XX"# - XX
IRRIGATION SCHEDULEMODEL NO.SYMBOL
1-1/2" 825YA AssemblyInstall per COT Std. Det. #800-11B
1" Dedicated Irrigation Water Meter
DETAIL
FEBCO
IRRIGATIONPOINT OF
CONNECTION
BACKFLOWPREVENTER
CONTROLVALVE
GATE VALVE WATTS
PVC MAINLINE
SLEEVING
NOTSHOWN
SECURITYENCLOSURE
IRRIGATIONMETER
1" Dedicated Irrigation Water Meter. Installedper COT Std Det #800-10A/B
Refer to Civil Utilityand Water Plans
PVC SPRAYLATERAL
3/4" PVC class 200
SENSOR RAIN BIRD
IRRIGATIONCONTROLLER
1-1/2" PVC Class 200.No 90 degree ells on mainline.
Size per line sizeThreaded ends
In StrongboxEnclosure
Class 200 PVC Solvent Weld Joints
Carson 1324-15-3L Super Jumbo Valve Box1" Sch. 80 PVC Ball Valve1" or 2" Toro 220-27-0-4/8 Brass Globe Valvewith EZ-REG Pressure Regulator (EZ-100)
Refer to Civil Utilityand Water Plans
Strongbox SBBC-22SS17.75"W X 28.5"H X 22"L
TORO
RAINMASTER
WR-2-RFS Wireless Rain/Freeze Sensor
NA
1" Buckner QB44-LCAR10QUICK
COUPLERBUCKNER
SS Pole Mounted
STRONGBOX
NA
NA
NA
NA
Unless otherwisenoted on the plan
Unless otherwisenoted on the plan
Carson 910 10" Standard Round Valve Box
Watts Brass Gate Valve (WGV-X)
Stainless SteelPedestal Cabinet8 Valves Total
DESCRIPTION MFR COMMENTS
Color:Green
MASTERVALVE &
FLOWSENSOR
TORO& DATA
INDUSTRIAL
Rain Master Eagle-I RME-XXEGi-SPEDCellular modem communication shall tie intoCity of Thornton existing controller network.
SERVICE LINE 1-1/2" Type K CopperNA Meter to Backflow
POC
M
C
See Sleeving Notes
Q
Pipe, fittings and ballvalves to match sizeof control valve.5 gpm min. flow.
VALVE CALLOUTS
Zone Designation:S (Shrubs Spray)
Valve/Station Number
Valve Flow: (GPM)Valve Size
Rain Bird RD-1812-S-P30-F-U U10 Series12.0" Pop-Up, with 30 psi in-stem pressureregulation, Seal-A-Matic check valve, andFlow-Shield Technology. 1/2" NPT femalethreaded inlet.
RAIN BIRDSHRUBSPRAY8' - 10'
1" TORO 220-27-0-4 Brass Series Valve1" Data Industrial 220BR Brass Flow Sensor
Carson 910 10" Standard Round Valve Box
Install with 1/2"pre-manufacturedflexible pipe joint.1.58 PrecipitationRate at 30 psi.
1. POINT OF CONNECTION: THE IRRIGATION POINT OF CONNECTION SHALL BE INSTALLED PER THE CITY OF THORNTONSTANDARD DETAILS 800-10A AND 800-11B WITH THE FOLLOWING EQUIPMENT: TAP DOWNSTREAM OF THE 1"DEDICATED IRRIGATION WATER METER (SEE CIVIL UTILITY PLANS) WITH 1-1/2" TYPE K COPPER PIPE AND EXTEND ATA DEPTH OF 48" OR PER LOCAL CODES, WHICHEVER IS GREATER TO BACKFLOW PREVENTER. INSTALL ONE 1-1/2"MANUAL DRAIN VALVE, ONE 1-1/2" REDUCED PRESSURE BACKFLOW PREVENTER, ONE 1" MASTER VALVE/FLOWSENSOR ASSEMBLY IN SECURITY ENCLOSURE WITH A FROST BLANKET. EXTEND 1-1/2" TYPE K COPPER A MINIMUM30" HORIZONTAL FROM BACKFLOW PREVENTER AND INSTALL ONE 1" QUICK COUPLER. TRANSITION TO 1-1/2" CLASS200BE PVC AND EXTEND TO VALVES AS SHOWN.POC 1: CONNECTION 1 IS FOR PHASE 1 AND IS LOCATED IN THE MEDIAN AT 144TH ST.POC ELEVATION: 5,270'PRESSURE AVAILABLE: 97 PSIDESIGN PRESSURE: 65 PSIMAXIMUM CAPACITY (FLOW): 35 GPMTHE CONTRACTOR SHALL CONFORM TO ALL LOCAL CODES AND OBTAIN AND PROVIDE PAYMENT FOR ALL PERMITSASSOCIATED WITH THIS WORK.
2. STATIC PRESSURE:THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE PRESSURE IN THE FIELD BEFORECONSTRUCTION BEGINS AND FOR NOTIFYING THE CITY REPRESENTATIVE OF ANY DISCREPANCY BETWEEN THEDESIGN PRESSURE OF THE IRRIGATION SYSTEM AND THE MEASURED PRESSURE IN THE FIELD. IF THECONTRACTOR FAILS TO NOTIFY THE CITY REPRESENTATIVE OF SUCH DISCREPANCIES, THEN THE CONTRACTORASSUMES ALL LIABILITY AND COSTS ASSOCIATED WITH SYSTEM MODIFICATIONS TO ACCOMMODATE THE ACTUALPRESSURE.
3. THE IRRIGATION SYSTEM HAS BEEN DESIGNED TO OPERATE MULTIPLE ZONES SIMULTANEOUSLY WHEN NECESSARYDUE TO INCREASED PLANT WATER REQUIREMENTS AND/OR DECREASED AVAILABLE WATERING TIMES, SUCH ASWATERING RESTRICTIONS.
4. MULTIPLE ZONES MAY BE REQUIRED TO RUN AT THE SAME TIME TO ACHIEVE THE FLOW SENSOR'S MINIMUM FLOWREQUIREMENT. MAXIMUM FLOW NOT TO EXCEED 35 GPM.
5. CONTROLLER LOCATION: THE RAIN MASTER EAGLE-i SERIES CONTROLLER IS LOCATED IN THE PLANTING AREAADJACENT TO THE POINT OF CONNECTION IN THE MEDIAN AS INDICATED ON THE PLANS. PROVIDE AN EIGHT FOOTCOPPER GROUNDING ROD AT THE CONTROLLER LOCATION PER CITY OF THORNTON SPECIFICATIONS. CONNECTIONTO 120 VOLT POWER THROUGH UL LISTED FUSED SERVICE DISCONNECT PANEL WITH LINE SUPPRESSION, ALLNECESSARY CONDUIT AND ALL RELATED EQUIPMENT SHALL CONFORM TO LOCAL CODES AND PER XCEL '2013STANDARDS FOR ELECTRICAL INSTALLATION AND USE'. CONTRACTOR IS RESPONSIBLE FOR FOR ALL COSTS FORSUPPLYING THE ELECTRICAL CONNECTION TO THE CONTROLLER. REFER TO CIVIL UTILITY AND ELECTRICAL PLANSAND COORDINATE WITH THE CITY REPRESENTATIVE AND APPROPRIATE UTILITY COMPANY FOR ADDITIONALINFORMATION REGARDING ELECTRICAL SERVICE FOR THE CONTROLLERS.
6. SENSOR LOCATION: RAIN BIRD WR2 SENSOR SHALL BE POLE MOUNTED IN A LOCATION IN FULL SUN AND OPEN TORAINFALL. SENSOR SHALL BE NO MORE THAN 800' FROM WIRELESS RECEIVER. MOUNT WIRELESS RECEIVER ON ORADJACENT TO THE IRRIGATION CONTROLLER.
7. EQUIPMENT LOCATION: BACKFLOW PREVENTER, IRRIGATION CONTROLLER AND ELECTRIC METER, SENSOR ARE TOBE LOCATED TOGETHER IN A MULCHED PLANTER BED WITHIN THE MEDIAN. FINAL LOCATION OF EQUIPMENT SHALLBE APPROVED BY THE CITY REPRESENTATIVE PRIOR TO INSTALLATION. IRRIGATION CONTROL AND CONNECTIONEQUIPMENT SHALL NOT BE SPRAYED ON. CONTRACTOR TO ADJUST OVER SPRAY TO AVOID THESE COMPONENTS.
8. MANUAL DRAIN VALVES: SHALL BE LOCATED AT THE BACKFLOW PREVENTER AND LOW POINTS ALONG THEMAINLINE. LOCATIONS SHALL BE APPROVED BY THE CITY REPRESENTATIVE PRIOR TO INSTALLATION.
IRRIGATION POINT OF CONNECTION NOTESIRRIGATION NOTES
SLEEVING COORDINATION NOTES1. INSTALLATION OF IRRIGATION SLEEVING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR . SLEEVES
SHALL BE INSTALLED PRIOR TO THE START OF PAVING OPERATIONS. THE GENERAL CONTRACTOR SHALLCOORDINATE WITH THE IRRIGATION CONTRACTOR FOR LOCATION AND SIZING OF SLEEVES PRIOR TO THE STARTOF CONSTRUCTION.
2. THE CONTRACTOR SHALL SLEEVE ALL IRRIGATION DISTRIBUTION LINES, VALVE CONTROL WIRES ANDCOMMUNICATION WIRES UNDER ALL PAVED SURFACES, WALL FOOTERS, DRAINAGE CHANNELS, INLETS, CATCHBASINS, ETC.
3. ALL SLEEVES SHALL EXTEND A MINIMUM OF 6" BEYOND EDGE OF ALL OBSTRUCTIONS. NO TEES, ELLS OR OTHERTURNS IN PIPING SHALL BE LOCATED UNDER ANY OBSTRUCTIONS .
4. MARK ALL SLEEVE LOCATIONS WITH A CHISLED 'X' IN THE PAVING DIRECTLY ABOVE SLEEVE LOCATION.5. SLEEVING SHALL BE INSTALLED PER THE SIZES AND QUANTITIES SHOWN ON THE PLANS BASED ON THE CHART
BELOW.6. ALL MAINLINE, VALVE CONTROL AND COMMUNICATION WIRES, LATERALS UNDER PAVED SURFACES ARE TO BE
INSTALLED IN SEPARATE SLEEVING.SLEEVED PIPE SIZE/WIRE QTY. REQUIRED SLEEVE SIZE AND QTY.
34"-1" PIPING 2" CLASS 200 PVC (1)
114"-11
2" PIPING 3" CLASS 200 PVC (1)1-50 CONTROL WIRES 2" CLASS 200 PVC (1)
1. THE CONTRACTOR SHALL REFER TO CITY OF THORNTON STANDARDS AND SPECIFICATIONS SECTION 809 - IRRIGATIONSYSTEMS AND COORDINATE WITH THE GENERAL CONTRACTOR AND CITY REPRESENTATIVE FOR SUCCESSFULCOMPLETION OF THIS WORK.
2. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY TO INSTALL THEIMPROVEMENTS SHOWN ON THE PLANS.
3. THE CONTRACTOR ASSUMES ALL LIABILITY ASSOCIATED WITH THE MODIFICATION OF THE IRRIGATION SYSTEMDESIGN WITHOUT NOTIFYING THE CITY REPRESENTATIVE.
4. ALL IRRIGATION EQUIPMENT IS TO BE AS SPECIFIED OR APPROVED EQUAL PER THE DISCRETION OF THE CITYREPRESENTATIVE.
5. IT IS THE CONTRACTOR'S RESPONSIBILITY TO CONDUCT A THOROUGH SITE INSPECTION AND REVIEW OF THEPROJECT CONSTRUCTION DOCUMENTS INCLUDING BUT NOT LIMITED TO THE FOLLOWING: LANDSCAPE PLAN, UTILITYPLAN, CIVIL PLAN, GRADING AND DRAINAGE PLAN AND ALL OTHER ASSOCIATED PLANS THAT AFFECT THIS WORKPRIOR TO BEGINNING CONSTRUCTION. IF THE CONTRACTOR OBSERVES ANY DISCREPANCIES AMONG THECONSTRUCTION DOCUMENTS AND THE EXISTING CONDITIONS ON SITE, IT IS THEIR RESPONSIBILITY TO CONTACT THECITY REPRESENTATIVE IMMEDIATELY.
6. THE CONTRACTOR SHALL CONFORM TO ALL LOCAL AND STATE REGULATIONS AND INSTALL THE IRRIGATION SYSTEMAND ITS COMPONENTS PER THE MANUFACTURER'S SPECIFICATIONS. THE CONTRACTOR SHALL OBTAIN AND PROVIDEPAYMENT FOR ALL PERMITS REQUIRED BY ANY LOCAL AND STATE AGENCIES AND UTILITY COMPANIES HAVINGJURISDICTION OVER THIS SITE.
7. CONTRACTOR IS RESPONSIBLE FOR SCHEDULING AND PAYING FOR TESTING OF THE BACKFLOW PREVENTER BY ASTATE CERTIFIED INSPECTOR. CONTRACTOR SHALL PROVIDE CERTIFICATES TO CITY REPRESENTATIVE.
8. THE CONTRACTOR MUST VERIFY THE LOCATION OF ALL UNDERGROUND UTILITIES PRIOR TO CONSTRUCTION. IF THECONTRACTOR FAILS TO DO SO AND DAMAGES ANY UNDERGROUND UTILITIES THROUGH THE COURSE OF HIS WORKTHE CONTRACTOR SHALL PAY FOR ANY REPAIR WORK ASSOCIATED WITH SAID DAMAGES.
9. IT IS THE INTENT OF THIS DESIGN THAT ALL IRRIGATION EQUIPMENT BE INSTALLED WITHIN LANDSCAPE AREAS ANDWITHIN THE PROJECT LIMITS. EQUIPMENT SHOWN OUTSIDE OF THESE LIMITS IS SHOWN FOR GRAPHIC CLARITY ONLY.IF THERE IS A QUESTION REGARDING THE LOCATION OF ANY COMPONENT OF THE IRRIGATION SYSTEM, IT IS THECONTRACTOR'S RESPONSIBILITY TO CONTACT THE CITY REPRESENTATIVE. IF THE CONTRACTOR NEGLECTS TONOTIFY THE NECESSARY PARTIES, THE CONTRACTOR SHALL PAY FOR ANY REPLACEMENT OR MODIFICATION TOINSURE PROPER LOCATION AND OPERATION OF THE IRRIGATION SYSTEM AND ITS COMPONENTS.
10. ALL VALVE BOXES AND LIDS SHALL BE PLASTIC WITH SELF LOCKING COVERS. LID COLOR TO BE GREEN. INSTALL PERTHE CONSTRUCTION DETAILS. DO NOT INSTALL IN PAVED AREAS.
11. ALL VALVE BOXES SHALL BE INSTALLED A MINIMUM OF 1'-0" FROM THE EDGE OF PAVED SURFACES AND 3'-0" FROMTHE CENTERLINE OF DRAINAGE SWALES OR RETENTION BASINS.THE CONTRACTOR SHALL ADJUST ALL VALVE BOXESTO BE FLUSH FINISH GRADE.
12. GROUNDING FOR THE IRRIGATION CONTROLLER IS TO BE INSTALLED PER CITY OF THORNTON SPECIFICATIONS, THEMANUFACTURER'S SPECIFICATIONS AND PER THE AMERICAN SOCIETY OF IRRIGATION CONSULTANTS GUIDELINE100-2002 FOR EARTH GROUNDING ELECTRONIC EQUIPMENT IN IRRIGATION SYSTEMS FOUND ATwww.asic.org/Design_Guides.aspx. FOR TECHNICAL SUPPORT REGARDING THE IRRIGATION CONTROLLER ORGROUNDING PLEASE CONTACT RAIN MASTER (800) 777-1477.
13. CONTRACTOR SHALL EXTEND (3) THREE SPARE CONTROLLER WIRES, LOOPED IN EACH VALVE BOX TO THE END OFALL MAINLINE BRANCHES FOR FUTURE EXPANSION CAPABILITY. COIL 24" LENGTH MIN. OF SPARE WIRES IN A 10"ROUND VALVE BOX.
14. CONTROLL WIRE SHALL BE 14GA MIN. UF LISTED, AWG, DIRECT BURY SOLID COPPER WIRE. WIRE SHALL BE TAPEDAND BUNDLED EVERY 10'. PROVIDE 24" LOOPS AT ALL VALVE BOXES, CHANGES IN DIRECTION GREATER THAN 90°, ATBOTH ENDS OF SLEEVES AND AT 100' INTERVALS ALONG CONTINUOUS RUNS OF WIRE.
15. CONTRACTOR SHALL USE UL APPROVED WIRE STRIPPER AND 3M DBY-6 WATERPROOF CONNECTIONS AT ALL SPLICESAND CONNECTIONS POINTS. DO NOT DIRECT BURY CONNECTIONS. ALL CONNECTIONS SHALL BE LOCATED IN A VALVEBOX OR LABELED SPLICE BOX.
16. CONTRACTOR SHALL INSTALL 14GA SINGLE STRAND DIRECT BURY COPPER YELLOW JACKET TRACER WIRE IN ALLIRRIGATION MAINLINE AND LATERAL LINE TRENCHES. TRACER WIRE TO BE ACCESSIBLE IN EVERY VALVE BOX.
17. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE ADEQUATE VERTICAL SEPARATION BETWEEN ALL IRRIGATIONDISTRIBUTION LINES AND ALL UTILITIES (EXISTING OR PROPOSED), CONDUIT, STORM WATER COMPONENTS, DRAINS,ETC.
18. PLANT MATERIAL LOCATIONS TAKE PRECEDENCE OVER IRRIGATION LINES. COORDINATE INSTALLATION OFIRRIGATION EQUIPMENT SO THAT IT DOES NOT INTERFERE WITH THE PLANTING OF TREES OR OTHER LANDSCAPEMATERIAL INCLUDING PERENNIAL BEDS.
19. THE CONTRACTOR SHALL STAKE THE LOCATION OF THE MAINLINE, CONTROL VALVES, GATE VALVES, AND SHRUBSPRAY LOCATIONS, ETC. AND SCHEDULE A REVIEW WITH THE CITY REPRESENTATIVE PRIOR TO INSTALLATION.
20. CONTRACTOR SHALL FLUSH SYSTEM THOROUGHLY AND EACH ZONE SHALL BE TESTED TO ENSURE PROPEROPERATING PRESSURE AT ALL HEADS IN ZONE.
21. CONTRACTOR SHALL LOCATE ROTOR HEADS A MINIMUM 6" AND ALL SPRAY HEADS A MINIMUM OF 3" FROM ALLPAVING. THE CONTRACTOR SHALL FINE TUNE AND ADJUST NOZZLE DIRECTION AND RADIUS TO REDUCE OVERSPRAYONTO ALL ELECTRICAL COMPONENTS, PAVING OR HARD SURFACES.
22. CONTRACTOR SHALL INSTALL A QUICK COUPLER IN 10" VALVE BOX AT THE END OF ALL BRANCHES OF THE MAINLINE,AT 300' INTERVALS ALONG THE MAINLINE AS SHOWN ON PLANS, FOR MAINTENANCE, WINTERIZATION AND FLUSHINGOF MAINLINE.
23. PVC REPAIR COUPLINGS SHALL BE NIBCO SLIP-FIX OR APPROVED EQUAL, SIZED TO THE PIPE SIZE. NO COMPRESSIONCOMPRESSION FITTINGS WILL BE ALLOWED. REPAIR COUPLINGS TO BE A MINIMUM 5' FROM OTHER FITTINGS ANDCONTROL VALVES.
24. THIS IRRIGATION SYSTEM HAS BEEN DESIGNED TO OPERATE BETWEEN THE HOURS OF 10 PM AND 5 AM PER CITY OFTHORNTON REQUIREMENTS. ESTABLISHMENT WATERING WILL REQUIRE UP TO TWICE AS MUCH IRRIGATION FOR A 21DAY PERIOD. THESE FIGURES ARE BASED ON A 30-YEAR AVERAGE WEATHER DATA AND WILL NEED TO BE ADJUSTEDDUE TO SEASONAL CHANGES AND WEATHER CONDITIONS.
25. CONTRACTOR TO PERFORM IRRIGATION AUDIT AS PART OF FINAL IRRIGATION ACCEPTANCE AND PROVIDE ANIRRIGATION SCHEDULE FOR CITY STAFF USE. A CERTIFIED LANDSCAPE IRRIGATION AUDITOR IN GOOD STANDINGWITH THE IRRIGATION ASSOCIATION SHALL PERFORM THE AUDIT.
26. CONTRACTOR SHALL WARRANTY THE IRRIGATION EQUIPMENT AS REQUIRED BY CITY OF THORNTON STANDARDS ANDSPECIFICATIONS.
27. THE CONTRACTOR PROVIDE WRITTEN ON-SITE VERIFICATION OF CELLULAR MODEM STRENGTH AT THE NEWCONTROLLER LOCATION TO PRIOR TO ORDERING SPECIFIED CONTROLLER. SIGNAL STRENGTH SHALL BE ADEQUATEFOR SPECIFIED PEDESTAL-TOP ANTENNA.
1. AVAILABLE WATER PRESSURE: THE SITE IS LOCATED IN WATER PRESSURE ZONE '3A' PER THE CITY OF THORNTONCOLORADO WATER PRESSURE ZONE MAP, REVISED6/9/2009. WATER PRESSURE ZONE ' 3A' IS STATED TO HAVE HIGHHGL OF 5,494' AT 97 PSI.SEE 'POINT OF CONNECTION' NOTES FOR SPECIFIC PRESSURE CALCULATIONS ON EACH POINT OF CONNECTION
2. DESIGN PRESSURE: SEE POINT OF CONNECTION NOTES ABOVE FOR DESIGN PRESSURE CALCULATIONS.3. DESIGN CAPACITY (FLOW): SEE POINT OF CONNECTION NOTES FOR FLOW REQUIREMENTS.4. RAIN SENSOR: WEATHER SENSOR PER IRRIGATION SCHEDULE IS TO BE INSTALLED FOR EACH POINT OF
CONNECTION. COORDINATE FINAL SENSOR LOCATION WITH OWNER'S REPRESENTATIVE PRIOR TO INSTALLATION.5. WATER WINDOW: THIS IRRIGATION SYSTEM IS DESIGNED TO APPLY 1.5" OF WATER WITHIN A MAXIMUM OF 48
HOURS OF RUN-TIME PER WEEK (10 PM - 5 AM).6. WINTERIZATION: IRRIGATION SYSTEM SHALL BE WINTERIZED BY THE MEANS OF FORCED AIR BY OCTOBER 31st
EACH YEAR.7. FIELD INSPECTION: A FIELD INSPECTION SHALL OCCUR AND AS-BUILT PLANS SHALL BE SUBMITTED TO THE CITY
PRIOR TO CITY OF THORNTON INITIAL ACCEPTANCE.
CITY OF THORNTON REQUIRED NOTES
NOTES
(2)Carson 1220-15-3L Jumbo Valve Box1-1/2" Watts Brass Gate Valve (WGV-X)
I103-2
I103-1/2
I103-1/2
I103-3
I103-4
I103-5
I103-6
I104-1
I104-1
I104-3
I104-6
I104-5
I104-2
I104-7
5 gpm min. flow.
OWNER:
DATE:
SHEET TITLE:
2/13/2015 - CD-01
TRUELIFE COMPANIES
5251 DTC PARKWAY
SUITE 1175
GREENWOOD VILLAGE
COLORADO
80111
8/6/2015 - CD-02
Know what's
R
10/22/2015 - CD-03
1/21/2016 - CD-04
4/07/2016 - CD-05
NOTES &SCHEDULE
I100
OWNER:
DATE:
SHEET TITLE:
2/13/2015 - CD-01
TRUELIFE COMPANIES
5251 DTC PARKWAY
SUITE 1175
GREENWOOD VILLAGE
COLORADO
80111
8/6/2015 - CD-02
Know what's
R
10/22/2015 - CD-03
1/21/2016 - CD-04
4/07/2016 - CD-05
IRRIGATIONCALCULATIONS
I101
VALVE OPERATING SCHEDULE
PRESSURE LOSS CALCULATIONS - WORST CASE ZONE
4''W
4''W
4''W
4''W
4''W
4''W
4''W
4''W
4''W
G
E. 144TH AVEQ
G
T E. 144TH AVE
FAIR
FAX
AVEN
UE
SSC
Q
M
4''W
4''W
4''W
4''W
4''W
4''W
4''W
4''W
4''W
4''W
G
G
E. 144TH AVE
Q
4''W
4
'
'
W
G
G
T
W
W
W
E
E. 144TH AVEHO
LLY
STRE
ET
SYMBOL
IRRIGATIONPOINT OF
CONNECTION
BACKFLOWPREVENTER
CONTROLVALVE
GATE VALVE
PVC MAINLINE
SLEEVING
IRRIGATIONMETER
SENSOR
IRRIGATIONCONTROLLER
QUICKCOUPLER
SS
DESCRIPTION
MASTERVALVE / FLOW
SENSOR
SERVICE LINE
C
DETAIL
Q
SHRUB SPRAY8' - 10'
IRRIGATION SCHEDULE
XX"# - XX
VALVE CALLOUTS
Zone Designation:S (Shrub Spray)
Valve/Station Number
Valve Flow: (GPM)Valve Size
PVC SPRAYLATERAL
POC
M
I103-2/3
I103-1/2
I103-1/2
I103-4
I103-5
I104-3
I104-6I104-5
I104-2
I104-7
I103-6
I104-1I104-1
OWNER:
DATE:
SHEET TITLE:
2/13/2015 - CD-01
TRUELIFE COMPANIES
5251 DTC PARKWAY
SUITE 1175
GREENWOOD VILLAGE
COLORADO
80111
8/6/2015 - CD-02
Know what's
R
10/22/2015 - CD-03
1/21/2016 - CD-04
4/07/2016 - CD-05
IRRIGATIONPLAN
I102
KEY MAP
I102A I102B I102C I102D144TH AVE
HO
LLY
S
T
P
A
R
K
W
A
Y
F
A
I
R
F
A
X
MATC
HLIN
E - S
EE S
ECTI
ON B
MATC
HLIN
E - S
EE S
ECTI
ON C
MATC
HLIN
E - S
EE S
ECTI
ON D
MATC
HLIN
E - S
EE S
ECTI
ON A
MATC
HLIN
E - S
EE S
ECTI
ON B
MATC
HLIN
E - S
EE S
ECTI
ON C
MEDIAN SECTION A
MEDIAN SECTION B
MEDIAN SECTION C
MEDIAN SECTION D
POC
POC ELEVATION:5,270'
IRRIGATION VALVES AND MAINLINE ARE SHOWN FORGRAPHIC CLARITY ON THIS PLAN. VALVES SHALL BE
LOCATED IN PLANTING AREAS. MAINLINE ANDSLEEVES SHALL BE LOCATED UNDER THE MEDIANWITHIN THE CURBS. COORDINATE LOCATION WITH
CIVIL UTILITY PLANS AND OWNER'S REPRESENTATIVEPRIOR TO CURB AND PAVING INSTALLATION.
34.52"1 - S
17.61.5"2 - S
17.61.5"3 - S
21.01.0"4 - S
IRRIGATION TAP AND CONNECTION TO METER ARESHOWN FOR REFERENCE. COORDINATE LOCATION OF
CONNECTION, CURB STOP AND METER WITH CIVILUTILITY PLANS AND OWNER'S REPRESENTATIVE PRIOR
TO CURB AND PAVING INSTALLATION.
REFER TO THE CIVIL CONSTRUCTION PLANS FOR THEMEDIAN HARDSCAPE DESIGN INCLUDING MEDIAN LIMITS,MEDIAN COVER, MEDIAN NOSES, AND MEDIAN TRENCH.
21.01.0"5 - T
24.71.0"6 - S
IRRIGATION IRRIGATION EQUIPMENT INCLUDINGBACKFLOW PREVENTER, CONTROLLER PEDESTAL AND
RAIN SENSOR LOCATIONS ARE SHOWN FORREFERENCE. COORDINATE LOCATION OF AVAILABLE
POWER CONNECTION AND SENSOR PLACEMENT WITHELECTRICAL SERVICE PLANS AND OWNER'SREPRESENTATIVE PRIOR TO INSTALLATION.
IRRIGATION MAINLINE AND TURF LATERALS TO BEINSTALLED ADJACENT TO CURBING. MAINLINE IS
SHOWN FOR GRAPHIC CLARITY. SEE SHEET I104 DETAIL1 AND COORDINATE WITH OWNER'S REPRESENTATIVE
PRIOR TO LANDSCAPE INSTALLATION.
RAINBIRD WR2 WIRELESS RAIN SENSOR (POLE MOUNTED)SCALE: NTS
1-1/2" x 1-1/2" F x F SCH. 40 GALV.TEE WITH 1-1/2" PLUG.WIRELESS RAIN SENSOR, LOCATEWITHIN 700' OF THECONTROLLER.1-1/2" DIAMETER SCH. 40GALVANIZED STEEL POST.12" DIA. CONCRETE BASE-FORMWITH SONA-TUBE OR EQ. POSTSHALL BE CENTERED WITHINBASE.
NOTE:1. INSTALL WR-2 NO GREATER THAN 700' FROM THE RECEIVER.2. INSTALL PER MANUFACTURER'S SPECIFICATIONS.3. SLOPE TOP OF FOOTER AWAY FROM POLE.4. FINAL LOCATION AND MOUNTING SYSTEM TO BE APPROVED BY OWNER.
R
2
36"MIN.
12"MIN.
12" DIA.
1
2
3
410'
MIN.
CONTROLLER PER SCHEDULE
METAL PEDESTAL MOUNTENCLOSURE PER SCHEDULE1" ELECTRICAL SUPPLY CONDUIT:SIZE, TYPE, DEPTH PER LOCALCODEGROUND WIRE CONDUIT MIN.1-1/2". GROUND PER ASICGUIDELINES.6" THICK CONCRETE BASE WITHSLEEVES FOR CONDUIT.ELECTRICAL METER ANDIRRIGATION CONTROLLER SHALLBE BE ON SAME CONCRETE PAD
FINISH GRADE
CONDUIT FOR DIRECT BURRYCONTROL WIRES. EXTEND 5'FROM CONTROLLER
8
ELECTRICAL METER (PROVIDEDBY OTHERS)NOTE:
1. ALL ELECTRICAL AND CONTROLLER WIRE TO BE INSTALLED PER LOCAL CODE ANDMANUFACTURER'S SPECIFICATIONS.
2. PROVIDE LOCK AND KEY FOR ENCLOSURE.3. GROUND CONTROLLER PER LOCAL CODE, MANUFACTURER AND ASIC SPECIFICATIONS.4. PROVIDE WATERPROOF SEALANT FOR ALL CONDUIT AND WIRE ACCESS POINTS.
1
2
3
4
5
6
7
PEDESTAL CONTROLLER INSTALLATIONSCALE: NTS
8
12"MIN
4"MIN
PAVING
WRAP 12 GAUGE GALVANIZEDWIRE AROUND EACH END OFSLEEVE (10 WRAPS MIN.) ANDEXTEND TO SURFACE AS ALOCATING DEVICE.
FINISH GRADE / TOP OF DG.
COMPACT SOIL AROUND SLEEVETO SAME DENSITY AS ADJACENTUNDISTURBED SOIL.WASHED AND GRADED MORTARSAND BACKFILL IN ROCKY SOILCONDITIONS.PVC SLEEVE PER SCHEDULE.TWICE DIAMETER OF THE SUM OFTHE PIPES/ WIRESEXTEND SLEEVES 12" BEYONDEDGES OF PAVING
IRRIGATION SLEEVESCALE: NTS
NOTE:1. ALL SLEEVES SHALL BE INSPECTED PRIOR TO BACKFILLING.2. CAP SLEEVES UNTIL USE.3. MULTIPLE SLEEVES REQUIRE 4" HORIZONTAL SEPARATION WITHIN SAME SLEEVE TRENCH.4. IRRIGATION PIPE AND WIRE SHALL NOT SHARE THE SAME SLEEVE.5. MARK / STAMP - 'X' AND/OR INSTALL PLACARD AT BACK OF CURB.
12" MIN.
18" MIN. DEPTH24" MIN. DEPTHFOR MAINLINE
5
6
7
IRRIGATIONDETAILS
I103
TOP VIEW PAD
1.
4. BACKFLOW PREVENTER. PADLOCK PROTECTIVE COVER.
7.
8.
6.
ANCHOR BASE MOUNT.2.
3.
SIDE VIEW
4"
4"
ENCLOSURE LOCKING SWING DOOR (DOOR MOUNTEDTO ANCHOR BASE)
NOTES:1. SMOOTH TOUCH ANCHOR BASE.2. MOUNTING BASE SECURED IN CONCRETE WITH 3
8" J BOLTS (4 PLACES).3. EXISTING CONCRETE CORNERS WILL NEED TO 3
8"x 3" REDHEAD ANCHORS.
ENCLOSURE SWIVEL POINT ATTACHED TO MOUNTING BASE.ENCLOSURE SECURED TO BASE ( 6 PLACES )
PADLOCK.5.
LEGENDSTRONGBOX SMOOTH TOUCH BACKFLOW CAGE ASSPECIFIED PER SIZE.
POURED CONCRETE BASE, 6" MINIMUM THICKNESS. EXTEND4" BEYOND OUTSIDE DIMENSIONS OF ENCLOSURE.
BACKFLOW ENCLOSURE - STRONGBOX SMOOTH TOUCH
SCALE: NTS
OWNER:
DATE:
SHEET TITLE:
INSERT TEXT AT
0.18" HGT, CENTERED
0.25", CENTERED
TYPE DDATTE FOR
EDITING,
NEVER EXPLODE BLOCK
REMOVE FROM XREF AND INSERT FIELDS
INTO EACH SHEET INDIVIDUALLY. UPDATE
FIELD AND VERIFY THAT ALL SHEETS ARE
NAMED CORRECTLY IN THE SHEET SET
MANAGER.
2/13/2015 - CD-01
TRUELIFE COMPANIES
5251 DTC PARKWAY
SUITE 1175
GREENWOOD VILLAGE
COLORADO
80111
8/6/2015 - CD-02
10/22/2015 - CD-03
1/21/2016 - CD-04
4/07/2016 - CD-05
IRRIGATION METER SETTING VAULT
COT STANDARDIRRIGATION BACKFLOW PREVENTER AND CONNECTION SCHEMATIC
COT STANDARD
3/4" COPPER
WINTERIZATION PIPE
UNION
UNION
SENTRY CABLE GUARD
PUMP (WHEN REQUIRED)
3/4" MALE
ADAPTER
HOSE BIBB
VACUUM BREAKER
3/4"FHT X 3/4" MHT
3/4" MPT X 1/2"
FPT ADAPTER
3/4" BRASS
MPT x MHT
BOILER DRAIN
3/4" COPPER
DIG 18-028
1/2" AIR VACUUM
RELIEF VALVE
3/4" FPT X 3/4" FPT X 3/4" FPT
BRASS T
3/4" CRUSHED GRANITE
CLASS 200 6" ACCESS SLEEVE.
CARSON 910 10" ROUND VALVE BOX
WATER
METER
SIDEWALK
6" THICK CONCRETE
PAD LENGTH AS REQUIRED
SLEEVE ALL PIPING IN CONCRETE PAD
MIN. SIZE TWO TIMES DIAMETER OF PIPE
CURB
NOTE:
CONCRETE PAD PENETRATION TO BE 1" LARGER THAN SLEEVING DIAMETER.
REFER TO ENCLOSURE INSTRUCTIONS FOR CONCRETE PAD DIMENSIONS.
ALL VALVES AND FITTINGS INCLUDING RPZ SHALL MATCH SIZE OF THE SERVICE LINE FROM METER. SEE
TABLE 800-1&2 IN THESE STANDARDS AND SPECIFICATIONS FOR MORE INFORMATION.
SEE DETAIL 800-9 FOR SPECIFIC METER SETTING REQUIREMENTS.
SEE SECTION 800 OF THE WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS OF
COMPONENTS.
EXTEND CRUSHED GRAVEL SUMP 6" BEYOND THE PERIMETER OF EACH ACCESS BOX FOR SUPPORT AND
DRAINAGE.
EXTEND TO MINIMUM 4" TAP
WITH DIP OR C900 PIPE
CAST IRON GATE VALVE
SEE COT DETAIL:
#200-6A/B 4" MINIMUM
SERVICE LINE
FROM WATER METER
REDUCED PRESSURE BACKFLOW
PREVENTER - FEBCO 825YA (2" AND BELOW)
BACKFLOW BLOWOUT
WITH 3/4" MALE
THREAD CAP
BACKFLOW ENCLOSURE -
STRONGBOX SMOOTH TOUCH
BUCKNER QB44LRCAR10
QUICK COUPLER VALVE
MASTER VALVE -TORO 220
LINE SIZE, WITH UNIONS
FLOW SENSOR
DATA INDUSTRIAL
DRAIN VALVE - LINE SIZE
CRUSHED GRAVEL SUMP
RAINBIRD PUMP
BOOSTER PUMP DETAIL:
WHEN REQUIRED
TYPE "K" CLASS 200
PVC PIPE HARD
COPPER
12"
MASTER VALVE
QUICK COUPLER
BACKFLOW PREVENTER
ELECTRICAL
PANEL
CONTROLLER
RIGHT OF WAY
PLANTING BED
METER
CURB STOP
SIDEWALK
TURF AREA
PLANT
SCREENING
TO CONCEAL
EQUIPMENT
FLOW SENSOR
GATE VALVE (TYP)
PUMP BYPASS
10" LOCKING ROUND BOX &COVER PER SCHEDULE. TOP OFBOX TO BE FLUSH WITH FINISHGRADE.
2" VALVE MARKER
2" CL160 PVC ACCESS SLEEVELENGTH AS REQUIRED.
3" DEPTH 3/4" CRUSHED GRAVEL6" BEYOND EDGE OF BOX
PVC PRESSURE MAIN LINE
SCH. 80 TEE PER MAINLINE SIZE.ALIGN IN A DOWNWARD POSITIONSCH. 80 PVC NIPPLE
FINISH GRADE
1" BRONZE STOP VALVE WITHSLOTTED KEY OPERATOR
SCH. 80 PVC ELL
SCH. 80 PVC NIPPLE
3/4" GRAVEL SUMP - 1 CU. FT. MIN
SOIL BLANKET ENCLOSING SUMPAMOCO ENG. FABRIC 4545 - 4.5OZ. OR EQUAL
4
3
2
1
MANUAL DRAIN VALVESCALE: NTS
NOTE:1. ALL THREADED CONNECTIONS SHALL BE COATED WITH TEFLON TAPE.2. LOCATE DRAIN VALVE AT POINT OF CONNECTION AND AT ALL LOW POINT(S) ALONG THE
IRRIGATION MAINLINE AS NEEDED.
5
6
7
8
9
10
11
12
13
6" ROUND BOX & COVER PERSCHEDULE. TOP OF BOX TOFLUSH WITH FINISH GRADE
FINISH GRADE
QUICK COUPLING VALVE W/LOCKING COVER PER SCHEDULE
SCH. 80 NIPPLE
3" DEPTH 3/4" GRAVEL BASEEXTEND 6" BEYOND EDGE OF BOX
1" PVC SWING JOINT
PVC MAINLINE
24" #4 REBAR TO HOLD COUPLERIN PLACE W/ (2) STAINLESS STEELCLAMPS
QUICK COUPLERSCALE: NTS
NOTE:1. EACH QUICK COUPLER SHALL BE IN A SEPARATE VALVE BOX2. PROVIDE (1) QUICK COUPLER KEY FOR EACH QUICK COUPLER VALVE.3. QUICK COUPLER SHALL HAVE YELLOW LOCKING RUBBER COVER4. COMPACT SOIL AROUND GATE VALVE ASSEMBLY TO THE SAME DENSITY AS ADJACENT
UNDISTURBED SUBGRADE.5. ALL THREADED CONNECTIONS SHALL BE COATED WITH TEFLON TAPE.
1
7
2
8
3
4
5
6
PLASTIC LOCKING VALVE BOXPER SCHEDULE. TOP OF BOX TOBE FLUSH WITH FINISH GRADE
MASTER VALVE PER SCHEDULE
CONTROLLER
WIRE HARNESS PERMANUFACTURER SPECIFICATIONWATERPROOF ELECTRICALCONNECTIONS. PERMANUFACTURER SPECIFICATION
FINISH GRADE
FLOW METER PER SCHEDULE
SCH. 80 UNION (TYP)
3/4" GRAVEL SUMP 8" DEPTH
BRICK SUPPORTS 2 MIN.
3
MASTER VALVE / FLOW SENSOR INSTALLATIONSCALE: NTS
ORANGEBLACK
BLUEWHITE
NOTE:1. INSTALL ICD SENSOR AND ICD DECODERS PER HUNTER'S SPECIFICATIONS FOR
WIRING AND GROUNDING. REFER TO DETAIL X OF THIS SHEET
MINIMUM UPSTREAMDISTANCE 10x
FLOW METER SIZE
MINIMUM DOWNSTREAMDISTANCE 5x
FLOW METER SIZE
1
2 4
5
6
7
8
9
10
MEDIAN IRRIGATION LINESSCALE: NTS
CONCRETE CURB
MARKER TAPE
PVC TURF LATERAL
PVC MAINLINE
VALVE CONTROL WIRE18"
12"
6" MAXIMUM CLEAR FROM BOC
2
3
1
4
MEDIAN WIDTH VARIES
8"
PLAN
4
SECTION
NOTE:1. ALL MAINLINES TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURER' SPECIFICATIONS.2. ALL PVC PIPING TO BE SNAKED IN TRENCHES FOR EXPANSION AS SHOWN IN PLAN VIEW ABOVE.3. ALL 120 VOLT WIRING IN CONDUIT TO BE INSTALLED AS PER LOCAL CODES.4. ALL ELECTRICAL WIRE CONNECTIONS TO VALVES AND SPLICES TO BE INSTALLED WITHIN A VALVE BOX AND MADE WITH DBY
WATERPROOF CONNECTORS, OR APPROVED EQUAL.5. BUNDLE AND TAPE WIRING AT 10' INTERVALS6. VALVE WIRES TO BE INSTALLED WITHIN MAINLINE TRENCH WHEREVER POSSIBLE.7. BEDDING MATERIAL SHALL BE 1/4” MINUS SAND, AND SHALL BE 3” BELOW LOWEST PIPE OR WIRE AND 3” ABOVE HIGHEST PIPE OR
WEIR WITHIN TRENCH.8. BEDDING MATERIAL SHALL BE IN MAINLINE TRENCH ONLY.9. EXCAVATED COVER MATERIAL SHALL BE FREE FROM DEBRIS AND ROCKS 1/2” OR GREATER.10. PIPE BEDDING MATERIAL TO BE ROCK AND DEBRIS FREE, BACKFILL IN 6” LIFTS, PUDDLE WITH WATER, BETWEEN LIFTS.
5
LOCKING ROUND BOX & COVERPER SCHEDULE. TOP OF BOX TOBE FLUSH WITH FINISH GRADE
FINISH GRADE
2" CL160 PVC ACCESS SLEEVELENGTH AS REQUIRED.
GATE VALVE W/ CROSS HANDLEAND SOLID WEDGE DISC PERSCHEDULE3/4" GRAVEL SUMP FILL IN ANDAROUND BOX AS REQUIRED.
3" DEPTH 3/4: GRAVEL EXTEND 6"BEYOND EDGE OF BOX
PVC MAINLINE AS PER PLAN
4
3
2
1
NOTE:1. COMPACT SOIL AROUND GATE VALVE ASSEMBLY TO THE SAME DENSITY AS ADJACENT
UNDISTURBED SUBGRADE.2. DO NOT REST VALVE BOX OR ACCESS SLEEVES ON MAINLINE OR LATERAL LINE.3. PROVIDE GATE VALVE KEY - LENGTH AS REQUIRED.
6
7
C
L
4" M
IN.
2" MIN.
SEE
TREN
CHIN
G DE
TAIL
FOR
PIPE
DEP
TH
GATE VALVE 3" & SMALLERSCALE: NTS
5
FINISH GRADE
POP-UP SPRAY SPRINKLER PERSCHEDULE
FLEXIBLE SWING JOINT - 18" MAX
PVC LATERAL PIPE
PVC SCH. 40 TEE OR ELL,THREADED
EDGE OF PAVING OR HEADER
POP-UP SPRAY ASSEMBLYSCALE: NTS
5
1
2
3
4
NOTE:1. AFTER FLUSHING HEADS, REGRADE AND COMPACT AS NEEDED TO RETURN TO FINISH GRADE
CONDITION.2. SPRINKLERS SHALL BE MIN. 6" FROM ANY WALLS, WALKS, COURTS, AND12" FROM TURF EDGE.3. ADJUST ALL SPRINKLERS HEADS SO THAT NO OVERSPRAY OCCURS ON ANY WALLS, WALKS,
COURTS, ETC.4. ALL THREADED CONNECTIONS SHALL BE COATED WITH TEFLON TAPE.5. COMPACT SOIL AROUND HEAD TO THE SAME DENSITY AS ADJACENT UNDISTURBED
SUBGRADE.
6"MIN.
6
OWNER:
DATE:
SHEET TITLE:
INSERT TEXT AT
0.18" HGT, CENTERED
0.25", CENTERED
TYPE DDATTE FOR
EDITING,
NEVER EXPLODE BLOCK
REMOVE FROM XREF AND INSERT FIELDS
INTO EACH SHEET INDIVIDUALLY. UPDATE
FIELD AND VERIFY THAT ALL SHEETS ARE
NAMED CORRECTLY IN THE SHEET SET
MANAGER.
2/13/2015 - CD-01
TRUELIFE COMPANIES
5251 DTC PARKWAY
SUITE 1175
GREENWOOD VILLAGE
COLORADO
80111
8/6/2015 - CD-02
10/22/2015 - CD-03
1/21/2016 - CD-04
4/07/2016 - CD-05
IRRIGATIONDETAILS
I104
AUTOMATIC CONTROL VALVE
COT STANDARD