Comfort Circle CASSETTE UNIT

CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

Embed Size (px)

Citation preview

Page 1: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircle

CASSETTEUNIT

Page 2: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCirclecassetteunit

All-roundcomfortWithtoday'senergyprices,buildingownersareincreasinglyawareoftheneedforanefficientclimatesystemtoheatorcool

commercialofficesandretailareas.Acomfortableindoorclimatecreatesapleasantworkingenvironmentforemployees,and

clientswillnaturallybeinclinedtostayforlonger.Forenergyefficientheatingandcoolinginshops,supermarketsandoffices,the

space-savingBiddlecassetteunitistheperfectcandidate.

OptimalindoorclimateTheComfortCircleallowsyoutoheatorcooltheindoorspaceexactlyasyouwish,inashortperiodoftime.Formaximum

comfort,thecircularairdischargepatternensuresanevendistributionofairthroughouttheroom.Heatingandcoolingcanbedone

separately,orcombinedwithinoneunit.Usingacombinedunithastheadvantageofreducingthenumberofinstalledunits

required.

Space-savingandunobtrusiveClimateequipmentshouldpreferablytakeupaslittlespaceaspossibleinyourbuilding.WiththecompactComfortCircle,floorand

wallsurfacesremainavailableforshelves,racksandotherfurniture.Thecassetteunitisarecessedceilingmodelandtherefore

meetsthisrequirement.Theunitcanquicklyandeasilybeinstalledinasuspendedceilingsystem;onlythestylishcircularair

dischargegrilleisvisible.

Page 3: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCirclecassetteunit

Waterheatingcoil

Energy-savingandefficientTheComfortCirclehasbeendesignedforusewithawaterbasedheatingandcoolingsystem.

Nowadays,increasingemphasisisbeingplacedonenergy-efficientandsustainableclimate

units,whichincorporatelowwatertemperatureranges.Thiscanbeachieved,forinstance,by

utilisingthewasteheatofacoolingunitorheatpump.TheComfortCircleiscompatibleforuse

withthiskindofsystem.Itisalsopossibletodeployacoolingunitforheating;theso-called

changeoversystem.Foroptimumcoordinationbetweenthecassetteunitandtheheatandcold

sources,anoptionalchangeoversensorcanbefitted.

CompleteclimateconceptsTheunobtrusiveappearanceandlownoiseemissionmaketheunitideallysuitedforusein

shops,offices,showrooms,receptionareas,museums,banksandlibraries.Togetherwiththe

automaticSensAiraircurtain,theComfortCircleformsacompleteclimatesolution(forrooms

withamaximumheightof4metres).Forventilation,theComfortCircle(ventilationmodel)can

alsobeusedincombinationwiththeHR(heatrecovery)unit.

BenefitsOptimalindoorclimate-Outstandingclimatecontrol

-Evenairandtemperaturedistribution

-Heatingand/orcoolinginoneunit

Space-savingandunobtrusive-Integratedinsuspendedceilingsystem

-Stylishairdischargegrille

-Compactandlow-noise

Energy-savingandefficient-Suitableforlowerwatertemperatures

-Optiontoutilizeresidualwasteheat

-User-friendlyandlowmaintenance

Andevenmore....-Severalcontroloptions

-User-friendlyandlowmaintenance

Page 4: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCirclecontrol

AcontroloptionforeverysituationThecassetteunitisperfectlysuitedforlargerspacessuchasshopsandofficeswithasuspendedceiling.Theingenious360°air

dischargepatternensuresanevenlydistributedtemperatureandairflowthroughtheentireroom,deliveringmaximumcomfort

withaverylowenergyconsumption.

Moreover,incommercialofficesandretailareasquickandeasyadjustmentoftheclimateisessential,withoutanydifficultiesforthe

users.Therefore,Biddle’sComfortCirclecomeswithuptofourdifferentcontroloptionsforanoptimal,user-friendlysolutionfor

everysituation.Theclientcansetthedesiredroomtemperatureviathecontrolpanel,quicklyandeasilybringingtheindoorclimate

tothemostcomfortablelevel.

Fourcontroloptions1. Basicunitwithoutcontroller(B0)

Thecassetteunitisequippedwithatransformerandiswiredbydefaultatonefixedsetting.

2. Fanspeedcontroller(T0)Thecassetteunitisfittedwithafanspeedcontrollerthatiscompatiblewithexternalcontrolsystems,suchasabuilding

managementsystem.Thefanspeedisthencontrolledexternally(0-10Voltsorzero-voltage)

3. Thermostaticair-sideBiddlecontrol(S0/S1)Thisplug&playcontrolregulatesthefanspeed(threespeeds)toobtainthedesiredroomtemperature.Thecontrolcanbe

deliveredwithafixed(S0)oranauto-adjustabledischargeangle(S1).

4.Modulatingairandwater-sideBiddlecontrol(M0/M1)Themostcomprehensiveplug&playcontrolforthecassetteunitregulatesboththefanspeedandthedischargeair

temperature,toachievepreciselythedesiredtemperature.Thiscontrolcanbedeliveredwithafixed(M0)oranauto-adjustable

dischargeangle(M1).

Page 5: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCirclecontrol

Welldesignedanduser-friendlyBothBiddlecontrols(thermostaticandmodulating)arecontrolledbyawelldesignedanduser-friendlycontrolpanel.

Thecontrolpanelhasvarioussoft-touchkeysandahandyLCDdisplay.Thedesiredroom

temperatureiseasilysetviathecontrolpanel,afterwhichtimethecontrolmaintainstheclimate

atthecorrectlevel.Thekeyscanbelockedwitha'keylock'.

Onecontrolpanelcanbeconnectedtoandoperateamaximumoftenunits.Theunitsarethen

linkedtogether.Themaximumlengthofthecontrolcablesinacontrolsystemis100metres.

Thecontrolpanelhasvariousmenusforseveralsettings,suchasuse,installation,serviceand

settingtheweektimer.

AutomaticormanualoperationThecontrolpanelallowstheusertochoosebetweenautomaticormanualoperationofthecassetteunit.Intheautomatic

mode,thecorrectfanspeedissetonthebasisofthetemperaturedifferencebetweentheactualroomtemperatureandthe

desiredroomtemperature.

AutomaticonandoffcontrolThecontrolpanelfeaturesaweektimerforswitchingtheunitonandoffautomatically,eachdayoftheweek.

MaximumconvenienceIfyouchooseoneofthetwointegratedBiddlecontrols,theunitswillbedeliveredcompletelyreadytouse:plug&play.For

connectiontothemains,theunitsareequippedwithafixedcableandamouldedplug.Thecontrolpanel,anyextraunitsandin

andoutputscanbeconnectedviatheconnectorplateandconnections.

ProjectspecificmodificationsTheComfortCirclecomeswiththreefixedtappingvoltages(fansspeeds)asfactorydefault.Byusingabuilt-intransformeritis

possibletoadjustthestandardspeedstothespecificsituation.

Benefits-Fourcontroloptions

-User-friendlycontrolpanel

-Automaticormanualoperation

-Plug&Play

-Projectspecific

Page 6: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircletechnology

CircularairdischargetechnologyThebottomofthecassetteunitconsistsofapanelwithacircularairdischargegrille.Withrecirculationunits,theairintakeand

dischargetakeplaceviathesamegrillepanel.Theairisdrawninthroughtheperforatedpatterninthemiddleofthepanel.After

theairhasbeenheatedorcooled,itisblownevenlyintotheroomacross360°viatheairdischargeopeningsonthesideofthe

grille.Thecircularairdischargepatterngeneratesanoptimalandevenairdistribution,whichensuresoptimalpenetrationandair

circulationevenatlowairspeeds.

Warmairisdischargedatafixed45°angletowardsthefloor,toachievegooddownwardpenetrationoftheairintotheroom

(fig.1).Whencooling,coldairisdischargedhorizontallyalongtheceilingtocreateanoptimaldraughtfreeclimate.ThisCoanda

effect(fig.2)givesabetterdistributionofthecooledairthroughouttheroom.

Fig.1:Heating

Fig.2:Cooling

Auto-adjustableringTheairdischargegrilleofunitsthatcanbothheatandcoolis

fittedwithapatentedadjustabledischargering.Theunit

adjuststheringautomaticallyandindoingsoselectstheair

dischargeanglethatbestfitstheparticularheating(fig.1)or

cooling(fig.2).Consequently,thedownwardpenetration

anddistributionoftheairarealwaysguaranteed.

FixedsettingairdischargeangleUnitsthateitherheatorcoolonlyhaveafixedsettingforthe

dischargeangleanddonothaveanadjustablering.

Page 7: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCirclepossibilities

Asolutionforeverysituation

TheComfortCircleissuitableforrecirculationandcaneither

heat,cool,ordoboth.Thecircularairdischargepattern

generatesanevenairdistributionthroughouttheroom.Airis

extractedfromtheroomviathesmallopeningsatthebottom

oftheunit.Aftertheairhasbeenheatedorcooled,itis

blownintotheroomat360°viatheairdischargeopenings

onthesideofthegrille.

TypecodeCC60-H1C2-M1

CC = ComfortCircleModelsize60 = 60x60recirculation90 = 90x90recirculationCoiltypeH2 = Hotwaterheating,2-rowH3 = Hotwaterheating,3-rowC2 = Cooling2-roworchange-overC3 = Cooling3-roworchange-overH1C2 = Heating1-row,cooling2-rowControlB0 = Basicunit,excl.control,incl.trafoT0 = FanspeedcontrollerS0 = Thermostaticairsidecontrol,excl.valveS1 = Thermostaticairsidecontrolwithautomatic

angleadjustment,excl.valveM0 = Modulatingairandwatersidecontrol,incl.valveM1 = Modulatingairandwatersidecontrolwith

automaticangleadjustment,incl.valve

SelectionTheComfortCircleisavailableintwomodels:

CC60:max.airflowis740m /h,suitableforheating

roomsof100m

CC90:max.airflowis1630m /h,suitableforheating

roomsofmax.200m

Specificcriteriaapplytocooling.Thisrequiresacoolingload

calculation.

Thecassetteunitissuitableforamaximuminstallationheight

of4m.

OptionsRecessedceilingmodel

Ventilationmodel

Freehangingmodelavailable

Waterheating

Recirculation:heatingand/orcooling

ControloptionsBasicunitwithoutcontrol(B0)

Speedcontrollercompatiblewithexternalcontrols(T0)

Thermostaticair-sidecontrol(S0/S1)

Modulatingairandwater-sidecontrol(M0/M1)

StandardcoloursRAL9016

OtherRALcoloursareavailableonrequest

VentilationmodelThecassetteunitisavailableasaventilationmodel,butonly

incombinationwithheatrecovery,modelHR.Information

abouttheventilationmodelisavailableonrequest.

Heatrecovery,ModelHR

3

2

3

2

Page 8: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircledelivery&accessories

Delivery&accessoriesVariouscontrolandassemblyaccessoriesareavailablefortheComfortCircle.

Usinganadaptorplate,the

CC90issuitablefor

mountinginasuspended

ceiling.

StandarddeliveryTwosuspensionbrackets

Twocoveringstripstoadjusttheairdischargepattern

Externalcondensationdrainpump(forcooling)

Externalcondensationtray(forcooling)

Oneortwowater-sidevalves,fittedwithactuators(onlywithmodulatingcontrol)

Control/operationIfoneofthetwoBiddlecontrols(S0/S1orM0/M1)isused,thesetwoaccessoriesarealways

required:

Controlpanel

Lowvoltagecables(variouslengths)

AccessoriesSuspensionset

Change-over-sensor

CC90adaptorplatetosuitceilingtile

SmartsuspensionsystemBiddlecassetteunitscanbeinstalledeitherbeforeorafterfittingasuspendedceiling.The

adjustablemountingsystemallowstheunittobemovedinanydirection.Thismeanstheunit

canbepositionedaccurately,withminimaleffort,andthereforeeasilyintegratedintotheceiling.

Page 9: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCirclespecifications

Specifications

ComfortCircle(ventilation

model)onlyincombination

withheatrecovery,modelHR

CasingThecasingismadefromzinc-platedsheetsteel,additionallyreinforcedtominimise

deformationsandvibrations.Theundersideoftheunithasarotatableplasticairinletand

dischargegrille.Thecasingisfittedwithsoundabsorbing,heatinsulatingmaterial.The

completeunitisdeliveredasstandardinthecolourRAL9016(white).OtherRALcoloursare

availableatanadditionalcharge.

Fan/motorassemblyTheradialbackwardcurvedfansaremountedinthecasingandcausenovibration.Thefanis

drivenbyanexternalrotormotoronballbearings.Thefancasingandtheimpelleraremade

fromaluminium.ThemotorismanufacturedinaccordancewithDIN40050,protectioncategory

IP44andinsulationcategoryB(CC60)andF(CC90).Themotorisprotectedfromoverheating

bythermalcontacts,whichwillbreaktheelectricalcircuitassoonasthemaximumpermissible

motortemperatureisexceeded(auto-reset).

Heating/Coolingcoil(LPHW/LPCW)Thecoilismanufacturedwith3/8"coppertubesandaluminiumfins.Thecoilsareavailablein

rowsof2or3.Theoperatingpressureismax.8baratmax.90°C.Thediameterofthepipe

workconnectionsforcoiltypeH1isDN15(15mm).ForcoiltypesH2,H3,C2andC3thisis

DN20(22mm).

ThemaximumwaterrangeofanH2coilwith:

Thermostaticair-sidecontrol(S0/S1)=80/60°C

Modulatingairandwater-sidecontrol(M0/M1)=90/70°C

ThemaximumwaterrangeofanH3coilwith:

Thermostaticair-sidecontrol(S0/S1)=70/50°C

Modulatingairandwater-sidecontrol(M0/M1)=90/70°C

Themaximumpermissibleoperatingpressureis8baratawaterinlettemperatureofmax.

90°C.Themaximumpermissibledischargeairtemperatureis65°C.Ifaunithastobe

connectedtoawaterrangewithhighertemperatures,pleaseconsultBiddleforadvice.

Page 10: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircleexplanationoftechnicaldata

ExplanationoftechnicaldataWaterflowrateWhenwaterandroomtemperaturesotherthanthevaluesrepresentedinthetablesareused,thewaterflowratecanberoughly

calculatedusingtheformulabelow.Beforedoingso,theheatingortotalcoolingcapacitymustberecalculatedbasedonthetables

withcorrectionfactors.

m =waterflowrate[l/h]

Q=capacity[kW]

C =specificheatofwater(=4.18)[kJ/kg°C]

ΔT =temperaturedifferencewater[°C]

ρ =densityofwaterat90°C(=0.984)[kg/l]

w

pw

w

w

WaterpressuredropWhenwatertemperaturesotherthanthevaluesrepresentedinthetablesareused,thewaterpressuredropcanbecalculated

usingthisformula.Todoso,thewaterflowratemustfirstbecalculated(seeabove).

Δp =waterpressureloss,tablevalues[kPa]

Δp =waterpressureloss[kPa]

m =waterflowrate,tablevalues[l/h]

m =waterflowratecalculatedusingformula[l/h]

w1

w2

w1

w2

SoundreferenceroomInthetables,asoundpressurelevelinthereverberationsoundfieldisgivenforallspeeds.Thesesoundpressurelevelvaluesare

basedontheuseofoneunitinareferenceroom.Thesoundpressureintheroomisdetermineddependentontheinstallation

andthespeedofthefan.Thesounddataareapplicabletoeachunitandmeasuredatadistanceof5mfromtheunit.

referenceroomunit volumeroom reverberationtimeCC60 300m 0,5sCC90 600m 0,6s

3

3

Page 11: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircleexplanationoftechnicaldata

SoundinadeviatingroomandwithmultipleunitsIfaunitisusedinadeviatingroom,orifmultipledevicesareusedinasingleroom,thesoundpressurelevelmustberecalculated.

Thiscanbedoneusingtheformulabelow.Therelevanttablevaluecanbefoundinthetables(generaldata).

L =soundpressure[dB(A)]

T=reverberationtimeindeviatingroom[s]

T =reverberationtime[s](seetable)

V=volumedeviatingroom[m ]

V =volumereferenceroom[m ](seetable)

n=numberofunits

p

o

3

o3

Examplecalculation:whatisthesoundpressurelevelinthereverberationfieldwhentwoCC60unitsatspeed2areusedinaroomwithareverberationtimeof0.7secandavolumeof600m ?

SoundpowerlevelindB

CC60speed soundpowerlevel

soundpressurelevel peroctavebandinthemediumfrequency,indB(Hz) LwdB(A) 63 125 250 500 1000 2000 4000 8000 dB(A)

1 37,6 44,6 54,4 50,5 45,7 44,8 44,5 29,2 16,3 50,52 47,1 47,6 62,1 59,4 55,3 55 53,7 46,8 34 603 52,1 50,9 65,7 64,2 60 60,3 57,4 53,4 41,3 65

CC90speed soundpowerlevel

soundpressurelevel peroctavebandinthemediumfrequency,indB(Hz) LwdB(A) 63 125 250 500 1000 2000 4000 8000 dB(A)

1 37,9 62,5 58,6 55,1 50,6 46,9 39,6 29,8 17,1 52,52 49,9 56,5 68 65,3 61,1 60,5 55,7 48,5 38,3 64,53 56,9 60,8 72 71,1 67,8 67,1 64,3 57,1 48,5 71,5

3

Page 12: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCirclecorrectionfactors

CorrectionfactorsheatingcapacityTheheatingcapacitiesshowninthetablesforcoiltypesH1andH2arebasedonawaterrange

of80/60°C.TheheatingcapacityforcoiltypeH3isbasedonawaterrangeof60/40°C.In

bothcasesanairinlettemperatureof20°Cisassumed.Withdifferentwatertemperatures

and/orairinlettemperatures,theheatingcapacitymustbemultipliedbythecorrectionfactors

givenbelow.

CorrectionfactorsheatingcapacitycoiltypesH1andH2

CCH2/H1C2waterrange airinlettemperature

-10°C 0°C 10°C 15°C 18°C 20°C90/70°C 1,95 1,69 1,44 1,33 1,26 1,2182/71°C 1,87 1,61 1,37 1,25 1,18 1,1480/60°C 1,72 1,47 1,23 1,11 1,05 170/50°C 1,5 1,25 1,01 0,9 0,83 0,7960/40°C 1,27 1,03 0,8 0,68 0,62 0,5750/40°C 1,17 0,93 0,71 0,6 0,53 0,4950/30°C 1,04 0,8 0,58 0,46 0,39 0,35

CorrectionfactorsheatingcapacitycoiltypeH3

CCH3waterrange airinlettemperature

-10°C 0°C 10°C 15°C 18°C 20°C90/70°C 3,3 2,86 2,44 2,24 2,12 2,0582/71°C 3,13 2,7 2,29 2,09 1,97 1,980/60°C 2,92 2,5 2,09 1,89 1,78 1,770/50°C 2,55 2,13 1,73 1,54 1,43 1,3660/40°C 2,18 1,77 1,38 1,19 1,07 150/40°C 1,98 1,58 1,2 1,01 0,91 0,8450/30°C 1,8 1,4 1,01 0,82 0,7 0,62

Page 13: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCirclecorrectionfactors

CorrectionfactorscoolingcapacityThecoolingcapacitiesshowninthetablesforcoiltypesC2andC3arebasedonawaterrange

of6/12°Candairinletconditionsof27°C/48%R.H.Withdifferentwatertemperatures

and/orairinletconditions,thecoolingcapacitymustbemultipliedbythecorrectionfactorsgiven

below.Datarelatingtootherdeviatingrefrigerantsareavailableonrequest.

CorrectionfactorscoolingcapacitycoiltypesC2andC3

CCC2/C3waterrange airinletconditions relativehumidity

40% 48% 50% 60%Qt Qs Qt Qs Qt Qs Qt Qs

6/12°C 22°C 0,56 0,75 0,58 0,74 0,59 0,73 0,7 0,7 23°C 0,61 0,81 0,65 0,79 0,67 0,78 0,81 0,75 24°C 0,66 0,87 0,72 0,84 0,75 0,84 0,93 0,81 27°C 0,86 1,03 1 1 1,05 1 1,29 0,98 28°C 0,94 1,08 1,11 1,06 1,16 1,05 1,42 1,038/14°C 22°C 0,47 0,62 0,47 0,62 0,47 0,62 0,53 0,59 23°C 0,52 0,69 0,52 0,68 0,53 0,68 0,62 0,65 24°C 0,56 0,75 0,58 0,74 0,6 0,73 0,72 0,7 27°C 0,72 0,93 0,81 0,89 0,85 0,89 1,07 0,86 28°C 0,79 0,98 0,91 0,95 0,96 0,94 1,2 0,9210/16°C 22°C 0,37 0,5 0,37 0,5 0,37 0,5 0,38 0,49 23°C 0,42 0,56 0,42 0,56 0,42 0,56 0,45 0,54 24°C 0,47 0,63 0,47 0,63 0,47 0,63 0,53 0,59 27°C 0,61 0,81 0,65 0,79 0,67 0,78 0,84 0,75 28°C 0,66 0,87 0,73 0,84 0,76 0,84 0,97 0,812/18°C 22°C 0,28 0,37 0,28 0,37 0,28 0,37 0,28 0,37 23°C 0,33 0,43 0,33 0,43 0,33 0,43 0,33 0,43 24°C 0,37 0,5 0,37 0,5 0,37 0,5 0,38 0,49 27°C 0,52 0,69 0,52 0,69 0,53 0,68 0,63 0,64 28°C 0,56 0,75 0,58 0,74 0,6 0,73 0,74 0,7

Page 14: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircletechnicaldata

HeatingCC60Basicdata

CC60electricalsupply V/ph/Hz 230/1/50 max.inputcurrent A 0,7max.fanpower W 143tapping 1 2 3 4 5 6 7 8 9 10 11tappingvoltage V 60 70 80 90 100 115 130 155 170 190 230airvolume m³/h 120 150 190 230 270 350 430 550 620 680 740soundpressurelevelat5m dB(A) 13 15 19 23 26 32 38 45 47 50 52

CC60-H2airinlettemperature °C 20weight kg 28waterrange °C 80/60speed 1 2 3airvolume m³/h 430 620 740heatingcapacity kW 6,4 8,5 9,7dischargeairtemperature °C 65 61 59waterflowrate l/h 280 370 425waterpressuredrop kPa 2,1 3,5 4,6waterpressuredropwith3-portvalve kPa 3,4 5,8 7,5waterpressuredropwith2-portvalve kPa 3,4 5,8 7,5

CC60-H3airinlettemperature °C 20weight kg 31waterrange °C 60/40speed 1 2 3airvolume m³/h 430 620 740heatingcapacity kW 4,3 5,8 6,7dischargeairtemperature °C 50 48 47waterflowrate l/h 185 250 290waterpressuredrop kPa 0,6 1,1 1,4waterpressuredropwith3-portvalve kPa 1,2 2,1 2,8waterpressuredropwith2-portvalve kPa 1,2 2,1 2,8

Theunitiswiredasstandardoncircuits7,9and11.Thisisspeed1,2and3.TheairinletconditionsareincompliancewithEuroventstandards.Theairdischargetemperatureofunitswithmodulatingcontrolislimitedto50°C.

Page 15: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircletechnicaldata

HeatingCC90Basicdata

CC90electricalsupply V/ph/Hz 230/1/50 max.inputcurrent A 1,2max.fanpower W 277tapping 1 2 3 4 5 6 7 8 9 10 11tappingvoltage V 60 70 80 90 100 115 130 155 170 190 230airvolume m³/h 240 300 360 430 510 630 750 1040 1260 1490 1630soundpressurelevelat5m dB(A) 24 23 25 28 29 34 38 45 50 54 57

CC90-H2airinlettemperature °C 20weight kg 49waterrange °C 80/60speed 1 2 3airvolume m³/h 750 1260 1630heatingcapacity kW 11,5 17 20,6dischargeairtemperature °C 65 60 58waterflowrate l/h 505 745 905waterpressuredrop kPa 1,9 3,9 5,5waterpressuredropwith3-portvalve kPa 3,5 7,4 10,6waterpressuredropwith2-portvalve kPa 4 8,4 12,2

CC90-H3airinlettemperature °C 20weight kg 52waterrange °C 60/40speed 1 2 3airvolume m³/h 750 1260 1630heatingcapacity kW 8 12 14,7dischargeairtemperature °C 51 48 47waterflowrate l/h 345 520 635waterpressuredrop kPa 0,5 1 1,4waterpressuredropwith3-portvalve kPa 1,2 2,7 3,9waterpressuredropwith2-portvalve kPa 1,4 3,2 4,7

Theunitiswiredasstandardoncircuits7,9and11.Thisisspeed1,2and3.TheairinletconditionsareincompliancewithEuroventstandards.Theairdischargetemperatureofunitswithmodulatingcontrolislimitedto50°C.

Page 16: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircletechnicaldata

CoolingCC60Basicdata

CC60electricalsupply V/ph/Hz 230/1/50 max.inputcurrent A 0,7max.fanpower W 143tapping 1 2 3 4 5 6 7 8 9 10 11tappingvoltage V 60 70 80 90 100 115 130 155 170 190 230airvolume m³/h 120 150 190 230 270 350 430 550 620 680 740soundpressurelevelat5m dB(A) 13 15 19 23 26 32 38 45 47 50 52

CC60-C2airinletconditions °C/% 27/48weight kg 29waterrange °C 6/12speed 1 2 3airvolume m³/h 430 620 740totalcoolingcapacity kW 2,8 3,6 4,1sensiblecoolingcapacity kW 2 2,7 3,1dischargeairtemperature °C 13 14 14condensate l/h 1,2 1,4 1,5waterflowrate l/h 405 520 590waterpressuredrop kPa 5,3 8,4 10,5waterpressuredropwith3-portvalve kPa 7,9 12,7 16waterpressuredropwith2-portvalve kPa 7,9 12,7 16

CC60-C3airinletconditions °C/% 27/48weight kg 32waterrange °C 6/12speed 1 2 3airvolume m³/h 430 620 740totalcoolingcapacity kW 3,3 4,3 4,9sensiblecoolingcapacity kW 2,3 3,1 3,6dischargeairtemperature °C 11 12 12condensate l/h 1,4 1,8 2waterflowrate l/h 470 615 705waterpressuredrop kPa 4,1 6,7 8,6waterpressuredropwith3-portvalve kPa 7,6 12,8 16,6waterpressuredropwith2-portvalve kPa 7,6 12,8 16,6

Theunitiswiredasstandardoncircuits7,9and11.Thisisspeed1,2and3.TheairinletconditionsareincompliancewithEuroventstandards.

Page 17: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircletechnicaldata

CoolingCC90Basicdata

CC90electricalsupply V/ph/Hz 230/1/50 max.inputcurrent A 1,2max.fanpower W 277tapping 1 2 3 4 5 6 7 8 9 10 11tappingvoltage V 60 70 80 90 100 115 130 155 170 190 230airvolume m³/h 240 300 360 430 510 630 750 1040 1260 1490 1630soundpressurelevelat5m dB(A) 24 23 25 28 29 34 38 45 50 54 57

CC90-C2airinletconditions °C/% 27/48weight kg 50waterrange °C 6/12speed 1 2 3airvolume m³/h 750 1260 1630totalcoolingcapacity kW 5,1 7,3 8,7sensiblecoolingcapacity kW 3,6 5,4 6,5dischargeairtemperature °C 12 14 15condensate l/h 2,2 2,8 3,1waterflowrate l/h 735 1055 1245waterpressuredrop kPa 4,7 9,1 12,4waterpressuredropwith3-portvalve kPa 8,1 16 22,1waterpressuredropwith2-portvalve kPa 9,1 18,1 25

CC90-C3airinletconditions °C/% 27/48weight kg 53waterrange °C 6/12speed 1 2 3airvolume m³/h 750 1260 1630totalcoolingcapacity kW 6,1 9,1 11sensiblecoolingcapacity kW 4,2 6,4 7,9dischargeairtemperature °C 10 11 12condensate l/h 2,8 3,9 4,5waterflowrate l/h 875 1305 1575waterpressuredrop kPa 3 6,2 8,8waterpressuredropwith3-portvalve kPa 7,8 16,9 24,3waterpressuredropwith2-portvalve kPa 9,3 20,1 29,1

Theunitiswiredasstandardoncircuits7,9and11.Thisisspeed1,2and3.TheairinletconditionsareincompliancewithEuroventstandards.

Page 18: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircletechnicaldata

Heating&CoolingCC60Basicdata

CC60electricalsupply V/ph/Hz 230/1/50 max.inputcurrent A 0,7max.fanpower W 143tapping 1 2 3 4 5 6 7 8 9 10 11tappingvoltage V 60 70 80 90 100 115 130 155 170 190 230airvolume m³/h 120 150 190 230 270 350 430 550 620 680 740soundpressurelevelat5m dB(A) 13 15 19 23 26 32 38 45 47 50 52

Heating

CC60-H1C2airinlettemperature °C 20weight kg 31waterrange °C 80/60speed 1 2 3airvolume m³/h 430 620 740heatingcapacity kW 3,1 3,9 4,4dischargeairtemperature °C 41 39 38waterflowrate l/h 135 170 195waterpressuredrop kPa 0,7 1 1,3waterpressuredropwith3-portvalve kPa 1,4 2,2 2,8waterpressuredropwith2-portvalve kPa 2,5 4 5

Cooling

CC60-H1C2airinletconditions °C/% 27/48weight kg 32waterrange °C 6/12speed 1 2 3airvolume m³/h 430 620 740totalcoolingcapacity kW 2,8 3,6 4,1sensiblecoolingcapacity kW 2 2,7 3,1dischargeairtemperature °C 13 14 14condensate l/h 1,2 1,4 1,5waterflowrate l/h 405 520 590waterpressuredrop kPa 5,3 8,4 10,5waterpressuredropwith3-portvalve kPa 7,9 12,7 16waterpressuredropwith2-portvalve kPa 7,9 12,7 16

Theunitiswiredasstandardoncircuits7,9and11.Thisisspeed1,2and3.TheairinletconditionsareincompliancewithEuroventstandards.Theairdischargetemperatureofunitswithmodulatingcontrolislimitedto50°C.

Page 19: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircletechnicaldata

Heating&CoolingCC90Basicdata

CC90electricalsupply V/ph/Hz 230/1/50 max.inputcurrent A 1,2max.fanpower W 277tapping 1 2 3 4 5 6 7 8 9 10 11tappingvoltage V 60 70 80 90 100 115 130 155 170 190 230airvolume m³/h 240 300 360 430 510 630 750 1040 1260 1490 1630soundpressurelevelat5m dB(A) 24 23 25 28 29 34 38 45 50 54 57

Heating

CC90-H1C2airinlettemperature °C 20weight kg 54waterrange °C 80/60speed 1 2 3airvolume m³/h 750 1260 1630heatingcapacity kW 6,2 8,7 10,4dischargeairtemperature °C 44 41 39waterflowrate l/h 270 385 455waterpressuredrop kPa 2 3,9 5,3waterpressuredropwith3-portvalve kPa 2,5 4,8 6,6waterpressuredropwith2-portvalve kPa 2,6 5,1 7

Cooling

CC90-H1C2airinletconditions °C/% 27/48weight kg 53waterrange °C 6/12speed 1 2 3airvolume m³/h 750 1260 1630totalcoolingcapacity kW 5,2 7,5 8,8sensiblecoolingcapacity kW 3,7 5,5 6,6dischargeairtemperature °C 12 14 15condensate l/h 2,2 2,9 3,2waterflowrate l/h 745 1070 1265waterpressuredrop kPa 4,9 9,5 13waterpressuredropwith3-portvalve kPa 8,4 16,6 23waterpressuredropwith2-portvalve kPa 9,4 18,8 26,1

Theunitiswiredasstandardoncircuits7,9and11.Thisisspeed1,2and3.TheairinletconditionsareincompliancewithEuroventstandards.Theairdischargetemperatureofunitswithmodulatingcontrolislimitedto50°C.

Page 20: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircledimensionalsketches

CC60

Page 21: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

ComfortCircledimensionalsketches

CC90

Page 22: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

Dimensionalsketches

IndexThecorrespondingnumbersinthedimensionalsketchesareexplainedbelow:

7-Airvent

14-Condensatedischarge(onlyforcooling)

15-Condensationpump(onlyforcooling)

16-Condensationtray(onlyforcooling)

20-Connectionplate

23-Coolingfor4-pipesH1C3

24-Coolingorheatingfor2-pipes

51-Heatingfor4-pipesH1C3

58-Locking

64-Return

78-Slottedholes

81-Supply

88-Threadedrods(M8)arenotsuppliedasastandard

Explanationdimensionalsketches•Alldimensionsinmm

•A=detailwaterconnections

ThediameterofthepipeworkconnectionsforcoiltypeH1isDN15(15mm).

ForcoiltypesH2,H3,C2andC3thisisDN20(22mm).

Page 23: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

Notes

Notes

Page 24: CASSETTE UNIT Comfort Circle - Biddle · Comfort Circle cassette unit All-round comfort With today's energy prices, building owners are increasingly aware of the need for an efficient

Subjecttochangewithoutpriornotice

BiddleAirSystemsLimitedSt.Mary’sRoad

WarwickshireCV115AUNuneaton

T+442476384233

[email protected]

Iwww.biddle-air.co.uk