Upload
sameer313
View
215
Download
1
Embed Size (px)
DESCRIPTION
ghick
Citation preview
SSystem TestPack # Location ItemNo Punch Point Description Category Discipline Company Raised by
NG2-01-04 B90-P-657 15 C PI PID Sydney
RMU-02-S B95-S-001 16 C QC SSA Ramanan
RMU-02-S B95-S-002 40 C PID SA Sydney
NG2-01-07 B90-P-648 44 C PI PID Sydney
LR-01-01 B94-P-002 51 C QC SSA Ramanan
B90-CBD-001 53 C PI PID K. Slater
RMU-02-PA B95-PA-002 77 C PID SA Sydney
NG2-01-05 B90-R-518 94 C PI PID Sydney
RMU-01-07 B95-R-003 162 5. AS PER SAES-L-110 CHART 1 WELDOLET C QC SSA A. Khadeer
B90-HPF-001 228 9. ITEM NO 11 LONG NECK FLANGE SHOULD NOT DIRECTLY WELD ON PIPE C PI SSA Raja Gopal
RMU-01-01 B95-P-001 249 C QC SSA A. Khadeer
RMU-01-05 B95-P-041 253 C QC SSA Ramanan
RMU-01-06 B95-P-044 261 C QC SSA Ramanan
RMU-01-05 B95-P-041 265 C QC SSA Ramanan
RMU-01-06 B95-P-044 272 C QC SSA Ramanan
RMU-01-05 B95-P-041 280 C QC SSA Ramanan
RMU-01-06 B95-P-044 290 C QC SSA Ramanan
B90-P-6913-2215-01 BD-757167-063-01A
3. SSA ENGG TO VERIFY AT SHOP JOINT # 009 LONG NECK FLANGE IS NOT ALLOWED TO WELD DIRECTLY ON PIPE AS PER STANDARD
B95-S-7460--2103-01,BD-757273-040-00F
13. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B95-S-7461-2121-01,BD-757291-015-01B (SHEET 2 OF 2)
6. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B90-P-8968-2217-02 BD-757169-114-01A
3. SSA ENGG TO VERIFY AT SHOP JOINT # 004 & 007 LONG NECK FLANGE IS NOT ALLOWED TO WELD DIRECTLY ON PIPE AS PER STANDARD
B94-P-0178-2119-01 ,BD-757289-012-02A
28. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
NG1-02-CBD
B90-CBD-9876-2103-01
BD-757117-001-02B7. AT WELD JOINT # 004 LONG WELD NECK FLANGE ARE NOT ALLOWED TO DIRECTLY WELDED ON PIPE AS PER STANDARD RECTIFY.
B95-PA-6744-2122-01,BD-757292-031-00B
4. AS PER SAES-L-110 CHART 1 ITS SAY'S THAT WELDOLET TO USED FIRST THEN LONG WELD NECK FLANGE
B90-R-7513-2219-06 BD-757171-125-02A
28. LONG NECK FLANGE USED AT TE-1096 CONNECTION REQUIRED WITH O'LET AS PER STANDARD
B95-R-3190-2101-01,BD-757271-018-02A
NG1-02-HPF
B90-HPF-9872-2103-01 BD-757117-045-04A-B
B95-P-1145-2119-01 BD-757289-017-01A
38.) AS PER SAES-L-110 LONG WELD NECK FLANGE SHALL NOT DIRECTLY WELD TO THE PIPE. WELDOLET TO BE USED THEN FLANGE
B95-P-2174-2107-01,BD-757277-008-01C (SHEET 1 OF 2)
3. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B95-P-2517-2105-02 ,BD-757275-020-01B
7. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B95-P-2186-2107-01,BD-757277-010-01B (SHEET 1 OF 2)
15. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B95-P-2517-2105-03,BD-757275-022-00F
18. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B95-P-2186-2107-03 ,BD-757277-012-01B
30. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B95-P-2517-2105-04 ,BD-757275-027-00C
36. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
RMU-01-05 B95-P-041 311 C QC SSA Ramanan
RMU-01-06 B95-P-046 338 C PID SA Sydney
RMU-01-05 B95-P-041 359 C QC SSA Ramanan
RMU-01-06 B95-P-046 365 C PID SA Sydney
RMU-01-05 B95-P-041 368 C QC SSA Ramanan
NG1-01-07 B90-P-064 381 C PID SA Jamil
RC-01-02 B90-R-003 400 C PID SA R. Harron
RC-01-02 B90-R-003 412 C PID SA R. Harron
RC-01-02 B90-R-003 413 C PID SA R. Harron
RMU-01-06 B95-P-046 429 C PID SA Sydney
RC-01-02 B90-R-003 440 C PID SA R. Harron
RC-01-02 B90-R-003 452 C PID SA R. Harron
RC-01-02 B90-R-003 460 C PID SA R. Harron
RC-01-02 B90-R-003 462 C PID SA R. Harron
RC-01-02 B90-R-003 471 72. ENGINEERING TO VERIFY LOW POINT DRAIN C PID SA R. Harron
RC-01-02 B90-R-003 472 C PID SA R. Harron
RC-01-02 B90-R-003 473 C PID SA R. Harron
NG1-01-07 B90-P-035 479 C PID SA A. Tagalog
B95-P-2218-2107-02,BD-757277-027-01C
61. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B95-P-2837-2107-01,BD-757277-048-02B (SHEET 1 OF 2)
34. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B95-P-2190-2101-01,BD-757271-010-01A
109. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B95-P-2847-2107-01 ,BD-757277-050-02C (SHEET 1 OF 2)
61. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B95-P-2192-2101-01,BD-757271-012-01D
118. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B90-P-1827-2117-03, BD-757131-101-02A
24. LONG NECK FLANGE USED AT TE-1007 CONNECTION REQUIRED WITH O'LET AS PER STANDARD
B90-R-3616-2123-01
,BD-757137-041-02B
1. ENGINEERING TO VERIFY AT SHOP JOINT # 009 LONG NECK FLANGE IS NOT ALLOWED TO WELD DIRECTLY ON PIPE AS PER STANDARD.
B90-R-3616-2123-02
BD-757137-042-02A
13. ENGINEERING TO VERIFY WEARPAD FOR SUPPORT # S24 BSG56 WEARPAD HAS BEEN INSTALLED FOR SUPPORT # S23 BSG56 BUT NOT INSTALLED ON S24 CLARIFY( PIPELINES ABOVE 14" HAVE WEAR PADS AT EACH SUPPORT FOR STRUCTURAL REINFORCEMENT AS PER STANDARD)
B90-R-3616-2123-02
BD-757137-042-02A14. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B95-P-2887-2102-01 ,BD-757272-012-02B
125. AS PER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B90-R-3618-2123-01
BD-757137-052-02A41. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B90-R-3618-2123-02
BD-757137-053-03A53. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B90-R-3716-2123-01
BD-757137-057-02B61. ENGINEERING TO VERIFY AT SHOP JOINT # 009 LONG NECK FLANGE IS NOT ALLOWED TO WELD DIRECTLY ON PIPE AS PER STANDARD.
B90-R-3716-2123-01
BD-757137-057-02B63. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B90-R-3716-2123-02
BD-757137-058-02A
B90-R-3716-2123-02
BD-757137-058-02A
73. ENGINEERING TO VERIFY WEARPAD FOR SUPPORT # S24 BSG56 WEARPAD HAS BEEN INSTALLED FOR SUPPORT # S23 BSG56 BUT NOT INSTALLED ON S24 CLARIFY( PIPELINES ABOVE 14" HAVE WEAR PADS AT EACH SUPPORT FOR STRUCTURAL REINFORCEMENT AS PER STANDARD)
B90-R-3716-2123-02
BD-757137-058-02A74. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B90-P-1801-2132-02,BD-757145-113-01A
63. LONG NECK FLANGE USED AT TE-1208 & TI-1206 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
NG1-01-03 B90-P-021 547 C QC SSA
NG1-01-05 B90-P-010 552 C PID SA Sydney
RC-01-02 B90-R-003 556 C PID SA R. Harron
RC-01-02 B90-R-003 557 C PID SA R. Harron
RC-01-02 B90-R-003 559 C PID SA R. Harron
RC-01-02 B90-R-003 565 C PID SA R. Harron
UW-01-02 B92-UW-002 566 C QC SSA
RC-01-02 B90-R-003 566 164. ENGINEERING TO VERIFY LOW POINT DRAIN C PID SA R. Harron
NG1-01-05 B90-P-010 568 C PID SA Sydney
RC-01-02 B90-R-003 572 C PID SA R. Harron
NG1-01-02 B90-P-006 574 C PID SA Sydney
NG1-01-07 B90-P-061 585 C QC SSA Raja Gopal
NG1-01-04 B90-P-070 587 C PI PID A. Tagalog
NG1-01-04 B90-P-070 614 C PI PID A. Tagalog
NG1-01-04 B90-P-070 623 C PI PID A. Tagalog
NG1-01-05 B90-P-010 626 C PID SA Sydney
NG1-01-07 B90-P-061 651 C QC SSA Raja Gopal
RC-01-02 B90-R-003 665 259. ENGINEERING TO VERIFY HIGH POINT VENT C PID SA R. Harron
B90-P-9204-2101-01,BD-757115-057-01A
1. SUPPORT S15 , 4 STOPS TO BE WELD EACH SIDE FOR DIRECTIONAL STOP AS PER SUPPORT DRAWING ( NOTE-2 )
Shakul Hameed
B90-P-0705-2117-01 ,BD-757131-042-01A
4. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-3820-2123-01
BD-757137-076-01A154. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B90-R-3820-2123-01
BD-757137-076-01A155. ENGINEERING TO VERIFY AT SHOP JOINT # 008 LONG NECK FLANGE IS NOT ALLOWED TO WELD DIRECTLY ON PIPE AS PER STANDARD.
B90-R-3820-2123-02
BD-757137-077-02A157. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B90-R-3820-2123-02
BD-757137-077-02A
163. ENGINEERING TO VERIFY WEARPAD FOR SUPPORTS( PIPELINES ABOVE 14" HAVE WEAR PADS AT EACH SUPPORT FOR STRUCTURAL REINFORCEMENT AS PER STANDARD)
UW-8895 to B92-G-0638 A/B/C
296.(B92-UW-8694-2104-01,BD-
757194-101-02A,
) for this package the welderwise 10% RT backlog is M.
Shameer
B90-R-3820-2123-02
BD-757137-077-02A
B90-P-0503-2119-10 ,BD-757133-054-01A
20. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-3820-2123-03
BD-757137-078-02A170. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B90-P-8804-2115-02 ,BD-757129-023-02A-B
26. ITEM NO 11 LONG NECK FLANGE SHOULD NOT DIRECTLY WELDED ON PIPE
B90-P-2032-2117-02 ,BD-757131-133-02A
18. LONG NECK FLANGE SHOUND NOT BE WELDED DIRECTLY ON PIPE AS PER STANDARD
B90-P-8704-2107-01 BD-757121-053-01A
40. LONG NECK FLANGE USED AT TE-1005 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-P-8704-2115-02 BD-757129-017-01A
67. LONG NECK FLANGE USED AT TE-1091 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-P-8809-2115-01 BD-757129-030-02A
76. LONG NECK FLANGE USED AT TI-1089 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-P-0705-2131-02 ,BD-757145-034-01A
78. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-P-2031-2117-02,BD-757131-131-02A
84. LONG NECK FLANGE SHOUND NOT BE WELDED DIRECTLY ON PIPE AS PER STANDARD
B90-R-3944-2123-01
BD-757137-105-02A
NG1-01-04 B90-P-070 669 C PI PID A. Tagalog
NG1-01-05 B90-P-011 710 C PI PID A. Tagalog
NG1-01-07 B90-P-061 712 C QC SSA Raja Gopal
NG1-01-05 B90-P-011 718 C PI PID A. Tagalog
RC-01-02 B90-R-003 726 C PID SA R. Harron
RC-01-02 B90-R-003 735 C PID SA R. Harron
RC-01-02 B90-R-003 737 C PID SA R. Harron
RC-01-02 B90-R-003 741 335. ENGINEERING TO VERIFY LOW POINT DRAIN C PID SA R. Harron
RC-01-02 B90-R-003 742 C PID SA R. Harron
RC-01-02 B90-R-003 743 C PID SA R. Harron
NG1-01-02 B90-P-005 755 C PI PID R. Harron
RC-01-02 B90-R-026 766 C PI SSA R. Harron
NG1-01-05 B90-P-011 791 C PI PID A. Tagalog
NG1-01-05 B90-P-037 819 C PI PID Sydney
NG1-01-02 B90-P-005 833 C PI PID R. Harron
NG1-01-02 B90-P-005 849 C PI PID R. Harron
NG1-01-05 B90-P-037 851 C PI PID Sydney
RW-01-02 B92-WW-012 883 29. WELDER BACKLOG TO BE CLEAR AS PER ATTACHED LIST C PID SA R. Harron
B90-P-8704-2115-01 BD-757129-016-01A
122. LONG NECK FLANGE USED AT TI-1118 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-P-0906-2131-03 BD-757145-061-02A
60. LONG NECK FLANGE USED AT TE-1151 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-P-2028-2117-02 ,BD-757131-125-02A
145. LONG NECK FLANGE SHOUND NOT BE WELDED DIRECTLY ON PIPE AS PER STANDARD
B90-P-0906-2131-02 BD-757145-060-01A
68. LONG NECK FLANGE USED AT TE-1151 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-R-3949-2123-02
BD-757137-110-02B320. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B90-R-3949-2123-03
BD-757137-111-02A329. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B90-R-3949-2123-09
BD-757137-117-02B331. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B90-R-3949-2123-04
BD-757137-112-02A
B90-R-3949-2123-04
BD-757137-112-02A
336. ENGINEERING TO VERIFY WEARPAD FOR SUPPORT # S17 BSG8, WEARPAD HAS BEEN INSTALLED FOR SUPPORT # S20 BSG8 BUT NOT INSTALLED ON S17 CLARIFY( PIPELINES ABOVE 14" HAVE WEAR PADS AT EACH SUPPORT FOR STRUCTURAL REINFORCEMENT AS PER STANDARD)
B90-R-3949-2123-04
BD-757137-112-02A337. ENGINEERING TO VERIFY FOR PIPE 30" AND ABOVE SADDLE TYPE SUPPORTS SHALL BE PROVIDED AS PER STANDARD
B90-P-8613-2107-01 BD-757121-038-04A
2. "AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE. "
B90-D-0116B to B90-K-0103B
40.AT SHOP WELD JT#007 LONG WELD NECK FLANGES IS NOT ALLOWED FOR BRANCH CONNECTION.
B90-P-0706-2131-02 BD-757145-097-01A
141. LONG NECK FLANGE USED AT TE-1147 & TI-1148 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-P-0603-2131-02 BD-757145-016-01A
10. LONG NECK FLANGE USED AT TE-1168 & TI-1167 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-P-8601-2107-01 BD-757121-026-04A
81. "AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE. "
B90-P-8602-2107-01 BD-757121-029-04A
97. "AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE. "
B90-P-0603-2131-05 BD-757145-019-01A
42. LONG NECK FLANGE USED AT TI-1138 & TE-1180 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B92-D-0640CtoB92-Q-0001
NG1-01-02 B90-P-005 885 C PI PID R. Harron
NG1-01-07 B90-P-017 896 C PID SA A. Tagalog
RC-01-04 B90-R-006 902 C PID SA K. Slater
NG1-01-05 B90-P-037 902 C PI PID Sydney
RC-01-04 B90-R-006 905 C PID SA K. Slater
NG1-01-07 B90-P-017 906 C PID SA A. Tagalog
RC-01-04 B90-R-006 908 C PID SA K. Slater
RC-01-04 B90-R-006 911 C PID SA K. Slater
RC-01-03 B90-R-004 913 C PID SA Jamil
RC-01-04 B90-R-006 914 C PID SA K. Slater
NG1-01-02 B90-P-005 917 C PI PID R. Harron
RC-01-04 B90-R-006 917 C PID SA K. Slater
RC-01-03 B90-R-004 920 C PID SA Jamil
RC-01-04 B90-R-006 920 C PID SA K. Slater
RC-01-04 B90-R-006 923 C PID SA K. Slater
RC-01-04 B90-R-006 926 C PID SA K. Slater
RC-01-04 B90-R-006 929 C PID SA K. Slater
NG1-01-07 B90-P-041 930 C PI SSA Raja Gopal
B90-P-8616-2107-01 BD-757121-042-04A
133. "AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE. "
B90-P-1215-2133-02,BD-757147-097-01A
26. LONG NECK FLANGE USED AT TE-1806 & TI-1810 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-R-4118-2127-03,BD-757141-085-00A
2. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-P-0604-2131-02 BD-757145-023-01A
94. LONG NECK FLANGE USED AT TE-1140 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-R-4118-2127-06,BD-757141-088-00A
5. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-P-1406-2133-02,BD-757147-115-01A
36. LONG NECK FLANGE USED AT TE-1906 & TI-1910 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-R-4118-2127-09,BD-757141-091-00A
8. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-12,BD-757141-094-00A
11. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-1931-2117-01,BD-757131-135-01A-B
3. ITEM NO 11 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD ON PIPE
B90-R-4118-2127-15 ,BD-757141-097-00A
14. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-P-8701-2107-01 BD-757121-048-04A
164. "AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE. "
B90-R-4118-2127-18 ,BD-757141-100-00A
17. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-1934-2117-01,BD-757131-143-01A-B
10. ITEM NO 11 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD ON PIPE
B90-R-4118-2127-21,BD-757141-103-00A
20. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-24,BD-757141-106-00A
23. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-27,BD-757141-109-00A
26. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-30,BD-757141-112-00A
29. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-P-1004-2117-01 BD-757131-064-01A-F SHT 2
5.ITEM NO 6, LONG NECK FLANGE SHOULD NOT BE DIRECTLY WELDED TO PIPE
RC-01-04 B90-R-006 932 C PID SA K. Slater
RC-01-04 B90-R-006 936 C PID SA K. Slater
RC-01-04 B90-R-006 939 C PID SA K. Slater
NG1-01-07 B90-P-041 939 14. F12 LONG NECK FLANGE SHOULD NOT DIRECTLY WELDED ON PIPE C PI SSA Raja Gopal
RC-01-04 B90-R-006 942 C PID SA K. Slater
RC-01-04 B90-R-006 946 C PID SA K. Slater
RC-01-04 B90-R-006 949 C PID SA K. Slater
RC-01-04 B90-R-006 952 C PID SA K. Slater
RC-01-04 B90-R-006 955 C PID SA K. Slater
RC-01-04 B90-R-006 957 C PID SA K. Slater
RC-01-04 B90-R-006 960 C PID SA K. Slater
NG1-01-02 B90-P-005 961 C PI PID R. Harron
RC-01-04 B90-R-006 964 C PID SA K. Slater
RC-01-04 B90-R-006 966 C PID SA K. Slater
RC-01-04 B90-R-006 969 C PID SA K. Slater
RC-01-04 B90-R-006 972 C PID SA K. Slater
RC-01-04 B90-R-006 975 C PID SA K. Slater
RC-01-04 B90-R-006 978 C PID SA K. Slater
B90-R-4118-2127-33,BD-757141-115-00A
32. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-39 ,BD-757141-121-00A
36. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-42 ,BD-757141-124-00A
39. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-P-1004-2131-02 BD-757145-064-01A-B
B90-R-4118-2127-45,BD-757141-127-00A
42. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-48,BD-757141-130-00A
46. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-51,BD-757141-133-00A
49. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-54, BD-757141-136-00A
52. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-57,BD-757141-139-00A
55. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-60,BD-757141-142-00A
57. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-63,BD-757141-145-00A
60. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-P-8715-2107-01 BD-757121-062-04A
208. "AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE. "
B90-R-4118-2127-66,BD-757141-148-00A
64. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-66,BD-757141-148-00A
66. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-72,BD-757141-154-00A
69. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-75,BD-757141-157-00A
72. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-78 ,BD-757141-160-00A
75. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-81,BD-757141-163-00A
78. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
RC-01-04 B90-R-006 982 C PID SA K. Slater
RC-01-04 B90-R-006 985 C PID SA K. Slater
RC-01-04 B90-R-006 988 C PID SA K. Slater
NG1-01-02 B90-P-005 990 C PI PID R. Harron
RC-01-04 B90-R-006 992 C PID SA K. Slater
RC-01-04 B90-R-006 995 C PID SA K. Slater
RC-01-01 B90-T-083 B90-LO-SKID-A to ATM 1000 C PID SA A. Tagalog
NG1-01-07 B90-P-041 1010 C PI SSA Raja Gopal
NG1-01-07 B90-P-043 1037 C PI PID Sydney
NG1-01-07 B90-P-043 1099 C PI PID Sydney
NG1-01-01 B90-R-012 1300 C PID SA Jamil
NG1-01-01 B90-R-012 1354 C PID SA Jamil
NG1-01-01 B90-P-120 1423 C PID SA Jamil
NG1-02-LO B90-LO-001 4520 C PI SSA
B95-CBD-002 5175 C PI SSA Jamil
NG1-02-LO B90-LO-001 5420 C PID SSA A. Tagalog
B90-R-4118-2127-84 ,BD-757141-166-00A
82. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-87,BD-757141-169-00A
85. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-90,BD-757141-172-00A
88. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-P-8722-2107-01 BD-757121-071-04A
237. "AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE. "
B90-R-4118-2127-93 ,BD-757141-175-00A
92. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
B90-R-4118-2127-96,BD-757141-178-00A
95. AS PER SAES-L-110 CLASS 300 LONG NECK FLANGE IS NOT ALLOWED TO DIRECTLY WELD WITH PIPE
6.FINAL P & ID AND ISO DRAWING TO BE ATTACHED. REVISION NO. TO BE UPDATED TOO
B90-P-1016-2131-02 BD-757145-079-02A-B
85. ITEM NO 11 LONG NECK FLANGE SHOULD NOT DIRECTLY WELDED ON PIPE
B90-P-0406-2117-02 BD-757131-027-02B
16. SSA ENGG TO VERIFY AT SHOP JOINT # 005 & 008 LONG NECK FLANGE IS NOT ALLOWED TO WELD DIRECTLY ON PIPE AS PER STANDARD
B90-P-0405-2117-03 BD-757131-023-01A
79. SSA ENGG TO VERIFY AT SHOP JOINT # 007 & 010 LONG NECK FLANGE IS NOT ALLOWED TO WELD DIRECTLY ON PIPE AS PER STANDARD
B90-R-8249-2111-02,BD-757125-132-02A
34. LONG NECK FLANGE USED AT TE-1029 & TI-1030 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-R-8241-2111-02 ,BD-757125-126-02A
88. LONG NECK FLANGE USED AT TE-1026 & TI-1027 CONNECTIONS REQUIRED WITH O'LET AS PER STANDARD
B90-FG-9835-2103-01, BD-757117-016-02A
59. LONG NECK FLANGE USED AT TE-1007 CONNECTION REQUIRED WITH O'LET AS PER STANDARD
B90-LO-3427-2130-01 BD-757144-026-00A
46.LONG NECK FLANGE USED AT TE-1096 CONNECTION REQUIRED WITH O'LET AS PER STANDARD
Shakul Hameed
RMU-02-CBD
B95-CBD-9882-2103-01 BD-757273-003-02C
27.AS FER SAES-L-110 CHART 1 ONLY WELDOLET TO BE USED INSTEAD LONG WELD NECK FLANGE FOR CONNECTION
B90-LO-3427-2130-01 BD-757144-026-00A
46.LONG NECK FLANGE USED AT TE-1096 CONNECTION REQUIRED WITH O'LET AS PER STANDARD
S.N0 PACKAGE NO STATUS
1 B90-R-027 RETURN2 B90-P-018 RETURN3 B90-N-006 RETURN4 B90-N-005 RETURN5 B90-CDS-094 RETURN6 B90-CDS-096 RETURN7 B90-HPF-012 RETURN8 B90-HPF-023 RETURN9 B90-R-028 RETURN10 B90-T-075 RETURN11 B90-P-016 RETURN12 B90-P-048 RETURN13 B90-P-121 RETURN14 B90-P-084 RETURN15 B90-P-076 RETURN16 B90-HO-004 RETURN17 B90-P-048 RETURN18 B90-CWS-001 RETURN