Cablesizer | Cable Sizing to IEC and NEC Standards
http://www.cablesizer.com/nec/report/[1/8/2013 2:33:35 PM]
HelpNew Cable
NEC / NFPA 70: National Electricity Code (2011)
AmpacityVolt DropReport
NEC Cable Sizing Report
Important Note: If you change the common input data (e.g. basic cable and load information) on onepage, make sure to run all of the relevant calculations again!
Basic Information
The following basic cable specification was selected:
Conductor material: CopperNEC Cable type: THHNNumber of cores: Multi core
The following load parameters were selected:
Load type: Service, Feederor Branch Load
Number of phases: Three phaseNominal load voltage: 208 VFull load power factor: 0.85 puContinuous Load: 51 ANon-Continuous Load: 0 AProtective Device Rating: 100 A
Ampacity Considerations
Cable installation method: Raceways
The cable is installed under the following conditions:
Ambient Temperature: 95.0°F (35°C)Conductor Temp Rating: 194°F (90.0°C)No. of grouped current-carryingconductors: 4 to 6
Given these installation conditions, the adjustment factors are as follows:
Ambient Temperature: 0.9574 NEC 2011 Article 310.15(B)(2)Grouping derating: 0.8 NEC 2011 Table 310.15(B)(3)(a)
Cablesizer | Cable Sizing to IEC and NEC Standards
http://www.cablesizer.com/nec/report/[1/8/2013 2:33:35 PM]
Total derating factor: 0.7659
125% x Continuous load + 100% x Non-Continuous load is 63.75 A. The protective device rating is 100 A.
The ampacity calculation is based on the larger of these two values, i.e. selected load current = 100 A
Result: For the selected load current: 100 A:
Minimum Multi Core cable size is: 1 AWGCable base ampacity: 145 A (NEC 2011 Table 310.15(B)(16))Installed / derated ampacity: 111.0555 A