tnxTower Report - version 7.0.5.1
June 23, 2016 Mr. Ryan Shaffer B+T Group Crown Castle 1717 S. Boulder, Suite 300 12725 Morris Road Extension, Suite 400 Tulsa, OK 74119 Alpharetta, GA 30004 (918) 587-4630 (678) 366-1233 [email protected] Subject: Structural Modification Report Carrier Designation: AT&T Mobility Co-Locate Carrier Site Number: 10080789 Carrier Site Name: Lake Trafford Crown Castle Designation: Crown Castle BU Number: 844061 Crown Castle Site Name: Lake Trafford Crown Castle JDE Job Number: 361974 Crown Castle Work Order Number: 1248031 Crown Castle Application Number: 328847 Rev. 5 Engineering Firm Designation: B+T Group Project Number: 106729.001.01 Site Data: 1025 Sanitation Road, Immokalee, FL, Collier County Latitude 26° 23' 59.27'', Longitude -81° 26' 3.8'' 260 Foot - Guyed Tower Dear Mr. Shaffer, B+T Group is pleased to submit this “Structural Modification Report” to determine the structural integrity of the above mentioned tower. This analysis has been performed in accordance with the Crown Castle Structural ‘Statement of Work’ and the terms of Crown Castle Purchase Order Number 910554, in accordance with application 328847, revision 5. The purpose of the analysis is to determine acceptability of the tower stress level. Based on our analysis we have determined the tower stress level for the structure and foundation, under the following load case, to be: LC4.5: TSA specified load case with proposed modifications Sufficient Capacity Note: See Table 1 and Table 2 for the proposed and existing loading, respectively. This analysis has been performed in accordance with the 2014 Florida Building Code, 5th Edition, based upon an ultimate 3-second gust wind speed of 152 mph converted to a nominal 3-second gust wind speed of 118 mph per section 1609.3.1 as required for use in the TIA-222-G Standard per Exception #5 of Section 1609.1.1. Exposure Category C and Risk Category II were used in this analysis. All modifications and equipment proposed in this report shall be installed in accordance with the attached drawings for the determined available structural capacity to be effective. We at B+T Group appreciate the opportunity of providing our continuing professional services to you and Crown Castle. If you have any questions or need further assistance on this or any other projects please give us a call. Respectfully submitted by: B+T Engineering, Inc. 27496; Exp:02/28/17 Umesh Shrestha, E.I.T. John W. Kelly III, P.E. Project Engineer Engineer of Record
Reviewed for CodeCompliance
PRBD20170308782
June 23, 2016 260 Ft Guyed Tower Structural Modification Report CCI BU No. 844061 Project Number 106729.001.01, Application 328847, Revision 5 Page 2
tnxTower Report - version 7.0.5.1
TABLE OF CONTENTS 1) INTRODUCTION 2) ANALYSIS CRITERIA Table 1 - Proposed Antenna and Cable Information Table 2 - Existing Antenna and Cable Information Table 3 - Design Antenna and Cable Information 3) ANALYSIS PROCEDURE Table 4 - Documents Provided 3.1) Analysis Method 3.2) Assumptions 4) ANALYSIS RESULTS Table 5 - Section Capacity (Summary) Table 6 - Tower Components vs. Capacity 4.1) Recommendations 5) APPENDIX A tnxTower Output 6) APPENDIX B Base Level Drawing 7) APPENDIX C Additional Calculations 8) APPENDIX D Tower Modification Drawings
Reviewed for CodeCompliance
PRBD20170308782
June 23, 2016 260 Ft Guyed Tower Structural Modification Report CCI BU No. 844061 Project Number 106729.001.01, Application 328847, Revision 5 Page 3
tnxTower Report - version 7.0.5.1
1) INTRODUCTION This tower is a 260 ft. guyed tower mapped by GPD Group in October of 2012. The original design standard and wind speed are unknown. This tower has been modified multiple times in the past to accommodate additional loading and those modifications are incorporated in this analysis. 2) ANALYSIS CRITERIA The structural analysis was performed for this tower in accordance with the requirements of TIA-222-G Structural Standards for Steel Antenna Towers and Antenna Supporting Structures using a 3-second gust wind speed of 118 mph with no ice and 60 mph under service loads, exposure category C.
Table 1 - Proposed Antenna and Cable Information
Mounting Level (ft)
Center Line
Elevation (ft)
Number of
Antennas
Antenna Manufacturer Antenna Model
Number of Feed Lines
Feed Line
Size (in)Note
257.0 261.0
2 CCI Antennas BSA-M65R-BUU-H6
1 2
3/8 3/4 --
4 Commscope SBNHH-1D85B
4 Ericsson RRUS 12
4 Ericsson RRUS 32 2 Ericsson RRUS-11
4 Powerwave LGP 17503
1 Raycap DC6-48-60-18-8F
Table 2 - Existing Antenna and Cable Information
Mounting Level (ft)
Center Line
Elevation (ft)
Number of
Antennas
Antenna Manufacturer Antenna Model
Number of Feed Lines
Feed Line
Size (in)Note
257.0
261.0
2 Allgon 7251.01
3 6 8 2 3
5/16 1-1/4 1-5/8 3/8 3/4
1
2 Andrew DBXCP-4545A-R2M 2 Andrew E15Z01P13
2 Commscope CBC78-DF-2X
4 Ericsson RRUS A2 MODULE 6 Ericsson RRUS-11
2 Raycap DC6-48-60-18-8F
257.0
2 Andrew DBXNH-6565B-R2M
-- -- 2
3 Ericsson RRUS 12 3 Ericsson RRUS-11 4 KMW ET-X-TU-42-15-37-18-iR-SP 4 Powerwave LGP1750X 4 Andrew E15Z01P13 1 -- Sector Mount [SM 602-3] -- -- 1
Notes: 1) Existing Equipment 2) Equipment to be Removed
Reviewed for CodeCompliance
PRBD20170308782
June 23, 2016 260 Ft Guyed Tower Structural Modification Report CCI BU No. 844061 Project Number 106729.001.01, Application 328847, Revision 5 Page 4
tnxTower Report - version 7.0.5.1
Table 3 - Design Antenna and Cable Information
Mounting Level (ft)
Center Line
Elevation (ft)
Number of
Antennas
Antenna Manufacturer Antenna Model
Number of Feed Lines
Feed Line
Size (in)
Information Not Available 3) ANALYSIS PROCEDURE
Table 4 - Documents Provided
Document Remarks Reference Source
Online Application AT&T Mobility Co-Locate, Rev.5 328847 CCIsitesTower Mapping GPD Group, Job No.2012772.33 4601425 CCIsites
Tower Modification Drawings CIVE Consulting Inc., Project No.T11-118-4125 5944453 CCIsites
Post Modification Inspection GPD Group, Job No.2012857.15 4601427 CCIsitesTower Modification Drawings GPD Group, Job No.2012818.51 4601426 CCIsites
Post Modification Inspection ETS, Project No.160031 6082908 CCIsites
Tower Modification Drawings GPD Group, Job No.2014777.844061.02 5171780 CCIsitesPost Modification Inspection TEP, Project No.57391-24567 5466656 CCIsites
Foundation Mapping GPD Group, Job No.2012772.33 4534595 CCIsites
Geotech Report GPD Group, Job No.2012772.33 4534596 CCIsitesAntenna Configuration Crown CAD Package Date:05/07/2016 CCIsites
3.1) Analysis Method
tnxTower (version 7.0.5.1), a commercially available analysis software package, was used to create a three-dimensional model of the tower and calculate member stresses for various loading cases. Selected output from the analysis is included in Appendix A.
3.2) Assumptions
1) Tower and structures were built in accordance with the manufacturer’s specifications. 2) The tower and structures have been maintained in accordance with the manufacturer’s
specification. 3) The configuration of antennas, transmission cables, mounts and other appurtenances are as
specified in Tables 1 and 2 and the referenced drawings. 4) Mount areas and weights are assumed based on photographs provided.
This analysis may be affected if any assumptions are not valid or have been made in error. B+T Group should be notified to determine the effect on the structural integrity of the tower.
Reviewed for CodeCompliance
PRBD20170308782
June 23, 2016 260 Ft Guyed Tower Structural Modification Report CCI BU No. 844061 Project Number 106729.001.01, Application 328847, Revision 5 Page 5
tnxTower Report - version 7.0.5.1
4) ANALYSIS RESULTS
Table 5 - Section Capacity (Summary) – LC4.5 Section
No. Elevation (ft) Component Type Size Critical Element P (K) SF*P_allow
(K) %
Capacity Pass / Fail
T1 260 - 240 Leg 1 3/4 3 -50.228 71.402 70.3 Pass
T2 240 - 220 Leg 1 3/4 72 -57.519 71.402 80.6 Pass
T3 220 - 200 Leg 1 3/4 141 -71.472 71.402 100.1 Pass2
T4 200 - 180 Leg 1 3/4 210 -63.356 71.402 88.7 Pass
T5 180 - 160 Leg 1 3/4 279 -66.606 71.402 93.3 Pass
T6 160 - 140 Leg 1 3/4 348 -69.676 71.402 97.6 Pass
T7 140 - 120 Leg 1 3/4 417 -57.891 71.402 81.1 Pass
T8 120 - 100 Leg 1 3/4 486 -67.627 71.402 94.7 Pass
T9 100 - 80 Leg 1 3/4 555 -56.329 71.402 78.9 Pass
T10 80 - 60 Leg 1 3/4 601 -39.782 71.402 55.7 Pass
T11 60 - 40 Leg 1 3/4 651 -43.122 71.402 60.4 Pass
T12 40 - 20 Leg 1 3/4 697 -46.551 71.402 65.2 Pass
T13 20 - 5.75 Leg 2 745 -46.207 102.811 44.9 Pass
T14 5.75 - 0 Leg 2 781 -45.240 128.203 35.3 Pass
T1 260 - 240 Diagonal 3/4 50 -6.090 6.467 94.2 Pass
T2 240 - 220 Diagonal 3/4 84 -3.216 6.467 49.7 Pass
T3 220 - 200 Diagonal 3/4 149 -3.720 6.467 57.5 Pass
T4 200 - 180 Diagonal 7/8 272 -3.729 10.657 35.0 Pass
T5 180 - 160 Diagonal 7/8 291 -4.285 10.657 40.2 Pass
T6 160 - 140 Diagonal 7/8 414 -4.979 10.657 46.7 Pass
T7 140 - 120 Diagonal 7/8 429 -4.037 10.657 37.9 Pass
T8 120 - 100 Diagonal 7/8 498 -4.486 10.657 42.1 Pass
T9 100 - 80 Diagonal 3/4'' w/ 1'' SR with Crosby
600 -4.262 5.465 78.0 Pass
T10 80 - 60 Diagonal 3/4 610 -1.916 2.733 70.1 Pass
T11 60 - 40 Diagonal 3/4 672 -2.740 2.733 100.3 Pass2
T12 40 - 20 Diagonal 3/4 744 -1.969 2.733 72.0 Pass
T13 20 - 5.75 Diagonal 3/4 756 -1.804 2.767 65.2 Pass
T1 260 - 240 Horizontal 3/4 43 -1.471 4.420 33.3 Pass
T2 240 - 220 Horizontal 3/4 87 1.504 14.314 10.5 Pass
T3 220 - 200 Horizontal 3/4 181 -0.834 4.420 18.9 Pass
T4 200 - 180 Horizontal 3/4 225 2.266 14.314 15.8 Pass
T5 180 - 160 Horizontal 3/4 294 2.335 14.314 16.3 Pass
T6 160 - 140 Horizontal 3/4 399 2.701 14.314 18.9 Pass
T7 140 - 120 Horizontal 3/4 432 2.523 14.314 17.6 Pass
T8 120 - 100 Horizontal 3/4 510 7.397 14.314 51.7 Pass
T9 100 - 80 Horizontal 3/4 567 -0.976 4.420 22.1 Pass
T10 80 - 60 Horizontal 3/4 613 -0.689 4.420 15.6 Pass
T11 60 - 40 Horizontal 3/4 662 -0.747 4.420 16.9 Pass
T12 40 - 20 Horizontal 3/4 709 -0.806 4.420 18.2 Pass
T13 20 - 5.75 Horizontal 3/4 757 -0.800 4.475 17.9 Pass
T1 260 - 240 Top Girt 3/4 4 -0.134 4.420 3.0 Pass
T2 240 - 220 Top Girt 3/4 73 0.957 14.314 6.7 Pass
T3 220 - 200 Top Girt 3/4 142 0.591 14.314 4.1 Pass
Reviewed for CodeCompliance
PRBD20170308782
June 23, 2016 260 Ft Guyed Tower Structural Modification Report CCI BU No. 844061 Project Number 106729.001.01, Application 328847, Revision 5 Page 6
tnxTower Report - version 7.0.5.1
Section No. Elevation (ft) Component Type Size Critical
Element P (K) SF*P_allow (K)
% Capacity Pass / Fail
T4 200 - 180 Top Girt 3/4 213 1.668 14.314 11.7 Pass
T5 180 - 160 Top Girt 3/4 282 1.242 14.314 8.7 Pass
T6 160 - 140 Top Girt 3/4 350 1.322 14.314 9.2 Pass
T7 140 - 120 Top Girt 3/4 419 1.550 14.314 10.8 Pass
T8 120 - 100 Top Girt 3/4 488 1.331 14.314 9.3 Pass
T9 100 - 80 Top Girt 3/4 558 -1.236 4.420 28.0 Pass
T10 80 - 60 Top Girt 3/4 606 -0.374 4.420 8.5 Pass
T11 60 - 40 Top Girt 3/4 652 -0.569 4.420 12.9 Pass
T12 40 - 20 Top Girt 3/4 701 -0.649 4.420 14.7 Pass
T13 20 - 5.75 Top Girt 3/4 749 -0.162 4.475 3.6 Pass
T14 5.75 - 0 Top Girt C4x5.4 784 7.351 51.516 14.3 Pass
T1 260 - 240 Bottom Girt 3/4 9 0.786 14.314 5.5 Pass
T2 240 - 220 Bottom Girt 3/4 76 -0.599 4.420 13.6 Pass
T3 220 - 200 Bottom Girt 3/4 147 0.881 14.314 6.2 Pass
T4 200 - 180 Bottom Girt 3/4 216 1.289 14.314 9.0 Pass
T5 180 - 160 Bottom Girt 3/4 285 1.789 14.314 12.5 Pass
T6 160 - 140 Bottom Girt 3/4 354 1.293 14.314 9.0 Pass
T7 140 - 120 Bottom Girt 3/4 423 1.545 14.314 10.8 Pass
T8 120 - 100 Bottom Girt 3/4 490 1.987 14.314 13.9 Pass
T9 100 - 80 Bottom Girt 3/4 561 -0.778 4.420 17.6 Pass
T10 80 - 60 Bottom Girt 3/4 608 -0.725 4.420 16.4 Pass
T11 60 - 40 Bottom Girt 3/4 657 -0.786 4.420 17.8 Pass
T12 40 - 20 Bottom Girt 3/4 705 -0.101 4.420 2.3 Pass
T13 20 - 5.75 Bottom Girt 3/4 753 1.454 14.314 10.2 Pass
T14 5.75 - 0 Mid Girt C4x5.4 793 0.210 51.516 0.4 Pass
T1 260 - 240 Guy [email protected] 3/4 801 32.664 34.980 93.4 Pass
T3 220 - 200 Guy [email protected] 9/16 807 16.389 21.000 78.0 Pass
T6 160 - 140 Guy [email protected] 5/8 813 13.209 25.440 51.9 Pass
T8 120 - 100 Guy [email protected] 9/16 827 8.660 21.000 41.2 Pass
T11 60 - 40 Guy [email protected] 11/16 837 10.493 29.400 35.7 Pass
T1 260 - 240 Guy [email protected] 3/4 800 32.744 34.980 93.6 Pass
T3 220 - 200 Guy [email protected] 9/16 806 16.476 21.000 78.5 Pass
T6 160 - 140 Guy [email protected] 5/8 812 13.312 25.440 52.3 Pass
T8 120 - 100 Guy [email protected] 9/16 821 8.960 21.000 42.7 Pass
T11 60 - 40 Guy [email protected] 11/16 836 10.527 29.400 35.8 Pass
T1 260 - 240 Guy [email protected] 3/4 796 32.624 34.980 93.3 Pass
T3 220 - 200 Guy [email protected] 9/16 802 16.421 21.000 78.2 Pass
T6 160 - 140 Guy [email protected] 5/8 808 13.280 25.440 52.2 Pass
T8 120 - 100 Guy [email protected] 9/16 814 9.145 21.000 43.5 Pass
T11 60 - 40 Guy [email protected] 11/16 832 10.511 29.400 35.8 Pass
T1 260 - 240 Top Guy [email protected]
3x3/8 797 6.771 36.450 18.6 22.3 (b)
Pass
T3 220 - 200 Top Guy [email protected]
3x1/4 805 3.219 24.300 13.2 Pass
T6 160 - 140 Top Guy [email protected]
3x3/8 811 4.078 36.450 11.2 13.4 (b)
Pass
T11 60 - 40 Top Guy [email protected]
3x1/4 834 3.770 24.300 15.5 Pass
Reviewed for CodeCompliance
PRBD20170308782
June 23, 2016 260 Ft Guyed Tower Structural Modification Report CCI BU No. 844061 Project Number 106729.001.01, Application 328847, Revision 5 Page 7
tnxTower Report - version 7.0.5.1
Section No. Elevation (ft) Component Type Size Critical
Element P (K) SF*P_allow (K)
% Capacity Pass / Fail
T8 120 - 100 Torque Arm [email protected]
L5x5x5/16 817 12.702 98.172 12.9 Pass
T8 120 - 100 Torque Arm [email protected]
L3 1/2x5x5/16 818 -12.577 41.922 30.0 Pass
Summary Leg (T3) 100.1 Pass2
Diagonal (T11) 100.3 Pass2
Horizontal (T8) 51.7 Pass
Top Girt (T9) 28.0 Pass
Bottom Girt (T11) 17.8 Pass
Mid Girt (T14) 0.4 Pass
Guy A (T1) 93.4 Pass
Guy B (T1) 93.6 Pass
Guy C (T1) 93.3 Pass
Top Guy Pull-Off (T1) 22.3 Pass
Torque Arm Top (T8) 12.9 Pass
Torque Arm Bottom (T8) 30.0 Pass
Bolt Checks 22.3 Pass
RATING = 100.3 Pass 2
Table 6 - Tower Component Stresses vs. Capacity - LC4.5
Notes Component Elevation (ft) % Capacity Pass / Fail
1 Base Foundation (Structure) Base 1.3 Pass 1 Base Foundation (Soil) Base 50.1 Pass
1,2 Guy Anchor Foundation (Structure) Base 104.2 Pass
1 Guy Anchor Foundation (Soil) Base 57.6 Pass
Structure Rating (max from all components) = 104.2%
Notes: 1) See additional documentation in “Appendix C – Additional Calculations” for calculations supporting the % capacity
consumed. 2) Capacities up to 105% are considered acceptable based on analysis methods used.
4.1) Recommendations
1) All modifications proposed in this report shall be installed in accordance with the attached drawings (Appendix D) for the determined available structural capacity to be effective.
Reviewed for CodeCompliance
PRBD20170308782
APPENDIX A
tnxTOWER OUTPUT
Reviewed for CodeCompliance
PRBD20170308782
B+T Group 1717 S Boulder Ave, Suite 300
Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265
Job: 106729.001.01 - Lake Trafford, FL (BU# 844061
Project: Client: Crown Castle Drawn by: ushrestha App'd:
Code: TIA-222-G Date: 06/22/16 Scale: NTS Path:
\\tower-two\BT Telecom Services\Projects\Crown Castle\106000\106729_844061_Lake Trafford\Engineering\tnxTower\001 - Mod\106729_001_01_Lake Trafford_FL_Mod.eri
Dwg No. E-1
3/4 EHS LC
=322'10-3/8" IT=12%
R=208'
9/16 EHS LC=293'2-3/32" IT=12%
5/8 EHS LC=258'11" IT=8%
9/16 EHS LC=230'4-9/32" IT=8%
9/16 EHS LC=230'4-9/32" IT=8%
11/16 EHS LC=212'3-15/32" IT=10%
260.0 ft
240.0 ft
248.6 ft248.6 ft248.6 ft
220.0 ft
200.0 ft
208.6 ft208.6 ft208.6 ft
180.0 ft
160.0 ft
140.0 ft
156.9 ft156.9 ft156.9 ft
120.0 ft
100.0 ft
105.9 ft105.9 ft105.9 ft105.9 ft105.9 ft105.9 ft
80.0 ft
60.0 ft
40.0 ft
51.4 ft51.4 ft51.4 ft
20.0 ft
5.8 ft
0.0 ft
121 K (Axial)1 kip-ft (Torque)
2 K69 K
53 K
87 K
ALL REACTIONS ARE FACTORED
Sec
tion
T1
T2
T3
T4
T5
T6
T7
T8
T9
T10
T11
T12
T13
T14
Leg
sS
R 1
3/4
SR
2
Leg
Gra
deA
572-
50
Dia
gona
lsS
R 3
/4S
R 7
/8A
SR
3/4
N.A
.
Dia
gona
l Gra
deA
36N
.A.
Top
Girt
sS
R 3
/4B
Mid
Girt
sN
.A.
B
Bot
tom
Girt
sS
R 3
/4N
.A.
Hor
izon
tals
SR
3/4
N.A
.
Top
Guy
Pul
l-Offs
3x3/
8N
.A.
3x1/
4N
.A.
3x3/
8N
.A.
3x1/
4N
.A.
Fac
e W
idth
(ft)
3.5
# P
anel
s @
(ft)
89 @
2.7
5C
Wei
ght (
K)
0.9
0.9
0.9
1.0
1.0
1.0
1.0
1.7
0.8
0.8
0.8
0.8
0.7
0.3
12.6
PLANR=208' R=207'
R=208'
R=208' R=207'
R=208'
R=208' R=207'
R=208'
R=208' R=207'
R=208'
R=208' R=207'
R=208'
Lightning Rod 3/4" x 6' (E) 263 Flash Beacon (E) 260 (2) DBXCP-4545A-R2M w/ Mount Pipe (E)
257 7251.01 w/ Mount Pipe (E) 257 7251.01 w/ Mount Pipe (E) 257 (2) E15Z01P13 (E) 257 (2) RRUS-11 (E) 257 (2) RRUS-11 (E) 257 (2) RRUS-11 (E) 257 DC6-48-60-18-8F (E) 257 DC6-48-60-18-8F (E) 257 (2) RRUS A2 MODULE (E) 257 RRUS A2 MODULE (E) 257 RRUS A2 MODULE (E) 257 CBC78-DF-2X (E) 257 CBC78-DF-2X (E) 257 (2) BSA-M65R-BUU-H6 w/ Mount Pipe (P)
257 (2) SBNHH-1D85B w/ Mount Pipe (P) 257 (2) SBNHH-1D85B w/ Mount Pipe (P) 257 (2) RRUS 32 (P) 257 RRUS 32 (P) 257 RRUS 32 (P) 257 (2) RRUS 12 (P) 257 RRUS 12 (P) 257 RRUS 12 (P) 257 (2) RRUS-11 (P) 257 (2) LGP 17503 (P) 257 (2) LGP 17503 (P) 257 DC6-48-60-18-8F (P) 257 6' x 2" Mount Pipe (E) 257 6' x 2" Mount Pipe (E) 257 Sector Mount [SM 602-3] (E) 257 Side Lighting (E) 129 Side Lighting (E) 129 Side Lighting (E) 129DESIGNED APPURTENANCE LOADINGTYPE TYPEELEVATION ELEVATION
Lightning Rod 3/4" x 6' (E) 263
Flash Beacon (E) 260
(2) DBXCP-4545A-R2M w/ Mount Pipe (E)
257
7251.01 w/ Mount Pipe (E) 257
7251.01 w/ Mount Pipe (E) 257
(2) E15Z01P13 (E) 257
(2) RRUS-11 (E) 257
(2) RRUS-11 (E) 257
(2) RRUS-11 (E) 257
DC6-48-60-18-8F (E) 257
DC6-48-60-18-8F (E) 257
(2) RRUS A2 MODULE (E) 257
RRUS A2 MODULE (E) 257
RRUS A2 MODULE (E) 257
CBC78-DF-2X (E) 257
CBC78-DF-2X (E) 257
(2) BSA-M65R-BUU-H6 w/ Mount Pipe (P)
257
(2) SBNHH-1D85B w/ Mount Pipe (P) 257
(2) SBNHH-1D85B w/ Mount Pipe (P) 257
(2) RRUS 32 (P) 257
RRUS 32 (P) 257
RRUS 32 (P) 257
(2) RRUS 12 (P) 257
RRUS 12 (P) 257
RRUS 12 (P) 257
(2) RRUS-11 (P) 257
(2) LGP 17503 (P) 257
(2) LGP 17503 (P) 257
DC6-48-60-18-8F (P) 257
6' x 2" Mount Pipe (E) 257
6' x 2" Mount Pipe (E) 257
Sector Mount [SM 602-3] (E) 257
Side Lighting (E) 129
Side Lighting (E) 129
Side Lighting (E) 129
SYMBOL LISTMARK MARKSIZE SIZE
A SR 3/4" w/ 1" SR with Crosby
B C4x5.4
C 4 @ 1.4375
MATERIAL STRENGTHGRADE GRADEFy FyFu Fu
A572-50 50 ksi 65 ksi A36 36 ksi 58 ksi
TOWER DESIGN NOTES1. Tower is located in Collier County, Florida.2. Tower designed for Exposure C to the TIA-222-G Standard.3. Tower designed for a 118 mph basic wind in accordance with the TIA-222-G Standard.4. Deflections are based upon a 60 mph wind.5. Tower Structure Class II.6. Topographic Category 1 with Crest Height of 0'7. TOWER RATING: 100.3%
Reviewed for CodeCompliance
PRBD20170308782
B+T Group 1717 S Boulder Ave, Suite 300
Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265
Job: 106729.001.01 - Lake Trafford, FL (BU# 844061
Project: Client: Crown Castle Drawn by: ushrestha App'd:
Code: TIA-222-G Date: 06/22/16 Scale: NTS Path:
\\tower-two\BT Telecom Services\Projects\Crown Castle\106000\106729_844061_Lake Trafford\Engineering\tnxTower\001 - Mod\106729_001_01_Lake Trafford_FL_Mod.eri
Dwg No. E-2
Base Elev=0'
R=208', 240 deg Azimuth R=207', 120 deg Azimuth
R=208', 0 deg Azimuth
15' 15'
389'4-13/16"
180'1-19/32" 179'3-7/32"
342'
15'
15'
104'
208'
Plot PlanTotal Area - 3.06 Acres
Reviewed for CodeCompliance
PRBD20170308782
B+T Group 1717 S Boulder Ave, Suite 300
Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265
Job: 106729.001.01 - Lake Trafford, FL (BU# 844061
Project: Client: Crown Castle Drawn by: ushrestha App'd:
Code: TIA-222-G Date: 06/22/16 Scale: NTS Path:
\\tower-two\BT Telecom Services\Projects\Crown Castle\106000\106729_844061_Lake Trafford\Engineering\tnxTower\001 - Mod\106729_001_01_Lake Trafford_FL_Mod.eri
Dwg No. E-3
<- Minimum -0 Maximum ->
<- Minimum -0 Maximum ->
-50
-50
-100
-100
-150
-150
50
50
100
100
150
150
TIA-222-G - 118 mph Exposure C
Leg Capacity Leg Compression (K)
260' 260'
240' 240'
248'7-1/2" 248'7-1/2"248'7-1/2" 248'7-1/2"248'7-1/2" 248'7-1/2"
220' 220'
200' 200'
208'7-1/2" 208'7-1/2"208'7-1/2" 208'7-1/2"208'7-1/2" 208'7-1/2"
180' 180'
160' 160'
140' 140'
156'10-1/2" 156'10-1/2"156'10-1/2" 156'10-1/2"156'10-1/2" 156'10-1/2"
120' 120'
100' 100'
105'10-1/2" 105'10-1/2"105'10-1/2" 105'10-1/2"105'10-1/2" 105'10-1/2"105'10-1/2" 105'10-1/2"105'10-1/2" 105'10-1/2"105'10-1/2" 105'10-1/2"
80' 80'
60' 60'
40' 40'
51'4-1/2" 51'4-1/2"51'4-1/2" 51'4-1/2"51'4-1/2" 51'4-1/2"
20' 20'
5'9" 5'9"
0' 0'
Ele
vatio
n (f
t)Reviewed for Code
CompliancePRBD20170308782
B+T Group 1717 S Boulder Ave, Suite 300
Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265
Job: 106729.001.01 - Lake Trafford, FL (BU# 844061
Project: Client: Crown Castle Drawn by: ushrestha App'd:
Code: TIA-222-G Date: 06/22/16 Scale: NTS Path:
\\tower-two\BT Telecom Services\Projects\Crown Castle\106000\106729_844061_Lake Trafford\Engineering\tnxTower\001 - Mod\106729_001_01_Lake Trafford_FL_Mod.eri
Dwg No. E-4
0
0
5
5
10
10
15
15
Global Mast Shear (K)260'
240'
248'7-1/2"248'7-1/2"248'7-1/2"
220'
200'
208'7-1/2"208'7-1/2"208'7-1/2"
180'
160'
140'
156'10-1/2"156'10-1/2"156'10-1/2"
120'
100'
105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"
80'
60'
40'
51'4-1/2"51'4-1/2"51'4-1/2"
20'
5'9"
0'
Ele
vatio
n (f
t)
0
0
50
50
100
100
150
150
200
200
Global Mast Moment (kip-ft)260'
240'
248'7-1/2"248'7-1/2"248'7-1/2"
220'
200'
208'7-1/2"208'7-1/2"208'7-1/2"
180'
160'
140'
156'10-1/2"156'10-1/2"156'10-1/2"
120'
100'
105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"
80'
60'
40'
51'4-1/2"51'4-1/2"51'4-1/2"
20'
5'9"
0'
TIA-222-G - 118 mph Exposure C Maximum ValuesVx Vz Mx Mz
Reviewed for CodeCompliance
PRBD20170308782
B+T Group 1717 S Boulder Ave, Suite 300
Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265
Job: 106729.001.01 - Lake Trafford, FL (BU# 844061
Project: Client: Crown Castle Drawn by: ushrestha App'd:
Code: TIA-222-G Date: 06/22/16 Scale: NTS Path:
\\tower-two\BT Telecom Services\Projects\Crown Castle\106000\106729_844061_Lake Trafford\Engineering\tnxTower\001 - Mod\106729_001_01_Lake Trafford_FL_Mod.eri
Dwg No. E-5
TIA-222-G - Service - 60 mph Maximum Values
0
0
5
5
Deflection (in)260'
240'
248'7-1/2"248'7-1/2"248'7-1/2"
220'
200'
208'7-1/2"208'7-1/2"208'7-1/2"
180'
160'
140'
156'10-1/2"156'10-1/2"156'10-1/2"
120'
100'
105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"
80'
60'
40'
51'4-1/2"51'4-1/2"51'4-1/2"
20'
5'9"
0'
Ele
vatio
n (f
t)
0
0
0.05
0.05
0.1
0.1
0.15
0.15
0.2
0.2
0.25
0.25
Tilt (deg)0
0
0.5
0.5
1
1
Twist (deg)260'
240'
248'7-1/2"248'7-1/2"248'7-1/2"
220'
200'
208'7-1/2"208'7-1/2"208'7-1/2"
180'
160'
140'
156'10-1/2"156'10-1/2"156'10-1/2"
120'
100'
105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"
80'
60'
40'
51'4-1/2"51'4-1/2"51'4-1/2"
20'
5'9"
0'
Reviewed for CodeCompliance
PRBD20170308782
B+T Group 1717 S Boulder Ave, Suite 300
Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265
Job: 106729.001.01 - Lake Trafford, FL (BU# 844061
Project: Client: Crown Castle Drawn by: ushrestha App'd:
Code: TIA-222-G Date: 06/22/16 Scale: NTS Path:
\\tower-two\BT Telecom Services\Projects\Crown Castle\106000\106729_844061_Lake Trafford\Engineering\tnxTower\001 - Mod\106729_001_01_Lake Trafford_FL_Mod.eri
Dwg No. E-6
260.0 ft
240.0 ft
248.6 ft248.6 ft248.6 ft
220.0 ft
200.0 ft
208.6 ft208.6 ft208.6 ft
180.0 ft
160.0 ft
140.0 ft
156.9 ft156.9 ft156.9 ft
120.0 ft
100.0 ft
105.9 ft105.9 ft105.9 ft105.9 ft105.9 ft105.9 ft
80.0 ft
60.0 ft
40.0 ft
51.4 ft51.4 ft51.4 ft
20.0 ft
5.8 ft
0.0 ft
121 K (Axial)1 kip-ft (Torque)
2 K
67 K
ELEVATION
52 K38 deg
67 K
3 K
PLAN
85 K
248'7-1/2"
208'7-1/2"
156'10-1/2"
105'10-1/2"
51'4-1/2"
3/4 EHS, SF = 1.07, Tm
ax = 32.664 K, Lc = 322'10-3/8", Lu = 322'5-3/4", Ls = 324'1-15/32"
R=208'
9/16 EHS, SF = 1.28, Tmax = 16.421 K, Lc = 293'2-3/32", Lu = 292'10-5/32", Ls = 294'1/4"
5/8 EHS, SF = 1.92, Tmax = 13.280 K, Lc = 258'11", Lu = 258'8-13/16", Ls = 259'5-1/8"
9/16 EHS, SF = 2.30, Tmax = 9.145 K, Lc = 230'4-9/32", Lu = 230'2-15/32", Ls = 230'8-5/8"
11/16 EHS, SF = 2.80, Tmax = 10.511 K, Lc = 212'3-15/32", Lu = 212'1-15/32", Ls = 212'6"
Guy Tensions and Tower ReactionsTIA-222-G - 118 mph Exposure C
Maximum ValuesAnchor 'C'@208 ft Azimuth 240 deg Elev 0 ft
Plane through centroid of towerReviewed for Code
CompliancePRBD20170308782
B+T Group 1717 S Boulder Ave, Suite 300
Tulsa, OK 74119 Phone: (918) 587-4630 FAX: (918) 295-0265
Job: 106729.001.01 - Lake Trafford, FL (BU# 844061
Project: Client: Crown Castle Drawn by: ushrestha App'd:
Code: TIA-222-G Date: 06/22/16 Scale: NTS Path:
\\tower-two\BT Telecom Services\Projects\Crown Castle\106000\106729_844061_Lake Trafford\Engineering\tnxTower\001 - Mod\106729_001_01_Lake Trafford_FL_Mod.eri
Dwg No. E-7
Feed Line Distribution Chart5'9" - 260'
Round Flat App In Face App Out Face Truss Leg
Face A
240'
248'7-1/2"248'7-1/2"248'7-1/2"
220'
200'
208'7-1/2"208'7-1/2"208'7-1/2"
180'
160'
140'
156'10-1/2"156'10-1/2"156'10-1/2"
120'
100'
105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"
80'
60'
40'
51'4-1/2"51'4-1/2"51'4-1/2"
20'
5'9"
260'
Ele
vatio
n (f
t)
(3)
AT
CB
-B01
(5/1
6")
(E)
(6)
LDF
6-50
A(1
-1/4
") (
E)
(6)
LDF
7-50
A(1
-5/8
") (
E)
(2)
LDF
7-50
A(1
-5/8
") (
E)
(3)
FB
-L98
B-0
02-X
XX
( 3/
8")
(2 E
+ 1
P)
(2)
WR
-VG
86S
T-B
RD
(3/4
") (
E)
(3)
WR
-VG
86S
T-B
RD
(3/4
") (
2 P
+ 1
E)
T-B
rack
ets
(Af)
(E
)
Face B257'257'257'257'257'257'257'257'
129'129'
Saf
ety
Line
3/8
(E
)
Face C
240'
248'7-1/2"248'7-1/2"248'7-1/2"
220'
200'
208'7-1/2"208'7-1/2"208'7-1/2"
180'
160'
140'
156'10-1/2"156'10-1/2"156'10-1/2"
120'
100'
105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"105'10-1/2"
80'
60'
40'
51'4-1/2"51'4-1/2"51'4-1/2"
20'
5'9"
260'257'257'257'257'257'257'257'257'
129'129'
AV
A5-
50(
7/8"
) (E
-Lig
htin
g)
(2)
AV
A5-
50(
7/8"
) (E
-Lig
htin
g)
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
1 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Tower Input Data The main tower is a 3x guyed tower with an overall height of 260' above the ground line. The base of the tower is set at an elevation of 0' above the ground line. The face width of the tower is 3'6'' at the top and tapered at the base. This tower is designed using the TIA-222-G standard. The following design criteria apply:
Tower is located in Collier County, Florida. Basic wind speed of 118 mph. Structure Class II. Exposure Category C. Topographic Category 1. Crest Height 0'. Deflections calculated using a wind speed of 60 mph. Pressures are calculated at each section. Safety factor used in guy design is 1. Stress ratio used in tower member design is 1. Local bending stresses due to climbing loads, feed line supports, and appurtenance mounts are not considered.
Leg B
Guy B
Leg C
Guy C
Leg A
Guy
A
Face
A Face B
Face C
Corner & Starmount Guyed Tower
Wind 0
Wind 90
Wind 180
Z
X
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
2 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Leg B
Guy B
Leg C
Guy C
Leg A
Guy
A
Face
A Face B
Face C
Face Guyed
Wind 0
Wind 90
Wind 180
Z
X
Tower Section Geometry
Tower Section
Tower Elevation
ft
Assembly Database
Description Section Width
ft
Number of
Sections
Section Length
ft
T1 260'-240' 3'6'' 1 20' T2 240'-220' 3'6'' 1 20' T3 220'-200' 3'6'' 1 20' T4 200'-180' 3'6'' 1 20' T5 180'-160' 3'6'' 1 20' T6 160'-140' 3'6'' 1 20' T7 140'-120' 3'6'' 1 20' T8 120'-100' 3'6'' 1 20' T9 100'-80' 3'6'' 1 20' T10 80'-60' 3'6'' 1 20' T11 60'-40' 3'6'' 1 20' T12 40'-20' 3'6'' 1 20' T13 20'-5'9'' 3'6'' 1 14'3'' T14 5'9''-0' 3'6'' 1 5'9''
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
3 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Tower Section Geometry (cont’d)
Tower Section
Tower Elevation
ft
Diagonal Spacing
ft
Bracing Type
Has K Brace
End Panels
Has Horizontals
Top Girt Offset
in
Bottom Girt Offset
in
T1 260'-240' 2'9'' X Brace No Yes 4.500 4.500 T2 240'-220' 2'9'' X Brace No Yes 4.500 4.500 T3 220'-200' 2'9'' X Brace No Yes 4.500 4.500 T4 200'-180' 2'9'' X Brace No Yes 4.500 4.500 T5 180'-160' 2'9'' X Brace No Yes 4.500 4.500 T6 160'-140' 2'9'' X Brace No Yes 4.500 4.500 T7 140'-120' 2'9'' X Brace No Yes 4.500 4.500 T8 120'-100' 2'9'' X Brace No Yes 4.500 4.500 T9 100'-80' 2'9'' K Brace Right No Yes 4.500 4.500 T10 80'-60' 2'9'' K Brace Right No Yes 4.500 4.500 T11 60'-40' 2'9'' K Brace Right No Yes 4.500 4.500 T12 40'-20' 2'9'' K Brace Right No Yes 4.500 4.500 T13 20'-5'9'' 2'9'' K Brace Right No Yes 3.000 3.000 T14 5'9''-0' 1'5-1/4'' X Brace No Yes 0.000 0.000
Tower Section Geometry (cont’d)
Tower Elevation
ft
Leg Type
Leg Size
Leg Grade
Diagonal Type
Diagonal Size
Diagonal Grade
T1 260'-240' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 3/4 A36 (36 ksi)
T2 240'-220' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 3/4 A36 (36 ksi)
T3 220'-200' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 3/4 A36 (36 ksi)
T4 200'-180' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 7/8 A36 (36 ksi)
T5 180'-160' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 7/8 A36 (36 ksi)
T6 160'-140' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 7/8 A36 (36 ksi)
T7 140'-120' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 7/8 A36 (36 ksi)
T8 120'-100' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 7/8 A36 (36 ksi)
T9 100'-80' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 3/4'' w/ 1'' SR with Crosby A36 (36 ksi)
T10 80'-60' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 3/4 A36 (36 ksi)
T11 60'-40' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 3/4 A36 (36 ksi)
T12 40'-20' Solid Round 1 3/4 A572-50 (50 ksi)
Solid Round 3/4 A36 (36 ksi)
T13 20'-5'9'' Solid Round 2 A572-50 (50 ksi)
Solid Round 3/4 A36 (36 ksi)
T14 5'9''-0' Solid Round 2 A572-50 (50 ksi)
Channel A36 (36 ksi)
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
4 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Tower Section Geometry (cont’d)
Tower Elevation
ft
Top Girt Type
Top Girt Size
Top Girt Grade
Bottom Girt Type
Bottom Girt Size
Bottom Girt Grade
T1 260'-240' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T2 240'-220' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T3 220'-200' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T4 200'-180' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T5 180'-160' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T6 160'-140' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T7 140'-120' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T8 120'-100' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T9 100'-80' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T10 80'-60' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T11 60'-40' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T12 40'-20' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T13 20'-5'9'' Solid Round 3/4 A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T14 5'9''-0' Channel C4x5.4 A36 (36 ksi)
Equal Angle L3 1/2x3 1/2x3/8 A36 (36 ksi)
Tower Section Geometry (cont’d)
Tower Elevation
ft
No. of
Mid Girts
Mid Girt Type
Mid Girt Size
Mid Girt Grade
Horizontal Type
Horizontal Size
Horizontal Grade
T1 260'-240' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T2 240'-220' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T3 220'-200' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T4 200'-180' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T5 180'-160' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T6 160'-140' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T7 140'-120' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T8 120'-100' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T9 100'-80' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
5 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Tower Elevation
ft
No. of
Mid Girts
Mid Girt Type
Mid Girt Size
Mid Girt Grade
Horizontal Type
Horizontal Size
Horizontal Grade
T10 80'-60' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T11 60'-40' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T12 40'-20' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T13 20'-5'9'' None Solid Round A36 (36 ksi)
Solid Round 3/4 A36 (36 ksi)
T14 5'9''-0' 3 Channel C4x5.4 A36 (36 ksi)
Channel C4x5.4 A36 (36 ksi)
Tower Section Geometry (cont’d)
Tower Elevation
ft
Gusset Area
(per face)
ft2
Gusset Thickness
in
Gusset Grade Adjust. FactorAf
Adjust. Factor
Ar
Weight Mult.
Double Angle Stitch Bolt Spacing
Diagonals in
Double Angle Stitch Bolt Spacing
Horizontals in
Double Angle Stitch Bolt Spacing
Redundants in
T1 260'-240' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T2 240'-220' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T3 220'-200' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T4 200'-180' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T5 180'-160' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T6 160'-140' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T7 140'-120' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T8 120'-100' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T9 100'-80' 0.000 0.000 A36 (36 ksi)
1 1 1.05 36.000 36.000 36.000
T10 80'-60' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T11 60'-40' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T12 40'-20' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T13 20'-5'9'' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
T14 5'9''-0' 0.000 0.000 A36 (36 ksi)
1 1 1 36.000 36.000 36.000
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
6 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Tower Section Geometry (cont’d)
K Factors1
Tower Elevation
ft
Calc K
Single Angles
Calc K
Solid Rounds
Legs X Brace Diags
X Y
K Brace Diags
X Y
Single Diags
X Y
Girts
X Y
Horiz.
X Y
Sec. Horiz.
X Y
Inner Brace
X Y
T1 260'-240' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
T2 240'-220' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
T3 220'-200' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
T4 200'-180' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 0.5
1 1
T5 180'-160' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 0.5
1 1
T6 160'-140' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 0.5
1 1
T7 140'-120' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
T8 120'-100' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
T9 100'-80' Yes No 1 1 1
0.495 0.495
1 1
0.7 0.7
0.7 0.7
1 1
1 1
T10 80'-60' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
T11 60'-40' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
T12 40'-20' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
T13 20'-5'9'' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
T14 5'9''-0' Yes Yes 1 1 1
1 1
1 1
1 1
1 1
1 1
1 1
1Note: K factors are applied to member segment lengths. K-braces without inner supporting members will have the K factor in the out-of-plane direction applied to the overall length.
Tower Section Geometry (cont’d)
Tower Elevation
ft
Leg Diagonal Top Girt Bottom Girt Mid Girt Long Horizontal Short Horizontal
Net Width Deduct
in
U
Net Width Deduct
in
U
Net WidthDeduct
in
U
Net Width Deduct
in
U
Net Width Deduct
in
U
Net Width Deduct
in
U
Net Width Deduct
in
U
T1 260'-240' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T2 240'-220' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T3 220'-200' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T4 200'-180' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T5 180'-160' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T6 160'-140' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T7 140'-120' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T8 120'-100' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T9 100'-80' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T10 80'-60' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T11 60'-40' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
7 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Tower Elevation
ft
Leg Diagonal Top Girt Bottom Girt Mid Girt Long Horizontal Short Horizontal
Net Width Deduct
in
U
Net Width Deduct
in
U
Net WidthDeduct
in
U
Net Width Deduct
in
U
Net Width Deduct
in
U
Net Width Deduct
in
U
Net Width Deduct
in
U
T12 40'-20' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T13 20'-5'9'' 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 0.000 1 T14 5'9''-0' 0.000 1 0.000 1 0.000 0.75 0.000 0.75 0.000 0.75 0.000 0.75 0.000 1
Tower Section Geometry (cont’d)
Tower Elevation
ft
Leg Connection
Type
Leg Diagonal Top Girt Bottom Girt Mid Girt Long Horizontal Short Horizontal
Bolt Size in
No. Bolt Size in
No. Bolt Sizein
No. Bolt Sizein
No. Bolt Sizein
No. Bolt Size in
No. Bolt Sizein
No.
T1 260'-240' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T2 240'-220' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T3 220'-200' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T4 200'-180' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T5 180'-160' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T6 160'-140' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T7 140'-120' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T8 120'-100' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T9 100'-80' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T10 80'-60' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T11 60'-40' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T12 40'-20' Flange 0.750 A325N
4 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T13 20'-5'9'' Flange 0.750 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
T14 5'9''-0' Flange 0.750 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0 0.625 A325N
0
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
8 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Guy Data
Guy Elevation
ft
Guy Grade
Guy Size
Initial Tension
K
%
Guy Modulus
ksi
Guy Weight
plf
Lu
ft
Anchor Radius
ft
Anchor Azimuth
Adj. °
Anchor Elevation
ft
End Fitting
Efficiency%
248.625 EHS A B C
3/4 3/4 3/4
6.996 6.996 6.996
12%12%12%
19000.00019000.00019000.000
1.155 1.155 1.155
322'6-7/32''321'10-19/32
'' 322'6-7/32''
208' 207' 208'
0.000 0.000 0.000
0' 0' 0'
100% 100% 100%
208.625 EHS A B C
9/16 9/16 9/16
4.200 4.200 4.200
12%12%12%
21000.00021000.00021000.000
0.671 0.671 0.671
292'10-19/32''
292'2-3/16''292'10-19/32
''
208' 207' 208'
0.000 0.000 0.000
0' 0' 0'
100% 100% 100%
156.875 EHS A B C
5/8 5/8 5/8
3.392 3.392 3.392
8% 8% 8%
21000.00021000.00021000.000
0.813 0.813 0.813
258'9-1/8'' 257'11-19/32
'' 258'9-1/8''
208' 207' 208'
0.000 0.000 0.000
0' 0' 0'
100% 100% 100%
105.875 EHS A B C
9/16 9/16 9/16
2.800 2.800 2.800
8% 8% 8%
21000.00021000.00021000.000
0.671 0.671 0.671
230'2-5/8'' 229'4''
230'2-5/8''
208' 207' 208'
0.000 0.000 0.000
0' 0' 0'
100% 100% 100%
51.375 EHS A B C
11/16 11/16 11/16
4.900 4.900 4.900
10%10%10%
21000.00021000.00021000.000
0.950 0.950 0.950
212'1-1/2'' 211'1-7/8'' 212'1-1/2''
208' 207' 208'
0.000 0.000 0.000
0' 0' 0'
100% 100% 100%
Guy Data (cont’d)
Guy Elevation
ft
Mount Type
Torque-Arm Spread
ft
Torque-Arm Leg Angle
°
Torque-Arm Style
Torque-Arm Grade
Torque-Arm Type
Torque-Arm Size
248.625 Corner 208.625 Corner 156.875 Corner 105.875 Torque Arm 12'1-23/32'' 26.600 Bat Ear A36
(36 ksi) Single Angle L5x5x5/16
L3 1/2x5x5/16 51.375 Corner
Guy Data (cont’d)
Guy Elevation
ft
Diagonal Grade
Diagonal Type
Upper Diagonal Size
Lower Diagonal Size
Is Strap.
Pull-Off Grade
Pull-Off Type Pull-Off Size
248'7-1/2'' A572-50 (50 ksi)
Solid Round Yes A36 (36 ksi)
Flat Bar 3x3/8
208'7-1/2'' A572-50 (50 ksi)
Solid Round Yes A36 (36 ksi)
Flat Bar 3x1/4
156'10-1/2''
A572-50 (50 ksi)
Solid Round Yes A36 (36 ksi)
Flat Bar 3x3/8
105'10-1/2''
A572-50 (50 ksi)
Solid Round A36 (36 ksi)
Solid Round
51'4-1/2'' A572-50 (50 ksi)
Solid Round Yes A36 (36 ksi)
Flat Bar 3x1/4
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
9 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Guy Data (cont’d)
Guy Elevation
ft
Cable Weight
A K
Cable Weight
B K
Cable Weight
C K
Cable Weight
D K
Tower Intercept
A ft
Tower Intercept
B ft
Tower Intercept
C ft
Tower Intercept
D ft
248.625 0.373 0.372 0.373 8'5-3/32'' 5.0 sec/pulse
8'4-11/16'' 5.0 sec/pulse
8'5-3/32'' 5.0 sec/pulse
208.625 0.197 0.196 0.197 6'8-31/32'' 4.5 sec/pulse
6'8-19/32'' 4.5 sec/pulse
6'8-31/32'' 4.5 sec/pulse
156.875 0.210 0.210 0.210 7'10-19/32'' 4.8 sec/pulse
7'10-1/32'' 4.8 sec/pulse
7'10-19/32'' 4.8 sec/pulse
105.875 0.154 0.154 0.154 6'3-5/16'' 4.3 sec/pulse
6'2-3/4'' 4.3 sec/pulse
6'3-5/16'' 4.3 sec/pulse
51.375 0.202 0.201 0.202 4'4-1/8'' 3.6 sec/pulse
4'3-21/32'' 3.6 sec/pulse
4'4-1/8'' 3.6 sec/pulse
Guy Data (cont’d)
Torque Arm Pull Off DiagonalGuy
Elevation ft
Calc K
Single Angles
Calc K
Solid Rounds
Kx Ky Kx Ky Kx Ky
248.625 No No 1 1 1 1 208.625 No No 1 1 1 1 156.875 Yes Yes 1 1 1 1 105.875 Yes Yes 1 1 1 1 1 1 51.375 No No 1 1 1 1
Guy Data (cont’d)
Torque-Arm Pull Off Diagonal Guy
Elevation ft
Bolt Size in
Number Net Width Deduct
in
U
Bolt Sizein
Number Net WidthDeduct
in
U
Bolt Sizein
Number Net WidthDeduct
in
U
248.625 0.625 A325N
0 0.000 0.75 0.625 A325X
2 0.000 1 0.625 A325N
0 0.000 0.75
208.625 0.625 A325N
0 0.000 0.75 0.625 A325N
0 0.000 1 0.625 A325N
0 0.000 0.75
156.875 0.000 A325N
0 0.000 0.75 0.625 A325X
2 0.000 1 0.625 A325N
0 0.000 0.75
105.875 0.000 A325N
0 0.000 0.75 0.625 A325N
0 0.000 1 0.625 A325N
0 0.000 0.75
51.375 0.625 A325N
0 0.000 0.75 0.625 A325N
0 0.000 1 0.625 A325N
0 0.000 0.75
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
10 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Guy Pressures
Guy Elevation
ft
Guy Location
z
ft
qz
ksf
qz Ice ksf
Ice Thickness
in 248.625 A
B C
124'3-3/4'' 124'3-3/4'' 124'3-3/4''
0.040 0.040 0.040
208.625 A B C
104'3-3/4'' 104'3-3/4'' 104'3-3/4''
0.039 0.039 0.039
156.875 A B C
78'5-1/4'' 78'5-1/4'' 78'5-1/4''
0.036 0.036 0.036
105.875 A B C
52'11-1/4'' 52'11-1/4'' 52'11-1/4''
0.034 0.034 0.034
51.375 A B C
25'8-1/4'' 25'8-1/4'' 25'8-1/4''
0.029 0.029 0.029
Feed Line/Linear Appurtenances - Entered As Round Or Flat
Description Face or
Leg
Allow Shield
Component Type
Placement
ft
Face Offset
in
Lateral Offset
(Frac FW)
# # Per Row
Clear Spacing
in
Width or Diameter
in
Perimeter
in
Weight
klf ATCB-B01(5/
16'') (E)
A No Ar (CaAa) 257' - 0' 0.000 0.03 3 3 0.315 0.315 0.000
LDF6-50A(1-1/4'') (E)
A No Ar (CaAa) 257' - 0' -1.000 0.22 6 3 0.750 1.550 0.001
LDF7-50A(1-5/8'') (E)
A No Ar (CaAa) 257' - 0' 0.000 0.37 6 2 0.850 0.750
1.980 0.001
LDF7-50A(1-5/8'') (E)
A No Ar (CaAa) 257' - 0' 0.000 -0.35 2 2 0.850 0.750
1.980 0.001
FB-L98B-002-XXX( 3/8'') (2 E + 1 P)
A No Ar (CaAa) 257' - 0' 0.000 0.08 3 3 0.375 0.394 0.000
WR-VG86ST-BRD(3/4'')
(E)
A No Ar (CaAa) 257' - 0' 0.000 0.12 2 1 0.750 0.795 0.001
WR-VG86ST-BRD(3/4'') (2 P + 1 E)
A No Ar (CaAa) 257' - 0' 0.000 -0.05 3 2 0.750 0.795 0.001
T-Brackets (Af) (E)
A No Af (CaAa) 257' - 0' 0.000 0 1 1 1.000 1.000 0.008
**-**-** AVA5-50(
7/8'') (E-Lighting)
C No Ar (CaAa) 260' - 129' 0.000 -0.5 1 1 0.850 0.750
1.102 0.000
AVA5-50( 7/8'')
(E-Lighting)
C No Ar (CaAa) 129' - 0' 0.000 -0.5 2 2 0.850 0.750
1.102 0.000
**-**-** Safety Line
3/8 B No Ar (CaAa) 260' - 0' 0.000 -0.15 1 1 0.375 0.375 0.000
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
11 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Description Face or
Leg
Allow Shield
Component Type
Placement
ft
Face Offset
in
Lateral Offset
(Frac FW)
# # Per Row
Clear Spacing
in
Width or Diameter
in
Perimeter
in
Weight
klf (E)
**-**-** **-**-**
Feed Line/Linear Appur tenances - Entered As Area
Description Face or
Leg
Allow Shield
Component Type
Placement
ft
Total Number
CAAA
ft2/ft
Weight
klf **-**-**
Feed Line/Linear Ap purtenances Section Areas Tower Section
Tower Elevation
ft
Face AR
ft2
AF
ft2
CAAA
In Face ft2
CAAA
Out Face ft2
Weight
K T1 260'-240' A
B C
0.000 0.000 0.000
0.000 0.000 0.000
55.943 0.750 2.204
0.000 0.000 0.000
0.378 0.004 0.006
T2 240'-220' A B C
0.000 0.000 0.000
0.000 0.000 0.000
65.816 0.750 2.204
0.000 0.000 0.000
0.445 0.004 0.006
T3 220'-200' A B C
0.000 0.000 0.000
0.000 0.000 0.000
65.816 0.750 2.204
0.000 0.000 0.000
0.445 0.004 0.006
T4 200'-180' A B C
0.000 0.000 0.000
0.000 0.000 0.000
65.816 0.750 2.204
0.000 0.000 0.000
0.445 0.004 0.006
T5 180'-160' A B C
0.000 0.000 0.000
0.000 0.000 0.000
65.816 0.750 2.204
0.000 0.000 0.000
0.445 0.004 0.006
T6 160'-140' A B C
0.000 0.000 0.000
0.000 0.000 0.000
65.816 0.750 2.204
0.000 0.000 0.000
0.445 0.004 0.006
T7 140'-120' A B C
0.000 0.000 0.000
0.000 0.000 0.000
65.816 0.750 3.196
0.000 0.000 0.000
0.445 0.004 0.009
T8 120'-100' A B C
0.000 0.000 0.000
0.000 0.000 0.000
65.816 0.750 4.408
0.000 0.000 0.000
0.445 0.004 0.012
T9 100'-80' A B C
0.000 0.000 0.000
0.000 0.000 0.000
65.816 0.750 4.408
0.000 0.000 0.000
0.445 0.004 0.012
T10 80'-60' A B C
0.000 0.000 0.000
0.000 0.000 0.000
65.816 0.750 4.408
0.000 0.000 0.000
0.445 0.004 0.012
T11 60'-40' A B C
0.000 0.000 0.000
0.000 0.000 0.000
65.816 0.750 4.408
0.000 0.000 0.000
0.445 0.004 0.012
T12 40'-20' A B C
0.000 0.000 0.000
0.000 0.000 0.000
65.816 0.750 4.408
0.000 0.000 0.000
0.445 0.004 0.012
T13 20'-5'9'' A B
0.000 0.000
0.000 0.000
46.894 0.534
0.000 0.000
0.317 0.003
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
12 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Tower Section
Tower Elevation
ft
Face AR
ft2
AF
ft2
CAAA
In Face ft2
CAAA
Out Face ft2
Weight
K C 0.000 0.000 3.141 0.000 0.009
T14 5'9''-0' A B C
0.000 0.000 0.000
0.000 0.000 0.000
18.922 0.216 1.267
0.000 0.000 0.000
0.128 0.001 0.003
Feed Line Center of Pressure
Section Elevation
ft
CPX
in
CPZ
in
CPX
Ice in
CPZ
Ice in
T1 260'-240' -1.414 -2.163 -1.489 -2.206 T2 240'-220' -1.521 -2.292 -1.599 -2.337 T3 220'-200' -1.501 -2.261 -1.578 -2.306 T4 200'-180' -1.506 -2.269 -1.584 -2.314 T5 180'-160' -1.506 -2.269 -1.584 -2.314 T6 160'-140' -1.486 -2.239 -1.563 -2.283 T7 140'-120' -1.421 -2.201 -1.498 -2.245 T8 120'-100' -1.321 -2.120 -1.396 -2.164 T9 100'-80' -1.374 -2.206 -1.453 -2.251 T10 80'-60' -1.374 -2.206 -1.453 -2.251 T11 60'-40' -1.356 -2.176 -1.433 -2.221 T12 40'-20' -1.374 -2.206 -1.453 -2.251 T13 20'-5'9'' -1.354 -2.174 -1.432 -2.219 T14 5'9''-0' -1.614 -1.492 -1.692 -1.537
Shielding Factor Ka
Tower Section
Feed Line Record No.
Description Feed Line Segment Elev.
Ka No Ice
Ka Ice
T1 1 ATCB-B01(5/16") 240.00 - 257.00 0.6000 0.6000T1 2 LDF6-50A(1-1/4") 240.00 - 257.00 0.6000 0.6000T1 3 LDF7-50A(1-5/8") 240.00 - 257.00 0.6000 0.6000T1 4 LDF7-50A(1-5/8") 240.00 - 257.00 0.6000 0.6000T1 5 FB-L98B-002-XXX( 3/8") 240.00 - 257.00 0.6000 0.6000T1 6 WR-VG86ST-BRD(3/4") 240.00 - 257.00 0.6000 0.6000T1 7 WR-VG86ST-BRD(3/4") 240.00 - 257.00 0.6000 0.6000T1 8 T-Brackets (Af) 240.00 - 257.00 0.6000 0.6000T1 10 AVA5-50( 7/8") 240.00 - 260.00 0.6000 0.6000T1 13 Safety Line 3/8 240.00 - 260.00 0.6000 0.6000T2 1 ATCB-B01(5/16") 220.00 - 240.00 0.6000 0.6000T2 2 LDF6-50A(1-1/4") 220.00 - 240.00 0.6000 0.6000T2 3 LDF7-50A(1-5/8") 220.00 - 240.00 0.6000 0.6000T2 4 LDF7-50A(1-5/8") 220.00 - 240.00 0.6000 0.6000T2 5 FB-L98B-002-XXX( 3/8") 220.00 - 240.00 0.6000 0.6000T2 6 WR-VG86ST-BRD(3/4") 220.00 - 240.00 0.6000 0.6000T2 7 WR-VG86ST-BRD(3/4") 220.00 - 240.00 0.6000 0.6000T2 8 T-Brackets (Af) 220.00 - 240.00 0.6000 0.6000T2 10 AVA5-50( 7/8") 220.00 - 240.00 0.6000 0.6000T2 13 Safety Line 3/8 220.00 - 240.00 0.6000 0.6000T3 1 ATCB-B01(5/16") 200.00 - 220.00 0.6000 0.6000T3 2 LDF6-50A(1-1/4") 200.00 - 220.00 0.6000 0.6000T3 3 LDF7-50A(1-5/8") 200.00 - 220.00 0.6000 0.6000T3 4 LDF7-50A(1-5/8") 200.00 - 220.00 0.6000 0.6000T3 5 FB-L98B-002-XXX( 3/8") 200.00 - 220.00 0.6000 0.6000T3 6 WR-VG86ST-BRD(3/4") 200.00 - 220.00 0.6000 0.6000
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
13 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Tower Section
Feed Line Record No.
Description Feed Line Segment Elev.
Ka No Ice
Ka Ice
T3 7 WR-VG86ST-BRD(3/4") 200.00 - 220.00 0.6000 0.6000T3 8 T-Brackets (Af) 200.00 - 220.00 0.6000 0.6000T3 10 AVA5-50( 7/8") 200.00 - 220.00 0.6000 0.6000T3 13 Safety Line 3/8 200.00 - 220.00 0.6000 0.6000T4 1 ATCB-B01(5/16") 180.00 - 200.00 0.6000 0.6000T4 2 LDF6-50A(1-1/4") 180.00 - 200.00 0.6000 0.6000T4 3 LDF7-50A(1-5/8") 180.00 - 200.00 0.6000 0.6000T4 4 LDF7-50A(1-5/8") 180.00 - 200.00 0.6000 0.6000T4 5 FB-L98B-002-XXX( 3/8") 180.00 - 200.00 0.6000 0.6000T4 6 WR-VG86ST-BRD(3/4") 180.00 - 200.00 0.6000 0.6000T4 7 WR-VG86ST-BRD(3/4") 180.00 - 200.00 0.6000 0.6000T4 8 T-Brackets (Af) 180.00 - 200.00 0.6000 0.6000T4 10 AVA5-50( 7/8") 180.00 - 200.00 0.6000 0.6000T4 13 Safety Line 3/8 180.00 - 200.00 0.6000 0.6000T5 1 ATCB-B01(5/16") 160.00 - 180.00 0.6000 0.6000T5 2 LDF6-50A(1-1/4") 160.00 - 180.00 0.6000 0.6000T5 3 LDF7-50A(1-5/8") 160.00 - 180.00 0.6000 0.6000T5 4 LDF7-50A(1-5/8") 160.00 - 180.00 0.6000 0.6000T5 5 FB-L98B-002-XXX( 3/8") 160.00 - 180.00 0.6000 0.6000T5 6 WR-VG86ST-BRD(3/4") 160.00 - 180.00 0.6000 0.6000T5 7 WR-VG86ST-BRD(3/4") 160.00 - 180.00 0.6000 0.6000T5 8 T-Brackets (Af) 160.00 - 180.00 0.6000 0.6000T5 10 AVA5-50( 7/8") 160.00 - 180.00 0.6000 0.6000T5 13 Safety Line 3/8 160.00 - 180.00 0.6000 0.6000T6 1 ATCB-B01(5/16") 140.00 - 160.00 0.6000 0.6000T6 2 LDF6-50A(1-1/4") 140.00 - 160.00 0.6000 0.6000T6 3 LDF7-50A(1-5/8") 140.00 - 160.00 0.6000 0.6000T6 4 LDF7-50A(1-5/8") 140.00 - 160.00 0.6000 0.6000T6 5 FB-L98B-002-XXX( 3/8") 140.00 - 160.00 0.6000 0.6000T6 6 WR-VG86ST-BRD(3/4") 140.00 - 160.00 0.6000 0.6000T6 7 WR-VG86ST-BRD(3/4") 140.00 - 160.00 0.6000 0.6000T6 8 T-Brackets (Af) 140.00 - 160.00 0.6000 0.6000T6 10 AVA5-50( 7/8") 140.00 - 160.00 0.6000 0.6000T6 13 Safety Line 3/8 140.00 - 160.00 0.6000 0.6000T7 1 ATCB-B01(5/16") 120.00 - 140.00 0.6000 0.6000T7 2 LDF6-50A(1-1/4") 120.00 - 140.00 0.6000 0.6000T7 3 LDF7-50A(1-5/8") 120.00 - 140.00 0.6000 0.6000T7 4 LDF7-50A(1-5/8") 120.00 - 140.00 0.6000 0.6000T7 5 FB-L98B-002-XXX( 3/8") 120.00 - 140.00 0.6000 0.6000T7 6 WR-VG86ST-BRD(3/4") 120.00 - 140.00 0.6000 0.6000T7 7 WR-VG86ST-BRD(3/4") 120.00 - 140.00 0.6000 0.6000T7 8 T-Brackets (Af) 120.00 - 140.00 0.6000 0.6000T7 10 AVA5-50( 7/8") 129.00 - 140.00 0.6000 0.6000T7 11 AVA5-50( 7/8") 120.00 - 129.00 0.6000 0.6000T7 13 Safety Line 3/8 120.00 - 140.00 0.6000 0.6000T8 1 ATCB-B01(5/16") 100.00 - 120.00 0.6000 0.6000T8 2 LDF6-50A(1-1/4") 100.00 - 120.00 0.6000 0.6000T8 3 LDF7-50A(1-5/8") 100.00 - 120.00 0.6000 0.6000T8 4 LDF7-50A(1-5/8") 100.00 - 120.00 0.6000 0.6000T8 5 FB-L98B-002-XXX( 3/8") 100.00 - 120.00 0.6000 0.6000T8 6 WR-VG86ST-BRD(3/4") 100.00 - 120.00 0.6000 0.6000T8 7 WR-VG86ST-BRD(3/4") 100.00 - 120.00 0.6000 0.6000T8 8 T-Brackets (Af) 100.00 - 120.00 0.6000 0.6000T8 11 AVA5-50( 7/8") 100.00 - 120.00 0.6000 0.6000T8 13 Safety Line 3/8 100.00 - 120.00 0.6000 0.6000T9 1 ATCB-B01(5/16") 80.00 - 100.00 0.6000 0.6000T9 2 LDF6-50A(1-1/4") 80.00 - 100.00 0.6000 0.6000T9 3 LDF7-50A(1-5/8") 80.00 - 100.00 0.6000 0.6000T9 4 LDF7-50A(1-5/8") 80.00 - 100.00 0.6000 0.6000T9 5 FB-L98B-002-XXX( 3/8") 80.00 - 100.00 0.6000 0.6000T9 6 WR-VG86ST-BRD(3/4") 80.00 - 100.00 0.6000 0.6000T9 7 WR-VG86ST-BRD(3/4") 80.00 - 100.00 0.6000 0.6000
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
14 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Tower Section
Feed Line Record No.
Description Feed Line Segment Elev.
Ka No Ice
Ka Ice
T9 8 T-Brackets (Af) 80.00 - 100.00 0.6000 0.6000T9 11 AVA5-50( 7/8") 80.00 - 100.00 0.6000 0.6000T9 13 Safety Line 3/8 80.00 - 100.00 0.6000 0.6000
T10 1 ATCB-B01(5/16") 60.00 - 80.00 0.6000 0.6000T10 2 LDF6-50A(1-1/4") 60.00 - 80.00 0.6000 0.6000T10 3 LDF7-50A(1-5/8") 60.00 - 80.00 0.6000 0.6000T10 4 LDF7-50A(1-5/8") 60.00 - 80.00 0.6000 0.6000T10 5 FB-L98B-002-XXX( 3/8") 60.00 - 80.00 0.6000 0.6000T10 6 WR-VG86ST-BRD(3/4") 60.00 - 80.00 0.6000 0.6000T10 7 WR-VG86ST-BRD(3/4") 60.00 - 80.00 0.6000 0.6000T10 8 T-Brackets (Af) 60.00 - 80.00 0.6000 0.6000T10 11 AVA5-50( 7/8") 60.00 - 80.00 0.6000 0.6000T10 13 Safety Line 3/8 60.00 - 80.00 0.6000 0.6000T11 1 ATCB-B01(5/16") 40.00 - 60.00 0.6000 0.6000T11 2 LDF6-50A(1-1/4") 40.00 - 60.00 0.6000 0.6000T11 3 LDF7-50A(1-5/8") 40.00 - 60.00 0.6000 0.6000T11 4 LDF7-50A(1-5/8") 40.00 - 60.00 0.6000 0.6000T11 5 FB-L98B-002-XXX( 3/8") 40.00 - 60.00 0.6000 0.6000T11 6 WR-VG86ST-BRD(3/4") 40.00 - 60.00 0.6000 0.6000T11 7 WR-VG86ST-BRD(3/4") 40.00 - 60.00 0.6000 0.6000T11 8 T-Brackets (Af) 40.00 - 60.00 0.6000 0.6000T11 11 AVA5-50( 7/8") 40.00 - 60.00 0.6000 0.6000T11 13 Safety Line 3/8 40.00 - 60.00 0.6000 0.6000T12 1 ATCB-B01(5/16") 20.00 - 40.00 0.6000 0.6000T12 2 LDF6-50A(1-1/4") 20.00 - 40.00 0.6000 0.6000T12 3 LDF7-50A(1-5/8") 20.00 - 40.00 0.6000 0.6000T12 4 LDF7-50A(1-5/8") 20.00 - 40.00 0.6000 0.6000T12 5 FB-L98B-002-XXX( 3/8") 20.00 - 40.00 0.6000 0.6000T12 6 WR-VG86ST-BRD(3/4") 20.00 - 40.00 0.6000 0.6000T12 7 WR-VG86ST-BRD(3/4") 20.00 - 40.00 0.6000 0.6000T12 8 T-Brackets (Af) 20.00 - 40.00 0.6000 0.6000T12 11 AVA5-50( 7/8") 20.00 - 40.00 0.6000 0.6000T12 13 Safety Line 3/8 20.00 - 40.00 0.6000 0.6000T13 1 ATCB-B01(5/16") 5.75 - 20.00 0.6000 0.6000T13 2 LDF6-50A(1-1/4") 5.75 - 20.00 0.6000 0.6000T13 3 LDF7-50A(1-5/8") 5.75 - 20.00 0.6000 0.6000T13 4 LDF7-50A(1-5/8") 5.75 - 20.00 0.6000 0.6000T13 5 FB-L98B-002-XXX( 3/8") 5.75 - 20.00 0.6000 0.6000T13 6 WR-VG86ST-BRD(3/4") 5.75 - 20.00 0.6000 0.6000T13 7 WR-VG86ST-BRD(3/4") 5.75 - 20.00 0.6000 0.6000T13 8 T-Brackets (Af) 5.75 - 20.00 0.6000 0.6000T13 11 AVA5-50( 7/8") 5.75 - 20.00 0.6000 0.6000T13 13 Safety Line 3/8 5.75 - 20.00 0.6000 0.6000T14 1 ATCB-B01(5/16") 0.00 - 5.75 0.5729 0.5729T14 2 LDF6-50A(1-1/4") 0.00 - 5.75 0.5729 0.5729T14 3 LDF7-50A(1-5/8") 0.00 - 5.75 0.5729 0.5729T14 4 LDF7-50A(1-5/8") 0.00 - 5.75 0.5729 0.5729T14 5 FB-L98B-002-XXX( 3/8") 0.00 - 5.75 0.5729 0.5729T14 6 WR-VG86ST-BRD(3/4") 0.00 - 5.75 0.5729 0.5729T14 7 WR-VG86ST-BRD(3/4") 0.00 - 5.75 0.5729 0.5729T14 8 T-Brackets (Af) 0.00 - 5.75 0.5729 0.5729T14 11 AVA5-50( 7/8") 0.00 - 5.75 0.5729 0.5729T14 13 Safety Line 3/8 0.00 - 5.75 0.5729 0.5729
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
15 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Discrete Tower Loads
Description Face or
Leg
Offset Type
Offsets: Horz
Lateral Vert
ft ft ft
Azimuth Adjustment
°
Placement
ft
CAAA Front
ft2
CAAA Side
ft2
Weight
K
Lightning Rod 3/4'' x 6' (E)
A None 0.000 263' No Ice 0.450 0.450 0.030
Flash Beacon (E)
C None 0.000 260' No Ice 3.000 3.000 0.100
Side Lighting (E)
A From Leg 0.500 0' 0'
0.000 129' No Ice 0.098 0.098 0.005
Side Lighting (E)
A From Leg 0.500 0' 0'
0.000 129' No Ice 0.098 0.098 0.005
Side Lighting (E)
A From Leg 0.500 0' 0'
0.000 129' No Ice 0.098 0.098 0.005
**-**-** (2) DBXCP-4545A-R2M w/
Mount Pipe (E)
A From Leg 4.000 0' 4'
0.000 257' No Ice 7.029 4.216 0.049
7251.01 w/ Mount Pipe (E)
B From Leg 4.000 0' 4'
0.000 257' No Ice 4.563 4.952 0.044
7251.01 w/ Mount Pipe (E)
C From Leg 4.000 0' 4'
0.000 257' No Ice 4.563 4.952 0.044
(2) E15Z01P13 (E)
A From Leg 4.000 0' 4'
0.000 257' No Ice 0.780 0.596 0.022
(2) RRUS-11 (E)
A From Leg 4.000 0' 4'
0.000 257' No Ice 2.784 1.187 0.048
(2) RRUS-11 (E)
B From Leg 4.000 0' 4'
0.000 257' No Ice 2.784 1.187 0.048
(2) RRUS-11 (E)
C From Leg 4.000 0' 4'
0.000 257' No Ice 2.784 1.187 0.048
DC6-48-60-18-8F (E)
A From Leg 4.000 0' 4'
0.000 257' No Ice 0.917 0.917 0.019
DC6-48-60-18-8F (E)
B From Leg 4.000 0' 4'
0.000 257' No Ice 0.917 0.917 0.019
(2) RRUS A2 MODULE (E)
A From Leg 4.000 0' 4'
0.000 257' No Ice 1.600 0.380 0.021
RRUS A2 MODULE (E)
B From Leg 4.000 0' 4'
0.000 257' No Ice 1.600 0.380 0.021
RRUS A2 MODULE (E)
C From Leg 4.000 0' 4'
0.000 257' No Ice 1.600 0.380 0.021
CBC78-DF-2X (E)
B From Leg 4.000 0' 4'
0.000 257' No Ice 0.388 0.375 0.014
CBC78-DF-2X C From Leg 4.000 0.000 257' No Ice 0.388 0.375 0.014
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
16 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Description Face or
Leg
Offset Type
Offsets: Horz
Lateral Vert
ft ft ft
Azimuth Adjustment
°
Placement
ft
CAAA Front
ft2
CAAA Side
ft2
Weight
K
(E) 0' 4'
(2) BSA-M65R-BUU-H6 w/ Mount Pipe
(P)
A From Leg 4.000 0' 4'
0.000 257' No Ice 17.354 8.463 0.124
(2) SBNHH-1D85B w/ Mount Pipe
(P)
B From Leg 4.000 0' 4'
0.000 257' No Ice 8.438 7.104 0.068
(2) SBNHH-1D85B w/ Mount Pipe
(P)
C From Leg 4.000 0' 4'
0.000 257' No Ice 8.438 7.104 0.068
(2) RRUS 32 (P)
A From Leg 4.000 0' 4'
0.000 257' No Ice 2.857 1.777 0.055
RRUS 32 (P)
A From Leg 4.000 0' 4'
0.000 257' No Ice 2.857 1.777 0.055
RRUS 32 (P)
A From Leg 4.000 0' 4'
0.000 257' No Ice 2.857 1.777 0.055
(2) RRUS 12 (P)
A From Leg 4.000 0' 4'
0.000 257' No Ice 3.145 1.285 0.058
RRUS 12 (P)
A From Leg 4.000 0' 4'
0.000 257' No Ice 3.145 1.285 0.058
RRUS 12 (P)
A From Leg 4.000 0' 4'
0.000 257' No Ice 3.145 1.285 0.058
(2) RRUS-11 (P)
A From Leg 4.000 0' 4'
0.000 257' No Ice 2.784 1.187 0.048
(2) LGP 17503 (P)
B From Leg 4.000 0' 4'
0.000 257' No Ice 0.817 0.233 0.014
(2) LGP 17503 (P)
C From Leg 4.000 0' 4'
0.000 257' No Ice 0.817 0.233 0.014
DC6-48-60-18-8F (P)
C From Leg 4.000 0' 4'
0.000 257' No Ice 0.917 0.917 0.019
6' x 2'' Mount Pipe (E)
B From Leg 4.000 0' 0'
0.000 257' No Ice 1.425 1.425 0.022
6' x 2'' Mount Pipe (E)
C From Leg 4.000 0' 0'
0.000 257' No Ice 1.425 1.425 0.022
Sector Mount [SM 602-3] (E)
C None 0.000 257' No Ice 33.110 33.110 1.541
**-**-**
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
17 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Load Combinations Comb.
No. Description
1 Dead Only 2 1.2 Dead+1.6 Wind 0 deg - No Ice+1.0 Guy 3 1.2 Dead+1.6 Wind 30 deg - No Ice+1.0 Guy 4 1.2 Dead+1.6 Wind 60 deg - No Ice+1.0 Guy 5 1.2 Dead+1.6 Wind 90 deg - No Ice+1.0 Guy 6 1.2 Dead+1.6 Wind 120 deg - No Ice+1.0 Guy 7 1.2 Dead+1.6 Wind 150 deg - No Ice+1.0 Guy 8 1.2 Dead+1.6 Wind 180 deg - No Ice+1.0 Guy 9 1.2 Dead+1.6 Wind 210 deg - No Ice+1.0 Guy 10 1.2 Dead+1.6 Wind 240 deg - No Ice+1.0 Guy 11 1.2 Dead+1.6 Wind 270 deg - No Ice+1.0 Guy 12 1.2 Dead+1.6 Wind 300 deg - No Ice+1.0 Guy 13 1.2 Dead+1.6 Wind 330 deg - No Ice+1.0 Guy 14 Dead+Wind 0 deg - Service+Guy 15 Dead+Wind 30 deg - Service+Guy 16 Dead+Wind 60 deg - Service+Guy 17 Dead+Wind 90 deg - Service+Guy 18 Dead+Wind 120 deg - Service+Guy 19 Dead+Wind 150 deg - Service+Guy 20 Dead+Wind 180 deg - Service+Guy 21 Dead+Wind 210 deg - Service+Guy 22 Dead+Wind 240 deg - Service+Guy 23 Dead+Wind 270 deg - Service+Guy 24 Dead+Wind 300 deg - Service+Guy 25 Dead+Wind 330 deg - Service+Guy
Maximum Tower Deflections - Service Wind
Section No.
Elevation
ft
Horz. Deflection
in
Gov. Load
Comb.
Tilt °
Twist °
T1 260 - 240 3.144 25 0.217 0.516 T2 240 - 220 2.419 20 0.174 0.469 T3 220 - 200 1.880 20 0.131 0.405 T4 200 - 180 1.473 20 0.085 0.339 T5 180 - 160 1.172 20 0.066 0.283 T6 160 - 140 0.917 20 0.050 0.223 T7 140 - 120 0.746 20 0.035 0.161 T8 120 - 100 0.612 24 0.029 0.094 T9 100 - 80 0.521 24 0.014 0.052 T10 80 - 60 0.479 24 0.017 0.085 T11 60 - 40 0.387 24 0.024 0.125 T12 40 - 20 0.288 24 0.025 0.162 T13 20 - 5.75 0.169 24 0.036 0.197 T14 5.75 - 0 0.050 24 0.041 0.209
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
18 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Critical Deflections and Radius of Curvature - Service Wind
Elevation
ft
Appurtenance Gov. Load
Comb.
Deflection
in
Tilt °
Twist °
Radius of Curvature
ft 263' Lightning Rod 3/4'' x 6' 25 3.144 0.217 0.516 73369 260' Flash Beacon 25 3.144 0.217 0.516 73369 257' (2) DBXCP-4545A-R2M w/ Mount
Pipe 25 3.019 0.210 0.509 73369
248'7-1/2'' Guy 20 2.693 0.192 0.491 32250 208'7-1/2'' Guy 20 1.633 0.103 0.366 27316 156'10-1/2'' Guy 20 0.885 0.048 0.214 42636
129' Side Lighting 24 0.668 0.032 0.123 167150 105'10-1/2'' Guy 24 0.541 0.018 0.060 62945 51'4-1/2'' Guy 24 0.344 0.024 0.140 720783
Maximum Tower Deflections - Design Wind
Section No.
Elevation
ft
Horz. Deflection
in
Gov. Load
Comb.
Tilt °
Twist °
T1 260 - 240 47.076 2 2.469 2.712 T2 240 - 220 37.031 2 2.247 2.446 T3 220 - 200 28.166 2 1.955 2.114 T4 200 - 180 20.768 2 1.576 1.776 T5 180 - 160 14.827 2 1.286 1.503 T6 160 - 140 10.188 10 0.985 1.208 T7 140 - 120 7.342 11 0.691 0.901 T8 120 - 100 5.430 4 0.476 0.574 T9 100 - 80 4.477 4 0.240 0.371 T10 80 - 60 3.885 4 0.188 0.496 T11 60 - 40 3.038 4 0.211 0.609 T12 40 - 20 2.191 4 0.206 0.695 T13 20 - 5.75 1.245 8 0.268 0.757 T14 5.75 - 0 0.368 8 0.298 0.757
Critical Deflections and Radius of Curvature - Design Wind
Elevation
ft
Appurtenance Gov. Load
Comb.
Deflection
in
Tilt °
Twist °
Radius of Curvature
ft 263' Lightning Rod 3/4'' x 6' 2 47.076 2.469 2.712 13684 260' Flash Beacon 2 47.076 2.469 2.712 13684 257' (2) DBXCP-4545A-R2M w/ Mount
Pipe 2 45.535 2.437 2.675 13684
248'7-1/2'' Guy 2 41.273 2.347 2.567 6014 208'7-1/2'' Guy 2 23.771 1.737 1.915 3129 156'10-1/2'' Guy 10 9.620 0.936 1.161 3221
129' Side Lighting 11 6.199 0.570 0.719 5008 105'10-1/2'' Guy 4 4.707 0.301 0.402 4312 51'4-1/2'' Guy 4 2.667 0.207 0.645 41907
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
19 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Bolt Design Data
Section No.
Elevation
ft
Component Type
Bolt Grade
Bolt Size
in
NumberOf
Bolts
MaximumLoad per
Bolt K
AllowableLoad
K
Ratio Load
Allowable
Allowable Ratio
Criteria
T1 260 Leg A325N 0.750 4 4.195 29.821 0.141
1 Bolt Tension
Top Guy [email protected]
5
A325X 0.625 2 3.386 15.186 0.223
1 Bolt Shear
T2 240 Leg A325N 0.750 4 5.023 29.821 0.168
1 Bolt Tension
T3 220 Leg A325N 0.750 4 5.541 29.821 0.186
1 Bolt Tension
T4 200 Leg A325N 0.750 4 4.984 29.821 0.167
1 Bolt Tension
T5 180 Leg A325N 0.750 4 5.841 29.821 0.196
1 Bolt Tension
T6 160 Leg A325N 0.750 4 5.056 29.821 0.170
1 Bolt Tension
Top Guy [email protected]
5
A325X 0.625 2 2.039 15.186 0.134
1 Bolt Shear
T7 140 Leg A325N 0.750 4 5.038 29.821 0.169
1 Bolt Tension
T8 120 Leg A325N 0.750 4 4.896 29.821 0.164
1 Bolt Tension
T9 100 Leg A325N 0.750 4 3.394 29.821 0.114
1 Bolt Tension
T10 80 Leg A325N 0.750 4 3.246 29.821 0.109
1 Bolt Tension
T11 60 Leg A325N 0.750 4 3.509 29.821 0.118
1 Bolt Tension
T12 40 Leg A325N 0.750 4 3.871 29.821 0.130
1 Bolt Tension
Guy Design Data Section
No. Elevation
ft
Size
Initial Tension
K
Breaking Load
K
Actual Tu
K
Allowable Tn K
Required S.F.
Actual S.F.
T1 248'7-1/2'' (A)
(801) 3/4 EHS 6.996 58.300 32.664 34.980 1.000
1.071
248'7-1/2'' (B) (800)
3/4 EHS 6.996 58.300 32.744 34.980 1.000 1.068
248'7-1/2'' (C) (796)
3/4 EHS 6.996 58.300 32.624 34.980 1.000 1.072
T3 208'7-1/2'' (A) (807)
9/16 EHS 4.200 35.000 16.389 21.000 1.000 1.281
208'7-1/2'' (B) (806)
9/16 EHS 4.200 35.000 16.476 21.000 1.000 1.275
208'7-1/2'' (C) (802)
9/16 EHS 4.200 35.000 16.421 21.000 1.000 1.279
T6 156'10-1/2'' (A) (813)
5/8 EHS 3.392 42.400 13.209 25.440 1.000 1.926
156'10-1/2'' (B) (812)
5/8 EHS 3.392 42.400 13.312 25.440 1.000 1.911
156'10-1/2'' (C) (808)
5/8 EHS 3.392 42.400 13.280 25.440 1.000 1.916
T8 105'10-1/2'' (A) (826)
9/16 EHS 2.800 35.000 8.386 21.000 1.000 2.504
105'10-1/2'' (A) 9/16 EHS 2.800 35.000 8.660 21.000 1.000 2.425
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
20 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Section No.
Elevation
ft
Size
Initial Tension
K
Breaking Load
K
Actual Tu
K
Allowable Tn K
Required S.F.
Actual S.F.
(827)
105'10-1/2'' (B) (820)
9/16 EHS 2.800 35.000 8.299 21.000 1.000 2.530
105'10-1/2'' (B) (821)
9/16 EHS 2.800 35.000 8.960 21.000 1.000 2.344
105'10-1/2'' (C) (814)
9/16 EHS 2.800 35.000 9.145 21.000 1.000 2.296
105'10-1/2'' (C) (815)
9/16 EHS 2.800 35.000 8.095 21.000 1.000 2.594
T11 51'4-1/2'' (A) (837)
11/16 EHS 4.900 49.000 10.493 29.400 1.000 2.802
51'4-1/2'' (B) (836)
11/16 EHS 4.900 49.000 10.527 29.400 1.000 2.793
51'4-1/2'' (C) (832)
11/16 EHS 4.900 49.000 10.511 29.400 1.000 2.797
Compression Checks
Leg Design Data (Compression) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T1 260 - 240 1 3/4 20' 2'9'' 75.4
K=1.00 2.405 -50.228 71.402 0.703 1
T2 240 - 220 1 3/4 20' 2'9'' 75.4 K=1.00
2.405 -57.519 71.402 0.806 1
T3 220 - 200 1 3/4 20' 2'9'' 75.4 K=1.00
2.405 -71.472 71.402 1.001 1
4.8.1 (1.00 CR) - 141/3 T4 200 - 180 1 3/4 20' 2'9'' 75.4
K=1.00 2.405 -63.356 71.402 0.887 1
T5 180 - 160 1 3/4 20' 2'9'' 75.4 K=1.00
2.405 -66.606 71.402 0.933 1
T6 160 - 140 1 3/4 20' 2'9'' 75.4 K=1.00
2.405 -69.676 71.402 0.976 1
T7 140 - 120 1 3/4 20' 2'9'' 75.4 K=1.00
2.405 -57.891 71.402 0.811 1
T8 120 - 100 1 3/4 20' 2'9'' 75.4 K=1.00
2.405 -67.627 71.402 0.947 1
T9 100 - 80 1 3/4 20' 2'9'' 75.4 K=1.00
2.405 -56.329 71.402 0.789 1
T10 80 - 60 1 3/4 20' 2'9'' 75.4 K=1.00
2.405 -39.782 71.402 0.557 1
T11 60 - 40 1 3/4 20' 2'9'' 75.4 K=1.00
2.405 -43.122 71.402 0.604 1
T12 40 - 20 1 3/4 20' 2'9'' 75.4 K=1.00
2.405 -46.551 71.402 0.652 1
T13 20 - 5.75 2 14'3'' 2'9'' 66.0 3.142 -46.207 102.811 0.449 1
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
21 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Section No.
Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn K=1.00
T14 5.75 - 0 2 6'1-1/8'' 1'6-9/32''
36.6 K=1.00
3.142 -45.240 128.203 0.353 1
1 P u / Pn controls
Diagonal Design Data (Compression) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T1 260 - 240 3/4 4'5-13/3
2'' 2'1-19/3
2'' 122.9
K=0.90 0.442 -6.090 6.467 0.942 1
T2 240 - 220 3/4 4'5-13/32''
2'1-19/32''
122.9 K=0.90
0.442 -3.216 6.467 0.497 1
T3 220 - 200 3/4 4'5-13/32''
2'1-19/32''
122.9 K=0.90
0.442 -3.720 6.467 0.575 1
T4 200 - 180 7/8 4'5-13/32''
2'1-19/32''
107.1 K=0.91
0.601 -3.729 10.657 0.350 1
T5 180 - 160 7/8 4'5-13/32''
2'1-19/32''
107.1 K=0.91
0.601 -4.285 10.657 0.402 1
T6 160 - 140 7/8 4'5-13/32''
2'1-19/32''
107.1 K=0.91
0.601 -4.979 10.657 0.467 1
T7 140 - 120 7/8 4'5-13/32''
2'1-19/32''
107.1 K=0.91
0.601 -4.037 10.657 0.379 1
T8 120 - 100 7/8 4'5-13/32''
2'1-19/32''
107.1 K=0.91
0.601 -4.486 10.657 0.421 1
T9 100 - 80 3/4'' w/ 1'' SR with Crosby 4'5-13/32''
4'3-3/16''
135.1 K=0.50
0.442 -4.262 5.465 0.780 1
T10 80 - 60 3/4 4'5-13/32''
4'3-3/16''
191.1 K=0.70
0.442 -1.916 2.733 0.701 1
T11 60 - 40 3/4 4'5-13/32''
4'3-3/16''
191.1 K=0.70
0.442 -2.740 2.733 1.003 1
4.8.1 (1.00 CR) - 672 T12 40 - 20 3/4 4'5-13/3
2'' 4'3-3/16'
' 191.1
K=0.70 0.442 -1.969 2.733 0.720 1
T13 20 - 5.75 3/4 4'5-13/32''
4'2-7/8'' 189.9 K=0.70
0.442 -1.804 2.767 0.652 1
1 P u / Pn controls
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
22 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Horizontal Design Data (Compression) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T1 260 - 240 3/4 3'6'' 3'4-1/4'' 150.3
K=0.70 0.442 -1.471 4.420 0.333 1
T2 240 - 220 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.110 4.420 0.025 1
T3 220 - 200 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.834 4.420 0.189 1
T8 120 - 100 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -1.930 4.420 0.437 1
T9 100 - 80 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.976 4.420 0.221 1
T10 80 - 60 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.689 4.420 0.156 1
T11 60 - 40 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.747 4.420 0.169 1
T12 40 - 20 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.806 4.420 0.182 1
T13 20 - 5.75 3/4 3'6'' 3'4'' 149.3 K=0.70
0.442 -0.800 4.475 0.179 1
1 P u / Pn controls
Top Girt Design Data (Compression) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T1 260 - 240 3/4 3'6'' 3'4-1/4'' 150.3
K=0.70 0.442 -0.134 4.420 0.030 1
T4 200 - 180 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.254 4.420 0.058 1
T9 100 - 80 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -1.236 4.420 0.280 1
T10 80 - 60 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.374 4.420 0.085 1
T11 60 - 40 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.569 4.420 0.129 1
T12 40 - 20 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.649 4.420 0.147 1
T13 20 - 5.75 3/4 3'6'' 3'4'' 149.3 K=0.70
0.442 -0.162 4.475 0.036 1
1 P u / Pn controls
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
23 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Bottom Girt Design Data (Compression) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T2 240 - 220 3/4 3'6'' 3'4-1/4'' 150.3
K=0.70 0.442 -0.599 4.420 0.136 1
T5 180 - 160 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.339 4.420 0.077 1
T9 100 - 80 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.778 4.420 0.176 1
T10 80 - 60 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.725 4.420 0.164 1
T11 60 - 40 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.786 4.420 0.178 1
T12 40 - 20 3/4 3'6'' 3'4-1/4'' 150.3 K=0.70
0.442 -0.101 4.420 0.023 1
1 P u / Pn controls
Mid Girt Design Data (Compression) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T14 5.75 - 0 C4x5.4 1'9'' 1'7'' 42.3
K=1.00 1.590 -0.057 46.882 0.001 1
1 P u / Pn controls
Torque-Arm Bottom Design Data Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T8 120 - 100 (818) L3 1/2x5x5/16 6'9-15/1
6'' 6'9'' 112.9
K=1.07 2.560 -12.577 41.922 0.300 1
T8 120 - 100 (819) L3 1/2x5x5/16 6'9-15/16''
6'9'' 112.9 K=1.07
2.560 -12.215 41.922 0.291 1
T8 120 - 100 (824) L3 1/2x5x5/16 6'9-15/16''
6'9'' 112.9 K=1.07
2.560 -12.239 41.922 0.292 1
T8 120 - 100 (825) L3 1/2x5x5/16 6'9-15/16''
6'9'' 112.9 K=1.07
2.560 -11.989 41.922 0.286 1
T8 120 - 100 (830) L3 1/2x5x5/16 6'9-15/16''
6'9'' 112.9 K=1.07
2.560 -12.405 41.922 0.296 1
T8 120 - 100 (831) L3 1/2x5x5/16 6'9-15/16''
6'9'' 112.9 K=1.07
2.560 -12.061 41.922 0.288 1
1 P u / Pn controls
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
24 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Tension Checks
Leg Design Data (Tension) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T1 260 - 240 1 3/4 20' 2'9'' 75.4 2.405 36.877 108.238 0.341 1
T2 240 - 220 1 3/4 20' 4-1/2'' 10.3 2.405 16.502 108.238 0.152 1
T3 220 - 200 1 3/4 20' 2'9'' 75.4 2.405 24.969 108.238 0.231 1
4.8.1 (1.00 CR) - 141/4 T4 200 - 180 1 3/4 20' 4-1/2'' 10.3 2.405 4.575 108.238 0.042 1
T5 180 - 160 1 3/4 20' 4-1/2'' 10.3 2.405 2.605 108.238 0.024 1
T6 160 - 140 1 3/4 20' 2'9'' 75.4 2.405 4.693 108.238 0.043 1
1 P u / Pn controls
Diagonal Design Data (Tension) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T1 260 - 240 3/4 4'5-13/3
2'' 2'1-19/3
2'' 136.5 0.442 6.575 14.314 0.459 1
T2 240 - 220 3/4 4'5-13/32''
2'1-19/32''
136.5 0.442 1.772 14.314 0.124 1
T3 220 - 200 3/4 4'5-13/32''
2'1-19/32''
136.5 0.442 2.560 14.314 0.179 1
T4 200 - 180 7/8 4'5-13/32''
2'1-19/32''
117.0 0.601 1.891 19.483 0.097 1
T5 180 - 160 7/8 4'5-13/32''
2'1-19/32''
117.0 0.601 1.976 19.483 0.101 1
T6 160 - 140 7/8 4'5-13/32''
2'1-19/32''
117.0 0.601 2.628 19.483 0.135 1
T7 140 - 120 7/8 4'5-13/32''
2'1-19/32''
117.0 0.601 1.320 19.483 0.068 1
T8 120 - 100 7/8 4'5-13/32''
2'1-19/32''
117.0 0.601 2.272 19.483 0.117 1
T9 100 - 80 3/4'' w/ 1'' SR with Crosby 4'5-13/32''
4'3-3/16''
273.0 0.442 3.605 14.314 0.252 1
T10 80 - 60 3/4 4'5-13/32''
4'3-3/16''
273.0 0.442 1.410 14.314 0.098 1
T11 60 - 40 3/4 4'5-13/32''
4'3-3/16''
273.0 0.442 2.565 14.314 0.179 1
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
25 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Section No.
Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T12 40 - 20 3/4 4'5-13/3
2'' 4'3-3/16'
' 273.0 0.442 1.642 14.314 0.115 1
T13 20 - 5.75 3/4 4'5-13/32''
4'2-7/8'' 271.3 0.442 1.100 14.314 0.077 1
1 P u / Pn controls
Horizontal Design Data (Tension) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T1 260 - 240 3/4 3'6'' 3'4-1/4'' 214.7 0.442 2.659 14.314 0.186 1
T2 240 - 220 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.504 14.314 0.105 1
T3 220 - 200 3/4 3'6'' 3'4-1/4'' 214.7 0.442 2.144 14.314 0.150 1
T4 200 - 180 3/4 3'6'' 3'4-1/4'' 214.7 0.442 2.266 14.314 0.158 1
T5 180 - 160 3/4 3'6'' 3'4-1/4'' 214.7 0.442 2.335 14.314 0.163 1
T6 160 - 140 3/4 3'6'' 3'4-1/4'' 214.7 0.442 2.701 14.314 0.189 1
T7 140 - 120 3/4 3'6'' 3'4-1/4'' 214.7 0.442 2.523 14.314 0.176 1
T8 120 - 100 3/4 3'6'' 3'4-1/4'' 214.7 0.442 7.397 14.314 0.517 1
T9 100 - 80 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.976 14.314 0.068 1
T10 80 - 60 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.689 14.314 0.048 1
T11 60 - 40 3/4 3'6'' 3'4-1/4'' 214.7 0.442 2.220 14.314 0.155 1
T12 40 - 20 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.806 14.314 0.056 1
T13 20 - 5.75 3/4 3'6'' 3'4'' 213.3 0.442 0.800 14.314 0.056 1
1 P u / Pn controls
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
26 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Top Girt Design Data (Tension) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T1 260 - 240 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.155 14.314 0.011 1
T2 240 - 220 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.957 14.314 0.067 1
T3 220 - 200 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.591 14.314 0.041 1
T4 200 - 180 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.668 14.314 0.117 1
T5 180 - 160 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.242 14.314 0.087 1
T6 160 - 140 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.322 14.314 0.092 1
T7 140 - 120 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.550 14.314 0.108 1
T8 120 - 100 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.331 14.314 0.093 1
T9 100 - 80 3/4 3'6'' 3'4-1/4'' 214.7 0.442 2.022 14.314 0.141 1
T10 80 - 60 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.849 14.314 0.059 1
T11 60 - 40 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.997 14.314 0.070 1
T12 40 - 20 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.804 14.314 0.056 1
T13 20 - 5.75 3/4 3'6'' 3'4'' 213.3 0.442 0.315 14.314 0.022 1
T14 5.75 - 0 C4x5.4 3'6'' 3'4'' 89.1 1.590 7.351 51.516 0.143 1
1 P u / Pn controls
Bottom Girt Design Data (Tension) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T1 260 - 240 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.786 14.314 0.055 1
T2 240 - 220 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.225 14.314 0.086 1
T3 220 - 200 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.881 14.314 0.062 1
T4 200 - 180 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.289 14.314 0.090 1
T5 180 - 160 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.789 14.314 0.125 1
T6 160 - 140 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.293 14.314 0.090 1
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
27 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Section No.
Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn
T7 140 - 120 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.545 14.314 0.108 1
T8 120 - 100 3/4 3'6'' 3'4-1/4'' 214.7 0.442 1.987 14.314 0.139 1
T9 100 - 80 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.598 14.314 0.042 1
T10 80 - 60 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.679 14.314 0.047 1
T11 60 - 40 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.900 14.314 0.063 1
T12 40 - 20 3/4 3'6'' 3'4-1/4'' 214.7 0.442 0.224 14.314 0.016 1
T13 20 - 5.75 3/4 3'6'' 3'4'' 213.3 0.442 1.454 14.314 0.102 1
1 P u / Pn controls
Mid Girt Design Data (Tension) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T14 5.75 - 0 C4x5.4 2'7-1/2'' 2'5-1/2'' 65.7 1.590 0.210 51.516 0.004 1
1 P u / Pn controls
Top Guy Pull-Off Design Data (Tension) Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T1 260 - 240 3x3/8 3'6'' 3'4-1/4'' 371.8 1.125 6.771 36.450 0.186 1 T3 220 - 200 3x1/4 3'6'' 3'4-1/4'' 557.7 0.750 3.219 24.300 0.132 1
L/R > 500 (T) - 805 T6 160 - 140 3x3/8 3'6'' 3'4-1/4'' 371.8 1.125 4.078 36.450 0.112 1 T11 60 - 40 3x1/4 3'6'' 3'4-1/4'' 557.7 0.750 3.770 24.300 0.155 1
L/R > 500 (T) - 834
1 P u / Pn controls
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
28 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Top Guy Pull-Off Bending Design Data Section
No. Elevation
ft
Size
Mux
kip-ft
Mnx
kip-ft
Ratio Mux
Mnx
Muy
kip-ft
Mny
kip-ft
Ratio Muy
Mny T1 260 - 240 3x3/8 0.000 2.278 0.000 0.000 0.285 0.000 T3 220 - 200 3x1/4 0.000 1.519 0.000 0.000 0.127 0.000 T6 160 - 140 3x3/8 0.000 2.278 0.000 0.000 0.285 0.000 T11 60 - 40 3x1/4 0.000 1.519 0.000 0.000 0.127 0.000
Top Guy Pull-Off Interaction Design Data Section
No. Elevation
ft
Size
Ratio Pu
Pn
Ratio Mux
Mnx
Ratio Muy
Mny
Comb. Stress Ratio
Allow. Stress Ratio
Criteria
T1 260 - 240 3x3/8 0.186 0.000 0.000 0.186 1 1.000 4.8.1
T3 220 - 200 3x1/4 0.132 0.000 0.000 0.132 1 1.000 4.8.1
T6 160 - 140 3x3/8 0.112 0.000 0.000 0.112 1 1.000 4.8.1
T11 60 - 40 3x1/4 0.155 0.000 0.000 0.155 1 1.000 4.8.1
1 P u / Pn controls
Torque-Arm Top Design Data Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T8 120 - 100 (816) L5x5x5/16 6'3'' 6'2-1/8'' 47.2 3.030 11.707 98.172 0.119 1
T8 120 - 100 (817) L5x5x5/16 6'3'' 6'2-1/8'' 47.2 3.030 12.702 98.172 0.129 1
T8 120 - 100 (822) L5x5x5/16 6'3'' 6'2-1/8'' 47.2 3.030 10.368 98.172 0.106 1
T8 120 - 100 (823) L5x5x5/16 6'3'' 6'2-1/8'' 47.2 3.030 10.726 98.172 0.109 1
T8 120 - 100 (828) L5x5x5/16 6'3'' 6'2-1/8'' 47.2 3.030 11.105 98.172 0.113 1
T8 120 - 100 (829) L5x5x5/16 6'3'' 6'2-1/8'' 47.2 3.030 12.401 98.172 0.126 1
1 P u / Pn controls
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
29 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Torque-Arm Bottom Design Data Section
No. Elevation
ft
Size
L
ft
Lu
ft
Kl/r
A
in2
Pu
K
Pn
K
Ratio Pu
Pn T8 120 - 100 (818) L3 1/2x5x5/16 6'9-15/1
6'' 6'9'' 78.6 2.560 1.530 82.944 0.018 1
T8 120 - 100 (819) L3 1/2x5x5/16 6'9-15/16''
6'9'' 78.6 2.560 1.505 82.944 0.018 1
T8 120 - 100 (824) L3 1/2x5x5/16 6'9-15/16''
6'9'' 78.6 2.560 1.602 82.944 0.019 1
T8 120 - 100 (825) L3 1/2x5x5/16 6'9-15/16''
6'9'' 78.6 2.560 1.607 82.944 0.019 1
T8 120 - 100 (830) L3 1/2x5x5/16 6'9-15/16''
6'9'' 78.6 2.560 1.559 82.944 0.019 1
T8 120 - 100 (831) L3 1/2x5x5/16 6'9-15/16''
6'9'' 78.6 2.560 1.384 82.944 0.017 1
1 P u / Pn controls
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
30 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Section Capacity Table
Section No.
Elevation ft
Component Type
Size CriticalElement
P K
øPallow
K %
Capacity Pass Fail
T1 260 - 240 Leg 1 3/4 3 -50.228 71.402 70.3 Pass T2 240 - 220 Leg 1 3/4 72 -57.519 71.402 80.6 Pass T3 220 - 200 Leg 1 3/4 141 -71.472 71.402 100.1 Fail T4 200 - 180 Leg 1 3/4 210 -63.356 71.402 88.7 Pass T5 180 - 160 Leg 1 3/4 279 -66.606 71.402 93.3 Pass T6 160 - 140 Leg 1 3/4 348 -69.676 71.402 97.6 Pass T7 140 - 120 Leg 1 3/4 417 -57.891 71.402 81.1 Pass T8 120 - 100 Leg 1 3/4 486 -67.627 71.402 94.7 Pass T9 100 - 80 Leg 1 3/4 555 -56.329 71.402 78.9 Pass T10 80 - 60 Leg 1 3/4 601 -39.782 71.402 55.7 Pass T11 60 - 40 Leg 1 3/4 651 -43.122 71.402 60.4 Pass T12 40 - 20 Leg 1 3/4 697 -46.551 71.402 65.2 Pass T13 20 - 5.75 Leg 2 745 -46.207 102.811 44.9 Pass T14 5.75 - 0 Leg 2 781 -45.240 128.203 35.3 Pass T1 260 - 240 Diagonal 3/4 50 -6.090 6.467 94.2 Pass T2 240 - 220 Diagonal 3/4 84 -3.216 6.467 49.7 Pass T3 220 - 200 Diagonal 3/4 149 -3.720 6.467 57.5 Pass T4 200 - 180 Diagonal 7/8 272 -3.729 10.657 35.0 Pass T5 180 - 160 Diagonal 7/8 291 -4.285 10.657 40.2 Pass T6 160 - 140 Diagonal 7/8 414 -4.979 10.657 46.7 Pass T7 140 - 120 Diagonal 7/8 429 -4.037 10.657 37.9 Pass T8 120 - 100 Diagonal 7/8 498 -4.486 10.657 42.1 Pass T9 100 - 80 Diagonal 3/4'' w/ 1'' SR with Crosby 600 -4.262 5.465 78.0 Pass T10 80 - 60 Diagonal 3/4 610 -1.916 2.733 70.1 Pass T11 60 - 40 Diagonal 3/4 672 -2.740 2.733 100.3 Fail T12 40 - 20 Diagonal 3/4 744 -1.969 2.733 72.0 Pass T13 20 - 5.75 Diagonal 3/4 756 -1.804 2.767 65.2 Pass T1 260 - 240 Horizontal 3/4 43 -1.471 4.420 33.3 Pass T2 240 - 220 Horizontal 3/4 87 1.504 14.314 10.5 Pass T3 220 - 200 Horizontal 3/4 181 -0.834 4.420 18.9 Pass T4 200 - 180 Horizontal 3/4 225 2.266 14.314 15.8 Pass T5 180 - 160 Horizontal 3/4 294 2.335 14.314 16.3 Pass T6 160 - 140 Horizontal 3/4 399 2.701 14.314 18.9 Pass T7 140 - 120 Horizontal 3/4 432 2.523 14.314 17.6 Pass T8 120 - 100 Horizontal 3/4 510 7.397 14.314 51.7 Pass T9 100 - 80 Horizontal 3/4 567 -0.976 4.420 22.1 Pass T10 80 - 60 Horizontal 3/4 613 -0.689 4.420 15.6 Pass T11 60 - 40 Horizontal 3/4 662 -0.747 4.420 16.9 Pass T12 40 - 20 Horizontal 3/4 709 -0.806 4.420 18.2 Pass T13 20 - 5.75 Horizontal 3/4 757 -0.800 4.475 17.9 Pass T1 260 - 240 Top Girt 3/4 4 -0.134 4.420 3.0 Pass T2 240 - 220 Top Girt 3/4 73 0.957 14.314 6.7 Pass T3 220 - 200 Top Girt 3/4 142 0.591 14.314 4.1 Pass T4 200 - 180 Top Girt 3/4 213 1.668 14.314 11.7 Pass T5 180 - 160 Top Girt 3/4 282 1.242 14.314 8.7 Pass T6 160 - 140 Top Girt 3/4 350 1.322 14.314 9.2 Pass T7 140 - 120 Top Girt 3/4 419 1.550 14.314 10.8 Pass T8 120 - 100 Top Girt 3/4 488 1.331 14.314 9.3 Pass T9 100 - 80 Top Girt 3/4 558 -1.236 4.420 28.0 Pass T10 80 - 60 Top Girt 3/4 606 -0.374 4.420 8.5 Pass T11 60 - 40 Top Girt 3/4 652 -0.569 4.420 12.9 Pass T12 40 - 20 Top Girt 3/4 701 -0.649 4.420 14.7 Pass T13 20 - 5.75 Top Girt 3/4 749 -0.162 4.475 3.6 Pass T14 5.75 - 0 Top Girt C4x5.4 784 7.351 51.516 14.3 Pass T1 260 - 240 Bottom Girt 3/4 9 0.786 14.314 5.5 Pass T2 240 - 220 Bottom Girt 3/4 76 -0.599 4.420 13.6 Pass T3 220 - 200 Bottom Girt 3/4 147 0.881 14.314 6.2 Pass T4 200 - 180 Bottom Girt 3/4 216 1.289 14.314 9.0 Pass
Reviewed for CodeCompliance
PRBD20170308782
ttnnxxTToowweerr Job
106729.001.01 - Lake Trafford, FL (BU# 844061)
Page
31 of 31
B+T Group 1717 S Boulder Ave, Suite 300
Project
Date
16:28:54 06/22/16 Tulsa, OK 74119
Phone: (918) 587-4630 FAX: (918) 295-0265
Client Crown Castle
Designed by
ushrestha
Section No.
Elevation ft
Component Type
Size CriticalElement
P K
øPallow
K %
Capacity Pass Fail
T5 180 - 160 Bottom Girt 3/4 285 1.789 14.314 12.5 Pass T6 160 - 140 Bottom Girt 3/4 354 1.293 14.314 9.0 Pass T7 140 - 120 Bottom Girt 3/4 423 1.545 14.314 10.8 Pass T8 120 - 100 Bottom Girt 3/4 490 1.987 14.314 13.9 Pass T9 100 - 80 Bottom Girt 3/4 561 -0.778 4.420 17.6 Pass T10 80 - 60 Bottom Girt 3/4 608 -0.725 4.420 16.4 Pass T11 60 - 40 Bottom Girt 3/4 657 -0.786 4.420 17.8 Pass T12 40 - 20 Bottom Girt 3/4 705 -0.101 4.420 2.3 Pass T13 20 - 5.75 Bottom Girt 3/4 753 1.454 14.314 10.2 Pass T14 5.75 - 0 Mid Girt C4x5.4 793 0.210 51.516 0.4 Pass T1 260 - 240 Guy [email protected] 3/4 801 32.664 34.980 93.4 Pass T3 220 - 200 Guy [email protected] 9/16 807 16.389 21.000 78.0 Pass T6 160 - 140 Guy [email protected] 5/8 813 13.209 25.440 51.9 Pass T8 120 - 100 Guy [email protected] 9/16 827 8.660 21.000 41.2 Pass T11 60 - 40 Guy [email protected] 11/16 837 10.493 29.400 35.7 Pass T1 260 - 240 Guy [email protected] 3/4 800 32.744 34.980 93.6 Pass T3 220 - 200 Guy [email protected] 9/16 806 16.476 21.000 78.5 Pass T6 160 - 140 Guy [email protected] 5/8 812 13.312 25.440 52.3 Pass T8 120 - 100 Guy [email protected] 9/16 821 8.960 21.000 42.7 Pass T11 60 - 40 Guy [email protected] 11/16 836 10.527 29.400 35.8 Pass T1 260 - 240 Guy [email protected] 3/4 796 32.624 34.980 93.3 Pass T3 220 - 200 Guy [email protected] 9/16 802 16.421 21.000 78.2 Pass T6 160 - 140 Guy [email protected] 5/8 808 13.280 25.440 52.2 Pass T8 120 - 100 Guy [email protected] 9/16 814 9.145 21.000 43.5 Pass T11 60 - 40 Guy [email protected] 11/16 832 10.511 29.400 35.8 Pass T1 260 - 240 Top Guy
[email protected] 3x3/8 797 6.771 36.450 18.6
22.3 (b) Pass
T3 220 - 200 Top Guy [email protected]
3x1/4 805 3.219 24.300 13.2 Pass
T6 160 - 140 Top Guy [email protected]
3x3/8 811 4.078 36.450 11.2 13.4 (b)
Pass
T11 60 - 40 Top Guy [email protected] 3x1/4 834 3.770 24.300 15.5 Pass T8 120 - 100 Torque Arm [email protected] L5x5x5/16 817 12.702 98.172 12.9 Pass T8 120 - 100 Torque Arm
[email protected] L3 1/2x5x5/16 818 -12.577 41.922 30.0 Pass
Summary Leg (T3) 100.1 Fail Diagonal
(T11) 100.3 Fail
Horizontal (T8)
51.7 Pass
Top Girt (T9)
28.0 Pass
Bottom Girt (T11)
17.8 Pass
Mid Girt (T14)
0.4 Pass
Guy A (T1) 93.4 Pass Guy B (T1) 93.6 Pass Guy C (T1) 93.3 Pass Top Guy
Pull-Off (T1)
22.3 Pass
Torque Arm Top (T8)
12.9 Pass
Torque Arm Bottom (T8)
30.0 Pass
Bolt Checks 22.3 Pass RATING = 100.3 Fail
Reviewed for CodeCompliance
PRBD20170308782
APPENDIX B
BASE LEVEL DRAWING
Reviewed for CodeCompliance
PRBD20170308782
BU: 844061
Reviewed for CodeCompliance
PRBD20170308782
APPENDIX C
ADDITIONAL CALCULATIONS
Reviewed for CodeCompliance
PRBD20170308782
CCI Foundation Tool Suite ‐ Guyed Drilled Pier Base
CCIFTS 1.2.108.14286 ‐ Phase 1‐2 Date: 6/22/2016
BU: 844061
Site Name: Lake Trafford, FLApp Number: 328847 Rev.5Work Order: 1248031
Guyed Drilled Pier Base
Input
Criteria
TIA Revision: G
ACI 318 Revision: 2008
Seismic Category: B
Forces
Dead Load Axial 0 kips
Dead Load Wind 121 kips
Shear 2 kips
Moment 0 k‐ftSwelling Force 0 kips
Foundation Dimensions
Pier Diameter: 4 ft
Ext. above grade: 0 ft
Depth below grade: 20 ft
Material Properties 12 *Steel is unknownNumber of Rebar: 8 0.5% code minimum was assumed
Rebar Size: 8
Tie Size 3
Rebar tensile strength: 60 ksi
Concrete Strength: 3000 psi
Ultimate Concrete Strain 0.003 in/in
Clear Cover to Ties: 3 in
Soil Profile: Soil
Layer
Thickness
(ft)
From
(ft)
To
(ft)
Unit Weight
(pcf)
Cohesion
(psf)
Friction Angle
(deg)
Ultimate Uplift Skin Friction
(ksf)
Ultimate Comp. Skin Friction
(ksf)
Ultimate Bearing Capacity
(ksf)
SPT 'N' Counts
1 2 0 2 115 0 0 0 0 0
2 2 2 4 115 31 0.2 0.3 0
3 2 4 6 53 31 0.3 0.45 0
4 2 6 8 58 33 0.4 0.6 0
5 5 8 13 58 33 0.5 0.75 0
6 4 13 17 58 33 0.6 0.9 0
7 3 17 20 58 33 0.8 1.2 15
Analysis ResultsConcrete/Steel Check
Soil Lateral Capacity Mu (from soil analysis) 13.20 k‐ftDepth to Zero Shear: 9.82 ft φMn 995.32 k‐ftMax Moment, Mu: 13.20 k‐ft RATING: 1.3%
Soil Safety Factor: 84.82
Safety Factor Req'd: 1.33
RATING: 1.6% rho provided 0.52
rho required 0.33 OK
Soil Axial CapacitySkin Friction (k): 128.65 kips Rebar Spacing 9.5
End Bearing (k): 113.10 kips Spacing required 16.0 OK
Comp. Capacity (k), φCn: 241.75 kips
Comp. (k), Cu: 121.00 kips
RATING: 50.1% Dev. Length required 9.9
Dev. Length provided 43.8 OK
Overall Foundation Rating: 50.1%
(8) ‐ #8
#3 Tie Size
20'
20'
0'
4'
" C.C.
Page 1 of 1
Reviewed for CodeCompliance
PRBD20170308782
CCI Foundation Tool Suite ‐ Guyed Drilled Pier Anchor
CCIFTS 1.2.108.14286 ‐ Phase 1‐2 Date: 6/23/2016
BU: 844061
Site Name: Lake Trafford, FLApp Number: 328847 Rev.5Work Order: 1248031
Guyed Drilled Pier Anchor
Input
Criteria
TIA Revision: G
ACI 318 Revision: 2008
Seismic Category: B
Forces
Uplift 53 kips
Shear 69 kips
Moment 0 k‐ftSwelling Force 0 kips
Foundation Dimensions
Pier Diameter: 4 ft
Ext. above grade: 1 ft
Depth below grade: 20 ft
Material PropertiesNumber of Rebar: 8 *Steel is unknownRebar Size: 8 0.5% code minimum was assumed
Tie Size 3
Rebar tensile strength: 60 ksi
Concrete Strength: 3000 psi
Ultimate Concrete Strain 0.003 in/in
Clear Cover to Ties: 3 in
Soil Profile: Soil
Layer
Thickness
(ft)
From
(ft)
To
(ft)
Unit Weight
(pcf)
Cohesion
(psf)
Friction Angle
(deg)
Ultimate Uplift Skin Friction
(ksf)
Ultimate Comp. Skin Friction
(ksf)
Ultimate Bearing Capacity
(ksf)
SPT 'N' Counts
1 2 0 2 115 0 0 0 0 0
2 2 2 4 115 31 0.2 0.3 0
3 2 4 6 53 31 0.3 0.45 0
4 2 6 8 58 33 0.4 0.6 0
5 5 8 13 58 33 0.5 0.75 0
6 4 13 17 58 33 0.6 0.9 0
7 3 17 20 58 33 0.8 1.2 15
Analysis ResultsConcrete/Steel Check
Soil Lateral Capacity Mu (from soil analysis) 511.11 k‐ftDepth to Zero Shear: 9.5 ft φMn 490.55 k‐ftMax Moment, Mu: 511.1 k‐ft RATING: 104.2%
Soil Safety Factor: 2.3Safety Factor Req'd: 1.33
RATING: 57.6%
rho provided (%) 0.35
Soil Axial Capacity rho required (%) 0.33 OK
Concrete Weight: 24.3 kips
Skin Friction: 85.8 kips Rebar Spacing 14.8
Soil Cone: kips Spacing required 16.0 OK
Uplift Capacity (k), φTn: 110.1 kips
Uplift (k), Tu: 53.0 kips
RATING: 48.1% Dev. Length required 10.3
Dev. Length provided 43.8 OK
Overall Foundation Rating: 104.2%
(8) ‐ #8
#3 Tie Size
21'
20'
1'
4'
3" C.C.
Page 1 of 1
Reviewed for CodeCompliance
PRBD20170308782
APPENDIX D
TOWER MODIFICATION DRAWINGS
Reviewed for CodeCompliance
PRBD20170308782
Reviewed for CodeCompliance
PRBD20170308782
Reviewed for CodeCompliance
PRBD20170308782
Reviewed for CodeCompliance
PRBD20170308782
Reviewed for CodeCompliance
PRBD20170308782
Reviewed for CodeCompliance
PRBD20170308782
Reviewed for CodeCompliance
PRBD20170308782
Reviewed for CodeCompliance
PRBD20170308782
Reviewed for CodeCompliance
PRBD20170308782
Reviewed for CodeCompliance
PRBD20170308782
Reviewed for CodeCompliance
PRBD20170308782