2.1 Current Carrying Capacity & Voltage Drop
2.2 Current Rating Factors
2.3 Short Circuit Ratings
2.4 Installation
3. Control Cables
3.0 Data Tables for control cables
This catalogue includes detailes about our product range of control & instrument cables providing our customers with general technical infromation and approximate dimensions and weights for the finished cables.
6
6
7
8
10
12
16
19
21
22
26
3
4. Instrument Cables
4.0 Data Tables for instrument cables
5. Building & Earthing Wires
5.0 Data Tables for earthing & building wires
6. Fire Resistance Control & Instrument Cables
6.0 Data Tables for Fire Resistance Control & Instrument Cables
7. Glossary
54
82
88
124
4 BICC CABLES
1.0 BICC Cables Background
5
1.0 BICC Cables Background
6 BICC CABLES
Incorporation of BICC as a joint venture between BICC Cables and Electro George Group.
Acquisition of 100% shares of BICC by consortium of financial investors led by Karnak Investments Ltd.
Acquisition of 100% shares of BICC shares by General Cable Coporation.
Acquisition of 100% shares of BICC shares by Amana International Holding.
1.1 History
1.2 Product Range
The company was originally established in 1996 under the name of BICC Egypt as a joint venture between BICC Cables UK and Egyptian investors. It was the only multinational cable manufacturer in Egypt. In September 2010, General Cable, a Fortune of 500 company and the leading manufacturer of wires and cables with 38 production facilities around the world, acquired BICC and rebranded itto General Cable.In May 2016, as part of its strategy to refocus on the American and European markets, General Cable sold the factory to a group of investors. The company gained its original brand name BICC Cables.
-Instrument Cables-Fire resistance & Fire Alarm Cables-Overhead Transmission Lines
We are proud of what we have achieved during last 3 years under the umbrella of our current management(AMANA HOLDING) as we could supply our cables in the most vital projects in country in many sectors such as contracting, industrial , tourism , electrical power stations, water treatment stations , airports,………etc.Also, we acquired new machines seeking increase our production capacity and improving ourproduct quality.There is still much work to be done and we are seeking in the current time to establish new production line so that we can meet our customer needs and satisfaction.
-LV Power Cables-Control Cables -Building Wires
This publication covers our range of production for Control & Instrument Cables.
BICC Cables Scope of production includes as follows:
1.0 BICC Cables Background
7
1.3 Product QualityQuality Control in all steps of manufacturing is one of the priorities of BICC cables, keen to provide its customers with the best quality and meeting deadlines. All our facilities operate under the highest ISO:9001:2015 Standards.We use the latest measuring devices (made in EU) for an effective application of quality standards.Also, we are using only tried and tested materials and processes in full compliance with all the relevant British and International standards. We are very keen to purchase raw materials from the most accredit-ed suppliers either from local market or from abroad.
8 BICC CABLES
1.4 Certifications• Quality Management System ISO 9001:2015
• KEMA Approval
• Health and Safety OHSAS 18001
1.0 BICC Cables Background
9
• BASEC Approval
10 BICC CABLES
Product Code For Control Cables
NO. OF CORES
THE CONDUCTORMATERIAL
THE OUTER SHEATH MATERIAL
THE ARMOURINGMATERIAL
SCREENINGMATERIAL
THE BEDDINGMATERIAL
THE INSULATIONMATERIAL
TAPE
01C Single Core02C Two Cores03C Three Cores
P Polyvinyl Chloride (PVC)X Cross Linked - Polyethylene (XLPE)L Low Smoke Zero Halogen (LSOH)
P Polyvinyl Chloride (PVC)L Low Smoke Zero Halogen (LSOH)
P Polyvinyl Chloride (PVC)L Low Smoke Zero Halogen (LSOH)
THE CONDUCTORCROSS SECTION
AREA (MM2)
C Copper
W Wire Armoured
CT Copper Tape
M Mica Tape
1.5 Product Code
1.0 BICC Cables Background
11
Product Code For Instrumentation Cables
NO.OF PAIRS/TRAIDS
01P 1 Pair02P 2 Pairs01T 1 Traid
THE CONDUCTORCROSS SECTION
AREA (MM2)
THE CONDUCTORMATERIALC Copper
THE OUTER SHEATH MATERIAL
P Polyvinyl Chloride (PVC)L Low Smoke Zero Halogen (LSOH)
THE ARMOURINGMATERIAL
T Tape ArmouredW Wire Armoured
THE BEDDINGMATERIAL
IS : Individual Shielding
P Polyvinyl Chloride (PVC)L Low Smoke Zero Halogen (LSOH)
THE INSULATIONMATERIAL
P Polyvinyl Chloride (PVC)X Cross Linked - Polyethylene (XLPE)L Low Smoke Zero Halogen (LSOH)
TAPE
M Mica Tape
OS : Overall Shielding
12 BICC CABLES
Specialist advice on all matters concerning control & instrument cables is available from BICC Cables sales team or direct from:
BICC CABLES S.A.E, FactoryIndustrial Zone, Abu Rawash Km 28 Cairo Alexandria Desert Road Giza, EgyptTel.: (202) 3539 0251,2,3,4Fax: (202) 3539 0255,6E-mail: [email protected]
1.6 Technical Advisory Service
Head Office34 Block A 1st District Services Center New Cairo,EgyptTel: (202) 22471677 / 22471699Fax.: (202) 22472011Website: www.bicccables.comE-mail: [email protected]
1.0 BICC Cables Background
13
Our products are designed & constructed to be hazard free under the prescribed conditions of use.
14 BICC CABLES
2.0 General Technical Information
15
2.0 General Technical Information
16 BICC CABLES
2.0 General Technical Information
2.1 Current Carrying Capacity & Voltage DropCurrent carrying capacity is the maximum current that can be continuously carried without exceeding its temperature rating. It is also known as ampacity.The effect of resistance to current flow is heating and this is dependent upon the size of the conductor where increasing the conductor size increases the current carrying capacity.Also, current is affected with insulation material around the conductor where the higher the temperature resistance of the insulating material, the higher the ampacity. A 90°C rated insulation (familiar for XLPE insulation) will have a higher current capacity than a 70°C rated insulation (familiar for PVC insulation).Also, current rating is affected by installation environment & its temperature. When current flows in a cable conductor there is a voltage drop between the ends of the conductor which is the product of the current and the impedance.The following tables indicate current rating and voltage drop for conductor sizesfrom 1 mm2 up to 10 mm2 For cables installed in air and laid in ground for 600/1000 V PVC & XLPE insulated cables.
17
Current Rating & Voltage Drop for PVC insulted Cables (installed in Air)
Current Rating & Voltage Drop for XLPE insulted Cables (installed in Air)
Conductor NominalArea (mm2 )
Two Cores Three and Four Cores
Current Rating in Free air at 40oC (Amp.)
Voltage Drop (mV/A/m)
Current Rating in Free air at 40oC (Amp.)
Voltage Drop (mV/A/m)
1.0 15 35 12 30
1.5 19 29 17 25
2.0 23 25 19 20
2.5 27 18 23 15
3.0 30 16 25 13
4.0 36 11 30 9.5
6.0 46 7.3 39 6.4
10.0 63 4.4 54 3.8
Conductor NominalArea (mm2 )
Two Cores Three and Four Cores
Current Rating in Free air at 40oC (Amp.)
Voltage Drop (mV/A/m)
Current Rating in Free air at 40oC (Amp.)
Voltage Drop (mV/A/m)
1.0 22 37 18 32
1.5 26 31 23 27
2.0 31 25 26 22
2.5 35 19 30 16
3.0 39 17 34 14
4.0 47 12 40 10
6.0 60 7.9 51 6.8
10.0 82 4.7 71 4.0
For cables installed in free air (Reference method 11 on cable tray or method 13 in free air– IEE wiring regulations 17th edition) & ambient temperature 40°C.
- Cables installed in Free Air
18 BICC CABLES
2.0 General Technical Information
- Cables laid in Ground & installed in single way ducts
Current ratings are based on Ground temperature 35°C, soil thermal resistivity 1.2 °C m/W, depth of laying 0.5 Mt and all circuits are thermally independent.Currents in ducts are for 100 mm diameter single way ducts.
Current Rating & Voltage Drop for PVC insulted Cables (Cables laid in Ground & Duct)
Current Rating & Voltage Drop for XLPE insulted Cables (Cables laid in Ground & Duct)
Conductor Nominal
Area (mm2)
Two Cores Three and Four Cores
Current Rating (Amp.)Voltage Drop
(mV/A/m)
Current Rating (Amp.)Voltage Drop
(mV/A/m)In Ground at (35oC)
In Duct at (35oC)
In Ground at (35oC)
In Duct at (35oC)
1.0 19 16 35 16 14 30
1.5 26 21 29 22 18 25
2.0 29 24 25 25 20 20
2.5 33 27 18 28 23 15
3.0 36 30 16 31 26 13
4.0 44 36 11 38 30 9.5
6.0 55 46 7.3 47 38 6.4
10.0 74 61 4.4 62 51 3.8
Conductor Nominal
Area (mm2)
Two Cores Three and Four Cores
Current Rating (Amp.)Voltage Drop
(mV/A/m)
Current Rating (Amp.)Voltage Drop
(mV/A/m)In Ground at (35oC)
In Duct at (35oC)
In Ground at (35oC)
In Duct at (35oC)
1.0 26 22 37 22 18 32
1.5 33 27 31 28 22 27
2.0 37 31 25 32 26 22
2.5 42 35 19 36 29 16
3.0 46 39 17 40 32 14
4.0 56 46 12 47 39 10
6.0 70 58 7.9 59 48 6.8
10.0 94 77 4.7 79 65 4
19
Current Rating for Non Sheathed (450/750 V) Single Core Cables
Current Rating Factors for Ambient Air Temperature (Cables installed in Air)
Current Rating Factors for Ground Temperature (Cables laid direct or in ground)
Conductor Area (mm2)Current Rating (Amp.)
In Free Air In Pipes
1.0 13 10
1.5 16 13
2.0 18 14
2.5 25 20
3.0 27 21
4.0 33 23
6.0 39 28
10.0 58 40
2.2 Current Rating FactorsCurrent carrying capacity is affected by installation environment and several factors such as ambient or ground temperature, change in depth of laying , soil thermal resistivity or number of grouping of cables.The current rating must be multiplied by relevant rating factors as in the below tables.
Ambient Air Tem-perature 25°C 30°C 35°C 40°C 45°C 50°C 55°C
Rating Factor
PVC Insulation 1.14 1.10 1.05 1.0 0.96 0.90 0.84
XLPE Insulation 1.22 1.15 1.08 1.0 0.91 0.80 0.70
Ground Temperature 15°C 20°C 25°C 30°C 35°C 40°C 45°C
Rating Factor
PVC Insulation 1.16 1.13 1.08 1.03 1.00 0.95 0.88
20 BICC CABLES
2.0 General Technical Information
Current Rating Factors for Depth Of Laying (For Cables laid in Ground)
Current Rating Factors for Variation in Soil Resistivity(For Cables laid in Ground or Duct)
Current Rating Factors for Number of cables (circuits) in group for cables in horizontal formation
Depth Of Laying (Mt)Multicore Cable
Direct ground In single way ducts
0.5 1.0 1.0
0.6 0.99 0.99
0.8 0.97 0.97
1.00 0.95 0.96
1.25 0.94 0.95
Type of InstallationSoil Thermal Resistivity in o Cm/W
0.8 0.9 1 1.5 2 2.5
Multicore cables laid directly in ground 1.09 1.06 1.04 0.93 0.84 0.77
Multicore cables installed in single way ducts 1.03 1.02 1.02 0.97 0.91 0.87
Method of installation No. of cables in group
Spacing between cable centers
Touching 0.15 Mt. 0.3 Mt. 0.45 Mt. 0.6 Mt.
Cables direct in Ground
2 0.81 0.87 0.91 0.93 0.94
3 0.70 0.78 0.84 0.87 0.90
4 0.63 0.74 0.81 0.86 0.89
5 0.59 0.70 0.78 0.83 0.87
6 0.55 0.67 0.76 0.82 0.86
Cables in single way Ducts
2 0.90 0.93 0.95 0.96
3 0.82 0.87 0.90 0.93
4 0.78 0.85 0.89 0.91
5 0.76 0.82 0.87 0.90
6 0.72 0.81 0.86 0.90
21
2.3 Short Circuit RatingsWhen cables are subjected to temperature higher than those permissible for continuous operation they may suffer damage. Therefore, in installation when there is possibility of the cables being overloaded by mistake or by accident , cables should be selected having regard to the characteristics of the device used or protection against excess current so that the effects of overloading are limited to a degree tolerable to or a relatively short period of operation.
XLPE Insulated CablesThe values of fault current given in the graph are based on the cable being fully loaded at the start of the short circuit (conductor temperature 90°C) and a final conductor temperature of 250°C. It should be ensured that the accessories associated with the cable are also capable of operation at these values of fault current and temperature.
PVC Insulated CablesThe values of fault current given in the graph are based on the cable being fully loaded at the start of the short circuit (conductor temperature 70°C) and a final conductor temperature of 160 oC.
22 BICC CABLES
2.4 Installation All cables in this publication can be used for outdoor applications but some reservations are necessary concerning cables without metal sheath for direct burial such as :- Unarmoured cables are not recommended for laying directly in the ground.- Cables laid directly in the ground, particularly in sustained wet conditions shouldhave extruded bedding.- For installations where there is water-logging or where it is likely to occur, advice should be obtained from our technical department. It may be desirable to recommend an alternative type of outer sheath for the cable (e.g. MDPE).
Also, bending radius shall be considered during installation where cables shall not be bent in radius smaller than that recommended noting that minimum bending radius as follows:
2.0 General Technical Information
Cable support shall be taken into consideration as in the below table
Recommended Support spacing
Recommended Minimum Bending Radius
Overall cable diametermm
Support spacing
Horizontal(mm)
Vertical(mm)
Below 15 350 450
15 to less than 20 400 550
20 to less than 40 450 600
40 to less than 60 700 900
Cable Type Minimum Bending Radius
Control or instrument cable in PVC outer sheath 10 Times of Cable Nominal External Diameter
Control or instrument cable in LSOH outer sheath 15 Times of Cable Nominal External Diameter
23
A world power in cable supply
24 BICC CABLES
3.0 Control Cables
25
3.0 Control Cables
26 BICC CABLES
3.0 Control Cables
Application
Construction
Design Specification Standards
Control Cables are commonly used as interconnecting cables for control devices , e.g. on machine tools, conveyor or assembly lines, transporting equipment, production lines and construction of industrial plants.
1. Conductor Copper (or Tinned Copper) In different flexibility degrees- Solid Copper: Class 1- Stranded Copper: Class 2- Flexible Copper: Class 5
2. Insulation- Cross Linked Polyethylene (XLPE) Maximum conductor temperature is 90°C- Polyvinyl Chloride (PVC) Maximum conductor temperature is 70°C & 105°C for fire alarm cables- Low Smoke Zero Halogen (LSOH) Maximum conductor temperature is 90°C
3. Bedding- Polyvinyl Chloride (PVC)- Low Smoke Zero Halogen (LSOH) (For applications where flame spread, minimal smoke and toxic gases emission are critical)
4. Armour / Screen- Armour : Galvanized Steel Wire Armour (GSWA) One layer of round wires is applied over the bedding for mechanical protection of cable- Screen: Copper Tape Screen (CTS) Screen of copper tape can be applied helically over the bedding
5. Outer Sheath- Polyvinyl Chloride (PVC)- Low Smoke Zero Halogen (LSOH)
Standard specification applied to cable
Standard specification applied to conductor Spread of Flame
principle to IEC 60502-1
IEC 60228
Flame retardant as per IEC 60332-1
27
Sizes
Core Identification
Options Available
Rated Voltage
This publication covers the following range
- No. of cores : From 2 cores up to 48 cores - Conductor area : from 1 mm2 up to 10 mm2
Two cores : Red , Black Three cores : Red , Yellow , Blue Four cores : Red , Yellow , Blue , Black Five cores : Red , Yellow , Blue , Black , Y/GMore than 5 cores : Black with white numbers
Other special colors are available upon request.
Sizes :All sizes are available upon request.
Material :Where necessary, special features can be incorporated into the cable enabling it to have- Improved fire performance- Low smoke and fume (Halogen free )- Termite resistance- Resistance to attack from oils, solvents or corrosive chemicals
For environment where emissions of smoke and toxic gases are critical , insulation , bedding and outer sheath material can be : Low Smoke Zero Halogen which has abbreviations of LS0H , LSOH & LSZH(the 3 abbreviations are the same material) with no halogen content and controlled emission of smokeAlso, it is the same as Low Smoke Halogen Free (LSHF).
Note: Values in the following tables are approximate and subject to manufacturing tolerance.
600/1000 V
28 BICC CABLES
Control Cables, Non Armoured,PVC insulatedApplicationControl cables are used as interconnecting cables for control devicesfor outdoor and indoor installation.
Construction
1. ConductorStranded Copper class 2
2. InsulationPolyvinyl Chloride (PVC)
3. SheathPolyvinyl Chloride (PVC)
3.0 Control Cables
29
Control Cables, Non Armoured, PVC Insulated
Product Code No. of Cores Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.0 mm2
02c001CP00P 2 7/0.43 0.8 8.9 107
03c001CP00P 3 7/0.43 0.8 9.4 182
04c001CP00P 4 7/0.43 0.8 10.1 212
07c001CP00P 7 7/0.43 0.8 12.3 293
12c001CP00P 12 7/0.43 0.8 15.6 434
19c001CP00P 19 7/0.43 0.8 18.0 596
27c001CP00P 27 7/0.43 0.8 21.3 785
37c001CP00P 37 7/0.43 0.8 23.7 997
48c001CP00P 48 7/0.43 0.8 27.0 1255
Conductor 1.5 mm2
02c001.5CP00P 2 7/0.53 0.8 9.4 206
03c001.5CP00P 3 7/0.53 0.8 9.9 215
04c001.5CP00P 4 7/0.53 0.8 10.7 244
07c001.5CP00P 7 7/0.53 0.8 13.0 345
12c001.5CP00P 12 7/0.53 0.8 16.6 521
19c001.5CP00P 19 7/0.53 0.8 19.2 729
27c001.5CP00P 27 7/0.53 0.8 22.7 969
37c001.5CP00P 37 7/0.53 0.8 25.3 1243
48c001.5CP00P 48 7/0.53 0.8 29.1 1573
Conductor 2.0 mm2
02c002C0P00P 2 7/0.60 0.8 9.9 230
03c002C0P00P 3 7/0.60 0.8 10.4 240
04c002C0P00P 4 7/0.60 0.8 11.3 278
07c002C0P00P 7 7/0.60 0.8 13.8 399
12c002C0P00P 12 7/0.60 0.8 17.6 607
19c002C0P00P 19 7/0.60 0.8 20.5 857
27c002C0P00P 27 7/0.60 0.8 24.3 1147
37c002C0P00P 37 7/0.60 0.8 27.2 1480
48c002C0P00P 48 7/0.60 0.8 31.4 1899
30 BICC CABLES
Product Code No. of Cores Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)Conductor 2.5 mm2
02c02.5C0P00P 2 7/0.67 0.8 10.2 250
03c02.5C0P00P 3 7/0.67 0.8 10.7 258
04c02.5C0P00P 4 7/0.67 0.8 11.6 308
07c02.5C0P00P 7 7/0.67 0.8 14.1 447
12c02.5C0P00P 12 7/0.67 0.8 18.2 685
19c02.5C0P00P 19 7/0.67 0.8 21.1 976
27c02.5C0P00P 27 7/0.67 0.8 25.1 1312
37c02.5C0P00P 37 7/0.67 0.8 28.3 1702
48c02.5C0P00P 48 7/0.67 0.8 32.5 2205
Conductor 3 mm2
02c003C0P00P 2 7/0.74 0.8 10.6 280
03c003C0P00P 3 7/0.74 0.8 11.2 295
04c003C0P00P 4 7/0.74 0.8 12.2 336
07c003C0P00P 7 7/0.74 0.8 14.8 494
12c003C0P00P 12 7/0.74 0.8 19.1 763
19c003C0P00P 19 7/0.74 0.8 22.2 1095
27c003C0P00P 27 7/0.74 0.8 26.5 1478
37c003C0P00P 37 7/0.74 0.8 29.8 1946
Conductor 4 mm2
02c004C0P00P 2 7/0.84 1.0 12.2 334
03c004C0P00P 3 7/0.84 1.0 12.9 350
04c004C0P00P 4 7/0.84 1.0 14.0 424
07c004C0P00P 7 7/0.84 1.0 17.1 633
12c004C0P00P 12 7/0.84 1.0 22.3 990
19c004C0P00P 19 7/0.84 1.0 26.1 1435
27c004C0P00P 27 7/0.84 1.0 31.7 1971
37c004C0P00P 37 7/0.84 1.0 35.7 2619
Follow: Control Cables, Non Armoured, PVC Insulated
3.0 Control Cables
31
Product Code No. of Cores Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 6 mm2
02c006C0P00P 2 7/1.04 1.0 13.2 396
03c006C0P00P 3 7/1.04 1.0 14.0 429
04c006C0P00P 4 7/1.04 1.0 15.3 527
Conductor 10 mm2
02c010C0P00P 2 7/1.36 1.0 15.3 513
03c010C0P00P 3 7/1.36 1.0 16.2 583
04c010C0P00P 4 7/1.36 1.0 17.7 725
Follow: Control Cables, Non Armoured, PVC Insulated
32 BICC CABLES
Control Cables, Non Armoured,XLPE insulated ApplicationControl cables are used as interconnecting cables for control devices for outdoor and indoor installations.
Construction
1. ConductorStranded Copper class 2
2. InsulationCross Linked Polyethylene (XLPE)
3. SheathPolyvinyl Chloride (PVC)
3.0 Control Cables
33
Control Cables, Non Armoured, XLPE Insulated
Product Code No. of Cores Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.0 mm2
02c001C0X00P 2 7/0.43 0.7 8.5 160
03c001C0X00P 3 7/0.43 0.7 8.9 175
04c001C0X00P 4 7/0.43 0.7 9.6 184
07c001C0X00P 7 7/0.43 0.7 11.7 248
12c001C0X00P 12 7/0.43 0.7 14.8 359
19c001C0X00P 19 7/0.43 0.7 17.0 483
27c001C0X00P 27 7/0.43 0.7 20.1 628
37c001C0X00P 37 7/0.43 0.7 22.3 784
48c001C0X00P 48 7/0.43 0.7 25.4 982
Conductor 1.5 mm2
02c01.5C0X00P 2 7/0.53 0.7 9.0 182
03c01.5C0X00P 3 7/0.53 0.7 9.4 195
04c01.5C0X00P 4 7/0.53 0.7 10.2 213
07c01.5C0X00P 7 7/0.53 0.7 12.4 295
12c01.5C0X00P 12 7/0.53 0.7 15.7 438
19c01.5C0X00P 19 7/0.53 0.7 18.2 602
27c01.5C0X00P 27 7/0.53 0.7 21.5 792
37c01.5C0X00P 37 7/0.53 0.7 23.9 1006
48c01.5C0X00P 48 7/0.53 0.7 27.3 1266
Conductor 2.0 mm2
02c002C0X00P 2 7/0.60 0.7 9.5 209
03c002C0X00P 3 7/0.60 0.7 10.0 217
04c002C0X00P 4 7/0.60 0.7 10.8 245
07c002C0X00P 7 7/0.60 0.7 13.2 345
12c002C0X00P 12 7/0.60 0.7 16.8 518
19c002C0X00P 19 7/0.60 0.7 19.5 721
27c002C0X00P 27 7/0.60 0.7 23.1 955
37c002C0X00P 37 7/0.60 0.7 25.6 1224
48c002C0X00P 48 7/0.60 0.7 29.6 1550
34 BICC CABLES
Product Code No. of Cores Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 2.5 mm2
02c02.5C0X00P 2 7/0.67 0.7 9.8 230
03c02.5C0X00P 3 7/0.67 0.7 10.3 240
04c02.5C0X00P 4 7/0.67 0.7 11.1 273
07c02.5C0X00P 7 7/0.67 0.7 13.5 390
12c02.5C0X00P 12 7/0.67 0.7 17.3 590
19c02.5C0X00P 19 7/0.67 0.7 20.1 830
27c02.5C0X00P 27 7/0.67 0.7 23.9 1116
37c02.5C0X00P 37 7/0.67 0.7 26.7 1435
48c02.5C0X00P 48 7/0.67 0.7 30.6 1820
Conductor 3 mm2
02c003C0X00P 2 7/0.74 0.7 10.2 250
03c003C0X00P 3 7/0.74 0.7 10.8 270
04c003C0X00P 4 7/0.74 0.7 11.7 300
07c003C0X00P 7 7/0.74 0.7 14.2 433
12c003C0X00P 12 7/0.74 0.7 18.3 662
19c003C0X00P 19 7/0.74 0.7 21.2 940
27c003C0X00P 27 7/0.74 0.7 25.2 1262
37c003C0X00P 37 7/0.74 0.7 28.4 1634
Conductor 4 mm2
02c004C0X00P 2 7/0.84 0.7 11.0 279
03c004C0X00P 3 7/0.84 0.7 11.6 290
04c004C0X00P 4 7/0.84 0.7 12.6 348
07c004C0X00P 7 7/0.84 0.7 15.3 511
12c004C0X00P 12 7/0.84 0.7 19.8 790
19c004C0X00P 19 7/0.84 0.7 23.1 1135
27c004C0X00P 27 7/0.84 0.7 27.8 1529
37c004C0X00P 37 7/0.84 0.7 31.3 2012
Follow: Control Cables, Non Armoured, XLPE Insulated
3.0 Control Cables
35
Product Code No. of Cores Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 6 mm2
02c006C0X00P 2 7/1.04 0.7 12.0 342
03c006C0X00P 3 7/1.04 0.7 12.7 364
04c006C0X00P 4 7/1.04 0.7 13.9 444
Conductor 10 mm2
02c010C0X00P 2 7/1.36 0.7 14.1 453
03c010C0X00P 3 7/1.36 0.7 14.9 508
04c010C0X00P 4 7/1.36 0.7 16.2 630
Follow: Control Cables, Non Armoured, XLPE Insulated
36 BICC CABLES
Control Cables, Armoured, PVC insulated ApplicationControl cables are used as interconnecting cables for control devices and armoured cablesin environment where mechanical damage is expected to occur.
Construction
1. ConductorStranded Copper class 2
2. InsulationPolyvinyl Chloride (PVC)
3. Armour Galvanized Round Steel Wire (GSWA)
4. SheathPolyvinyl Chloride (PVC)
3.0 Control Cables
37
Control Cables, Armoured, PVC Insulated
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.0 mm2
02c001C0PPWP 2 7/0.43 0.8 0.9 13.0 320
03c001C0PPWP 3 7/0.43 0.8 0.9 13.5 400
04c001C0PPWP 4 7/0.43 0.8 0.9 14.2 447
07c001C0PPWP 7 7/0.43 0.8 1.25 17.1 563
12c001C0PPWP 12 7/0.43 0.8 1.25 20.4 877
19c001C0PPWP 19 7/0.43 0.8 1.6 23.5 1100
27c001C0PPWP 27 7/0.43 0.8 1.6 26.8 1546
37c001C0PPWP 37 7/0.43 0.8 1.6 29.4 1872
48c001C0PPWP 48 7/0.43 0.8 2.0 33.7 2260
Conductor 1.5 mm2
02c01.5C0PPWP 2 7/0.53 0.8 0.9 13.5 425
03c01.5C0PPWP 3 7/0.53 0.8 0.9 14.0 439
04c01.5C0PPWP 4 7/0.53 0.8 0.9 14.8 495
07c01.5C0PPWP 7 7/0.53 0.8 1.25 17.8 722
12c01.5C0PPWP 12 7/0.53 0.8 1.6 22.1 1001
19c01.5C0PPWP 19 7/0.53 0.8 1.6 24.7 1416
27c01.5C0PPWP 27 7/0.53 0.8 1.6 28.4 1789
37c01.5C0PPWP 37 7/0.53 0.8 1.6 31.2 2195
48c01.5C0PPWP 48 7/0.53 0.8 2.0 35.8 2918
Conductor 2.0 mm2
02c002C0PPWP 2 7/0.60 0.8 0.9 14.0 451
03c002C0PPWP 3 7/0.60 0.8 0.9 14.5 476
04c002C0PPWP 4 7/0.60 0.8 0.9 15.4 538
07c002C0PPWP 7 7/0.60 0.8 1.25 18.6 794
12c002C0PPWP 12 7/0.60 0.8 1.6 23.1 1225
19c002C0PPWP 19 7/0.60 0.8 1.6 26.0 1578
27c002C0PPWP 27 7/0.60 0.8 1.6 30.3 2034
37c002C0PPWP 37 7/0.60 0.8 1.6 34.1 2504
48c002C0PPWP 48 7/0.60 0.8 2.0 38.1 3352
38 BICC CABLES
Product Code No. of CoresStrand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 2.5 mm2
02c02.5C0PPWP 2 7/0.67 0.8 0.9 14.3 481
03c02.5C0PPWP 3 7/0.67 0.8 0.9 14.8 511
04c02.5C0PPWP 4 7/0.67 0.8 1.25 16.4 656
07c02.5C0PPWP 7 7/0.67 0.8 1.25 18.9 863
12c02.5C0PPWP 12 7/0.67 0.8 1.6 23.7 1346
19c02.5C0PPWP 19 7/0.67 0.8 1.6 26.6 1749
27c02.5C0PPWP 27 7/0.67 0.8 1.6 31.0 2253
37c02.5C0PPWP 37 7/0.67 0.8 2.0 35.0 3016
48c02.5C0PPWP 48 7/0.67 0.8 2.0 39.2 3746
Conductor 3 mm2
02c003C0PPWP 2 7/0.74 0.8 0.9 14.7 504
03c003C0PPWP 3 7/0.74 0.8 0.9 15.3 540
04c003C0PPWP 4 7/0.74 0.8 1.25 17.0 696
07c003C0PPWP 7 7/0.74 0.8 1.25 19.6 921
12c003C0PPWP 12 7/0.74 0.8 1.6 24.6 1442
19c003C0PPWP 19 7/0.74 0.8 1.6 27.9 1887
27c003C0PPWP 27 7/0.74 0.8 1.6 32.4 2500
37c003C0PPWP 37 7/0.74 0.8 2.0 36.5 3400
Conductor 4 mm2
02c004C0PPWP 2 7/0.84 1.0 1.25 17.0 672
03c004C0PPWP 3 7/0.84 1.0 1.25 17.7 730
04c004C0PPWP 4 7/0.84 1.0 1.25 18.8 838
07c004C0PPWP 7 7/0.84 1.0 1.25 21.9 1238
12c004C0PPWP 12 7/0.84 1.0 1.6 27.8 1776
19c004C0PPWP 19 7/0.84 1.0 1.6 32.0 2386
27c004C0PPWP 27 7/0.84 1.0 2.0 38.4 3462
37c004C0PPWP 37 7/0.84 1.0 2.0 42.4 4270
Follow: Control Cables, Armoured, PVC Insulated
3.0 Control Cables
39
Product Code No. of CoresStrand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 6 mm2
02c006C0PPWP 2 7/1.04 1.0 1.25 18.0 764
03c006C0PPWP 3 7/1.04 1.0 1.25 18.8 843
04c006C0PPWP 4 7/1.04 1.0 1.25 20.6 974
Conductor 10 mm2
02c010C0PPWP 2 7/1.36 1.0 1.25 20.1 922
03c010C0PPWP 3 7/1.36 1.0 1.25 21.0 1040
04c010C0PPWP 4 7/1.36 1.0 1.6 23.4 1344
Follow: Control Cables, Armoured, PVC Insulated
40 BICC CABLES
Control Cables, Armoured, XLPE insulated ApplicationControl cables are used as interconnecting cables for control devices and armoured cablesin environment where mechanical damage is expected to occur.
Construction
1. ConductorStranded Copper class 2
2. InsulationCross Linked Polyethylene (XLPE)
3. Armour Galvanized Round Steel Wire (GSWA)
4. SheathPolyvinyl Chloride (PVC)
3.0 Control Cables
41
Control Cables, Armoured, XLPE Insulated
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.0 mm2
02c001C0XPWP 2 7/0.43 0.7 0.9 12.6 359
03c001C0XPWP 3 7/0.43 0.7 0.9 13.0 369
04c001C0XPWP 4 7/0.43 0.7 0.9 13.7 406
07c001C0XPWP 7 7/0.43 0.7 1.25 16.5 573
12c001C0XPWP 12 7/0.43 0.7 1.25 19.6 775
19c001C0XPWP 19 7/0.43 0.7 1.6 22.5 1070
27c001C0XPWP 27 7/0.43 0.7 1.6 25.6 1330
37c001C0XPWP 37 7/0.43 0.7 1.6 28.0 1580
48c001C0XPWP 48 7/0.43 0.7 1.6 31.3 1905
Conductor 1.5 mm2
02c01.5C0XPWP 2 7/0.53 0.7 0.9 13.1 401
03c01.5C0XPWP 3 7/0.53 0.7 0.9 13.5 410
04c01.5C0XPWP 4 7/0.53 0.7 0.9 14.3 458
07c01.5C0XPWP 7 7/0.53 0.7 1.25 17.2 655
12c01.5C0XPWP 12 7/0.53 0.7 1.25 20.5 890
19c01.5C0XPWP 19 7/0.53 0.7 1.6 23.7 1248
27c01.5C0XPWP 27 7/0.53 0.7 1.6 27.0 1567
37c01.5C0XPWP 37 7/0.53 0.7 1.6 29.6 1895
48c01.5C0XPWP 48 7/0.53 0.7 2.0 34.2 2465
Conductor 2.0 mm2
02c002C0XPWP 2 7/0.60 0.7 0.9 13.6 422
03c002C0XPWP 3 7/0.60 0.7 0.9 14.1 441
04c002C0XPWP 4 7/0.60 0.7 0.9 14.9 568
07c002C0XPWP 7 7/0.60 0.7 1.25 18.0 715
12c002C0XPWP 12 7/0.60 0.7 1.6 22.3 1102
19c002C0XPWP 19 7/0.60 0.7 1.6 25.0 1416
27c002C0XPWP 27 7/0.60 0.7 1.6 28.8 1781
37c002C0XPWP 37 7/0.60 0.7 1.6 31.7 2164
48c002C0XPWP 48 7/0.60 0.7 2.0 36.3 3012
42 BICC CABLES
Product Code No. of CoresStrand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 2.5 mm2
02c02.5C0XPWP 2 7/0.67 0.7 0.9 13.9 446
03c02.5C0XPWP 3 7/0.67 0.7 0.9 14.4 469
04c02.5C0XPWP 4 7/0.67 0.7 0.9 15.2 608
07c02.5C0XPWP 7 7/0.67 0.7 1.25 18.3 780
12c02.5C0XPWP 12 7/0.67 0.7 1.6 22.8 1210
19c02.5C0XPWP 19 7/0.67 0.7 1.6 25.6 1560
27c02.5C0XPWP 27 7/0.67 0.7 1.6 29.6 1980
37c02.5C0XPWP 37 7/0.67 0.7 2.0 33.4 2665
48c02.5C0XPWP 48 7/0.67 0.7 2.0 37.5 3330
Conductor 3 mm2
02c003C0XPWP 2 7/0.74 0.7 0.9 14.3 468
03c003C0XPWP 3 7/0.74 0.7 0.9 14.9 573
04c003C0XPWP 4 7/0.74 0.7 1.25 16.5 644
07c003C0XPWP 7 7/0.74 0.7 1.25 19.0 835
12c003C0XPWP 12 7/0.74 0.7 1.6 23.8 1300
19c003C0XPWP 19 7/0.74 0.7 1.6 26.7 1690
27c003C0XPWP 27 7/0.74 0.7 1.6 31.1 2190
37c003C0XPWP 37 7/0.74 0.7 2.0 35.1 2935
Conductor 4 mm2
02c004C0XPWP 2 7/0.84 0.7 0.9 15.1 588
03c004C0XPWP 3 7/0.84 0.7 1.25 16.4 634
04c004C0XPWP 4 7/0.84 0.7 1.25 17.4 716
07c004C0XPWP 7 7/0.84 0.7 1.25 20.1 945
12c004C0XPWP 12 7/0.84 0.7 1.6 25.3 1480
19c004C0XPWP 19 7/0.84 0.7 1.6 28.8 1950
27c004C0XPWP 27 7/0.84 0.7 2.0 34.5 2770
37c004C0XPWP 37 7/0.84 0.7 2.0 38.0 3470
Follow: Control Cables, Armoured, XLPE Insulated
3.0 Control Cables
43
Product Code No. of CoresStrand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 6 mm2
02c006C0XPWP 2 7/1.04 0.7 1.25 16.8 676
03c006C0XPWP 3 7/1.04 0.7 1.25 17.5 732
04c006C0XPWP 4 7/1.04 0.7 1.25 18.7 844
Conductor 10 mm2
02c010C0XPWP 2 7/1.36 0.7 1.25 18.9 827
03c010C0XPWP 3 7/1.36 0.7 1.25 19.2 929
04c010C0XPWP 4 7/1.36 0.7 1.25 20.5 1095
Follow: Control Cables, Armoured, XLPE Insulated
44 BICC CABLES
Control Cables, Copper Tape Screened,PVC Insulated ApplicationThese cables are used for interconnecting of control devices and designed to be complete with copper tape screen applied helically after bedding.
Construction
1. ConductorStranded Copper class 2
2. InsulationPolyvinyl Chloride (PVC)
3. Screen Copper Tape Screen (CTS)
4. SheathPolyvinyl Chloride (PVC)
3.0 Control Cables
45
Control Cables, Copper Tape Screened, PVC Insulated
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.0 mm2
05c001C0PPCTP 5 7/0.43 0.8 12.7 345
07c001C0PPCTP 7 7/0.43 0.8 14.1 402
10c001C0PPCTP 10 7/0.43 0.8 16.9 521
12c001C0PPCTP 12 7/0.43 0.8 17.4 568
14c001C0PPCTP 14 7/0.43 0.8 18.1 622
16c001C0PPCTP 16 7/0.43 0.8 18.9 678
19c001C0PPCTP 19 7/0.43 0.8 19.8 753
24c001C0PPCTP 24 7/0.43 0.8 22.7 907
30c001C0PPCTP 30 7/0.43 0.8 23.8 1045
37c001C0PPCTP 37 7/0.43 0.8 25.5 1212
Conductor 1.5 mm2
05c01.5C0PPCTP 5 7/0.53 0.8 13.3 392
07c01.5C0PPCTP 7 7/0.53 0.8 14.8 463
10c01.5C0PPCTP 10 7/0.53 0.8 17.9 607
12c01.5C0PPCTP 12 7/0.53 0.8 18.4 669
14c01.5C0PPCTP 14 7/0.53 0.8 19.1 736
16c01.5C0PPCTP 16 7/0.53 0.8 20.0 805
19c01.5C0PPCTP 19 7/0.53 0.8 21.0 901
24c01.5C0PPCTP 24 7/0.53 0.8 24.0 1091
30c01.5C0PPCTP 30 7/0.53 0.8 25.3 1268
37c01.5C0PPCTP 37 7/0.53 0.8 27.1 1480
Conductor 2.0 mm2
05c002C0PPCTP 5 7/0.60 0.8 14.0 434
07c002C0PPCTP 7 7/0.60 0.8 15.6 517
10c002C0PPCTP 10 7/0.60 0.8 18.9 681
12c002C0PPCTP 12 7/0.60 0.8 19.4 755
14c002C0PPCTP 14 7/0.60 0.8 20.3 835
16c002C0PPCTP 16 7/0.60 0.8 21.3 917
19c002C0PPCTP 19 7/0.60 0.8 22.3 1030
24c002C0PPCTP 24 7/0.60 0.8 25.6 1253
30c002C0PPCTP 30 7/0.60 0.8 27.2 1465
37c002C0PPCTP 37 7/0.60 0.8 29.2 1737
46 BICC CABLES
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable (kg/km)
Conductor 2.5 mm2
05c02.5C0PPCTP 5 7/0.67 0.8 14.4 474
07c02.5C0PPCTP 7 7/0.67 0.8 15.9 572
10c02.5C0PPCTP 10 7/0.67 0.8 19.4 758
12c02.5C0PPCTP 12 7/0.67 0.8 20.0 844
14c02.5C0PPCTP 14 7/0.67 0.8 20.8 937
16c02.5C0PPCTP 16 7/0.67 0.8 21.9 1032
19c02.5C0PPCTP 19 7/0.67 0.8 22.9 1164
24c02.5C0PPCTP 24 7/0.67 0.8 26.4 1419
30c02.5C0PPCTP 30 7/0.67 0.8 28.0 1683
37c02.5C0PPCTP 37 7/0.67 0.8 30.1 1981
Conductor 3.0 mm2
05c003C0PPCTP 5 7/0.74 0.8 15.0 523
07c003C0PPCTP 7 7/0.74 0.8 16.6 634
10c003C0PPCTP 10 7/0.74 0.8 20.3 844
12c003C0PPCTP 12 7/0.74 0.8 20.9 942
14c003C0PPCTP 14 7/0.74 0.8 21.8 1045
16c003C0PPCTP 16 7/0.74 0.8 22.9 1154
19c003C0PPCTP 19 7/0.74 0.8 24.0 1303
24c003C0PPCTP 24 7/0.74 0.8 27.9 1609
30c003C0PPCTP 30 7/0.74 0.8 29.4 1893
37c003C0PPCTP 37 7/0.74 0.8 32.2 2299
Conductor 4.0 mm2
05c004C0PPCTP 5 7/0.84 1.0 17.1 633
07c004C0PPCTP 7 7/0.84 1.0 18.9 778
10c004C0PPCTP 10 7/0.84 1.0 23.4 1046
12c004C0PPCTP 12 7/0.84 1.0 24.1 1176
14c004C0PPCTP 14 7/0.84 1.0 25.3 1315
16c004C0PPCTP 16 7/0.84 1.0 26.6 1457
19c004C0PPCTP 19 7/0.84 1.0 28.1 1673
Follow: Control Cables, Copper Tape Screened, PVC Insulated
3.0 Control Cables
47
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable (kg/km)
Conductor 4.0 mm2
24c004C0PPCTP 24 7/0.84 1.0 33.2 2123
30c004C0PPCTP 30 7/0.84 1.0 35.2 2537
37c004C0PPCTP 37 7/0.84 1.0 38.1 3017
Conductor 6 mm2
02c006C0PPCTP 2 7/1.04 1.0 15.0 490
03c006C0PPCTP 3 7/1.04 1.0 15.8 552
04c006C0PPCTP 4 7/1.04 1.0 17.1 660
05c006C0PPCTP 5 7/1.04 1.0 18.5 769
06c006C0PPCTP 6 7/1.04 1.0 20.5 881
07c006C0PPCTP 7 7/1.04 1.0 20.5 960
Conductor 10 mm2
02c010C0PPCTP 2 7/1.36 1.0 17.1 515
03c010C0PPCTP 3 7/1.36 1.0 18.0 645
04c010C0PPCTP 4 7/1.36 1.0 19.5 785
05c010C0PPCTP 5 7/1.36 1.0 21.1 945
06c010C0PP CTP 6 7/1.36 1.0 22.8 1065
07c010C0PPCTP 7 7/1.36 1.0 22.8 1178
Follow: Control Cables, Copper Tape Screened, PVC Insulated
48 BICC CABLES
Control Cables, Copper Tape Screened,XLPE Insulated ApplicationThese cables are used for interconnecting of control devices and designed to be complete with copper tape screen applied helically.
Construction
1. ConductorStranded Copper class 2
2. InsulationCross Linked Polyethylene (XLPE)
3. Screen Copper Tape Screen (CTS)
4. SheathPolyvinyl Chloride (PVC)
3.0 Control Cables
49
Control Cables, Copper Tape Screened, XLPE Insulated
Product Code No.of Cores
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.0 mm2
05c001C0XPCTP 5 7/0.43 0.7 12.2 306
07c001C0XPCTP 7 7/0.43 0.7 13.5 352
10c001C0XPCTP 10 7/0.43 0.7 16.1 450
12c001C0XPCTP 12 7/0.43 0.7 16.6 480
14c001C0XPCTP 14 7/0.43 0.7 17.2 530
16c001C0XPCTP 16 7/0.43 0.7 18.0 570
19c001C0XPCTP 19 7/0.43 0.7 18.8 630
24c001C0XPCTP 24 7/0.43 0.7 21.5 755
30c001C0XPCTP 30 7/0.43 0.7 22.6 860
37c001C0XPCTP 37 7/0.43 0.7 24.1 990
Conductor 1.5 mm2
05c01.5C0XPCTP 5 7/0.53 0.7 12.8 350
07c01.5C0XPCTP 7 7/0.53 0.7 14.2 410
10c01.5C0XPCTP 10 7/0.53 0.7 17.1 530
12c01.5C0XPCTP 12 7/0.53 0.7 17.5 580
14c01.5C0XPCTP 14 7/0.53 0.7 18.2 630
16c01.5C0XPCTP 16 7/0.53 0.7 19.1 689
19c01.5C0XPCTP 19 7/0.53 0.7 20.0 765
24c01.5C0XPCTP 24 7/0.53 0.7 22.8 920
30c01.5C0XPCTP 30 7/0.53 0.7 24.0 1060
37c01.5C0XPCTP 37 7/0.53 0.7 25.7 1230
Conductor 2.0 mm2
05c002C0XPCTP 5 7/0.60 0.7 13.5 390
07c002C0XPCTP 7 7/0.60 0.7 15.0 460
10c002C0XPCTP 10 7/0.60 0.7 18.1 600
12c002C0XPCTP 12 7/0.60 0.7 18.6 660
14c002C0XPCTP 14 7/0.60 0.7 19.4 730
16c002C0XPCTP 16 7/0.60 0.7 20.3 800
19c002C0XPCTP 19 7/0.60 0.7 21.3 890
24c002C0XPCTP 24 7/0.60 0.7 24.4 1080
30c002C0XPCTP 30 7/0.60 0.7 25.7 1250
37c002C0XPCTP 37 7/0.60 0.7 27.8 1450
50 BICC CABLES
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable (kg/km)
Conductor 2.5 mm2
05c02.5C0XPCTP 5 7/0.67 0.7 13.9 430
07c02.5C0XPCTP 7 7/0.67 0.7 15.3 510
10c02.5C0XPCTP 10 7/0.67 0.7 18.6 670
12c02.5C0XPCTP 12 7/0.67 0.7 19.1 750
14c02.5C0XPCTP 14 7/0.67 0.7 20.0 820
16c02.5C0XPCTP 16 7/0.67 0.7 20.9 900
19c02.5C0XPCTP 19 7/0.67 0.7 21.9 1010
24c02.5C0XPCTP 24 7/0.67 0.7 25.2 1230
30c02.5C0XPCTP 30 7/0.67 0.7 26.5 1440
37c02.5C0XPCTP 37 7/0.67 0.7 29.1 1700
Conductor 3.0 mm2
05c003C0XPCTP 5 7/0.74 0.7 14.5 460
07c003C0XPCTP 7 7/0.74 0.7 16.0 560
10c003C0XPCTP 10 7/0.74 0.7 19.5 740
12c003C0XPCTP 12 7/0.74 0.7 20.1 820
14c003C0XPCTP 14 7/0.74 0.7 20.9 910
16c003C0XPCTP 16 7/0.74 0.7 22.0 1000
19c003C0XPCTP 19 7/0.74 0.7 23.0 1125
24c003C0XPCTP 24 7/0.74 0.7 26.5 1370
30c003C0XPCTP 30 7/0.74 0.7 28.1 1625
37c003C0XPCTP 37 7/0.74 0.7 30.8 1910
Conductor 4.0 mm2
05c004C0XPCTP 5 7/0.84 0.7 15.5 530
07c004C0XPCTP 7 7/0.84 0.7 17.1 640
10c004C0XPCTP 10 7/0.84 0.7 21.0 860
12c004C0XPCTP 12 7/0.84 0.7 21.6 960
14c004C0XPCTP 14 7/0.84 0.7 22.6 1060
16c004C0XPCTP 16 7/0.84 0.7 23.7 1175
Follow: Control Cables, Copper Tape Screened, XLPE Insulated
3.0 Control Cables
51
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable (kg/km)
Conductor 4.0 mm2
19c004C0XPCTP 19 7/0.84 0.7 24.9 1330
24c004C0XPCTP 24 7/0.84 0.7 29.4 1645
30c004C0XPCTP 30 7/0.84 0.7 31.2 1940
37c004C0XPCTP 37 7/0.84 0.7 33.7 2350
Conductor 6 mm2
02c006C0XPCTP 2 7/1.04 0.7 13.8 430
03c006C0XPCTP 3 7/1.04 0.7 15.0 480
04c006C0XPCTP 4 7/1.04 0.7 15.7 570
05c006C0XPCTP 5 7/1.04 0.7 16.9 660
06c006C0XPCTP 6 7/1.04 0.7 18.7 750
07c006C0XPCTP 7 7/1.04 0.7 18.7 810
Conductor 10 mm2
02c010C0XPCTP 2 7/1.36 0.7 15.9 470
03c010C0XPCTP 3 7/1.36 0.7 16.7 550
04c010C0XPCTP 4 7/1.36 0.7 18.0 650
05c010C0XPCTP 5 7/1.36 0.7 19.5 800
06c010C0XPCTP 6 7/1.36 0.7 21.0 930
07c010C0XPCTP 7 7/1.36 0.7 21.0 1050
Follow: Control Cables, Copper Tape Screened, XLPE Insulated
52 BICC CABLES
4.0 Instrument Cables
53
4.0 Instrument Cables
54 BICC CABLES
4.0 Instrument Cables
Application
Construction
Specification Standards
These cables are designed to connect electrical instrument circuits and provide communication services working as signal carrier used in and around process plants ( e.g. petrochemical industry etc.).
1. ConductorCopper (or Tinned Copper) in different flexibility degrees:- Solid Copper: Class 1- Stranded Copper: Class 2- Flexible Copper: Class 5
2. Insulation- Cross Linked Polyethylene (XLPE): Maximum conductor temperature is 90°C.- Polyvinyl Chloride (PVC) 70°C.- Polyvinyl Chloride (PVC) 105°C (for fire alarm cables).- Low Smoke Zero Halogen (LSOH) 90°C.
3. Shielding- Individual Shield: Shielding for each pair /triple in the multi pair/triple cables using Up to 50 μm Aluminium/ PET tape over tinned copper drain wires with 0.5 mm²- Overall Shield: Overall shield for all pairs / triples or cores in cable using Up to 50 μm Aluminium/ PET tape over tinned copper drain wires with 0.5 mm²
4. Bedding - Polyvinyl Chloride (PVC) - Low Smoke Zero Halogen (LSOH) (For applications where flame spread, minimal smoke and toxic gases emission are critical)
5. Armour / Screen- Armour: Galvanized Steel Wire Armour (GSWA) One layer of round wires is applied helically over the bedding
6. Outer Sheath- Polyvinyl Chloride (PVC) - Low Smoke Zero Halogen (LSOH)
Standard specification applied to cable:
Standard specification applied to conductor:
Spread of Flame
BS EN 50288-7 IEC 60228
Flame retardant as per IEC 60332-1
55
Sizes
Core Identification
Options Available
Rated Voltage
This publication covers the following range
- Conductor area: From 0.5 mm2 up to 2.5 mm2
- No. of pairs: From one till 20 pairs - No. of triples: From one till 15 triples All variation from no. of pairs, triples and quads too are available upon request.
Sizes :All sizes are available upon request
Material :Where necessary, special features can be incorporated into the cable enabling it to have:- Improved fire performance- Low smoke and fume (Halogen free )- Termite resistance- Resistance to attack from oils, solvents or corrosive chemicals
For environment where emissions of smoke and toxic gases are critical , insulation , bedding and outer sheath material can be : Low Smoke Zero Halogen which has abbreviations of LS0H , LSOH & LSZH( the 3 abbreviations are the same material) with no halogen content and controlled emission of smokeAlso, it is the same as Low Smoke Halogen Free (LSHF).
Note: Values in the following tables are approximate and subject to manufacturing tolerance.
500 V
- Pair: White & Black - Triple: White, Black & Red - Multi Cores more than five cores: Black with white numbers
Other special colors are available upon request. For multi pair and traid colored cores are identified by numbers on the white core only and can be on each coe (upon request)
56 BICC CABLES
Multi Pair/Triple & Multi Core, Non Armoured, Overall Shielding ApplicationMulti pair/triple & multi core instrument cables are used as signal carrier for connecting electrical instrument circuits.
Construction
1. ConductorStranded Copper class 2
2. InsulationPolyvinyl Chloride (PVC)Alternative: Cross Linked Polyethylene (XLPE )
3. Shielding Overall Shielding 4. SheathPolyvinyl Chloride (PVC)
4.0 Instrument Cables
57
Multi Pair Instrument Cables, Non Armoured, Overall Shielded
Product Code No. of Pairs
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 0.5 mm2
01p00.5C0P0S000P 1 7/0.30 0.6 6.2 66
02p00.5C0POS000P 2 7/0.30 0.6 10.8 98
04p00.5C0POS000P 4 7/0.30 0.6 12.8 199
06p00.5C0POS000P 6 7/0.30 0.6 13.6 264
10p00.5C0POS000P 10 7/0.30 0.6 17.8 379
15p00.5C0POS000P 15 7/0.30 0.6 21.0 539
20p00.5C0POS000P 20 7/0.30 0.6 24.0 675
Conductor 0.75 mm2
01p0.75C0POS000P 1 7/0.37 0.6 7.0 74
02p0.75C0POS000P 2 7/0.37 0.6 11.9 109
04p0.75C0POS000P 4 7/0.37 0.6 14.0 231
06p0.75C0POS000P 6 7/0.37 0.6 14.7 303
10p0.75C0POS000P 10 7/0.37 0.6 19.4 463
15p0.75C0POS000P 15 7/0.37 0.6 22.6 646
20p0.75C0POS000P 20 7/0.37 0.6 25.9 845
Conductor 1.0 mm2
01p1.00C0POS000P 1 7/0.43 0.6 7.1 79
02p1.00C0POS000P 2 7/0.43 0.6 13.0 152
04p1.00C0POS000P 4 7/0.43 0.6 15.4 282
06p1.00C0POS000P 6 7/0.43 0.6 16.4 383
10p1.00C0POS000P 10 7/0.43 0.6 21.7 589
15p1.00C0POS000P 15 7/0.43 0.6 25.7 803
20p1.00C0POS000P 20 7/0.43 0.6 29.3 1047
58 BICC CABLES
Product Code No. of Pairs
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
01p1.50C0POS000P 1 7/0.53 0.6 7.6 99
02p1.50C0POS000P 2 7/0.53 0.6 14.0 159
04p1.50C0POS000P 4 7/0.53 0.6 16.5 328
06p1.50C0POS000P 6 7/0.53 0.6 17.7 445
10p1.50C0POS000P 10 7/0.53 0.6 23.9 665
15p1.50C0POS000P 15 7/0.53 0.6 27.8 975
20p1.50C0POS000P 20 7/0.53 0.6 31.7 1276
Conductor 2.0 mm2
01p2.00C0POS000P 1 7/0.60 0.6 8.0 124
02p2.00C0POS000P 2 7/0.60 0.6 15.2 208
04p2.00C0POS000P 4 7/0.60 0.6 17.8 417
06p2.00C0POS000P 6 7/0.60 0.6 19.5 588
10p2.00C0POS000P 10 7/0.60 0.6 26.0 929
15p2.00C0POS000P 15 7/0.60 0.6 30.7 1334
20p2.00C0POS000P 20 7/0.60 0.6 35.1 1700
Conductor 2.5 mm2
01p2.50C0POS000P 1 7/0.67 0.6 8.4 131
02p2.50C0POS000P 2 7/0.67 0.6 15.7 221
04p2.50C0POS000P 4 7/0.67 0.6 18.4 443
06p2.50C0POS000P 6 7/0.67 0.6 20.3 627
10p2.50C0POS000P 10 7/0.67 0.6 27.0 994
15p2.50C0POS000P 15 7/0.67 0.6 31.9 1433
20p2.50C0POS000P 20 7/0.67 0.6 36.5 1892
Follow: Multi Pair Instrument Cables, Non Armoured, Overall Shielded
4.0 Instrument Cables
59
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 0.5 mm2
01t00.5C0POS000P 1 7/0.30 0.6 6.5 76
02t00.5C0POS000P 2 7/0.30 0.6 11.7 137
04t00.5C0POS000P 4 7/0.30 0.6 11.9 253
06t00.5C0POS000P 6 7/0.30 0.6 14.6 331
10t00.5C0POS000P 10 7/0.30 0.6 19.2 500
12t00.5C0POS000P 12 7/0.30 0.6 20.0 579
15t00.5C0POS000P 15 7/0.30 0.6 22.4 726
Conductor 0.75 mm2
01t0.75C0POS000P 1 7/0.37 0.6 6.8 88
02t0.75C0POS000P 2 7/0.37 0.6 12.5 159
04t0.75C0POS000P 4 7/0.37 0.6 12.9 303
06t0.75C0POS000P 6 7/0.37 0.6 15.7 394
10t0.75C0POS000P 10 7/0.37 0.6 20.8 611
12t0.75C0POS000P 12 7/0.37 0.6 21.6 738
15t0.75C0POS000P 15 7/0.37 0.6 24.0 890
Conductor 1.0 mm2
01t1.00C0POS000P 1 7/0.43 0.6 7.5 103
02t1.00C0POS000P 2 7/0.43 0.6 14.0 203
04t1.00C0POS000P 4 7/0.43 0.6 14.5 356
06t1.00C0POS000P 6 7/0.43 0.6 17.5 501
10t1.00C0POS000P 10 7/0.43 0.6 23.6 762
12t1.00C0POS000P 12 7/0.43 0.6 24.5 887
15t1.00C0POS000P 15 7/0.43 0.6 27.5 1074
Multi Triple Instrument Cables, Non Armoured, Overall Shielded
60 BICC CABLES
Follow: Multi Triple Instrument Cables, Non Armoured, Overall Shielded
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
01t1.50C0POS000P 1 7/0.53 0.6 8.0 127
02t1.50C0POS000P 2 7/0.53 0.6 14.5 249
04t1.50C0POS000P 4 7/0.53 0.6 15.6 431
06t1.50C0POS000P 6 7/0.53 0.6 19.2 612
10t1.50C0POS000P 10 7/0.53 0.6 25.6 940
12t1.50C0POS000P 12 7/0.53 0.6 26.6 1099
15t1.50C0POS000P 15 7/0.53 0.6 30.0 1372
Conductor 2.0 mm2
01t2.00C0POS000P 1 7/0.60 0.6 8.6 159
02t2.00C0POS000P 2 7/0.60 0.6 16.0 312
04t2.00C0POS000P 4 7/0.60 0.6 16.9 551
06t2.00C0POS000P 6 7/0.60 0.6 20.9 798
10t2.00C0POS000P 10 7/0.60 0.6 27.9 1270
12t2.00C0POS000P 12 7/0.60 0.6 29.3 1464
15t2.00C0POS000P 15 7/0.60 0.6 32.9 1843
Conductor 2.5 mm2
01t2.50C0POS000P 1 7/0.67 0.6 9.0 162
02t2.50C0POS000P 2 7/0.67 0.6 16.7 350
04t2.50C0POS000P 4 7/0.67 0.6 18.5 578
06t2.50C0POS000P 6 7/0.67 0.6 22.0 830
10t2.50C0POS000P 10 7/0.67 0.6 29.4 1334
12t2.50C0POS000P 12 7/0.67 0.6 30.5 1548
15t2.50C0POS000P 15 7/0.67 0.6 34.8 1933
4.0 Instrument Cables
61
Multi Core Instrument Cables, Non Armoured, Overall Shielded
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 0.5 mm2
02c00.5C0POS000P 2 7/0.30 0.6 6.2 65
03c00.5C0POS000P 3 7/0.30 0.6 6.5 76
04c00.5C0POS000P 4 7/0.30 0.6 7.0 91
05c00.5C0POS000P 5 7/0.30 0.6 7.6 107
07c00.5C0POS000P 7 7/0.30 0.6 8.2 140
12c00.5C0POS000P 12 7/0.30 0.6 10.5 225
19c00.5C0POS000P 19 7/0.30 0.6 12.8 324
24c00.5C0POS000P 24 7/0.30 0.6 15.0 398
Conductor 0.75 mm2
02c0.75C0POS000P 2 7/0.37 0.6 6.6 74
03c0.75C0POS000P 3 7/0.37 0.6 6.9 89
04c0.75C0POS000P 4 7/0.37 0.6 7.5 106
05c0.75C0POS000P 5 7/0.37 0.6 8.1 131
07c0.75C0POS000P 7 7/0.37 0.6 8.9 165
12c0.75C0POS000P 12 7/0.37 0.6 11.9 268
19c0.75C0POS000P 19 7/0.37 0.6 13.9 390
24c0.75C0POS000P 24 7/0.37 0.6 16.1 482
Conductor 1.0 mm2
02c1.00C0POS000P 2 7/0.43 0.6 7.1 82
03c1.00C0POS000P 3 7/0.43 0.6 7.5 100
04c1.00C0POS000P 4 7/0.43 0.6 8.2 122
05c1.00C0POS000P 5 7/0.43 0.6 9.0 155
07c1.00C0POS000P 7 7/0.43 0.6 9.8 195
12c1.00C0POS000P 12 7/0.43 0.6 13.0 319
19c1.00C0POS000P 19 7/0.43 0.6 15.3 458
24c1.00C0POS000P 24 7/0.43 0.6 17.8 578
62 BICC CABLES
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable (kg/km)
Conductor 1.5 mm2
02c1.50C0POS000P 2 7/0.53 0.6 7.6 98
03c1.50C0POS000P 3 7/0.53 0.6 8.0 132
04c1.50C0POS000P 4 7/0.53 0.6 8.9 161
05c1.50C0POS000P 5 7/0.53 0.6 9.7 191
07c1.50C0POS000P 7 7/0.53 0.6 10.5 260
12c1.50C0POS000P 12 7/0.53 0.6 14.2 417
19c1.50C0POS000P 19 7/0.53 0.6 16.5 602
24c1.50C0POS000P 24 7/0.53 0.6 19.3 761
Conductor 2.0 mm2
02c2.00C0POS000P 2 7/0.60 0.6 8.1 124
03c2.00C0POS000P 3 7/0.60 0.6 8.6 161
04c2.00C0POS000P 4 7/0.60 0.6 9.5 199
05c2.00C0POS000P 5 7/0.60 0.6 10.4 252
07c2.00C0POS000P 7 7/0.60 0.6 11.7 322
12c2.00C0POS000P 12 7/0.60 0.6 15.3 512
19c2.00C0POS000P 19 7/0.60 0.6 17.8 763
24c2.00C0POS000P 24 7/0.60 0.6 20.9 947
Conductor 2.5 mm2
02c2.50C0POS000P 2 7/0.67 0.6 8.4 136
03c2.50C0POS000P 3 7/0.67 0.6 9.1 171
04c2.50C0POS000P 4 7/0.67 0.6 9.9 211
05c2.50C0POS000P 5 7/0.67 0.6 10.7 268
07c2.50C0POS000P 7 7/0.67 0.6 12.0 344
12c2.50C0POS000P 12 7/0.67 0.6 15.8 550
19c2.50C0POS000P 19 7/0.67 0.6 18.6 824
24c2.50C0POS000P 24 7/0.67 0.6 21.7 1053
Follow: Multi Core Instrument Cables, Non Armoured, Overall Shielded
4.0 Instrument Cables
63
The highest purity of copper
64 BICC CABLES
Multi Pair/Triple, Non Armoured,Individual & Overall ShieldingApplicationMulti pair/triple instrument cables are used as signal carrier for connecting electrical instrument circuits.
Construction
1. ConductorStranded Copper class 2
2. InsulationPolyvinyl Chloride (PVC)Alternative: Cross Linked Polyethylene (XLPE )
3. Shielding Individual & Overall Shielding 4. SheathPolyvinyl Chloride (PVC)
4.0 Instrument Cables
65
Product Code No. of Pairs
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 0.5 mm2
02p00.5C0PISOS00P 2 7/0.30 0.6 12.0 164
04p00.5C0PISOS00P 4 7/0.30 0.6 13.7 247
06p00.5C0PISOS00P 6 7/0.30 0.6 14.2 327
10p00.5C0PISOS00P 10 7/0.30 0.6 18.8 506
15p00.5C0PISOS00P 15 7/0.30 0.6 21.9 723
20p00.5C0PISOS00P 20 7/0.30 0.6 25.0 910
Conductor 0.75 mm2
02p0.75C0PISOS00P 2 7/0.37 0.6 12.3 187
04p0.75C0PISOS00P 4 7/0.37 0.6 14.5 294
06p0.75C0PISOS00P 6 7/0.37 0.6 15.3 397
10p0.75C0PISOS00P 10 7/0.37 0.6 20.2 589
15p0.75C0PISOS00P 15 7/0.37 0.6 24.0 845
20p0.75C0PISOS00P 20 7/0.37 0.6 27.0 1104
Conductor 1.0 mm2
02p1.00C0PISOS00P 2 7/0.43 0.6 13.6 205
04p1.00C0PISOS00P 4 7/0.43 0.6 15.8 327
06p1.00C0PISOS00P 6 7/0.43 0.6 17.0 461
10p1.00C0PISOS00P 10 7/0.43 0.6 22.5 731
15p1.00C0PISOS00P 15 7/0.43 0.6 26.6 1002
20p1.00C0PISOS00P 20 7/0.43 0.6 30.4 1310
Conductor 1.5 mm2
02p1.50C0PISOS00P 2 7/0.53 0.6 14.6 253
04p1.50C0PISOS00P 4 7/0.53 0.6 17.0 394
06p1.50C0PISOS00P 6 7/0.53 0.6 18.5 558
10p1.50C0PISOS00P 10 7/0.53 0.6 24.7 853
15p1.50C0PISOS00P 15 7/0.53 0.6 29.2 1222
20p1.50C0PISOS00P 20 7/0.53 0.6 32.8 1616
Conductor 2.0 mm2
02p2.00C0PISOS00P 2 7/0.60 0.6 15.6 312
04p2.00C0PISOS00P 4 7/0.60 0.6 18.5 487
06p2.00C0PISOS00P 6 7/0.60 0.6 20.1 624
10p2.00C0PISOS00P 10 7/0.60 0.6 26.8 1013
15p2.00C0PISOS00P 15 7/0.60 0.6 32.0 1538
20p2.00C0PISOS00P 20 7/0.60 0.6 36.0 1986
Multi Pair Instrument Cables, Non Armoured,Individual & Overall Shielded
66 BICC CABLES
Multi Triple Instrument Cables, Non Armoured,Individual & Overall Shielded
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 0.5 mm2
02t00.5C0PISOS00P 2 7/0.30 0.6 12.2 184
04t00.5C0PISOS00P 4 7/0.30 0.6 12.4 283
06t00.5C0PISOS00P 6 7/0.30 0.6 15.0 380
10t00.5C0PISOS00P 10 7/0.30 0.6 20.1 620
12t00.5C0PISOS00P 12 7/0.30 0.6 20.8 707
15t00.5C0PISOS00P 15 7/0.30 0.6 23.8 852
Conductor 0.75 mm2
02t0.75C0PISOS00P 2 7/0.37 0.6 13.0 224
04t0.75C0PISOS00P 4 7/0.37 0.6 13.1 347
06t0.75C0PISOS00P 6 7/0.37 0.6 16.3 491
10t0.75C0PISOS00P 10 7/0.37 0.6 21.6 749
12t0.75C0PISOS00P 12 7/0.37 0.6 22.5 892
15t0.75C0PISOS00P 15 7/0.37 0.6 25.6 1073
Product Code No. of Pairs
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 2.5 mm2
02p2.50C0PISOS00P 2 7/0.67 0.6 16.0 325
04p2.50C0PISOS00P 4 7/0.67 0.6 19.0 526
06p2.50C0PISOS00P 6 7/0.67 0.6 20.9 736
10p2.50C0PISOS00P 10 7/0.67 0.6 27.8 1221
15p2.50C0PISOS00P 15 7/0.67 0.6 32.8 1683
20p2.50C0PISOS00P 20 7/0.67 0.6 37.6 2229
4.0 Instrument Cables
Follow: Multi Pair Instrument Cables, Non Armoured,Individual & Overall Shielded
67
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.0 mm2
02t1.00C0PISOS00P 2 7/0.43 0.6 14.4 240
04t1.00C0PISOS00P 4 7/0.43 0.6 14.8 391
06t1.00C0PISOS00P 6 7/0.43 0.6 18.0 556
10t1.00C0PISOS00P 10 7/0.43 0.6 24.5 888
12t1.00C0PISOS00P 12 7/0.43 0.6 25.4 1016
15t1.00C0PISOS00P 15 7/0.43 0.6 28.9 1271
Conductor 1.5 mm2
02t1.50C0PISOS00P 2 7/0.53 0.6 15.4 296
04t1.50C0PISOS00P 4 7/0.53 0.6 16.0 489
06t1.50C0PISOS00P 6 7/0.53 0.6 19.8 712
10t1.50C0PISOS00P 10 7/0.53 0.6 26.4 1090
12t1.50C0PISOS00P 12 7/0.53 0.6 27.4 1300
15t1.50C0PISOS00P 15 7/0.53 0.6 31.2 1584
Conductor 2.0 mm2
02t2.00C0PISOS00P 2 7/0.60 0.6 16.5 370
04t2.00C0PISOS00P 4 7/0.60 0.6 17.4 610
06t2.00C0PISOS00P 6 7/0.60 0.6 21.5 781
10t2.00C0PISOS00P 10 7/0.60 0.6 29.0 1304
12t2.00C0PISOS00P 12 7/0.60 0.6 30.2 1576
15t2.00C0PISOS00P 15 7/0.60 0.6 33.8 1933
Conductor 2.5 mm2
02t2.50C0PISOS00P 2 7/0.67 0.6 17.0 389
04t2.50C0PISOS00P 4 7/0.67 0.6 18.0 648
06t2.50C0PISOS00P 6 7/0.67 0.6 22.4 916
10t2.50C0PISOS00P 10 7/0.67 0.6 30.2 1523
12t2.50C0PISOS00P 12 7/0.67 0.6 31.3 1741
15t2.50C0PISOS00P 15 7/0.67 0.6 35.8 2127
Follow: Multi Triple Instrument Cables, Non Armoured,Individual & Overall Shielded
68 BICC CABLES
Multi Pair/Triple & Multi Core, Armoured,Overall ShieldingApplicationMulti pair/triple & multi core instrument cables are used as signal carrier for connecting electrical instrument circuits.
Construction
1. ConductorStranded Copper class 2
2. InsulationPolyvinyl Chloride (PVC)Alternative: Cross Linked Polyethylene (XLPE )
3. Shielding Overall Shielding
4. ArmourGalvanized Round Steel Wire (GSWA) 5. SheathPolyvinyl Chloride (PVC)
4.0 Instrument Cables
69
Product Code No. of Pairs
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 0.5 mm2
01p00.5C0POS0PWP 1 7/0.30 0.6 0.9 11.1 277
02p00.5C0POS0PWP 2 7/0.30 0.6 1.25 16.8 334
04p00.5C0POS0PWP 4 7/0.30 0.6 1.25 19.0 669
06p00.5C0POS0PWP 6 7/0.30 0.6 1.25 19.8 804
10p00.5C0POS0PWP 10 7/0.30 0.6 1.6 24.9 1189
15p00.5C0POS0PWP 15 7/0.30 0.6 1.6 28.2 1507
20p00.5C0POS0PWP 20 7/0.30 0.6 1.6 31.3 1755
Conductor 0.75 mm2
01p0.75C0POS0PWP 1 7/0.37 0.6 0.9 11.5 296
02p0.75C0POS0PWP 2 7/0.37 0.6 1.25 17.9 365
04p0.75C0POS0PWP 4 7/0.37 0.6 1.25 20.2 730
06p0.75C0POS0PWP 6 7/0.37 0.6 1.25 21.0 1011
10p0.75C0POS0PWP 10 7/0.37 0.6 1.6 26.5 1338
15p0.75C0POS0PWP 15 7/0.37 0.6 1.6 29.9 1701
20p0.75C0POS0PWP 20 7/0.37 0.6 2.0 34.2 2266
Conductor 1.0 mm2
01p1.00C0POS0PWP 1 7/0.43 0.6 0.9 12.0 297
02p1.00C0POS0PWP 2 7/0.43 0.6 1.25 19.0 511
04p1.00C0POS0PWP 4 7/0.43 0.6 1.6 22.3 850
06p1.00C0POS0PWP 6 7/0.43 0.6 1.6 23.5 1204
10p1.00C0POS0PWP 10 7/0.43 0.6 1.6 29.0 1664
15p1.00C0POS0PWP 15 7/0.43 0.6 2.0 34.0 2284
20p1.00C0POS0PWP 20 7/0.43 0.6 2.0 37.8 2735
Conductor 1.5 mm2
01p1.50C0POS0PWP 1 7/0.53 0.6 0.9 12.5 354
02p1.50C0POS0PWP 2 7/0.53 0.6 1.25 20.4 532
04p1.50C0POS0PWP 4 7/0.53 0.6 1.6 23.6 1036
06p1.50C0POS0PWP 6 7/0.53 0.6 1.6 24.8 1271
10p1.50C0POS0PWP 10 7/0.53 0.6 1.6 31.2 1689
15p1.50C0POS0PWP 15 7/0.53 0.6 2.0 36.3 2472
20p1.50C0POS0PWP 20 7/0.53 0.6 2.0 40.4 2969
Multi Pair Instrument Cables, Armoured, Overall Shielded
70 BICC CABLES
Product Code No. of Pairs
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 2.0 mm2
01p2.00C0POS0PWP 1 7/0.60 0.6 0.9 13.2 401
02p2.00C0POS0PWP 2 7/0.60 0.6 1.6 22.1 613
04p2.00C0POS0PWP 4 7/0.60 0.6 1.6 24.9 1195
06p2.00C0POS0PWP 6 7/0.60 0.6 1.6 26.6 1508
10p2.00C0POS0PWP 10 7/0.60 0.6 2.0 34.3 2302
15p2.00C0POS0PWP 15 7/0.60 0.6 2.0 39.2 3043
20p2.00C0POS0PWP 20 7/0.60 0.6 2.5 44.5 3645
Conductor 2.5 mm2
01p2.50C0POS0PWP 1 7/0.67 0.6 0.9 13.5 410
02p2.50C0POS0PWP 2 7/0.67 0.6 1.6 22.6 629
04p2.50C0POS0PWP 4 7/0.67 0.6 1.6 25.5 1251
06p2.50C0POS0PWP 6 7/0.67 0.6 1.6 27.4 1564
10p2.50C0POS0PWP 10 7/0.67 0.6 2.0 35.3 2408
15p2.50C0POS0PWP 15 7/0.67 0.6 2.0 40.4 3166
20p2.50C0POS0PWP 20 7/0.67 0.6 2.5 45.9 4231
Follow: Multi Pair Instrument Cables, Armoured, Overall Shielded
4.0 Instrument Cables
71
Multi Triple Instrument Cables, Armoured, Overall Shielded
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter
(mm)
Overall Cable Diameter
(mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 0.5 mm2
01t00.5C0POS0PWP 1 7/0.30 0.6 0.9 11.4 297
02t00.5C0POS0PWP 2 7/0.30 0.6 1.25 17.8 521
04t00.5C0POS0PWP 4 7/0.30 0.6 1.25 19.0 771
06t00.5C0POS0PWP 6 7/0.30 0.6 1.25 20.8 1046
10t00.5C0POS0PWP 10 7/0.30 0.6 1.6 26.4 1406
12t00.5C0POS0PWP 12 7/0.30 0.6 1.6 27.3 1548
15t00.5C0POS0PWP 15 7/0.30 0.6 1.6 29.7 1805
Conductor 0.75 mm2
01t0.75C0POS0PWP 1 7/0.37 0.6 0.9 11.8 320
02t0.75C0POS0PWP 2 7/0.37 0.6 1.25 18.6 585
04t0.75C0POS0PWP 4 7/0.37 0.6 1.25 19.7 981
06t0.75C0POS0PWP 6 7/0.37 0.6 1.6 22.6 1185
10t0.75C0POS0PWP 10 7/0.37 0.6 1.6 28.1 1597
12t0.75C0POS0PWP 12 7/0.37 0.6 1.6 28.9 1811
15t0.75C0POS0PWP 15 7/0.37 0.6 1.6 32.3 2311
Conductor 1.0 mm2
01t1.00C0POS0PWP 1 7/0.43 0.6 0.9 12.4 345
02t1.00C0POS0PWP 2 7/0.43 0.6 1.25 20.2 653
04t1.00C0POS0PWP 4 7/0.43 0.6 1.25 21.5 1056
06t1.00C0POS0PWP 6 7/0.43 0.6 1.6 24.6 1327
10t1.00C0POS0PWP 10 7/0.43 0.6 1.6 31.0 1803
12t1.00C0POS0PWP 12 7/0.43 0.6 1.6 32.0 2234
15t1.00C0POS0PWP 15 7/0.43 0.6 2.0 36.0 2554
72 BICC CABLES
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness (mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
01t1.50C0POS0PWP 1 7/0.53 0.6 0.9 13.1 400
02t1.50C0POS0PWP 2 7/0.53 0.6 1.25 21.2 754
04t1.50C0POS0PWP 4 7/0.53 0.6 1.6 22.4 1220
06t1.50C0POS0PWP 6 7/0.53 0.6 1.6 26.3 1528
10t1.50C0POS0PWP 10 7/0.53 0.6 2.0 33.9 2337
12t1.50C0POS0PWP 12 7/0.53 0.6 2.0 35.1 2616
15t1.50C0POS0PWP 15 7/0.53 0.6 2.0 38.7 3061
Conductor 2.0 mm2
01t2.00C0POS0PWP 1 7/0.60 0.6 0.9 13.7 455
02t2.00C0POS0PWP 2 7/0.60 0.6 1.6 23.0 820
04t2.00C0POS0PWP 4 7/0.60 0.6 1.6 24.0 1429
06t2.00C0POS0PWP 6 7/0.60 0.6 1.6 28.2 1847
10t2.00C0POS0PWP 10 7/0.60 0.6 2.0 36.4 2863
12t2.00C0POS0PWP 12 7/0.60 0.6 2.0 37.8 3173
15t2.00C0POS0PWP 15 7/0.60 0.6 2.0 41.6 3808
Conductor 2.5 mm2
01t2.50C0POS0PWP 1 7/0.67 0.6 0.9 14.2 535
02t2.50C0POS0PWP 2 7/0.67 0.6 1.6 23.8 890
04t2.50C0POS0PWP 4 7/0.67 0.6 1.6 24.7 1463
06t2.50C0POS0PWP 6 7/0.67 0.6 1.6 29.1 1863
10t2.50C0POS0PWP 10 7/0.67 0.6 2.0 37.9 2907
12t2.50C0POS0PWP 12 7/0.67 0.6 2.0 39.0 3259
15t2.50C0POS0PWP 15 7/0.67 0.6 2.0 43.7 3840
Follow: Multi Triple Instrument Cables, Armoured, Overall Shielded
4.0 Instrument Cables
73
Multi Core Instrument Cables, Armoured, Overall Shielded
Product Code No. of Cores
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 0.5 mm2
02c00.5C0POS0PWP 2 7/0.30 0.6 0.9 11.1 277
03c00.5C0POS0PWP 3 7/0.30 0.6 0.9 11.4 297
04c00.5C0POS0PWP 4 7/0.30 0.6 0.9 11.9 327
05c00.5C0POS0PWP 5 7/0.30 0.6 0.9 12.5 367
07c00.5C0POS0PWP 7 7/0.30 0.6 0.9 13.3 423
12c00.5C0POS0PWP 12 7/0.30 0.6 1.25 16.3 695
19c00.5C0POS0PWP 19 7/0.30 0.6 1.25 18.8 865
24c00.5C0POS0PWP 24 7/0.30 0.6 1.25 21.2 1157
Conductor 0.75 mm2
02c0.75C0POS0PWP 2 7/0.37 0.6 0.9 11.5 292
03c0.75C0POS0PWP 3 7/0.37 0.6 0.9 11.8 316
04c0.75C0POS0PWP 4 7/0.37 0.6 0.9 12.4 357
05c0.75C0POS0PWP 5 7/0.37 0.6 0.9 13.2 408
07c0.75C0POS0PWP 7 7/0.37 0.6 0.9 14.0 539
12c0.75C0POS0PWP 12 7/0.37 0.6 1.25 17.9 759
19c0.75C0POS0PWP 19 7/0.37 0.6 1.25 20.1 1090
24c0.75C0POS0PWP 24 7/0.37 0.6 1.6 23.0 1295
Conductor 1.0 mm2
02c1.00C0POS0PWP 2 7/0.43 0.6 0.9 12.0 313
03c1.00C0POS0PWP 3 7/0.43 0.6 0.9 12.4 343
04c1.00C0POS0PWP 4 7/0.43 0.6 0.9 13.3 390
05c1.00C0POS0PWP 5 7/0.43 0.6 0.9 14.1 526
07c1.00C0POS0PWP 7 7/0.43 0.6 0.9 14.9 593
12c1.00C0POS0PWP 12 7/0.43 0.6 1.25 19.0 850
19c1.00C0POS0PWP 19 7/0.43 0.6 1.6 22.2 1204
24c1.00C0POS0PWP 24 7/0.43 0.6 1.6 24.9 1458
74 BICC CABLES
Product Code No. of Cores
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02c1.50C0POS0PWP 2 7/0.53 0.6 0.9 12.5 353
03c1.50C0POS0PWP 3 7/0.53 0.6 0.9 13.1 405
04c1.50C0POS0PWP 4 7/0.53 0.6 0.9 14.1 534
05c1.50C0POS0PWP 5 7/0.53 0.6 0.9 14.8 591
07c1.50C0POS0PWP 7 7/0.53 0.6 1.25 16.3 714
12c1.50C0POS0PWP 12 7/0.53 0.6 1.25 20.4 1125
19c1.50C0POS0PWP 19 7/0.53 0.6 1.6 23.6 1427
24c1.50C0POS0PWP 24 7/0.53 0.6 1.6 26.4 1718
Conductor 2.0 mm2
02c2.00C0POS0PWP 2 7/0.60 0.6 0.9 13.2 400
03c2.00C0POS0PWP 3 7/0.60 0.6 0.9 13.7 538
04c2.00C0POS0PWP 4 7/0.60 0.6 0.9 14.6 604
05c2.00C0POS0PWP 5 7/0.60 0.6 1.25 16.2 713
07c2.00C0POS0PWP 7 7/0.60 0.6 1.25 17.7 817
12c2.00C0POS0PWP 12 7/0.60 0.6 1.6 22.2 1291
19c2.00C0POS0PWP 19 7/0.60 0.6 1.6 24.9 1683
24c2.00C0POS0PWP 24 7/0.60 0.6 1.6 28.2 2026
Conductor 2.5 mm2
02c2.50C0POS0PWP 2 7/0.67 0.6 0.9 13.5 422
03c2.50C0POS0PWP 3 7/0.67 0.6 0.9 14.2 550
04c2.50C0POS0PWP 4 7/0.67 0.6 0.9 15.0 620
05c2.50C0POS0PWP 5 7/0.67 0.6 1.25 16.7 732
07c2.50C0POS0PWP 7 7/0.67 0.6 1.25 18.0 843
12c2.50C0POS0PWP 12 7/0.67 0.6 1.6 22.7 1359
19c2.50C0POS0PWP 19 7/0.67 0.6 1.6 25.7 1762
24c2.50C0POS0PWP 24 7/0.67 0.6 1.6 29.0 2168
Follow: Multi Core Instrument Cables, Armoured, Overall Shielded
4.0 Instrument Cables
75
Galvanize the moment with the best cable
76 BICC CABLES
Multi Pair/Triple, Armoured,Individual & Overall ShieldingApplicationMulti pair/triple instrument cables are used as signal carrier for connecting electrical instrument circuits.
Construction
1. ConductorStranded Copper class 2
2. InsulationPolyvinyl Chloride (PVC)Alternative: Cross Linked Polyethylene (XLPE )
3. Shielding Individual & Overall Shielding
4. ArmourGalvanized Round Steel Wire (GSWA) 5. SheathPolyvinyl Chloride (PVC)
4.0 Instrument Cables
77
Product Code No. of Pairs
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 0.5 mm2
02p00.5C0PISOSPWP 2 7/0.30 0.6 1.25 17.6 622
04p00.5C0PISOSPWP 4 7/0.30 0.6 1.25 19.8 774
06p00.5C0PISOSPWP 6 7/0.30 0.6 1.25 20.4 1083
10p00.5C0PISOSPWP 10 7/0.30 0.6 1.6 25.9 1489
15p00.5C0PISOSPWP 15 7/0.30 0.6 1.6 29.2 2071
20p00.5C0PISOSPWP 20 7/0.30 0.6 1.6 32.6 2422
Conductor 0.75 mm2
02p0.75C0PISOSPWP 2 7/0.37 0.6 1.25 18.3 672
04p0.75C0PISOSPWP 4 7/0.37 0.6 1.25 20.7 985
06p0.75C0PISOSPWP 6 7/0.37 0.6 1.6 22.2 1220
10p0.75C0PISOSPWP 10 7/0.37 0.6 1.6 27.5 1643
15p0.75C0PISOSPWP 15 7/0.37 0.6 1.6 31.3 2312
20p0.75C0PISOSPWP 20 7/0.37 0.6 2.0 35.5 2771
Conductor 1.0 mm2
02p1.00C0PISOSPWP 2 7/0.43 0.6 1.25 19.8 707
04p1.00C0PISOSPWP 4 7/0.43 0.6 1.6 22.8 1042
06p1.00C0PISOSPWP 6 7/0.43 0.6 1.6 24.1 1324
10p1.00C0PISOSPWP 10 7/0.43 0.6 1.6 29.8 2055
15p1.00C0PISOSPWP 15 7/0.43 0.6 2.0 35.1 2528
20p1.00C0PISOSPWP 20 7/0.43 0.6 2.0 38.9 3045
Conductor 1.5 mm2
02p1.50C0PISOSPWP 2 7/0.53 0.6 1.25 20.8 959
04p1.50C0PISOSPWP 4 7/0.53 0.6 1.6 24.0 1218
06p1.50C0PISOSPWP 6 7/0.53 0.6 1.6 25.6 1538
10p1.50C0PISOSPWP 10 7/0.53 0.6 1.6 32.2 2357
15p1.50C0PISOSPWP 15 7/0.53 0.6 2.0 37.7 3006
20p1.50C0PISOSPWP 20 7/0.53 0.6 2.0 41.5 4040
Multi Pair Instrument Cables, Armoured,Individual & Overall Shielded
78 BICC CABLES
Product Code No. of Pairs
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 2.0 mm2
02p2.00C0PISOSPWP 2 7/0.60 0.6 1.6 22.5 1070
04p2.00C0PISOSPWP 4 7/0.60 0.6 1.6 25.6 1377
06p2.00C0PISOSPWP 6 7/0.60 0.6 1.6 27.4 1703
10p2.00C0PISOSPWP 10 7/0.60 0.6 2.0 35.3 2724
15p2.00C0PISOSPWP 15 7/0.60 0.6 2.0 40.3 3900
20p2.00C0PISOSPWP 20 7/0.60 0.6 2.5 45.6 4738
Conductor 2.5 mm2
02p2.50C0PISOSPWP 2 7/0.67 0.6 1.6 23.0 1101
04p2.50C0PISOSPWP 4 7/0.67 0.6 1.6 26.2 1446
06p2.50C0PISOSPWP 6 7/0.67 0.6 1.6 28.2 1840
10p2.50C0PISOSPWP 10 7/0.67 0.6 2.0 36.3 2964
15p2.50C0PISOSPWP 15 7/0.67 0.6 2.0 41.5 3700
20p2.50C0PISOSPWP 20 7/0.67 0.6 2.5 47.4 5022
Follow: Multi Pair Instrument Cables, Armoured,Individual & Overall Shielded
Multi Triple Instrument Cables, Armoured,Individual & Overall Shielded
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 0.5 mm2
02t00.5C0PISOSPWP 2 7/0.30 0.6 1.25 18.2 666
04t00.5C0PISOSPWP 4 7/0.30 0.6 1.25 18.4 957
06t00.5C0PISOSPWP 6 7/0.30 0.6 1.6 22.1 1181
10t00.5C0PISOSPWP 10 7/0.30 0.6 1.6 27.4 1683
12t00.5C0PISOSPWP 12 7/0.30 0.6 1.6 28.1 1802
15t00.5C0PISOSPWP 15 7/0.30 0.6 1.6 31.1 2286
Conductor 0.75 mm2
02t0.75C0PISOSPWP 2 7/0.37 0.6 1.25 19.0 743
04t0.75C0PISOSPWP 4 7/0.37 0.6 1.25 20.0 1078
4.0 Instrument Cables
79
Follow: Multi Triple Instrument Cables, Armoured,Individual & Overall Shielded
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 0.75 mm2
06t0.75C0PISOSPWP 6 7/0.37 0.6 1.6 23.0 1374
10t0.75C0PISOSPWP 10 7/0.37 0.6 1.6 28.9 2105
12t0.75C0PISOSPWP 12 7/0.37 0.6 1.6 29.8 2290
15t0.75C0PISOSPWP 15 7/0.37 0.6 2.0 33.9 2658
Conductor 1.0 mm2
02t1.00C0PISOSPWP 2 7/0.43 0.6 1.25 20.6 790
04t1.00C0PISOSPWP 4 7/0.43 0.6 1.25 22.0 1176
06t1.00C0PISOSPWP 6 7/0.43 0.6 1.6 25.2 1503
10t1.00C0PISOSPWP 10 7/0.43 0.6 1.6 32.0 2342
12t1.00C0PISOSPWP 12 7/0.43 0.6 2.0 33.7 2538
15t1.00C0PISOSPWP 15 7/0.43 0.6 2.0 37.4 2971
Conductor 1.5 mm2
02t1.50C0PISOSPWP 2 7/0.53 0.6 1.6 22.3 1041
04t1.50C0PISOSPWP 4 7/0.53 0.6 1.6 23.5 1372
06t1.50C0PISOSPWP 6 7/0.53 0.6 1.6 26.9 1787
10t1.50C0PISOSPWP 10 7/0.53 0.6 2.0 34.7 2758
12t1.50C0PISOSPWP 12 7/0.53 0.6 2.0 36.0 3021
15t1.50C0PISOSPWP 15 7/0.53 0.6 2.0 39.7 3941
Conductor 2.0 mm2
02t2.00C0PISOSPWP 2 7/0.60 0.6 1.6 23.6 1186
04t2.00C0PISOSPWP 4 7/0.60 0.6 1.6 24.5 1578
06t2.00C0PISOSPWP 6 7/0.60 0.6 1.6 28.8 2088
10t2.00C0PISOSPWP 10 7/0.60 0.6 2.0 37.6 3375
12t2.00C0PISOSPWP 12 7/0.60 0.6 2.0 38.7 3654
15t2.00C0PISOSPWP 15 7/0.60 0.6 2.0 42.5 4274
Conductor 2.5 mm2
02t2.50C0PISOSPWP 2 7/0.67 0.6 1.6 24.2 1209
04t2.50C0PISOSPWP 4 7/0.67 0.6 1.6 25.2 1622
06t2.50C0PISOSPWP 6 7/0.67 0.6 1.6 29.7 2186
10t2.50C0PISOSPWP 10 7/0.67 0.6 2.0 38.7 3505
12t2.50C0PISOSPWP 12 7/0.67 0.6 2.0 39.8 3912
15t2.50C0PISOSPWP 15 7/0.67 0.6 2.5 45.1 4572
80 BICC CABLES
5.0 Earthing & Building Wires
81
5.0 Earthing & Building Wires
82 BICC CABLES
5.0 Earthing & Building Wires
Application
Sizes
Insulation Color
Rated Voltage
Construction
Specification Standards
Earthing wires are used for indoor fixed installations in dry locations, laid in conduits as well as in steel support brackets mainly inside appliances, switchgear and control gear.
This publication covers single core wires from conductor size 1 mm2 up to 10 mm2.
Yellow / Green is the most common used color for such wires and all other colorsare available upon request.
450/750 V
1. ConductorCopper (or Tinned Copper)In different flexibility degrees
2. Insulation- Polyvinyl Chloride (PVC) 70°C- Low Smoke Zero Halogen (LSOH) 90°C
Standard specification applied to PVC insulation
Standard specification applied to LSOH insulation
Standard specification applied to Conductor
Spread of Flame
IEC 60227-3 BS EN 50525-3-41
IEC 60228
Flame retardant as per IEC 60332-1
Note: Values in the following tables are approximate and subject to manufacturing tolerance.
83
Bringing energy to your door
84 BICC CABLES
5.0 Earthing & Building Wires
Earthing / Building Wires ApplicationThese wires are used for indoor fixed installations in dry locations, laid in conduits as well as in steel support brackets mainly inside appliances, switchgear and control gear.
Construction
1. ConductorStranded Copper class 2
2. InsulationPolyvinyl Chloride (PVC)Alternative: Low Smoke Zero Halogen (LSOH)
85
Single Core PVC Insulated Conductor (450/750 V)
Single Core LSOH Insulated Conductor (450/750 V)
Product Code Conductor Area (mm2)
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
01c001CP0000 1.0 7/0.43 0.7 2.7 16
01c01.5CP0000 1.5 7/0.53 0.7 2.8 21
01c002CP0000 2.0 7/0.60 0.8 3.4 28
01c02.5CP0000 2.5 7/0.67 0.8 3.5 33
01c003CP0000 3.0 7/0.74 0.8 3.7 38
01c004CP0000 4.0 7/0.84 0.8 4.1 48
01c006CP0000 6.0 7/1.04 0.8 4.6 68
01c010CP0000 10.0 7/1.36 1 5.8 110
Product Code Conductor Area (mm2)
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
01c001CL0000 1.0 7/0.43 0.7 2.7 16
01c01.5CL0000 1.5 7/0.53 0.7 2.8 21
01c002CL0000 2.0 7/0.60 0.8 3.4 28
01c02.5CL0000 2.5 7/0.67 0.8 3.5 33
01c003CL0000 3.0 7/0.74 0.8 3.7 38
01c004CL0000 4.0 7/0.84 0.8 4.1 48
01c006CL0000 6.0 7/1.04 0.8 4.6 68
01c010CL0000 10.0 7/1.36 1 5.8 110
86 BICC CABLES
6.0 Fire Resistance Control & Instrument Cables
87
88 BICC CABLES
Application
Construction
Fire resistance cables are used when the cables are required to keep circuit integrity and continue to operate in the presence of a fire for a specified time under defined conditions.
1. ConductorCopper (in variable classes 1,2&5)Tinned Copper is also available.
2. Fire resistance materialMICA Glass Tape
3. Insulation- Cross Linked Polyethylene (XLPE)- Low Smoke Zero Halogen (LSOH): For required controlled emissions of halogen and smoke
4. Bedding & Outer Sheath materialMaterial shall be compatible with the required function from these cables such as Low Smoke Zero Halogen(LSOH)
Spread Of Flame Spread of Flame
Circuit Integrity
Flame retardant as per IEC 60332-1 Fire resistance cable with glass mica tape 950°C in accordance with BS 6387 (category C,W & Z) and IEC 60331
These cables can be designed complete with Galvanized Steel Wire Armour and individual & Overall Shielding similar to categories illustrated in this publication.
6.0 Fire Resistance Control & Instrument Cables
89
Options AvailableSizesAll sizes are available upon request
MaterialWhere necessary, special features can be incorporated into the cable enabling it to have:- Improved fire performance- Low smoke and fume (Halogen free)* IEC 60754-1&2 : Test on gas evolved during the combustion of material from cables* IEC 61034: Measurement of smoke density for cables burning under defined conditions- Termite resistance- Resistance to attack from oils, solvents or corrosive chemicals
Note: Values in the following tables are approximate and subject to manufacturing tolerance.
90 BICC CABLES
Fire Resistance Control Cables,Non Armoured ApplicationThese cables are used for interconnecting control devices mainly in hazardous areas wheresafety and circuit integrity are highly required during fire conditions.
Construction
1. ConductorStranded Copper class 2
2. Fire resistance material MICA Glass Tape
3. InsulationCross Linked Polyethylene (XLPE)
4. SheathLow Smoke Zero Halogen (LSOH)
6.0 Fire Resistance Control & Instrument Cables
91
Fire Resistance Control Cables, Non Armoured, XLPE Insulated
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Di-ameter (mm)
Approx. Weight of Completed Cable (kg/km)
Conductor 1.0 mm2
02c001CMX00L 2 7/0.43 0.7 10.6 180
03c001CMX00L 3 7/0.43 0.7 11.1 190
04c001CMX00L 4 7/0.43 0.7 12.0 208
07c001CMX00L 7 7/0.43 0.7 13.9 280
12c001CMX00L 12 7/0.43 0.7 17.7 406
19c001CMX00L 19 7/0.43 0.7 20.4 546
27c001CMX00L 27 7/0.43 0.7 24.1 710
37c001CMX00L 37 7/0.43 0.7 26.9 886
48c001CMX00L 48 7/0.43 0.7 31.1 1110
Conductor 1.5 mm2
02c01.5CMX00L 2 7/0.53 0.7 11.1 200
03c01.5CMX00L 3 7/0.53 0.7 11.6 220
04c01.5CMX00L 4 7/0.53 0.7 12.5 241
07c01.5CMX00L 7 7/0.53 0.7 14.6 333
12c01.5CMX00L 12 7/0.53 0.7 18.6 495
19c01.5CMX00L 19 7/0.53 0.7 21.6 680
27c01.5CMX00L 27 7/0.53 0.7 25.6 895
37c01.5CMX00L 37 7/0.53 0.7 28.5 1137
48c01.5CMX00L 48 7/0.53 0.7 32.5 1431
Conductor 2.0 mm2
02c002CMX00L 2 7/0.60 0.7 11.6 230
03c002CMX00L 3 7/0.60 0.7 12.2 245
04c002CMX00L 4 7/0.60 0.7 13.2 277
07c002CMX00L 7 7/0.60 0.7 15.4 390
12c002CMX00L 12 7/0.60 0.7 19.7 585
19c002CMX00L 19 7/0.60 0.7 22.9 815
27c002CMX00L 27 7/0.60 0.7 27.2 1079
37c002CMX00L 37 7/0.60 0.7 30.6 1383
48c002CMX00L 48 7/0.60 0.7 35.3 1752
92 BICC CABLES
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable (kg/km)
Conductor 2.5 mm2
02c02.5CMX00L 2 7/0.67 0.7 11.9 260
03c02.5CMX00L 3 7/0.67 0.7 12.5 270
04c02.5CMX00L 4 7/0.67 0.7 13.5 308
07c02.5CMX00L 7 7/0.67 0.7 15.7 441
12c02.5CMX00L 12 7/0.67 0.7 20.2 667
19c02.5CMX00L 19 7/0.67 0.7 23.5 938
27c02.5CMX00L 27 7/0.67 0.7 28.2 1261
37c02.5CMX00L 37 7/0.67 0.7 31.7 1622
48c02.5CMX00L 48 7/0.67 0.7 36.3 2057
Conductor 3.0 mm2
02c003CMX00L 2 7/0.74 0.7 12.3 280
03c003CMX00L 3 7/0.74 0.7 13.0 295
04c003CMX00L 4 7/0.74 0.7 14.0 339
07c003CMX00L 7 7/0.74 0.7 16.4 489
12c003CMX00L 12 7/0.74 0.7 21.2 748
19c003CMX00L 19 7/0.74 0.7 24.6 1062
27c003CMX00L 27 7/0.74 0.7 29.5 1426
37c003CMX00L 37 7/0.74 0.7 33.2 1846
Conductor 4.0 mm2
02c004CMX00L 2 7/0.84 0.7 13.1 321
03c004CMX00L 3 7/0.84 0.7 13.8 330
04c004CMX00L 4 7/0.84 0.7 14.9 393
07c004CMX00L 7 7/0.84 0.7 17.5 577
12c004CMX00L 12 7/0.84 0.7 22.7 893
19c004CMX00L 19 7/0.84 0.7 26.5 1283
27c004CMX00L 27 7/0.84 0.7 32.1 1728
37c004CMX00L 37 7/0.84 0.7 36.1 2274
Follow: Fire Resistance Control Cables, Non Armoured, XLPE Insulated
6.0 Fire Resistance Control & Instrument Cables
93
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable (kg/km)
Conductor 6.0 mm2
02c006CMX00L 2 7/1.04 0.7 14.1 376
03c006CMX00L 3 7/1.04 0.7 14.9 400
04c006CMX00L 4 7/1.04 0.7 16.2 488
Conductor 10 mm2
02c010CMX00L 2 7/1.36 0.7 15.7 498
03c010CMX00L 3 7/1.36 0.7 16.6 559
04c010CMX00L 4 7/1.36 0.7 18.1 693
Follow: Fire Resistance Control Cables, Non Armoured, XLPE Insulated
94 BICC CABLES
Fire Resistance Control Cables,Armoured ApplicationThese cables are used for interconnecting control devices mainly in hazardous areas where safety and circuit integrity are highly required during fire conditions.
Construction
1. ConductorStranded Copper class 2
2. Fire Resistance Material MICA Glass Tape
3. InsulationCross Linked Polyethylene (XLPE)
4. Armour Galvanized Round Steel Wire (GSWA)
5. SheathLow Smoke Zero Halogen (LSOH)
6.0 Fire Resistance Control & Instrument Cables
95
Fire Resistance Control Cables, Armoured, XLPE Insulated
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.0 mm2
02c001CMXLWL 2 7/0.43 0.7 0.9 14.9 424
03c001CMXLWL 3 7/0.43 0.7 0.9 15.4 435
04c001CMXLWL 4 7/0.43 0.7 1.25 17.0 479
07c001CMXLWL 7 7/0.43 0.7 1.25 18.9 676
12c001CMXLWL 12 7/0.43 0.7 1.6 23.4 915
19c001CMXLWL 19 7/0.43 0.7 1.6 26.1 1263
27c001CMXLWL 27 7/0.43 0.7 1.6 30.0 1569
37c001CMXLWL 37 7/0.43 0.7 2.0 33.8 1864
48c001CMXLWL 48 7/0.43 0.7 2.0 38.0 2248
Conductor 1.5 mm2
02c01.5CMXLWL 2 7/0.53 0.7 0.9 15.4 473
03c01.5CMXLWL 3 7/0.53 0.7 0.9 15.9 484
04c01.5CMXLWL 4 7/0.53 0.7 1.25 17.5 540
07c01.5CMXLWL 7 7/0.53 0.7 1.25 19.6 773
12c01.5CMXLWL 12 7/0.53 0.7 1.6 24.3 1050
19c01.5CMXLWL 19 7/0.53 0.7 1.6 27.3 1473
27c01.5CMXLWL 27 7/0.53 0.7 1.6 31.7 1849
37c01.5CMXLWL 37 7/0.53 0.7 2.0 35.6 2236
48c01.5CMXLWL 48 7/0.53 0.7 2.0 39.8 2909
Conductor 2.0 mm2
02c002CMXLWL 2 7/0.60 0.7 0.9 15.9 498
03c002CMXLWL 3 7/0.60 0.7 1.25 17.2 520
04c002CMXLWL 4 7/0.60 0.7 1.25 18.2 670
07c002CMXLWL 7 7/0.60 0.7 1.25 20.4 844
12c002CMXLWL 12 7/0.60 0.7 1.6 25.4 1300
19c002CMXLWL 19 7/0.60 0.7 1.6 28.8 1671
27c002CMXLWL 27 7/0.60 0.7 2.0 34.3 2102
37c002CMXLWL 37 7/0.60 0.7 2.0 37.7 2554
48c002CMXLWL 48 7/0.60 0.7 2.0 42.2 3554
96 BICC CABLES
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter
(mm)
Overall Cable Diameter
(mm)
Approx. Weight of Completed Cable (kg/km)
Conductor 2.5 mm2
02c02.5CMXLWL 2 7/0.67 0.7 1.25 16.9 526
03c02.5CMXLWL 3 7/0.67 0.7 1.25 17.5 553
04c02.5CMXLWL 4 7/0.67 0.7 1.25 18.5 717
07c02.5CMXLWL 7 7/0.67 0.7 1.25 20.9 920
12c02.5CMXLWL 12 7/0.67 0.7 1.6 25.9 1428
19c02.5CMXLWL 19 7/0.67 0.7 1.6 29.4 1841
27c02.5CMXLWL 27 7/0.67 0.7 2.0 35.0 2336
37c02.5CMXLWL 37 7/0.67 0.7 2.0 38.6 3145
48c02.5CMXLWL 48 7/0.67 0.7 2.0 43.3 3929
Conductor 3.0 mm2
02c003CMXLWL 2 7/0.74 0.7 1.25 17.3 552
03c003CMXLWL 3 7/0.74 0.7 1.25 18.0 676
04c003CMXLWL 4 7/0.74 0.7 1.25 19.0 760
07c003CMXLWL 7 7/0.74 0.7 1.25 21.4 985
12c003CMXLWL 12 7/0.74 0.7 1.6 26.9 1534
19c003CMXLWL 19 7/0.74 0.7 1.6 30.6 1994
27c003CMXLWL 27 7/0.74 0.7 2.0 36.9 2584
37c003CMXLWL 37 7/0.74 0.7 2.0 40.2 3463
Conductor 4.0 mm2
02c004CMXLWL 2 7/0.84 0.7 1.25 18.1 694
03c004CMXLWL 3 7/0.84 0.7 1.25 18.8 748
04c004CMXLWL 4 7/0.84 0.7 1.25 19.9 845
07c004CMXLWL 7 7/0.84 0.7 1.6 23.2 1115
12c004CMXLWL 12 7/0.84 0.7 1.6 28.6 1746
19c004CMXLWL 19 7/0.84 0.7 1.6 32.6 2301
27c004CMXLWL 27 7/0.84 0.7 2.0 39.0 3269
37c004CMXLWL 37 7/0.84 0.7 2.0 43.0 4095
Follow: Fire Resistance Control Cables, Armoured, XLPE Insulated
6.0 Fire Resistance Control & Instrument Cables
97
Product Code No. of Cores
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter
(mm)
Overall Cable Diameter
(mm)
Approx. Weight of Completed Cable (kg/km)
Conductor 6.0 mm2
02c006CMXLWL 2 7/1.04 0.7 1.25 19.1 744
03c006CMXLWL 3 7/1.04 0.7 1.25 19.9 805
04c006CMXLWL 4 7/1.04 0.7 1.25 21.2 928
Conductor 10 mm2
02c010CMXLWL 2 7/1.36 0.7 1.25 20.7 910
03c010CMXLWL 3 7/1.36 0.7 1.25 21.6 1022
04c010CMXLWL 4 7/1.36 0.7 1.6 23.8 1205
Follow: Fire Resistance Control Cables, Armoured, XLPE Insulated
98 BICC CABLES
Fire Resistance Multi Pair/Triple & Core Cables, Non Armoured, XLPE Insulated, Overall Shielding ApplicationThese cables are used as signal carrier for connecting electrical instrument circuits mainly in hazardous areas where safety and circuit integrity are highly required during fire conditions.
Construction
1. ConductorStranded Copper class 2
2. Fire Resistance Material MICA Glass Tape
3. InsulationCross Linked Polyethylene (XLPE)
4. Shielding Overall Shielding
5. SheathLow Smoke Zero Halogen (LSOH)
6.0 Fire Resistance Control & Instrument Cables
99
Fire Resistance Multi Pair Cables, Non Armoured, Overall Shielded, XLPE Insulated
Product Code No. of Pairs Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diame-ter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
01p01.5CMXOS000L 1 7/0.53 0.6 9.0 115
02p01.5CMXOS000L 2 7/0.53 0.6 16.6 183
04p01.5CMXOS000L 4 7/0.53 0.6 19.6 376
06p01.5CMXOS000L 6 7/0.53 0.6 21.5 508
10p01.5CMXOS000L 10 7/0.53 0.6 29.1 749
15p01.5CMXOS000L 15 7/0.53 0.6 33.9 1094
20p01.5CMXOS000L 20 7/0.53 0.6 38.7 1430
Conductor 2.5 mm2
01p02.5CMXOS000L 1 7/0.67 0.6 9.8 154
02p02.5CMXOS000L 2 7/0.67 0.6 18.1 256
04p02.5CMXOS000L 4 7/0.67 0.6 21.5 514
06p02.5CMXOS000L 6 7/0.67 0.6 24.3 725
10p02.5CMXOS000L 10 7/0.67 0.6 32.2 1145
15p02.5CMXOS000L 15 7/0.67 0.6 38.1 1644
20p02.5CMXOS000L 20 7/0.67 0.6 43.3 2169
100 BICC CABLES
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
01t01.5CMXOS000L 1 7/0.53 0.6 9.5 146
02t01.5CMXOS000L 2 7/0.53 0.6 17.6 286
04t01.5CMXOS000L 4 7/0.53 0.6 18.9 490
06t01.5CMXOS000L 6 7/0.53 0.6 23.5 688
10t01.5CMXOS000L 10 7/0.53 0.6 31.2 1050
12t01.5CMXOS000L 12 7/0.53 0.6 32.4 1225
15t01.5CMXOS000L 15 7/0.53 0.6 36.9 1529
Conductor 2.5 mm2
01t02.5CMXOS000L 1 7/0.67 0.6 10.3 188
02t02.5CMXOS000L 2 7/0.67 0.6 19.5 350
04t02.5CMXOS000L 4 7/0.67 0.6 20.9 663
06t02.5CMXOS000L 6 7/0.67 0.6 26.0 950
10t02.5CMXOS000L 10 7/0.67 0.6 35.2 1521
12t02.5CMXOS000L 12 7/0.67 0.6 36.5 1760
15t02.5CMXOS000L 15 7/0.67 0.6 40.9 2199
6.0 Fire Resistance Control & Instrument Cables
Fire Resistance Multi Triple Cables, Non Armoured, Overall Shielded, XLPE Insulated
101
Product Code No. of Cores Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02c01.5CMXOS000L 2 7/0.53 0.6 9.0 115
03c01.5CMXOS000L 3 7/0.53 0.6 9.5 153
04c01.5CMXOS000L 4 7/0.53 0.6 10.4 185
05c01.5CMXOS000L 5 7/0.53 0.6 11.7 219
07c01.5CMXOS000L 7 7/0.53 0.6 12.7 296
12c01.5CMXOS000L 12 7/0.53 0.6 16.7 471
19c01.5CMXOS000L 19 7/0.53 0.6 19.7 674
24c01.5CMXOS000L 24 7/0.53 0.6 23.3 851
Conductor 2.5 mm2
02c02.5CMXOS000L 2 7/0.67 0.6 9.8 161
03c02.5CMXOS000L 3 7/0.67 0.6 10.3 199
04c02.5CMXOS000L 4 7/0.67 0.6 11.7 245
05c02.5CMXOS000L 5 7/0.67 0.6 12.7 310
07c02.5CMXOS000L 7 7/0.67 0.6 14.0 396
12c02.5CMXOS000L 12 7/0.67 0.6 18.5 631
19c02.5CMXOS000L 19 7/0.67 0.6 21.6 939
24c02.5CMXOS000L 24 7/0.67 0.6 25.7 1201
Fire Resistance Multi Core Cables, Non Armoured, Overall Shielded, XLPE Insulated
102 BICC CABLES
Fire Resistance Multi Pair/Triple Cables, Non Armoured, XLPE Insulated, Individual & Overall Shielding ApplicationThese cables are used as signal carrier for connecting electrical instrument circuits mainly in hazardous areas where safety and circuit integrity are highly required during fire conditions.
Construction
1. ConductorStranded Copper class 2
2. Fire resistance material MICA Glass Tape
3. InsulationCross Linked Polyethylene (XLPE)
4. Shielding Individual & Overall Shielding
5. SheathLow Smoke Zero Halogen (LSOH)
6.0 Fire Resistance Control & Instrument Cables
103
Fire Resistance Multi Pair Cables, Non Armoured,Individual & Overall Shielded, XLPE Insulated
Fire Resistance Multi Triple Cables,Non Armoured, Individual & Overall Shielded, XLPE Insulated
Product Code No. of Pairs Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02p01.5CMXISOS00L 2 7/0.53 0.6 17.0 300
04p01.5CMXISOS00L 4 7/0.53 0.6 20.1 459
06p01.5CMXISOS00L 6 7/0.53 0.6 22.1 648
10p01.5CMXISOS00L 10 7/0.53 0.6 29.9 983
15p01.5CMXISOS00L 15 7/0.53 0.6 35.4 1403
20p01.5CMXISOS00L 20 7/0.53 0.6 39.8 1853
Conductor 2.5 mm2
02p02.5CMXISOS00L 2 7/0.67 0.6 18.5 388
04p02.5CMXISOS00L 4 7/0.67 0.6 22.0 619
06p02.5CMXISOS00L 6 7/0.67 0.6 24.9 861
10p02.5CMXISOS00L 10 7/0.67 0.6 33.0 1429
15p02.5CMXISOS00L 15 7/0.67 0.6 39.1 1956
20p02.5CMXISOS00L 20 7/0.67 0.6 44.4 2590
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02t01.5CMXISOS00L 2 7/0.53 0.6 18.0 345
04t01.5CMXISOS00L 4 7/0.53 0.6 19.4 550
06t01.5CMXISOS00L 6 7/0.53 0.6 24.1 813
10t01.5CMXISOS00L 10 7/0.53 0.6 32.0 1238
12t01.5CMXISOS00L 12 7/0.53 0.6 33.2 1478
15t01.5CMXISOS00L 15 7/0.53 0.6 37.9 1788
Conductor 2.5 mm2
02t02.5CMXISOS00L 2 7/0.67 0.6 19.9 458
04t02.5CMXISOS00L 4 7/0.67 0.6 21.4 751
06t02.5CMXISOS00L 6 7/0.67 0.6 26.4 1058
10t02.5CMXISOS00L 10 7/0.67 0.6 36.0 1758
12t02.5CMXISOS00L 12 7/0.67 0.6 37.3 2003
15t02.5CMXISOS00L 15 7/0.67 0.6 42.2 2440
104 BICC CABLES
Fire Resistance Multi Pair/Triple & Multi Core Cables, Armoured, XLPE Insulated, Overall Shielding ApplicationThese cables are used as signal carrier for connecting electrical instrument circuits mainly in hazardous areas where safety and circuit integrity are highly required during fire conditions.
Construction
1. ConductorStranded Copper class 2
2. Fire resistance material MICA Glass Tape
3. InsulationCross Linked Polyethylene (XLPE)
4. Shielding Overall Shielding
5. ArmourGalvanized Round Steel Wire (GSWA)
6. SheathLow Smoke Zero Halogen (LSOH)
6.0 Fire Resistance Control & Instrument Cables
105
Fire Resistance Multi Pair Cables, Armoured, Overall Shielded,XLPE Insulated
Product Code No. of Pairs Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter
(mm)
Overall Cable Diameter
(mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
01p01.5CMXOS0LWL 1 7/0.53 0.6 0.9 14.1 434
02p01.5CMXOS0LWL 2 7/0.53 0.6 1.25 22.8 648
04p01.5CMXOS0LWL 4 7/0.53 0.6 1.6 26.7 1261
06p01.5CMXOS0LWL 6 7/0.53 0.6 1.6 28.8 1539
10p01.5CMXOS0LWL 10 7/0.53 0.6 2.0 37.6 2029
15p01.5CMXOS0LWL 15 7/0.53 0.6 2.0 42.6 2965
20p01.5CMXOS0LWL 20 7/0.53 0.6 2.5 48.5 3541
Conductor 2.5 mm2
01p02.5CMXOS0LWL 1 7/0.67 0.6 0.9 14.9 504
02p02.5CMXOS0LWL 2 7/0.67 0.6 1.6 25.2 768
04p02.5CMXOS0LWL 4 7/0.67 0.6 1.6 28.8 1525
06p02.5CMXOS0LWL 6 7/0.67 0.6 1.6 31.8 1896
10p02.5CMXOS0LWL 10 7/0.67 0.6 2.0 40.9 2913
15p02.5CMXOS0LWL 15 7/0.67 0.6 2.5 47.9 3810
20p02.5CMXOS0LWL 20 7/0.67 0.6 2.5 53.1 5093
106 BICC CABLES
Fire Resistance Multi Triple Cables, Armoured, Overall Shielded,XLPE Insulated
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire
Diameter (mm)
Overall Cable Diameter
(mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
01t01.5CMXOS0LWL 1 7/0.53 0.6 0.9 14.6 488
02t01.5CMXOS0LWL 2 7/0.53 0.6 1.6 24.7 913
04t01.5CMXOS0LWL 4 7/0.53 0.6 1.6 26.0 1475
06t01.5CMXOS0LWL 6 7/0.53 0.6 1.6 30.8 1838
10t01.5CMXOS0LWL 10 7/0.53 0.6 2.0 39.7 2798
12t01.5CMXOS0LWL 12 7/0.53 0.6 2.0 41.1 3121
15t01.5CMXOS0LWL 15 7/0.53 0.6 2.5 46.3 3641
Conductor 2.5 mm2
01t02.5CMXOS0LWL 1 7/0.67 0.6 1.25 16.1 550
02t02.5CMXOS0LWL 2 7/0.67 0.6 1.6 26.6 1005
04t02.5CMXOS0LWL 4 7/0.67 0.6 1.6 28.2 1771
06t02.5CMXOS0LWL 6 7/0.67 0.6 2.0 34.3 2241
10t02.5CMXOS0LWL 10 7/0.67 0.6 2.5 44.6 3488
12t02.5CMXOS0LWL 12 7/0.67 0.6 2.5 45.9 3899
15t02.5CMXOS0LWL 15 7/0.67 0.6 2.5 50.7 4583
6.0 Fire Resistance Control & Instrument Cables
107
Fire Resistance Multi Core Cables, Armoured, Overall Shielded,XLPE Insulated
Product Code No. of Cores Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02c01.5CMXOS0LWL 2 7/0.53 0.6 0.9 14.1 434
03c01.5CMXOS0LWL 3 7/0.53 0.6 0.9 14.6 494
04c01.5CMXOS0LWL 4 7/0.53 0.6 1.25 16.2 650
05c01.5CMXOS0LWL 5 7/0.53 0.6 1.25 17.7 718
07c01.5CMXOS0LWL 7 7/0.53 0.6 1.25 18.7 863
12c01.5CMXOS0LWL 12 7/0.53 0.6 1.6 23.8 1356
19c01.5CMXOS0LWL 19 7/0.53 0.6 1.6 26.8 1705
24c01.5CMXOS0LWL 24 7/0.53 0.6 1.6 30.6 2048
Conductor 2.5 mm2
02c02.5CMXOS0LWL 2 7/0.67 0.6 0.9 14.9 518
03c02.5CMXOS0LWL 3 7/0.67 0.6 1.25 16.1 674
04c02.5CMXOS0LWL 4 7/0.67 0.6 1.25 17.7 755
05c02.5CMXOS0LWL 5 7/0.67 0.6 1.25 18.7 891
07c02.5CMXOS0LWL 7 7/0.67 0.6 1.25 20.2 1020
12c02.5CMXOS0LWL 12 7/0.67 0.6 1.6 25.6 1641
19c02.5CMXOS0LWL 19 7/0.67 0.6 1.6 28.9 2111
24c02.5CMXOS0LWL 24 7/0.67 0.6 2.0 34.0 2595
108 BICC CABLES
Fire Resistance Multi Pair/Triple Cables, Armoured,XLPE Insulated, Individual & Overall Shielding ApplicationThese cables are used as signal carrier for connecting electrical instrument circuits mainly in hazardous areas where safety and circuit integrity are highly required during fire conditions.
Construction
1. ConductorStranded Copper class 2
2. Fire resistance material MICA Glass Tape
3. InsulationCross Linked Polyethylene (XLPE)
4. Shielding Individual & Overall Shielding
5. ArmourGalvanized Round Steel Wire (GSWA)
6. SheathLow Smoke Zero Halogen (LSOH)
6.0 Fire Resistance Control & Instrument Cables
109
Fire Resistance Multi Pair Cables, Armoured,Individual & Overall Shielded, XLPE Insulated
Fire Resistance Multi Triple Cables, Armoured,Individual & Overall Shielded , XLPE Insulated
Product Code No. of Pairs
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02p01.5CMXISOSLWL 2 7/0.53 0.6 1.6 24.1 1181
04p01.5CMXISOSLWL 4 7/0.53 0.6 1.6 27.4 1490
06p01.5CMXISOSLWL 6 7/0.53 0.6 1.6 29.4 1873
10p01.5CMXISOSLWL 10 7/0.53 0.6 2.0 38.4 2863
15p01.5CMXISOSLWL 15 7/0.53 0.6 2.5 44.8 3633
20p01.5CMXISOSLWL 20 7/0.53 0.6 2.5 49.6 4883
Conductor 2.5 mm2
02p02.5CMXISOSLWL 2 7/0.67 0.6 1.6 25.6 1356
04p02.5CMXISOSLWL 4 7/0.67 0.6 1.6 29.3 1769
06p02.5CMXISOSLWL 6 7/0.67 0.6 1.6 32.4 2241
10p02.5CMXISOSLWL 10 7/0.67 0.6 2.0 41.7 3608
15p02.5CMXISOSLWL 15 7/0.67 0.6 2.5 48.9 4479
20p02.5CMXISOSLWL 20 7/0.67 0.6 2.5 54.4 6081
Product Code No. of Triples
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02t01.5CMXISOSLWL 2 7/0.53 0.6 1.6 25.1 1276
04t01.5CMXISOSLWL 4 7/0.53 0.6 1.6 26.5 1663
06t01.5CMXISOSLWL 6 7/0.53 0.6 1.6 31.6 2160
10t01.5CMXISOSLWL 10 7/0.53 0.6 2.0 40.7 3324
12t01.5CMXISOSLWL 12 7/0.53 0.6 2.0 41.9 3629
15t01.5CMXISOSLWL 15 7/0.53 0.6 2.5 47.7 4625
Conductor 2.5 mm2
02t02.5CMXISOSLWL 2 7/0.67 0.6 1.6 27.2 1481
04t02.5CMXISOSLWL 4 7/0.67 0.6 1.6 28.7 1963
06t02.5CMXISOSLWL 6 7/0.67 0.6 2.0 35.1 2523
10t02.5CMXISOSLWL 10 7/0.67 0.6 2.5 45.4 4075
12t02.5CMXISOSLWL 12 7/0.67 0.6 2.5 47.1 4394
15t02.5CMXISOSLWL 15 7/0.67 0.6 2.5 52.0 5125
110 BICC CABLES
Fire Resistance Multi Pair/Triple & Cores Cables, Non Armoured, LSOH Insulated, Overall Shielding ApplicationThese cables are used as signal carrier for connecting electrical instrument circuits mainly in hazardous areas where safety and circuit integrity are highly required during fire conditions.
Construction
1. ConductorStranded Copper class 2
2. Fire resistance material MICA Glass Tape
3. InsulationLow Smoke Zero Halogen (LSOH)
4. Shielding Overall Shielding
5. SheathLow Smoke Zero Halogen (LSOH)
6.0 Fire Resistance Control & Instrument Cables
111
Fire Resistance Multi Pair Cables, Non Armoured, Overall Shielded, LSOH Insulated
Product Code No. of Pairs Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
01p01.5CMLOS000L 1 7/0.53 0.6 9.0 124
02p01.5CMLOS000L 2 7/0.53 0.6 16.6 199
04p01.5CMLOS000L 4 7/0.53 0.6 19.6 410
06p01.5CMLOS000L 6 7/0.53 0.6 21.5 556
10p01.5CMLOS000L 10 7/0.53 0.6 29.1 831
15p01.5CMLOS000L 15 7/0.53 0.6 33.9 1219
20p01.5CMLOS000L 20 7/0.53 0.6 38.7 1595
Conductor 2.5 mm2
01p02.5CMLOS000L 1 7/0.67 0.6 9.8 164
02p02.5CMLOS000L 2 7/0.67 0.6 18.1 276
04p02.5CMLOS000L 4 7/0.67 0.6 21.5 554
06p02.5CMLOS000L 6 7/0.67 0.6 24.3 784
10p02.5CMLOS000L 10 7/0.67 0.6 32.2 1243
15p02.5CMLOS000L 15 7/0.67 0.6 38.1 1791
20p02.5CMLOS000L 20 7/0.67 0.6 43.3 2365
112 BICC CABLES
Fire Resistance Multi Triple Cables, Non Armoured, Overall Shielded, LSOH Insulated
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
01t01.5CMLOS000L 1 7/0.53 0.6 9.5 159
02t01.5CMLOS000L 2 7/0.53 0.6 17.6 311
04t01.5CMLOS000L 4 7/0.53 0.6 18.9 539
06t01.5CMLOS000L 6 7/0.53 0.6 23.5 765
10t01.5CMLOS000L 10 7/0.53 0.6 31.2 1175
12t01.5CMLOS000L 12 7/0.53 0.6 32.4 1374
15t01.5CMLOS000L 15 7/0.53 0.6 36.9 1715
Conductor 2.5 mm2
01t02.5CMLOS000L 1 7/0.67 0.6 10.3 203
02t02.5CMLOS000L 2 7/0.67 0.6 19.5 381
04t02.5CMLOS000L 4 7/0.67 0.6 20.9 723
06t02.5CMLOS000L 6 7/0.67 0.6 26.0 1038
10t02.5CMLOS000L 10 7/0.67 0.6 35.2 1668
12t02.5CMLOS000L 12 7/0.67 0.6 36.5 1935
15t02.5CMLOS000L 15 7/0.67 0.6 40.9 2416
6.0 Fire Resistance Control & Instrument Cables
113
Fire Resistance Multi Core Cables, Non Armoured, Overall Shielded, LSOH Insulated
Product Code No. of Cores Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02c01.5CMLOS000L 2 7/0.53 0.6 9.0 123
03c01.5CMLOS000L 3 7/0.53 0.6 9.5 165
04c01.5CMLOS000L 4 7/0.53 0.6 10.4 201
05c01.5CMLOS000L 5 7/0.53 0.6 11.7 239
07c01.5CMLOS000L 7 7/0.53 0.6 12.7 325
12c01.5CMLOS000L 12 7/0.53 0.6 16.7 521
19c01.5CMLOS000L 19 7/0.53 0.6 19.7 753
24c01.5CMLOS000L 24 7/0.53 0.6 23.3 951
Conductor 2.5 mm2
02c02.5CMLOS000L 2 7/0.67 0.6 9.8 170
03c02.5CMLOS000L 3 7/0.67 0.6 10.3 214
04c02.5CMLOS000L 4 7/0.67 0.6 11.7 264
05c02.5CMLOS000L 5 7/0.67 0.6 12.7 335
07c02.5CMLOS000L 7 7/0.67 0.6 14.0 430
12c02.5CMLOS000L 12 7/0.67 0.6 18.5 688
19c02.5CMLOS000L 19 7/0.67 0.6 21.6 1030
24c02.5CMLOS000L 24 7/0.67 0.6 25.7 1316
114 BICC CABLES
Fire Resistance Multi Pair/Triple Cables, Non Armoured, LSOH Insulated, Individual & Overall Shielding ApplicationThese cables are used as signal carrier for connecting electrical instrument circuits mainly in hazardous areas where safety and circuit integrity are highly required during fire conditions.
Construction
1. ConductorStranded Copper class 2
2. Fire resistance material MICA Glass Tape
3. InsulationLow Smoke Zero Halogen (LSOH)
4. Shielding Individual & Overall Shielding
5. SheathLow Smoke Zero Halogen (LSOH)
6.0 Fire Resistance Control & Instrument Cables
115
Fire Resistance Multi Pair Cables, Non Armoured,Individual & Overall Shielded, LSOH Insulated
Fire Resistance Multi Triple Cables, Non Armoured,Individual & Overall Shielded, LSOH Insulated
Product Code No. of Pairs Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02p01.5CMLISOS00L 2 7/0.53 0.6 17.0 316
04p01.5CMLISOS00L 4 7/0.53 0.6 20.1 493
06p01.5CMLISOS00L 6 7/0.53 0.6 22.1 698
10p01.5CMLISOS00L 10 7/0.53 0.6 29.9 1066
15p01.5CMLISOS00L 15 7/0.53 0.6 35.4 1528
20p01.5CMLISOS00L 20 7/0.53 0.6 39.8 2020
Conductor 2.5 mm2
02p02.5CMLISOS00L 2 7/0.67 0.6 18.5 406
04p02.5CMLISOS00L 4 7/0.67 0.6 22.0 658
06p02.5CMLISOS00L 6 7/0.67 0.6 24.9 920
10p02.5CMLISOS00L 10 7/0.67 0.6 33.0 1515
15p02.5CMLISOS00L 15 7/0.67 0.6 39.1 2104
20p02.5CMLISOS00L 20 7/0.67 0.6 44.4 2786
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02t01.5CMLISOS00L 2 7/0.53 0.6 18.0 370
04t01.5CMLISOS00L 4 7/0.53 0.6 19.4 611
06t01.5CMLISOS00L 6 7/0.53 0.6 24.1 890
10t01.5CMLISOS00L 10 7/0.53 0.6 32.0 1363
12t01.5CMLISOS00L 12 7/0.53 0.6 33.2 1625
15t01.5CMLISOS00L 15 7/0.53 0.6 37.9 1980
Conductor 2.5 mm2
02t02.5CMLISOS00L 2 7/0.67 0.6 19.9 486
04t02.5CMLISOS00L 4 7/0.67 0.6 21.4 810
06t02.5CMLISOS00L 6 7/0.67 0.6 26.4 1145
10t02.5CMLISOS00L 10 7/0.67 0.6 36.0 1904
12t02.5CMLISOS00L 12 7/0.67 0.6 37.3 2176
15t02.5CMLISOS00L 15 7/0.67 0.6 42.2 2659
116 BICC CABLES
Fire Resistance Multi Pair/Triple & Core Cables, Armoured,LSOH Insulated, Overall ShieldingApplicationThese cables are used as signal carrier for connecting electrical instrument circuits mainly in hazardous areas where safety and circuit integrity are highly required during fire conditions.
Construction
1. ConductorStranded Copper class 2
2. Fire resistance material MICA Glass Tape
3. InsulationLow Smoke Zero Halogen (LSOH)
4. Shielding Overall Shielding
5. ArmourGalvanized Round Steel Wire (GSWA)
6. SheathLow Smoke Zero Halogen (LSOH)
6.0 Fire Resistance Control & Instrument Cables
117
Fire Resistance Multi Pair Cables, Armoured, Overall Shielded,LSOH Insulated
Product Code No. of Pairs Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter
(mm)
Overall Cable Diameter
(mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
01p01.5CMLOS0LWL 1 7/0.53 0.6 0.9 14.1 443
02p01.5CMLOS0LWL 2 7/0.53 0.6 1.25 22.8 665
04p01.5CMLOS0LWL 4 7/0.53 0.6 1.6 26.7 1295
06p01.5CMLOS0LWL 6 7/0.53 0.6 1.6 28.8 1589
10p01.5CMLOS0LWL 10 7/0.53 0.6 2.0 37.6 2111
15p01.5CMLOS0LWL 15 7/0.53 0.6 2.0 42.6 3034
20p01.5CMLOS0LWL 20 7/0.53 0.6 2.5 48.5 3711
Conductor 2.5 mm2
01p02.5CMLOS0LWL 1 7/0.67 0.6 0.9 14.9 513
02p02.5CMLOS0LWL 2 7/0.67 0.6 1.6 25.2 786
04p02.5CMLOS0LWL 4 7/0.67 0.6 1.6 28.8 1564
06p02.5CMLOS0LWL 6 7/0.67 0.6 1.6 31.8 1955
10p02.5CMLOS0LWL 10 7/0.67 0.6 2.0 40.9 3010
15p02.5CMLOS0LWL 15 7/0.67 0.6 2.5 47.9 3958
20p02.5CMLOS0LWL 20 7/0.67 0.6 2.5 53.1 5289
118 BICC CABLES
Fire Resistance Multi Triple Cables, Armoured, Overall Shielded,LSOH Insulated
Product Code No. of Triples
Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire
Diameter (mm)
Overall Cable Diameter
(mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
01t01.5CMLOS0LWL 1 7/0.53 0.6 0.9 14.6 500
02t01.5CMLOS0LWL 2 7/0.53 0.6 1.6 24.7 943
04t01.5CMLOS0LWL 4 7/0.53 0.6 1.6 26.0 1525
06t01.5CMLOS0LWL 6 7/0.53 0.6 1.6 30.8 1910
10t01.5CMLOS0LWL 10 7/0.53 0.6 2.0 39.7 2921
12t01.5CMLOS0LWL 12 7/0.53 0.6 2.0 41.1 3270
15t01.5CMLOS0LWL 15 7/0.53 0.6 2.5 46.3 3826
Conductor 2.5 mm2
01t02.5CMLOS0LWL 1 7/0.67 0.6 1.25 16.1 569
02t02.5CMLOS0LWL 2 7/0.67 0.6 1.6 26.6 1035
04t02.5CMLOS0LWL 4 7/0.67 0.6 1.6 28.2 1829
06t02.5CMLOS0LWL 6 7/0.67 0.6 2.0 34.3 2329
10t02.5CMLOS0LWL 10 7/0.67 0.6 2.5 44.6 3634
12t02.5CMLOS0LWL 12 7/0.67 0.6 2.5 45.9 4074
15t02.5CMLOS0LWL 15 7/0.67 0.6 2.5 50.7 4800
6.0 Fire Resistance Control & Instrument Cables
119
Fire Resistance Multi Core Cables, Armoured, Overall Shielded,LSOH Insulated
Product Code No. of Cores Strand No. / Diameter (mm)
Insulation Thickness
(mm)
Armour Wire Diameter
(mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02c01.5CMLOS0LWL 2 7/0.53 0.6 0.9 14.1 441
03c01.5CMLOS0LWL 3 7/0.53 0.6 0.9 14.6 506
04c01.5CMLOS0LWL 4 7/0.53 0.6 1.25 16.2 668
05c01.5CMLOS0LWL 5 7/0.53 0.6 1.25 17.7 739
07c01.5CMLOS0LWL 7 7/0.53 0.6 1.25 18.7 893
12c01.5CMLOS0LWL 12 7/0.53 0.6 1.6 23.8 1406
19c01.5CMLOS0LWL 19 7/0.53 0.6 1.6 26.8 1784
24c01.5CMLOS0LWL 24 7/0.53 0.6 1.6 30.6 2148
Conductor 2.5 mm2
02c02.5CMLOS0LWL 2 7/0.67 0.6 0.9 14.9 528
03c02.5CMLOS0LWL 3 7/0.67 0.6 1.25 16.1 688
04c02.5CMLOS0LWL 4 7/0.67 0.6 1.25 17.7 775
05c02.5CMLOS0LWL 5 7/0.67 0.6 1.25 18.7 915
07c02.5CMLOS0LWL 7 7/0.67 0.6 1.25 20.2 1054
12c02.5CMLOS0LWL 12 7/0.67 0.6 1.6 25.6 1699
19c02.5CMLOS0LWL 19 7/0.67 0.6 1.6 28.9 2203
24c02.5CMLOS0LWL 24 7/0.67 0.6 2.0 34.0 2710
120 BICC CABLES
Fire Resistance Multi Pair/Triple Cables, Armoured LSOH Insulated, Individual & Overall Shielding ApplicationThese cables are used as signal carrier for connecting electrical instrument circuits mainly in hazardous areas where safety and circuit integrity are highly required during fire conditions.
Construction
1. ConductorStranded Copper class 2
2. Fire resistance material MICA Glass Tape
3. InsulationLow Smoke Zero Halogen (LSOH)
4. Shielding Individual & Overall Shielding 5. ArmourGalvanized Round Steel Wire (GSWA)
6. SheathLow Smoke Zero Halogen (LSOH)
6.0 Fire Resistance Control & Instrument Cables
121
Fire Resistance Multi Pair Cables, Armoured,Individual & Overall Shielded, LSOH Insulated
Fire Resistance Multi Triple Cables, Armoured,Individual & Overall Shielded, LSOH Insulated
Product Code No. of Pairs
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02p01.5CMLISOSLWL 2 7/0.53 0.6 1.6 24.1 1199
04p01.5CMLISOSLWL 4 7/0.53 0.6 1.6 27.4 1523
06p01.5CMLISOSLWL 6 7/0.53 0.6 1.6 29.4 1923
10p01.5CMLISOSLWL 10 7/0.53 0.6 2.0 38.4 2946
15p01.5CMLISOSLWL 15 7/0.53 0.6 2.5 44.8 3758
20p01.5CMLISOSLWL 20 7/0.53 0.6 2.5 49.6 5050
Conductor 2.5 mm2
02p02.5CMLISOSLWL 2 7/0.67 0.6 1.6 25.6 1376
04p02.5CMLISOSLWL 4 7/0.67 0.6 1.6 29.3 1808
06p02.5CMLISOSLWL 6 7/0.67 0.6 1.6 32.4 2300
10p02.5CMLISOSLWL 10 7/0.67 0.6 2.0 41.7 3705
15p02.5CMLISOSLWL 15 7/0.67 0.6 2.5 48.9 4625
20p02.5CMLISOSLWL 20 7/0.67 0.6 2.5 54.4 6278
Product Code No. of Triples
Strand No. / Diameter
(mm)
Insulation Thickness
(mm)
Armour Wire Diameter (mm)
Overall Cable Diameter (mm)
Approx. Weight of Completed Cable
(kg/km)
Conductor 1.5 mm2
02t01.5CMLISOSLWL 2 7/0.53 0.6 1.6 25.1 1301
04t01.5CMLISOSLWL 4 7/0.53 0.6 1.6 26.5 1715
06t01.5CMLISOSLWL 6 7/0.53 0.6 1.6 31.6 2234
10t01.5CMLISOSLWL 10 7/0.53 0.6 2.0 40.7 3448
12t01.5CMLISOSLWL 12 7/0.53 0.6 2.0 41.9 3776
15t01.5CMLISOSLWL 15 7/0.53 0.6 2.5 47.7 4926
Conductor 2.5 mm2
02t02.5CMLISOSLWL 2 7/0.67 0.6 1.6 27.2 1511
04t02.5CMLISOSLWL 4 7/0.67 0.6 1.6 28.7 2028
06t02.5CMLISOSLWL 6 7/0.67 0.6 2.0 35.1 2610
10t02.5CMLISOSLWL 10 7/0.67 0.6 2.5 45.4 4219
12t02.5CMLISOSLWL 12 7/0.67 0.6 2.5 47.1 4568
15t02.5CMLISOSLWL 15 7/0.67 0.6 2.5 52.0 5343
BICC CABLES
7.0 GLOSSARY
124 BICC CABLES
AAbrasion ResistanceAbility of a material or cable to resist surface wear.A.C. ResistanceThe total resistance offered by a device to alternating current circuit due to inductive and capacitive effects,as well as the direct current resistance.Active currentIn an alternating current, a component in phase with the voltage. The working component as distinguished from the idle or wattles component.Aerial cableA cable suspended in the air on poles or otheroverhead structure.Alternating current (AC)An electric current that continually reverses its direction giving a repetitive plus and minus wave form at fixed intervals.Alternating voltageThe voltage developed across a resistance or impedance through which alternating current is flowing.Ambient temperatureThe romal temperature within a given area.American wire gaugeA standard used in the determination of the physical size of a conductor determined by its circular mil area. Usually expressed as AWG. Also referred to as Brown and Sharpe (B&S) wire gauge.AmpacityThe maximum current an insulated wire or cable can safely carry without exceeding either the insulation or jacket material limitations (Same as current carrying capacity).AmpereThe current unit. One ampere is the current flowing through one ohm of resistance at one volt potential.Anneal To subjectto high heat wit subsequent cooling. When annealing copper, the act of softening the metal by means of heat to render it less brittle expressed in Hertz.Area of conductorThe size of conductor cross-section measured in circular mils, square inches, etc.ArmorA braid or wrapping of metal, usually steel, used for mechanical protection.Armored cableA cable having a metallic covering for protection against mechanical injury.ASTMThe American Society for Testing and MaterialsAWGAbbreviation for American Wire Gauge.
BBare conductorA conductor having no covering.A conductor with no coatingor cladding on the copper.BeddingA layer of material applied to a cable immediatelybelow the armoring.BinderA spirally served tape or thread used for holding assembled cable components in place awaiting subsequent manufacturing operations.BraidA fibrous or metallic group of filaments interwoven in cylindrical form to form a covering over one or more wires.Breakdown of insulationFailure of an insulated conductor resulting a flow of current through the insulation. It may be caused by the application of excess voltage or by defects or decay.Break down voltageThe voltage at which the insulation between two conductors breaks down.Bunched StrandAny number of conductor strands twisted together in one direction with the same lay length.Buried CableA cable installed directly in the ground without use of under ground conduit. Also called "direct burial cable".
CCableA group of individually insulated conductors in twisted or parallel configuration, with or without an overall covering.CablingThe act of twisting together two or more insulated components by machine to form a cable.CapacitanceStorage of electrically separated charges between two plates having different potentials.The value depends on the surface area of the plates and the distance and material between them.The quantity of electricity held statically in a capacitor or an insulated conductor.Colour CodeA colour system for circuit identification by use of solid colours, tracers, braids, surface printing, etc.Composite cableA cable consisting of two or more different types or sizes of wires.
7.0 Glossary
125
ConcentricityIn a wire or cable, the measurement of the location of the center of the conductor with respect to the geometric center of the circular insulation.Concentric StrandingA group of wires twisted so as to contain a center core with one or more distinct layers of spirally wrapped, wires laid overall.ConductanceThe ability of a conductor to carry electric current.It is the reciprocal of resistance and is measured in Mhos.ConductivityA term used in describing the capability of a material to carry an electrical charge. Usually expressed as a percentage of copper conductivity.ConductorAny material capable of transferring electrical charge easily.CoreIn cables, a term used to denote a component or assembly of components, over which other materials are applied, such as additional components, shield, sheath, or armor.Cross-Sectional AreaThe area of the cut surface of an object cut at right angles to the length of the object.CurrentThe rate of flow of electricity in a circuit, measured in amperes.Current Carrying Capacity The maximum current an insulated conductor or cable can continuously carry without exceeding its temperature rating.It is also called ampacity.Direct Current (DC)Electrical current whose electrons flow in one direction only;it may be constant or pulsating as long as their movementis in the same direction.CycleThe complete sequence of alternation or reversal of alternation or reversal of the flow of an alternating electric current.(See Hertz)
Dielectric testA test in which a higher than the rated voltage is applied for a specified time to determine the adequacy of the insulation under normal conditions.Direct capacitanceThe capacitance measured directly from conductor to conductor through a single insulation layer.Direction of LayThe direction, either clockwise or counterclockwise,of a conductor or group of conductors when looking axiallydown a cable length.Drawingin The manufacturing of wire , pulling the metal through a die or series dies for reduction of diameter to a specified size.
DDCAbbreviation for "Direct Current".Dielectric Constant (K)The ratio of the capacitance of a capacitor (or consoles) with dielectric between the electrodes to the capacitance with air is between the electrodes. Also called permittivity and specific inductive capacity.Dielectric StrengthThe voltage which an insulation can withstand before breakdown occurs. Usually expressed as a voltage gradient(such as volts per mil).
EEccentricityLike concentricity, a measure of the center of a conductor's location with respect to the circular cross-section of the insulation; expressed as a percentage of center displacement of one circle within the other.EmbossingA means of identification or lettering using heat and or pressure to leave raised lettering on the sheath material of the cable.ExtrusionThe process of continuously forcing a plastic or elastomer and a conductor core through a die, thereby applying a continuous coating of insulation or jacket to the core or conductor.
FFaradA unit of electrical capacity.Filler(1) A material used in the cable to fill large interstices between
electrical components;(2) A substance, often inert, added to a compound to improve
properties and / or decrease cost.Flame ResistanceAbility of the material to extinguish flame once the source of heat is removed.Flexible CableA cable containing one or more cores, each formed of a group of wires, the diameters of the wires being sufficiently small to afford flexibility.FlexibilityThe ease with which a cable may be bent.FrequencyNumber of times an alternating current reverses itself in one second. Expressed in Hertz (Hz), which is one cycle per second.
126 BICC CABLES
JJacketA material covering over a wire insulation or an assembly of components. An overall jacket on a complex cable grouping is also often referred to as a sheath
KKilohertz1000 Hertz (cycles per second}.KilovoltA term denoting 1000 volts.KilowattA term denoting 1000 watts.
HHarnessAn arrangement of wires and cables, usually with many breakouts, which have been tied together or pulled into a rubber or plastic sheath, used to interconnect electric circuit.Heat ResistanceAbility of a substance to maintain physical chemical and electrical integrity under specified temperature conditions.HenryUnit of inductance such that the induced voltage in volts is numerically equal to the rate of change of current inamperes per second.Hertz (Hz)A term replacing cycles-per seconds as a unit of frequency.High Temperature wire and cableThose electrical wires and cables having thermal operating characteristics of 125°C and higher.HzAbbreviation for Hertz.
IICEAAn Insulated Cable Engineers Association (formerly IPCEA) IECInternational Electro technical Commission, Similar to the ISO in structure and scope.IEEEInstitute of Electrical and Electronic Engineers.impedanceThe total opposition that a circuit offers to the flow of alternating current or any other varying current at a particular frequency. It is a combination of resistance R and reactance X,measured in ohms.impulse (Or pulse}A surge of unidirectional polarity.induced CurrentAn electric current set up in a circuit by interacting electrical fields. A Current caused by electromagnetic induction.inductanceThe property of a circuit element that opposes a change in current flow, thus causing current change to lag behind voltage changes. It is measured in Henrys.inductionThe phenomenon of a voltage, magnetic field or electrostatic charge being produced in an object by lines of force from the source of such fields.
GGaugeA term used to denote physical size.
LLay DirectionThe direction in which the strands of a conductor run over the top of the conductor as they recede from and observer looking along the axis of the conductor.Leakage CurrentThe undesirable flow of current through or over the surface of insulation.
MMega ohmOne million ohms.MhoThe unit of conductivity. The reciprocal of an ohm.
Inductive couplingCrosstalk resulting from the action of the electromagnetic field of one conductor on the other.insulationA non-conductive material usually surrounding or separating two conductive materials. Often called the dielectric in a radio frequency cable.insulation ResistanceThat property of an insulating material which resists electrical current flow through the insulating material when a potential difference is applied.Insulation ThicknessThe wall thickness of the applied insulation.InterferenceAny undesired electrical signal induced into a conductor by electrical or electromagnetic means (Noise).ISOInternational Standards Organization.
7.0 Glossary
127
OOhmUnit of resistance such that a constant current of one Ampere produces a force of one volt.Overall DiameterFinished diameter over wire or cable.Over CurrentThe Current which causes an excessive temperature risein a conductor.Overload Capacity The maximum level of current, voltage, or power which a device can withstand before it is damaged.
RRated TemperatureThe maximum temperature at which an electric component can operate for extended periods without loss of its operating properties.Rated VoltageThe maximum voltage at which an electric component can operate for extended periods without degradation of performance or safety hazard.ReactanceThe opposition offered to the flow of alternating current by the inductance or capacitance of a component or circuit.ResistanceIn D.C. circuits, the opposition a material offers to current, measured in ohms. In A.C. Circuits, resistance is the real component of impedance, and may be higher than the value measured at D.C.Round ConductorA conductor whose cross-section is substantially circular.
QQuadA four- wire unit of insulated conductors.
PPolyesterPolyethylene terephthalate which is used extensively in the production of a high strength moisture resistant film used as cable core wrapping material.PolyethyleneA family of insulating materials derived from polymerization of ethylene gas. They are basically pure hydrocarbon resins, with excellent dielectric properties.Polyvinly chloride (PVC).A thermoplastic material composed of polymers of vinyl chloride which may be rigid or elastomeric, depending on specific formulation.Power FactorThe ratio of resistance to impedance. The ratio of the actual power of an alternating current to apparent power. Mathematically, the cosine of the angle between the voltage applied and the current resulting.Propagation timeTime required for an electrical wave to travel between two points on a transmission line.
MhzMegahertz (one million cycles per second).Moisture ResistanceThe ability of a material to resist absorbing moisture from the air or when immersed in water.Multi-ConductorMore than one conductor within a single cable.Mutual inductanceThe ratio of voltage induced in one conductor to the time rate of current change in the separate conductor causing this induction.MylarDuPont trademark for polyethylene terephthalate (polyester) film used in the form of a tape.
PulseA current or voltage which changes abruptly from one value to another and back to the original value in a finite length of time.Pulse CableA type of coaxial cable constructed to transmit repeated high voltage pulses without degradation.
SSheathThe material, usually an extruded plastic or elastomer, applied outer most to a wire or cable. Very often referred to as a jacket.ShieldA metallic layer around an insulated conductor or group of conductors to prevent electrostatic or electromagnetic interference between the enclosed wires and external fields. This shield can be braided or served wires, foil wrap, foil backed tape, a metallic tube, or conductors. the
shielding effectiveness is in proportion to the amount of coverage,
usually expressed in percentage.
Shield CoverageThe physical area of a cable that is actually covered by the shielding material and is expressed in percentage.SignalCurrent used to convey information, either digital, analogue, audio or video.
128 BICC CABLES
VVelocity of PropagationThe speed of an electric signal down a length of cable compared to speed in free space expressed as a percentage. It is the reciprocal of the square root of the dielectric constant of the cable insulation.
TTemperature RatingThe maximum temperature at which insulating material may be used in continuous operation without loss of its basic properties.Tensile strengthA term denoting the greatest longitudinal tensile stressa substance can bear without mechanical failure.Thermal RatingThe maximum and / or minimum temperature at which a material will perform its functions without undue degration .Thermal ShockA test to determine the ability of a material to withstand heat and cold by subjecting it to rapid and wide change in temperature.Tinned CopperTin coating over copper to aid in soldering and inhibit corrosion.Tinned wireCopper wire that has been coated with a layer of tin or solder to simplify soldering.
WWattA unit of electrical power. One watt is equivalent to the power generated by one ampere of current under a pressure of one volt in a D.C. circuit.
Single cableA cable designed to carry current of usually less than one ampere per conductor.Solid ConductorA conductor consisting of a single wire.Spark TestA test designed to locate imperfections (usually pin- holes) in a wire insulation by application of an electrical potential across the material for a short period of time while the wire is drawn through an electrode field with one end of the wire grounded.Stranded conductorA conductor composed of individual groups of wires twisted together to form an entire unit.Strand Lay lengthA distance of advance of a strand of a spirally stranded conductor, in one turn, measured axially.
Volt (potential difference}A unit of electrical pressure. One volt is the amount of pressure that will cause one ampere of current in one ohm of resistance.VoltageThe term most often used in place of electromotive force, potential, potential difference, or voltage drop, to designate electric pressure that exists between two points and is capable of producing a flow of current when a circuit is connected between the two points.Voltage DropThe amount of voltage loss between two power in a circuit.Voltage RatingThe highest voltage that may be continuously applied to a wire or cord in conformance with standards or specifications.Volume ReceptivityThe electrical resistance between opposite face of a 1 cm cube of insulating material commonly expressed in ohms/ centimeter.
7.0 Glossary
129
WE WILL INVADE THE WORLD
BICC CABLES
Connecting The Future