    CALCULATION OF ELECTRICALCALCULATION OF ELECTRICALINDUCTION NEAR POWER LINESINDUCTION NEAR POWER LINES

    Direction Expertise et Support Technique de TransportLignes, Cbles et environnement

    Prepared by : Richard Lehoux, [email protected]

    May 2008May 2008

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    2/22

    Scope of the presentationScope of the presentation

    1. Calculation of Electric Field

    2. Electric field induction in a human body1. IEEE Std80-2000 (Guide for Safety in AC Substation Grounding)2. EPRI (Electric Power Research Institute)3. CSA (Canadian Standard Association)

    3. Design criteria

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP22

    1. CSA2. HQT (Hydro-Qubec Transnergie)

    4. Methods of determining induced current1. Empirical2. Boundary Element Method (BEM)

    5. Comparison results: Empirical versus BEM

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    3/22

    Electric field induction in a human bodyElectric field induction in a human body

    Range of tolerable current in a human body IEEE Std 80-2000, Article 5.2 "Effect of magnitude and duration"

    1mA: threshold of perception 1-6 mA: unpleasant to sustain 10.5 mA: threshold for women let-go currents 16 mA: threshold for men let-go currents Note: the duration of the fault is infinite

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP33

    Range of tolerable current in a human body EPRI "TRANSMISSION LINE REFERENCE BOOK",

    Chapter 8, "Field effect of overhead transmission lines and stations",

    Article 8.10 "Electric-field induction in people", paragraph "Response tosteady-State Currents" 5 mA: let-go values for children for a probability of 0.5% have been

    conservatively estimated as equal to 5 mA threshold of perception

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    4/22

    Electric field induction in a human bodyElectric field induction in a human body

    CSAC22.3 No.1-06, Article A.5.3.1 "Vertical desing clearances of wiresand conductors above ground or rails and Tables 2 and 4"

    5 mA: let-go currents

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP44

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    5/22

    Design criteriaDesign criteria Height of conductorsHeight of conductors

    CSA calculation criteria Article : A5.3.1 Based on the worst-case condition :

    Vehicle is insulated from the ground by rubber tires Person contacting the vehicle is touching or standing on a well-grounded surface Induced current in all cases is below 5 mA (Let-go currents) Maximum line to ground voltage

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP55

    HQT Use CSA design criteria

    4,15 m

    5 mA

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    6/22

    Methods of determining induced currentMethods of determining induced current

    Two methods are available at HQT to determine theinduced current (5 mA let-go) in a human body

    Empirical method (EPRI) Eas , fast, chea , a roximate

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP66

    Boundary Element Method (Maxwell's Equations) Expensive, accurate

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    7/22

    Empirical methodEmpirical method

    Method of approximating induced current in objects closeto ground EPRI "TRANSMISSION LINE REFERENCE BOOK"

    Chapter 8, "Field effects of overhead transmission lines and stations" Method of approximating calculation of current induced on objects

    close to the ground

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP77

    Figure 8.8.2 "Shape for a rectangular solids"

    (The shape is collecting electrical charge)

    Many others shape available Horizontal / Vertical cylinder Flat plate House Horse Etc.

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    8/22

    Empirical methodEmpirical method

    Sizes of vehicles(m)

    Length Width Height

    ArticleC22.3-01-06

    2003 2006 HQ 2003 2006 HQ 2003 2006 HQ

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP88

    Truck A5.3.1 15.2 23.0 23.0 2.4 2.6 2,6 4.15 4.15 4,15

    Large

    farm

    A5.3.1 7.6 7.6 7.6 2.4 2.4 2.4 4.15 4.15 4.5 *

    TrainA5.3.1

    (example 4)4000.0 6.706

    * : Height used by HQT

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    9/22

    Calculation with EPRI method to get 5 mA induced in a human body

    Size of the truck :Length (A): 23 m

    Width (B) : 2.6mHeight (H) : 4.15mCenter : 4.15/2 = 2.08

    Ratio :A/B : 23/2.6=9.62

    H/B

    Empirical methodEmpirical method -- Exemple : TruckExemple : Truck

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP99

    H/B : 4.15/2.6=1.6

    With abacus :S/(A*B)=S/(23*2.6)=5.1

    S=304.9

    5mA=S*E/300 (E: Electric field)E=(5mA*300)/304.9=4.9kV/m

    at 2.08m (center of vehicle) See slide 14 to determine

    height of conductors

    9.62

    1.6

    S/(AB

    )

    A/B

    5.1

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    10/22

    Calculation with EPRI to get 5 mA induced in a human body

    Size of the Large Farm Vehicle :Length (A) : 7.6 mWidth (B) : 2.4m

    Height (H) : 4.5m (HQT - Study)Center : 4.5/2=2.25m

    H/B

    B)

    Ratio :A/B : 7.6/2.4=3.2

    Empirical methodEmpirical method -- Exemple : Large FarmExemple : Large Farmvehiclevehicle -- HQTHQT

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP10103.2

    1.9

    S/(

    A/B

    8.0

    . . = .

    With abacus :S/(A*B)= 8S=8(7.6*2.4)=146

    5mA = S*E/300 (E: Electric field)E=(5mA*300)/146=10.3kV/m

    at 2.25m (center of vehicle) See slide 14 to determine

    height of conductors

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    11/22

    Calculation with EPRI to get 5 mA induced in a human body

    Size of the Large Farm Vehicle :Length (A) : 7.6 mWidth (B) : 2.4m

    Height (H) : 4.15m (CSA)Center : 4.15/2=2.08m

    H/B

    B)

    Ratio :A/B : 7.6/2.4=3.2

    Empirical methodEmpirical method -- Exemple : Large FarmExemple : Large Farmvehiclevehicle -- CSACSA

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP11113.2

    1.9

    S/(

    A/B

    7.0

    . . = .

    With abacus :S/(A*B)= 7S=8(7.6*2.4)=129

    5mA = S*E/300 (E: Electric field)E=(5mA*300)/129=11.6kV/m

    at 2.25m (center of vehicle) See slide 14 to determine

    height of conductors

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    12/22

    Calculation of Electric FieldCalculation of Electric Field

    The electric field is determined by these parameters :1. Voltage2. Distance between phases3. Diameter of conductors4. Number of conductors per bundle5. Presence of overhead ground wire6. Distance of conductors from the ground

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP1212

    Software available to calculate the electric field : CDEGS of SES (Package : MultiField - 38 k$ - Available on market) Coulomb (3D Electric Field Solver Used by IREQ - Available on

    market) Expomag (In house software HQ)

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    13/22

    Calculation of Electric FieldCalculation of Electric Field

    FAA TOWER - 735 kV /

    Electro-mechanicals specifications 1 circuit Conductors

    4 per bundles : 3.556 cm

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP1313

    s ances e ween

    Voltage max 765 kV

    Overhead ground wire Quantity : 2 : 1.27cm

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    14/22

    735 kV Electric Field

    8

    10

    12

    kV/m

    Calculation of Electric FieldCalculation of Electric Field

    Electric field 735 kV (FAA Tower) Conductors at rest

    Heightof

    Max. Elec. field: 10.3 kV/m Large Farm Vehicle

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP1414

    0

    2

    4

    6

    0 4 8 12 16 20 24 28 32 36

    m

    21.0 m

    13.4 m

    conductors

    HQT ROW (80 m)< 2 kV/m

    Max. Elec. field: 4.9 kV/m - Truck

    Center of the ROW

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    15/22

    Boundary Element Method (BEM)Boundary Element Method (BEM)

    Equivalent circuit of a truck near a power linesEquivalent circuit of a truck near a power lines

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP1515

    Human body

    Represented by a 1 k

    Isc = 5 mA

    Modelizationdone by IREQ(Alain Turgeon)

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    16/22

    BEM ExampleBEM Example Truck parallel to the lineTruck parallel to the line

    Capacitive induction simulation for a truck located at 17 metersof the center line and parallel to conductors

    735 kV with FAA towers

    4

    4.5

    5kV/m

    17 m

    Height of conductors simulation :21 - 22 - 23 - 24 Height of conductors

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP1616

    0

    0.5

    1

    1.5

    2

    2.5

    3

    3.5

    -50 -40 -30 -20 -10 0 10 20 30 40 50

    m

    Example of an electric profile field

    ROW

    2,6 m

    4,15 m

    15,7 18,3

    5 mA

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    17/22

    BEM ExampleBEM Example Truck parallelTruck parallel

    Height of

    conductorsCapacitances

    Currentin a human

    body

    (m)Ca-t(pF)

    Cb-t(pF)

    Cc-t(pF)

    Ct-g(pF)

    ISC(ma)

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP1717

    21 3,03 15,8 43,4 1,46 5,9622 3,19 15,4 40,6 1,46 5,51

    23 3,33 15,0 38,0 1,46 5,09

    24 3,45 14,6 35,6 1,46 4,71

    o m t t e

    current in ahuman body

    at 5 mAthe height ofconductors

    must behigher than

    23.2 m

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    18/22

    BEM ExempleBEM Exemple Truck perpendicular to lineTruck perpendicular to line

    Capacitive induction simulation for a truck located perpendicular to conductors735 kV with FAA towers

    5

    6 kV/m

    Height of conductors simulation :17 - 18 - 19 - 20 Height of conductors

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP1818

    0

    1

    2

    3

    4

    -50 -40 -30 -20 -10 0 10 20 30 40 50

    m

    4,15 m

    Example of an electric profile field

    ROW

    23 m

    5,5 28,5

    5 mA

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    19/22

    BEM ExampleBEM Example Truck perpendicularTruck perpendicular

    Heightof conductors

    CapacitancesCurrent

    in a humanbody

    (m)Ca-t(pF)

    Cb-t(pF)

    Cc-t(pF)

    Ct-g(pF)

    ISC(mA)

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP1919

    17 4,19 21,2 49,1 1,44 6,54

    18 4,36 20,3 45,9 1,45 6,05

    19 4,52 19,5 42,9 1,45 5,58

    20 4,65 18,7 40,3 1,45 5,18

    To limit thecurrent in ahuman bodyat 5 mA theheight of

    conductorsmust be

    higher than20.5 m

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    20/22

    Comparison results: Empirical versus BEMComparison results: Empirical versus BEM

    Height of conductors

    735 kV FAA towerEmpiricalMethod

    (m)

    BEMMethod

    (m)

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP2020

    21 20.5 perpendicular23.2 parallel

    HQT chose empirical method for it's in house standard

    BEM method permitted HQT to check the accuracy of empiricalmethod

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines

    21/22

    Empirical methodEmpirical method HQT resultsHQT results

    NominalVoltage

    (kV)TOWER

    MINIMUM HEIGHT OF CONDUCTORS(m)

    TRUCK(Electric Field : 4.9 kV/m)

    LARGE FARM VEHICULE(Electric Field : 10.3 kV/m)

    735 FAA Single circuit 21 13.8

    May 13th 2008May 13th 2008CEA EMF WORKHOPCEA EMF WORKHOP2121

    ou e c rcu t . < .

    315 EFK Single circuit 10.6 7

    230 DPD Double circuit 6.7

  • 7/28/2019 Calculation of Electrical Induction Near Power Lines