    front face1 opening push-button (O)

    2 closing push-button (I)3 keylock for "connected",

    "disconnected" or "test" position4 door interlock5 stored-energy-mechanism charging

    handle6 operations counter7 "open" position keylock8 racking handle storage9 functional position indicator:

    "connected", "test" and "disconnected"10 controls on fixed chassis (accessible

    with cubicle door closed)11 padlocking facilities for "connected",

    "disconnected" or "test" position

    12 stored-energy-mechanism statusindicator

    c"charged"

    c"discharged"

    13 main-contact position indicator

    c"OFF" (O);

    c"ON" (I).

    14 fault-trip indicator/breaker reset buttonLV circuit-breaker: blue figuresEnclosure: red figures

    Masterpact: presentation

    Masterpact circuit breakers are used toprotect and control low-voltage distributionsystems. They may be installed in main LV

    switchboards (incoming units, main andsecondary outgoers). Masterpact is acomplete range offering a large selection ofperformance levels:

    cratings from 800 to 6300 A AC,

    from 1000 to 8000 A DC;cbreaking capacity from 40 to 150 kA rms;coperational voltages 690 V AC,1000 V DC.

    2 Merlin Gerin

    Many versions

    c3 or 4 poles;

    cfixed or drawout versions;

    ccurrent-limiting version up to 2500 A;

    cwide range of control units offeringmultiple functions.

    Circuit breakers designed for allapplications

    c1000 V AC version;

    cDC version;

    canti-corrosion version;

    csource-changeover version;cmerchant-marine and military versions.

    Masterpact circuit breakers comply with allmajor international standardsand meetT2 tropicalisation criteria.

    Reduced dimensionscAC circuit breakers:va single frame size from 800 to 3200 A,vcommon height and depth from 800 to

    6300 A;

    cDC circuit breakers:

    vcommon height and length from 1000 to8000 A for operational voltages of up to 500V DC,

    vcommon height and length from 1000 to

    4000 A for operational voltages greater than500 V DC.

    push to reset

    I

    I1 I2I3

    90%

    50%

    20%

    STR 58 UE

    0.63

    IoIr

    0.8

    0.51

    xIn

    90

    105

    %Ir

    .88

    .9 .9 2.95

    .981

    .8.85

    xIo

    Imtm

    3

    4 56

    8

    101.52

    xIo

    .3

    .4 . 3

    .1

    .1.2

    on I2t off

    .2

    0

    Ir fault

    tr

    Imfault

    tm

    I

    faultIh

    th

    t

    i

    test

    + S

    T +

    T

    F

    Ihth

    400

    500 600

    800

    1000

    1200250

    320

    A

    .3

    .4 .4

    .2

    .1.2

    on I2t off

    .3

    .1

    I

    off2

    xIn

    Ir :

    Im:

    th :

    I

    IG L I

    G

    LLG

    LIG

    off

    resetV

    tr

    60

    120 2 40

    480

    1530

    at 1,5Ir

    4

    6

    8 12

    17

    22

    Ic1Ic2

    .86

    .9 . 93

    .95

    .98

    1.8

    .85

    .7

    .8 .85

    .95

    .5.6

    xIr

    .9

    1

    R

    xIr

    test

    Opush OFF

    connected

    test

    disconnected

    O OFFdischarged

    I

    push ON

    MERLIN GERIN

    M32H1masterpact

    IEC947-2

    00000

    Ui

    Ue

    Icu

    Ics

    Icw

    1000V

    380/440V

    100kA

    100kA

    75kA 1s

    50/60Hz

    480/69 0V

    85kA

    85kA

    M63M50 M40

    M08 M32

    charged

    discharged

    O OFF

    I ON

    E28791

    E28761

    E28760

    M08 to M32

    035928PC

    11

    14

    7

    2

    5

    1

    6

    12

    13

    4

    39 108

    BTP207E-1.010-presentation 21/12/01, 9:342

  • 8/11/2019 Catlogo Masterpact

    4/114

    3Merlin Gerin

    drawout version1 arc chute cover2 auxiliary terminal shield

    3 auxiliaries connection block4 fixed chassis

    5 safety shutters6 arc chute7 remote control voltage release8 motor for electrical charging of

    stored energy mechanism

    9 control unit (AC system)10 front cover

    1

    2

    3

    6

    7

    8

    10

    9

    5

    4

    015159

    BTP207E-1.010-presentation 21/12/01, 9:343

  • 8/11/2019 Catlogo Masterpact

    5/114

    Merlin Gerin4

    Automatic source-changeover controller

    Fixed circuit breaker

    50%

    20%

    STR 58 U

    0.63

    IoIr tr

    0.8

    0.5 1

    xIn

    90

    105

    tr

    %Ir

    .88

    .9 .92.95

    .98

    1.8.85

    xIo

    60120 240

    480

    1530

    at1 .5Ir

    Im tm

    3

    4 5

    6

    8

    101.5

    2

    xIr

    .3

    .4 .3

    .1

    .1

    .2

    on I2t off

    .2

    0

    Ir fault

    tr

    Imfault

    tm

    I

    faultIh

    th

    i

    test

    +

    +

    T

    R

    test

    Ih1200A Max th

    400

    500 600800

    1000

    1200250

    320

    A

    .3

    .4 .4

    .2

    .1.2

    on I2t off

    .3

    .1

    I

    8

    12 14

    19

    22

    Max.2

    4

    xIn

    Ic1 Ic2

    .86

    .9 .93

    .95

    .98

    1.8.85

    xIr

    .7

    .8 .85

    .95

    .5.6

    .9

    1xIr

    Ir :

    Im:

    th:

    min.

    norm

    overcurrent

    ground

    isolation renforceclasse II

    sparation totaleentre chaque phase

    dclencheurs voltmtriquesaccessibles l'avant

    Masterpact: presentation

    safety and reliabilitycreduced, simple maintenance (maincontacts easily accessible, with wearindication feature);cdouble insulation from the front face;cpositive contact indication;cauxiliary devices can be fitted on sitewithout adjustment;cfewer parts than conventional ranges (by afactor of 5-10);ca trip interlock ensures that the circuitbreaker is open during connection anddisconnection;cconnection to top or bottom terminals;cfully tropicalised as standard.

    stored energy operating

    mechanismMasterpact circuit breakers are operated viaa stored energy mechanism forinstantaneous opening and closing.The mechanism is charged either manuallyor electrically. Closing and openingoperations can be initiated either from thelocal pushbuttons on the circuit breaker frontface, or by remote control.

    common auxiliariesfrom 800 A to 6300 AAuxiliariescaccessible from the front, mounted in aseparate compartment insulated from powercircuits;csecured by a single screw;cadjustment-free;ccan be fitted on site.

    ccccc Source changeover systemFour solutions are available:vmechanical interlocking for 2 or 3 circuitbreakers, adaptable to various source-changeover configurations;vautomatic source-changeover controller,easy to implement on any two suitablyequipped circuit breakers (electricallycharged operating mechanism, etc.) (for 3circuit breakers, consult us);vcomplete assembly including 2 or3 mechanically (rod assembly) interlocked

    circuit breakers, adaptable to varioussource-changeover configurations;vcomplete assembly including2 mechanically (rod assembly) interlocked

    circuit breakers and an automatic source-changeover controller, adaptable to varioussource-changeover configurations. Readyfor connection.

    other possibilities ccccc Fixed circuit breakerThe fixed circuit breaker is derived from themoving part of the drawout circuit breaker byadding a fixing bracket on each side.

    ccccc Switch versionThe switch (unprotected) version is deriveddirectly from the standard circuit breaker, but

    does not implement a control unit (or themagnetic trip units used with the DC circuitbreakers). Available models are:vstandard: type HI and NI;vhigh performance: type HF, equipped witha protection system that instantaneously

    opens the circuit breaker in the event ofclosure under fault conditions.

    ccccc Earthing switchA special short-circuit and earthing switch isavailable on request for the M08 to M32Hdrawout types, 3 or 4 poles. Please consult

    us.

    ccccc 1000 V AC circuit breakers

    E

    29490

    voltage releasesaccessible from thefront

    total phaseseparation

    double insulation

    035929

    053061

    053060

    053058

    BTP207E-1.015-presentation 21/12/01, 9:354

  • 8/11/2019 Catlogo Masterpact

    6/114

    Merlin Gerin 5

    Drawout Masterpact DC circuit breaker

    Fixed Masterpact DC circuit breaker

    device identificationM 20 H1

    breaking capacity;cN1: standard;cH1: H2: high performance;cL1: current limiting;cDC: direct current.

    ratingcrated current / 100.

    familycMasterpact: LV power aircircuit breaker.

    DC circuit breakersMasterpact DC circuit breakers are availablein fixed and drawout versions. They benefitfrom the AC range technology andadvantages.c5 available ratings from 1000 to 8000 A;c2 breaking capacities, 100 kA at 500 V,50 kA at 750 and 1000 V;

    ca circuit-breaker version offeringinstantaneous short-circuit protection withan adjustable, magnetic trip unit (DINA);

    ca switch (unprotected) version.note:up to 125 V DC, the devices in the AC

    range (M08 to M63) may be used only in theswitch version, in which case a three-pole,type HI device should be used, with:c1 pole for the positive polarity;c

    1 pole for the negative polarity;c1 pole not used.

    Auxiliaries

    All the auxiliaries designed for theMasterpact AC circuit breakers may be usedon the DC versions, with the exception of theposition switches, indicating the connected(CE), disconnected (CD) and test (CT)positions.Auxiliary connections are made via one ortwo manually disconnectable plugs thatremain accessible from the front.

    AccessoriesStandard Masterpact DC range equipmentincludes an arc-chute cover (CC) and, on

    drawout versions, safety shutters (VO).Interphase barriers (EIP) are not availablefor the DC range.

    86094

    86096

    BTP207E-1.015-presentation 21/12/01, 9:355

  • 8/11/2019 Catlogo Masterpact

    7/114

    Merlin Gerin6

    Masterpact: presentation

    Masterpact circuit breakers are the product

    of Merlin Gerins vast experience in the fieldof power circuit breakers. They incorporateall the qualities of traditional air circuitbreakers while drawing on certain of theadvantages specific to moulded-case circuit

    breakers. In particular, they require nopreventive maintenance.

    ease of installationMasterpact is a complete and rationallydesigned range.c10 ratings;c4 breaking-capacity levels;c6 control units;ca complete range of auxiliaries andaccessories;

    cnumerous versions (three and four-poledevices, fixed and drawout versions, etc.).

    Masterpact circuit breakers are easy toincorporate in switchboards.ca single frame size from 800 to 3200 A,

    thus making for standardised columns;can upper safety clearance equal to zerodue to the arc-chute cover, on both the fixedand drawout versions;cbuilt-in measurement functions in thecontrol units;cauxiliaries are the same for the entirerange and may be easily implemented (onlya screwdriver is required).

    Masterpact circuit breakers are easy to

    connect to the main distribution system.

    call types of connections are available(horizontal and vertical terminals, front andmixed connections);cconnections are possible with bars of anythickness;cconnection to the input power source is

    possible on the upper or lower terminals ofthe circuit breakers.

    Due to their small size, Masterpact circuitbreakers can replace most existingcircuit breakers.

    continuity of serviceMasterpact circuit breakers are designedwith continuity of service in mind. Theresult is:ctotal time discrimination on the N1 and H1circuit breakers and maximum discrimination

    on H2 circuit breakers;cfactory pre-setting of Masterpact circuitbreakers which never require any periodicmaintenance;chigh electrical endurance: 10 000 cycles at1600 A and 30 cycles at 50 kA, withoutmaintenance;cpreventive indications: load-sheddingindication switch, long-time thresholdoverrun alarm, etc.;ceasy access to the main contacts fitted

    with mechanical wear indicators. An optionalfunction on the STR68 control unit is theremote indication of contact wear, thus

    making possible continuous monitoring ofcircuit breakers during their service life.

    operating safetyThe insulating casing of Masterpactcircuit breakers provides for:cuser safety:vdouble insulation on the front face(class II),vauxiliary circuits in a compartmentinsulated from the power circuits;cswitchboard safety when the circuitbreaker is in the open position:

    veach pole is effectively isolated in its ownhousing,vlimitation of external disturbances.

    Positive contact indicationThe position indicator cannot indicateopen unless the poles are effectively

    separated by the required distance.The circuit breakers automatically open

    during racking in and out.

    reliabilitycMasterpact circuit breakers comprise tentimes fewer parts than traditional devices.

    They are easier to produce and morereliable.c

    the Masterpact circuit-breaker factory iscertified ISO 9002;cthe design of Masterpact circuit breakers

    is modular with delayed differentiation(highest possible number of common partson all models). The result is shorter deliverytimes and enhanced reliability.

    ,

    0

    36634

    025179

    2500 A Masterpact circuit breaker

    Top: front connectionBottom: rear vertical connection

    BTP207E-1.020-contents 21/12/01, 9:386

  • 8/11/2019 Catlogo Masterpact

    8/114

    7

    LV power air

    circuit breakers and

    switch-disconnectors

    Masterpact

    2/ functions andcharacteristics

    page

    generales characteristics 0

    circuit breaker selection 0

    switch-disconnectors 0

    dimensions an weights 0

    control unit selection 0

    control unit accessories 0

    electrical auxiliaries 0

    mechanical accessories 0

    source changeover systems 0

    BTP207E-2.001-content 21/12/01, 9:397

  • 8/11/2019 Catlogo Masterpact

    9/114

    Merlin Gerin8

    MERLIN GERINmasterpact

    M32 H2

    Ui 1000V 50/60Hz

    Ue 380/440V 480/690V

    Icu 100kA 85kA

    Ics 100kA 85kA

    Icw 75kA 1s

    IEC 947-2

    Masterpact: functions and characteristics

    general characteristics

    Standardised characteristics indicated onthe rating plate:Ui: rated insulation voltageUe: rated operational voltage

    Icu: ultimate breaking capacity, for variousvalues of the rated operational voltage UeIcs: service breaking capacityIcw: short-time withstand current

    : suitable for isolation

    Masterpact circuit breakers comply with allthe major international standards:

    cInternational standard IEC 947-2;

    cNorth American standards (please consult

    us):UL 489, ANSI C37-50, CSA C22-2,NEMA AB1 et SG3;

    cJapanese standards: JIS 160 and C 8372.

    They also comply with the following national

    standards:

    cFrance NF C 63-120;

    cGermany VDE 0660;

    cUnited Kingdom BS 4752;

    cAustralia AS ;

    cItaly CEI.Masterpact circuit breakers comply with the

    specifications of the marine classificationcompanies (Veritas, Lloyd's Register ofShipping, Det Norske Veritas, etc.).

    IEC 947-2This standard replaces IEC 157-1,applicable since 1973.The circuit breaker selection criteria are

    unchanged, but the new standard providesthe user with a better guarantee concerningquality and performance.Circuit breakers are subjected to tests thatare more representative of real operating

    conditions.IEC 947-2 also clarifies the notion ofbreaking capacity.

    cIcu :the ultimate breaking capacity, whichmust be greater than or equal to the 3-phase

    short-circuit current at the point ofinstallation of the circuit breaker, a value

    unlikely to be reached under real conditions;cIcs :the service breaking capacity,generally expressed as a percentage of the

    ultimate breaking capacity (25, 50, 75 or100 % of Icu). It corresponds to a short-circuit current that is more likely to bereached under real conditions. The circuitbreaker must continue to operate normally

    after having interrupted a current equal toIcs several times;

    cIcw :short-time withstand current forcircuit breakers belonging to category B(category B refers to circuit breakers withtime discrimination and category A to thosewithout time discrimination).Furthermore, IEC 947-2 takes into accountrecent technological advances:

    csuitability for isolation recognised for

    circuit breakers having passed specialelectrical and mechanical tests;

    cindustrial earth-fault circuit breakerscovered by an appendix;

    cdefinition of tests designed to ensure

    coordination between two circuit breakers.

    conformity with standards

    tropicalisationAs standard, Masterpact circuit breakerscomply with NF C 63-100 standard level 2

    conditions (95 % relative humidity at 45 Cor 80 % at 55 C, hot and humid climateconditions). They also comply with thefollowing standards:

    cIEC 68-2-30 damp heat;

    cIEC 68-2-2 dry heat;cIEC 68-2-11 salt spray;cIEC 68-2-1 low temperatures during

    storage.Corrosive atmospheres: Special grease or

    other surface coatings available (pleaseconsult us).

    pollution degreeMasterpact circuit breakers are certified foroperation in pollution degree IVenvironments as defined byIEC standard 947 (industrial environments).

    E29049

    BTP207E-2.020-gen. charact.. 21/12/01, 9:408

  • 8/11/2019 Catlogo Masterpact

    10/114

  • 8/11/2019 Catlogo Masterpact

    11/114

    Merlin Gerin6

    Masterpact: functions and characteristics

    circuit breaker selection

    (1) Defined for a power factor of 0.25 if 20 < kA rms 50 or 0.20 of kA rms > 50.(2) Closing at 6 x Ie and opening at 0.17 x Un.(3) For control unit STR 68 U, the minimum ratingIn is 400 A.

    Masterpact circuit breakersnumber of poleselectrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40 C

    rating of 4th pole (A)

    rated insulation voltage (V) Ui

    rated impulse withstand voltage (V) Uimp

    rated operational voltage (V) Ue AC 50/60 Hz

    type of circuit breakerultimate breaking capacity (1) Icu AC 50/60 Hz 220/415 V(kA rms) 440 V

    500/690 V

    service breaking capacity Ics (% Icu)

    short-time withstand current Icw AC 50/60 Hz 0.5 s

    (kA rms) 1 s3 s

    making capacity (kA peak) Icm AC 50/60 Hz 220/415 V

    440 V

    500/690 V

    electrodynamic withstand (kA peak)

    utilisation category

    suitability for isolation

    break time

    closing time

    endurance (C-O cycles) x 1000 mechanical with maintenance

    no maintenance

    electrical no maintenance 440 V - In

    690 V - In

    motor control (AC3-947-4) (2) 690 V

    electrical characteristics as per standard Nema AB1breaking capacity (kA) 480 V

    600 V

    protection (see following pages)sensor ratings (A) (see page 12)

    control unit instantaneous STR 18 Mprotection type distribution STR 28 D

    selective STR 38 S

    universal STR 58 U

    STR 68 U

    installation and connectionsconnection

    version drawout

    fixed

    indication and measurement auxiliariesauxiliary switches

    electronic trip unit related functions

    control auxiliariesauxiliary releases (MN, MNR, MX, XF)

    motor mechanism (MCH)

    operation counter (CDM)

    installation and connection accessorieslocking by padlock or keylock/mismatch protection

    safety shutters (VO)

    interphase barriers (EIP)

    partitioning fixture (AC)

    arc-chute cover (CC)

    terminal-block cover (CB)

    door frame (CDP)

    transparent cover (CCP)

    0

    35928

    Masterpact M16 H1

    BTP207E-2.060-M08...16 21/12/01, 9:416

  • 8/11/2019 Catlogo Masterpact

    12/114

    7Merlin Gerin

    M08 M10 M12 M163, 4 3, 4 3, 4 3, 4

    800 1000 1250 1600

    800 1000 1250 1600

    1000 1000 1000 1000

    8000 8000 8000 8000

    690 690 690 690

    N1 H1 H2 L1 N1 H1 H2 L1 N1 H1 H2 L1 N1 H1 H2 L140 65 100 130 40 65 100 130 40 65 100 130 40 65 100 130

    40 65 100 110 40 65 100 110 40 65 100 110 40 65 100 110

    40 65 85 65 40 65 85 65 40 65 85 65 40 65 85 65

    100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 %

    40 65 65 12 40 65 65 12 40 65 65 12 40 65 65 17

    30 50 50 12 30 50 50 12 30 50 50 12 40 50 50 1722 32 32 12 22 32 32 12 22 32 32 12 22 32 32 12

    84 143 220 286 84 143 220 286 84 143 220 286 84 143 220 286

    84 143 220 242 84 143 220 242 84 143 220 242 84 143 220 242

    84 143 187 143 84 143 187 143 84 143 187 143 84 143 187 143

    84 143 143 24 84 143 143 24 84 143 143 24 84 143 143 34

    B B B B B B B B B B B B B B B B

    c c c c

    25 to 30 ms without intentional time delay and 9 ms for type L1

    70 ms

    20 20 20 20 20 20 20 20 20 20 20 15 20 20 20 15

    10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

    10 10 10 3 10 10 10 2.7 10 10 10 2.5 10 10 10 2.2

    10 10 10 3 10 10 10 2.7 10 10 10 2.5 10 10 10 2.2

    10 10 10 - 10 10 10 - 10 10 10 - 10 10 10 -

    40 65 100 - 40 65 100 - 40 65 100 - 40 65 100 -

    40 65 65 - 40 65 65 - 40 65 65 - 40 65 65 -

    200 to 800 (3) 200 to 1000 (3) 200 to 1250 (3) 200 to 1600 (3)

    c c c c c c c c c c c c

    c c c c c c c c c c c c

    c c c c c c c c c c c c c c c c

    c c c c c c c c c c c c c c c c

    c c c c c c c c c c c c c c c c

    front and rear connections

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    BTP207E-2.060-M08...16 21/12/01, 9:417

  • 8/11/2019 Catlogo Masterpact

    13/114

    Merlin Gerin8

    Masterpact: functions and characteristics

    circuit breaker selection (cont.)

    Masterpact circuit breakersnumber of poleselectrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40 C

    rating of 4th pole (A)

    rated insulation voltage (V) Ui

    rated impulse withstand voltage (V) Uimp

    rated operational voltage (V) Ue AC 50/60 Hz

    type of circuit breakerultimate breaking capacity (1) Icu AC 50/60 Hz 220/415 V(kA rms) 440 V

    500/690 V

    service breaking capacity Ics (% Icu)

    short-time withstand current Icw AC 50/60 Hz 0.5 s

    (kA rms) 1 s3 s

    making capacity (kA peak) Icm AC 50/60 Hz 220/415 V

    440 V

    500/690 V

    electrodynamic withstand (kA peak)

    utilisation category

    suitability for isolation

    break time

    closing time

    endurance (C-O cycles) x 1000 mechanical with maintenance

    no maintenance

    electrical no maintenance 440 V - In

    690 V - In

    motor control (AC3-947-4) (2) 690 V

    electrical characteristics as per standard Nema AB1breaking capacity (kA) 480 V

    600 V

    protection (see following pages)sensor ratings (A) (see page 12)

    control unit instantaneous STR 18 Mprotection type distribution STR 28 D

    selective STR 38 S

    universal STR 58 U

    STR 68 U

    installation and connectionsconnection

    version drawout

    fixed

    indication and measurement auxiliariesauxiliary switches

    electronic trip unit related functions

    control auxiliariesauxiliary releases (MN, MNR, MX, XF)

    motor mechanism (MCH)

    operation counter (CDM)

    installation and connection accessorieslocking by padlock or keylock/mismatch protection

    safety shutters (VO)

    interphase barriers (EIP)

    partitioning fixture (AC)

    arc-chute cover (CC)

    terminal-block cover (CB)

    door frame (CDP)

    transparent cover (CCP)

    0

    36635

    Masterpact M50 H1

    (1) Defined for a power factor of 0.25 if 20 < kA rms

    50 or 0.20 of kA rms > 50.(2) Closing at 6 x Ie and opening at 0.17 x Un.(3) For control unit STR 68 U, the minimum ratingIn is 400 A.(4)83% if Ue i440 V.(5)Consult us for full rated neutral.

    BTP207E-2.070-M20...63 21/12/01, 9:428

  • 8/11/2019 Catlogo Masterpact

    14/114

    9Merlin Gerin

    M20 M25 M32 M40 M50 M633, 4 3, 4 3, 4 3, 4 3, 4 3, 4

    2000 2500 3200 4000 5000 6300

    2000 2500 3200 4000 2500 (5) 3200

    1000 1000 1000 1000 1000 1000

    8000 8000 8000 8000 8000 8000

    690 690 690 690 690 690

    N1 H1 H2 L1 N1 H1 H2 L1 H1 H2 H1 H2 H1 H2 H1 H255 75 100 130 55 75 100 130 75 100 75 100 100 150 100 150

    55 75 100 110 55 75 100 110 75 100 75 100 100 150 100 150

    55 75 85 65 55 75 85 65 75 85 75 85 85 85 85 85

    100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % 100 % (4) 100 % 100 % (4)

    55 75 75 17 55 75 75 17 75 75 75 75 100 100 100 100

    55 75 75 17 55 75 75 17 75 75 75 75 100 100 100 10050 57 57 17 50 75 75 17 75 75 75 75 100 100 100 100

    121 165 220 286 121 165 220 286 165 220 165 220 220 330 220 330

    121 165 220 242 121 165 220 242 165 220 165 220 220 330 220 330

    121 165 187 143 121 165 187 143 165 187 165 187 187 187 187 187

    121 165 165 34 121 165 165 34 165 165 165 165 220 220 220 220

    B B B B B B B B B B B B B B B B

    c c c c c c

    25 to 30 ms without intentional time delay and 9 ms for type L1

    70 ms 80 ms

    15 15 15 15 15 15 15 15 15 15 10 10 10 10 10 10

    10 10 10 10 10 10 10 10 10 10 5 5 5 5 5 5

    9 9 9 2 8 8 8 1.8 4 4 3 3 3 3 2 2

    7 7 7 2 6 6 6 1.8 2.6 2.6 2.5 2.5 2.5 2.5 1.5 1.5

    7 7 7 - 6 6 6 - 2.6 2.6 2.5 2.5 2.5 2.5 1.5 1.5

    55 75 100 - 55 75 100 - 75 100 75 100 100 125 100 150

    55 75 75 - 55 75 75 - 75 75 75 75 100 100 100 100

    200 to 2000 (3) 300 to 2500 (3) 600 to 3200 2000 to 4000 2000 to 5000 2000 to 6300

    c c c c c c c c c c c c c c

    c c c c c c c c c c c c c c

    c c c c c c c c c c c c c c c c

    c c c c c c c c c c c c c c c c

    c c c c c c c c c c c c c c c c

    front and rear connections rear connections

    c c c c c c

    c c c c c (3P only)

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c(3P only)

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c c c

    BTP207E-2.070-M20...63 21/12/01, 9:429

  • 8/11/2019 Catlogo Masterpact

    15/114

    Merlin Gerin10

    Masterpact: functions and characteristics

    circuit breaker selection (cont.)Masterpact 1000 V AC

    Masterpact 1000 V AC circuit breakersnumber of poleselectrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40 C

    rating of 4th pole (A)

    rated insulation voltage (V) Ui

    rated impulse withstand voltage (V) Uimp

    rated operational voltage (V) Ue AC 50/60 Hz

    type of circuit breakerultimate breaking capacity (1) Icu AC 50/60 Hz 220/415 V(kA rms) 440 V

    500/690 V

    1000 V

    service breaking capacity Ics (% Icu)

    short-time withstand current Icw AC 50/60 Hz 0.5 s(kA rms) 1 s

    3 s

    making capacity (kA peak) Icm AC 50/60 Hz 220/415 V

    440 V

    500/690 V

    1000 V

    electrodynamic withstand (kA peak)

    utilisation category

    suitability for isolation

    break time

    closing time

    endurance (C-O cycles) x 1000 mechanical with maintenance

    no maintenance

    electrical no maintenance 440 V - In690 V - In

    motor control (AC3-947-4) (2) 690 V

    protection (see following pages)sensor ratings (A) (see page 12)

    control unit instantaneous STR 18 Mprotection type distribution STR 28 D

    selective STR 38 S

    universal STR 58 U

    STR 68 U

    installation and connectionsconnection

    version drawout

    fixed

    indication and measurement auxiliariesauxiliary switches

    electronic trip unit related functions

    control auxiliariesauxiliary releases (MN, MNR, MX, XF)

    motor mechanism (MCH)

    operation counter (CDM)

    installation and connection accessorieslocking by padlock or keylock/mismatch protection

    safety shutters (VO)

    interphase barriers (EIP)

    partitioning fixture (AC)

    arc-chute cover (CC) (as standard on the 1000 V version)

    terminal-block cover (CB)

    door frame (CDP)

    transparent cover (CCP)

    (1) Defined for a power factor of 0.25 if 20 < kA rms 50 or 0.20 of kA rms > 50.(2) Closing at 6 x Ie and opening at 0.17 x Un.(3) For control unit STR 68 U, the minimum ratingIn is 400 A.

    Masterpact M20 H1 1000 V

    0

    52380

    BTP207E-2.080-M08...32 21/12/01, 9:4210

  • 8/11/2019 Catlogo Masterpact

    16/114

  • 8/11/2019 Catlogo Masterpact

    17/114

    Merlin Gerin12

    Masterpact: functions and characteristics

    switch-disconnectors

    Masterpact switch-disconnectorsnumber of poleselectrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40 C

    rating of 4th pole (A)

    rated insulation voltage (V) Ui

    rated impulse withstand voltage (V) Uimp

    rated operational voltage (V) Ue AC 50/60 Hz

    type of switch-disconnectorshort-time withstand current Icw AC 50/60 Hz 0.5 s(kA rms) 1 s

    3 s

    making capacity (kA peak) Icm AC 50/60 Hz 440 V

    500/690 V

    electrodynamic withstand (kA peak)suitability for isolation

    closing time

    endurance (C-O cycles) x 1000 mechanical with maintenance

    no maintenance

    electrical no maintenance 440 V - In

    690 V - In

    motor control (AC3-947-4) (1) 690 V

    protectionSTR 08 dummy unit (no protection)

    STR 18I (protection against short-circuits when closing)

    installation and connectionsconnection

    version drawout

    fixed

    indication and measurement auxiliariesauxiliary switches

    control auxiliariesauxiliary releases (MN, MNR, MX, XF)

    motor mechanism (MCH)

    operation counter (CDM)

    installation and connection accessorieslocking by padlock or keylock/mismatch protection

    safety shutters (VO)

    interphase barriers (EIP)

    partitioning fixture (AC)

    arc-chute cover (CC)

    terminal-block cover (CB)

    door frame (CDP)

    transparent cover (CCP)

    (1) Closing at 6 x Ie and opening at 0.17 x Un.

    Masterpact M10 NI

    0

    52384

    BTP207E-2.082-inter M08 21/12/01, 9:4212

  • 8/11/2019 Catlogo Masterpact

    18/114

    13Merlin Gerin

    M08 M10 M12 M163, 4 3, 4 3, 4 3, 4

    800 1000 1250 1600

    800 1000 1250 1600

    1000 1000 1000 1000

    8000 8000 8000 8000

    690 690 690 690

    NI HI HF NI HI HF NI HI HF NI HI HF40 65 65 40 65 65 40 65 65 40 65 65

    30 50 50 30 50 50 30 50 50 30 50 50

    22 32 32 22 32 32 22 32 32 22 32 32

    84 105 143 84 105 143 84 105 143 84 105 143

    84 105 143 84 105 143 84 105 143 84 105 143

    84 143 143 84 143 143 84 143 143 84 143 143c c c c

    70 ms

    20 20 20 20 20 20 20 20 20 20 20 20

    10 10 10 10 10 10 10 10 10 10 10 10

    10 10 10 10 10 10 10 10 10 10 10 10

    10 10 10 10 10 10 10 10 10 10 10 10

    10 10 10 10 10 10 10 10 10 10 10 10

    c c c c c c c c

    c c c c

    front and rear connections

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    c c c c

    BTP207E-2.082-inter M08 21/12/01, 9:4213

  • 8/11/2019 Catlogo Masterpact

    19/114

    Merlin Gerin12

    Masterpact: functions and characteristics

    switch-disconnectors (cont.)

    Masterpact switch-disconnectorsnumber of poleselectrical characteristics as per IEC 947-2 and EN 60947-2rated current (A) In 40 C

    rating of 4th pole (A)

    rated insulation voltage (V) Ui

    rated impulse withstand voltage (V) Uimp

    rated operational voltage (V) Ue AC 50/60 Hz

    type of switch-disconnectorshort-time withstand current Icw AC 50/60 Hz 0.5 s(kA rms) 1 s

    3 s

    making capacity (kA peak) Icm AC 50/60 Hz 440 V

    500/690 V

    electrodynamic withstand (kA peak)suitability for isolation

    closing time

    endurance (C-O cycles) x 1000 mechanical with maintenance

    no maintenance

    electrical no maintenance 440 V - In

    690 V - In

    motor control (AC3-947-4) (1) 690 V

    protectionSTR 08 dummy unit (no protection)

    STR 18 I (protection against short-circuits when closing)

    installation and connectionsconnection

    version drawout

    fixed

    indication and measurement auxiliariesauxiliary switches

    control auxiliariesauxiliary releases (MN, MNR, MX, XF)

    motor mechanism (MCH)

    operation counter (CDM)

    installation and connection accessorieslocking by padlock or keylock/mismatch protection

    safety shutters (VO)

    interphase barriers (EIP)

    partitioning fixture (AC)

    arc-chute cover (CC)

    terminal-block cover (CB)

    door frame (CDP)

    transparent cover (CCP)

    (1) Closing at 6 x Ie and opening at 0.17 x Un.

    Masterpact M50 HI

    0

    52388

    BTP207E-2.084-inter M20 21/12/01, 9:4312

  • 8/11/2019 Catlogo Masterpact

    20/114

    13Merlin Gerin

    M20 M25 M32 M40 M50 M633, 4 3, 4 3, 4 3, 4 3, 4 3, 4

    2000 2500 3200 4000 5000 6300

    2000 2500 3200 4000 2500 3200

    1000 1000 1000 1000 1000 1000

    8000 8000 8000 8000 8000 8000

    690 690 690 690 690 690

    NI HI HF NI HI HF HI HF HI HF HI HF HI HF55 75 75 55 75 75 75 75 75 75 100 100 100 100

    55 75 75 55 75 75 75 75 75 75 100 100 100 100

    50 57 57 50 75 75 75 75 75 75 100 100 100 100

    84 105 165 84 105 165 105 165 105 165 187 220 187 220

    84 105 165 84 105 165 105 165 105 165 187 220 187 220

    121 165 165 121 165 165 165 165 165 165 220 220 220 220c c c c c c

    70 ms 80 ms

    15 15 15 15 15 15 15 15 10 10 10 10 10 10

    10 10 10 10 10 10 10 10 5 5 5 5 5 5

    9 9 9 8 8 8 4 4 3 3 3 3 2 2

    7 7 7 6 6 6 2.6 2.6 2.5 2.5 2.5 2.5 1.5 1.5

    7 7 7 6 6 6 2.6 2.6 2.5 2.5 2.5 2.5 1.5 1.5

    c c c c c c c c

    c c c c c c

    front and rear connections rear connections

    c c c c c c

    c c c c c (3P only)

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c (3P only)

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c c c

    c c c c c c

    BTP207E-2.084-inter M20 21/12/01, 9:4313

  • 8/11/2019 Catlogo Masterpact

    21/114

    Merlin Gerin12

    Masterpact: functions and characteristics

    dimensions and weights

    Masterpact circuit breakers and switch-disconnectorstype

    dimensions and weightsdimensions W x H x D drawout 3P(mm) 4P

    fixed 3P

    4P

    maximum weight drawout 3P(kg) 4P

    fixed 3P

    4P

    Masterpact circuit breakers and switch-disconnectors

    type

    dimensions and weightsdimensions W x H x D drawout 3P(mm) 4P

    fixed 3P

    4P

    maximum weight drawout 3P(kg) 4P

    fixed 3P

    4P

    Masterpact 1000 V circuit breakers

    type

    dimensions and weightsdimensions W x H x D drawout 3P(mm) 4P

    maximum weight drawout 3P(kg) 4P

    sensor selectionIn (A) 200 250 320 400 500 600 630 800 1000 1200

    Ir threshold 80 100 125 160 200 240 250 320 400 480

    settings (A) to 200 to 250 to 320 to 400 to 500 to 600 to 630 to 800 to 1000 to 1200

    In (A) 1250 1600 2000 2500 3000 3200 4000 5000 6000 6300

    Ir threshold 500 640 800 1000 1200 1280 1600 2000 2400 2500

    settings (A) to 1250 to 1600 to 2000 to 2500 to 3000 to 3200 to 4000 to 5000 to 6000 to 6300

    The table above indicates:c all the available sensor ratings In;c the limits of the long time Ir settings.

    BTP207E-2.090-M08...63 21/12/01, 9:4712

  • 8/11/2019 Catlogo Masterpact

    22/114

    13Merlin Gerin

    M08 M10 M12 M16 M20 M25 M32N1/H1/H2/L1 N1/H1/H2/L1 N1/H1/H2/L1 N1/H1/H2 L1 N1/H1/H2 L1 N1/H1/H2 L1 H1/H2

    NI/HI/HF NI/HI/HF NI/HI/HF NI/HI/HF NI/HI/HF NI/HI/HF HI/HF

    435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367

    550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367

    422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290 422 x 356 x 290

    537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290 537 x 356 x 290

    65 65 65 69 82 82 130 82 130 130

    80 80 80 85 102 102 150 102 150 150

    43 43 43 46 55 55 80 55 80 80

    54 54 54 58 69 69 90 69 90 90

    M40 M50 M63

    H1/H2 H1/H2 H1/H2HI/HF HI/HF HI/HF

    550 x 439 x 367 815 x 484 x 367 1045 x 484 x 367

    815 x 484 x 367 1045 x 484 x 367 1045 x 484 x 367

    537 x 356 x 290 802 x 356 x 290

    801 x 356 x 290

    150 215 245

    200 230 265

    90 110

    110

    M08 M10 M12 M16 M20 M25 M32

    H1 H1 H1 H1 H1 H1 H1

    435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367 435 x 439 x 367

    550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367 550 x 439 x 367

    65 65 65 69 82 82 130

    80 80 80 85 102 102 150

    BTP207E-2.090-M08...63 21/12/01, 9:4713

  • 8/11/2019 Catlogo Masterpact

    23/114

    Merlin Gerin14

    16080 1250 2000 2500 4000 6300500032001600400

    STR 18 M

    STR 28 D

    STR 38 S

    STR 58 U

    STR 68 U

    Masterpact: functions and characteristics

    control unit selection

    Masterpact M08 to M63 circuit breakers are

    equipped with microprocessor-basedelectronic control units.

    All the protection functions are powered by

    the AC system and no auxiliary powersupply is required. The same is true for mostof the complementary functions.

    Each control unit of the Masterpact rangecorresponds to a certain type of application(instantaneous, distribution, selective,universal).All the STR control units measure the truerms value of the current and are thereforenot affected by harmonics that may bepresent on the system.

    current settings (A)

    protectionSTR 18 M

    3

    I I

    t

    0

    push to reset

    STR 18 M

    I

    xIn

    test

    +

    1

    8

    1214

    19

    22max2

    4

    2

    5

    3

    4

    5

    Key:

    1 reset button: pops out when the circuitbreaker has tripped on a fault and mustbe pressed (reset) before the circuit

    breaker can be closed again.

    2 maximum protection rating.

    3 instantaneous pick-up.

    4 test connector.

    5 holes for sealable cover plate screws.

    instantaneous protection

    distribution protection

    selective protection

    universal protection

    E31218

    E31219

    E30703

    other functionsc fault indication.

    BTP207E-2.110-unit cont. 21/12/01, 9:4714

  • 8/11/2019 Catlogo Masterpact

    24/114

    15Merlin Gerin

    protectionSTR 28 DKey:

    1 reset button: pops out when the circuitbreaker has tripped on a fault and mustbe pressed (reset) before the circuit

    breaker can be closed again.

    2 ammeter digital display.

    3 bar graph indicating load level (% Ir).

    4 maximum protection rating.

    5-6 long-time current setting as a function of:Io x Ir x In.

    7 instantaneous pick-up.

    8 overcurrent indicator LED.

    9 noted settings.

    10 test connector.

    11 holes for sealable cover plate screws.

    push to reset

    II1 I2 I3

    90%

    50%

    20%

    STR 28 D

    Io

    xIn

    90

    105%Ir

    xIo

    Im

    xIr

    Ir

    Im

    t

    i

    test

    +

    Ir :

    Im :

    Ir

    1

    .88

    .9 .92

    .95

    .981.8

    .850.5

    0.63 0.8

    1

    34 5

    6

    8101.5

    2

    2

    3

    4

    11

    5

    6

    7

    9

    8

    10

    11

    protectionSTR 38 SKey:

    1 reset button: pops out when the circuitbreaker has tripped on a fault and mustbe pressed (reset) before the circuit

    breaker can be closed again.

    2 ammeter digital display.

    3 bar graph indicating load level (% Ir).

    4 maximum protection rating.

    5 overcurrent indicator LED.

    6-7 long-time current setting as a function of:

    Io x Ir x In.8 short-time pick-up.

    9 short-time delay.

    10 noted settings.

    11 instantaneous pick-up.

    12 earth fault pick-up.

    13 earth fault delay.

    14 LEDs indicating tripping on long-time,short-time or earth fault.

    15 test connector.

    16 holes for sealable cover plate screws.

    17 battery supplying backup power for faultindication.

    18 fault indication reset and/or battery test.

    19 re-indication of last fault.

    push to reset

    II1 I2 I3

    90%

    50%

    20%

    STR 38 S

    xIn xIo

    Im tm

    xIr on I2t off

    Ir fault

    tr

    Im faulttm

    I

    faultIh

    th

    t

    i

    test

    +

    +

    T

    F

    test

    Ih th

    A on I2t off

    I

    xIn

    Ir :

    Im :

    th :

    overcurrent

    ground

    1

    2

    3

    4

    16

    90

    105

    %Ir

    Io

    0.5

    0.63 0.8

    1

    Ir

    .88.9 .92

    .95

    .981.8

    .85

    34 5

    6

    8101.5

    2

    .3.4 .3

    .2

    .10.1

    .2

    max. off

    400500 600

    800

    10001200250

    320

    .3.4 .4

    .3

    .2.1.1

    .2

    5

    6

    7

    8 9

    12

    11

    1314

    16 15

    19

    18

    17

    10

    7

    6

    I IIr

    t

    0

    other functionsc fault indication;c indication of LT overrun;c ammeter;c self-monitoring (internal overheating).

    11

    Ir Im

    8

    I I

    t

    0

    7

    9

    12

    13

    I2t ON

    I2t OFF

    other functionsc fault indication;c indication of LT overrun;c ammeter;c self-monitoring (internal overheating);c indication of type of fault (F).

    E30704

    E31220

    E31221

    E33950

    BTP207E-2.110-unit cont. 21/12/01, 9:4715

  • 8/11/2019 Catlogo Masterpact

    25/114

    Merlin Gerin16

    Masterpact: functions and characteristics

    control unit selection (cont.)

    protectionSTR 58 U

    push to reset

    II1 I2 I3

    90%

    50%

    20%

    STR 58 U

    tr

    Ir fault

    tr

    Im faulttm

    I

    faultIh

    th

    t

    i

    test

    +

    +

    T

    R

    Ftest

    Ir :

    Im :

    th :

    Max.

    norm

    overcurrent

    ground

    2

    3

    4

    5

    21

    6

    7

    8

    21

    16

    V

    reset V II+T L+I

    L+I+T

    ToffL

    L+T

    xIn

    Io

    0.5

    0.630.8

    1

    90

    105%Ir .88

    .9 .92

    .95

    .981.8

    .85

    Ir

    xIo

    60

    120 240

    480

    1530

    tr

    at 1.5Ir

    Im tm

    xIr on I2t off

    34 5

    6

    8101.5

    2

    .3.4 .3

    .2

    .10.1

    .2

    I

    xInoff

    22

    191412

    8

    4

    2

    Ih 1200A Max th

    A on I2t off

    400500 600

    800

    10001200250

    320

    .3.4 .4

    .3

    .2.1.1

    .2

    Ic1 Ic2

    xIr

    .86.9 .93

    .95

    .9818

    .85

    .7.8 .85

    .9

    .951.5

    .6

    xIr

    1

    12

    9

    10

    11

    13

    15

    14

    17

    19

    24 18

    20

    23

    22

    protectionSTR 68 U

    STR 68 U

    reset

    1 2 3 max

    A

    Ir Im I

    s

    Ih

    tm

    th

    fault

    adjustments

    24 V DC

    test

    KA

    S

    1

    tr

    A

    trip no trip MEM

    test

    2%

    load monitoringmaintenance

    N 1 2 3

    Hz

    Cos

    kW

    MWh

    +

    685812

    V

    10

    8

    8

    9

    7

    611

    5

    4

    3

    2

    2

    1Key:

    1 reset button: pops out when the circuit

    breaker has tripped on a fault and mustbe pressed (reset) before the circuitbreaker can be closed again.

    2 selection of displayed value (voltage,power, energy, power factor, frequency).

    3 display of current or interrupted current(when flashing).

    4 local fault indication and indication reset.5 selection and indication of protection

    parameter to be set.

    6 selection and indication of loadmonitoring parameters.

    7 adjustment and saving of parametersettings.

    8 holes for sealable cover plate screws.9 test connector.10 test.11 maintenance indicator.

    Ir Im I I

    t

    0

    I2t ON

    I2t OFFLT setting(Ir)

    ST pick-up(Im)

    ST time delay(tm)

    instantaneouspick-up (I)

    earth faulttime delay (th)

    earth faultpick-up (Ih)

    LT time delay(tr)

    other functionsc fault indications and memorisation;c maintenance indicator;c ammeter;c integrated test;c power measurement;c load monitoring (R);c self-monitoring (internal overheating,

    malfunction of the microprocessor);c zone selective interlocking for earth

    faults.

    other functionsc fault indication;

    c indication of LT overrun;c ammeter;c self-monitoring (internal overheating);c fault type indication (F);c segregated alarm switch for selected

    fault type (V);c zone selective interlocking (Z);c load monitoring (R);c communication (COM).

    9

    13

    Ir Im

    10

    I I

    t

    0

    8

    11

    14

    15

    I2t ON

    I2t OFF

    E30705

    E31222

    E31223

    E33949

    Key:

    1 reset button: pops out when the circuitbreaker has tripped on a fault and mustbe pressed (reset) before the circuitbreaker can be closed again.

    2 selection of fault type for segregatedalarm: Ir and/or Im and/or IhL: long-time fault (Ir)I: short-time fault (Im/l)T: earth fault (Ih)

    3 ammeter digital display.4 bar graph indicating load level (% Ir).5 maximum protection rating.6 overcurrent indicator LED.7-8 long-time current setting as a function of:

    Io x Ir x In.

    9 long-time trip delay10 short-time pick-up.

    11 short-time delay.12 adjustment of thermal memory after

    tripping.

    13 instantaneous pick-up.14 earth fault pick-up.15 earth fault delay.16 noted settings.17-18 load monitoring settings.19 test connector.20 battery supplying backup power for fault

    indication.21 holes for sealable cover plate screws.

    22 fault indication reset and/or battery test.23 re-indication of last fault.24 LEDs indicating tripping on long-time,

    short-time or earth fault.

    BTP207E-2.120-unit cont. 21/12/01, 9:5016

  • 8/11/2019 Catlogo Masterpact

    26/114

    17Merlin Gerin

    I

    t

    0

    Ih

    Th

    I2t ON

    I2t OFF

    options for STR control units

    zone selective interlocking(Z)

    "earth fault" protection(T or W)

    This earth fault protection is designed to

    protect the installation against the risks offire due to high earth faults (not to beconfused with schemes designed for the

    protection of persons against electricalshock).Two types of earth protection are available

    for Masterpact:c residual current type (T): the control unit

    calculates the vector sum of the phase andneutral (if distributed) currents;c source ground return type (W): the control

    unit acts directly on the signal received froman external current transformer installed onthe source earthing circuit.

    earth fault curves for the STR 58

    load monitoring (R) Remote indication of threshold overrun forload-shedding or load-reconnectionpurposes.

    I

    t

    0

    Ic2

    Ic1

    load monitoring curves for the STR 58

    communication: STR 58 Utransmission: STR 68 U

    Transmission of the control unit settings,circuit breaker position and current, voltageand power measurements.

    indication andmeasurement

    c ammeter (I):a digital displaycontinuously indicates the current of thephase with the greatest load (Imax). By

    pressing a scroll button, it is also possible todisplay successively the readings of I1, I2,I3, Ineutral and Ih.

    In addition, three bargraphs provide animmediate visual indication of the load oneach of the three phases.

    E26037

    E31225

    A number of circuit breakers areinterconnected one after another by a pilot-

    wire. In the event of a short-time or earthfault, the control unit applies the set timedelay only if it receives a signal from a

    downstream circuit breaker. If not, it tripsinstantaneously (tripping time as 0.1 short-time setting). In this way, the fault is clearedrapidly by the nearest circuit breaker. Thethermal stresses in the installation areminimised while maintaining timediscrimination throughout the entire

    installation.Opto-electronic outputsThe use of opto-transistors ensures totalisolation between the internal circuits of thecontrol unit and the circuits wired by theuser.

    Other information that can be transmittedincludes the value of the interrupted current,the state of the thermal memory and themaintenance indications

    c indication of type of fault (F);

    c segregated alarm switch for selectedfault type (V), wired in parallel with theopening button (MX), it disables circuitbreaker closing for the selected type of fault.

    BTP207E-2.120-unit cont. 21/12/01, 9:5017

  • 8/11/2019 Catlogo Masterpact

    27/114

    Merlin Gerin18

    Masterpact: functions and characteristics

    control unit selection (cont.)STR 18 M to STR 58 U

    control unittype of circuit breaker

    basic protectionlong time protection LT

    current setting (Ir) as a function of Io and Ir Io = In x ...

    settings tripping between 1.05 and 1.20 x Ir Ir = Io x ...

    time delay (tr)

    accuracy: + 0 - 20 % tr at 1.5 Ir (s)

    tr at 6 Ir (s)

    tr at 7.2 Ir (s)

    short-time protection ST

    pick-up (Im) adjustable by Im sett ing Im = Ir x .. .

    time delay (tm) tm setting with I2t OFF

    tm setting with I2t ON

    max. overcurrent time before tripping (ms)

    max. break time (ms)

    instantaneous protection I

    pick-up setting

    setting range

    accuracy

    OFF switch on front face

    basic functionsfault indication

    for tripping on a fault indicator button on front face

    fault trip alarm contact (SDE)

    for LT setting overrun LED (lights up at 0.9 Ir and flashes at 1.05 Ir)

    LT overrun alarm contact (optional)

    self-powered

    self-monitoring internal overheatingoptional functionsammeter (I) display between 0.2 and 1.20 In

    current readings with an accuracy of 1.5 % (1) (3)

    bargraph indication of current levels with a resolution of 10 %

    self-powered

    earth fault protection: residual current(T)or source ground return (W) type on request

    pick-up adjustable by Ih setting Ih = In x ...

    time delay (th) th setting with I2t ON and I2t OFF

    max. overcurrent time before tripping (ms)

    max. break time (ms)

    indication of type of fault (F)(LT - CT/Inst. - Earth) by LEDs on front face

    power supply with battery module

    with external power supply by AD module

    segregated alarm switch for selected fault type (V) (LT - CT/Inst. - Earth)output via relay contact

    power supply by AD module

    zone selective interlocking (Z)

    by opto-electronic contact on ST and earth (T/W) fault

    load monitoring (R)

    adjustment of load limit thresholds by Ic1 and Ic2 settings Ic1 = Ir x ... / Ic2 = Ir x ...

    time delay tr1 at 1.5 Ic1

    time delay tr2 at 1.5 Ic2

    output via opto-electronic contact 0.1 A / 240 V

    time delay for load reconnection

    communication (COM)

    2 outputs for data transmission to Dialpact module

    transmitted values all control unit settings

    alarms: Ir warning, fault type, self-monitoringload monitoring thresholds

    current values I1, I2, I3, IN

    power supply by AD module

    STR 58 U

    048449

    (1) Plus the uncertainty of the built-in transformers:3 %.

    (2) Max = In x ... N1/H1 H2 L1

    630 A 22 28 14800 - 1000 A 22 28 101200 - 1600 A 22 24 82000 A 17 20 62500 A 12 14 63000 - 3200 A 10 12 4000 - 6300 A 8 10

    (3) Continuous display for the phase with thegreatest load.

    (4) 0.2 x In to 1200 A without external powersupply or 0.1 x In with external power supply.

    (5) Accuracy with respect to the long time LTprotection.

    (6) Resettable maximum ammeter.

    BTP207E-2.130-STR1858 21/12/01, 9:5118

  • 8/11/2019 Catlogo Masterpact

    28/114

    19Merlin Gerin

    STR 18 M STR 28 D STR 38 S STR 58 UN1, H1, H2 N1, H1, H2 N1, H1, H2, L1 N1, H1, H2, L1

    c c c

    0.5 to 1 (4 settings) 0.5 to 1 (4 settings) 0.5 to 1 (4 settings)

    0.8 to 1 (8 settings) 0.8 to 1 (8 settings) 0.8 to 1 (8 settings)

    fixed fixed adjustable

    120 120 15 30 60 120 240 480

    7.5 7.5 0.94 1.88 3.75 7.50 15 30

    5.2 5.2 0.65 1.30 2.60 5.20 10 21

    c c

    1.5 to 10 15 % 1.5 to 10 15 %

    0 0.1 0.2 0.3 0.4 0 0.1 0.2 0.3 0.4

    0.1 0.2 0.3 0.1 0.2 0.3

    0 80 140 230 350 0 80 140 230 350

    80 140 230 350 500 80 140 230 350 500

    c c c c

    Im = In x ... Im = Ir x ... I = In x ... I = In x ...

    2 x In to Max (2) 1.5 to 10 x Ir fixed at high set (Max) (2) 2 x In to Max (2)

    15 % 15 % 20 % 15 %

    on types N1 and H1 on types N1 and H1 on types N1 and H1

    c c c c

    c c c c

    c c c

    c c c

    c c c

    c c c

    c c c

    I1, I2, I3, IN, Imax (6) I1, I2, I3, IN, Ih, Imax (6) I1, I2, I3, IN, Ih, Imax (6)

    I1, I2, I3 I1, I2, I3 I1, I2, I3

    c c c

    c c

    0.1 at 1 (max 1200 A) (4)15 % 0.1 at 1 (max 1200 A) (4)15 %

    0.1 0.2 0.3 0.4 0.1 0.2 0.3 0.4

    60 140 230 350 60 140 230 350

    140 230 350 500 140 230 350 500

    c c

    c c

    c c

    c

    c

    c

    0.8 to 1 (8 settings) 1 % (5)

    0.5 x tr

    0.25 x tr

    c

    fixed at 10 s

    c

    c

    c

    c

    c

    c

    BTP207E-2.130-STR1858 21/12/01, 9:5119

  • 8/11/2019 Catlogo Masterpact

    29/114

    Merlin Gerin20

    Masterpact: functions and characteristics

    control unit selection (cont.)STR 68 U

    presentationThe STR 68 U control unitoffersmeasurement, supervision and energy

    management functions.Microprocessor technology, liquid crystaldisplay and function keys ensure highaccuracy and easy adjustment.

    The standard STR 68 U control unit providesthe following:

    c universal protection;

    c ammeter function;

    c indication of fault type;c values of interrupted currents;c maintenance indicator;

    c integrated test.

    The following options can be added:c power measurement module (P);c "earth fault" protection module;c control and indication modules (M) with or

    without transmission to a supervisor.Certain M modules can provide loadmonitoring or zone selective interlocking forearth fault protection.

    The STR 68 control unit provides:

    c overload protection, with long timeprotection LT including:

    v adjustable time delay and thermalmemory possibility;c short-circuit protection:v delayed, with short time function ST, forwhich the I2t curve can be disabled by the

    user,

    v instantaneous, with the INST function thatcan be disabled by the user;

    protection

    036630

    c "earth" protectionwith timediscrimination or zone selective interlocking.The protection is of the residual current type(or source ground return type on request).

    basic functions c ammeter;c maintenance indicator;

    c fault indications and values of theinterrupted currents;

    c self-monitoring: in the event of

    overheating of the control unit or amalfunction of the microprocessor, an alarmsignal is transmitted. Unless the "servicecontinuity" option was ordered, the circuit

    breaker will trip ;c test.

    BTP207E-2.140-unit cont. 21/12/01, 9:5120

  • 8/11/2019 Catlogo Masterpact

    30/114

    21Merlin Gerin

    optional functions c power measurement (P);c indication and control (M)Thirty-one different modules offer variouscombinations of functions including:

    v load monitoring,

    v trip indication,

    v self-monitoring,

    v zone selective interlocking for "earth fault"protection,

    v transmission of data to a supervisor(modules M17 to M31 only).Each STR 68 U control unit can be equippedwith only one M module.For the function offered by each M module,

    (see page xxx).

    c "earth fault" protection (T)

    Of the residual current type (or sourceground return type on request), it is possibleto obtain zone selective interlocking bycombining the T option with the appropriate

    M option.

    BTP207E-2.140-unit cont. 21/12/01, 9:5121

  • 8/11/2019 Catlogo Masterpact

    31/114

    Merlin Gerin22

    Masterpact: functions and characteristics

    control unit selection (cont.)STR 68 U

    control unit STR 68 Utype of circuit breaker N1. H1. H2. L1basic protectionlong time protection LT c

    current setting (Ir) adjustable in 2 % steps Ir = In x ... 0.4 to 1 (mini 160 A)

    tripping between 1.05 and 1.20 x Ir

    time delay (tr) adjustable

    accuracy: + 0 - 20 % tr at 1.5 Ir (s) 15 30 60 120 240 480

    tr at 6 Ir (s) 0.94 1.88 3.75 7.50 15 30

    tr at 7.2 Ir (s) 0.65 1.30 2.60 5.20 10 21

    thermal memory (30 mn) standard + OFF position

    short time protection ST c

    pick-up (Im) adjustable in 4 % steps Im = Ir x ... 0.4 to 15 10 %

    time delay (tr) tm setting with I2t OFF 0.1 0.2 0.3 0.4

    tm setting with I2t ON 0.1 0.2 0.3 0.4max. overcurrent time before tripping (ms) 60 140 230 350

    max. break time (ms) 140 230 350 500

    thermal memory (10 mn) standard

    instantaneous protection I c

    fixed pick-up I (kA) M08 to M16 : 65. M20 to M63: 75.

    pick-up (I) adjustable in 8 % steps from In to fixed pick-up (mini at 1.6 kA)

    accuracy 15 %

    OFF switch on front face on types N1 and H1

    basic functionsfault indication

    for tripping on a fault button on front face c

    fault trip alarm contact (SDE) c

    for Ir setting overrun LED on front face c

    self powered cindication of fault type LEDs on front face cand value of interrupted current display on ammeter c

    power supply 110 V - 220 V - 380 V AC 50/60 Hz

    self-monitoring internal overheating and microprocessor errors c

    maintenance indicator c

    displays degree of wear of main contacts between 0 and 655

    ammeter c

    current readings with an accuracy of 3 % I1. I2. I3. Imax (1)

    self-powered c

    integrated test c

    (1) Current of the phase carrying the highest load.

    BTP207E-2.160-STR68U 21/12/01, 9:5222

  • 8/11/2019 Catlogo Masterpact

    32/114

    23Merlin Gerin

    optional functionsearth fault protection: residual current (T) or source ground return (W) type on request c(zone selective interlocking with option M)pick-up (Ih) adjustable in 2 % steps Ih = In x ... 0.2 to 1 (maxi 1200 A. mini 160 A ) 15 %

    time delay (th) th setting 0.1 0.2 0.3 0.4

    max. overcurrent time before tripping (ms) 60 140 230 350

    max. break time (ms) 140 230 350 500

    thermal memory (10 mn) c

    power measurement (P) (see opposite page for details) c

    output characteristics opto-decoupled 0.2 A - 24 V DC

    integrated power supply c

    voltage measurements U12. U23. U31 160 to 690 1 %

    V1N. V2N. V3N 90 to 400 V 1 %

    frequency measurement: f 45 to 65 Hz 0.5 %

    power factor measurement: cos - 1 to + 1 2.5 %

    instantaneous active power measurement: P - 9000 to 9000 kW 5 %

    instantaneous active energy measurement: EP 0 to 9999 MWh 5 %

    indication and control (M): 31 modules (1 per control unit) providing the following combinations: c

    load monitoring 2 possible options

    option 1: 2 load limit pick-ups Ic1 and Ic2 Ic1 = In x ... 0.2 to 1 In 2 % steps

    delay tr1 = 0.5 x tr 5 %

    Ic2 = In x ... 0.2 to 1 In 2 % steps

    delay tr2 = 0.25 x tr 5 %

    option 2: 1 load limit pick-up Ic1 Ic1 = In x ... 0.2 to 1 In 2 % steps

    1 load reconnection pick-up Ic2 delay tr1 = 0.5 x tr 5 %

    Ic2 = In x ... 0.2 to 1 In 2 % steps

    delay tr2 = 60 s fixed 5 %

    zone selective interlocking for earth fault protection

    trip indications

    for type of fault long-time, short-time, earth

    for self-monitoring (1) alarm

    transmission

    characteristics type RS 485

    protocol JBus

    speed 9600 bauds

    max. number of addresses 255

    values transmitted: type of fault tripping on Im, Ir, Ih

    circuit breaker status self-monitoring alarm

    settings all pick-ups and delays

    circuit breaker status open or closed

    values transmitted: ammeter currents I1, I2, I3 max

    power system status voltmeter voltages U12, U23, U31

    voltages V1N, V2N, V3N

    power factor, frequency cos , f

    instantaneous active power and energy: P. EP - 9000 to 9000 kW. 0 to 9999 MWh 5 %

    instantaneous reactive power and energy: Q. EQ - 9000 to 9000 kVar. 0 to 9999 MVahr 5 %

    power supply 24, 48, 125 V DC or 100, 240 V AC

    (1)Depending on the equipment, the "self-monitoring" alarm signal may or may not trip the circuit breaker, see "service continuity" option on the order form.

    BTP207E-2.160-STR68U 21/12/01, 9:5223

  • 8/11/2019 Catlogo Masterpact

    33/114

    Merlin Gerin24

    option m selection Option M can be incorporated in control unitSTR68U to provide the following functions:cRS485 data transmission at 9600 bauds toJBUS protocol;cremote signal via opto-electronic output;czone selective interlocking for earth faultprotection.

    The following table indicates the functions of

    the different versions, designated m01 tom31.For terminal wiring see page xxxx.

    without data transmissionoption m01 m02 m03 m04 m05 m06 m07 m08 m09 m10 m11 m12 m13 m14 m15 m16

    remoting

    load monitoring and control

    pick-up Ic1 indication c c c c c c c c c c

    load shedding c c c c c c c c c c c c c

    pick-up Ic2 indication c c c c

    load shedding c c c c c c c c c

    load reconnection c c c c

    fault indications

    Ir c c c c c c c c c c c

    Im/I c c c c c c c c c c c c c c c c(1)

    Ih c c c c c c c c c c

    self-monitoring c c c c c c c c c

    zone selective interlocking

    on the earth fault protection c c c c c

    with data transmissionoption m17 m18 m19 m20 m21 m22 m23 m24 m25 m26 m27 m28 m29 m30 m31

    data transmission

    all parameters (see page xxxx) c c c c c c c c c c c c c c c

    remoting

    load monitoring and control

    pick-up Ic1 indication c c c

    load shedding c c c c c cpick-up Ic2 indication c

    load shedding c

    load reconnection c

    fault indications

    Ir c

    Im/I c c c c c

    Ih c c c c

    self-monitoring c c c c

    zone selective interlocking

    on the earth fault protection c c c c

    Masterpact: functions and characteristics

    control unit selectionSTR 68 U (cont.)

    (1)Two separate outputs for Im and I.

    BTP207E-2.170-STR68U 21/12/01, 9:5224

  • 8/11/2019 Catlogo Masterpact

    34/114

    25Merlin Gerin

    Factory adjustments

    The STR68U control unit is factory adjustedas follows:

    LT setting Ir In

    time delay tr 480 s

    ST pick-up Im 4 In

    time delay tm 0,2 s

    INST pick-up I maxi

    T earth fault pick-up Ih 0,2 In

    time delay th 0,1 s

    load monitor Ic1 In

    Ic2 In

    Earth fault protection (option T)

    operating zones

    Basic functions: long time LT,short time ST, instantaneous INST

    2

    5

    Ir Im

    3

    I I

    t

    0

    1

    4

    I2t ON

    I2t OFF

    I

    t

    0

    T1

    T2

    I2t ON

    I2t OFF

    overcurrent settings1 : LT setting Ir (long time)2 : LT time delay tr (long time)3 : ST pick-up Im ( short time)4 : ST time delay tm ( short time)5 : INST pick-up I (instantaneous)

    earth fault protection settingsT1 : earth fault pick-up IhT2 : earth fault time delay th

    load monitoring and control(option M)

    Operation with 2 load limit pick-ups

    I

    t

    0

    Ic2

    Ic1

    I

    t

    0

    Ic2

    Ic1

    load monitoring and control settingsIc1 pick-up (load limit)Ic2 pick-up (load limit)

    load monitoring and control settingsIc1 pick-up (load limit)Ic2 pick-up (load reconnection)

    Operation with 1 load limit and 1 loadreconnection pick-up

    E26

    037

    E26

    038

    E26039

    E26042

    BTP207E-2.170-STR68U 21/12/01, 9:5225

  • 8/11/2019 Catlogo Masterpact

    35/114

    Merlin Gerin26

    Masterpact: functions and characteristics

    control unit accessories

    battery module (PIL)Complementary to the local indication of thefaults (F option for STR 38 and STR 58 tripunits), the battery module avoids the need

    for any external power supply to save frontface indications.

    This module is equipped with a button for re-

    activation, of fault indications that have beende-activated by the battery power-savingfeature. A test button is used to check thebattery status.

    interface module ET44Compulsory with the data transmissionoption on the STR 68 trip unit, the ET44interface module allows:

    c setting of the transmission speed;c definition of the address of the breaker(which will not be affected by any drawout

    breaker manipulation);

    c the direct remote control of the breaker,thanks to two outputs directly controlledthrough the data transmission.

    Installation: on vertical plate or symmetricalrail.

    Power supply: 24 V DC with galvanicisolation, or AD type power module.

    0

    48327

    048321

    relay module (MR6)For relaying of information from outputs ofmodules m01 to m32 of control unit STR 68via output changeover contacts10 A/220 V AC or 3 A/24 V DC.

    Installation : on vertical plate or symmetrical

    rail.Power supply module (AD) is required.

    025172

    power supply module (AD)These modules can be used to powercontrol unit complementary functions whichcannot be self-powered by the built-in

    current transformers:cSTR 38 and STR 58: fault type indication(F);cSTR 58: segregated alarm switch (V);cSTR 58: communication option (COM);

    cSTR 28, STR 38, STR 58: ammeter (I) forload less than 20% of In.cSTR 68: indication and saving of

    025173 measurements, alarms, maintenance

    indicator;cMR6 module.Moreover, these modules protect the trip unitfrom transient overvoltages thanks togalvanic isolation.

    Available voltages:c AC 50/60 Hz: 110 V, 220 V or 380 V(20 %; +15 %) (consumption 10 VA);

    cDC : 24/30 V, 48/60 V, 125 V (20 %)(consumption 10 W).

    Installation: on vertical plate or symmetricalrail.

    047035

    052172

    battery module (BAT)Providing a complement to the AD module,

    the battery module provides backup powerfor display indications and maintenanceindicator data in the event of a power failure.

    Float connected between the power supplyand the control unit, it ensures a backup

    time of approximately:

    c 12 h with STR 38 and STR 58 controlunits;c 1.5 h with STR 68 control unit.

    Installation: on vertical plate or symmetricalrail. (ambient temperature from: 0 C to+50 C).

    mini test kit (BU)This self-contained portable unit is used tocheck STR 18 M to STR 58 U control unitsoperations and breaker tripping.Power supply: five 9 V alkaline batteries (notsupplied).

    This test kit is common to the Masterpact,Compact NS, C, CM ranges.

    025171

    portable test kit for STR 18to STR 58The portable test kit is used:cfor control unit STR 68, to power, check

    and carry out adjustments and tests on thebreaker/control unit assembly (control unitwithout auxiliary power supply connected);

    cfor other control units, to check theoperation of the trip unit by measuring theactual trip time:

    vlong-time protection,vshort-time protection,vinstantaneous protection,

    vearth-fault protection.

    Power supply: 110, 220 V AC 50/60 Hz.This test kit is common to the Masterpact,Compact NS, C, CM ranges.

    BTP207E-2.180-unit cont 21/12/01, 9:5626

  • 8/11/2019 Catlogo Masterpact

    36/114

    27Merlin Gerin

    Masterpact: functions and characteristics

    auxiliary power supplies

    The protection functions and most of the

    options available for the STR control unitsare self-powered. An auxiliary power supplyis nevertheless required for certain uses.

    (1)Not recommended: possible with a 24 V DC source, class 2, 5 Watt, ripple factor < 10%.(2)Display will in this case be "". Auxiliary supply allows to save maximeter information.(3)Ih pick-ups for which protection is not self-powered are printed in red on the trip unit front face.

    self-powered auxiliary power supply

    direct AD + BAT terminals battery

    connection modules

    STR 28 / 58

    protection : LT, ST, INST yes

    option I if I u20% In yes

    if I < 20% In no no (1) yes (2) F1/F2 noor single phase load

    option F no no (1) yes F1/F2 yes

    option FV no no (1) yes F1/F2 no

    option ALR yes

    option R yes

    option T/W if Ih u0.2 x In yes

    if Ih < 0.2 x In no (3) no (1) yes F1/F2 no

    STR 68

    protection : LT, ST, INST, T, W yes

    other functions : see drawings page 71

    BTP207E-2.180-unit cont 21/12/01, 9:5627

  • 8/11/2019 Catlogo Masterpact

    37/114

    Merlin Gerin14

    Masterpact: functions and characteristics

    auxiliaries

    electrical operatingmechanismAdded to the manual charging mechanism,a motor charges and automaticallyrecharges the stored-energy spring uponbreaker closing making possible fastO-C-O cycles.Opening and closing operations areinstantaneous.The manual mechanism remains availablefor emergency use.

    The electrical operating mechanismincludes:

    cthe gear motor(MCH);

    ca closing release (XF);ca shunt release (MX) or an undervoltagerelease (MN) for opening;

    c"springs charged" limit switch changeovercontact (CH).

    The addition of the electrical operatingmechanism does not alter circuit breakerdimensions.

    characteristics geared motor MCH

    power supply 50/60 Hz (V) 100/127 - 200/240 - 250/277 - 380 - 415 - 440 - 480

    consumption (VA) 180

    DC (V) 24/30 - 48/60 - 100/125 - 200/250 consumption (W) 180

    motor start-up surge 2 to 3 In for 0.1 s

    charging time 3 to 4 s

    013282

    BTP207E-2.202-circuit-breaker 21/12/01, 9:5814

  • 8/11/2019 Catlogo Masterpact

    38/114

    15Merlin Gerin

    operation counter(CDM)With gear-motor option only. The operationcounter is read from the front and gives thetotal number of breaker operating cycles.

    035932

    BTP207E-2.202-circuit-breaker 21/12/01, 9:5815

  • 8/11/2019 Catlogo Masterpact

    39/114

    Merlin Gerin16

    Masterpact: functions and characteristics

    auxiliaries(cont.)

    Shunt release (MX)

    This release instantaneously opens thebreaker when energised. The supply can bemaintained or automatically disconnected. In

    the latter case, the user can series connectan internal auxiliary contact (OF).

    releasesTwo types of voltage releases can be usedfor remote opening of Masterpact circuitbreakers.

    Undervoltage releases

    cinstantaneous (MN)This release instantaneously opens thebreaker when its supply voltage drops below

    a value between 35 % and 70 % of its ratedvoltage.

    If the release is not energised, the breakercannot be closed (either manually ofelectrically). Any attempt to close will have

    no effect on the main contacts.Closing is possible when the release voltagereaches 85 % of its rated value.

    ctime delayed (MNR)To prevent the breaker tripping in the eventof transient voltage dips, this release has abuilt-in time delay.A special version, available on request,allows instantaneous tripping (from amushroom-head emergency off button) bythe wiring of an external contact.

    closing release (XF)This device releases the breaker closingmechanism when the spring is charged.Energisation can be maintained, as theclosing release provides an antipumpingfunction.

    Note: anti-pumping function:After the breaker has been opened, either by

    fault trip or by manual or electrical operation,anti-pumping is provided by requiringcancellation of the initial closing command

    before reclosure of the breaker is possible.The closing release is supplied on requestwith the manual operating mechanism

    (1)500/525 V AC not available for MNR.

    (2)MNR: DC, 125 V only.

    0

    16813

    036051

    Release combinationsEach Masterpact circuit breaker can beequipped with:1 MX + 1 MN + 1 XF, or2 MX + 1 XF

    characteristics undervoltage and shunt releases closing release

    MN MNR MX XF

    breaker response time 90 ms 5 0.5 s-0.9 s 50 ms 10 70 ms + 10, 15at Un 1.5 s-3 s i3 200 A

    80 ms 10 > 3 200 A

    operating thresholds

    opening from 0.35 to 0.7 Un 0.7 to 1.1 Un

    closing 0.85 Un 0.85 to 1.1 Un

    power supply

    AC 50/60 Hz (V) 100 -110/127 -200 -220/250 -277 -380/415 -440/480 -500/525(1)

    consumption (VA) 20

    DC (V) (2) 24 - 30 - 48 - 60 - 100/110 - 125 - 200/220 - 250

    consumption (W) 15

    BTP207E-2.204-auxiliaries 21/12/01, 10:0816

  • 8/11/2019 Catlogo Masterpact

    40/114

    17Merlin Gerin

    Changeover switches to indicate "connected"position "CE"

    Double break changeover switches "OF"

    auxiliary switchesIn addition to the main contact positionindication on the front, 3 auxiliary switchblocks are available to indicate the open andclosed breaker positions.cstandard: 4 contacts (O) (2 normallyopen 2 normally closed);coptional: 4 directly-operated double

    break changeover switches (OF)whichoperate only when the minimum isolatingdistance between the main contacts is

    reached;coptional: 24 additional changeoverswitches (OFSUP block).Thesemicroswitches can be parallel connected inpairs to increase the rated current and

    breaking capacity (in drawout version only).

    "ready to close" contact(PF)Optional:This contact simultaneously indicates the

    following:cthe breaker is open;cthe stored-energy mechanism is charged;

    cthe mechanism is correctly reset;cthe breaker opening pushbutton is notlocked;

    cno opening order is present.

    This contact can be series connected to theclosing release (XF) to disable the anti-pumping function.

    connected/disconnectedposition carriage switchesIn addition to the local "connected/test/

    disconnected" position indicator, two seriesof optionalcarriage switches are availablefor the fixed chassis (of drawout circuit

    breaker).ca block of 4 changeover switchestoindicate "connected" position (CE);

    ca block of 2 changeover switchestoindicate "disconnected" position (CD). Thedisconnected position is indicated only whenthe minimum isolating distance betweenmain and auxiliary circuits has beenreached.

    By series connection of these contacts thetest position can be indicated.c1 changeover switchto indicate "test"position (CT).

    contact characteristics

    "spring charged"contact (CH)In addition to the local mechanical indicatorand the "ready to close" contact, the gear-motor limit switch changeover contact canindicate that the operating mechanism isready (spring charged). This contact issupplied as standard with the gear motor.

    fault-trip indication (SDE)As standard and independent from thedifferentiated fault indications on the controlunit, any fault-trip is indicated by:c1 fault-trip indicator/reset button;c1 changeover contact (SDE).

    The reset button must always be pressedafter a fault-trip to enable breaker closing.Optional: automatic reset, allowing remotebreaker closing without local resetting (the

    SDE contact operates up to the reset).

    auxiliary contacts type O OF OFSUP SDE PF CE CD CT CH

    quantity changeover 4 24 1 1 4 2 1 1

    NO 2 NO

    NC 2 NC

    current rating (A) 10 10 10 10 10 10 10 10 10

    breaking capacity 110 V 15

    AC 50/60 Hz(A rms.) 240 V 10 10 10 10 10 10 10 10 10

    pf u 0.3 380 V 6 10 6 5 5 6 6 6 6

    480 V 6 10 6 6 6 6 6

    600 V 3 6 3 3 3 3 3DC(A) 48 V 3 5 3 3 3 3 3 3 3

    L/R i 0.01 s 125 V 0.5 3 0.5 0.3 0,3 0.5 0.5 0.5 0.5

    250 V 0.25 3 0.25 0.15 0.15 0.25 0.25 0.25 0.25

    500 V 0.5

    0

    16814

    018242

    016524

    Additional changeover switches ("OFSUP" block)

    BTP207E-2.204-auxiliaries 21/12/01, 10:0817

  • 8/11/2019 Catlogo Masterpact

    41/114

    Merlin Gerin18

    a: partitioning fixture (AC)b: interphase barrier (EIP)

    Fixed portion of drawout circuit breakers with arc chute andterminal shield

    035928

    Fixed portion of drawout circuit breakers with safety shutters

    safety shutters (VO)Optional:mounted on the fixed portion ofdrawout breakers, the safety shutters

    automatically block access to thedisconnection contacts when the breaker isin the disconnected or test position (degree

    of protection IP 20).

    Masterpact: functions and characteristics

    accessories

    terminal shield (CB)Optional:attached to the fixed portion ofdrawout circuit breakers, this cover preventsaccess to the electrical auxiliary connectionterminals.

    arc chute cover (CC)Optional: attached to the fixed portion ofdrawout circuit breakers or on the fixedcircuit breaker, this cover eliminates the

    safety clearance requirement above thebreaker (this option is incompatible with frontconnection on top).

    interphase barrier(EIP)Optional:attached to the fixed portion ofdrawout breaker (Masterpact iM40 3P), theinsulated partitions for vertical installationbetween connection pads to:creinforce insulation at connection points ininsulated busbar installation;cprevent arc propagation to the breaker inthe event of a line side fault on the mainbusbars.

    partitioning fixture (AC)Optional:attached to the fixed portion ofdrawout breakers (except when equippedwith front connections), this fixture providesIP30 partitioning between the breakercompartment (accessible from the front) andthe connection zone (located in the rear). It

    simplifies partition cut-outs.Example of partition cut-out forMasterpact M08 to M32.

    shutter lock (VVC)Optional: mounted on the fixed portion ofdrawout breakers, a mobile and lockable

    slide (padlocks not supplied) is used to:clock the shutters in the closed position;,chold the shutters in the open position.

    A support is provided at the back of theframe to hold the slide when not in use. Asecond slide is supplied:con request for Masterpact i 3200 A ;cin standard for Masterpact 4000 Ato 6300 A.

    360

    445 (3 ples) et 560 (4 ples)

    60

    plan de fixationchssis

    rfrence

    445 (3 pole) and 560 (4 pole)

    chassis

    fixingdatum

    016818

    013280

    a b

    28518

    BTP207E-2.206-accessories 21/12/01, 10:0918

  • 8/11/2019 Catlogo Masterpact

    42/114

    19Merlin Gerin

    Auxiliaries for drawout version

    Auxiliaries for fixed version

    016814

    door frame (CDP)Optional:fixed to the cublicle door, thisframe provides an equipment seal function

    (degree of protection IP 405).Suitable for fixed and drawout patterns.

    Earth connectionThe earth connection terminal (drawoutpattern) is on the left hand side of thechassis. It is marked with the symbol t

    transparent cover (CCP)Optional:hinge-mounted and equipped witha screw-closure, this cover is designed forthe door frame (CDP). It provides a degreeof protection of IP549.Suitable for fixed and drawout patterns.

    01

    6819

    auxiliaries connection

    Fixed versionConnection by one or two plugs,disconnectable and accessible from the front(screwless tunnel terminals for flex cable upto 2.5 mm2).

    Drawout versioncstandard: connection to a terminal blockin the front of the fixed frame (screwless

    tunnel terminals for flex cable up to2.5 mm2).The breaker auxiliary circuits are connected

    by connection blocks that operateautomatically to isolate the auxiliaries whenthe breaker is in "disconnected" position.

    On request, an additional 5-way terminalblock (BS) is available to provide five

    common points.

    coptional: by one or two plugs,disconnectable and accessible from the

    front, installed on the mobile part of theassembly.

    "Connected/disconnect/test" positioncontactsInstalled on the fixed chassis, these contacts

    are directly connected by 6.35 mmconnectors.

    015561

    breaker mismatchprotectionOptional:for drawout version only, thissystems allows only correctly matchedbreakers (rating, type wiring, etc.) to beinserted in a given fixed frame.Two matching parts (1 for the fixed chassisand 1 for the mobile assembly) can be usedto create 20 different user selectedcombinations.

    035940

    BTP207E-2.206-accessories 21/12/01, 10:0919

  • 8/11/2019 Catlogo Masterpact

    43/114

    Merlin Gerin20

    "disconnected","connected" and "test"position locking (1)

    Mounted on the frame and accessible withthe cubicle door locked, this system isavailable in two versions:

    c"disconnected" position locking;

    vas standard by 1 padlocking device (1 to 3padlocks not supplied),

    voptional:by a locking device with 1 or 2

    Profalux key locks;c"disconnected", "connected" and "test"

    position locking (optional);

    vby 1 padlocking device, with 1 to 3padlocks not supplied (VEC),

    vby 1 locking device, with 1 or 2 Profaluxkey locks (VSPEC),

    padlocks 1 keylock 2 keylocks

    "disconnected"standard

    "disconnected" "disconnected"standard optional

    "disconnected" "disconnected" "disconnected"standard optional optional

    "disconnected,connected"

    "disconnected, "disconnected,

    connected" connected""disconnected, "disconnected, "disconnected,connected" connected" connected"

    pushbutton locking deviceOptional: this padlockable device (padlocksnot supplied) prevents direct operation of thecircuit breaker by covering the "on" and "off"pushbuttons. This locking device can also beused for lead sealing.

    Masterpact: functions and characteristics

    accessories (cont.)

    (1) keylock typesProfalux B24 D4ZRonis 1351 BKirk CN22-12

    Castell SK7113/1Trayvou L1P1E

    "off" position lockingdeviceOptional:a Profalux key lock locks thebreaker in "off" position by holding thepushbutton in its depressed position.

    pushbutton locking deviceby padlocks (not supplied) VBP

    "off " position locking device (1)

    1 Profalux key lock VSPA1

    2 Profalux key locks, identical profiles VSPA2

    adaptation fixture for 1 Profalux key lock, lock not supplied VSPRAC

    On request1 Ronis key lock VSRA1

    2 Ronis key locks, identical profiles VSRA2

    adaptation for 1 Castell key lock, lock not supplied VSCA

    adaptation for 1 Kirk key lock, lock not supplied VSKA

    Remarkscthe keylocks are of the captive key type,i.e. key free when locked;cProfalux and Ronis keylocks can be usedtogether;

    ca second Profalux or Ronis lock, identicalto the one mounted on the chassis, can besupplied separately.

    035932

    035931

    BTP207E-2.208-accessories 21/12/01, 10:0920

  • 8/11/2019 Catlogo Masterpact

    44/114

    21Merlin Gerin

    016817

    "disconnected" position lockingby padlocks (not supplied) as standard

    1 Profalux key lock VSPC1

    2 Profalux key locks, identical profiles VSPC2

    2 Profalux key locks, different profiles 2 VSPC1

    adaptation fixture for Profalux key lock (lock not supplied) VSPRCC

    On request

    1 Ronis key lock VSRC1

    2 Ronis key locks, identical profiles VSRC2

    2 Ronis key locks, different profiles 2 VSRC1

    adaptation fixture for Castell key lock (lock not supplied) VSCC

    adaptation fixture for Kirk key lock (lock not supplied) VSKC

    adaptation fixture for Trayvou key lock (lock not supplied) VSTC

    "disconnected", "connected" and "test" position lockingby padlocks (not supplied) VEC

    1 Profalux key lock VSEPC

    2 Profalux key lock, different profiles 2 VSEPC

    On request

    1 Ronis key lock VSERC

    2 Ronis key locks, differents profiles 2 VSERC

    adaptation fixture for Castell key lock (lock not supplied) VSECC

    adaptation fixture for Kirk key lock (lock not supplied) VSEKC

    door interlockOptional: mounted on the chassis, this lockprevents the cubicle door from being openedwhen the breaker is in the "connected"position. If the breaker is put into the"connected" position with the door open, the

    latter can be closed without disconnectingthe breaker.

    racking interlockOptional: this lock prevents insertion of thebreaker racking handle when the cubicle

    door is open. It can be defeated by pressingon the unlocking mechanism.

    withdrawal/spring chargedinterlockOptional: this lock prevents withdrawal ofthe breaker from the chassis when the

    springs are charged.Incompatible with MN or MNR release.

    a: racking interlockb: door latch

    door interlock

    right-hand side VPECD

    left-hand side VPECG

    racking interlock VPOC

    withdrawal/spring charged interlock VEAA

    a b

    BTP207E-2.208-accessories 21/12/01, 10:0921

  • 8/11/2019 Catlogo Masterpact

    45/114

    Merlin Gerin36

    Masterpact: functions and characteristics

    automatic source-changeover systems

    Masterpact