    Please send me the X/R ratio of transformer for 1600kVA Trihal transformer?

    The X/R ratio for the 1600kVA Trihal transformer can be calculated using the Trihal electrical characteristics(impedance & losses data gi!en normall" in transformer datasheets (attached !alues gi!en in transformerdatasheet#

    $%oad losses in atts (at ' )*

    $+o$load losses in atts* and$rated impedance !oltage , -.

    then calculation of the X/R ratio can be performed as follos#e can obtain the R. as follos#

    $R. , 100

    2(3ull load loss ($no load loss (/(transformer rated poer (kVA10004

    then using the impedance relation# - , R5X*e can calculate X. , 7(-.8 $ R.8*hence "ou can get X./R. , X/R ratio

    Remarks#1 9atasheets for both :standard losses: t"pe and :reduced losses: t"pe Trihal transformers are attached

    Also the impedance !alue shall be clear on transformer nameplate

    ; an eample of abo!e calculation has been attached for "our reference