(kBTU)

Preheat Coil Load

(kBTU)

Central Cooling Coil

Load(kBTU)

Terminal Heating Coil

Load(kBTU)

Humidifier Load

(kBTU)Supply Fan

(kWh)Return Fan

(kWh)

January 0 47191 411924 494 14308 26195 26195

February 0 37383 374160 335 11286 23692 23692

March 0 21544 431686 1 5481 26339 26339

April 0 5513 444019 0 1991 25612 25612

May 19108 0 480112 0 926 26526 26526

June 43693 0 497295 0 0 25768 25768

July 74939 0 523973 0 0 26655 26655

August 61716 0 519977 0 0 26700 26700

September 42369 0 495915 0 0 25746 25746

October 0 3881 480091 0 631 26440 26440

November 0 15441 424030 20 3522 25468 25468

December 0 32082 413595 265 10746 26202 26202

Total 241824 163033 5496775 1114 48892 311343 311343

Air System Simulation Results (Table 2) :

MonthLighting(kWh)

Electric Equipment

(kWh)

January 19989 33559

February 18054 30311

March 19989 33559

April 19344 32476

May 19989 33559

June 19344 32476

July 19989 33559

August 19989 33559

September 19344 32476

October 19989 33559

November 19344 32476

December 19989 33559

Total 235349 395126

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I15 of 48

Page 17: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Sizing Summary for AHU 6Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

Air System Information Air System Name AHU 6 Equipment Class CW AHU Air System Type VAV

Number of zones 22Floor Area 11840.3 ft²Location Washington, Dist. of Columbia

Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads

Calculation Months Jan to DecSizing Data Calculated

Central Cooling Coil Sizing Data Total coil load 157.6 Tons Total coil load 1891.1 MBH Sensible coil load 1772.0 MBH Coil CFM at Oct 1400 50306 CFM Max block CFM at Jul 1500 56449 CFM Sum of peak zone CFM 57091 CFM Sensible heat ratio 0.937 ft²/Ton 75.1 BTU/(hr-ft²) 159.7 Water flow @ 10.0 °F rise 378.43 gpm

Load occurs at Oct 1400OA DB / WB 82.5 / 69.9 °FEntering DB / WB 82.6 / 62.1 °FLeaving DB / WB 50.0 / 48.1 °FCoil ADP 46.3 °FBypass Factor 0.100Resulting RH 34 %Design supply temp. 55.0 °FZone T-stat Check 22 of 22 OKMax zone temperature deviation 0.0 °F

Precool Coil Sizing Data Total coil load 15.1 Tons Total coil load 181.7 MBH Sensible coil load 113.0 MBH Coil CFM at Jul 1500 2996 CFM Max coil CFM 2996 CFM Sensible heat ratio 0.622 Water flow @ 10.0 °F rise 36.36 gpm

Load occurs at Jul 1500OA DB / WB 95.0 / 76.0 °FEntering DB / WB 95.0 / 76.0 °FLeaving DB / WB 60.0 / 58.5 °FBypass Factor 0.100

Preheat Coil Sizing Data Max coil load 21.5 MBH Coil CFM at Des Htg 571 CFM Max coil CFM 2996 CFM Water flow @ 20.0 °F drop N/A

Load occurs at Des HtgEnt. DB / Lvg DB 15.0 / 50.0 °F

Humidifier Sizing Data Max steam flow at Des Htg 10.48 lb/hr Airflow Rate 571 CFM

Air mass flow 2563.00 lb/hrMoisture gain .00409 lb/lb

Supply Fan Sizing Data Actual max CFM at Jul 1500 56449 CFM Standard CFM 56315 CFM Actual max CFM/ft² 4.77 CFM/ft²

Fan motor BHP 148.35 BHPFan motor kW 110.62 kWFan static 9.02 in wg

Return Fan Sizing Data Actual max CFM at Jul 1500 56449 CFM Standard CFM 56315 CFM Actual max CFM/ft² 4.77 CFM/ft²

Fan motor BHP 148.35 BHPFan motor kW 110.62 kWFan static 9.02 in wg

Outdoor Ventilation Air Data Design airflow CFM 2996 CFM CFM/ft² 0.25 CFM/ft²

CFM/person 26.19 CFM/person

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I16 of 48

Page 18: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Design Load Summary for AHU 6Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG

COOLING OA DB / WB 82.5 °F / 69.9 °F HEATING OA DB / WB 15.0 °F / 12.2 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 315 ft² 10027 - 315 ft² - -

Wall Transmission 4066 ft² 5208 - 4066 ft² 16667 -

Roof Transmission 0 ft² 0 - 0 ft² 0 -

Window Transmission 315 ft² 832 - 315 ft² 10187 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 0 ft² 0 - 0 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 22465 W 67085 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 98130 W 304944 - 0 0 -

People 114 21025 23452 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 361687 0 - 0 0

Safety Factor 50% / 50% 385404 11726 50% 13427 0

>> Total Zone Loads - 1156211 35178 - 40281 0

Zone Conditioning - 1225206 35178 - 32488 0

Plenum Wall Load 0% 0 - 0 0 -

Plenum Roof Load 0% 0 - 0 0 -

Plenum Lighting Load 0% 0 - 0 0 -

Return Fan Load 50306 CFM 273659 - 571 CFM -113237 -

Ventilation Load 2996 CFM -489 83888 571 CFM 145126 8983

Supply Fan Load 50306 CFM 273659 - 571 CFM -113237 -

Space Fan Coil Fans - 0 - - 0 -

Duct Heat Gain / Loss 0% 0 - 0% 0 -

>> Total System Loads - 1772035 119067 - -48860 8983

Central Cooling Coil - 1772035 119100 - -110161 -2069

Precool Coil - 0 0 - 0 0

Preheat Coil - 0 - - 21529 -

Humidification Load - - 0 - - 11052

Terminal Reheat Coils - 0 - - 39772 -

>> Total Conditioning - 1772035 119100 - -48860 8983

Key: Positive values are clg loads Positive values are htg loads

Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I17 of 48

Page 19: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Simulation Results for AHU 6Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:20PM

Air System Simulation Results (Table 1) :

Month

Precool Coil Load

(kBTU)

Preheat Coil Load

(kBTU)

Central Cooling Coil

Load(kBTU)

Terminal Heating Coil

Load(kBTU)

Humidifier Load

(kBTU)Supply Fan

(kWh)Return Fan

(kWh)

January 0 47191 409140 852 14307 26130 26130

February 0 37383 371953 505 11286 23638 23638

March 0 21544 429493 8 5481 26283 26283

April 0 5513 442686 0 1992 25569 25569

May 19108 0 479508 0 927 26499 26499

June 43693 0 497164 0 0 25750 25750

July 74939 0 523559 0 0 26631 26631

August 61716 0 518837 0 0 26652 26652

September 42369 0 493829 0 0 25673 25673

October 0 3881 477278 0 631 26362 26362

November 0 15441 421349 42 3522 25401 25401

December 0 32082 411307 510 10745 26147 26147

Total 241824 163033 5476104 1916 48892 310735 310735

Air System Simulation Results (Table 2) :

MonthLighting(kWh)

Electric Equipment

(kWh)

January 19989 33559

February 18054 30311

March 19989 33559

April 19344 32476

May 19989 33559

June 19344 32476

July 19989 33559

August 19989 33559

September 19344 32476

October 19989 33559

November 19344 32476

December 19989 33559

Total 235349 395126

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I18 of 48

Page 20: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Sizing Summary for AHU 7Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

Air System Information Air System Name AHU 7 Equipment Class CW AHU Air System Type VAV

Number of zones 22Floor Area 11840.3 ft²Location Washington, Dist. of Columbia

Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Peak zone sensible load Space CFM Individual peak space loads

Calculation Months Jan to DecSizing Data Calculated

Central Cooling Coil Sizing Data Total coil load 157.8 Tons Total coil load 1893.4 MBH Sensible coil load 1774.3 MBH Coil CFM at Oct 1500 50338 CFM Max block CFM at Jul 1500 56545 CFM Sum of peak zone CFM 56978 CFM Sensible heat ratio 0.937 ft²/Ton 75.0 BTU/(hr-ft²) 159.9 Water flow @ 10.0 °F rise 378.89 gpm

Load occurs at Oct 1500OA DB / WB 83.0 / 70.0 °FEntering DB / WB 82.7 / 62.1 °FLeaving DB / WB 50.0 / 48.1 °FCoil ADP 46.3 °FBypass Factor 0.100Resulting RH 34 %Design supply temp. 55.0 °FZone T-stat Check 22 of 22 OKMax zone temperature deviation 0.0 °F

Precool Coil Sizing Data Total coil load 15.1 Tons Total coil load 181.7 MBH Sensible coil load 113.0 MBH Coil CFM at Jul 1500 2996 CFM Max coil CFM 2996 CFM Sensible heat ratio 0.622 Water flow @ 10.0 °F rise 36.36 gpm

Load occurs at Jul 1500OA DB / WB 95.0 / 76.0 °FEntering DB / WB 95.0 / 76.0 °FLeaving DB / WB 60.0 / 58.5 °FBypass Factor 0.100

Preheat Coil Sizing Data Max coil load 21.5 MBH Coil CFM at Des Htg 570 CFM Max coil CFM 2996 CFM Water flow @ 20.0 °F drop N/A

Load occurs at Des HtgEnt. DB / Lvg DB 15.0 / 50.0 °F

Humidifier Sizing Data Max steam flow at Des Htg 10.46 lb/hr Airflow Rate 570 CFM

Air mass flow 2557.90 lb/hrMoisture gain .00409 lb/lb

Supply Fan Sizing Data Actual max CFM at Jul 1500 56545 CFM Standard CFM 56410 CFM Actual max CFM/ft² 4.78 CFM/ft²

Fan motor BHP 148.60 BHPFan motor kW 110.81 kWFan static 9.02 in wg

Return Fan Sizing Data Actual max CFM at Jul 1500 56545 CFM Standard CFM 56410 CFM Actual max CFM/ft² 4.78 CFM/ft²

Fan motor BHP 148.60 BHPFan motor kW 110.81 kWFan static 9.02 in wg

Outdoor Ventilation Air Data Design airflow CFM 2996 CFM CFM/ft² 0.25 CFM/ft²

CFM/person 26.19 CFM/person

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I19 of 48

Page 21: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Design Load Summary for AHU 7Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 83.0 °F / 70.0 °F HEATING OA DB / WB 15.0 °F / 12.2 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 343 ft² 10748 - 343 ft² - -

Wall Transmission 4038 ft² 5081 - 4038 ft² 17119 -

Roof Transmission 0 ft² 0 - 0 ft² 0 -

Window Transmission 343 ft² 1014 - 343 ft² 11094 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 0 ft² 0 - 0 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 22465 W 67713 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 98130 W 306907 - 0 0 -

People 114 21486 23452 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 361687 0 - 0 0

Safety Factor 50% / 50% 387318 11726 50% 14107 0

>> Total Zone Loads - 1161954 35178 - 42321 0

Zone Conditioning - 1226210 35178 - 34466 0

Plenum Wall Load 0% 0 - 0 0 -

Plenum Roof Load 0% 0 - 0 0 -

Plenum Lighting Load 0% 0 - 0 0 -

Return Fan Load 50338 CFM 273508 - 570 CFM -113429 -

Ventilation Load 2996 CFM 1123 83878 570 CFM 145255 8965

Supply Fan Load 50338 CFM 273508 - 570 CFM -113429 -

Space Fan Coil Fans - 0 - - 0 -

Duct Heat Gain / Loss 0% 0 - 0% 0 -

>> Total System Loads - 1774348 119056 - -47138 8965

Central Cooling Coil - 1774348 119071 - -110360 -2065

Precool Coil - 0 0 - 0 0

Preheat Coil - 0 - - 21486 -

Humidification Load - - 0 - - 11030

Terminal Reheat Coils - 0 - - 41736 -

>> Total Conditioning - 1774348 119071 - -47138 8965

Key: Positive values are clg loads Positive values are htg loads

Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I20 of 48

Page 22: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Simulation Results for AHU 7Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:20PM

Air System Simulation Results (Table 1) :

Month

Precool Coil Load

(kBTU)

Preheat Coil Load

(kBTU)

Central Cooling Coil

Load(kBTU)

Terminal Heating Coil

Load(kBTU)

Humidifier Load

(kBTU)Supply Fan

(kWh)Return Fan

(kWh)

January 0 47191 409263 1255 14308 26157 26157

February 0 37383 371991 730 11287 23660 23660

March 0 21544 429472 21 5482 26304 26304

April 0 5513 442856 0 1992 25592 25592

May 19108 0 479904 0 927 26525 26525

June 43693 0 497577 0 0 25772 25772

July 74939 0 524159 0 0 26657 26657

August 61716 0 519153 0 0 26670 26670

September 42369 0 494005 0 0 25692 25692

October 0 3881 477317 0 631 26385 26385

November 0 15441 421277 81 3523 25421 25421

December 0 32082 411397 747 10746 26173 26173

Total 241824 163033 5478371 2835 48897 311009 311009

Air System Simulation Results (Table 2) :

MonthLighting(kWh)

Electric Equipment

(kWh)

January 19989 33559

February 18054 30311

March 19989 33559

April 19344 32476

May 19989 33559

June 19344 32476

July 19989 33559

August 19989 33559

September 19344 32476

October 19989 33559

November 19344 32476

December 19989 33559

Total 235349 395126

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I21 of 48

Page 23: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Sizing Summary for AHU 8Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

Air System Information Air System Name AHU 8 Equipment Class CW AHU Air System Type VAV

Number of zones 22Floor Area 11840.3 ft²Location Washington, Dist. of Columbia

Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads

Calculation Months Jan to DecSizing Data Calculated

Central Cooling Coil Sizing Data Total coil load 155.9 Tons Total coil load 1870.4 MBH Sensible coil load 1751.4 MBH Coil CFM at Oct 1500 49771 CFM Max block CFM at Jul 1500 56197 CFM Sum of peak zone CFM 56445 CFM Sensible heat ratio 0.936 ft²/Ton 76.0 BTU/(hr-ft²) 158.0 Water flow @ 10.0 °F rise 374.27 gpm

Load occurs at Oct 1500OA DB / WB 83.0 / 70.0 °FEntering DB / WB 82.6 / 62.1 °FLeaving DB / WB 50.0 / 48.2 °FCoil ADP 46.4 °FBypass Factor 0.100Resulting RH 34 %Design supply temp. 55.0 °FZone T-stat Check 22 of 22 OKMax zone temperature deviation 0.0 °F

Precool Coil Sizing Data Total coil load 15.1 Tons Total coil load 181.7 MBH Sensible coil load 113.0 MBH Coil CFM at Jul 1500 2996 CFM Max coil CFM 2996 CFM Sensible heat ratio 0.622 Water flow @ 10.0 °F rise 36.36 gpm

Load occurs at Jul 1500OA DB / WB 95.0 / 76.0 °FEntering DB / WB 95.0 / 76.0 °FLeaving DB / WB 60.0 / 58.5 °FBypass Factor 0.100

Preheat Coil Sizing Data Max coil load 21.3 MBH Coil CFM at Des Htg 564 CFM Max coil CFM 2996 CFM Water flow @ 20.0 °F drop N/A

Load occurs at Des HtgEnt. DB / Lvg DB 15.0 / 50.0 °F

Humidifier Sizing Data Max steam flow at Des Htg 10.36 lb/hr Airflow Rate 564 CFM

Air mass flow 2533.95 lb/hrMoisture gain .00409 lb/lb

Supply Fan Sizing Data Actual max CFM at Jul 1500 56197 CFM Standard CFM 56063 CFM Actual max CFM/ft² 4.75 CFM/ft²

Fan motor BHP 147.68 BHPFan motor kW 110.13 kWFan static 9.02 in wg

Return Fan Sizing Data Actual max CFM at Jul 1500 56197 CFM Standard CFM 56063 CFM Actual max CFM/ft² 4.75 CFM/ft²

Fan motor BHP 147.68 BHPFan motor kW 110.13 kWFan static 9.02 in wg

Outdoor Ventilation Air Data Design airflow CFM 2996 CFM CFM/ft² 0.25 CFM/ft²

CFM/person 26.19 CFM/person

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I22 of 48

Page 24: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Air System Design Load Summary for AHU 8Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:00PM

DESIGN COOLING DESIGN HEATING

COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG

COOLING OA DB / WB 83.0 °F / 70.0 °F HEATING OA DB / WB 15.0 °F / 12.2 °F

Sensible Latent Sensible Latent

ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)

Window & Skylight Solar Loads 315 ft² 4686 - 315 ft² - -

Wall Transmission 4066 ft² 4050 - 4066 ft² 22813 -

Roof Transmission 0 ft² 0 - 0 ft² 0 -

Window Transmission 315 ft² 931 - 315 ft² 10187 -

Skylight Transmission 0 ft² 0 - 0 ft² 0 -

Door Loads 0 ft² 0 - 0 ft² 0 -

Floor Transmission 0 ft² 0 - 0 ft² 0 -

Partitions 0 ft² 0 - 0 ft² 0 -

Ceiling 0 ft² 0 - 0 ft² 0 -

Overhead Lighting 22465 W 67713 - 0 0 -

Task Lighting 0 W 0 - 0 0 -

Electric Equipment 98130 W 306907 - 0 0 -

People 114 21486 23452 0 0 0

Infiltration - 0 0 - 0 0

Miscellaneous - 361687 0 - 0 0

Safety Factor 50% / 50% 383730 11726 50% 16500 0

>> Total Zone Loads - 1151190 35178 - 49500 0

Zone Conditioning - 1212406 35178 - 41493 0

Plenum Wall Load 0% 0 - 0 0 -

Plenum Roof Load 0% 0 - 0 0 -

Plenum Lighting Load 0% 0 - 0 0 -

Return Fan Load 49771 CFM 268911 - 564 CFM -112731 -

Ventilation Load 2996 CFM 1215 83721 564 CFM 144262 8884

Supply Fan Load 49771 CFM 268911 - 564 CFM -112731 -

Space Fan Coil Fans - 0 - - 0 -

Duct Heat Gain / Loss 0% 0 - 0% 0 -

>> Total System Loads - 1751443 118900 - -39706 8884

Central Cooling Coil - 1751443 118917 - -109690 -2046

Precool Coil - 0 0 - 0 0

Preheat Coil - 0 - - 21285 -

Humidification Load - - 0 - - 10929

Terminal Reheat Coils - 0 - - 48699 -

>> Total Conditioning - 1751443 118917 - -39706 8884

Key: Positive values are clg loads Positive values are htg loads

Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I23 of 48

Page 25: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Simulation Results for AHU 8Project Name: NIH Building 37b 03/22/2005 Prepared by: Penn State University 10:20PM

Air System Simulation Results (Table 1) :

Month

Precool Coil Load

(kBTU)

Preheat Coil Load

(kBTU)

Central Cooling Coil

Load(kBTU)

Terminal Heating Coil

Load(kBTU)

Humidifier Load

(kBTU)Supply Fan

(kWh)Return Fan

(kWh)

January 0 47191 407096 1235 14312 26015 26015

February 0 37383 369850 741 11290 23528 23528

March 0 21544 426673 32 5484 26147 26147

April 0 5513 439809 0 1993 25437 25437

May 19108 0 477100 0 928 26376 26376

June 43693 0 494826 0 0 25627 25627

July 74939 0 521390 0 0 26512 26512

August 61716 0 515524 0 0 26498 26498

September 42369 0 490760 0 0 25534 25534

October 0 3881 474509 0 631 26230 26230

November 0 15441 419022 86 3524 25280 25280

December 0 32082 409689 677 10751 26041 26041

Total 241824 163033 5446246 2771 48913 309225 309225

Air System Simulation Results (Table 2) :

MonthLighting(kWh)

Electric Equipment

(kWh)

January 19989 33559

February 18054 30311

March 19989 33559

April 19344 32476

May 19989 33559

June 19344 32476

July 19989 33559

August 19989 33559

September 19344 32476

October 19989 33559

November 19344 32476

December 19989 33559

Total 235349 395126

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I24 of 48

Page 26: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Annual Component Costs - NIH Building 37NIH Building 37b 03/22/2005 Penn State University 10:32PM

48.1%Air System Fans

3.6% Cooling 0.2% Heating

18.0% Lights

30.0% Electric Equipment

1. Annual Costs

ComponentAnnual Cost

($) ($/ft²)Percent of Total

(%)

Air System Fans 413,333 4.269 48.1

Cooling 30,696 0.317 3.6

Heating 2,090 0.022 0.2

Pumps 0 0.000 0.0

Cooling Tower Fans 0 0.000 0.0

HVAC Sub-Total 446,119 4.607 51.9

Lights 154,733 1.598 18.0

Electric Equipment 257,903 2.663 30.0

Misc. Electric 0 0.000 0.0

Misc. Fuel Use 0 0.000 0.0

Non-HVAC Sub-Total 412,637 4.261 48.1

Grand Total 858,756 8.869 100.0

Note: Cost per unit floor area is based on the gross building floor area.

Gross Floor Area 96832.1 ft² Conditioned Floor Area 96832.1 ft²

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I25 of 48

Page 27: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Annual Cost SummaryNIH Building 37b 03/22/2005 Penn State University 10:32PM

Table 1. Annual Costs

ComponentNIH Building 37

($)

Air System Fans 413,333

Cooling 30,696

Heating 2,090

Pumps 0

Cooling Tower Fans 0

HVAC Sub-Total 446,119

Lights 154,733

Electric Equipment 257,903

Misc. Electric 0

Misc. Fuel Use 0

Non-HVAC Sub-Total 412,637

Grand Total 858,756

Table 2. Annual Cost per Unit Floor Area

ComponentNIH Building 37

($/ft²)

Air System Fans 4.269

Cooling 0.317

Heating 0.022

Pumps 0.000

Cooling Tower Fans 0.000

HVAC Sub-Total 4.607

Lights 1.598

Electric Equipment 2.663

Misc. Electric 0.000

Misc. Fuel Use 0.000

Non-HVAC Sub-Total 4.261

Grand Total 8.869

Gross Floor Area (ft²) 96832.1

Conditioned Floor Area (ft²) 96832.1

Note: Values in this table are calculated using the Gross Floor Area.

Table 3. Component Cost as a Percentage of Total Cost

ComponentNIH Building 37

( % )

Air System Fans 48.1

Cooling 3.6

Heating 0.2

Pumps 0.0

Cooling Tower Fans 0.0

HVAC Sub-Total 51.9

Lights 18.0

Electric Equipment 30.0

Misc. Electric 0.0

Misc. Fuel Use 0.0

Non-HVAC Sub-Total 48.1

Grand Total 100.0

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I26 of 48

Page 28: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Annual Energy and Emissions SummaryNIH Building 37b 03/22/2005 Penn State University 10:32PM

Table 1. Annual Costs

ComponentNIH Building 37

($)

HVAC Components

Electric 413,333

Natural Gas 0

Fuel Oil 0

Propane 0

Remote HW 0

Remote Steam 2,090

Remote CW 30,696

HVAC Sub-Total 446,119

Non-HVAC Components

Electric 412,609

Natural Gas 0

Fuel Oil 0

Propane 0

Remote HW 0

Remote Steam 0

Non-HVAC Sub-Total 412,609

Grand Total 858,728

Table 2. Annual Energy Consumption

Component NIH Building 37

HVAC Components

Electric (kWh) 5,184,940

Natural Gas (na) 0

Fuel Oil (na) 0

Propane (na) 0

Remote HW (na) 0

Remote Steam (kBTU) 19,097

Remote CW (kBTU) 475,289

Non-HVAC Components

Electric (kWh) 5,172,086

Natural Gas (na) 0

Fuel Oil (na) 0

Propane (na) 0

Remote HW (na) 0

Remote Steam (kBTU) 0

Totals

Electric (kWh) 10,357,030

Natural Gas (na) 0

Fuel Oil (na) 0

Propane (na) 0

Remote HW (na) 0

Remote Steam (kBTU) 19,097

Remote CW (kBTU) 475,289

Hourly Analysis Program v.4.2 Page 1 of 2

Appendix I27 of 48

Page 29: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Annual Energy and Emissions SummaryNIH Building 37b 03/22/2005 Penn State University 10:32PM

Table 3. Annual Emissions

Component NIH Building 37

CO2 (lb) 0

SO2 (kg) 0

NOx (kg) 0

Table 4. Annual Cost per Unit Floor Area

ComponentNIH Building 37

($/ft²)

HVAC Components

Electric 4.269

Natural Gas 0.000

Fuel Oil 0.000

Propane 0.000

Remote HW 0.000

Remote Steam 0.022

Remote CW 0.317

HVAC Sub-Total 4.607

Non-HVAC Components

Electric 4.261

Natural Gas 0.000

Fuel Oil 0.000

Propane 0.000

Remote HW 0.000

Remote Steam 0.000

Non-HVAC Sub-Total 4.261

Grand Total 8.868

Gross Floor Area (ft²) 96832.1

Conditioned Floor Area (ft²) 96832.1

Note: Values in this table are calculated using the Gross Floor Area.

Table 5. Component Cost as a Percentage of Total Cost

ComponentNIH Building 37

( % )

HVAC Components

Electric 48.1

Natural Gas 0.0

Fuel Oil 0.0

Propane 0.0

Remote HW 0.0

Remote Steam 0.2

Remote CW 3.6

HVAC Sub-Total 52.0

Non-HVAC Components

Electric 48.0

Natural Gas 0.0

Fuel Oil 0.0

Propane 0.0

Remote HW 0.0

Remote Steam 0.0

Non-HVAC Sub-Total 48.0

Grand Total 100.0

Hourly Analysis Program v.4.2 Page 2 of 2

Appendix I28 of 48

Page 30: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Annual Energy Costs - NIH Building 37NIH Building 37b 03/22/2005 Penn State University 10:32PM

48.1%HVAC Electric

0.2%HVAC Remote Steam 3.6% HVAC Remote Chilled Water

48.0% Non-HVAC Electric

1. Annual Costs

ComponentAnnual Cost

($/yr) ($/ft²)Percent of Total

(%)

HVAC Components

Electric 413,333 4.269 48.1

Natural Gas 0 0.000 0.0

Fuel Oil 0 0.000 0.0

Propane 0 0.000 0.0

Remote Hot Water 0 0.000 0.0

Remote Steam 2,090 0.022 0.2

Remote Chilled Water 30,696 0.317 3.6

HVAC Sub-Total 446,119 4.607 52.0

Non-HVAC Components

Electric 412,609 4.261 48.0

Natural Gas 0 0.000 0.0

Fuel Oil 0 0.000 0.0

Propane 0 0.000 0.0

Remote Hot Water 0 0.000 0.0

Remote Steam 0 0.000 0.0

Non-HVAC Sub-Total 412,609 4.261 48.0

Grand Total 858,728 8.868 100.0

Note: Cost per unit floor area is based on the gross building floor area.

Gross Floor Area 96832.1 ft² Conditioned Floor Area 96832.1 ft²

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I29 of 48

Page 31: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Annual HVAC & Non-HVAC Cost Totals - NIH Building 37NIH Building 37b 03/22/2005 Penn State University 10:32PM

51.9%HVAC

48.1% Non-HVAC

1. Annual Costs

ComponentAnnual Cost

($/yr) ($/ft²)Percent of Total

(%)

HVAC 446,119 4.607 51.9

Non-HVAC 412,637 4.261 48.1

Grand Total 858,756 8.869 100.0

Note: Cost per unit floor area is based on the gross building floor area.

Gross Floor Area 96832.1 ft² Conditioned Floor Area 96832.1 ft²

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I30 of 48

Page 32: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Billing Details - Electric - NIH Building 37NIH Building 37b 03/22/2005 Penn State University 10:32PM

1. Component Charges

BillingPeriod

Energy Charges($)

Demand Charges($)

CustomerCharges

($)Taxes

($)Total Charge

($)

Jan 74,359 1,734 276 1,558 77,926

Feb 67,212 1,740 276 1,412 70,639

Mar 74,580 1,749 276 1,563 78,168

Apr 72,357 1,763 276 1,518 75,914

May 74,878 1,767 276 1,569 78,489

Jun 45,844 10,059 276 1,146 57,325

Jul 47,391 10,067 276 1,178 58,911

Aug 47,389 10,075 276 1,178 58,917

Sep 45,820 10,045 276 1,145 57,286

Oct 47,279 10,022 276 1,175 58,751

Nov 72,135 1,752 276 1,513 75,675

Dec 74,393 1,736 276 1,559 77,964

Totals 743,636 62,508 3,308 16,513 825,966

2. Totals

BillingPeriod

Total Charges($)

Total Consumption

(kWh)Avg Price

($/kWh)

Jan 77,926 875,209 0.0890

Feb 70,639 791,107 0.0893

Mar 78,168 877,891 0.0890

Apr 75,914 851,775 0.0891

May 78,489 881,488 0.0890

Jun 57,325 854,539 0.0671

Jul 58,911 883,722 0.0667

Aug 58,917 883,662 0.0667

Sep 57,286 853,656 0.0671

Oct 58,751 879,563 0.0668

Nov 75,675 849,090 0.0891

Dec 77,964 875,622 0.0890

Totals 825,966 10,357,322 0.0797

3. Consumption TotalsBillingPeriod

Peak(kWh)

Mid-Peak(kWh)

Normal Peak(kWh)

Off-Peak(kWh)

Overall(kWh)

Jan 492,110 218,914 0 164,185 875,209

Feb 445,082 197,728 0 148,296 791,107

Mar 494,792 218,914 0 164,185 877,891

Apr 481,034 211,852 0 158,889 851,775

May 498,390 218,914 0 164,185 881,488

Jun 483,798 211,852 0 158,889 854,539

Jul 500,623 218,914 0 164,185 883,722

Aug 500,563 218,914 0 164,185 883,662

Sep 482,915 211,852 0 158,889 853,656

Oct 496,464 218,914 0 164,185 879,563

Nov 478,349 211,852 0 158,889 849,090

Dec 492,523 218,914 0 164,185 875,622

Totals 5,846,644 2,577,530 0 1,933,148 10,357,322

Hourly Analysis Program v.4.2 Page 1 of 2

Appendix I31 of 48

Page 33: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Billing Details - Electric - NIH Building 37NIH Building 37b 03/22/2005 Penn State University 10:32PM

4. Billing DemandsBillingPeriod

Peak(kW)

Mid-Peak(kW)

Normal Peak(kW)

Off-Peak(kW)

Overall(kW)

Jan 1685.0 882.7 0.0 882.7 1685.0

Feb 1690.6 882.7 0.0 882.7 1690.6

Mar 1699.7 882.7 0.0 882.7 1699.7

Apr 1713.8 882.7 0.0 882.7 1713.8

May 1717.0 882.7 0.0 882.7 1717.0

Jun 1719.0 882.7 0.0 882.7 1719.0

Jul 1721.1 882.7 0.0 882.7 1721.1

Aug 1723.3 882.7 0.0 882.7 1723.3

Sep 1715.2 882.7 0.0 882.7 1715.2

Oct 1708.7 882.7 0.0 882.7 1708.7

Nov 1702.3 882.7 0.0 882.7 1702.3

Dec 1687.5 882.7 0.0 882.7 1687.5

5. Maximum DemandsBillingPeriod

Peak(kW)

Mid-Peak(kW)

Normal Peak(kW)

Off-Peak(kW)

Overall(kW)

Jan 1685.0 882.7 0.0 882.7 1685.0

Feb 1690.6 882.7 0.0 882.7 1690.6

Mar 1699.7 882.7 0.0 882.7 1699.7

Apr 1713.8 882.7 0.0 882.7 1713.8

May 1717.0 882.7 0.0 882.7 1717.0

Jun 1719.0 882.7 0.0 882.7 1719.0

Jul 1721.1 882.7 0.0 882.7 1721.1

Aug 1723.3 882.7 0.0 882.7 1723.3

Sep 1715.2 882.7 0.0 882.7 1715.2

Oct 1708.7 882.7 0.0 882.7 1708.7

Nov 1702.3 882.7 0.0 882.7 1702.3

Dec 1687.5 882.7 0.0 882.7 1687.5

6. Time Of Maximum DemandsBillingPeriod

Peak(m/d/h)

Mid-Peak(m/d/h)

Normal Peak(m/d/h)

Off-Peak(m/d/h)

Overall(m/d/h)

Jan 1/5/1400 1/1/0300 n/a 1/1/0000 1/5/1400

Feb 2/23/1500 2/1/0300 n/a 2/1/0000 2/23/1500

Mar 3/26/1500 3/1/0300 n/a 3/1/0000 3/26/1500

Apr 4/15/1500 4/1/0300 n/a 4/1/0000 4/15/1500

May 5/31/1500 5/1/0300 n/a 5/1/0000 5/31/1500

Jun 6/30/1500 6/1/0300 n/a 6/1/0000 6/30/1500

Jul 7/8/1500 7/1/0300 n/a 7/1/0000 7/8/1500

Aug 8/16/1500 8/1/0300 n/a 8/1/0000 8/16/1500

Sep 9/7/1500 9/1/0300 n/a 9/1/0000 9/7/1500

Oct 10/15/1500 10/1/0300 n/a 10/1/0000 10/15/1500

Nov 11/15/1500 11/1/0300 n/a 11/1/0000 11/15/1500

Dec 12/5/1400 12/1/0300 n/a 12/1/0000 12/5/1400

Hourly Analysis Program v.4.2 Page 2 of 2

Appendix I32 of 48

Page 34: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Simulation Results for Central Steam PlantNIH Building 37b 03/22/2005 Penn State University 10:30PM

Plant Simulation Results (Table 1) :

Month

Heating Coil Load

(kBTU)

Remote Steam Load

(kBTU)

January 540761 540761

February 428830 428830

March 243641 243641

April 75758 75758

May 8609 8609

June 622 622

July 136 136

August 183 183

September 738 738

October 48891 48891

November 177000 177000

December 384496 384496

Total 1909666 1909666

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I33 of 48

Page 35: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Unmet Load Report for Central Steam PlantNIH Building 37b 03/22/2005 Penn State University 10:30PM

1. Unmet Load Statistics

Month

EquipmentCapacity is

Sufficient(hrs)

CapacityInsufficient

by 0%-5%(hrs)

CapacityInsufficientby 5%-10%

(hrs)

CapacityInsufficient

by >10%(hrs)

Total Hourswith Unmet

Loads

Total Hourswith

EquipmentLoads

January 744 0 0 0 0 744

February 671 0 0 0 0 671

March 700 0 0 0 0 700

April 565 0 0 0 0 565

May 389 0 0 0 0 389

June 235 0 0 0 0 235

July 124 0 0 0 0 124

August 140 0 0 0 0 140

September 242 0 0 0 0 242

October 553 0 0 0 0 553

November 672 0 0 0 0 672

December 744 0 0 0 0 744

Total 5779 0 0 0 0 5779

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I34 of 48

Page 36: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Heating Plant Sizing Summary for Central Steam PlantNIH Building 37b 03/22/2005 Penn State University 10:27PM

1. Plant Information: Plant Name Central Steam Plant Plant Type Remote Steam Design Weather Washington, Dist. of Columbia

2. Heating Plant Sizing Data: Maximum Plant Load 1020.5 MBH Load occurs at Winter Design BTU/(hr-ft²) 10.5 BTU/(hr-ft²) Floor area served by plant 96832.1 ft²

3. Coincident Air System Heating Loads for Winter Design

System Heating Coil LoadAir System Name Mult. ( MBH )

AHU 1 1 415.7

AHU 2 1 105.8

AHU 3 1 104.1

AHU 4 1 87.1

AHU 5 1 80.3

AHU 6 1 72.4

AHU 7 1 74.3

AHU 8 1 80.9

System loads are for coils whose heating source is ' Steam ' .

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I35 of 48

Page 37: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Hourly Chiller Load Profiles for Chiller Water PlantNIH Building 37b 03/22/2005 Penn State University 10:27PM

1. Plant Information: Plant Name Chiller Water Plant Plant Type Remote Chilled Water Design Weather Washington, Dist. of Columbia

2. Chiller Load Profiles from July to July :

DESIGN MONTH: JULY

OA TOTAL TEMP COOLING

Hour ( °F ) ( Tons )

0000 81.4 104.0

0100 80.6 104.1

0200 79.7 104.3

0300 79.1 104.6

0400 78.6 104.9

0500 78.4 106.6

0600 78.7 116.8

0700 79.6 1342.4

0800 81.1 1338.0

0900 83.2 1344.7

1000 85.7 1349.6

1100 88.5 1354.2

1200 91.2 1360.9

1300 93.2 1371.8

1400 94.5 1383.9

1500 95.0 1392.8

1600 94.5 523.7

1700 93.3 510.9

1800 91.5 493.4

1900 89.4 99.0

2000 87.2 105.0

2100 85.4 104.4

2200 83.7 104.0

2300 82.4 103.9

Total Ton-hrs 15027.7

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I36 of 48

Page 38: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Chiller Design Day Loads for Chiller Water PlantNIH Building 37b 03/22/2005 Penn State University 10:27PM

0

200

400

600

800

1000

1200

1400

Data for July

Chiller Load (Tons)

Hour of Day

0001

0203

0405

0607

0809

1011

1213

1415

1617

1819

2021

2223

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I37 of 48

Page 39: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Hourly Chiller Load Profiles for Chiller Water PlantNIH Building 37b 03/22/2005 Penn State University 09:51PM

1. Plant Information: Plant Name Chiller Water Plant Plant Type Remote Chilled Water Design Weather Washington, Dist. of Columbia

2. Chiller Load Profiles from July to July :

DESIGN MONTH: JULY

OA TOTAL TEMP COOLING

Hour ( °F ) ( Tons )

0000 81.4 104.0

0100 80.6 104.1

0200 79.7 104.3

0300 79.1 104.6

0400 78.6 104.9

0500 78.4 106.6

0600 78.7 116.8

0700 79.6 1342.4

0800 81.1 1338.0

0900 83.2 1344.7

1000 85.7 1349.6

1100 88.5 1354.2

1200 91.2 1360.9

1300 93.2 1371.8

1400 94.5 1383.9

1500 95.0 1392.8

1600 94.5 523.7

1700 93.3 510.9

1800 91.5 493.4

1900 89.4 99.0

2000 87.2 105.0

2100 85.4 104.4

2200 83.7 104.0

2300 82.4 103.9

Total Ton-hrs 15027.7

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I38 of 48

Page 40: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Hourly Chiller Load Profiles for Chiller Water PlantNIH Building 37b 03/22/2005 Penn State University 10:27PM

1. Plant Information: Plant Name Chiller Water Plant Plant Type Remote Chilled Water Design Weather Washington, Dist. of Columbia

2. Chiller Load Profiles from July to July :

DESIGN MONTH: JULY

OA TOTAL TEMP COOLING

Hour ( °F ) ( Tons )

0000 81.4 104.0

0100 80.6 104.1

0200 79.7 104.3

0300 79.1 104.6

0400 78.6 104.9

0500 78.4 106.6

0600 78.7 116.8

0700 79.6 1342.4

0800 81.1 1338.0

0900 83.2 1344.7

1000 85.7 1349.6

1100 88.5 1354.2

1200 91.2 1360.9

1300 93.2 1371.8

1400 94.5 1383.9

1500 95.0 1392.8

1600 94.5 523.7

1700 93.3 510.9

1800 91.5 493.4

1900 89.4 99.0

2000 87.2 105.0

2100 85.4 104.4

2200 83.7 104.0

2300 82.4 103.9

Total Ton-hrs 15027.7

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I39 of 48

Page 41: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Simulation Results for Central Steam PlantNIH Building 37b 03/22/2005 Penn State University 10:30PM

Plant Simulation Results (Table 1) :

Month

Heating Coil Load

(kBTU)

Remote Steam Load

(kBTU)

January 540761 540761

February 428830 428830

March 243641 243641

April 75758 75758

May 8609 8609

June 622 622

July 136 136

August 183 183

September 738 738

October 48891 48891

November 177000 177000

December 384496 384496

Total 1909666 1909666

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I40 of 48

Page 42: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Unmet Load Report for Chiller Water PlantNIH Building 37b 03/22/2005 Penn State University 10:30PM

1. Unmet Load Statistics

Month

EquipmentCapacity is

Sufficient(hrs)

CapacityInsufficient

by 0%-5%(hrs)

CapacityInsufficientby 5%-10%

(hrs)

CapacityInsufficient

by >10%(hrs)

Total Hourswith Unmet

Loads

Total Hourswith

EquipmentLoads

January 744 0 0 0 0 744

February 672 0 0 0 0 672

March 744 0 0 0 0 744

April 720 0 0 0 0 720

May 744 0 0 0 0 744

June 720 0 0 0 0 720

July 744 0 0 0 0 744

August 744 0 0 0 0 744

September 720 0 0 0 0 720

October 744 0 0 0 0 744

November 720 0 0 0 0 720

December 744 0 0 0 0 744

Total 8760 0 0 0 0 8760

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I41 of 48

Page 43: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Cooling Plant Sizing Summary for Chiller Water PlantNIH Building 37b 03/22/2005 Penn State University 10:27PM

1. Plant Information: Plant Name Chiller Water Plant Plant Type Remote Chilled Water Design Weather Washington, Dist. of Columbia

2. Cooling Plant Sizing Data: Maximum Plant Load 1393.7 Tons Load occurs at Aug 1500 ft²/Ton 69.5 ft²/Ton Floor area served by plant 96832.1 ft²

3. Coincident Air System Cooling Loads for Aug 1500

System Cooling Coil LoadAir System Name Mult. ( Tons )

AHU 1 1 178.6

AHU 2 1 204.0

AHU 3 1 175.0

AHU 4 1 168.2

AHU 5 1 167.8

AHU 6 1 167.1

AHU 7 1 167.4

AHU 8 1 165.7

System loads are for coils whose cooling source is ' Chilled Water ' .

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I42 of 48

Page 44: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Energy Budget by Energy Source - NIH Building 37NIH Building 37b 03/22/2005 Penn State University 10:32PM

1. Annual Coil Loads

ComponentLoad

(kBTU) (kBTU/ft²)

Cooling Coil Loads 47,528,850 490.838

Heating Coil Loads 1,909,667 19.721

Grand Total 49,438,519 510.559

2. Energy Consumption by Energy Source

ComponentSite Energy

(kBTU)Site Energy(kBTU/ft²)

Source Energy(kBTU)

Source Energy(kBTU/ft²)

HVAC Components

Electric 17,691,014 182.698 63,182,192 652.492

Natural Gas 0 0.000 0 0.000

Fuel Oil 0 0.000 0 0.000

Propane 0 0.000 0 0.000

Remote Hot Water 0 0.000 0 0.000

Remote Steam 1,909,666 19.721 1,909,666 19.721

Remote Chilled Water 47,528,860 490.838 47,528,860 490.838

HVAC Sub-Total 67,129,540 693.257 112,620,718 1163.051

Non-HVAC Components

Electric 17,647,156 182.245 63,025,564 650.875

Natural Gas 0 0.000 0 0.000

Fuel Oil 0 0.000 0 0.000

Propane 0 0.000 0 0.000

Remote Hot Water 0 0.000 0 0.000

Remote Steam 0 0.000 0 0.000

Non-HVAC Sub-Total 17,647,156 182.245 63,025,564 650.875

Grand Total 84,776,696 875.502 175,646,282 1813.926

Notes:1. 'Cooling Coil Loads' is the sum of all air system cooling coil loads.2. 'Heating Coil Loads' is the sum of all air system heating coil loads.3. Site Energy is the actual energy consumed.4. Source Energy is the site energy divided by the electric generating efficiency (28.0%).5. Source Energy for fuels equals the site energy value.6. Energy per unit floor area is based on the gross building floor area. Gross Floor Area 96832.1 ft² Conditioned Floor Area 96832.1 ft²

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I43 of 48

Page 45: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Energy Budget by System Component - NIH Building 37NIH Building 37b 03/22/2005 Penn State University 10:32PM

1. Annual Coil Loads

ComponentLoad

(kBTU) (kBTU/ft²)

Cooling Coil Loads 47,528,850 490.838

Heating Coil Loads 1,909,667 19.721

Grand Total 49,438,519 510.559

2. Energy Consumption by System Component

ComponentSite Energy

(kBTU)Site Energy

(kBTU/ft²)Source Energy

(kBTU)Source Energy

(kBTU/ft²)

Air System Fans 17,691,014 182.698 63,182,192 652.492

Cooling 47,528,860 490.838 47,528,860 490.838

Heating 1,909,666 19.721 1,909,666 19.721

Pumps 0 0.000 0 0.000

Cooling Towers 0 0.000 0 0.000

HVAC Sub-Total 67,129,540 693.257 112,620,718 1163.051

Lights 6,617,889 68.344 23,635,316 244.086

Electric Equipment 11,030,436 113.913 39,394,416 406.832

Misc. Electric 0 0.000 0 0.000

Misc. Fuel Use 0 0.000 0 0.000

Non-HVAC Sub-Total 17,648,325 182.257 63,029,732 650.918

Grand Total 84,777,865 875.514 175,650,450 1813.969

Notes:1. 'Cooling Coil Loads' is the sum of all air system cooling coil loads.2. 'Heating Coil Loads' is the sum of all air system heating coil loads.3. Site Energy is the actual energy consumed.4. Source Energy is the site energy divided by the electric generating efficiency (28.0%).5. Source Energy for fuels equals the site energy value.6. Energy per unit floor area is based on the gross building floor area. Gross Floor Area 96832.1 ft² Conditioned Floor Area 96832.1 ft²

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I44 of 48

Page 46: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Component Costs - NIH Building 37NIH Building 37b 03/22/2005 Penn State University 10:32PM

0

5000

10000

15000

20000

25000

30000

35000

40000

Cost ($)

MonthJan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Air System Fans Cooling Heating Lights Electric Equipment

1. HVAC Component Costs

MonthAir System Fans

($)Cooling

($)Heating

($)Pumps

($)Cooling Towers

($)HVAC Total

($)

January 38,812 2,229 225 0 0 41,266

February 35,210 2,040 210 0 0 37,460

March 39,053 2,332 185 0 0 41,570

April 38,025 2,392 163 0 0 40,580

May 39,373 2,664 154 0 0 42,191

June 28,806 2,869 153 0 0 31,828

July 29,626 3,162 153 0 0 32,941

August 29,628 3,067 153 0 0 32,848

September 28,757 2,848 153 0 0 31,758

October 29,408 2,565 160 0 0 32,133

November 37,786 2,288 177 0 0 40,251

December 38,849 2,241 204 0 0 41,294

Total 413,332 30,696 2,090 0 0 446,119

2. Non-HVAC Component Costs

MonthLights

($)

Electric Equipment

($)Misc. Electric

($)Misc. Fuel Use

($)Non-HVAC Total

($)Grand Total

($)

January 14,667 24,447 0 0 39,114 80,380

February 13,286 22,144 0 0 35,430 72,890

March 14,668 24,448 0 0 39,116 80,686

April 14,208 23,681 0 0 37,889 78,469

May 14,668 24,448 0 0 39,116 81,307

June 10,694 17,825 0 0 28,519 60,347

July 10,981 18,303 0 0 29,285 62,226

August 10,983 18,307 0 0 29,290 62,138

September 10,698 17,831 0 0 28,529 60,287

October 11,003 18,340 0 0 29,343 61,476

November 14,208 23,682 0 0 37,890 78,141

December 14,667 24,447 0 0 39,115 80,409

Total 154,733 257,903 0 0 412,637 858,756

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I45 of 48

Page 47: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Energy Use by Component - NIH Building 37NIH Building 37b 03/22/2005 Penn State University 10:32PM

1. Monthly Energy Use by System Component

Component Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Air System Fans (kWh) 435911 394322 438593 426648 442189 429412 444424 444364 428527 440265 423962 436323

Cooling

Electric (kWh) 0 0 0 0 0 0 0 0 0 0 0 0

Natural Gas (na) 0 0 0 0 0 0 0 0 0 0 0 0

Fuel Oil (na) 0 0 0 0 0 0 0 0 0 0 0 0

Propane (na) 0 0 0 0 0 0 0 0 0 0 0 0

Remote HW (na) 0 0 0 0 0 0 0 0 0 0 0 0

Remote Steam (kBTU) 0 0 0 0 0 0 0 0 0 0 0 0

Remote CW (kBTU) 34183 31075 35881 36879 41352 44728 49549 47995 44383 39726 35155 34383

Heating

Electric (kWh) 0 0 0 0 0 0 0 0 0 0 0 0

Natural Gas (na) 0 0 0 0 0 0 0 0 0 0 0 0

Fuel Oil (na) 0 0 0 0 0 0 0 0 0 0 0 0

Propane (na) 0 0 0 0 0 0 0 0 0 0 0 0

Remote HW (na) 0 0 0 0 0 0 0 0 0 0 0 0

Remote Steam (kBTU) 5408 4288 2436 758 86 6 1 2 7 489 1770 3845

Pumps (kWh) 0 0 0 0 0 0 0 0 0 0 0 0

Clg. Tower Fans (kWh) 0 0 0 0 0 0 0 0 0 0 0 0

Lighting (kWh) 164733 148790 164733 159419 164733 159419 164733 164733 159419 164733 159419 164733

Electric Eqpt. (kWh) 274569 248000 274569 265714 274569 265714 274569 274569 265714 274569 265714 274569

Misc. Electric (kWh) 0 0 0 0 0 0 0 0 0 0 0 0

Misc. Fuel

Natural Gas (na) 0 0 0 0 0 0 0 0 0 0 0 0

Propane (na) 0 0 0 0 0 0 0 0 0 0 0 0

Remote HW (na) 0 0 0 0 0 0 0 0 0 0 0 0

Remote Steam (kBTU) 0 0 0 0 0 0 0 0 0 0 0 0

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I46 of 48

Page 48: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Energy Costs - NIH Building 37NIH Building 37b 03/22/2005 Penn State University 10:32PM

0

5000

10000

15000

20000

25000

30000

35000

40000

Cost ($)

MonthJan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

HVAC Electric HVAC Remote Steam Non-HVAC Electric

1. HVAC Costs

MonthElectric

($)Natural Gas

($)Fuel Oil

($)Propane

($)

Remote Hot Water

($)Remote Steam

($)

Remote Chilled Water

($)

January 38,812 0 0 0 0 225 2,229

February 35,210 0 0 0 0 210 2,040

March 39,053 0 0 0 0 185 2,332

April 38,025 0 0 0 0 163 2,392

May 39,373 0 0 0 0 154 2,664

June 28,806 0 0 0 0 153 2,869

July 29,626 0 0 0 0 153 3,162

August 29,628 0 0 0 0 153 3,067

September 28,757 0 0 0 0 153 2,848

October 29,408 0 0 0 0 160 2,565

November 37,786 0 0 0 0 177 2,288

December 38,849 0 0 0 0 204 2,241

Total 413,332 0 0 0 0 2,090 30,696

2. Non-HVAC Costs

MonthElectric

($)Natural Gas

($)Fuel Oil

($)Propane

($)

Remote Hot Water

($)Remote Steam

($)

January 39,112 0 0 0 0 0

February 35,428 0 0 0 0 0

March 39,113 0 0 0 0 0

April 37,887 0 0 0 0 0

May 39,114 0 0 0 0 0

June 28,517 0 0 0 0 0

July 29,283 0 0 0 0 0

August 29,288 0 0 0 0 0

September 28,528 0 0 0 0 0

October 29,341 0 0 0 0 0

November 37,887 0 0 0 0 0

December 39,112 0 0 0 0 0

Total 412,609 0 0 0 0 0

Hourly Analysis Program v.4.2 Page 1 of 1

Appendix I47 of 48

Page 49: APPENDIX I HAP OUTPUT ·  · 2005-04-02Total coil load 174.6 Tons Total coil load 2095.3 MBH Sensible coil load 1975.7 MBH Coil CFM at Oct 1500 55924 CFM Max block CFM at ... COOLING

Monthly Energy Use by Energy Type - NIH Building 37NIH Building 37b 03/22/2005 Penn State University 10:32PM

1. HVAC Energy Use

MonthElectric(kWh)

Natural Gas(na)

Fuel Oil(na)

Propane(na)

Remote HW(na)

Remote Steam(kBTU)

Remote CW(kBTU)

Jan 435,911 0 0 0 0 5,408 34,183

Feb 394,322 0 0 0 0 4,288 31,075

Mar 438,593 0 0 0 0 2,436 35,881

Apr 426,648 0 0 0 0 758 36,879

May 442,189 0 0 0 0 86 41,352

Jun 429,412 0 0 0 0 6 44,728

Jul 444,424 0 0 0 0 1 49,549

Aug 444,364 0 0 0 0 2 47,995

Sep 428,527 0 0 0 0 7 44,383

Oct 440,265 0 0 0 0 489 39,726

Nov 423,962 0 0 0 0 1,770 35,155

Dec 436,323 0 0 0 0 3,845 34,383

Totals 5,184,940 0 0 0 0 19,097 475,289

2. Non-HVAC Energy Use

MonthElectric(kWh)

Natural Gas(na)

Fuel Oil(na)

Propane(na)

Remote HW(na)

Remote Steam(kBTU)

Jan 439,272 0 0 0 0 0

Feb 396,767 0 0 0 0 0

Mar 439,272 0 0 0 0 0

Apr 425,104 0 0 0 0 0

May 439,272 0 0 0 0 0

Jun 425,104 0 0 0 0 0

Jul 439,272 0 0 0 0 0

Aug 439,272 0 0 0 0 0

Sep 425,104 0 0 0 0 0

Oct 439,272 0 0 0 0 0

Nov 425,104 0 0 0 0 0

Dec 439,272 0 0 0 0 0

Totals 5,172,086 0 0 0 0 0

Hourly Analysis Program v.4.2 Page 1 of 1