7/30/2019 Bricks Tests
1/34
NAME OF WORK:-PROVIDING&LAYING OF SW PIPE SEWERS. RCC P1/
FROG MARK : SEWER BRICKS
LOCATION : SITE DATE OF TESTING: 05/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4606 4520-4680
2-Width of 20 bricks (mm) 2220 2160-2240
3-Height of 20 bricks (mm) 1418 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.051 3.036 3.047 3.022 3.068
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.224 3.2 3.248 3.180 3.256
3 Water Absorption
(%) 5.67 5.40 6.60 5.23 6.13
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 108 455.00 18.40
2 228 108 460.00 18.68
3 229 109 450.00 18.03
4 228 110 465.00 18.54
5 227 109 455.00 18.39
D - EFFLOROSCENCE :1 Nil
2 Nil
3 Slight
4 Slight
5 Nil
Agency(L&T) J E A.E.E EE(CD)VIII
PUNJAB WATER SUPPLY AND SEWERAGE DIVISION
BRICKS TEST REPORT
5.80
18.41
SAMPLE NO.
(AS PER IS:4885)
7/30/2019 Bricks Tests
2/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : SEWER BRICKS
LOCATION : SITE DATE OF TESTING: 31/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4608 4520-4680
2-Width of 20 bricks (mm) 2214 2160-2240
3-Height of 20 bricks (mm) 1414 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.032 3.256 3.198 3.084 3.262
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.242 3.462 3.388 3.240 3.448
3 Water Absorption
(%)6.93 6.33 5.94 5.06 5.70
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 109 455.00 18.23
2 228 108 460.00 18.683 227 109 450.00 18.19
4 228 110 465.00 18.54
5 229 109 460.00 18.43
D - EFFLOROSCENCE :
1 Slight
2 Nil
3 Nil
4 Nil
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
SAMPLE NO.
5.99
18.41
BRICKS TEST REPORT
(AS PER IS:4885)
7/30/2019 Bricks Tests
3/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : Sewer Bricks
LOCATION : SITE DATE OF TESTING : 06/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4614 4520-4680
2-Width of 20 bricks (mm) 2210 2160-2240
3-Height of 20 bricks (mm) 1408 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.412 3.378 3.332 3.298 3.256
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.624 3.578 3.548 3.494 3.442
3 Water Absorption
(%)
6.21 5.92 6.48 5.94 5.71
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 227 109 455.00 18.39
2 228 108 440.00 17.87
3 229 110 450.00 17.86
4 229 109 445.00 17.83
5 228 108 450.00 18.27
D - EFFLOROSCENCE :
1 Slight2 Nil
3 Slight
4 Nil
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
6.05
18.04
SAMPLE NO.
(AS PER IS:4885)
7/30/2019 Bricks Tests
4/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : Sewer Bricks
LOCATION : SITE DATE OF TESTING: 20/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4608 4520-4680
2-Width of 20 bricks (mm) 2212 2160-2240
3-Height of 20 bricks (mm) 1414 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.100 3.258 3.096 3.140 3.228
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.31 3.464 3.258 3.318 3.426
3 Water Absorption
(%)6.77 6.32 5.23 5.67 6.13
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 227 110 450.00 18.02
2 229 109 465.00 18.633 228 108 445.00 18.07
4 230 108 460.00 18.52
5 229 109 455.00 18.23
D - EFFLOROSCENCE :
1 Slight
2 Nil
3 Slight
4 Nil
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
SAMPLE NO.
6.03
18.29
BRICKS TEST REPORT
(AS PER IS:4885)
7/30/2019 Bricks Tests
5/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : R B F
LOCATION : SITE DATE OF TESTING: 16/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4610 4520-4680
2-Width of 20 bricks (mm) 2208 2160-2240
3-Height of 20 bricks (mm) 1412 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.064 3.020 3.018 3.100 3.048
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.412 3.394 3.416 3.508 3.422
3 Water Absorption
(%)
11.36 12.38 13.19 13.16 12.27
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 109 225.00 9.01
2 228 107 220.00 9.02
3 227 108 230.00 9.38
4 228 108 220.00 8.93
5 229 109 235.00 9.41
D - EFFLOROSCENCE :
1 Slight2 Nil
3 Slight
4 Slight
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.47
9.15
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
6/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : J B
LOCATION : SITE DATE OF TESTING: 23/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4614 4520-4680
2-Width of 20 bricks (mm) 2208 2160-2240
3-Height of 20 bricks (mm) 1410 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.022 3.046 3.100 3.000 3.062
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.398 3.416 3.522 3.366 3.48
3 Water Absorption
(%)12.44 12.15 13.61 12.20 13.65
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 108 235.00 9.54
2 228 107 220.00 9.023 229 110 230.00 9.13
4 227 109 225.00 9.09
5 229 108 235.00 9.50
D - EFFLOROSCENCE :
1 Nil
2 Nil
3 Slight
4 Nil
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
SAMPLE NO.
12.81
9.26
BRICKS TEST REPORT
(AS PER IS:1077)
7/30/2019 Bricks Tests
7/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : M.B.S
LOCATION : SITE DATE OF TESTING: 07/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4614 4520-4680
2-Width of 20 bricks (mm) 2212 2160-2240
3-Height of 20 bricks (mm) 1410 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.066 3.048 3.100 3.082 3.000
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.426 3.398 3.452 3.498 3.37
3 Water Absorption
(%)
11.74 11.48 11.35 13.50 12.33
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 108 235.00 9.50
2 228 109 240.00 9.66
3 229 108 225.00 9.10
4 227 107 230.00 9.47
5 229 108 220.00 8.90
D - EFFLOROSCENCE :
1 Slight2 Slight
3 Nil
4 Nil
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.08
9.32
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
8/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : RG
LOCATION : SITE DATE OF TESTING: 09/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4614 4520-4680
2-Width of 20 bricks (mm) 2210 2160-2240
3-Height of 20 bricks (mm) 1414 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.104 3.098 3.046 3.026 3.080
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.476 3.452 3.43 3.422 3.438
3 Water Absorption
(%)11.98 11.43 12.61 13.09 11.62
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 109 245.00 9.86
2 229 107 230.00 9.393 228 110 220.00 8.77
4 227 108 225.00 9.18
5 229 109 235.00 9.41
D - EFFLOROSCENCE :
1 Slight
2 Nil
3 Nil
4 Slight
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
(AS PER IS:1077)
SAMPLE NO.
12.15
9.32
7/30/2019 Bricks Tests
9/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : GANESH
LOCATION : SITE DATE OF TESTING: 06/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4612 4520-4680
2-Width of 20 bricks (mm) 2214 2160-2240
3-Height of 20 bricks (mm) 1408 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.054 3.062 3.032 3.100 3.080
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.452 3.428 3.396 3.512 3.462
3 Water Absorption
(%)
13.03 11.95 12.01 13.29 12.40
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 110 225.00 8.97
2 229 109 240.00 9.61
3 227 108 235.00 9.59
4 227 109 220.00 8.89
5 229 108 235.00 9.50
D - EFFLOROSCENCE :
1 Slight2 Nil
3 Nil
4 Slight
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.54
9.31
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
10/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : MAAN
LOCATION : SITE DATE OF TESTING: 07/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4616 4520-4680
2-Width of 20 bricks (mm) 2210 2160-2240
3-Height of 20 bricks (mm) 1406 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.100 3.068 3.000 3.024 3.112
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.512 3.468 3.342 3.364 3.52
3 Water Absorption
(%)13.29 13.04 11.40 11.24 13.11
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 108 220.00 8.90
2 228 109 235.00 9.463 227 109 235.00 9.50
4 229 108 240.00 9.70
5 228 108 225.00 9.14
D - EFFLOROSCENCE :
1 Nil
2 Slight
3 Nil
4 Slight
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
(AS PER IS:1077)
SAMPLE NO.
12.42
9.34
7/30/2019 Bricks Tests
11/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : PK
LOCATION : SITE DATE OF TESTING: 05/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4610 4520-4680
2-Width of 20 bricks (mm) 2204 2160-2240
3-Height of 20 bricks (mm) 1408 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.052 3.024 3.102 3.060 3.082
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.396 3.398 3.512 3.472 3.488
3 Water Absorption
(%)
11.27 12.37 13.22 13.46 13.17
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 107 225.00 9.22
2 229 108 235.00 9.50
3 228 109 230.00 9.25
4 230 109 240.00 9.57
5 229 108 220.00 8.90
D - EFFLOROSCENCE :
1 Nil2 Slight
3 Slight
4 Nil
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.70
9.29
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
12/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : S.B.C.
LOCATION : SITE DATE OF TESTING: 05/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4614 4520-4680
2-Width of 20 bricks (mm) 2210 2160-2240
3-Height of 20 bricks (mm) 1412 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
2.948 2.970 2.958 2.966 2.982
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.306 3.326 3.354 3.344 3.362
3 Water Absorption
(%)12.14 11.99 13.39 12.74 12.74
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 109 220.00 8.81
2 229 110 225.00 8.933 228 108 235.00 9.54
4 227 108 220.00 8.97
5 228 109 240.00 9.66
D - EFFLOROSCENCE :
1 Nil
2 Slight
3 Slight
4 Nil
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
(AS PER IS:1077)
SAMPLE NO.
12.60
9.18
7/30/2019 Bricks Tests
13/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : J.S.P
LOCATION : SITE DATE OF TESTING: 04/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4612 4520-4680
2-Width of 20 bricks (mm) 2210 2160-2240
3-Height of 20 bricks (mm) 1412 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.000 3.108 3.044 3.100 3.028
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.338 3.462 3.468 3.470 3.448
3 Water Absorption
(%)
11.27 11.39 13.93 11.94 13.87
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 109 225.00 9.05
2 229 108 240.00 9.70
3 228 107 235.00 9.63
4 227 108 220.00 8.97
5 228 109 210.00 8.45
D - EFFLOROSCENCE :
1 Slight2 Nil
3 Slight
4 Slight
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.48
9.16
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
14/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : R.K
LOCATION : SITE DATE OF TESTING: 03/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4612 4520-4680
2-Width of 20 bricks (mm) 2208 2160-2240
3-Height of 20 bricks (mm) 1410 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.022 3.060 3.100 3.058 3.000
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.398 3.412 3.45 3.434 3.388
3 Water Absorption
(%)12.44 11.50 11.29 12.30 12.93
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 108 220.00 8.90
2 227 107 230.00 9.473 228 109 235.00 9.46
4 229 107 210.00 8.57
5 228 110 230.00 9.17
D - EFFLOROSCENCE :
1 Nil
2 Nil
3 Nil
4 Slight
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
SAMPLE NO.
12.09
9.11
BRICKS TEST REPORT
(AS PER IS:1077)
7/30/2019 Bricks Tests
15/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : G.B.C
LOCATION : SITE DATE OF TESTING: 02/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4612 4520-4680
2-Width of 20 bricks (mm) 2210 2160-2240
3-Height of 20 bricks (mm) 1416 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.020 3.000 3.112 3.042 2.998
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.382 3.364 3.468 3.448 3.41
3 Water Absorption
(%)
11.99 12.13 11.44 13.35 13.74
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 108 225.00 9.14
2 227 110 235.00 9.41
3 228 109 240.00 9.66
4 229 108 225.00 9.10
5 229 109 210.00 8.41
D - EFFLOROSCENCE :
1 Slight2 Slight
3 Nil
4 Nil
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.53
9.14
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
16/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : J.S.R
LOCATION : SITE DATE OF TESTING: 02/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4608 4520-4680
2-Width of 20 bricks (mm) 2212 2160-2240
3-Height of 20 bricks (mm) 1410 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.064 3.000 3.082 3.100 3.028
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.444 3.368 3.486 3.510 3.4
3 Water Absorption
(%)12.40 12.27 13.11 13.23 12.29
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 109 230.00 9.25
2 227 110 210.00 8.413 230 108 220.00 8.86
4 229 109 235.00 9.41
5 227 108 225.00 9.18
D - EFFLOROSCENCE :
1 Slight
2 Nil
3 Nil
4 Slight
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
(AS PER IS:1077)
SAMPLE NO.
12.66
9.02
7/30/2019 Bricks Tests
17/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : J - B
LOCATION : SITE DATE OF TESTING: 01/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4614 4520-4680
2-Width of 20 bricks (mm) 2218 2160-2240
3-Height of 20 bricks (mm) 1412 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.032 2.996 3.008 3.102 3.054
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.392 3.388 3.366 3.508 3.426
3 Water Absorption
(%)
11.87 13.08 11.90 13.09 12.18
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 108 225.00 9.14
2 230 108 240.00 9.66
3 227 110 230.00 9.21
4 229 107 220.00 8.98
5 228 109 235.00 9.46
D - EFFLOROSCENCE :
1 Nil2 Slight
3 Nil
4 Slight
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.43
9.29
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
18/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : NEELAM - 13
LOCATION : SITE DATE OF TESTING: 01/02/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4618 4520-4680
2-Width of 20 bricks (mm) 2214 2160-2240
3-Height of 20 bricks (mm) 1408 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.046 3.100 2.998 3.120 3.068
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.43 3.468 3.416 3.522 3.45
3 Water Absorption
(%)12.61 11.87 13.94 12.88 12.45
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 109 235.00 9.46
2 229 108 230.00 9.303 228 109 220.00 8.85
4 227 110 235.00 9.41
5 229 109 220.00 8.81
D - EFFLOROSCENCE :
1 Slight
2 Slight
3 Slight
4 Nil
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
SAMPLE NO.
12.75
9.17
BRICKS TEST REPORT
(AS PER IS:1077)
7/30/2019 Bricks Tests
19/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : RAHUL
LOCATION : SITE DATE OF TESTING: 31/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4612 4520-4680
2-Width of 20 bricks (mm) 2210 2160-2240
3-Height of 20 bricks (mm) 1410 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.020 2.998 3.028 3.100 3.050
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.354 3.386 3.394 3.492 3.466
3 Water Absorption
(%)
11.06 12.94 12.09 12.65 13.64
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 108 220.00 8.90
2 228 109 240.00 9.66
3 227 110 230.00 9.21
4 230 109 225.00 8.97
5 229 108 235.00 9.50
D - EFFLOROSCENCE :
1 Nil2 Nil
3 Slight
4 Nil
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.47
9.25
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
20/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : MANOJ
LOCATION : SITE DATE OF TESTING: 31/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4610 4520-4680
2-Width of 20 bricks (mm) 2208 2160-2240
3-Height of 20 bricks (mm) 1412 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.100 3.030 3.000 3.042 3.078
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.512 3.452 3.356 3.424 3.43
3 Water Absorption
(%)13.29 13.93 11.87 12.56 11.44
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 110 230.00 9.17
2 227 108 220.00 8.973 228 107 225.00 9.22
4 227 107 235.00 9.68
5 230 109 220.00 8.78
D - EFFLOROSCENCE :
1 Slight
2 Slight
3 Slight
4 Nil
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
(AS PER IS:1077)
SAMPLE NO.
12.62
9.16
7/30/2019 Bricks Tests
21/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : SAGAR
LOCATION : SITE DATE OF TESTING : 30/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4618 4520-4680
2-Width of 20 bricks (mm) 2210 2160-2240
3-Height of 20 bricks (mm) 1416 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.026 3.030 3.000 3.100 3.056
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.368 3.400 3.372 3.498 3.436
3 Water Absorption
(%)11.30 12.21 12.40 12.84 12.43
4 Average Water Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 227 110 225.00 9.01
2 228 109 220.00 8.85
3 229 107 240.00 9.79
4 228 108 220.00 8.93
5 229 109 235.00 9.41
D - EFFLOROSCENCE :
1 Nil
2 Slight3 Slight
4 Nil
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.24
9.20
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
22/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : R.B- 20
LOCATION : SITE DATE OF TESTING: 30/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4608 4520-4680
2-Width of 20 bricks (mm) 2204 2160-2240
3-Height of 20 bricks (mm) 1414 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.008 3.086 3.000 3.104 3.036
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.368 3.438 3.398 3.500 3.414
3 Water Absorption
(%)11.97 11.41 13.27 12.76 12.45
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 109 240 9.66
2 229 110 225 8.933 228 108 230 9.34
4 230 107 235 9.55
5 227 109 225 9.09
D - EFFLOROSCENCE :
1 Slight
2 Nil
3 Nil
4 Slight
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
SAMPLE NO.
12.37
9.31
BRICKS TEST REPORT
(AS PER IS:1077)
7/30/2019 Bricks Tests
23/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : R K
LOCATION : SITE DATE OF TESTING : 29/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4612 4520-4680
2-Width of 20 bricks (mm) 2218 2160-2240
3-Height of 20 bricks (mm) 1408 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.104 2.996 3.082 2.998 3.100
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.492 3.376 3.482 3.420 3.51
3 Water Absorption
(%)
12.50 12.68 12.98 14.08 13.23
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 227 108 230.00 9.38
2 228 109 225.00 9.05
3 229 108 235.00 9.50
4 227 110 230.00 9.21
5 228 109 240.00 9.66
D - EFFLOROSCENCE :
1 Slight2 Nil
3 Slight
4 Nil
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
13.09
9.36
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
24/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : M.B.C
LOCATION : SITE DATE OF TESTING: 29/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4614 4520-4680
2-Width of 20 bricks (mm) 2210 2160-2240
3-Height of 20 bricks (mm) 1416 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.048 3.000 3.064 3.100 3.120
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.456 3.362 3.4 3.460 3.532
3 Water Absorption
(%)13.39 12.07 10.97 11.61 13.21
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 109 225 9.05
2 228 110 245 9.773 229 110 230 9.13
4 227 108 230 9.38
5 229 107 240 9.79
D - EFFLOROSCENCE :
1 Nil
2 Slight
3 Slight
4 Nil
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
(AS PER IS:1077)
SAMPLE NO.
12.25
9.43
7/30/2019 Bricks Tests
25/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : GSR
LOCATION : SITE DATE OF TESTING: 27/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4614 4520-4680
2-Width of 20 bricks (mm) 2212 2160-2240
3-Height of 20 bricks (mm) 1416 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven dried
bricks (Kgs)2.990 3.000 3.058 3.102 3.064
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.342 3.412 3.462 3.460 3.398
3 Water Absorption
(%) 11.77 13.73 13.21 11.54 10.904 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 108 235.00 9.50
2 227 109 230.00 9.30
3 228 109 235.00 9.46
4 229 110 225.00 8.93
5 228 108 240.00 9.75
D - EFFLOROSCENCE :1 Slight
2 Nil
3 Nil
4 Slight
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.23
9.39
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
26/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : R.V.S
LOCATION : SITE DATE OF TESTING: 28/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4608 4520-4680
2-Width of 20 bricks (mm) 2214 2160-2240
3-Height of 20 bricks (mm) 1406 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven driedbricks (Kgs)
2.992 2.968 2.986 2.972 3.000
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.338 3.382 3.312 3.380 3.368
3 Water Absorption
(%)11.56 13.95 10.92 13.73 12.27
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 108 225.00 9.14
2 228 107 220.00 9.023 227 110 235.00 9.41
4 229 108 235.00 9.50
5 227 109 230.00 9.30
D - EFFLOROSCENCE :
1 Slight
2 Nil
3 Nil
4 Slight
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
SAMPLE NO.
12.49
9.27
BRICKS TEST REPORT(AS PER IS:1077)
7/30/2019 Bricks Tests
27/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : Neelam - 11
LOCATION : SITE DATE OF TESTING: 27/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4600 4520-4680
2-Width of 20 bricks (mm) 2210 2160-2240
3-Height of 20 bricks (mm) 1412 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.046 3.120 3.064 3.056 3.078
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.448 3.498 3.462 3.410 3.466
3 Water Absorption
(%)
13.20 12.12 12.99 11.58 12.61
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 110 240.00 9.57
2 227 110 230.00 9.21
3 228 109 235.00 9.46
4 230 109 225.00 8.97
5 229 110 220.00 8.73
D - EFFLOROSCENCE :
1 Slight2 Nil
3 Nil
4 Slight
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.50
9.19
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
28/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : M.K- 21
LOCATION : SITE DATE OF TESTING: 25/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4612 4520-4680
2-Width of 20 bricks (mm) 2214 2160-2240
3-Height of 20 bricks (mm) 1410 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.020 3.000 2.986 3.045 3.100
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.426 3.381 3.344 3.410 3.48
3 Water Absorption
(%)13.44 12.70 11.99 11.99 12.26
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 108 240.00 9.75
2 229 109 225.00 9.013 227 109 240.00 9.70
4 228 108 235.00 9.54
5 229 110 230.00 9.13
D - EFFLOROSCENCE :
1 Slight
2 Nil
3 Slight
4 Slight
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
(AS PER IS:1077)
SAMPLE NO.
12.48
9.43
7/30/2019 Bricks Tests
29/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : SHIV JEE
LOCATION : SITE DATE OF TESTING: 23/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4612 4520-4680
2-Width of 20 bricks (mm) 2214 2160-2240
3-Height of 20 bricks (mm) 1410 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.064 3.010 3.072 3.056 3.100
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.456 3.428 3.444 3.426 3.496
3 Water Absorption
(%)
12.79 13.89 12.11 12.11 12.77
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 110 235.00 9.37
2 227 109 240.00 9.70
3 229 108 230.00 9.30
4 229 109 235.00 9.41
5 228 108 245.00 9.95
D - EFFLOROSCENCE :
1 Nil2 Nil
3 Slight
4 Slight
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.73
9.55
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
30/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK :M.B.F
LOCATION : SITE DATE OF TESTING: 24/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4620 4520-4680
2-Width of 20 bricks (mm) 2208 2160-2240
3-Height of 20 bricks (mm) 1410 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
3.100 3.068 3.050 3.042 3.100
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.482 3.464 3.472 3.430 3.486
3 Water Absorption
(%)12.32 12.91 13.84 12.75 12.45
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 227 110 240.00 9.61
2 227 110 230.00 9.213 229 108 225.00 9.10
4 228 109 245.00 9.86
5 228 109 235.00 9.46
D - EFFLOROSCENCE :
1 Slight
2 Nil
3 Slight
4 Nil
5 Nil
Agency
(L&T) J E A.E.E EE(CD)VIII
SAMPLE NO.
12.85
9.45
BRICKS TEST REPORT
(AS PER IS:1077)
7/30/2019 Bricks Tests
31/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : S P
LOCATION : SITE DATE OF TESTING: 17/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4614 4520-4680
2-Width of 20 bricks (mm) 2212 2160-2240
3-Height of 20 bricks (mm) 1412 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.048 3.040 2.992 3.034 3.060
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.42 3.392 3.402 3.458 3.442
3 Water Absorption
(%)
12.20 11.58 13.70 13.97 12.48
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 110 225.00 8.93
2 229 109 240.00 9.61
3 228 109 235.00 9.46
4 227 108 220.00 8.97
5 228 109 230.00 9.25
D - EFFLOROSCENCE :
1 Nil2 Slight
3 Slight
4 Nil
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.79
9.25
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
32/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : PRADHAN
LOCATION : SITE DATE OF TESTING: 22/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4618 4520-4680
2-Width of 20 bricks (mm) 2214 2160-2240
3-Height of 20 bricks (mm) 1410 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
2.948 2.982 2.964 3.000 2.928
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.310 3.32 3.286 3.398 3.296
3 Water Absorption
(%)12.28 11.33 10.86 13.27 12.57
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 110 220.00 8.73
2 229 109 235.00 9.413 228 108 230.00 9.34
4 228 109 230.00 9.25
5 227 108 240.00 9.79
D - EFFLOROSCENCE :
1 Slight
2 Slight
3 Nil
4 Nil
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
SAMPLE NO.
12.06
9.31
BRICKS TEST REPORT
(AS PER IS:1077)
7/30/2019 Bricks Tests
33/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : R.B - 1
LOCATION : SITE DATE OF TESTING: 07/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4612 4520-4680
2-Width of 20 bricks (mm) 2210 2160-2240
3-Height of 20 bricks (mm) 1408 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of oven
dried bricks (Kgs)3.012 2.988 3.024 3.000 2.980
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.386 3.322 3.36 3.366 3.37
3 Water Absorption
(%)
12.42 11.18 11.11 12.20 13.09
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 228 109 240.00 9.66
2 229 110 245.00 9.73
3 229 108 230.00 9.30
4 229 109 235.00 9.41
5 228 110 225.00 8.97
D - EFFLOROSCENCE :
1 Slight2 Nil
3 Nil
4 Slight
5 Slight
Agency
(L&T) J E A.E.E EE(CD)VIII
BRICKS TEST REPORT
12.00
9.41
SAMPLE NO.
(AS PER IS:1077)
7/30/2019 Bricks Tests
34/34
DELHI STATE INDUSTRAIL & INFRASTRUCTURE DEV. CORP.LTD
NAME OF WORK : INFRASTRUCTURE DEVELOPMENT WORKS ( ROADS,WATER SUPPLY,
SEWERAGE,AND STORM WATER DRAINAGE ) IN NEW INDUSTRIAL AREA
AT VILL.BHORGARH PART- B( BAWANA PH - II ) DELHI.
FROG MARK : R.B.C.
LOCATION : SITE DATE OF TESTING: 12/01/09
A - DIMENSIONAL CHECK :
TESTING STEPSOBSERVED VALUE
(mm)
TOLERANCE LIMIT
(mm)
1-Length of 20 bricks (mm) 4610 4520-4680
2-Width of 20 bricks (mm) 2208 2160-2240
3-Height of 20 bricks (mm) 1412 1360-1440
B - WATER ABSORPTION :
SL NO. TESTING STEPS
1 2 3 4 5
1 Weight of ovendried bricks (Kgs)
2.948 3.000 2.992 2.868 2.972
2 Weight of bricks
after immersion in
water for 24 hours
(Kgs)
3.298 3.352 3.386 3.184 3.342
3 Water Absorption
(%)11.87 11.73 13.17 11.02 12.45
4 Average Water
Absorption (%)
C - COMPRESSIVE STRENGTH:
Sl No. Length (mm) Width (mm)Load @ failure
(KN)
Comp.Strength
(N/mm2)
Average
Comp.Strength
(N/mm2)
1 229 110 235.00 9.33
2 228 111 240.00 9.483 229 108 225.00 9.10
4 227 109 235.00 9.50
5 230 108 230.00 9.26
D - EFFLOROSCENCE :
1 Slight
2 Nil
3 Nil
4 Slight
5 Nil
SAMPLE NO.
12.05
9.33
BRICKS TEST REPORT
(AS PER IS:1077)