BID 2022-B0013 BIC 1463 Speech Class room Update pre-bid location map
October 6, 2021 11:00 a.m. Site Visit
Park in Fawell B lot, enter BIC at fountain entrance, Door 3 before proceeding to BIC 1463
THIS RENOVATION TO CLASSROOM 1463 IN THE BERG INSTRUCTIONAL CENTER WILL CREATE A PROTOTYPE SPEECH LAB THAT ENHANCES TEACHING AND LEARNING THROUGH THE IMPLEMENTATION OF NEW AV SYSTEMS AND A MORE COLLABORATIVE CLASSROOM LAYOUT.
THE FOLLOWING PROJECT GENERAL NOTES APPLY TO THE ENTIRE DRAWING SET AND ARE NOT SPECIFIC TO ANY ONE DISCIPLINE, UNLESS OTHERWISE NOTED:
A. THE DRAWING SET AND SPECIFICATIONS (PROJECT MANUAL) ARE COMPLEMENTARY AND ESTABLISH DETAILED MINIMUM REQUIREMENTS FOR THE DESIGN AND CONSTRUCTION OF THE PROJECT.
B. THE DRAWING SET CONSISTS OF ALL SHEETS LISTED BY THE SHEET INDEX. THE WORK DESCRIBED BY THE DRAWINGS OF ANY ONE DISCIPLINE MAY BE AFFECTED BY THE WORK DESCRIBED ON DRAWINGS OF ANOTHER DISCIPLINE AND MAY REQUIRE REFERENCE TO DRAWINGS OF ANOTHER DISCIPLINE. PARTIAL DRAWING SETS ARE INCOMPLETE. DO NOT DISTRIBUTE OR UTILIZE PARTIAL DRAWINGS SETS. PARTIAL SETS OF DRAWINGS ARE INCOMPLETE. DO NOT DISTRIBUTE OR UTILIZE PARTIAL SETS OF DRAWINGS.
C. COLUMN GRID LINES IDENTIFIED BY A LETTER DESIGNATION ARE PARALLEL, UNLESS OTHERWISE NOTED. COLUMN GRID LINES IDENTIFIED BY A NUMBER DESIGNATION ARE PARALLEL AND ARE PERPENDICULAR TO THOSE WITH LETTER DESIGNATIONS, UNLESS OTHERWISE NOTED.
D. DISCIPLINE GENERAL NOTES, SYMBOLS AND DEFINITIONS APPLICABLE TO EACH DISCIPLINE'S DRAWINGS MAY BE FOUND AT THE FRONT OF EACH DISCIPLINE'S PORTION OF THE DRAWING SET AND ARE LISTED IN THE SHEET INDEX.
E. UNLESS INDICATED OTHERWISE, THE 'ARCHITECTURAL' SERIES DRAWINGS TAKE PRECEDENCE FOR THE FINISHED APPEARANCE AND LOCATION OF ALL EXPOSED ELEMENTS OF THE WORK OF ALL TRADES, INCLUDING THAT WORK WHICH IS ILLUSTRATED PRIMARILY ON DRAWINGS OF OTHER DISCIPLINES.
F. THE DRAWINGS MAY MAKE REFERENCE TO OR ILLUSTRATE ITEMS WHICH ARE NOT PART OF THE WORK OF THE CONTRACT. THESE "NOT IN CONTRACT" ITEMS AS INDICATED ARE REFERENCED OR ILLUSTRATED FOR THE CONTRACTOR'S REFERENCE, INFORMATION AND COORDINATION ONLY.
G. EXISTING CONDITIONS, IF SHOWN, ARE FROM AVAILABLE RECORD DRAWINGS AND/OR VISUAL FIELD SURVEYS. THE CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT THE SITE PRIOR TO SUBMITTING A BID, AND NOTIFY THE ARCHITECT, IN WRITING AND PRIOR TO SUBMITTING A BID, OF ANY DISCREPANCIES.SUCH REPAIRS OR REPLACEMENTS..
H. ALL PARTS OF THE WORK, INCLUDING BUT NOT LIMITED TO MATERIALS, METHODS, OR ASSEMBLIES, MUST COMPLY WITH THE REQUIREMENTS OF THE GOVERNING CODES AND REGULATIONS OF ALL FEDERAL, STATE AND LOCAL AUTHORITIES HAVING JURISDICTION OVER THE PROJECT, AS WELL AS THOSE GREATER REQUIREMENTS INDICATED BY THE CONTRACT DOCUMENTS. NO PART OF THE CONTRACT DOCUMENTS MAY BE CONSTRUED TO REQUIRE OR ALLOW WORK CONTRARY TO A GOVERNING CODE OR REGULATION.
I. IDENTIFY AND NOTIFY THE ARCHITECT OF CONFLICTS BETWEEN THE WORK OF DIFFERENT PARTIES AT THE EARLIEST POSSIBLE DATE SO AS TO ALLOW REASONABLE AND ADEQUATE TIME FOR THE CONFLICT TO BE RESOLVED WITHOUT DELAYING THE WORK. ALL DEVIATIONS FROM THE CONTRACT DOCUMENTS MUST BE APPROVED IN ADVANCE BY THE ARCHITECT AND OWNER.
J. REVIEW AND COORDINATE THE WORK OF ALL SUB-CONTRACTORS, DELEGATED DESIGN ENTITIES, TRADES AND SUPPLIERS WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS BEFORE COMMENCING CONSTRUCTION, AND ASSURE THAT ALL PARTIES ARE AWARE OF ALL REQUIREMENTS, REGARDLESS OF WHERE THE REQUIREMENTS OCCUR IN THE CONTRACT DOCUMENTS, WHICH MIGHT AFFECT THE WORK OF THAT PARTY.
Plot
Date:
ISSUE DATE:
COLLEGE OF DUPAGE425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
VOLUME I OF IISSUED FOR:BID
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
9/13/2
021 1
1:32:2
1 AM
College of DuPage - Speech Classroom Update - Prototype 2
09.13.2021
College of DuPage
13340.000
SHEET LIST
SHEET NUMBER SHEET NAME OWNE
R RE
VIEW
08.0
2.202
1BI
D 09
.13.20
21GENERALG0.0 PROJECT COVER SHEET X XG2.1.1 BUILDING CODE SUMMARY & BASIC ACCESSIBILITY REQUIREMENTS X X
ARCHITECTURALA0.1 ARCHITECTURAL ABBREVIATIONS AND SYMBOLS X XA0.4 TYPICAL RULES FOR DETERMINING MOUNTING HEIGHTS AND LOCATIONS AND DIMENSIONING CONVENTIONS X XA2.1.1AD LEVEL 01 - ROOM 1463 - DEMOLITION PLANS X XA2.1.1 LEVEL 01 - ROOM 1463 - FLOOR PLAN AND REFLECTED CEILING PLAN X XA8.1.1 INTERIOR ELEVATIONS X XA9.1.1 INTERIOR DETAILS XAI2.1.1 LEVEL 01 - ROOM 1463 - FURNITURE CONFIGURATION PLANS X
ELECTRICALE0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONS X XE2.1.2 LEVEL 01 - ROOM 1463 - ELECTRICAL PLANS X X
TECHNOLOGY & AVTA0.00 LEVEL 01 - ROOM 1463 - AV SYSTEM COVER SHEET GENERAL NOTES SCHEDULES XTA0.01 LEVEL 01 - ROOM 1463 - AV SYSTEM ELEVATIONS XTA0.02 LEVEL 01 - ROOM 1463 - AV SYSTEM ELEVATIONS XTA0.03 LEVEL 01 - ROOM 1463 - AV SYSTEM CONDUIT RISER XTA0.04 LEVEL 01 - ROOM 1463 - AV SYSTEM CONCEPTUAL VIDEO FLOW XTA0.05 LEVEL 01 - ROOM 1463 - AV SYSTEM CONCEPTUAL AUDIO & CONTROL FLOW XTA1.01 LEVEL 01 - ROOM 1463 - AV SYSTEM FLOOR PLANS AND REFLECTED CEILING PLANS X
OWNER / CLIENT:COLLEGE OF DUPAGE425 W. Fawell Blvd.Glen Ellyn, Illinois 60137T: (630) 942-2800WEBSITE: www.cod.edu
ARCHITECT:SMITHGROUP35 EAST WACKER, SUITE 900CHICAGO, IL, 60601T: (312) 641-0770F:WEBSITE: SMITHGROUP.COM
ELECTRICAL ENGINEER:SMITHGROUP35 EAST WACKER, SUITE 900CHICAGO, IL, 60601T: (312) 641-0770F:WEBSITE: SMITHGROUP.COM
PROJECT TEAM
PROJECT DESCRIPTIONPROJECT GENERAL NOTES
BIC - ROOM 1463 LOCATION DIAGRAM
PROJECT SHEET INDEX
ROOM 1463
NORTH
LOCATION MAP - BERG INSTRUCTIONAL CENTERPROJECT NORTH
LEVEL 01
AUDIOVISUAL ENGINEER:AXENT AV4020 GRAND AVE.WESTERN SPRING, IL 60558T: (708) 505-9886F:WEBSITE: WWW.AXENT-AV.COM
Figure 304.3.1Circular Turning Space
Figure 304.3.2T-Shaped Turning Space
Figure 305.3Clear Floor or Ground Space
Figure 305.5Position of Clear Floor or Ground Space
Figure 305.7.1Maneuvering Clearance in an
Alcove, Forward Approach
Figure 305.7.2Maneuvering Clearance in an
Alcove, Parallel Approach
Figure 306.2Toe Clearance
Figure 306.3Knee Clearance
Figure 308.3.1Unobstructed Side
Reach
Figure 308.3.2Unobstructed High Side
Reach
Figure 308.2.2Obstructed High Forward Reach
Figure 308.2.1Unobstructed Forward Reach
Figure 307.2Limits of Protruding Objects
Figure 404.2.4.1Maneuvering Clearance at Manual Swinging Doors and Gates
ACCE
SSIB
LE R
OUTE
SBU
ILDIN
G BL
OCKS
60 min1525
60 min1525
60 m
in15
2536 m
in91
5
36 min915 12 min
30512 min
305
24 min610
arm
arm
base
48 min1220
30 m
in76
0
48 m
in12
20
30 min760
30 m
in76
0
48 min1220
36 min915
60 min1525
X > 2
461
0
X > 1
538
0
6 max150
9230
17-25430-635
30 m
in76
0
11 min280
9 min230
8 min205
27 m
in68
5 30 m
in76
0
25 max635
(b)plan
(a)elevation
(b)plan
(a)elevation
48 m
ax12
20
15 m
in38
0
10 max255
>10 - 24 max255 - 610
46 m
ax11
70
34 m
ax86
548 m
ax12
20
10 max255
34 m
ax86
5
44 m
ax11
20
> 20 - 25 max510 - 635
20 max510
48 m
ax12
20
(a) (b)(b)(a)
48 m
ax12
20
15 m
in38
0
X ≥
8020
30
4 max100
X > 2
768
5
60 m
in15
2554
min
1370
48 m
in12
20
60 m
in15
25
18 min445
12 min*305
36 min915
42 min1065
42 m
in*
1065
(e)hinge approach, pull side
(j)latch approach, push side
(k)latch approach, push side
*48 min if door provided with closer
(i)latch approach, pull side
*54 min if door provided with closer
(h)latch approach, pull side
(f)hinge approach, push side
(g)hinge approach, push side
*if door provided with both closer and latch** 48 min if both closer and latch provided
(b)front approach, push side
(c)front approach, push side
*if door provided with both closer and latch
(a)front approach, pull side
(d)hinge approach, pull side
24 min610
22 min560
12 min*305
42 m
in**
1065
48 m
in*
1220
24 min610
(a)forward
(b)parallel
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FOR CONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage – Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/13/2
021 1
1:32:2
3 AM
BUILDING CODESUMMARY & BASIC
ACCESSIBILITYREQUIREMENTS
G2.1.1
STAR
T Sh
eet
13340.000
INTERNATIONAL BUILDING CODES
(IBC) INTERNATIONAL BUILDING CODE 2009(IEBC) INTERNATIONAL REHABILITATION CODE 2009(IECC) INTERNATIONAL ENERGY CONSERVATION CODE 2018(IFC) INTERNATIONAL FIRE CODE 2009(IMC) INTERNATIONAL MECHANICAL CODE 2009(ISPC) ILLINOIS STATE PLUMBING CODE 2014
NATIONAL FIRE PROTECTION ASSOCIATION
NFPA 10 STANDARD FOR PORTABLE FIREEXTINGUISHERS
2009
NFPA 13 INSTALLATION OF SPRINKLER SYSTEMS 2009NFPA 14 STANDARD FOR THE INSTALLATION OF
STANDPIPE AND HOSE SYSTEMS2009
NFPA 70 NATIONAL ELECTRICAL CODE 2011NFPA 72 NATIONAL FIRE ALARM AND SIGNALING
CODE2009
NFPA 101 LIFE SAFETY CODE 2009ACCESSIBILITY GUIDELINES
ADA ADA STANDARDS FOR ACCESSIBLE DESIGNBY THE U.S. DEPARTMENT OF JUSTICE
2010
IAC ILLINOIS ACCESSIBILITY CODE 2018ICC/ANSI117.1
ACCESSIBLE AND USABLE BUILDINGS ANDFACILITIES
2003
CODES / STANDARDSAPPLICABLE CODES/CRITERIA/DESIGN POLICY:AUTHORITY HAVING JURISDICTION:Village of Glen Ellyn
AREA OF WORKROOM 1463 AREA = 635 SFOCCUPANCY = BUSINESS (CLASSROOM UNDER 50 SEATS)NO CHANGE TO OCCUPANCY OR EXISTING BUILDING AREAINTERIOR RENOVATION OF CLASSROOM ONLY
A. THE INFORMATION ON THIS SHEET REPRESENTS THEFIGURES FROM THE UNITED STATES ACCESS BOARD(PUBLISHED JULY 23, 2004 AND AMENDED AUGUST 5,2005) WHICH DEVELOPS THE GUIDELINES FOR THEARCHITECTURAL BARRIERS ACT (ABA) AND THEAMERICANS WITH DISABILITIES ACT (ADA). THEGUIDELINES REPRESENT THE BASIS OF THEARCHITECTURAL BARRIERS ACT ACCESSIBILITYSTANDARDS (ABAAS) AND THE ADA STANDARDS FORACCESSIBLE DESIGN (ADA STANDARDS),RESPECTIVELY. THE FIGURES ARE REPRESENTEDHERE FOR REFERENCE PURPOSES ONLY.
B. LOCAL JURISDICTIONS MAY REFERENCEPUBLICATIONS OTHER THAN THOSE REFERENCEDABOVE AND SHOULD BE CONSULTED IF THE LOCALGUIDELINES DIFFER FROM THOSE SHOWNHEREWITH.
C. THE REQUIREMENTS SHOWN ARE SOME, BUT NOTALL OF THE REQUIREMENTS OF THE RESPECTIVEACCESSIBILITY GUIDELINES. IT IS NOT THE INTENT OFTHIS SHEET TO PORTRAY ALL THE REQUIREMENTSOF THE RESPECTIVE GUIDELINES.
D. IN THE EVENT OF A CONFLICT OR OMISSIONBETWEEN THE ARCHITECTS OR ENGINEERSDRAWINGS AND THE ABAAS/ADA STANDARDSREQUIREMENTS, THE LATEST ADOPTED EDITIONS OFTHE PUBLISHED ABAAS/ADA STANDARDS WILL TAKEPRIORITY.
E. EACH AND EVERY ONE OF THE SITUATIONS SHOWNON THIS SHEET MAY NOT OCCUR ON THIS PROJECT.
ACCESSIBILITY REQUIREMENTS
ROOM 1463
NORTHLEVEL 01
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
AB
AANCHOR BOLT
ACT ACOUSTICAL CEILING TILEACP
AD
ACOUSTICAL CEILING PANEL
AREA DRAINADDL ADDITIONALADH
ADDITIONAL
ADJADHESIVE
ADJADJUSTABLE
AFFADJACENT
AFGABOVE FINISH FLOOR
AFSABOVE FINISH GRADE
AGGRABOVE FINISH SLAB
ALUMAGGREGATE
ALTALUMINUM
ANODALTERNATE
APPROXANODIZED
ARCHAPPROXIMATE(LY)
ACS PNL ACCESS PANEL
ARCHITECT(URAL)ASPH ASPHALTAVG AVERAGE
BB
BBULLETIN BOARD
BD BOARDBTWN
BLDG
BETWEEN
BUILDINGBM
BOT
BENCHMARK
BOTTOM
BITUM BITUMINOUS
BOS BOTTOM OF STEELBRG BEARINGBSMT BASEMENT
CAB
CCABINET
CB CATCH BASIN
CCT
CG
CUBICLE CURTAIN TRACK
CORNER GUARDCEMCER
CEMENT, CEMENTITIOUSCERAMIC
CCTV CLOSED CIRCUIT TELEVISION
CH BD CHALKBOARDCI CAST IRONCJ CONTROL JOINTCLCLGCLRCMUCNTRCOLCONCCONFCONNCONSTRCONTCONTRCORRCPTCSKCSPCSWK
CUCW
CENTER LINECEILINGCLEARCONCRETE MASONRY UNITCOUNTERCOLUMNCONCRETECONFERENCECONNECTIONCONSTRUCTIONCONTINUOUSCONTRACTORCORRUGATEDCARPETCOUNTERSUNKCOMBINATION STANDPIPECASEWORK
CUBICCOLD WATER
D
DDEPTH
DBL DOUBLEDBL ACT DOUBLE ACTINGDEG DEGREEDEMO DEMOLISHDEPT DEPARTMENTDET DETAILDF DRINKING FOUNTAINDIA DIAMETERDIAG DIAGONALDIFF DIFFUSERDIM DIMENSIONDIM PT DIMENSION POINTDISP DISPENSERDIST DISTANCEDN DOWNDR DRAINDS DOWNSPOUTDSP DRY STANDPIPEDT DRAPERY TRACKDWG DRAWINGDWGS DRAWINGS
(E)
EEXISTING
EA EACHEDR EQUIPMENT DRAWINGEG EDGE GUARDEIFS EXTERIOR INSULATION FINISH SYSTEMEL ELEVATIONELAST ELASTOMERICELEC ELECTRICALELEV ELEVATOREMER EMERGENCYENCL ENCLOSUREENGR ENGINEEREOS EDGE OF SLABEP ELECTRICAL PANELEPB ELECTRICAL PANEL BOARDEPDM ETHYLENE PROPYLENE DIENE MONOMEREQ EQUALEQL SP EQUALLY SPACEDEQUIP EQUIPMENTEQUIV EQUIVALENTESCAL ESCALATOREST ESTIMATE(D)EWC ELECTRIC WATER COOLEREXC EXCAVATEDEXH EXHAUSTEXP EXPANSIONEXP JT EXPANSION JOINTEXT EXTERIOR
F/F
FFACE TO FACE
FA FIRE ALARMFAS FIRE ALARM STATIONFB FLAT BARFCU FAN COIL UNITFD FLOOR DRAINFDC FIRE DEPARTMENT CONNECTIONFDN FOUNDATIONFEC FIRE EXTINGUISHER CABINETFE FIRE EXTINGUISHERFF FINISH FACEFHC FIRE HOSE CABINETFH/FEC FIRE HOSE / FIRE EXTINGUISHER CABINETFHMS FLAT HEAD MACHINE SCREWFHWS FLAT HEAD WOOD SCREWFHY FIRE HYDRANTFLAM FLAMMABLEFLASH FLASHINGFLEX FLEXIBLEFLUOR FLUORESCENTFO FACE OFFSB FOLDING SHOWER BENCHFSTNR FASTENERFT FOOT, FEETFTG FOOTINGFURN FURNITUREFXTR FIXTURE
G
GGAS
H
HHIGH
GA GAUGE, GAGEGAL GALLONGALV GALVANIZEDGB GRAB BARGC GENERAL CONTRACTORGFRC GLASS FIBER REINFORCED CONCRETEGFRG GLASS FIBER REINFORCED GYPSUMGL GLASSGLU LAM GLUE LAMINATEDGLZ GLAZINGGR GRADE OR GRADINGGVL GRAVELGYP GYPSUMGYP BD GYPSUM BOARDGYP PLAS GYPSUM PLASTER
ID
IINSIDE DIAMETER
JAN
JJANITOR
KG
KKILOGRAM
L
LLENGTH, LONG
M
MMETERS
(N)
NNEW
OC
OON CENTER
PA
PPUBLIC ADDRESS
QT
QQUARRY TILE
R
RRISER
S SOUTH
T
TTREAD
VAC
VVACUUM
W
WWEST
XFMR
XTRANSFORMER
YD
YYARD
HB HOSE BIBBHC HOLLOW COREHD HEADHDBD HARDBOARDHDW HARDWAREHDWD HARDWOODHGT HEIGHTHM HOLLOW METALHNDRL HANDRAILHORIZ HORIZONTALHPT HIGH POINTHR HOURHVAC HEATING-VENTILATION-AIR CONDITIONING
IN INCHINCAND INCANDESCENTINCL INCLUDE, INCLUDINGINFO INFORMATIONINSUL INSULATIONINTR INTERIORINV INVERTIVT INTRAVENOUS TRACK
JST JOISTJT JOINT
KIT KITCHENKPL KICK PLATEKS KNEE SPACE
LAB LABORATORYLAM LAMINATE, LAMINATIONLAV LAVATORYLB POUNDLED LIGHT EMITTING DIODELF LINEAR FOOTLG LENGTHLIN LINEARLL LEAD LINEDLPT LOW POINTLT LIGHTLT WT LIGHT WEIGHTLTG LIGHTINGLVR LOUVER
HW HOT WATER S
MACH MACHINEMATL MATERIALMATV MASTER ANTENNA TELEVISION SYSTEMMAX MAXIMUMMB MACHINE BOLTMC MEDICINE CABINETMDO MEDIUM DENSITY OVERLAYMECH MECHANICALMED MEDIUMMEMB MEMBRANEMFR MANUFACTURERMH MANHOLEMIN MINIMUMMISC MISCELLANEOUSMLDG MOLDINGMM MILLIMETERSMO MASONRY OPENINGMOD MODULE, MODULARMTD MOUNTEDMTG MOUNTINGMVBL MOVABLEMULL MULLION
NA NOT APPLICABLENAT NATURALNE NORTHEASTNIC NOT IN CONTRACTNO NUMBERNOM NOMINALNRC NOICE REDUCTION COEFFICIENTNTS NOT TO SCALENW NORTHWEST
OA OVERALLOD OUTSIDE DIAMETEROFCI OWNER FURNISHED-CONTRACTOR INSTALLEDOFOI OWNER FURNISHED-OWNER INSTALLEDOPP OPPOSITEORD OVERFLOW ROOF DRAINOVHD OVERHEADOZ OUNCE
PART PARTIALPBD PARTICLEBOARDPBX PRIVATE TELEPHONE EXCHANGEPCF POUNDS PER CUBIC FOOTPCI POUNDS PER CUBIC INCHPERF PERFORATEDPERIM PERIMETERPERM PERMANENTPERP PERPENDICULARPI POINT OF INTERSECTIONPL PLATEPLAM PLASTIC LAMINATEPLAS PLASTERPLBG PLUMBINGPLF POUNDS PER LINEAR FOOTPLYWD PLYWOODPNEU PNEUMATICPNL PANELPNL BD PANEL BOARDPNT PAINTPORT PORTABLEPP PUSH PLATEPPM PARTS PER MILLIONPR PAIRPRCST PRECASTPREP PREPARATIONPREFAB PREFABRICATIONPRKG PARKINGPROJ PROJECTPROP PROPERTYPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPT POINTPTN PARTITIONPTS PNEUMATIC TUBE STATIONPVC POLYVINYL CHLORIDEPVG PAVINGPVMT PAVEMENTPWR POWER
QTR QUARTERQTY QUANTITY
RA RETURN AIRRAD RADIUSRB RESILIENT BASERCP REFLECTED CEILING PLANRCPT RECEPTACLERD ROOF DRAINRECT RECTANGULARREF REFERENCEREFR REFRIGERATORREG REGISTERREINF REINFORCE (D) (ING) (MENT)REQD REQUIREDREQT REQUIREMENTRESIL RESILIENTRET RETURNREV REVISIONRF RESILIENT FLOORINGRH RIGHT HANDRHMS ROUND HEAD MACHINE SCREWRHWS ROUND HEAD WOOD SCREWRM ROOMRND ROUNDRO ROUGH OPENINGROW RIGHT OF WAYRWL RAIN WATER LEADER
SA SUPPLY AIRSB SPLASH BLOCKSC SOLID CORESCHED SCHEDULESCRN SCREENSD STORM DRAINSE SOUTHEASTSECT SECTIONSEG SEGMENTSEP SEPARATION OR SEPARATESEP JT SEPARATION JOINTSHT SHEET, SHEETINGSHWR SHOWERSHV SHELVES, SHELVINGSIM SIMILARSK SINKSMS SHEET METAL SCREWSP SPACE, SPACED, SPACINGSPEC SPECIFICATIONSPKLR SPRINKLERSPKR SPEAKERSQ SQUARESS SANITARY SEWERSSK SERVICE SINKSST STAINLESS STEELST STREETSTA STATIONSTAG STAGGEREDSTC SOUND TRANSMISSION COEFFICIENTSTD STANDARDSTL STEELSTOR STORAGESTRUCT STRUCTURALSTS SELF-TAPPING STEELSUSP SUSPENDEDSUSP CLG SUSPENDED CEILINGSVCE SERVICESW SOUTHWESTSYMM SYMMETRICALSYST SYSTEM
T&B TOP AND BOTTOMT&G TONGUE AND GROOVETC TOP OF CONCRETE, TOP OF CURBTD TRENCH DRAINTEL TELEPHONETEMP TEMPORARYTHERM THERMALTHK THICK, THICKNESSTHRES THRESHOLDTHRU THROUGHTMPD GL TEMPERED GLASSTO TOP OFTOR TOP OF RAILINGTOS TOP OF STEELTOT TOTALTOW TOP OF WALLTP TOP OF PAVEMENTTTB TELEPHONE TERMINAL BOARDTV TELEVISION
UC
UUNDER COUNTER
TYP TYPICAL
UL UNDERWRITERS LABORATORIESUON UNLESS OTHERWISE NOTEDUPS UNINTERRUPTABLE POWER SUPPLYUTIL UTILITY
VB VALVE BOXVCT VINYL COMPOSITION TILEVERT VERTICALVEST VESTIBULE
VIT VITREOUSVP VENT PIPEVOL VOLUMEVWC VINYL WALL COVERING
W/ WITHW/O WITHOUTW/W WALL TO WALLWC WATER CLOSET OR WALL COVERINGWD WOODWDW WINDOWWGL WIRE GLASSWCHR WHEELCHAIRWM WIRE MESHWO WHERE OCCURSWPT WORKING POINTWR WATER RESISTANTWSCT WAINSCOTWSP WET STANDPIPEWT WEIGHTWTHPRF WEATHERPROOFWTRPRF WATERPROOFWWF WELDED WIRE FABRICWWM WELDED WIRE MESH
CCR CARD CONTROL READER
BUR BUILT UP ROOFING SYSTEM
CT CERAMIC TILE
BOD BASIS OF DESIGN
VIF VERIFY IN FIELD
THE FOLLOWING GENERAL NOTES APPLY TO ALL ARCHITECTURAL SERIES SHEETS. FOR GENERAL NOTES APPLICABLE TO ALL SHEETS REFER TO THE "PROJECT GENERAL NOTES":
A. THE ARCHITECTURAL SERIES SHEETS ARE PART OF A COMPLETE SET OF CONSTRUCTION DOCUMENTS DESCRIBING THE WORK FOR THIS PROJECT. USERS OF THESE DOCUMENTS ARE RESPONSIBLE TO REVIEW ALL CONSTRUCTION DOCUMENTS TO UNDERSTAND AND COORDINATE THE GRAPHIC AND ANNOTATED INFORMATION PROVIDED IN THESE ARCHITECTURAL SERIES SHEETS.
B. EXCEPT WHERE DIRECTED TO PLACE ITEMS OF WORK AT THE APPROXIMATE LOCATIONS SHOWN, DO NOT SCALE DRAWINGS FOR DIMENSIONAL INFORMATION. ALL ELEMENTS OF THE DRAWINGS MAY NOT BE DRAWN TO EXACT SCALE. ALL DIMENSIONS REQUIRED ARE SHOWN OR MAY BE DERIVED FROM THOSE SHOWN ON THE FLOOR PLANS, DETAIL PLANS, ELEVATIONS, SECTIONS, DETAILS, SCHEDULES, AND SPECIFICATIONS.
C. ALL VISUALLY EXPOSED STRUCTURAL, MECHANICAL AND ELECTRICAL ELEMENTS, INCLUDING EXPOSED METAL FLOOR AND ROOF DECK, ARE TO BE PAINTED UNLESS OTHERWISE NOTED. THIS INCLUDES ELEMENTS THAT MAY BE VISIBLE THROUGH GRILLES, LOUVERS OR CEILINGS. COLORS AND PAINT MATERIALS ARE DEFINED IN THE FINISH SCHEDULE, THE SPECIFICATIONS, AND THE DRAWINGS AS APPLICABLE TO THE CONSTRUCTION DOCUMENTS.
A. THE PURPOSE OF THIS SHEET IS TO ILLUSTRATE AND DEFINE TYPICAL GRAPHIC SYMBOLS WHICH MAY TYPICALLY OCCUR ON THE ARCHITECTURAL DRAWINGS.
B. ADDITIONAL SYMBOLS NOT SHOWN OR DEFINED ON THIS SHEET MAY BE USED ON THE ARCHITECTURAL DRAWINGS AND ARE TYPICALLY DEFINED ON OTHER SHEETS.
C. SYMBOLS ARE NOT DRAWN TO SCALE. TO DETERMINE THE ACTUAL SIZES OF ELEMENTS REPRESENTED BY SYMBOLS, REFER TO THE SPECIFICATIONS AND OTHER SHEETS, AS MAY APPLY.
A. THE TERM "REFERENCE" ELEVATION OR DIMENSIONS REFERS TO A NOMINAL WORK POINT. THE ACTUAL ELEVATION MAY VARY FROM THE REFERENCE POINT. REFER TO APPLICABLE DETAIL TO DETERMINE THE RELATIONSHIP BETWEEN THE ACTUAL ELEVATION OR DIMENSION AND THE STATED REFERENCE POINT."
B. THE DESIGN REFERENCE ELEVATION +0'-0" SHOWN ON THE ARCHITECTURAL DRAWINGS CORRESPONDS TO THE FINISH FLOOR ELEVATION OF THE GROUND FLOOR. ESTABLISH THE ACTUAL ELEVATION WITH RESPECT TO SITE-SPECIFIC BENCHMARKS AND CONTROL POINTS AS DEFINED IN THE CIVIL DRAWINGS.
C. "FINISH FLOOR" ELEVATIONS ARE MEASURED AT THE TOP OF THE CONCRETE FLOOR SLAB UNLESS OTHERWISE NOTED. APPLIED FINISHES SUCH AS RESILIENT FLOORING OR CARPET MAY RAISE THE ACTUAL FINISH SURFACE ABOVE THE REFERENCE ELEVATION PROVIDED FOR THE FINISH FLOOR.
D. WHERE CONCRETE FLOOR SLAB IS DEPRESSED TO ACCOMMODATE MORTAR BEDS, SETTING BEDS, RAISED ACCESS FLOORS, AND OTHER SIMILAR FLOOR ASSEMBLIES, "FINISHED FLOOR" ELEVATIONS ARE MEASURED AS IF CONCRETE DEPRESSION DOES NOT OCCUR.
E. CEILING HEIGHT ELEVATIONS ARE MEASURED TO BOTTOM OF FINISH SURFACES AND STATED IN RELATION TO DISTANCE ABOVE THE REFERENCE ELEVATION FOR THE FINISH FLOOR UNLESS OTHERWISE NOTED.
SECOND LEVEL+10'-0"
BUILDING SECTIONWALL SECTION NUMBER
DIRECTION OF VIEW
SHEET WHERE DRAWN
WALL SECTIONWALL SECTION NUMBER
NORTH ARROW REFERENCES
TRUE NORTH
90.000
°
NEW GRIDIDENTIFICATION
EXISTING GRIDIDENTIFICATION
LAYOUT GRID LINES
BASIC DRAWING TITLE
SHEET WHERE DRAWN
DIRECTION OF VIEW
LEVEL LINE
REVISION NUMBER AND EXTENT
DETAIL REFERENCE
SECTION DETAIL REFERENCE
EXTERIOR ELEVATION
A102 2
1
1
2
INTERIOR ELEVATION REFERENCE
ROOM NAME AND NUMBER
ELEVATION NUMBER ANDDIRECTION
SHEET WHERE DRAWN
SHEET WHERE DRAWN
ELEVATION NUMBER ANDDIRECTION OF VIEW
SHEET WHERE DRAWN,HYPHEN INDICATES DETAILON SAME SHEET.
DETAIL NUMBER
SHEET WHERE DRAWN
ELEVATION NUMBER ANDDIRECTION
AX.X.X X
WINDOW AND LOUVER TYPE MARK
SEE CORRESPONDING NUMBER ON SCHEDULE
SEE ASSEMBLY TYPE FOR DETAILS.
NAME OF LEVEL
INDICATES HEIGHT ABOVE PROJECT DATUM
REVISION NUMBER - SEE REVISION HISTORY ON THE TITLE BLOCK OF EACH SHEET
EXTENT OF CURRENT REVISION
SHEET KEYNOTE MARK
MATCH LINE REFERENCES
DRAWING TITLE SYMBOLS
A502SEE CORRESPONDING NUMBERED KEYNOTE ON SHEET WHERE REFERENCE OCCURS
REFER TO THE SHEET WHERE CONTINUATION IS FOUND
A B
1
SCALE:
1A101
SIM
A1011
SIM
1A101
SIM
A1011
SIM
1
MATCH LINE
W-X
1 View Name1/8" = 1'-0"
REFERENCE KEYNOTE MARK
088000.A03
THE FIRST SIX DIGITSREPRESENT THE SPECIFICATION SECTION
EXAMPLE 1:THE CHARACTERSFOLLOWING THE PERIODREPRESENT PARTICULARITEMS OF THE SPECIFIED SYSTEM
NORTH PROJECT NORTH
OR OR
BASIC DRAWING TITLE WITH LINESCALE:1 View Name
1/8" = 1'-0"
DRAWING TITLE WHEN ONLY ONE PLAN EXISTS ON THE DRAWING
SCALE:View Name
1/8" = 1'-0"
SHEET A2.1.1
SHEET A2.1.2
SHEET A2.1.1
OR
REFER TO THE SHEETS EITHER SIDE OF THE MATCH LINE
Room Name101
M-X
061600 5/8" PLYWOOD
EXAMPLE 2:THE TEXT IS THE PRODUCT DESCRIPTION
EARTH
AGGREGATE BASE COURSE
CONCRETE
CONCRETE MASONRY UNIT
BRICK MASONRY
PRECAST CONCRETE
LIMESTONE, SANDSTONE, GRANITE
MARBLE
STEEL, STAINLESS STEEL(LARGE SCALE)
ALUMINUM (LARGE SCALE)
OTHER METALS (LARGE SCALE)
WOOD FRAMING -CONTINUOUS (LARGE SCALE)
WOOD FRAMING - DISCONTINUOUS(LARGE SCALE)
PLYWOOD(LARGE SCALE)
FINISH WOOD (LARGE SCALE)
EIFS INSULATION BOARD (LARGE SCALE)
SEMI-RIGID INSULATION(LARGE SCALE)
BATT INSULATION(LARGE SCALE)
MORTAR, SAND, FIREPROOFING,STUCCO, GYPSUM BOARD
TERRAZZO (LARGE SCALE)
COMPOSITE BOARD (LARGE SCALE)
ACOUSTIC TILE (LARGE SCALE)
PROTECTION BOARD(LARGE SCALE)
CERAMIC TILE (LARGE SCALE)
GLASS (LARGE SCALE)
PLASTER CONCRETE
MASONRY, METAL SIDING (HORIZONTAL)
GLASS BLOCK, CERAMIC TILE
METAL SIDING (VERTICAL)
GLASS
ELEVATION
PLAN AND SECTION
ACOUSTIC PANEL
FOR THE ASSEMBLY TYPES LISTED, SEE THE FOLLOWING SHEETS FOR SYSTEM DETAILS AND DESCRIPTIONS:
TYPE A = EXTERIOR WALLS - ABOVE GRADE - SHEET A5.0.XTYPE B = EXTERIOR WALLS - BELOW GRADE - SHEET A5.0.XTYPE H = EXTERIOR WALLS - 1/2 HEIGHT AND PARAPETS - SHEET A5.0.XTYPE L = FOUNDATION SLAB SYSTEMS - SHEET A5.0.XTYPE R = ROOFING SYSTEMS - SHEET A5.0.XTYPE S = EXTERIOR SOFFITS - SHEET A5.0.XTYPE T = EXTERIOR TRIM AND COPING - SHEET A5.0.X
TYPE G = EXTERIOR GLAZING / PANEL SYSTEMS - SHEET A5.4.XTYPE X = EXTERIOR FENESTRATION SYSTEMS - SHEET A5.4.XTYPE W = EXTERIOR FRAMED WINDOWS AND LOUVERS - SHEET A5.4.X
TYPE F = FLOORING SYSTEMS - SHEET A9.1.XTYPE P = INTERIOR WALL PARTITIONS - SHEET A9.2.XTYPE C = INTERIOR CEILINGS - SHEET A9.4.X
TYPE E = INTERIOR GLAZING / PANEL SYSTEMS - SHEET A9.3.XTYPE Y = INTERIOR FENESTRATION SYSTEMS - SHEET A9.3.XTYPE M = INTERIOR FRAMED WINDOWS AND LOUVERS - SHEET A9.3.X
TYPICAL ARCHITECTURAL ASSEMBLY IDENTIFICATION MARK
A000X
A000X
PLAN
SECTION
A000X
ASSEMBLY TYPE
ASSEMBLY NAMEREPRESENTING: -MAJOR GROUP-FINISH SYSTEM-SUBSTRATE CONFIGURATION
ASSEMBLY VARIABLE(NOT ALWAYS PRESENT)
ASSEMBLY TAG DESIGNATION
EXISTING PARTITION TO REMAIN
EXISTING PARTITION TO BE REMOVED
EXISTING DOOR TO REMAIN
EXISTING DOOR AND FRAME TO BE REMOVED
EXISTING WINDOW TO REMAIN
EXISTING WINDOW TO BE REMOVED
EXISTING LAY-IN CEILING TO BE REMOVED
EXISTING LAY-IN CEILING TO REMAIN
OVERHEAD ROLLING DOOR
PAIR DOORS - UNEQUAL SIZES
DOUBLE ACTING DOOR
SINGLE OPENING DOOR
2 PANEL BI-FOLD DOOR
PAIR - BI FOLD DOOR
122
DOOR OPENING MARK
PAIR DOORS - EQUAL SIZES
PAIR DOORS - DOUBLE EGRESS
DOOR WITH SIDE LIGHT
SLIDING DOOR - BETWEEN JAMBS
SLIDING POCKET DOOR
122
122
122
122
122
122
122
122
122
INTERIOR GLAZED WINDOW
122
122
1 HOUR FIRE RESISTANCE RATING
2 HOUR FIRE RESISTANCE RATING
3 HOUR FIRE RESISTANCE RATING
0 HOUR SMOKE PARTITION
4 HOUR FIRE RESISTANCE RATING
BASE CABINETS
BASE AND WALL CABINETS
WALL CABINETS
TOILET PARTITION AND DOOR
TOILET - WALL HUNG
URINAL - FLOOR/WALL HUNG
LAVATORY - COUNTERTOP
LAVATORY -PEDESTAL/WALL HUNG
GENERAL SYMBOLS PLUMBING SYMBOLS
HANDRAIL
BUMPER GUARD
CG CGCORNER GUARD
EDGE GUARD
OVERHEAD ITEMS
UNDER-COUNTER ITEMS
NIC NOT-IN-CONTRACT ITEMS
10' - 0"
10' - 0"
JANITOR'S RECEPTOR
DRINKING FOUNTAIN / EWC
EG
DIMENSION SYMBOLS
UTILITY SINK
BATHTUB
SHOWER
FLOOR DRAIN IN SLOPING FLOOR
FEC
FEC
FEXT
FEC
FIRE EXTINGUISHER BRACKET MOUNTED
FIRE EXTINGUISHER SURFACE MOUNTED
FIRE EXTINGUISHER CABINETSEMI-RECESSED
FIRE EXTINGUISHER CABINET RECESSED
DIMENSION SHOWN TO:- STRUCTURAL GRID- LAYOUT GRID- CENTERLINE OF ASSEMBLY- CENTER OF OPENING- CENTER OF EQUIP/ FURN
GRID OR CENTER LINE TYPICAL
DIMENSION SHOWN TO:- PARTITION ASSEMBLY- EDGE OF DOOR OPENING- OTHER BUILDING ELEMENT- WORKING POINT INDICATED ON DETAIL
FD
FIRE EXTINGUISHER SYMBOLS
DETAILS ARE NUMBERED ACCORDING TO THEIR LOCATION ON EACH SHEET AND ARE NOT NUMBERED CONSECUTIVELY. EACH MODULE MAINTAINS THE NUMBER ASSOCIATED WITH IT
THIS SYSTEM CAN BE APPLIED TO ANY SHEET THAT CONTAINS MULTIPLE IMAGES. THE IMAGES ARE NUMBERED ACCORDING TO THE MODULE SYSTEM SHOWN ILLUSTRATED TO THE LEFT
EACH DETAIL MAY OCCUPY ONE OR MORE WHOLE MODULES. THE DETAIL MODULE IS USED TO ESTABLISH THE IDENTIFYING LABEL FOR EACH DETAIL, NOT TO LIMIT THE SIZE OF THE DETAIL
DETAIL MODULE LAYOUT
DETAIL NUMBERING EXAMPLE
THE NUMBER OF THE MODULE WHICH OCCURS IN THE LOWER LEFT CORNER OF A SINGLE MODULE OR SEVERAL MODULES GROUPED TOGETHER WILL DEFINE THE FINAL DETAIL NUMBER AS SHOWN IN THE ILLUSTRATION TO THE LEFT. ALTHOUGH THE MODULE NUMBERS OCCUR IN CONSECUTIVE ORDER, NOT ALL NUMBERS ARE NECESSARILY USED ON EACH SHEET
64
63
62
61
60
59
58
57
56
55
54
53
52
51
50
49
48
47
46
45
44
43
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
67
28
14
163256
55
54 46
45
4872
69
72
71
70
69
68
67
66
65
ARCHITECTURAL
2'X4' LAY IN ACOUSTIC TILE CEILING
2'X2' LAY IN ACOUSTIC TILE CEILING
GYPSUM BOARD
ACCESS PANELAP
MECHANICAL
SUPPLY GRILLE
RETURN GRILLE
EXHAUST GRILLE
LINEAR DIFFUSER
SPRINKLER HEAD - CLG MOUNT
SPRINKLER HEAD - WALL MOUNT
ELECTRICAL
MISCELLANEOUS
2'X4' LIGHTING FIXTURE
2'X2' LIGHTING FIXTURE
1'X4' LIGHTING FIXTURE
LIGHTING STRIP FIXTURE
RECESSED DOWN LIGHT
WALL WASH
TRACK LIGHTING
EXIT SIGN, SINGLE-SIDED
EXIT SIGN, DOUBLE-SIDED
FIRE ALARM
SPEAKER
SMOKE DETECTOR
WIRELESS INTERNETW
P
S
F
HEIGHT OF CEILING FINISH ABOVE FINISH FLOOR
+12'-8" SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FOR CONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage – Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/13/2
021 1
1:32:1
1 AM
ARCHITECTURALABBREVIATIONS AND
SYMBOLS
A0.1
STAR
T Sh
eet
13340.000
ARCHITECTURAL REFERENCE SYMBOLS ARCHITECTURAL GENERAL NOTESARCHITECTURAL FLOOR PLAN SYMBOLSARCHITECTURAL ABBREVIATIONS
ARCH REFLECTED CEILING PLAN SYMBOLS
DOOR AND INTERIOR OPENING SYMBOLS
ARCHITECTURAL MATERIAL INDICATIONS
MODULAR LAYOUT / DETAIL NUMBER
REFERENCE ELEVATION DEFINITIONS
FIRE RESISTIVE RATING INDICATION
ARCHITECTURAL DEMOLITION SYMBOLS
ARCHITECTURAL SYMBOL NOTES
ARCHITECTURAL ASSEMBLY SYSTEM TAGS
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
GRID
GRID
GRIDGRID
GRID
GRID
LOCATE ITEMS AS INDICATED WHEN SHOWN DIMENSIONED (VERTICAL) BY AN ELEVATION, SECTIONAL ELEVATION, OR DETAIL ELEVATION AND DIMENSIONED (HORIZONTAL) BY A PLAN OR DETAIL PLAN.
SPECIFIC VERTICAL DIMENSIONS SHOWN BY ELEVATIONS, SECTIONAL ELEVATIONS, OR DETAIL ELEVATIONS AND SPECIFIC HORIZONTAL DIMENSION SHOWN BY PLANS AND DETAIL PLANS TAKE PRECEDENCE OVER TYPICAL MOUNTING HEIGHTS AND LOCATION RULES.
WHEN COMPLETELY DIMENSIONED BY COMBINATION OF PLAN AND ELEVATION
RULE 2
WHEN COMPLETELY DIMENSIONED ON PLANS
RULE 3
LOCATE ITEMS AS INDICATED WHEN SHOWN DIMENSIONED (BOTH HORIZONTAL AND VERTICAL) BY A PLAN OR DETAIL PLAN.SPECIFIC VERTICAL DIMENSIONS SHOWN BY ELEVATIONS, SECTIONAL ELEVATIONS, OR DETAIL ELEVATIONS AND SPECIFIC HORIZONTAL DIMENSIONS SHOWN BY PLANS AND DETAIL PLANS TAKE PRECEDENCE OVER TYPICAL MOUNTING HEIGHTS AND LOCATION RULES.
NON-TYPICAL MOUNTING HEIGHTS MAY BE INDICATED BY SYMBOL (AS SHOWN), BY KEYED NOTE, OR BY NOTATION ON PLANS.
10'-6"C
C
C
WHEN DIMENSIONED HORIZONTALLY IN PLAN OR ELEVATION, BUT NOT DIMENSIONED VERTICALLY
RULE 4
LOCATE ITEMS AT TYPICAL MOUNTING HEIGHT WHEN NO VERTICAL DIMENSION IS PROVIDED. LOCATE ITEMS AS INDICATED WHEN HORIZONTAL DIMENSION IS PROVIDED BY ELEVATION, SECTIONAL ELEVATION, DETAIL ELEVATION, PLAN, OR DETAIL PLAN.
SPECIFIC HORIZONTAL DIMENSIONS SHOWN BY ELEVATIONS, SECTIONAL ELEVATIONS, DETAIL ELEVATIONS, PLANS, OR DETAIL PLANS TAKE PRECEDENCE OVER TYPICAL MOUNTING LOCATION RULES.
C
NOT DIMENSIONED AND LOCATED ON COLUMN OR PILASTER
RULE 6
WHEN NOT DIMENSIONED AND SHOWN LOCATED ON A COLUMN OR PILASTER, AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: HORIZONTALLY CENTER ITEM ON FACE OF COLUMN OR PILASTER. ALIGN VERTICALLY CENTERS OF MULTIPLE ITEMS HAVING DIFFERING TYPICAL MOUNTING HEIGHTS.
WHEN MULTIPLE ITEMS HAVING THE SAME TYP MOUNTING HEIGHT ARE INDICATED, HORIZONTALLY CENTER GROUP OF ITEMS ON FACE OF COLUMN OR PILASTER (SEE RULE 7).
ON PLANS, ITEMS TO BE VERTICALLY ALIGNED MAY BE SHOWN ADJACENT.
WHEN NOT DIMENSIONED AND SHOWN LOCATED ON A COLUMN OR PILASTER, AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: HORIZONTALLY CENTER GROUP OF SIMILAR ITEMS HAVING THE SAME MOUNTING HEIGHT(S) ABOUT THE CENTERLINE OF THE COLUMN OR PILASTER.
WHEN APPLICABLE, COMBINE THIS RULE WITH RULE 6 TO SYMMETRICALLY ARRANGE GROUPS OF ITEMS HAVING BOTH DIFFERING AND SIMILAR MOUNTING HEIGHTS.
ARRANGE ITEMS AT SAME HEIGHT SYMMETRICALLY ABOUT CENTERLINE
NOT DIMENSIONED AND LOCATED ON COLUMN OR PILASTER
RULE 7
WHEN NOT DIMENSIONED AND SHOWN LOCATED ON A COLUMN OR PILASTER, AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: HORIZONTALLY CENTER GROUP OF DISSIMILAR ITEMS HAVING CONFLICTING MOUNTING HEIGHT(S) ABOUT THE CENTERLINE OF THE COLUMN OR PILASTER.
WHEN APPLICABLE, COMBINE THIS RULE WITH RULE 6 AND/OR RULE 7 TO SYMMETRICALLY ARRANGE GROUPS OF ITEMS HAVING DIFFERING, SIMILAR, AND CONFLICTING MOUNTING HEIGHTS.
ARRANGE ITEMS AT CONFLICTING HEIGHTS SYMMETRICALLY ABOUT CENTERLINE
NOT DIMENSIONED AND LOCATED ON COLUMN OR PILASTER
RULE 8
WHEN NOT DIMENSIONED AND SHOWN LOCATED ADJACENT TO STRIKE SIDE OF DOOR, AND WHEN STRIKE-SIDE CLEARANCE IS BETWEEN 12 INCHES AND 18 INCHES, AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: MOUNT ITEMS IN RELATION TO FRAME USING TYPICAL OFFSET DIMENSION. VERTICALLY ALIGN CENTERS OF ITEMS MOUNTED AT DIFFERENT HEIGHTS.
STRIKE SIDE OF DOOR
LINE OF WALL OR OTHER RESTRICTION ON STRIKE-SIDE OF DOOR
WHEN MULTIPLE ITEMS HAVING THE SAME TYPICAL MOUNTING HEIGHT ARE INDICATED, MOUNT FIRST ITEM IN RELATION TO FRAME USING TYPICAL OFFSET DIMENSION AND PLACE REMAINING ADJACENT TO FIRST ON SIDE OPPOSITE FRAME AS ILLUSTRATED BY THIS DIAGRAM. DO NOT CROWD MULTIPLE ITEMS AGAINST WALL OR RESTRICTION.
NOT DIMENSIONED AND LOCATED ADJACENT TO MINIMUM STRIKE-SIDE OF DOOR
RULE 9
WHEN NOT DIMENSIONED AND LOCATED ADJACENT TO CHANGE IN WALL DIRECTION
RULE 12
WHEN NOT DIMENSIONED AND SHOWN LOCATED ADJACENT TO CHANGE IN PLANE OF WALL, AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: MOUNT ITEMS IN RELATION TO PLANE CHANGE USING TYPICAL OFFSET DIMENSION. VERTICALLY ALIGN CENTERS OF ITEMS MOUNTED AT DIFFERENT HEIGHTS.
WHEN MULTIPLE SIMILAR ITEMS HAVING THE SAME TYPICAL MOUNTING HEIGHT ARE INDICATED, MOUNT FIRST ITEM IN RELATION TO PLANE CHANGE USING TYPICAL OFFSET DIMENSION AND PLACE REMAINING ITEMS ADJACENT TO FIRST ON SIDE OPPOSITE PLANE CHANGE AS ILLUSTRATED BY THIS DIAGRAM.
MULTIPLE SIMILAR ITEMS AT SAME HEIGHT
FOR PURPOSES OF THESE RULES, ITEMS SHOWN LOCATED APPROXIMATELY WITHIN 4 FEET OF PLANE CHANGE ARE CONSIDERED TO BE ADJACENT TO CHANGE IN PLANE.
MULTIPLE DISSIMILAR ITEMS WITH CONFLICTING MOUNTING HEIGHTS
WHEN NOT DIMENSIONED AND SHOWN LOCATED ADJACENT TO CHANGE IN PLANE OF WALL, AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: MOUNT ITEMS IN RELATION TO PLANE CHANGE USING TYPICAL OFFSET DIMENSION. VERTICALLY ALIGN CENTERS OF ITEMS MOUNTED AT DIFFERENT HEIGHTS.
WHEN MULTIPLE DISSIMILAR ITEMS HAVING CONFLICTING MOUNTING HEIGHTS ARE INDICATED, MOUNT FIRST ITEM IN RELATION TO PLANE CHANGE USING TYPICAL OFFSET DIMENSION. SEPARATE DISSIMILAR ITEM FROM GROUP OF SIMILAR ITEMS BY 24" MINIMUM AS ILLUSTRATED BY THIS DIAGRAM.
FOR PURPOSES OF THESE RULES, ITEMS SHOWN LOCATED APPROXIMATELY WITHIN 4 FEET OF PLANE CHANGE ARE CONSIDERED TO BE ADJACENT TO CHANGE IN PLANE.
WHEN NOT DIMENSIONED AND LOCATED ADJACENT TO CHANGE IN WALL DIRECTION
RULE 13
WHEN NOT DIMENSIONED AND SHOWN ON A WALL NOT ADJACENT TO DOORS, WINDOWS, OR CHANGES IN WALL PLANE, AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: LOCATE AT APPROXIMATE HORIZONTAL POSITION SHOWN ON PLANS OR ELEVATIONS. GROUP ITEMS HAVING DIFFERENT MOUNTING HEIGHTS INTO SINGLE, SYMMETRICAL ARRANGEMENT BY VERTICALLY ALIGNING CENTERS OF ITEMS. MAINTAIN MINIMUM 36" HORIZONTAL SEPARATION BETWEEN ITEMS OR GROUPS OF ITEMS WHICH CANNOT BE ALIGNED VERTICALLY (SEE RULE 15).
WHEN APPLICABLE, SYMMETRICALLY ARRANGE GROUPS OF SIMILAR ITEMS HAVING THE SAME MOUNTING HEIGHT AROUND THE VERTICAL AXIS ESTABLISHED.
ARRANGE SIMILAR ITEMS AT SAME HEIGHT SYMMETRICALLY ABOUT CENTERLINE
NOT DIMENSIONED AND LOCATED ON OPEN WALL
RULE 14
NOT DIMENSIONED AND LOCATED ON OPEN WALL
RULE 15
WHEN NOT DIMENSIONED AND SHOWN ON A WALL NOT ADJACENT TO DOORS, WINDOWS, OR CHANGES IN WALL PLANE, AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: MAINTAIN MINIMUM 36 INCH HORIZONTAL SEPARATION BETWEEN DISSIMILAR ITEMS OR GROUPS OF ITEMS WITH CONFLICTING MOUNTING HEIGHTS WHICH CANNOT BE VERTICALLY ALIGNED PER RULE 14.
SEPARATE DISSIMILAR ITEMS WITH CONFLICTING MOUNTING HEIGHTS.
ITEMS WHICH CAN BE VERTICALLY ALIGNED PER RULE NO 14.
MIN3' - 0"
ON E
LEVA
TIO N
VERT
ICAL
DIM
ENSI
ON
HORIZONTAL DIMENSION ON PLAN
HORIZONTAL DIMENSION ON PLAN
HORIZONTAL DIMENSION ON ELEVATION
HORIZONTAL DIMENSION ON PLAN
EQ EQ
EQ EQ6"
EQ EQ
EQ EQ
8" TYP
3" MIN
1'-6" MIN SWING SIDE
1'-0" MIN OPP SWING SIDE
4' - 0"
8" TYP
4' - 0"
APPROXIMATE LOCATION
4' - 0"
APPROXIMATE LOCATION
2' -0" MIN 8" MIN
4' - 0"
A. THE A-SERIES DRAWINGS ESTABLISH AND GOVERN THE FINISHED APPEARANCE AND LOCATION OF THE EXPOSED WORK OF ALL TRADES, INCLUDING THAT WHICH IS ILLUSTRATED PRIMARILY ON DRAWINGS OF OTHER DISCIPLINES. LOCATIONS SHOWN ON DRAWINGS OF OTHER DISCIPLINES ARE SCHEMATIC, UNLESS NOTED OTHERWISE ON THE A-SERIES DRAWINGS. THE A-SERIES DRAWINGS TAKE PRECEDENCE FOR DETERMINING THE FINISHED APPEARANCE AND LOCATION OF ALL PARTS OF THE WORK.
EXCEPTION: DIMENSIONED LOCATIONS SHOWN ON DRAWINGS OF OTHER DISCIPLINES SHALL GOVERN ONLY WHERE:
1. SPECIFICALLY AND INDIVIDUALLY INDICATED BY SYMBOL, KEYED NOTE, OR NOTATION ON THE A-SERIES DRAWINGS.
2. WHICH A-SERIES SHEET OR SCHEDULE NOTES INDICATE THAT DIMENSIONS PROVIDED ELSEWHERE SHALL GOVERN.
B. THE PURPOSE OF THIS SHEET IS TO ILLUSTRATE THE TYPICAL RULES WHICH GOVERN THE LOCATION, CONFIGURATION IN RELATIONSHIP TO OTHER ELEMENTS OF THE WORK, AND FINISHED ALIGNMENT OF ALL ITEMS OCCURRING ON VERTICAL SURFACES OF THE PROJECT.
C. THE A-SERIES FLOOR PLANS, REFLECTED CEILING PLANS, SECTIONS, ELEVATIONS, AND DETAILS ILLUSTRATE THE DIMENSIONED LOCATION OF MANY - BUT NOT ALL - EXPOSED PARTS OF THE WORK. APPLY THE RULES ON THIS SHEET - IN ORDER - TO DETERMINE THE LOCATION OF EXPOSED PART OF THE WORK.
1. WHEN UNIQUELY AND SPECIFICALLY DIMENSIONED ON THE A-SERIES PLANS, SECTIONS, OR ELEVATIONS (OR COMBINATION THEREOF), LOCATE AS DIMENSIONED (SEE RULES 1 THRU 3).
2. WHEN SHOWN WITH HORIZONTAL DIMENSION ON THE A-SERIES PLANS, SECTIONS, OR ELEVATIONS, LOCATE HORIZONTALLY AS DIMENSIONED AND AT THE APPLICABLE TYPICAL MOUNTING HEIGHT (SEE RULE 4).
3. IF NOT SHOWN, OR IF SHOWN BUT NOT DIMENSIONED, BY THE A-SERIES PLANS OR ELEVATIONS, LOCATE AS INDICATED BY THE APPLICABLE TYPICAL ARCHITECTURAL CONFIGURATION DIAGRAM (SEE RULE 5).
4. WHEN DIMENSION SHOWN ON DRAWINGS OF OTHER DISCIPLINES IS INDICATED TO GOVERN, LOCATE AS DIMENSIONED. UTILIZE RULES 6 THRU 15 TO ESTABLISH RELATIVE LOCATIONS OF ITEMS NOT DIMENSIONED WHICH MAY OCCUR IN PROXIMITY TO THE DIMENSIONED ITEM.
5. IF NO TYPICAL ARCHITECTURAL CONFIGURATION DIAGRAM APPLIES, LOCATE AT APPROXIMATE HORIZONTAL LOCATION SHOWN AND AT APPLICABLE TYPICAL MOUNTING HEIGHT. UTILIZE RULES 6 THROUGH 15 TO ESTABLISH LOCATION AND RELATIONSHIP WITH OTHER PARTS OF THE WORK.
D. TYPICAL ARCHITECTURAL CONFIGURATION DIAGRAMS ARE ELEVATIONS WHICH ILLUSTRATE TYPICAL RULES GOVERNING THE RELATIONSHIPS BETWEEN - AND PLACEMENT OF - ITEMS WHICH OCCUR IN GROUPS OF RELATED ITEMS (SUCH AS TOILET ACCESSORIES) OR IN CLOSE PROXIMITY TO OTHER PARTS OF THE WORK (SUCH AS SWITCHES AND DOOR FRAMES). REFER TO THE ""PROJECT SHEET INDEX"" FOR ADDITIONAL INFORMATION REGARDING OTHER TYPICAL ARCHITECTURAL CONFIGURATION DRAWINGS PROVIDED FOR THIS PROJECT.
- CONTINUED AT TOP OF NEXT COLUMN
D.
5.
DIMENSION, WHEN OCCURS
ALIGN
B.
C.
B.
A.
4.
3.
A.
F.
E.
D.
1.
2.
E.
NOTE NO 4 CONTINUED:4.
C.
EXCEPT WHERE DIRECTED TO PLACE ITEMS OF THEWORK AT THE "APPROXIMATE LOCATION SHOWN,"DO NOT SCALE DRAWINGS FOR DIMENSIONALINFORMATION.
ALL ELEMENTS OF THE DRAWINGS MAY NOT BEDRAWN TO EXACT SCALE. ALL DIMENSIONSREQUIRED ARE SHOWN (OR MAY BE DERIVEDFROM THOSE SHOWN OR NOTED) ON THE FLOORPLANS, DETAIL PLANS, ELEVATIONS, SECTIONS,SCHEDULES, CONFIGURATION DETAILS, ANDSPECIFICATIONS. SEE THE NOTES BELOW ANDSYMBOLS ON SHEET A0.1 FOR DIMENSIONINGCONVENTIONS USED ON THIS PROJECT.
EXCEPT WHERE SPECIFICALLY NOTED TO THECONTRARY, ALL DIMENSIONS SHOWN ON THEARCHITECTURAL DRAWINGS CONFORM TO THEFOLLOWING CONVENTIONS:
DIMENSIONS UTILIZING THE "CENTERLINE" SYMBOLARE MEASURED TO:
STRUCTURAL OR DIMENSIONAL GRID LINES.
CENTERLINE OF CONCRETE OR CONCMASONRY UNIT WALLS (EXCLUSIVE OFFURRING OR APPLIED FINISHES HAVINGTHICKNESS). REFER TO THE ARCH PLANSAND SECTIONS, THE STRUCT DRAWINGS,OR PARTITION SCHEDULE TO DETERMINETHE THICKNESS OF CONCRETE OR CONCMASONRY UNIT WALLS.
CENTERLINE OF PARTITION ASSEMBLY(EXCLUSIVE OF ANY APPLIED FINISHESHAVING THICKNESS WHICH MAY BEADDED TO SUCH WALLS) AT PARTITIONSFRAMED WITH METAL STUDS. REFER TO"PARTITION SCHEDULE" TO DETERMINETHICKNESS OF EACH PARTITION TYPE.
CENTERLINE OF DOOR, WINDOW, OR LOUVER OPENING.
CENTERLINE OF EQUIPMENT OR FURNISHING.
CENTERLINE OF OTHER FEATURES AS INDICATED.
REFER TO SHEET A0.1 FOR SYMBOL USEDTO INDICATE CENTERLINE DIMENSION.
DIMENSIONS UTILIZING THE "FACE OF"SYMBOL ARE MEASURED TO:
FACE OF CONCRETE OR CONC MASONRYUNIT WALL (EXCLUSIVE OF APPLIEDFINISHES HAVING THICKNESS OR FURRINGWHICH MAY BE ADDED TO THE FACE OFSUCH WALLS).
FACE OF PARTITION ASSEMBLY(EXCLUSIVE OF ANY APPLIED FINISHESHAVING THICKNESS WHICH MAY BEADDED TO SUCH WALL) AS DEFINEDBY THE PARTITION SCHEDULE.UNLESS NOTED AS A "FACE OFFINISH" OR "CLEAR" DIMENSION (SEENOTE 'E' BELOW), DIMENSIONS ARENOT MEASURED TO THE FACE OFAPPLIED FINISH. REFER TO THE"PARTITION SCHEDULE" TO DETERMINETHE THICKNESS OF EACH PARTITIONTYPE.
INSIDE EDGE OF FINISHED DOOROPENING. REFER TO THE "DOORSCHEDULE" FOR ADDITIONALDIMENSIONAL INFORMATION.
DIMENSION OR WORK POINT ASINDICATED ON RELATED ARCH DETAILPLAN, SECTION, ELEVATION, LAYOUTOR CONFIGURATION DETAIL, ORCONSTRUCTION DETAIL.
REFER TO SHEET A0.1 FOR SYMBOL USEDTO INDICATE "FACE OF" DIMENSION.
WHERE "FACE OF FINISH" OR "CLEAR" DIMENSIONSARE SPECIFICALLY NOTED, THE DIM IS MEASUREDTO:
FINISH FACES AT THE MOST NARROWOR CONSTRICTED POINTS OF SECTIONWHERE DIMENSION IS SHOWN, WHENTHE DIMENSION OCCURS ACROSS ANOPEN SPACE. THIS CASE, A "FACEOF FINISH" DIMENSION IS EQUIVALENTTO A "CLEAR" DIMENSION.
FINISH FACES AT THE WIDEST OR MOSTEXPANSIVE POINTS OF THE SECTION THEDIMENSION IS SHOWN WHEN THE DIMENSIONOCCURS ACROSS AN OBJECT OR GROUP OFOBJECTS.
WHERE "EQUAL" DIMENSIONS ARE USEDON REFLECTED CEILING PLANS TOLOCATE CEILING GRID WORK POINTS,MEASURE DIMENSIONS TO:
EDGE OF THE INDICATED CEILING ATTHE FACE OF THE ADJACENT APPLIEDFINISH MEASURED AT THE PLANE OFTHE CEILING.
CAUTION: DUE TO THE POSSIBLEAPPLICATION OF APPLIED FINISHES -THICKNESS OF WHICH MAY VARYBETWEEN FLOOR AND CEILING AND ISNOT ACCOUNTED FOR (EXCEPT ASINDICATED BY "FOF" OR "CLEAR") BYTHE DIMENSION SHOWN ON THE FLOORPLANS - THE CONTRACTOR MUSTADJUST, AS NECESSARY, THE FLOORPLAN DIMENSIONS TO REFLECT THEACTUAL DIMENSIONS FOUND AT PLANEOF THE CEILING.
WHERE DIMENSIONS ARE NOT PROVIDED ONFLOOR PLANS TO LOCATE DOOR OPENINGS,APPLY THE FOLLOWING RULES, IN ORDER, TODETERMINE THE LOCATION OF DOOR OPENINGS:
DOOR OPENINGS MAY BEDIMENSIONED ON DRAWINGS OTHERTHAN THE FLOOR PLANS. REFER TOTHE SECTIONS, ELEVATIONS, DETAILS,AND DOOR SCHEDULE NOTES FORADDITIONAL DIMENSIONAL INFORMATION.WHERE THE HINGE-SIDE OF A DOOR ISSHOWN ADJACENT TO A WALL - OR WALLS- PERPENDICULAR TO THE WALL IN WHICHTHE DOOR OPENING OCCURS:
AT DOORS OCCURRING IN METAL FRAMEDGYPSUM BOARD PARTITIONS, LOCATE THEHINGE-SIDE OF THE DOOR FINISHEDOPENING 4 INCHES FROM THE FACE(EXCLUSIVE OF APPLIED FINISHES) OF THETHE CLOSEST PERPENDICULAR WALL ORPARTITION ASSEMBLY.
AT DOORS OCCURRING IN WALLS OF CONCMASONRY UNIT CONSTRUCTION, LOCATETHE HINGE-SIDE OF THE DOOR FINISHEDOPENING 10 INCHES FROM THE FACE(EXCLUSIVE OF APPLIED FINISHES) OF THETHE CLOSEST PERPENDICULAR WALL ORPARTITION ASSEMBLY.
WHERE DOOR OCCURS NOT ADJACENT TO APERPENDICULAR WALL AND EITHER "DIM E"OR "DIM F" IS 16'-0" OR LESS, LOCATEDOOR UTILIZING THE FOLLOWING MINIMUMDIMENSIONS:
DIMENSION A = 18 INCHES MIN
DIMENSION B = 12 INCHES MIN
DIMENSION C = DOOR WIDTH + 2INCHES MINIMUM
DIMENSION D = 4 INCHES MIN ATMETAL FRAMED GYP BD PARTITIONSOR - EVEN MULTIPLE OF 1/2 CMUMODULE PLUS 2 INCHES AT CONCMASONRY UNIT WALLS
DIMENSIONS E AND F = AS SHOWN ON PLANS
DIMENSION G = 36 INCHES MIN
DIMENSION H = 60 INCHES MIN
IF SPACE ALLOWS, CENTER DOOR INWALL SHOWN ON THE DRAWINGS SOTHAT EITHER "DIM A" EQUALS "DIM C"OR "DIM B" EQUALS "DIM D".
IF "DIM E" IN DIAGRAMS BELOW IS LESSTHAN THE SUM OF 2 TIMES THE DOORWIDTH PLUS 20 INCHES, LOCATE DOORSO THAT MINIMUMS STATED BY NOTENO 4C ABOVE FOR "DIM A", "DIM B,"AND "DIM D" ARE MET - MAXIMIZING"DIM A" AND MINIMIZING "DIM D" TOTHE EXTENT POSSIBLE.
WHERE DOOR IS SHOWN LOCATED IN ALARGE EXPANSE OF OPEN WALL ("DIME" AND "DIM F" IN DIAGRAM BELOWBOTH EXCEED 16'-0"), PLACE DOORAT APPROXIMATE LOCATION SHOWN ONTHE PLANS. WHERE DOOR OCCURS INCMU WALL, PLACE DOOR ATAPPROXIMATE LOCATION SHOWN WHILEMINIMIZING "CUT" OR PARTIAL CMUMODULES ADJACENT TO THE JAMBS.
WHERE WALLS AND/OR PARTITIONS OFUNEQUAL THICKNESS ABUT, ALIGN EXPOSEDFACES, UNLESS OTHERWISE NOTED.
3. NOTE NO 3 CONTINUED:
MEASURED AT CLG PLANE"EQUAL" DIM AT CEILING
MEASURED TO FACE OF PTNTYPICAL DIM ON CEILING PLAN
4"
4"
10"
10"
DIM E > 16'-0"
DIM F > 16'-0"
EA
EA D
B D B
EA C
F
B D
G H
- CONTINUED AT TOP OF NEXT COLUMN
3. NOTE NO 3 CONTINUED: NOTE NO 4 CONTINUED:4.
- CONTINUED AT TOP OF NEXT COLUMN
- CONTINUED AT TOP OF NEXT COLUMN
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FOR CONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage – Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/13/2
021 1
1:32:1
2 AM
TYPICAL RULES FORDETERMINING MOUNTINGHEIGHTS AND LOCATIONS
AND DIMENSIONINGCONVENTIONS
A0.4
STAR
T Sh
eet
13340.000
GENERAL MOUNTING NOTES
TYPICAL RULES FOR DETERMINING MOUNTING HEIGHTS, LOCATIONS, AND CONFIGURATIONS
ARCHITECTURAL DIMENSIONING CONVENTIONS
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
C
PTZ
DT
A. REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS DRAWING.
B. EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND VISUAL FIELD SURVEYS. THE CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT THE SITE PRIOR TO SUBMITTING A BID. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ANY DISCREPANCIES.
C. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE UNNECESSARY INCONVENIENCE OR DANGER TO USERS OF THE PREMISES AND ADJACENT SITE AND NOT INTERFERE WITH ITS OPERATION. ANY DEMOLITION WORK TO BE PERFORMED MUST BE PLANNED IN ADVANCE AND APPROVED BY THE OWNER.
D. ANY EQUIPMENT, MATERIALS, AND SUPPLIES TEMPORARILY REMOVED FOR THE PURPOSE OF PROTECTION SHALL BE REPLACED IN ORIGINAL LOCATIONS AND CONDITIONS. ANY MATERIALS DAMAGED SHALL BE REPLACED WITH NEW MATERIALS OF LIKE KIND AND QUALITY.
E. REFER TO AND COORDINATE WITH STRUCTURAL, CIVIL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION INFORMATION NOT SHOWN ON THIS DRAWING.
F. ALL MATERIALS INDICATED TO BE REMOVED SHALL BE DISPOSED OF PROPERLY AND REMOVED FROM THE SITE.
G. ALL REMOVED MATERIALS AND EQUIPMENT WHICH IS CLASSIFIED AS "SALVAGE FOR OWNER" SHALL REMAIN THE PROPERTY OF THE OWNER. DELIVER SUCH MATERIALS AND EQUIPMENT ON THE PREMISES AS DIRECTED BY THE OWNER AND NEATLY STORE AND PROTECT FROM DAMAGE.
H. ALL REMOVED MATERIALS AND EQUIPMENT WHICH IS CLASSIFIED "SALVAGE FOR RELOCATION" SHALL REMAIN THE PROPERTY OF THE OWNER. THE CONTRACTOR IS RESPONSIBLE FOR PLACING ITEMS IN STORAGE ON SITE AND FOR THE PROTECTION OF THOSE ITEMS. THESE ITEMS WILL BE RELOCATED. REFER TO THE FLOOR PLANS FOR NEW LOCATIONS.
J. PATCH AND REPAIR ALL ELEMENTS THAT ARE TO REMAIN WHICH ARE DAMAGED FROM THE DEMOLITION WORK WITH CONSTRUCTION TO MATCH EXISTING CONDITIONS.
K. ADDITIONAL SELECTIVE DEMOLITION WILL BE REQUIRED FOR INSTALLATION OF NEW EQUIPMENT. COORDINATE WITH ARCHITECTURAL DRAWINGS.
NOT IN CONTRACT (NIC)
21A 21B 22 23 23A
14
13
CLASSROOM1463
ELECTRICAL1468
CAREFULLY REMOVE AND SALVAGE EXISTING MARKER BOARDS, TYP. OF FIVE (5) IN ROOM. DELIVER TO BIC LEVEL 0 OR REMOVE FROM SITE, CONTRACTOR TO COORDINATE REMOVAL AND STORAGE WITH OWNER. PATCH, REPAIR, AND FINISH WALL TO MATCH EXISTING.
ALL CARPET, WALL BASE, WALL PROTECTION EXISTING TO REMAIN UNLESS OTHERWISE NOTED.
REMOVE EXISTING 12" CHAIR RAIL WALL PROTECTION ALONG ENTIRE LENGTH OF WEST WALL ONLY. PREPARE SURFACE TO RECEIVE NEW CHAIR RAIL WALL PROTECTION AND PAINT.
21A 21B 22 23 23A
14
13
REMOVE AND SALVAGE EXISTING CEILING MOUNTED PROJECTOR SCREEN. REPLACE DAMAGED CEILING TILES TO MATCH EXISTING.
EXISTING CEILING AND ALL CEILING ELEMENTS THIS ROOM EXISTING TO REMAIN.
EXISTING CEILING MOUNTED PROJECTOR TO BE REMOVED BY OWNER. CONTRACTOR TO REMOVE AND SALVAGE SUPPORT POST AND TRAPEZE AND REMOVE EXISTING QUAD RECEPTACLE IN CEILING. REPLACE DAMAGED CEILING TILES TO MATCH EXISTING.EXISTING ACOUSTICAL CEILING TILES, LIGHT FIXTURES, DIFFUSERS, AND OTHER CEILING ELEMENTS EXISTING TO REMAIN UNLESS OTHERWISE NOTED. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL DETAIL.
REMOVE AND SALVAGE EXISTING CEILING MOUNTED SPEAKERS. REPLACE DAMAGED CEILING TILES TO MATCH EXISTING
REMOVE AND SALVAGE EXISTING MICROPHONE. REPLACE DAMAGED CEILING TILES TO MATCH EXISTING.
REMOVE AND SALVAGE EXISTING WALL MOUNTED CAMERA. REPAIR, PATCH, AND PAINT WALL TO MATCH EXISTING.
REMOVE AND SALVAGE FOR REINSTALLATION EXISTING COD MASTER CLOCK. REPAIR, PATCH, AND PAINT WALL TO MATCH EXISTING.
CLASSROOM1463
ELECTRICAL1468
REMOVE EXISTING DOWNLIGHTS AND ASSOCIATED CONDUCTORS, CONDUIT, ETC. BACK TO LAST JUNCTION NOT MODIFIED UNDER THIS SCOPE OF WORK. REPLACE DAMAGED CEILING TILES, TYP. OF FOUR (4).
DEMOLISH LIGHT SWITCHES AND EXISTING 3-GANG BOX. RETAIN CONDUIT FOR RECONNECTION TO MULTI-GANG BOX IN NEW WORK
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FOR CONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage – Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/13/2
021 1
1:32:1
3 AM
LEVEL 01 - ROOM 1463 -DEMOLITION PLANS
A2.1.1AD
STAR
T Sh
eet
13340.000
GENERAL SHEET NOTES
PROJECT NORTHPROJECT NORTH
GRAPHIC LEGEND
SCALE: 1/4" = 1'-0"1 LEVEL 1 - DEMOLITION FLOOR PLAN ROOM 1463SCALE: 1/4" = 1'-0"2 LEVEL 1 - REFLECTED CEILING DEMOLITION PLAN ROOM 1463
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
H
H
H
H
H
HH
H
PTZ
PTZ
PTZ
DT
D
DT
A. REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B. ALL DIMENSIONS SHOWN SHALL BE VERIFIED PRIOR TO CONSTRUCTION. PENETRATION LOCATIONS ARE SHOWN FOR GRAPHICAL PURPOSES ONLY. COORDINATE PENETRATION LOCATIONS WITH ELECTRICAL, MECHANICAL, PLUMBING, AND STRUCTURAL DISCIPLINES.
C. ALL EXISTING ACOUSTICAL CEILING TILE TO REMAIN. SALVAGE AND RECONFIGURE EXISTING TILES TO ACCOMMODATE NEW CONSTRUCTION.
CLASSROOM1463
PNT-02PNT-01
ELECTRICAL1468
21A 21B 22 23 23A
14
13
A8.1.1
18
67
42
66
NEW AV PODIUM BY OWNER
DASHED LINE INDICATES AREA OF EXISTING FLOOR BOX AT PODIUM LOCATION
TEACHING WALL
TEAC
HING
WAL
L
SEE INTERIOR ELEVATIONS FOR EQUIPMENT NOTES AND LOCATIONS
13' - 2 7/8" 8' - 1 5/8" 4' - 3 7/8"
29' -
0"
CORRIDOR
REFER TO ELECTRICAL DRAWINGS FOR WORK IN THIS AREA.
VIF23' - 3 1/8"
VIF
27' -
10 3/
8"
A9.1.137
TYP.
13A9.1.1
TYP.
16A9.1.1
TYP.
21A 21B 22 23 23A
14
13
CLASSROOM1463
ELECTRICAL1468
EXISTING CONDUIT ZONE. ROUTE NEW EQUIPMENT CONDUIT IN ALTERNATE LOCATION.
NEW WALL MOUNTED PROJECTOR SCREEN, TYP. OF (1). REFER TO AV DRAWINGS.
NEW WALL MOUNTED SHORT THROW PROJECTOR, TYP. OF (1), REFER TO AV DRAWINGS.
NEW CAMERA, TYP. OF (3). REFER TO AV DRAWINGS.
RELOCATED COD MASTER CLOCK. REFER TO ELECTRICAL.
ALL CEILING ELEMENTS EXISTING TO REMAIN UNLESS NOTED OTHERWISE
NEW MICROPHONE ARRAY, TYP. OF TWO (2). REFER TO AV DRAWINGS.
NEW SPEAKER, TYP. OF FOUR (4). REFER TO AV DRAWINGS.
NEW ADJUSTABLE DOWNLIGHT, REFER TO ELECTRICAL.BASE: TYP. OF (10)ALT 1: TYP. OF (6)
NEW SWITCHES FOR RECORDING IN PROGRESS LIGHT AND ROOM LIGHTING. REFER TO ELECTRICAL.
EXISTING THERMOSTAT
"QUIET PLEASE. RECORDING IN PROGRESS." SIGNAGE. REFER TO ELECTRICAL.
13' - 2 7/8" 8' - 1 5/8" 4' - 3 7/8"
29' -
0"
CORRIDOR
40A9.1.1
TYP.
NEW OCCUPANCY SENSOR. REFER TO ELECTRICAL DRAWINGS.
NOT IN CONTRACT (NIC)
Room Name
101 ROOM NUMBER
PNT-01 WALL FINISHPNT-02 WALL BASE FINISH
NOTE: REFER TO SPECIFICATIONS FOR FINISH SCHEDULE.
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FOR CONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage – Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/13/2
021 1
1:32:1
2 AM
LEVEL 01 - ROOM 1463 -FLOOR PLAN AND
REFLECTED CEILING PLAN
A2.1.1
STAR
T Sh
eet
13340.000
GENERAL SHEET NOTESGRAPHIC LEGEND
SCALE: 1/4" = 1'-0"69 LEVEL 1 - ROOM 1463 - FLOOR PLANPROJECT NORTHPROJECT NORTH
SCALE: 1/4" = 1'-0"37 LEVEL 1 - ROOM 1463 - REFLECTED CEILING PLAN
FINISH LEGEND
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
A. REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B. REFER TO AND COORDINATE WITH MECHANICAL, PLUMBING, AND ELECTRICAL FOR ADDITIONAL INFORMATION NOT SHOWN ON THIS SHEET.
C. THE PURPOSE OF THE DRAWINGS ON THIS SHEET IS TO ILLUSTRATE THE OVERALL CONFIGURATION OF ALL ITEMS OF ALL TRADES OCCURRING ON THE INTERIOR ELEVATIONS. LOCATIONS OF ELEMENTS SHOWN ON ELECTRICAL, MECHANICAL, AND PLUMBING DRAWINGS ARE SCHEMATIC AND THE DIMENSIONS SHOWN HERE TAKE PRECEDENCE.
D. REFER TO THE A0.X SERIES SHEETS FOR TYPICAL MOUNTING HEIGHTS FOR DIMENSIONS NOT SHOWN ON THIS SHEET.
E. ALL FLOOR, WALL, AND CEILING FINISHES SHOWN ARE EXISTING TO REMAIN. ANY REPAIR OR REPLACEMENT REQUIRED AS A RESULT OF THE SCOPE OF NEW WORK SHOWN SHOULD MATCH EXISTING FINISHES, COLORS, AND PRODUCTS.
F. COORDINATE ALL MOUNTING HEIGHTS SHOWN WITH EXISTING CONDITIONS.
G. FURNITURE SHOWN IS FOR REFERENCE ONLY AND OFOI.
H. ACOUSTIC PANEL DIMENSION TAKEN TO CENTER LINE OF JOINTS AND FACE OF PANEL ON ADJACENT WALL.
I. WALL MOUNTED AV EQUIPMENT DIMENSIONS TAKEN FROM FACE OF EXISTING GYP. BD. PARTITION TO CENTER LINE OF EQUIPMENT.
J. REFER TO AV DRAWINGS FOR ADDITIONAL EQUIPMENT DETAILS AND TO COORDINATE FINAL MOUNTING HEIGHTS.
NEW 8" WIDE WALL PROTECTION AS SPECIFIED.
EXISTING WALL MOUNTED TELEPHONE TO BE REINSTALLED
WITH EXTENSION RING IN EXISTING LOCATION ON TOP OF
ACOUSTIC PANELS
NEW DUPLEX AND USB PORTS, REFER TO ELECTRICAL DRAWINGS.
EXISTING DUPLEX TO REMAIN.
NEW DIGITAL CLOCK/TIMER, REFER TO AV & ELECTRICAL DRAWINGS.
NEW DUPLEX AND USB PORTS. REFER TO ELECTRICAL DRAWINGS.
NEW WALL MOUNT SHORT THROW. REFER TO AV & ELECTRICAL DRAWINGS.
NEW A/V PODIUM BY OWNER
4' X 8' WHITE BOARD
NEW 50" FLAT SCREEN ON ARTICULATING MOUNT. REFER TO
AV& ELECTRICAL DRAWINGS.
ACOUSTIC WALL PANELS AS SPECIFIED
NEW 50" FLAT SCREEN ON ARTICULATING MOUNT. REFER TO AV & ELECTRICAL DRAWINGS.
NEW WALL MOUNTEDMANUAL PROJECTION SCREEN.
ALL EXPOSED DRYWALL (BEHIND TV MONITOR AND BELOW WALL PROTECTION) TO BE PAINTED.
EXISTING FIN. CEILING9'-8"
4' X 4' WHITE BOARD12" WALL MOUNT TOUCH SCREEN. REFER TO AV & ELECTRICAL DRAWINGS.
NEW WALL MOUNTED CAMERA, REFER TO AV & ELECTRICAL DRAWINGS.
5' - 0
"
12' - 0 7/8"6' - 0 7/8"
18' - 1 1/8"3' - 1 7/8" 1' - 8 1/8"
3' - 2
"4'
- 0"
VIF
2' - 5
1/2"
1' - 8 1/8" 6' - 0" 4' - 0 1/4" 8' - 0" 4' - 0 1/4"VIF
3' - 11 3/4" +/-CL CL CL CL CL
40A9.1.1
TYP.13
A9.1.1
TYP.
7' - 1
1"1'
- 2"
EXISTING DOOR, FRAMING, AND GLASS TO REMAIN.
RIGID WALL PROTECTION EXISTING TO REMAIN
NEW WALL MOUNTED CAMERA. REFER TO AV & ELECTRICAL DRAWINGS.
NEW WALL MOUNTED DIGITAL CLOCK/TIMER. REFER TO AV & ELECTRICAL DRAWINGS FOR DETAILS.
NEW 65" FLAT SCREEN ON FIXED MOUNT. REFER TO AV & ELECTRICAL DRAWINGS.
ALL EXPOSED DRYWALL TO BE PAINTED.
4' X 3'-6" WHITEBOARD WITH MARKER TRAY
"QUIET PLEASE. RECORDING IN PROGRESS" SIGN INSET INTO EXISTING SIDELITE. SIGN TO FACE CORRIDOR. REFER TO ELECTRICAL DRAWINGS.
RELOCATED COD MASTER CLOCK.
7' - 6
"
8' - 2
"
5' - 1
1"
EQ EQEQ EQ
8' - 2
"
VIF3' - 4 1/2" +/- EQ. 5' - 1 3/8" EQ.
4' - 6
"
3' - 2
"4'
- 0"
VIF
2' - 5
1/2"
A8.1.124
VIF4' - 2 1/8" +/-
CL CL
16A9.1.1
TYP.13
A9.1.1
TYP.
1' - 3
"3'
- 0 3/
8"2'
- 2 1/
4"
RIGID WALL PROTECTION EXISTING TO REMAIN
EXISTING DUPLEX TO REMAIN. REFER TO ELECTRICAL DRAWINGS.
NEW DIGITAL CLOCK/TIMER. REFER TO ELECTRICAL DRAWINGS. REFER TO AV & ELECTRICAL DRAWINGS.
4'X6' WHITEBOARD WITH MARKER TRAY
NEW AV PODIUM BY OWNER
ACOUSTIC WALL PANELS
EXISTING LIGHTING TO REMAIN
ALL EXPOSED DRYWALL (BELOW WALL PROTECTION AND BEHIND MONITOR) TO BE PAINTED.
EXISTING FIN. CEILING9'-7 1/2"
86" TOUCH MONITOR. REFER TO AV & ELECTRICAL DRAWINGS.
RESILIENT BASE, EXISTING TO REMAIN
EQ EQ
5' - 0
"
EQ.6' - 0"6' - 9"6' - 0"EQ.
VIF
2' - 5
1/2"
4' - 0
"3'
- 2"
CL CL CL CL
16A9.1.1
TYP.13
A9.1.1
TYP.
8' - 2
"
EXISTING DUPLEX TO REMAIN. NEW DUPLEX AND USB PORTS, REFER
TO ELECTRICAL DRAWINGS
NEW WALL MOUNTEDDIGITAL CLOCK/TIMER, REFER TO
AV & ELECTRICAL DRAWINGS.
NEW WALL MOUNTEDCAMERA, REFER TO AV & ELECTRICAL DRAWINGS.
RESILIENT BASE, EXISTING TO REMAIN
ACOUSTIC WALL PANELSNEW 50" FLAT SCREEN
ON ARTICULATING MOUNT. REFER TO AV & ELECTRICAL DRAWINGS.
ALL EXPOSED DRYWALL (BEHIND TV MONITOR AND BELOW WALL PROTECTION) TO BE PAINTED.
EXISTING FIN. CEILING9'-7 1/2"
RIGID WALL PROTECTION, EXISTING TO REMAIN
NEW DUPLEX AND USB PORTS. REFER TO ELECTRICAL DRAWINGS.
4'-0" X 6'-0" WHITE BOARD
EXISTING FIRE ALARM TO REMAIN
5' - 0
"
7' - 4 7/8"
17' - 5 1/8"
7' - 6
"
8' - 2
"
2' - 5 1/2" 6' - 0" 4' - 0 1/4" 6' - 0" 4' - 0 1/4"VIF
5' - 3 3/4" +/-
3' - 2
"4'
- 0"
VIF
2' - 5
1/2"
CL CL CL CL CL
16A9.1.1
TYP. 13A9.1.1
TYP.
7 1/4"
2' - 5
1/2"
11 1/
4"
4' - 6
"1"
10 5/
8"
1/2"VIF11" 1/2"
CLEAR GLASS SIGN WITH ETCHED WRITING AND EDGE LIT CLEAR ANODIZED EXTRUSION. REFER TO ELECTRICAL FOR DETAILS.
EXISTING SIDELITE
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FOR CONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage – Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/13/2
021 1
1:32:1
6 AM
INTERIOR ELEVATIONS
A8.1.1
STAR
T Sh
eet
13340.000
GENERAL SHEET NOTES
SCALE: 1/4" = 1'-0"67 EAST ELEVATION (TEACHING WALL)
SCALE: 1/4" = 1'-0"18 SOUTH ELEVATIONSCALE: 1/4" = 1'-0"42 NORTH ELEVATION
SCALE: 1/4" = 1'-0"66 WEST ELEVATION
SCALE:72 CLASSROOM 1463 LOOKING NORTHSCALE:48 CLASSROOM 1463 LOOKING SOUTH
SCALE: 1" = 1'-0"24 SIGNAGE ELEVATION
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
EXISTING PARTITION
Z- CLIPS, SPACEDPER MANUFACTURER'S RECOMENDATIONS
TYP.1"
WHITEBOARD INSTALLED PER MANUFACTURER RECOMENDATIONS
TYP.1"
Z- CLIPS, SPACEDPER MANUFACTURER'S RECOMENDATIONS
ACOUSTIC PANEL AS SPECIFIED
SQUARE EDGE
EXISTING CEILING
PAINT DRYWALL AT EXPOSED JOINTS, TYP.
TYP.2"
ACOUSTIC PANEL AS SPECIFIED, REFER TO A9.1.1 FOR DETAILS
TYP.2"
ACOUSTIC PANEL AS SPECIFIED, REFER TO A9.1.1 FOR DETAILS
REPAIR EXISTING WALL CONSTRUCTION TO MATCH ADJACENT EXISTING, PATCH AND PAINT TO MATCH EXISTING AS NECESSARY FOR INSTALLATION OF NEW EQUIPMENT
RECESSED BACKBOX AS SPECIFIED, PROVIDE BLOCKING AS NECESSARY AND TWO (2) LAYERS 5/8" GYP. BD. AROUND OPENING.
NEW MONITOR ON FIXED MOUNT. REFER TO AV DRAWINGS.
PAINT DRYWALL AT EXPOSED JOINTS, TYP.
MANUAL PROJECTION SCREEN SUSPENDED FROM BRACKET AS SPECIFIED. COORDINATE MOUNTING WITH A/V EQUIPMENT SELECTIONS.
FASTENERS SPACED PER MANUFACTURER RECOMMENDATIONS
ACOUSTIC WALL PANEL, REFER TO DETAILS SHEET A9.1.1
PROVIDE FIRE RETARDANT TREATED WOOD BLOCKING IN WALL AS NEEDED FOR PROJECTOR AND SCREEN MOUNTING
WALL MOUNTED SHORT THROW PROJECTOR AS SPECIFIED
EXISTING WALL CONSTRUCTION
FASTENERS SPACED PER MANUFACTURER RECOMMENDATIONS
REPAIR EXISTING WALL CONSTRUCTION TO MATCH ADJACENT EXISTING, PATCH AND PAINT TO MATCH EXISTING AS NECESSARY FOR INSTALLATION OF NEW EQUIPMENT
TYP.1"
EXISTING CEILING
TYP.1"
PAINT DRYWALL AT EXPOSED JOINTS, TYP.
ACOUSTIC WALL PANEL BEYOND.
NEW WHITEBOARD AS SPECIFIED.
EXISTING PARTITION TO REMAIN
PANEL AS SPECIFIED
SQUARE EDGE
Z- CLIPS, SPACEDPER MANUFACTURER'S RECOMENDATIONS
1"
1. ALL WOOD BLOCKING TO BE FIRE RETARDANT TREATED.
PANEL AS SPECIFIED
SQUARE EDGE
Z- CLIPS, SPACEDPER MANUFACTURER'S RECOMENDATIONS
ALIGN
EXISTING PARTITION TO REMAIN
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FOR CONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage – Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/13/2
021 1
1:32:1
7 AM
INTERIOR DETAILS
A9.1.1
STAR
T Sh
eet
13340.000
SCALE: 3" = 1'-0"16 ACOUSTIC PANEL DETAILS
SCALE: 3" = 1'-0"13 MONITOR MOUNTING DETAIL
SCALE: 3" = 1'-0"40 PROJECTOR MOUNTING DETAIL
SCALE: 3" = 1'-0"37 ACOUSTIC PANEL PLAN DETAIL - INSIDE CORNER
GENERAL SHEET NOTES
SCALE: 3" = 1'-0"29 ACOUSTIC PANEL PLAN DETAIL - OUTSIDE CORNERISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
H
H
H
H
H
H
HH
H
H
H
H
H
H
H
HH
H
H
H
H
H
H
H
HH
H
A. REFER TO THE A0.X SERIES SHEETS FOR ARCHITECTURAL GENERAL NOTES, DRAWING, REFERENCE AND MATERIAL SYMBOLS, ABBREVIATIONS, AS WELL AS DIMENSIONING CONVENTIONS USED ON THIS SHEET.
B. COORDINATE ALL FURNITURE LOCATIONS AND DIMENSIONS WITH FURNITURE VENDOR.
C. COORDINATE LOCATION OF ELECTRICAL CONNECTIONS WITH FINAL FURNITURE LAYOUT.
D. FURNITURE SHOWN IS FOR REFERENCE ONLY AND OFOI.
21A 21B 22
14
13
21A 21B 22
14
13
21A 21B 22
14
13
NOT IN CONTRACT (NIC)
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FOR CONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage – Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/13/2
021 1
1:32:1
8 AM
LEVEL 01 - ROOM 1463 -FURNITURE
CONFIGURATION PLANS
AI2.1.1
STAR
T Sh
eet
13340.000
GENERAL SHEET NOTES
SCALE: 1/4" = 1'-0"69 LEVEL 01 - FURNITURE PLAN - GROUPSSCALE: 1/4" = 1'-0"45 LEVEL 01 - FURNITURE PLAN - LECTURE EAST
SCALE: 1/4" = 1'-0"29 LEVEL 01 - FURNITURE PLAN - LECTURE NORTH
PROJECT NORTHPROJECT NORTH PROJECT NORTH
GRAPHIC LEGEND
22 SEATS
22 SEATS22 SEATS
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
ELECTRICAL POWER SYMBOLS
J JJ
SR-X
6-30R
JUNCTION BOX (CEILING, FLOOR OR WALL MOUNTED) INDICATED IN POWER, LIGHTING & FIRE ALARM SYSTEMS PLANS.
SPECIAL PURPOSE RECEPTACLE. TYPE AS INDICATED ON DRAWINGS. COORDINATE RECEPTACLE TYPE WITH ACTUAL EQUIPMENT PRIOR TO INSTALLATION.
QUADRUPLEX RECEPTACLE, (2) 20A, 125V, 2P, 3W., FLOOR MTD SERVICE FITTING, FLUSH TYPE UON("S" DENOTES SURFACE TYPE)
DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)'H' SUBSCRIPT INDICATES HORIZONTAL ORIENTATION.
QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES WITH A COMMON FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
SURFACE RACEWAY ("X" DENOTES TYPE AS SPECIFIED)
P P
PD PD
POWER SERVICE FITTING (CEILING, FLOOR OR WALL MOUNTED) FOR CONNECTION TO FURNITURE SYSTEM AS SPECIFIED.
COMBINATION POWER AND TELECOMMUNICATIONS BOX (CEILING, FLOOR OR WALL MOUNTED) FOR POWER AND DATA CONNECTION INDICATED IN POWER & SPECIAL SYSTEMS PLANS.
WHERE INDICATED IN AN EXISTING FLOOR, PROVIDE CORE DRILL PACKAGE TO MAINTAIN FIRE RATING OF FLOOR. EXTEND CONDUIT AND WIRING IN CEILING SPACE OF FLOOR BELOW TO ELECTRICAL CLOSET OR PANELBOARD.
DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W., FLOOR MTD SERVICE FITTING, FLUSH TYPE UON("S" DENOTES SURFACE TYPE)
QUADRUPLEX IG RECEPTACLE, (2) 20A, 125V, 2P, 3W., FLOOR MTD SERVICE FITTING, FLUSH TYPE UON ("S" DENOTES SURFACE TYPE)
COMBINATION USB DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W WITH (2) 5VDC, 2.1A USB CHARGING PORTS
FULLY CONTROLLED DUPLEX/QUADRUPLEX RECEPTACLE. PROVIDE ALL WIRING, EQUIPMENT, POWER PACKS, AND OCCUPANCY SENSOR INTEGRATION REQUIRED TO TURN OFF RECEPTACLE(S) WHEN SPACE IS UNOCCUPIED.
HALF CONTROLLED DUPLEX/QUADRUPLEX RECEPTACLE. PROVIDE ALL WIRING, EQUIPMENT, POWER PACKS, AND OCCUPANCY SENSOR INTEGRATION REQUIRED TO TURN OFF HALF OF RECEPTACLE(S) WHEN SPACE IS UNOCCUPIED.
REFERENCE SYMBOLS
1
SECTION NUMBER
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
DRAWING NUMBER WHERE DRAWN
1E1-1.0 KEY NOTE
1E1-1.0
ELECTRICAL ABBREVIATIONS GENERAL NOTES
A. PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF THREE CIRCUITS PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.
B. PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.
C. COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN.
D. PROVIDE FIRE STOPPING FOR CONDUITS FOR WALLS AND CEILINGS TO MAINTAIN FIRE RATING.
E. INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE MANNER.
F. LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE DERATING FACTOR FOR ROOF-MOUNTED CONDUITS.
G. REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING MOUNTED DEVICES AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.
H. WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL PHONES) ARE INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A COMMON FACEPLATE.
I. WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES BETWEEN ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.
J. WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.
K. FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE PLANS PRIOR TO INSTALLATION.
L. MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE DRAWINGS AND IN MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.
M. THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC. PROVIDE ALL COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.
P
PD
TV AUIDO/VISUAL BACKBOX. CHIEF PAC525 OR EQUAL. PROVIDE (2) DUPLEX RECEPTACLE, (1) 3/4"C, (2) DATA DROP, (1) 1"C STUBBED INTO CEILING FOR AV USE.
C MASTER CLOCK OUTLET. COORDINATE REQUIREMENTS WITH OWNER FOR POWER AND DATA CONNECTION REQUIREMENTS
DATA OUTLET WITH 2 MODULAR JACKS ON COMMON FACE PLATE (PANDUIT CFPL2). 4-11/16" SQUARE EXTRA DEEP BACK BOX WITH 1-GANG MUD RING. PROVIDE 1"C STUBBED INTO CEILING.
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FOR CONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage – Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/13/2
021 1
1:32:1
9 AM
ELECTRICAL SYMBOLSAND ABBREVIATIONS
E0.1
Autho
r
13340.000
(M)MCA MINIMUM CIRCUIT AMPACITYMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMECH MECHANICALMFR MANUFACTURERMH MANHOLEMIN MINIMUMMISC MISCELLANEOUSMLO MAIN LUGS ONLYMOCP MAXIMUM OVERCURRENT PROTECTIONMTD MOUNTEDMTG MOUNTINGMTS MANUAL TRANSFER SWITCHMV MEDIUM VOLTAGE (OVER 600V LESS THAN 35KV)
(N)N NEUTRALNC NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATIONNIC NOT IN CONTRACTNO NORMALLY OPENNO., NUM. # NUMBERNTS NOT TO SCALE
(O)OC ON CENTEROCPD OVERCURRENT PROTECTION DEVICEOFCI OWNER FURNISHED, CONTRACTOR INSTALLEDOFOI OWNER FURNISHED, OWNER INSTALLEDOH OVERHEADOHE/T OVERHEAD ELECTRIC/TELEPHONEOPP OPPOSITE
(P)P POLEPA PUBLIC ADDRESSPB PULL BOXPDP POWER DISTRIBUTION PANELPE PHOTO ELECTRICPF POWER FACTORPH, Ø PHASEPNL PANELPRI PRIMARYPT POTENTIAL TRANSFORMERPVC POLYVINYL CHLORIDEPWR POWER
(Q)QTY QUANTITY
(R)R, RE RELOCATE AS SHOWNRCLP REMOTE CONTROL LIGHTING PANELRCPT RECEPTACLEREF REFRIGERATORRF RADIO FREQUENCYRLA RATED (RUNNING) LOAD AMPSRM ROOMRP RECEPTACLE PANELBOARDRSC RIGID STEEL CONDUIT
(S)SCH, SCHED SCHEDULESEC SECONDARYSF SQUARE FOOTSPD SURGE PROTECTIVE DEVICESPDT SINGLE POLE DOUBLE THROWSPEC(S) SPECIFICATION(S)SPKR SPEAKERSPST SINGLE POLE SINGLE THROWSTD STANDARDSW SWITCHSWBD SWITCHBOARDSWGR SWITCHGEARSYM SYMMETRICAL
(T)TB TERMINAL BLOCKTBB TELEPHONE BACKBOARDTC TIME CLOCKTEL, TELE TELEPHONETELECOM TELECOMMUNICATIONSTP TAMPERPROOFTV TELEVISIONTYP TYPICAL
(U)UG UNDERGROUNDUGP UNDERGROUND PRIMARYUGS UNDERGROUND SECONDARYUGT UNDERGROUND TELEPHONEUL UNDERWRITER'S LABORATORYUON UNLESS OTHERWISE NOTEDUPS UNINTERRUPTIBLE POWER SUPPLY
(V)V VOLTSVA VOLT-AMPERESVFD VARIABLE FREQUENCY DRIVE/ VARIABLE
FREQUENCY MOTOR CONTROLLER
(W)W WIREW/ WITHW/O WITHOUTWHM WATT HOUR METERWP WEATHERPROOF
(X)X REMOVE DEVICEXFMR TRANSFORMER
(Z)%Z PERCENT IMPEDANCE
(A)A AMPERESAC ALTERNATING CURRENTAF AMPERE FRAME (BREAKER RATING)AFC ABOVE FINISHED COUNTERAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAHU AIR HANDLING UNITAIC AMPERE INTERRUPTING CAPACITYALT ALTERNATEARCH ARCHITECTAT AMPERES TRIPATS AUTOMATIC TRANSFER SWITCHAUTO AUTOMATICAUX AUXILIARYAWG AMERICAN WIRE GAUGE
(B)BLDG BUILDINGBRKR, BKR BREAKER
(C)C CONDUITCATV CABLE TELEVISIONCB CIRCUIT BREAKERCCTV CLOSED CIRCUIT TELEVISIONCKT CIRCUITCLG CEILINGCOM, COMM COMMUNICATIONSCP CONTROL PANELCPT CONTROL POWER TRANSFORMERCT CURRENT TRANSFORMERCU COPPER
(D)DC DIRECT CURRENTDISC DISCONNECTDIST DISTRIBUTIONDIV DIVISIONDN DOWNDP DISTRIBUTION PANELDPDT DOUBLE POLE DOUBLE THROWDPST DOUBLE POLE SINGLE THROWDWG DRAWING
(E)E, EX, EXIST EXISTINGEG EQUIPMENT GROUNDELEC ELECTRIC, ELECTRICALEM. EMEG EMERGENCYEMT ELECTRIC METALLIC CONDUITENCL ENCLOSUREEQ, EQIP EQUIPMENTEWC ELECTRIC WATER COOLEREWH ELECTRIC WATER HEATER
(F)FA FIRE ALARMFAAP FIRE ALARM ANNUNCIATOR PANELFACP FIRE ALARM CONTROL PANELFC FOOT CANDLEFDR FEEDERFL, FLR FLOORFLA FULL LOAD AMPSFLEX FLEXIBLEFT FOOT / FEET (')
(G)G, GND, GRD GROUNDGFI GROUND FAULT INTERRUPTER
(H)H HORIZONTAL MOUNTINGHOA HAND-OFF-AUTOMATICHP HORSEPOWERHR HOURHT HEIGHTHTR HEATERHVAC HEATING VENTILATION AND AIR CONDITIONINGHZ HERTZ
(I)IG ISOLATED GROUNDIN INCH / INCHES (")
(J)JB, JBOX JUNCTION BOX
(K)K KEY INTERLOCKKcmil 1000 CIRCULAR milsKV KILOVOLTS (THOUSAND VOLTS)KVA KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)kW KILOWATTS (THOUSAND WATTS)KWH KILOWATT-HOURS
(L)L-G LINE TO GROUNDL-L LINE TO LINEL-N LINE TO NEUTRALLA LIGHTNING ARRESTORLAN LOCAL AREA NETWORKLC, LCP LIGHTING CONTROL PANELLP LIGHTING PANELLSI LONG-TIME, SHORT-TIME, INSTANTANEOUSLSIA LONG-TIME, SHORT-TIME,
INSTANTANEOUS,GROUND-FAULT ALARM ONLYLSIG LONG-TIME, SHORT-TIME,
INSTANTANEOUS,GROUND-FAULTLTG LIGHTINGLV LOW VOLTAGE (BELOW 50 VOLTS)
Notes:
Total Est. Demand: 9 ATotal Conn.: 9 A
Total Est. Demand: 3240 VAReceptacle 1080 VA 100.00% 1080 VA Total Conn. Load: 3240 VAEquipment 2160 VA 100.00% 2160 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 6 A 12 A 9 ATotal Load: 720 VA 1440 VA 1080 VA
83 SPARE 20 A 1 0 0 1 20 A SPARE 8481 SPARE 20 A 1 0 0 1 20 A SPARE 8279 SPARE 20 A 1 0 0 1 20 A SPARE 8077 SPARE 20 A 1 0 0 1 20 A SPARE 7875 SPARE 20 A 1 0 0 1 20 A SPARE 7673 SPARE 20 A 1 0 0 1 20 A SPARE 7471 SPARE 20 A 1 0 0 1 20 A SPARE 7269 SPARE 20 A 1 0 0 1 20 A SPARE 7067 SPARE 20 A 1 0 0 1 20 A SPARE 6865 SPARE 20 A 1 0 0 1 20 A SPARE 6663 SPACE -- 1 -- -- 1 -- SPACE 6461 SPACE -- 1 -- -- 1 -- SPACE 6259 SPACE -- 1 -- -- 1 -- SPACE 6057 SPACE -- 1 -- -- 1 -- SPACE 5855 SPACE -- 1 -- -- 1 -- SPACE 5653 SPACE -- 1 -- -- 1 -- SPACE 5451 SPACE -- 1 -- -- 1 -- SPACE 5249 SPACE -- 1 -- -- 1 -- SPACE 5047 SPACE -- 1 -- -- 1 -- SPACE 4845 SPACE -- 1 -- -- 1 -- SPACE 4643 SPACE -- 1 -- -- 1 -- SPACE 4441 SPARE 20 A 1 0 0 1 20 A SPARE 4239 SPARE 20 A 1 0 0 1 20 A SPARE 4037 SPARE 20 A 1 0 0 1 20 A SPARE 3835 SPARE 20 A 1 0 0 1 20 A SPARE 3633 RCPTS RM. 1463 (ST PROJECTOR) 20 A 1 360 0 1 20 A SPARE 3431 RCPTS RM. 1463 (USB) 20 A 1 720 0 1 20 A SPARE 3229 RCPTS RM. 1463 (MONITORS) S, W 20 A 1 1080 0 1 20 A EXISTING 3027 RCPTS RM. 1463 (MONITORS) N, E 20 A 1 1080 0 1 20 A EXISTING 2825 EXISTING 20 A 1 0 0 1 20 A EXISTING 2623 EXISTING 20 A 1 0 0 1 20 A EXISTING 2421 EXISTING 20 A 1 0 0 1 20 A EXISTING 2219 EXISTING 20 A 1 0 0 1 20 A EXISTING 2017 EXISTING 20 A 1 0 0 1 20 A EXISTING 1815 EXISTING 20 A 1 0 0 1 20 A EXISTING 1613 EXISTING 20 A 1 0 0 1 20 A EXISTING 1411 EXISTING 20 A 1 0 0 1 20 A EXISTING 129 EXISTING 20 A 1 0 0 1 20 A EXISTING 107 EXISTING 20 A 1 0 0 1 20 A EXISTING 85 EXISTING 20 A 1 0 0 1 20 A EXISTING 63 EXISTING 20 A 1 0 0 1 20 A EXISTING 41 EXISTING 20 A 1 0 0 1 20 A EXISTING 2
CKT Circuit Description Trip Poles A (VA) B (VA) C (VA) Poles Trip Circuit Description CKT
Enclosure: Type 1 MCB Rating: 225 AMounting: Surface Wires: 4 Bus Rating: 225 A
Supply From: Phases: 3 Mains Type: MLOLocation: ELECTRICAL 1468 Volts: 208Y/120 A.I.C. Rating:
Panelboard: (E)7L2
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
H
H
H
H
H
J
TV
TV
TV
TV
J
H
HTV
TV
H
H
J
C
J
DT
D
DT
J
21A 21B 22 23 23A
14
13
CLASSROOM1463
ELECTRICAL1468
TEACHING WALL(E)
(E)7H2
(E)7L2
PROVIDE BACK BOXES FOR CAMERA/CLOCK, EACH WITH CONDUIT STUBBED INTO CEILING. COORDINATE WITH TA-SERIES AND FINAL DEVICE LOCATION
DATA FOR TOUCHSCREEN
(E)
PROVIDE EXTENSION RING FOR FIRE ALARM DEVCE TO BRING FLUSH WITH WALL PANEL
(E)
(E) (E)
(E)
RELOCATE MASTER CLOCK CONNECTIONS
+106"AFF
2931
29
31
29
2731
33
27
31
27
PROVIDE BACK BOX FOR CLOCK, WITH CONDUIT STUBBED INTO CEILING. COORDINATE LOCATION WITH TA-SERIES AND FINAL DEVICE LOCATION
(E)
(R)
21A 21B 22 23 23A
14
13
CLASSROOM1463
ELECTRICAL1468
(E)7H2
QUITE PLEASE - RECORDING IN PROGRESS LIGHT, ZIKEN SIGNAGE, REFERENCE "2020-0731 COD ON AIR SIGNAGE."PROVIDE J-BOX AND DRIVER. ROUTE 12V #18 AWG WIRES THROUGH MULLION.
D1 D1 D1
D1
(E) (E)
(E)
PROVIDE NEW 5-GANG BOX TWO 3-WAY DIMMER SWITCHES AND TWO 3-WAY SWITCHES, PLUS NEW SWITCH FOR RECORDING IN PROGRESS LIGHT. PROVIDE EXTENSION RING AS REQUIRED TO BRING DEVICES FLUSH TO ACOUSTIC PANEL.
FIVE-GANG BOX WITH TWO 3-WAY DIMMER SWITCHES AND TWO 3-WAY SWITCHES
D1D1
D1
D1
D1
D1
ABOVE CEILING DATA OUTLET FOR MIC ARRAY. COORDINATE WITH TA-SERIES AND FINAL PRODUCT FOR CONNECTION AND LOCATION
NEW OCCUPANCY SENSOR TIED INTO NEW D1 FIXTURES.
a,b,k1,k2
k1 k1 k1 k1 k1
k2
k2
k2
k2
k2
11 11 11 11 11
11
11
11
11
11a,b,k1,k2
CONDUIT BANK ABOVE CEILING, TIGHT TO CEILING GRID. COORDINATE LOCATIONS AS REQUIRED.
(E)7L2
BASE BID: (10) TOTAL D1 AS INDICATEDALT 1 SCOPE: (6) TOTAL D1 AS OUTLINED
A. COORDINATE FINAL LOCATION OF BACK BOXES FOR CAMERAS, CLOCKS, AND RECEPTACLES WITH AV EQUIPMENT.
B. COORDINATE FINAL CONNECTION TO EQUIPMENT WITH MANUFACTURER'S REQUIREMENTS
C. DATA DEVICES ARE SHOWN FOR RACEWAY ONLY. COORDINATE NUMBER OF NETWORK DROPS WITH TECHNOLOGY DRAWINGS AND OWNER.
D. UTILIZE EXISTING SPARE BREAKERS FOR NEW CIRCUITSE. ARCHITECT TO APPROVE ALL DEVICE FINISHES DURING
SHOP DRAWING REVIEW.F. COORDINATE ALL DEVICE MOUNTING HEIGHTS WITH
ARCHITECTURAL DRAWINGS.G. ENSURE ALL RECEPTACLES ARE LOCATED SUCH THAT AT
LEAST ONE STUD IS LOCATE BETWEEN RECEPTACLES ON OPPOSITE FACES OF THE SAME WALL.
H. PROVIDE EXTRA DEEP MUD RINGS AS REQUIRED TO BRING DEVICES FLUSH WITH ACOUSTIC PANELS AS REQUIRED. DEVICES SHALL MAKE SOLID METAL TO METAL CONTACT BETWEEN DEVICE YOLK AND MUD RING.
I. ALL NETWORK DROPS AT PROJECTORS, CAMERAS, MIC ARRAYS, AND FLAT PANEL DISPLAYS TO ROUTE BACK TO AV RACK. PROVIDE PANDUIT PUP6004B-UY CABLE WITH ORANGE JACKET AND APPLICABLE PANDUIT ACCESSORIES, ORANGE COLOR, FOR A COMPLETE CONNECTED SYSTEM. COORDINATE WITH AV DRAWINGS FOR FINAL LOCATIONS AND REQUIREMENTS.
J. NEW LIGHTING TO BE FED FROM PANEL 7H2 AND NEW POWER TO BE FED FROM PANEL 7L2 IN ROOM 1468.BASE SCOPE: ALL (10) D1 FIXTURES AS INDICATEDDEDUCT ALTERNATE 1 SCOPE: (6) D1 FIXTURES AS OUTLINED
K. RETAIN EXISTING PENDANT LIGHT ZONING, INDICATED AS ZONES 'a' AND 'b' AND PROVIDE 3-WAY SWITCHES. PROVIDE ADDITIONAL WIRES AS REQUIRED FOR 3-WAY OPERATION. TRAVELLER CONDUCTOR SHALL BE A DIFFERENT COLOR THAN HOT CONDUCTOR.
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FOR CONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage – Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/13/2
021 1
1:32:2
0 AM
LEVEL 01 - ROOM 1463 -ELECTRICAL PLANS
E2.1.2
Autho
r
13340.000
SCALE: 1/4" = 1'-0"1 LEVEL 1 - POWER PLANSCALE: 1/4" = 1'-0"2 LEVEL 1 - ROOM 1463 - REFLECTED CEILING PLAN Copy 2
GENERAL SHEET NOTES
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
LIGHTING FIXTURE SCHEDULETYPE DESCRIPTION MANUFACTURER MODEL LOAD LAMP BALLAST VOLTAGE MOUNTING COMMENTS TYPE
4' DIRECT/INDIRECT PENDANT EXISTING EXISTING 51 VA 2-LAMP T8 ELECTRONIC 277 V PENDANT EXISTINGD1 ONE LIGHT RECESSED ACCENT LUMINAIRE WITH RETRACTABLE YOKE-MOUNTED GIMBAL KEY LIGHT LF ILLUMINATION MN31BN-S-13C-8040-V-RG-DMU-WW 13 VA LED 0-10V DIMMING 277 V RECESSED CONFIRM FINISH WITH ARCHITECT. AIM AT 45 DEGRESS DOWN AND TOWARDS WALL AS INSTALLED AIMING. D1
ABBREVIATIONS
ANSI - AMERICAN NATIONAL STANDARDS INSTITUTE
ATC - AUDIO TELECONFERENCE
AV - AUDIO VIDEO
AVC - AUDIO VIDEO CONTRACTOR
AWG - AMERICAN WIRE GAUGE
DC - DATA/LOW VOLTAGE CONTRACTOR
DSP - AUDIO DIGITAL SIGNAL PROCESSOR
EC - ELECTRICAL CONTRACTOR
GC - GENERAL CONTRACTOR
IEEE - INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS
MAP - MIDDLE ATLANTIC PRODUCTS, INC
NEC - NATIONAL ELECTRIC CODE
NRTL - NATIONALLY RECOGNIZED TESTING LAB
OFE - OWNER FURNISHED EQUIPMENT
STP - SHIELDED TWISTED PAIR
UL - UNDERWRITER'S LABORATORY
UTP - UNSHIELDED TWISTED PAIR
VIF - VERIFY IN FIELD
VTC - VIDEO TELECONFERENCE
DRAWING SCHEDULE
SHEETNO. SHEET NAME ISSUE DATE
TA0.00 COVER SHEET, GENERAL NOTES, AND LEGENDS 2 9/13/2021
TA0.01 ELEVATIONS 2 9/13/2021
TA0.02 INSTALLATION DETAILS 2 9/13/2021
TA0.03 CONDUIT RISER 2 9/13/2021
TA0.04 CONCEPTUAL VIDEO FLOW 2 9/13/2021
TA0.05 CONCEPTUAL AUDIO & CONTROL FLOW 2 9/13/2021
TA1.01 AV FLOORPLANS AND RCPS 2 9/13/2021
GENERAL NOTES
1. GEM BOXES ARE UNACCEPTABLE FOR AV SYSTEM USE.2. ALL CONDUIT SHALL BE 3 4" DIAMETER UNLESS OTHERWISE
NOTED.3. ALL CONDUIT SHOWN IS FOR AV SYSTEM USE ONLY.4. A PULL STRING SHALL BE INSTALLED IN EACH CONDUIT FOR
USE BY THE AVC.5. ALL CONDUIT SHALL BE INSTALLED PER NEC AND ANY
APPLICABLE LOCAL CODES.6. IF LOCAL CODES ALLOW, CONDUIT STUBS TO ACCESSIBLE
CEILINGS ARE ACCEPTIBLE.7. NO CONDUIT SIZES SHALL BE REDUCED WITHOUT EXPRESS
WRITTEN DIRECTION FROM THE AVC.8. AC DESIGNATIONS ARE FOR REFERENCE ONLY.9. SPEAKER LOCATIONS ARE APPROXIMATE; SPEAKERS ARE TO
BE ALIGNED WITH LIGHT FIXTURES AND OTHER CEILINGDEVICES IN AN AESTHETICALLY PLEASING MANNER.
INSTALL CABLE SCHEDULE
ID DESCRIPTION RISER CABLE PLENUM CABLE
A1 MIC/LINE CABLE, TWISTED PAIR 22AWG WITH SHIELD AND DRAIN WIRE WEST PENN 77291 WEST PENN D25291
A2 SPEAKER CABLE 70V, TWISTED PAIR 18AWG WEST PENN 224 WEST PENN 25224BN1 NETWORK CABLE, CAT-6 U/UTP PANDUIT PUR6004*-W PANDUIT PUP6004*W
V1 NETWORK CABLE, CAT-6 F/UTP WINDY CITY WIRECAT6AS-GRY
WINDY CITY WIRECAT6ASP-WHT
PREMADE CABLE SCHEDULE
ID DESCRIPTION MANUFACTURER PART NUMBER
NET1 CAT-6 PATCH CORD, UTP, 7' LENGTH CABLES TO GO (C2G) 27142
VID1 HDMI CABLE CAPABLE OF 4K @ 60HZ (4:4:4), 6' LENGTH CABLES TO GO (C2G) 56783VID2 HDMI CABLE CAPABLE OF 4K @ 60HZ (4:4:4), 15' LENGTH CABLES TO GO (C2G) 50612
EQUIPMENT SCHEDULE
TAG MAKE MODEL DESCRIPTION OWNER FURNISHED SUBSTITUTIONS?
AMP-01 QSC SPA2-60 2 CH AMPLIFIER, 60W PER CHANNEL, BRIDGE FOR 70V NO ALLOWED
CAM-01QSC PTZ-IP 12X72 PTZ CAMERA NO NOQSC PTZ-WMB1 WALLMOUNT BRACKET FOR PTZ CAMERA NO NO
CAM-02 TBD TBD DOCUMENT CAMERA YES N/A
CON-01EXTRON 60-1912-01 IPCP PRO 350XI CONTROL PROCESSOR NO NOEXTRON 60-604-11 RSB 126 RACK SHELF NO ALLOWED
DA-01 EXTRON 60-1438-01 DTP HD DA8 4K 230 NO NODSP-01 QSC QSC CORE FLEX QSYS CORE WITH 8 FLEX IO, 8X8 SOFTWARE DANTE NO NOMIC-01 SHURE MXA 910A CEILING MICROPHONE ARRAY NO NOMNT-01 PEERLESS SUA761P MEDIUM THIN ARTICULATING DISPLAY MOUNT NO NOMNT-02 PEERLESS SUF660P ULTRA-THIN FIXED LARGE DISPLAY MOUNT NO NOMNT-03 PEERLESS SF680 FIXED EXTRA-LARGE DISPLAY MOUNT NO NOMON-01 SHARP PN-UH501 50" DISPLAY NO NOMON-02 SHARP PN-HB651 65" DISPLAY NO NOMON-03 LG 86TR3DJ0B 86" INTEGRATED TOUCH DISPLAY NO NOMON-04 TBD TBD LECTERN MONITOR YES N/ANSW-01 NETGEAR GS724TPP POE+ UNMANAGED NETWORK SWITCH NO ALLOWEDPLT-01 EXTRON 70-726-63 WPD 110 A HDMI WALLPLATE NO ALLOWEDRCK-01 TBD TBD CUSTOM LECTERN WITH BUILT-IN EQUIPMENT RACK YES N/ARX-01 EXTRON 60-1271-13 DTP HDMI 4K 230 RX RECEIVER UNIT NO NO
SCR-01 DA-LITE 85324 106"D (92"W X 52"H) 16:9 MANUAL PROJECTION SCREEN NO NOSP-01 EXTRON 60-1310-03 SF 26CT CEILING SPEAKERS NO NOTP-01 EXTRON 60-1787-02 12" TOUCH SCREEN, POE NO NOTP-01 EXTRON 70-690-01 BB 700M BACK BOX FOR 12" TOUCH SCREEN NO NOTP-02 APPLE iPAD IPAD FOR SYSTEM CONTROL YES N/A
VP-01EPSON POWERLITE 800F ULTRA-SHORT-THROW PROJECTOR NO NOEPSON ELPMB62 ULTRA-SHORT-THROW PROJECTOR WALL MOUNT NO NO
VSW-01 EXTRON 60-1484-01 SW4 HD 4K 4X1 HDMI VIDEO SWITCHER NO NOWLS-01 MERSIVE SP-8000-E3 SOLSTICE POD WIRELESS PRESENTATION SYSTEM NO NO
4020 GRAND AVEWESTERN SPRINGS, IL 60558708.505.9886www.axent-av.com
C:\Users\bstanley\SmithGroup Companies Inc\PRJ - 13340 - SmithGroup - SmithGroup\CAD\08 Architecture\2021-0909 Exports for Axent\13340-000-A-LOGO-2440571.JPG
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FORCONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage - Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/9/20
21 11
:18:03
AM
LEVEL 01 - ROOM 1463 -AV SYSTEM
COVER SHEETGENERAL NOTES
SCHEDULES
TA0.00
STAR
T Sh
eet
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
C:\__\COD\Speech Lab 2\Drawings\ta00.dwg, 9/13/2021 7:06:18 PM, AutoCAD PDF (General Documentation).pc3
12:00
1'-034"
913 16"
EAST
3'-814"
2'-112"
3'-814"
2'-112"
+48" AFF
+60" AFF
+90" AFF
+98" AFF
+109" AFF
+18" AFF
1'
EAST
1'-4" 1'-4"
+48" AFF
+60" AFF
+90" AFF
+98" AFF
+109" AFF
+18" AFF
1'-4"
+60" AFF
+98" AFF
3'-91116"
12:00
6'-5 116"
+60" AFF
+98" AFF
1'-4"1'-4"
+60" AFF
+90" AFF
+98" AFF
+18" AFF
12:00
3'-814"
2'-112"
3'-814"
2'-112"
+60" AFF
+90" AFF
+98" AFF
+18" AFF
4'-9 516"
2'-81116"
12:00
+90" AFF
+98" AFF
+71" AFF
1'-4"+90" AFF
+98" AFF
+71" AFF
4020 GRAND AVEWESTERN SPRINGS, IL 60558708.505.9886www.axent-av.com
C:\Users\bstanley\SmithGroup Companies Inc\PRJ - 13340 - SmithGroup - SmithGroup\CAD\08 Architecture\2021-0909 Exports for Axent\13340-000-A-LOGO-2440571.JPG
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FORCONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage - Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/9/20
21 11
:18:03
AM
LEVEL 01 - ROOM 1463 -AV SYSTEM
ELEVATIONS
TA0.01
STAR
T Sh
eet
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
Scale: 1/2":1'0"EAST WALL DISPLAY ELEVATION1
MON-01
MNT-01
Scale: 1/2":1'0"EAST WALL INFRASTRUCTURE ELEVATION2
VM
WP
Scale: 1/2":1'0"NORTH WALL DISPLAY ELEVATION3 Scale: 1/2":1'0"
NORTH WALL INFRASTRUCTURE ELEVATION4
Scale: 1/2":1'0"WEST WALL DISPLAY ELEVATION5 Scale: 1/2":1'0"
WEST WALL INFRASTRUCTURE ELEVATION6
Scale: 1/2":1'0"SOUTH WALL DISPLAY ELEVATION7 Scale: 1/2":1'0"
SOUTH WALL INFRASTRUCTURE ELEVATION8
TP-01
CAM-01
CLK-01
MON-01
MNT-01
VP-01MNT-04
SCR-01
PLT-01 PLT-01
PLT-01
MON-01CENTER DISPLAYIN OPENING
MNT-01
MON-01CENTER DISPLAYIN OPENING
MNT-01
CLK-01
MON-03CENTER DISPLAYIN OPENING
MNT-03
CAM-01
CLK-01
CAM-01
CLK-01
PLT-01
MON-02CENTER DISPLAYIN OPENING
MNT-02
CM
CL
TP
VP
VM
WP
CL
CL
CL
CM
CM
VM
VM VM
VM
WP WP
OPENING INWALL TREAMENT
OPENING INWALL TREAMENT
OPENING INWALL TREAMENT
OPENING INWALL TREAMENT
OPENING INWALL TREAMENT
OPENING INWALL TREAMENT
BACKING TO SUPPORT50 LBS W/ 5:1 SAFETY
BACKING TO SUPPORT50 LBS W/ 5:1 SAFETY
BACKING TO SUPPORT50 LBS W/ 5:1 SAFETY
BACKING TO SUPPORT50 LBS W/ 5:1 SAFETY
BACKING TO SUPPORT50 LBS W/ 5:1 SAFETY
BACKING TO SUPPORT85 LBS W/ 5:1 SAFETY
C:\__\COD\Speech Lab 2\Drawings\ta00.dwg, 9/13/2021 7:06:19 PM, AutoCAD PDF (General Documentation).pc3
PIN 1PIN 2PIN 3
WHT/ORG
ORG
WHT/GRN
ORG
WHT/BLUPIN 4PIN 5PIN 6PIN 7PIN 8
WHT/GRN
PIN 1PIN 2PIN 3PIN 4PIN 5PIN 6PIN 7PIN 8
BLU
GRN
WHT/BRN
BRN
BLU
WHT/BLU
GRN
WHT/BRN
BRN
WHT/ORG
PIN 1PIN 2PIN 3
WHT/ORG
ORG
WHT/GRN
ORG
WHT/BLU
SHIELDEDRJ45
PIN 4PIN 5PIN 6PIN 7PIN 8
WHT/GRN
PIN 1PIN 2PIN 3
SHIELDEDRJ45
PIN 4PIN 5PIN 6PIN 7PIN 8
BLU
GRN
WHT/BRN
BRN
BLU
WHT/BLU
GRN
WHT/BRN
BRN
WHT/ORG
SHDSHDSHD SHD
Scale: ntsUNSHIELDED T568B4
Scale: ntsSHIELDED T568B5
Scale: 1 1/2":1'0"CEILING SPEAKER DETAIL1
SPEAKER CABLING
USE HOOKS OR RINGS TOSUPPORT SPEAKER CABLINGEYEBOLT OR ANCHOR
POINT IN STRUCTURE.
TILE BRIDGE PERMANUFACTURERINSTRUCTIONS
Scale: 1 1/2":1'0"CEILING MICROPHONE DETAIL2
CAT-6 PATCH
USE HOOKS OR RINGS TOSUPPORT MIC CABLING
SHUREMXA910W-US
INSTALL RUBBER PADSPER MANUFACTURERINSTRUCTIONS
EYEBOLT ORANCHOR POINTIN STRUCTURE
FOR SAFETY CABLE
PANDUITNK2BXWH-A
EXTRON SF 26CT
SPEAKER CABLING
USE HOOKS OR RINGS TOSUPPORT SPEAKER CABLINGEYEBOLT OR ANCHOR
POINT IN STRUCTURE.
TILE BRIDGE PERMANUFACTURERINSTRUCTIONS
Scale: 1 1/2":1'0"CAMERA DETAIL3
0.75" CONDUIT STUBTO ACCESSIBLECEILING
2 GANG JUNCTIONBOX
QSCCAMERAMOUNT
QSC PTZ-IP 12X72
PANDUITNK2BXWH-A
CAT-6 PATCH
USE HOOKS OR RINGS TOSUPPORT MIC CABLING
4020 GRAND AVEWESTERN SPRINGS, IL 60558708.505.9886www.axent-av.com
C:\Users\bstanley\SmithGroup Companies Inc\PRJ - 13340 - SmithGroup - SmithGroup\CAD\08 Architecture\2021-0909 Exports for Axent\13340-000-A-LOGO-2440571.JPG
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FORCONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage - Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/9/20
21 11
:18:03
AM
LEVEL 01 - ROOM 1463 -AV SYSTEM
ELEVATIONS
TA0.02
STAR
T Sh
eet
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
C:\__\COD\Speech Lab 2\Drawings\ta00.dwg, 9/13/2021 7:06:20 PM, AutoCAD PDF (General Documentation).pc3
Scale: 1/2":1'0"CLASSROOM CONDUIT RISER1
EXISTING 2" C.STUB TO CLNG
VM
CACLCL
NEW 0.75" C.STUB TO CLNG
NEW 0.75" C.STUB TO CLNG
WP
1.00" CONDUIT
VM
WP
VM
WP
VM
WP
CLCLCA CA
VMVM
VP
4020 GRAND AVEWESTERN SPRINGS, IL 60558708.505.9886www.axent-av.com
C:\Users\bstanley\SmithGroup Companies Inc\PRJ - 13340 - SmithGroup - SmithGroup\CAD\08 Architecture\2021-0909 Exports for Axent\13340-000-A-LOGO-2440571.JPG
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FORCONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage - Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/9/20
21 11
:18:03
AM
LEVEL 01 - ROOM 1463 -AV SYSTEM
CONDUIT RISER
TA0.03
STAR
T Sh
eet
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
C:\__\COD\Speech Lab 2\Drawings\ta00.dwg, 9/13/2021 7:06:20 PM, AutoCAD PDF (General Documentation).pc3
DTP DA
DA-01
LECTERN EQUIPMENT RACK
OWNER FURNISHEDPRESENTATION PC
PC-01
DTP RECEIVER
RX-01
SHORT THROW
VP-01V1
RJ45S DTPRJ45SDTP 1
WIRELESS PRESENTATION
WLS-01
SHORT THROW PROJECTOR LOCATION
DTP RECEIVER
RX-01
86" TOUCH DISPLAY
MON-03
WIRELESS PRESENTATION
WLS-01
TOUCH DISPLAY LOCATION
DTP RECEIVER
RX-01
65" DISPLAY
MON-02
WIRELESS PRESENTATION
WLS-01
CONFIDENCE DISPLAY LOCATION
DTP RECEIVER
RX-01
HDMIHDMI
50" DISPLAY
MON-01
HDMI HDMI 1
VID1
A1
WIRELESS PRESENTATION
WLS-01
DISPLAY #1 LOCATION
PHXCOM DB9 RS232
HDMIHDMI HDMI HDMI 2
VID1
DTP RECEIVER
RX-01
50" DISPLAY
MON-01
WIRELESS PRESENTATION
WLS-01
DISPLAY #2 LOCATION
DTP RECEIVER
RX-01
50" DISPLAY
MON-01
WIRELESS PRESENTATION
WLS-01
DISPLAY #3 LOCATION
DTP RECEIVER
RX-01
50" DISPLAY
MON-01
WIRELESS PRESENTATION
WLS-01
DISPLAY #4 LOCATION
HDMIHDMI HDMI HDMI 1
VID1
A1
PHXCOM DB9 RS232
HDMIHDMI HDMI HDMI 2
VID1
HDMIHDMI HDMI HDMI 1
VID1
A1
PHXCOM DB9 RS232
HDMIHDMI HDMI HDMI 2
VID1
HDMIHDMI HDMI HDMI 1
VID1
A1
PHXCOM DB9 RS232
HDMIHDMI HDMI HDMI 2
VID1
HDMIHDMI HDMI HDMI 1
VID1
A1
PHXCOM DB9 RS232
HDMIHDMI HDMI HDMI 2
VID1
HDMIHDMI HDMI HDMI 1
VID1
A1
PHXCOM DB9 RS232
HDMIHDMI HDMI HDMI 2
VID1
HDMIHDMI HDMI HDMI 1
VID1
A1
PHXCOM DB9 RS232
HDMIHDMI HDMI HDMI 2
VID1
HDMIMON 1 HDMI HDMI IN
VID1
OWNER FURNISHEDLECTERN MONITOR
MON-04
HDMIHDMI OUT HDMI HDMI 1
VID1
HDMI SWITCHER
VSW-01
HDMIHDMI OUT HDMI HDMI IN
VID1
OWNER FURNISHEDDOC CAM
CAM-02
HDMIHDMI OUT HDMI HDMI 1
VID1
WIRELESS PRESENTATION
WLS-01
HDMIHDMI HDMI HDMI 1
VID1
OWNER FURNISHEDRECORDING PC
PC-02
HDMIHDMI HDMI HDMI 1
VID1
WALL PLATE
PLT-01
HDMIHDMI HDMI HDMI
VID2
WALL PLATE
PLT-01
HDMIHDMI HDMI HDMI
VID2
WALL PLATE
PLT-01
HDMIHDMI HDMI HDMI
VID2
WALL PLATE
PLT-01
HDMIHDMI HDMI HDMI
VID2
V1
RJ45S DTPRJ45SDTP 2
V1
RJ45S DTPRJ45SDTP 3
V1
RJ45S DTPRJ45SDTP 4
V1
RJ45S DTPRJ45SDTP 5
V1
RJ45S DTPRJ45SDTP 6
V1
RJ45S DTPRJ45SDTP 7
4020 GRAND AVEWESTERN SPRINGS, IL 60558708.505.9886www.axent-av.com
C:\Users\bstanley\SmithGroup Companies Inc\PRJ - 13340 - SmithGroup - SmithGroup\CAD\08 Architecture\2021-0909 Exports for Axent\13340-000-A-LOGO-2440571.JPG
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FORCONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage - Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/9/20
21 11
:18:03
AM
LEVEL 01 - ROOM 1463 -AV SYSTEM
CONCEPTUALVIDEO FLOW
TA0.04
STAR
T Sh
eet
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
C:\__\COD\Speech Lab 2\Drawings\ta00.dwg, 9/13/2021 7:06:21 PM, AutoCAD PDF (General Documentation).pc3
LECTERN EQUIPMENT RACK
12" TOUCHSCREEN
TP-01
AUDIO DSP
DSP-01
PHX FLX 1/2
70V AMPLIFIER
AMP-01
PHX CH 1PHXFLX 8
A1
70V CEILING SPEAKERQTY 4SP-01
PHX CH 1TERM70V OUT
A2
ETHERNET SWITCH
NSW-01
RJ45 PORT 1RJ45LAN A
NET1
CONTROLLER
CON-01
RJ45 PORT 3RJ45AV LAN
NET1
RJ45 LAN
CLIENT LANVIA EXISTING
FLOORBOX
OWNER FURNISHEDPRESENTATION PC
PC-01
RJ45 LAN
CLIENT LANVIA EXISTING
FLOORBOXOWNER FURNISHED
RECORDING PC
PC-02
RJ45 LAN
CLIENT LANVIA EXISTING
FLOORBOX
TRSAUD
AUD1
PHX FLX 3/4TRSAUD
AUD1
USB3 USBUSB3USB3
USB1
OWNER FURNISHEDRECORDING PC
PC-02
PHX FLX 5/6TRSAUD
AUD1
RJ45 PORT 2RJ45LAN
NET1
RJ45 PORT 4RJ45LAN
N1
PTZ CAMERA
CAM-01
RJ45 PORT 5RJ45LAN
N1
PTZ CAMERA
CAM-01
RJ45 PORT 6RJ45LAN
N1
PTZ CAMERA
CAM-01
RJ45 PORT 7RJ45LAN
N1
MICROPHONE ARRAY
MIC-01
RJ45 PORT 8RJ45LAN
N1
MICROPHONE ARRAY
MIC-01
RJ45 PORT 9RJ45LAN
N1
CLOCK INTERFACE
CLK-02N1
SOUTH WALLCLOCK
CLK-01
WEST WALLCLOCK
CLK-01
EAST WALLCLOCK
CLK-01
NORTH WALLCLOCK
CLK-01
PHXCOM 1
N1
RJ45 INRJ45OUT 2 RJ45 RS422
RJ45OUT 3 RJ45 RS422
RJ45OUT 4 RJ45 RS422
RJ45OUT 5 RJ45 RS422
N1
SHORT THROW PROJECTORWIRELESS PRESENTATION
WLS-01
RJ45PORT 10 RJ45 LAN
N1
86" TOUCH DISPLAYWIRELESS PRESENTATION
WLS-01
RJ45PORT 11 RJ45 LAN
N1
CONFIDENCE DISPLAYWIRELESS PRESENTATION
WLS-01
RJ45PORT 12 RJ45 LAN
N1
SHORT THROW PROJECTORDISPLAY #1
WLS-01
RJ45PORT 13 RJ45 LAN
N1
SHORT THROW PROJECTORDISPLAY #2
WLS-01
RJ45PORT 14 RJ45 LAN
N1
SHORT THROW PROJECTORDISPLAY #3
WLS-01
RJ45PORT 15 RJ45 LAN
N1
SHORT THROW PROJECTORDISPLAY #4
WLS-01
RJ45PORT 16 RJ45 LAN
4020 GRAND AVEWESTERN SPRINGS, IL 60558708.505.9886www.axent-av.com
C:\Users\bstanley\SmithGroup Companies Inc\PRJ - 13340 - SmithGroup - SmithGroup\CAD\08 Architecture\2021-0909 Exports for Axent\13340-000-A-LOGO-2440571.JPG
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FORCONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage - Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/9/20
21 11
:18:03
AM
LEVEL 01 - ROOM 1463 -AV SYSTEM
CONCEPTUALAUDIO & CONTROL
FLOW
TA0.05
STAR
T Sh
eet
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
C:\__\COD\Speech Lab 2\Drawings\ta00.dwg, 9/13/2021 7:06:23 PM, AutoCAD PDF (General Documentation).pc3
21A 21B 22
14
13
HH
CLASSROOM1463
CORRIDOR
21A 21B 22
14
13VM
VM
VM
WP
VM
VMCA
CL
VP
CA
CL
CL
CA
CL
TPFB EE
VM
WP
WP
WP
E
H
H
CLASSROOM1463
CORRIDOR
21A 21B 22
14
13
S
S S
M M
DT
D
DT
CLASSROOM1463
CORRIDOR
S
21A 21B 22
14
13
DT
D
DT
CLASSROOM1463
CORRIDOR
Scale: 1/4":1'0"CLASSROOM 1463 AV INFRASTRUCTURE FLOORPLAN3
SP-01
Scale: 1/4":1'0"CLASSROOM 1463 AV INFRASTRUCTURE REFLECTED CEILING PLAN4
Scale: 1/4":1'0"CLASSROOM 1463 AV EQUIPMENT FLOORPLAN1 Scale: 1/4":1'0"
CLASSROOM 1463 AV EQUIPMENT REFLECTED CEILING PLAN2
MON-03
LECTERN
TP-01
DISPLAY #1MON-01
DISPAY #2MON-01
CONFIDENCE DISPLAYMON-02
DISPLAY #4MON-01
VP-01
DISPLAY #3MON-01
CAM-01CLK-01
CAM-01CLK-01
CAM-01CLK-01
CLK-01
SP-01
SP-01SP-01
MIC-01 MIC-01
AUDIO VISUAL INFRASTRUCTURE SYMBOL SCHEDULE
SYMBOL DESCRIPTION
CAMERA LOCATION. 2 GANG EXTRA DEEP BOX FLUSH MOUNTED AT 7'6" AFF, WITH CONDUIT AS SHOWN.
CLOCK LOCATION. 1 GANG EXTRA DEEP BOX, FLUSH MOUNTED HORIZONTALLY AT 8'2" AFF WITH CONDUIT ASSHOWN.
EXISTING LECTERN FLOORBOX. SHOWN FOR REFERENCE ONLY.
TOUCHSCREEN LOCATION. AVC TO PROVIDE & INSTALL EXTRON BB 700M FLUSH MOUNTED AT STANDARD SWITCHHEIGHT, FOLLOWING MANUFACTURER INSTRUCTIONS, WITH CONDUIT AS SHOWN.
VIDEO MONITOR LOCATION. 1 GANG EXTRA DEEP BOX FLUSH MOUNTED AT ELEVATION SHOWN ON TA0.02, WITHCONDUIT AS SHOWN.
VIDEO PROJECTOR LOCATION. 1 GANG EXTRA DEEP BOX FLUSH MOUNTED AT ELEVATION SHOWN ON TA0.02, WITHCONDUIT AS SHOWN.
HDMI INPUT LOCATION. 1 GANG EXTRA DEEP BOX FLUSH MOUNTED AT STANDARD OUTLET HEIGHT WITH CONDUITAS SHOWN.
DUPLEX OUTLET LOCATION. EC TO PROVIDE AND INSTALL (1) 120VAC, 20AMP CIRCUIT IN FLUSH MOUNTED DUPLEXRECEPTACLE AT STANDARD OUTLET HEIGHT.
QUAD OUTLET LOCATION. EC TO PROVIDE AND INSTALL (1) 120VAC, 20AMP CIRCUIT FLUSH MOUNTED QUADRECEPTACLE AT ELEVATION SHOWN.
THREE NETWORK DROPS REQUIRED IN FLOORBOX AT LECTERN LOCATION. EXISTING NETWORK DROPS CAN BEUSED.
CL
CA
VP
FB
VM
TP
WP
AUDIO VISUAL INFRASTRUCTURE SYMBOL SCHEDULE
1. REFERENCE EQUIPMENT LIST ON SHEET TA0.00
2TA0.01
6TA0.01
4TA0.01
8TA0.01
4020 GRAND AVEWESTERN SPRINGS, IL 60558708.505.9886www.axent-av.com
C:\Users\bstanley\SmithGroup Companies Inc\PRJ - 13340 - SmithGroup - SmithGroup\CAD\08 Architecture\2021-0909 Exports for Axent\13340-000-A-LOGO-2440571.JPG
SHEET NUMBER
PROJECT NUMBER
SHEET TITLE
SEALS AND SIGNATURES
ISSUED FOR REV DATE
NOT FORCONSTRUCTION
35 EAST WACKERSUITE 900CHICAGO, IL 60601312.641.0770smithgroup.com
Plot
Date:
College of DuPageCollege of DuPage - Speech Lab - BIC 1463425 W. Fawell Blvd.Glen Ellyn, Illinois 60137
9/9/20
21 11
:18:03
AM
LEVEL 01 - ROOM 1463 -AV SYSTEM
FLOORPLANS ANDREFLECTED CEILING
PLANS
TA1.01
STAR
T Sh
eet
ISSUED FOR OWNER REVIEW 08.02.2021ISSUED FOR BID 09.13.2021
1TA0.01
5TA0.01
3TA0.01
7TA0.01
C:\__\COD\Speech Lab 2\Drawings\ta00.dwg, 9/13/2021 7:06:25 PM, AutoCAD PDF (General Documentation).pc3