ATTACHMENT A

Page 2: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

GEOTECHNICAL ENGINEERING REPORT Sewer Aerial Crossing 1781 Leicester Road Richmond, Virginia

Schnabel Reference 15613100

August 28, 2015 Prepared For: Greeley and Hansen

Page 3: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

August 28, 2015

Ms. Neepa Shah, P.E.

Greeley and Hansen

9020 Stony Point Parkway, Suite 475

Richmond, Virginia 23235

Subject: Project 15613100, Geotechnical Engineering Report, Sewer Aerial Crossing, 1781

Leicester Road, Richmond, Virginia

Dear Ms. Shah:

SCHNABEL ENGINEERING CONSULTANTS, INC. (Schnabel) is pleased to submit our geotechnical

engineering report for this project. This study was performed in accordance with our proposal dated July

2, 2015, as authorized by Mr. George Guhse on August 4, 2015.

SCOPE OF SERVICES

Our proposal dated July 2, 2015, defines the scope of services for this project. The scope of services

includes the following:

Subsurface exploration including three hand augers.

Laboratory testing of materials encountered in the subsurface exploration.

Geotechnical engineering analysis and report.

SITE AND PROJECT DESCRIPTION

The existing sewer that crosses the unnamed creek behind 1781 Leicester Road in Richmond, Virginia

collapsed and a section of the southeastern bank was washed out during a storm event. The sewer has

been temporarily replaced with a 12-inch PVC pipe that is supported with 4x4 timbers and by an existing

concrete foundation along the northeastern bank. The stream channel is steeply sloped and lined with

riprap. The existing easement is heavily overgrown and overhead power and telephone lines are present

within the easement.

We understand that a concrete supporting beam and new foundations on each side of the creek will be

constructed. Additionally the southern side of the creek bank will be reconstructed, most likely with

gabion baskets.

Page 4: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

Greeley and Hansen

Sewer Aerial Crossing, 1781 Leicester Road

August 28, 2015 Page 2 Schnabel Engineering Consultants, Inc. Project 15613100 ©2015 All Rights Reserved

We obtained the site information and project details from the communication with Greely and Hansen,

and through our site visits. A Site Vicinity Map is included as Figure 1.

SUBSURFACE EXPLORATION AND LABORATORY TESTING PROGRAM

We performed a subsurface exploration and field testing program to identify the subsurface stratigraphy

underlying the site and to evaluate the geotechnical properties of the materials encountered. This

program included hand augers. Exploration methods used are discussed below. The appendices contain

the results of our exploration.

Subsurface Exploration Methods

Hand Augers

Our personnel drilled three hand augers on August 12, 2015. Appendix A includes specific observations,

remarks, and logs for the hand augers; classification criteria; excavation methods; and sampling

protocols. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

will retain soil samples up to 45 days beyond the issuance of this report, unless you request other

disposition.

Soil Laboratory Testing

Our laboratory performed tests on selected samples collected during the subsurface exploration. The

testing aided in the classification of materials encountered in the subsurface exploration and provided

data for use in the development of recommendations for design of foundations and earthwork. The

results of the laboratory tests are included in Appendix B and are summarized for each stratum in the Site

Geology and Subsurface Conditions section of this report. Selected test results are also shown on the

hand auger logs in Appendix A.

Index Testing

We performed index testing on a sample collected as part of the exploration to provide soil classification

and to provide parameters for use with published correlations with soil properties. Index testing included

performing natural moisture content, Atterberg Limits, and gradation tests on one jar sample of soil

representing Stratum C.

SITE GEOLOGY AND SUBSURFACE CONDITIONS

Site Geology

We reviewed existing geologic data and information in our files. Based on this review, the geologic

stratigraphy consists of Pleistocene Age upland terrace deposits over residual materials derived from the

weathering of the Petersburg granite formation. The terrace deposits are alluvial soils that typically

consist of a mixture of clay, silt, sand and gravel. These soils typically exhibit moderate to high strength

and low to moderate compressibility. The residual soils are derived from the chemical and physical

weathering of the underlying parent material, the Petersburg granite rock.

Page 5: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

Greeley and Hansen

Sewer Aerial Crossing, 1781 Leicester Road

August 28, 2015 Page 3 Schnabel Engineering Consultants, Inc. Project 15613100 ©2015 All Rights Reserved

The above stratigraphy is typical in the Richmond area. However, in the immediate vicinity of the creek,

some or all of the above strata have been eroded or excavated, and commonly have been replaced with

recent alluvial deposits.

Generalized Subsurface Stratigraphy

We characterized the following generalized subsurface stratigraphy based on the exploration and

laboratory test data included in the appendices.

Ground Cover: Forest Litter, Rootmat, and Topsoil

At the ground surface, hand augers HA-1 and HA-3 encountered a 2 and 3 inch thick layer of

forest litter, rootmat and topsoil. Hand auger HA-2 was performed at the toe of the recently failed

slope, and did not have any ground cover.

Stratum A: Alluvium

Hand auger HA-2 encountered a layer of recent alluvial soils consisting of sandy elastic silt (MH)

with varying amounts of mica and gravel to a depth of 2 ft, El 150. Based on the Dynamic Cone

Penetrometer (DCP) tests performed, this stratum is very soft: DCP = 1 to 2.

Stratum B: Terrace

Below the ground cover, hand augers HA-1 and HA-3 encountered a terrace deposit consisting of

silty sand and silty gravel (SM, GM) with varying amounts of gravel and root fragments to depths

of 2.9 and 3.7 ft, El 155.3 and 155.6. The natural moisture content measured was about 8

percent. Based on the DCP tests performed, this stratum is loose to medium dense: DCP = 6 to

>30.

Stratum C: Residuum

Below the alluvial and terrace soils, the hand augers encountered residual soils consisting of silty

sand and silty sand with gravel (SM) with varying amounts of mica and rock fragments to the

bottoms of the hand augers, a maximum depth of 10 ft. One sample of soil from this stratum was

of moderate plasticity having a liquid limit of 50, and a plasticity index of 16. The natural moisture

contents measured were about 10 to 19 percent. Based on the DCP tests performed, this stratum

is loose to medium dense: DCP = 4 to 28.

Groundwater

We observed groundwater in hand auger HA-2 at a depth of 1.1 ft, about El 150.9. The groundwater

elevation was near the surface level of the stream. The hand auger logs in Appendix A include

groundwater observations obtained during our subsurface exploration. These data include depths to

groundwater encountered during drilling and upon drilling completion.

The groundwater levels on the logs indicate our estimate of the hydrostatic water table at the time of our

subsurface exploration. The final design should anticipate the fluctuation of the hydrostatic water table

depending on variations in precipitation, surface runoff, leaking utilities, stream levels, and similar factors.

Page 6: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

Greeley and Hansen

Sewer Aerial Crossing, 1781 Leicester Road

August 28, 2015 Page 4 Schnabel Engineering Consultants, Inc. Project 15613100 ©2015 All Rights Reserved

GEOTECHNICAL RECOMMENDATIONS

We based our geotechnical engineering analysis on the information developed from our subsurface

exploration and soil laboratory testing, along with the site plan furnished to our office. We recommend

spread footings for support of the proposed sewer based on our analysis. The following sections of the

report provide our detailed recommendations.

Spread Footings

We consider spread footings suitable for support of the proposed sewer. Footings should be founded on

suitable natural soils of Strata B and C or on compacted structural fill. Compacted structural fill should

meet the requirements outlined in the Site Grading and Earthwork section of this report. We recommend

footings supported on these materials be designed for a net allowable soil bearing pressure of 2,000 psf.

This bearing pressure provides a factor of safety against general bearing capacity failure of at least 3.0.

The above allowable soil bearing pressure may be increased by 33 percent for wind and seismic loads

when used in conjunction with load combinations defined in IBC 2009 Section 1605.3.2, Alternative Basic

Load Combinations for use with allowable stress design. This increase is not applicable for other

allowable stress load combinations, strength design, or load and resistance factor design.

We anticipate suitable natural soils will be encountered at shallow depths (less than 2 ft) below existing

grade. All footing subgrades should be observed by the Geotechnical Engineer prior to placement of

concrete to evaluate if subgrade materials are as anticipated.

If unsuitable soils are encountered at the design bearing grade, these soils should be removed and

replaced as recommended by the Geotechnical Engineer. Unsuitable soils should be replaced with

compacted fill, open graded crushed stone such as VDOT No. 57 or No. 78 aggregate, controlled low

strength material (CLSM), or concrete.

Settlements of shallow foundations supported on suitable natural soils and on properly placed compacted

structural fill are not expected to exceed about one-half (1/2) of an inch. Differential settlements between

similarly loaded footings are not expected to exceed about half this value.

The footings should be at least 12 inches wide, for shear considerations. The footings should be founded

at least 2 ft below final grade for frost protection.

Earthwork

Subgrades to receive compacted structural fill for foundation support should be stripped of vegetation,

topsoil, and organic matter. Schnabel’s subsurface exploration indicated topsoil to depths of 0.2 to 0.3 ft

below the ground surface. However, stripping of wooded sites typically results in some disturbance and

contamination of near-surface soils, particularly during periods of wet weather. Therefore, we

recommend a topsoil stripping depth of 0.5 ft be considered for the site during the project planning.

Compacted structural fill subgrades should consist of suitable natural soils of Strata B and C. These soils

are expected to be encountered at shallow depths beneath the topsoil and root mat.

Page 7: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

Greeley and Hansen

Sewer Aerial Crossing, 1781 Leicester Road

August 28, 2015 Page 5 Schnabel Engineering Consultants, Inc. Project 15613100 ©2015 All Rights Reserved

The Geotechnical Engineer should evaluate the suitability of the fill subgrades. The stripped subgrades

should be evaluated with a combination of probing with a penetrometer, drilling hand augers, or observing

test pits to evaluate the subgrade suitability for support of the compacted structural fill prior to any

undercutting or initiation of fill placement. Areas that are considered unsuitable should be scarified, dried

and recompacted, or undercut and replaced with compacted structural fill as recommended by the

Geotechnical Engineer.

Compacted structural fill subgrades should be free of snow, ice, and frozen soils. If snow, ice, or frozen

soils are present at subgrade levels, these materials should be removed as recommended by the

Geotechnical Engineer.

The existing concrete foundation for the sewer will need to be removed before earthwork construction.

Existing foundations should be completely removed from the area of the new sewer foundations.

Compacted structural fill and backfill should consist of non-organic on-site soils. If off-site borrow

materials are needed, these soils should classify SC, SM, SP, SW, GC, GM, GP or GW according to

ASTM D2487. Fill materials should not contain particles larger than 3 inches.

Compacted structural fill should be placed in maximum 8-inch thick horizontal, loose lifts. Fill should be

compacted to at least 95 percent of the maximum dry density per ASTM D698 Standard Proctor. Backfill

placed in excavations, trenches, and other areas that large compaction equipment cannot access should

be placed in maximum 6-inch thick lifts. Backfill should meet the material, placement, and compaction

requirements outlined above.

CONSTRUCTION CONSIDERATIONS

Spread Footings

The Contractor should exercise care during excavation for footings so that as little disturbance as

possible occurs at the foundation level. The Contractor should carefully clean loose or soft soils from the

bottom of the excavation before placing concrete. A Geotechnical Engineer from our firm should observe

footing subgrades prior to concrete placement to evaluate whether subgrade soils are as anticipated in

this report.

Footing subgrades needing undercut may be concreted at the elevation of undercut or backfilled to the

original design subgrade elevation with an open-graded crushed stone such as No. 57 aggregate.

Placement of concrete should take place the same day as excavation of footings.

Earthwork

The hand auger data indicates the approximate depth of topsoil based on our visual identification

procedures. The depth of stripping needed to provide a suitable base for placement of earthwork or

pavements may include topsoil and other softer surficial layers. Stripping depths in wooded or previously

cultivated areas will be greater, particularly during periods of wet weather. The depth of required stripping

should be determined by the excavation Contractor prior to construction using test pits, probes, or other

means.

Page 8: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

Greeley and Hansen

Sewer Aerial Crossing, 1781 Leicester Road

August 28, 2015 Page 6 Schnabel Engineering Consultants, Inc. Project 15613100 ©2015 All Rights Reserved

The on-site soils are susceptible to moisture changes, will be easily disturbed, and will be difficult to

compact under wet weather conditions. Drying and reworking of the soils are likely to be difficult during

periods of wet months. We recommend that the earthwork phases of this project be performed during the

warmer, drier times of the year to limit the potential for disturbance of on-site soils.

Engineering Services During Construction

The engineering recommendations provided in this report are based on the information obtained from the

subsurface exploration and laboratory testing. However, conditions on the site may vary between the

discrete locations observed at the time of our subsurface exploration. The nature and extent of variations

between hand augers may not become evident until during construction.

To account for this variability, we should provide professional observation and testing of subsurface

conditions revealed during construction as an extension of our engineering services. These services will

also help in evaluating the contractor's conformance with the plans and specifications in accordance with

building code requirements. Because of our unique position to understand the intent of the geotechnical

engineering recommendations, retaining Schnabel for these services will allow the owner to receive

consistent service throughout the project construction.

General Specification Recommendations

An allowance should be established to account for possible additional costs that may be required to

construct earthwork and foundations as recommended in this report. Additional costs may be incurred for

a variety of reasons including variation of soil between hand augers, unsuitable soils, need for borrow fill

material, wet on-site soils, obstructions, temporary dewatering, etc.

We recommend that the construction contract include unit prices for scarifying and drying wet and/or

loose subgrade soils, and provide an allowance for this work. In addition, the construction contract

should include an allowance for undercutting soft or loose, near-surface soils, and replacement with

compacted structural fill. Add/deduct unit prices should also be established in the contract so

adjustments can be made for the actual volume of materials handled.

The project specifications should indicate the Contractor's responsibility for providing adequate site

drainage during construction. Inadequate drainage will most likely lead to disturbance of soils by

construction traffic and increased volume of undercut.

This report may be made available to prospective bidders for informational purposes. We recommend

that the project specifications contain the following statement:

Schnabel Engineering Consultants, Inc., has prepared this geotechnical engineering report for

this project. This report is for informational purposes only and is not part of the contract

documents. The opinions expressed represent the Geotechnical Engineer’s interpretation of the

subsurface conditions, tests, and the results of analyses performed. Should the data contained in

this report not be adequate for the Contractor's purposes, the Contractor may make, before

bidding, independent exploration, tests and analyses. This report may be examined by bidders at

the office of the Owner, or copies may be obtained from the Owner at nominal charge.

Page 9: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

Greeley and Hansen

Sewer Aerial Crossing, 1781 Leicester Road

August 28, 2015 Page 7 Schnabel Engineering Consultants, Inc. Project 15613100 ©2015 All Rights Reserved

Additional data and reports prepared by others that could have an impact upon the Contractor's bid

should also be made available to prospective bidders for informational purposes.

LIMITATIONS

We based the analyses and recommendations submitted in this report on the information revealed by our

exploration. We attempted to provide for normal contingencies, but the possibility remains that

unexpected conditions may be encountered during construction.

This report has been prepared to aid in the evaluation of this site and to assist in the design of the project.

It is intended for use concerning this specific project. We based our recommendations on information on

the site and proposed construction as described in this report. Substantial changes in loads, locations, or

grades should be brought to our attention so we can modify our recommendations as needed. We would

appreciate an opportunity to review the plans and specifications as they pertain to the recommendations

contained in this report, and to submit our comments to you based on this review.

We have endeavored to complete the services identified herein in a manner consistent with that level of

care and skill ordinarily exercised by members of the profession currently practicing in the same locality

and under similar conditions as this project. No other representation, express or implied, is included or

intended, and no warranty or guarantee is included or intended in this report, or other instrument of

service.

We appreciate the opportunity to be of service for this project. Please call us if you have any questions regarding this report.

Sincerely,

SCHNABEL ENGINEERING CONSULTANTS, INC.

Kevin D. Pocta, EIT

Senior Staff Engineer

Jeremy L. Mydlinski, PE

Senior Associate

KDP:JLM

Figures

Appendix A: Subsurface Exploration Data

Appendix B: Soil Laboratory Test Data

G:\2011 - 2020\2015\Richmond\15613100 Aerial Crossing, 1781 Leicester Road\03-SE Products\03-Reports\02-Final\15613100 GER Sewer Aerial Crossing.docx

Page 10: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

August 28, 2015 Schnabel Engineering Consultants, Inc. Project 15613100 ©2015 All Rights Reserved

FIGURES

Figure 1: Site Vicinity Map

Figure 2: Hand Auger Location Plan

Page 11: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We
Page 12: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We
Page 13: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

August 28, 2015 Schnabel Engineering Consultants, Inc. Project 15613100 ©2015 All Rights Reserved

APPENDIX A

SUBSURFACE EXPLORATION DATA

Subsurface Exploration Procedures

General Notes for Subsurface Exploration Logs

Identification of Soil

Hand Auger Logs, HA-1 through HA-3

Page 14: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

August 28, 2015 Schnabel Engineering Consultants, Inc. Project 15613100 ©2015 All Rights Reserved

SUBSURFACE EXPLORATION PROCEDURES

Hand Augers

Our personnel drilled the hand augers using a 3-inch O.D. auger. We visually classified the soils

encountered according to ASTM D2488. Dynamic Cone Penetrometer (DCP) measurements were

obtained in the hand augers to provide a general indication of the relative density or consistency of the in-

situ soils. DCP blows are indicated on the hand auger logs. Each number represents the blows needed

to drive the DCP 1¾ inches, using a 15-lb weight falling 20 inches.

Soil Classification Criteria

The group symbols on the logs represent the Unified Soil Classification System Group Symbols (ASTM

D2487) based on visual observation and limited laboratory testing of the samples. Criteria for visual

identification of soil samples are included in this appendix. Some variation can be expected between

samples visually classified and samples classified in the laboratory.

Hand Auger Locations and Elevations

Hand augers were located using sub-meter GPS equipment. Approximate hand auger locations are

shown on Figure 2. Ground surface elevations at the hand auger locations were obtained from the

topographic site plan provided by Greeley and Hansen. Locations and elevations should be considered

no more accurate than the methods used to determine them.

Page 15: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

August 28, 2015 Schnabel Engineering Consultants, Inc. Project 15613100 ©2015 All Rights Reserved

GENERAL NOTES FOR SUBSURFACE EXPLORATION LOGS

1. Numbers in sampling data column next to Dynamic Cone Penetrometer (DCP) symbols indicate

blows needed to drive the DCP 1¾ inches, using a 15-lb weight falling 20 inches.

2. Visual classification of soil is in accordance with terminology set forth in “Identification of Soil.”

The ASTM D2487 group symbols (e.g., CL) shown in the classification column are based on

visual observations.

3. Estimated water levels indicated on the logs are only estimates from available data and may vary

with precipitation, porosity of the soil, site topography, and other factors.

4. The logs and related information depict subsurface conditions only at the specific locations and at

the particular time when drilled or excavated. Soil conditions at other locations may differ from

conditions occurring at these locations. Also, the passage of time may result in a change in the

subsurface soil and water level conditions at the subsurface exploration location.

5. The stratification lines represent the approximate boundary between soil and rock types as

obtained from the subsurface exploration. Some variation may also be expected vertically

between samples taken. The soil profile, water level observations and penetration resistances

presented on these logs have been made with reasonable care and accuracy and must be

considered only an approximate representation of subsurface conditions to be encountered at the

particular location.

6. Key to symbols and abbreviations:

S-1, DCP Sample No., Dynamic Cone Penetrometer Test

5+10+1 Number of blows in each 1.75-inch increment

LL Liquid Limit

MC Moisture Content (percent)

PL Plastic Limit

%Passing#200 Percent by weight passing a No. 200 Sieve

Page 16: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

IDENTIFICATION OF SOIL

I. DEFINITION OF SOIL GROUP NAMES (ASTM D2487) SYMBOL GROUP NAME

II. DEFINITION OF SOIL COMPONENT PROPORTIONS (ASTM D2487)

III. GLOSSARY OF MISCELLANEOUS TERMS SYMBOLS

FILLPROBABLE FILL

DISINTEGRATED ROCK (DR)PARTIALLY WEATHERED ROCK (PWR)BOULDERS & COBBLES

LENSESLAYERSPOCKETMOISTURE CONDITIONSCOLOR

Page 17: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We
Page 18: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We
Page 19: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We
Page 20: ATTACHMENT A - City of Richmond, Virginia. Figure 2 included at the end of this report indicates the approximate hand auger locations. We

August 28, 2015 Schnabel Engineering Consultants, Inc. Project 15613100 ©2015 All Rights Reserved

APPENDIX B

SOIL LABORATORY TEST DATA

Summary of Laboratory Tests