Cable Code Classification / Nomenclature 2010 Heavy Duty Cables: TROPODUR & TROPOTHEN-X Heavy Duty Cables : a) Letters used in Type Designations : A = Appearing as a first letter denotes Aluminium Conductor. Y = TROPODUR (PVC) Insulation or TROPODUR (PVC) Sheath depending on the position in which it appears. 2X = TROPOTHEN-X (Cross-linked Polyethylene) Insulation. W = Round Steel Wire Armouring. WW = Double Round Steel Wire Armouring. F = Formed Steel Wire (Strip) Armouring. FF = Double Formed Steel Wire (Strip) Armouring. C = Metallic Screening (Usually of Copper). CE = Metallic Screening (usually of Copper) over each individual core. Gb = Holding Helix Tape (of Steel) Wa = Aluminium Round Wire & Aluminium Formed Wire (Strip) Fa Armouring b) Type Designations : AYY Aluminium Conductor, TROPODUR Insulated, TROPODUR Outer Sheathed Heavy Duty Cables. AYWY Aluminium Conductor, TROPODUR Insulated, Galvanised Round Steel Wire Armoured and TROPODUR Outer Sheathed Heavy Duty Cables. AYFY Aluminium Conductor, TROPODUR Insulated, Galvanised Flat Steel Wire (Strip) Armoured and TROPODUR Outer Sheathed Heavy Duty Cable. AYCY Aluminium Conductor, TROPODUR Insulated, Metallic Screened and TROPODUR Outer Sheathed Heavy Duty Cable. A2XCY Aluminium Conductor, TROPOTHEN-X Insulated, Metallic Screened and TROPODUR Outer Sheathed Heavy Duty Cable. AYCEFY Aluminium Conductor, TROPODUR Insulated, individual core metallic screened, Flat steel Wire (strip) Armoured and TROPODUR Outer Sheathed Heavy duty Cable. A2XCEFY Aluminium Conductor, TROPOTHEN-X Insulated, individual cores metallic screened, Flat Steel Wire (Strip) Armoured and TROPODUR Outer Sheathed Heavy Duty Cable. NOTE : If the first letter A is dropped in the above designations (i.e. YY, YWY, YFY etc.) they will denote corresponding types with Copper Conductors. SUT | 1

Cable Nomenclature

Embed Size (px)

DESCRIPTION

to download this file fallow the linkn http://www.ziddu.com/downloadlink/8257927/CABLENOMENCLATURE.docx

Citation preview

Page 1: Cable Nomenclature

Cable Code Classification / Nomenclature 2010

Heavy Duty Cables: TROPODUR & TROPOTHEN-X Heavy Duty Cables :

a) Letters used in Type Designations :

A = Appearing as a first letter denotes Aluminium Conductor.Y = TROPODUR (PVC) Insulation or TROPODUR (PVC) Sheath depending on the position in which it appears.2X = TROPOTHEN-X (Cross-linked Polyethylene) Insulation.W = Round Steel Wire Armouring.WW = Double Round Steel Wire Armouring.F = Formed Steel Wire (Strip) Armouring.FF = Double Formed Steel Wire (Strip) Armouring.C = Metallic Screening (Usually of Copper).CE = Metallic Screening (usually of Copper) over each individual core.Gb = Holding Helix Tape (of Steel)Wa = Aluminium Round Wire & Aluminium Formed Wire (Strip) Fa Armouring 

b) Type Designations :

AYY Aluminium Conductor, TROPODUR Insulated, TROPODUR Outer Sheathed Heavy Duty Cables.AYWY Aluminium Conductor, TROPODUR Insulated, Galvanised Round Steel Wire Armoured and TROPODUR Outer Sheathed Heavy Duty Cables.AYFY Aluminium Conductor, TROPODUR Insulated, Galvanised Flat Steel Wire (Strip) Armoured and TROPODUR Outer Sheathed Heavy Duty Cable.AYCY Aluminium Conductor, TROPODUR Insulated, Metallic Screened and TROPODUR Outer Sheathed Heavy Duty Cable. A2XCY Aluminium Conductor, TROPOTHEN-X Insulated, Metallic Screened and TROPODUR Outer Sheathed Heavy Duty Cable. AYCEFY Aluminium Conductor, TROPODUR Insulated, individual core metallic screened, Flat steel Wire (strip) Armoured and TROPODUR Outer Sheathed Heavy duty Cable.A2XCEFY Aluminium Conductor, TROPOTHEN-X Insulated, individual cores metallic screened, Flat Steel Wire (Strip) Armoured and TROPODUR Outer Sheathed Heavy Duty Cable.

NOTE : If the first letter A is dropped in the above designations (i.e. YY, YWY, YFY etc.) they will denote corresponding types with Copper Conductors.

YWWGby…(Mining) Copper Conductor, TROPODUR Insulated, double round wire armoured and TROPODUR Outer Sheathed Heavy Duty Mining Cable.

YFFGby…(Mining) Copper Conductor, TROPODUR Insulated, double flat wire (strip) armoured and TROPODUR Outer Sheathed Heavy Duty Mining Cable.

| 1

Page 2: Cable Nomenclature

Cable Code Classification / Nomenclature 2010

Paper Cables :a) Letters used in Type Designations :

A = Appearing as a first letter denotes Aluminium Conductor.P = Paper InsulationL = Lead SheathLy = Lead Alloy SheathS = Lapped bedding or serving of compounded fibrous materials (when it comes below armouring in armoured cables, it is known as bedding).Y = Extruded PVC Bedding or Serving.T = Double steel tape armouring.Tg = Double steel tape armouring galvanised.W = Single round steel wire armouring.WW = Double round steel wire armouring.F = Single formed steel wire (strip) armouring.FF = Double formed steel wire (strip) armouring.

b) Type Designations:

APLS:- Aluminium Conductor, Paper Insulated, Lead Sheathed and Served Cable.APLyS :- Aluminium Conductor, Paper Insulated, Lead Alloy Sheathed and Served Cable.APLy Aluminium Conductor, Paper Insulated, Lead Sheathed and overall PVC Sheath protect ted Cable.APLyY Aluminium Conductor, Paper Insulated, Lead Alloy Sheathed and overall PVC Sheath protected Cable.APLSTS Aluminium Conductor, Paper Insulated, Lead Sheathed, double steel tape armoured and served Cable. APLySTS Aluminium Conductor, Paper Insulated, Lead Alloy Sheathed, double steel tape armoured and overall PVC Sheath protected cable.

NOTE :

1. If the first letter A is dropped in the above designations (i.e. PLS, PLSTS, PLSTY, etc) they will denote the corresponding types with Copper Conductors.

2. If the cable is armoured with round steel wire armouring or formed steel wire (strip) armouring replace T in above by W or F respectively e.g. APLSWS, APLSFS, etc.

3. If the cable is armoured with double round steel wire armouring or double formed steel wire (strip) armouring replace T by WW or FF respectively e.g. APLSWWS, APLSFFS, etc.

4. If the cable is armoured with galvanised double steel tape, replace T by Tg e.g. APLSTgS.5. In the case of H type cable with common Lead Sheath, add suffix (screened) e.g. APLSTS

(screened) APLSTY (screened) etc.6. In the case of HSL type cable with separately Lead Sheathed cores, add suffix (screened SL)

e.g. APLSTS (screened SL), APLSTY (screened SL) etc.

Rubber Cable :

| 2

Page 3: Cable Nomenclature

Cable Code Classification / Nomenclature 2010

For Cables other than Ship Wiring :

Constituent Code Letter

Aluminium Conductor A

Elastomer (Rubber) Insulation R

Copper wire braiding or helical screening of Copper wires C

Semi-conducting extruded Screening over & below Insulation CgCopper wire braiding or helical screening of Copper wires on individual cores CE @

Glass Fibre Yarn braiding C

Textile Braiding B

Synthetic Yarn Braiding S

Textile Braiding on individual cores BE @

Synthetic Yarn Braiding on individual cores SE @

Steel round wire armoring W

Double steel round wire armouring WW

Steel strip armouring F

Double steel strip armouring FF

Non-magnetic round wire armouring Wa

Non-magnetic strip armouring Fa

Steel wire braiding Wb

Steel wire pliable armouring Wp

Elastomer (Rubber) Outer Sheath R

PVC Outer Sheath Y

Normal flexible conductor is denoted as 'rf' & special (as per client requirement) flexible conductor is denoted as "rff". When the conductor material is Copper no Code Letter is requried for conductor @ In case only some of the cores are individually screened/braided the number of such cores shall be indicated as suffix to the Code Letter e.g. CE4, BE4, etc

For Ship Wiring Cables :

Constituent Code Letter

Ship Wiring Cable (Marine use) M

Elastomer (Rubber) Insulation G

Braiding of Steel/Copper/Annealed Tinned Copper C

Elastomer (Rubber) Outer Sheath G

PVC Outer Sheath Y

NOTE :

Material of braiding shall be indicated in brackets at the end as follows :

Plain Copper (CU) and Annealed Tinned Copper (ATC)

| 3

Page 4: Cable Nomenclature

Cable Code Classification / Nomenclature 2010

Examples for the above code letters :

1) Annealed tinned Copper flexible conductor of nominal cross-section 25Sqmm insulated with Rubber Compound, provided with Copper wire braiding on individual cores, for cores stranded together, inner sheathed, provided with steel wire braiding and overall sheathed with Rubber compound.

The Type Designation shall be RCEWbR 4 x 25 rf

2) Annealed tinned Copper (2.5 sq.mm) flexible conductor, insulated with silicon rubber, overall braided with Glass Fibre Yarn and varnished cable.

The type designation shall be RG 1 x 2.5 rf.

3) Annealed tinned copper flexible conductor of nominal cross-section 2.5 sq.mm insulated with Rubber Compound, 2 cores provided with protective screen of annealed tinned Copper wire braiding, 2 screened cores and 14 un-screened cores laid up together in one layer, inner sheathed, provided with annealed tinned Copper wire braiding and overall sheathed with Rubber Compound with reinforcement of Synthetic Yarn Braid.

The Type Designation shall be RCE2CSR (14 + 2) x 2.5rf

4) Stranded conductor of annealed tinned Copper of nominal cross-section 2.5 sq.mm, insulated with Rubber Compound, 3 cores stranded together, inner sheathed, provided with plain Copper/annealed tinned copper/steel wire braiding and overall sheathed with Rubber/PVC Compound.

The Type Designation shall be :

With Plain Copper Wire : MGCG (Cu) 3 x 2.5 rmBraiding : MGCY (Cu) 3 x 2.5 rm

With annealed tinned : MGCG (ATC) 3 x 2.5 rm

Copper Wirebraiding : MGCY (ATC) 3 x 2.5 rm

Examples :- For completely specifying the cable, the type designation is to be followed by indication of number of cores, nominal cross-section of conductor, construction of conductor and voltage rating of cable as shown in the following examples :

1. AYY 3 1/2 x 50/25 sm 0.65/1.1 kV 

| 4

Page 5: Cable Nomenclature

Cable Code Classification / Nomenclature 2010

2. AYFY 3 x 185sm 3.8/6.6 kV (E) 3. AYCY 1 x 400 rm 6.35/11 kV (E) 4. AYCEFY 3 x 240 rm/v 6.35/11 kV (E) 5. A2XCEFY 3 x 300 rm/v 12.7/22 kV (E) 6. YWWGbY 3 x 16 rm/12 (Mining) 0.65/1.1 kV 7. YFFGbY 3 x 70 sm/35 (Mining) 1.9/3.3 kV 8. APLS 1 x 630 rm 3.8/6.6 kV (E) 9. APLySWY 3 x 240 sm 6.35/11 kV (E) 10. APLSTS 3 x 400 sm 11 kV (UE) 11. APLSTS (Screened) 3 x 150 sm 12.7/22 kV (E) 12. APLSTgY (Screened) 3 x 300 rm 19/33 kV (E)

NOTE :

i. The nominal cross-section of conductors indicated are in sq.mm.ii. In Item (1) the cross-section indicated as ' 50/25 ' mean that the main conductors are of

nominal cross-section 50 sq.mm. and the neutral conductor is of nominal cross-section 25 sq.mm. 

iii. The construction of conductor is indicated as follows :

re : circular, solid conductor

rm : circular, multiwire stranded conductor

rm/v : circular, compact multiwire stranded conductor

sm : shaped, multiwire stranded conductor

In Items (6) and (7) the examples for TROPODUR Mining Cables the figures ' 16 rm/12 ' & ' 70 sm/35 ' denote that the nominal cross-section of conductor is 16 sq.mm. (circular, multiwire stranded), 70 sq.mm. (shaped, multi-wire stranded) and the minimum effective cross-sections of armouring are equivalent to 12 sq.mm. of copper* and 35 sq.mm. of copper* respectively.

(*or Aluminium in case of Aluminium conductor Mining cables)

| 5