    How to Conduct a Boiler Performance Test

    written by: Dr V T Sathyanathan • edited by: Lamar Stonecypher • updated: 5/20/2011

    The performance test in a boier e!auates the practicay achie!abe boier efficiency"#erformance tests are aso carried out to pro!e boier $uarantees" %s $uarantees in!o!econtractua conditions& the procedure in!o!ed are more eaborate than the test for e!auatin$

     performance"

    • 'onductin$ a boier performance test can be for understandin$ the current e!e of

     performance of the boier& for any troube shootin$ of the boier for performance de!iations& andfor pro!in$ the performance $uarantees" These entire three re(uirements can be met by the

     procedure adopted for performance $uarantee testin$" )efore startin$ the performance $uarantee

    test we ha!e to understand the contact re(uirement fuy& understand fuy the performance e!eof the boier& *eep in mind the norma areas of concern& decide the ri$ht time for the test&

    or$ani+e the test instruments& ma*e sure a oca measurement $rid points are in order& insta atest instruments at the specified areas& do a tria test& and decare the $uarantee test"

    Understand the contact requirement

    o ,nderstand a $uarantees we incudin$ those a$reed incudin$ added any after

    contract finai+ation

    o Ta* to performance desi$ner as to whether he has ta*en any cacuated ris*

    durin$ the proposa

    o Loo* at the penaty for each $uarantee and be cear about the se!erity e!es

    o )e cear on the demonstration $uarantee - what each means

    o Loo* at re.ection causes in the contract

    o Study the performance $uarantee proposa submitted and appro!ed

    Understand fully the performance level of the boiler

    o a*e sure you ha!e o$ readin$s of each oad under which $uarantees are a$reed

    o !auate the performance of the boier and correct it to desi$n fue

    o )e sure you are usin$ the contracted and appro!ed code for # test

    o a*e sure you are e!auatin$ a unaccounted osses and chec* how far you are

    eatin$ into the manufacturers mar$in

  • 8/18/2019 Boiler Performance Test

    2/5

    o f re(uired& inform the site of the findin$s from o$ data and as* them to retune

    and $i!e another set of data

    The normal areas of concern

    o 34y$en and fue $as temperature at boier outet - ony sin$e point measurementfor re$uar o$ readin$

    o Do a $rid measurement durin$ commissionin$ and chec* whether the point is

    cose to the a!era$e $rid !aue for the a oads $uarantee is made

    o 'oa sampin$ and testin$ - tota moisture e!auation is !ery critica and has to be

    done as per procedure in the standard bein$ foowed

    o #ower consumption readin$s - (uipment a$reed to be incuded and current&

    !ota$e and power factor readin$s to be ta*en

    o #ercenta$e combustibes measurement in bottom ash - fy ash normay no

     probem faced

    Decide the right time for the test

    o a*e sure the ambient conditions are conduci!e for # test - a!oid rainy season

    o 'ompete the performance e!auation of the boier and ma*e sure the $uarantees

    are met with correction to desi$n conditions as per contracted code

    o Decide test team - it is a $ood practice to ha!e a performance en$ineer in the team

    if the boier is first of its *ind

    o a*e out cear responsibiity for each team member - ne!er e4ceed fi!e four in

    the team is $ood6 e4cudin$ the performance en$ineer 

    o !o!e strate$y for achie!in$ the $uarantee if there is any concern in any area

    Test instruments

    o a*e sure a instruments panned to be used ha!e !aid caibration certificate and

    from a third a$ency of repute

    o The muti point measurement probes for temperature and fue $as sampin$ are

    made ready and are as per standard

    o % the thermocoupes must be indi!iduay caibrated and shoud be within the

    e4piration of caibration period

  • 8/18/2019 Boiler Performance Test

    3/5

    o 7ue $as anaysis e(uipment for o4y$en& carbon-dio4ide& and poutants i*e 834

    and S34 must be caibrated with caibration $ases pro!ided by suppier 

    o The fue $as measurement by 3rsat must aso be or$ani+ed - ea*a$e of air into

    fue $as durin$ sampin$ is a ma.or concern" % efforts to a!oid this shoud be ta*en by

    chec*in$ and rechec*in$

    Local measurement grid points

    o Location of $rid is !ery important as in a ar$e duct there wi be hi$h amount of

    imbaance and stratification

    o 'are must be ta*en whie pro!idin$ the $rid tappin$ points for proper access to

    insert the on$ probes

    o %!oid tappin$ points near a direction chan$e& !oid re$ion& or near the tappin$

     point hoe

    o The number of points for $rid must be as per code used for # test

    o The power consumption measurement points and connections must be identified

    and connection procedure ensured

    • nstallation of all test instruments

    o % probes for %#9 inet and outet $as temperature and fue $as sampin$ must

     be assembed with thermocoupe

    o ach thermocoupe on the probe shoud be cose to the $as sampin$ hoe if not at

    the sampin$ hoe

    o 'onnection to the measurement de!ice data o$$er or oca measurement6 shoud

     be carefuy chec*ed for any de!iation or defect

    o The $as sampin$ probe shoud be connected by fe4ibe tubin$ to the samper

    trou$h a bubber

    o

    The sampin$ must be done by a pump and a air in$ress points in the connectionnet wor* may be fuy chec*ed and seaed

    o The $as temperature is measured at each point but the $as can be samped from a

     points as a composite one

    o 'onnect the other $rid temperature measurements in areas i*e air temperature

    enterin$ air preheater& temperature and o4y$en at D inet

  • 8/18/2019 Boiler Performance Test

    4/5

    o % the air and fue $as pressure shoud be measured usin$ a standard water tube

    manometer 

    o % pressure $au$es& if pressure drop $uarantee is there& must be done

    o % steam& water temperature must be done throu$h a caibrated thermocoupethrou$h a thermowe

    o % thermocoupe must be appropriatey corrected for cod .unction compensation

    o The ambient temperature& both wet and dry bub& must be ta*en cose to the air

    inta*e point of 7D and #% fan at the re(uired fre(uency

    o The readin$s in the contro room must be separatey o$$ed with a re(uired

    fre(uency

    o The coa& fyash& bottom ash and mi re.ects must be coected at the re(uiredfre(uency and e(uipment

    Trial test

    o %t the re(uired oad condition wa bow the boier and aso do the soot bowin$ if 

    needed - oo* at contract cause for any prere(uisites

    o Tune the combustion for the owest aowed e4cess air and owest achie!abe

    %#9 outet $as temperature

    o %ow the boier to stabii+e for about one hour and start the tria test

    o Ta*e a readin$s at the re(uired fre(uency as per the standard

    o 'hec* the tota moisture in coa and the combustibes in ash" f pro4imate anaysis

    of is a!aiabe which is within 2 hours this can be ta*en for immediate chec*in$ of thetria readin$ - correct the same for desi$n coa

    The guarantee test

    o f resuts of tria test are 3;& then decare #erformance uarantee test& ma*e sure

    a customer representati!e or consutant as per contract is a witness for a readin$s and

    data o$$ed - Si$n the o$ data then and there from a incudin$ customer rep orconsutant

    o  8ormay a # test are run for four hours uness otherwise a$reed before test

  • 8/18/2019 Boiler Performance Test

    5/5

    o 'oect a sampes& coa& mi re.ect& fy ash and bottom ash ma*e in to three

     portions one for customer& one for your use and the other as reference sampe in case

    needed"

    o The reference sampe is si$ned and seaed by both suppier and customer %so

    consutant if in!o!ed in test6

    o Do the test at a the a$reed oad

    o a*e sure that a o$ readin$s and sampes are propery si$ned& abeed and

     pac*ed propery to a!oid mi4-up"

    o et the tota moisture readin$ done for each test and a si$ned copy $ot from the

    customer or his assi$ned a$ency

    o f any de!iation is noticed durin$ any test because of oad fuctuation or any other 

    reason then record the same in that particuar o$ sheet for reference in future

    o a*e a fina minutes of meetin$ with customer / consutant about the test carried

    out& any specia obser!ation& and when the report wi be submitted"