Upload
others
View
8
Download
0
Embed Size (px)
Citation preview
Calculations & Examples for selecting
Water Heating Systems
Features of Heat-Pump Water Heating Systems
• Energy efficient COP factors over 4.5 Can reach 6+ under ideal conditions
• Can operate in low ambient conditions : between minus 7°C and + 43°C
• Supplies constant hot water up to 55°C
– On demand, direct to taps
– As supply to geyser, for storage
– For under-floor or radiator panel heaters
C O P efficiency graph
Calculation Facts
Facts:
• The energy required to raise one litre of water by one degree Centigrade is a calorie.
• Water weighs 1kg / litre
• 1 kW heat equals 860 calories, a factor of 1.163
• An “average guest in a 5 star hotel” uses 125 ~ 150 litres hot water per day
Hot Water useage
CIBSE:Chartered Institute of Building Service Engineers
ASHRAE : American Society Of Heating, Refrigeration & Air-conditioning
Institute of Plumbing
Suppliers of Water Heating products
Domestic Scenario # 1. Current situation: 4 adults, 2 bathrooms, 2 x 150 litre geysers of 3kW
Electricity Account 2007/08 = 21 563 kWhr = R 6 534.24 ( +- 33c/kWhr) • Assume that 50% of electricity consumption is for hot water
generation
Then : 50% of 21 563kWhr ÷365 days = 29.54 kWhr/day
Therefore : 29.54kWhr ÷ 6kW elements = 4.92 hours
Hence each geysers work for an average of 4.92 hours per day.
• Say 5hours / day to heat 150 litres of water, using 3kW power
Unit Selection & Savings • Each geyser operates for 5 hours per day, consuming 3kW each.
By selecting an Airco ARSJ-72/300 we get: 7.2 kW heated water (additional 17% capacity) at 180 litres per hour ( 1.66 hours operation per day) using only 1.87 kW power (electricity saving of 69%)
Therefore :
29.54 kWhr/day less 1.87 kW used x 1.66 hours x 365 = 16 765 kWhrs @ 33c/kWhour = R 5 532.53
Saving of R 1 001.71 per annum at current rates.
Hotel # 2.
• 3 star hotel of 250 guests
• “Make-up” or recovery time of 6 hours
• Hot water required at 55°C
• Supply water at 20°C supply
Calculations
An hotel with 250 guests @125 l/day = 30 000 litres consumption.
Hence: litres water x ▲T x factor 1.163 1 000 w x 6 hours recovery time
= 30 000 x (55 – 20) x 1.163 6 000
= 1 221 150 6 000
= 203 kW Energy Required to heat 30 000 litres to 55°C
litres water x Delta T x 1.163 factor 1 000 x hours (time limit for heating water)
30 000 x (55 – 20) x 1.163 1000 x 6
= 305 kW
Unit Selection
• 203 kW Energy required
No of units required = 3; therefore 203 kW ÷ 3 = 67 kW, however
• 30 000 litres of hot water to be produced in 6 hours = 5 000l/hr
5 000 l/hr ÷ 3 units = 1 666 litres per hour.
Airco ARSJ770/S-820 unit produces 77kW of constant hot water at 1 660litres / hour at 55°C
Selection & Savings
Model Airco ARSJ770/S-820 unit produces 77kW of constant hot water at 1 660litres / hour at 55°C
Total Energy output / unit = 77 kW x 3 = 231 kW
Total Power input / unit = 17.4 kW = 52.2 kW
Saving: 77.4% on electricity
C O P = 4.42
Clinic # 3. • Existing: 1 x 4000 litre geysers with 72kW of electric elements
• Make-up period, maximum of 4 hours.
• Tariff @ R0.50 per kW/hr, plus max demand charge of R63.00 / kVa
Select Airco 2 x ARSJ380/S-820, each capable of 38.5kW @ 830l/hr. Total Heating : 77 kW @ 1 660l/hr at 60°C using 17.4 kW/hr
Energy Saving: (72kW – 8.7kW) x 2units = 54.6 kW/hr
Max demand saving: 54.6 x R0.50 x 12months = R 41 277.60
kVa demand = (72 kW – 8.7 kW) x R 63.00 x 2 units x 12 months = R 95 709.60 Total Savings: = R 136 987.20
Determining Back-up Electrical Capacity 22 room hotel x 1.5 people, 80% occupancy, x 125 l/person = 3 300 litres Allow 25% for losses & mixing = 4 125 litres Recovery period of 4 hours, therefore 2 x 2 000 litre tanks is adequate
Select: 2 x Airco ARSJ-200/S-540, power input/output of 4.35 / 20kW @ 430l/hr. In winter temperatures can drop to -2°C and COP reduces from 4.6 to 2.8
Revised COP
Back-up electrical element calcs.
• Revised COP of 2.8 at -2°C, but Power input remains 4.35 kW
Therefore: 2.8 x 4.35 = 12 kW (revised unit capacity at -2°)
• 12 kW will raise 2 000 litres to 20.6°C in 4 hours and a further 12kW is required to raise temperature from 20° to 65°C in 4.5 hours
• Electric back-up of 12 kW required in storage vessel, but only operational for 4,5 hours to maintain 2 000litres of water at 65°C
Electricity Tarriffs
• Each municipality charges different rates – Fixed charge Demand charge or Consumption charge
Seasonal rates - Winter & Summer months
• Some consumers get preferrential rates
If we can get a copy of : Electricity Tariff Schedule recent account We can calculate: Savings in Rands per month Payback period in months
Quality Approved & Certification
All units are manufactured to ISO standards and are internationally approved & certified