Upload
baxi-spa
View
240
Download
7
Tags:
Embed Size (px)
DESCRIPTION
Luna Platinum 12-32 kW Luna SAT 135 173 203 226 Water in heating system for housing applications Close examination: 95 P. 2 P. Technical specifications 4 Dimensions 5 Diagrams 6 Burner exchanger unit 7 Wiring diagrams 8 Wiring diagram for connection to an heating system and/or to a cylinder for DHW production 9 Solutions for centralized heating systems installations 3
Citation preview
2Index
Modular condensing generators (GMC) 85
95
135
173
203
226
Luna Duo-tec MP 35 - 110kW 3
P.
Luna Platinum 12-32 kW
Power HT 45-150 kW
Power HT 230-320 KW
Close examination:
Water in heating system for housing applications
Luna SAT
3Solutions for centralized heating systems installations
Luna Duo-tec MPP.
Technical specifications 4
Dimensions 5
Diagrams 6
Burner exchanger unit 7
Wiring diagrams 8
Wiring diagram for connection to an heating system and/or to a cylinder for DHW production
9
Coxial flue system installation 10
Coxial flue system accessories 12
Dual flue system installation 13
Dual flue system accessories 15
Dual flue system accessoires 80 17
Flexible ducting system accessories 80 16
Electronics 18
Programming, setting and digital control 19
Remote control THINK 20
Single installation 21
Single installation schemes 33
Cascade installation 44
Cascade installation schemes 55
Hydraulic separators 73
Condensate neutralizer kits 79
Other accessories 80
41.35 1.50 1.60 1.70 1.90 1.110
Maximum heating heat input kW 34,8 46,3 56,6 66,9 87,4 104,9
Maximum heating heat output 80/60C kW 33,8 45 55 65 85 102
Maximum heating heat output 50/30C kW 36,5 48,6 59,4 70,2 91,8 110,2
Minimum heat output 80/60C kW 5 5 6,1 7,2 9,7 11,7
Minimum heat output 50/30C kW 5,4 5,4 6,6 7,8 10,2 12,3
Energetic efficiency 92/42/CEE HHHH HHHH HHHH HHHH HHHH HHHH
Average efficiency (DIN4702-T8) % 109,8 109,8 109,8 109,8 109,8 109,8
Nominal efficiency 80/60C % 97,4 97,4 97,2 97,2 97,3 97,2
Nominal efficiency 50/30C % 105 105 105 105 105 105
Efficiency at 30% % 107,7 107,8 107,4 107,6 107,3 107,4
Minimum flow on the exchanger lt/h 800 800 1000 1500 2000 2250
Nox class (EN483) 5 5 5 5 5 5
Minimum working temperature C -5 -5 -5 -5 -5 -5
Water content lt 4 4 5 6 9 10
Quantity of condensing lt/h 3,7 4,1 5,5 7,3 9,2 11,1
Heating system max pressure bar 4 4 4 4 4 4
Safety valve intervention pressure bar 4 4 4 4 4 4
Regulation of water temperature in heating circuit
C 25/80 25/80 25/80 25/80 25/80 25/80
Coaxial flue system m 80/125 80/125 80/125 80/125 110/160 110/160
Dual flue system m 80+80 80+80 80+80 80+80 110+110 110+110
Maximum flue mass flow rate kg/s 0,016 0,021 0,026 0,031 0,04 0,047
Minimum flue mass flow rate kg/s 0,002 0,002 0,003 0,004 0,005 0,005
Maximum flue temperature C 76 80 80 74 70 70
Residual flue prevalence Pa 200 270 270 270 320 370
Comburent air-flow at Qn kg/s 3,7 4,9 6 7,1 9,3 11,1
Dimensions (hxwxd) mm 766x450x377 766x450x377 766x450x377 766x450x505 952x600x584 952x600x584
Net weight kg 40 40 40 50 83 93
Type of gas natural gas/LPG natural gas/LPG natural gas/LPG natural gas/LPG natural gas/LPG natural gas/LPG
Power consumption W 180 190 210 210 275 320
Power consumption in stand-by way W 5 5 5 5 5 5
Max lenght of the duct of the outdoor sensor m 120 120 120 120 120 120
Noise (1 mt far from the boiler) dBA
5Solutions for centralized heating systems installations
Dimensions
risks of corrosion due to condensate. The modulating pump fully optimises the boilers yield, precisely adjusting capacity in
order to obtain an optimal temperature difference between delivery and return. Lastly, the wide modulation range of the burner
means that boiler power can be best adapted to the required thermal load. Adjustment of the various generator components
is carried out by a digital PCB with latest generation double microprocessor, resulting in simple and reliable management of
the boiler through a control panel with large LCD. As well as daily and weekly programming of heating and sanitary functions
and the setting of climatic adjustment in accordance with the users criteria of comfort, the electronics system also permits easy
integration with renewable energy heat generation system by programming a series of regulating parameters with which the
generator can be configured to optimise its performance in relation to the type of system it will be working on. Further proof of
the great flexibility of this range of boilers in highly diversified contexts.
GASS.C. M.R. R.R. GASS.C. M.R. R.R.
GAS Gas inlet G 1M.R. Heating system flow (G1-G1/2) with cylinder connection optionR.R. Heating system return (G1-1/2) with cylinder connection optionS.C. Condensing trap that can be installed on a 21 pipe
Luna Duo-tec 1.90-1.110
GAS Gas inlet G M.R. Heating system flow (G1) with cylinder connection optionR.R. Heating system return (G1) with cylinder connection optionS.C. Condensing trap that can be installed on a 21 pipe
Coaxial flue system 110/160Dual flue system 110
Luna Duo-tec 1.35-1.50-1.60-1.70
(A)
(A) 377 mm Mod.1.35-1.50-1.60 505 mm Mod. 1.70
450
225 225 229
140
763
584
112
600
354,5 245,522
395
2
Coaxial flue system 80/75Dual flue system 80
6DiagramsThe following diagrams, over and above supplying a better definition of the plan of the system, permit a more detailed analysis of how the generator behaves under different working conditions.The pump capacity-prevalence curve defines the dynamic characteristics of the BAXI circulator in the hydraulic unit. It is well known that the temperature of the return water has a direct influence on the performance of a condensation boiler. At very low temperatures there is better exploitation of the latent heat and consequently better boiler performance. The diagram shows the variations in performance as a ratio between the capacity and thermal power of the specified condensation generator in function of the boilers return temperature. The final diagram shows the trend of the generator flue temperature in function of the return temperature.
30 35 40
Effic
iency
of t
he b
oiler
%
Return temperature of the system C
EFFICIENCY OF THE BOILER ACCORDING TO THE RETURN TEMPERATURE
30% load100% load
45 50 55 60979899
100101102103104105106107108
30 35 40 45 50 55 6030354045505560657075
100% load
30% load
Flues
tem
pera
ture
%
Return temperature of the system C
FLUES TEMPERATURE ACCORDING TO THE RETURN TEMPERATURE
FLOW RATE/HEAD CURVE
FLOW RATE/HEAD CURVE
FLOW RATE (l/h)
FLOW RATE (l/h)
HEAD
(mH 2
O)HE
AD (m
H 2O)
FLOW RATE/HEAD CURVE
FLOW RATE/HEAD CURVE
FLOW RATE (l/h)
FLOW RATE (l/h)
HEAD
(mH 2
O)HE
AD (m
H 2O)
FLOW RATE/HEAD CURVE
FLOW RATE/HEAD CURVE
FLOW RATE (l/h)
FLOW RATE (l/h)
HEAD
(mH 2
O)HE
AD (m
H 2O)
FLOW RATE/HEAD CURVE
FLOW RATE/HEAD CURVE
FLOW RATE (l/h)
FLOW RATE (l/h)
HEAD
(mH 2
O)HE
AD (m
H 2O)
7Solutions for centralized heating systems installations
Burner-exchanger unitThe air-gas premixing unit, the burner and the primary exchanger are the components that ensure high performances from these
condensing heat generators.
The premixing unit is a new conception which, thanks to a new design and the double clapet technique, ensures that the burner
constantly has an optimal air/gas ratio independently from the number of fan revs, keeping consumption to a minimum and
always guaranteeing correct combustion and consequently a reduction in polluting emissions. On the same subject of energy
saving and highest performances, this new component permits achievement of a modulation ratio of 1:9, giving the generator
such great flexibility as to be adaptable to great variations in thermal load, as happens increasingly in new generation multifamily
homes.
In the range from 35 to 70 kW the stainless steel burner, through the internal diffuser and special micro-perforation on the
cylindrical surface, achieves uniform distribution of the air/gas mixture independently of its length. In the power range of 90 to
110 kW the burner is in metal fibre. This produces a spread of very short flame for optimal heat radiation while minimising the
formation of nitrogen oxides.
In the range from 35 to 70 kW the primary exchanger, entirely in stainless steel, comprises one single burner/fumes chamber,
which keeps the size of the generator down for high power and actually more versatile installations even in relatively restricted
spaces. The two highest powered generators (90 and 110 kW) employ the dual chamber exchanger in stainless steel. The two
cylindrical fumes chambers set vertically (burner chamber and condensation chamber) contain the stainless steel coils that carry
the primary circuit water. In the upper chamber the hot exhaust gases transfer heat to the system return water in the coils,
bringing about condensation of the fumes themselves and thus transferring the latent heat to the water, preheating it prior to its
entry into the burner chamber.
Primary exchanger
Primary exchanger
Chamber of the burner
Condensation chamber
Flues outlet
Burner
BurnerCoils
Coils
VenturiGroup
VenturiGroup
Fan
Fan
Mixer
Mixer
Air - gas conveyor
Air - gas conveyor
Luna Duo-tec MP 1.35 - 1.50 - 1.60 - 1.70 Luna Duo-tec MP 1.90 - 1.110
8Wiring diagramsThe figure shows the hook-up diagram for the boiler PCB connectors. Sensors and functional components of the generator are
controlled by the PCB to which they are connected by means of the internal connectors highlighted in the figure.
Another 3 connectors accessible externally to the board are available for checking the devices servicing and regulating the
thermal system (pumps, outdoor sensor, room thermostat etc.).
1Fuses
2P
ower supply 230 V
3R
oom U
nit4
Heating flow
sensor5
Heating return sensor
6P
ressure sensor7
Fume sensor
8S
anitary water heater sensor
9A
uxiliary sensor 110
Auxiliary sensor 2
11E
xternal sensor12
Rem
ote Control
13B
oiler pump
Flame detection electrode
1415S
witch on electrode
16Igniter
17G
as valve 18
Safety therm
ostat 105C19
Fan20
Heating circuit pum
p21
Sanitary w
ater heater pump
CB
lueM
Brow
nN
Black
RG/VR
edY
ellow/G
reenV
Green
BW
hiteG
Grey
YY
ellowP
Violet
9Solutions for centralized heating systems installations
The boilers in the high power wall-mounted BAXI range are easily hooked up to a heating system and a sanitary water heater by means of the terminal blocks in the dashboard. The connections, with related diagram and instructions, are shown below. The pumps for the heating system (P1) and the sanitary hot water (P3) must be supplied in accordance with the diagram in the figure, inserting a relay between the boiler PCB and the pumps.The sanitary water circuit pump (P3), serving an external heater, must be connected to boiler Terminal Block M3 at terminals 4 and 5. It is always advisable to connect the sanitary circuit pump (P3) after a hydraulic separator (as shown in the figure). Connect the NTC probe for sanitary water precedence, supplied as an accessory, to terminals 9 and 10 of boiler Terminal Block M2. The sensitive element of the NTC probe must be inserted into the special housing in the heater.Regulation of the temperature of hot sanitary water and the selection of the time schedule programme can be carried out directly on the boiler control panel, as described in the manual supplied with the product.When the hydraulic separator is used, for installation of a recirculation pump on the DHW tank heater the following accessories are required: clip-in module THINK, to be installed in the boiler dashboard.
Wiring diagram for connection to an heating system and/or to a cylinder for DHW production
P1
P3
Circulatingpump
Clip-inmodule
10
Coaxial flue system installationThe installation of the boiler can be made easily and with flexibility thanks to the supplied accessories. The boiler is originally equipped for a coaxial flue system, vertical or horizontal. Through the dual flue duct, it is possible a dual flue system installation.
* 15 meters is the maximum length of flue system
Type of ductsMax length flue
pipes
For each 90 installed curve the max length decreases of
For each 45 installed curve the max length decreases of
Diameter of the chimney terminal
Diameter of the external duct
Coaxial 110/160 mm 10m 1m 0,5m 163mm 160mm
Vertical dual flue system
15m 0,5m 0,25m 163mm 110mm
Coaxial 80/125 mm 10m 1m 0,5m 133mm 125mm
Vertical dual flue system
15m 0,5m 0,25m 133mm 80mm
Horizontal dual flue system*
60m 0,5m 0,25m - 80mm
COAXIAL FLUE SYSTEM
LUNA DUO-TEC MP 1.35 - 1.50
1.60 - 1.70 = 80/125 mm
LUNA DUO-TEC MP 1.90 - 1.110
= 110/160 mm
DUAL FLUE SYSTEM
LUNA DUO-TEC MP 1.35 - 1.50
1.60 - 1.70 = 80+80 mm
LUNA DUO-TEC MP 1.90 - 1.110
= 110+110 mm
11
Solutions for centralized heating systems installations
Coaxial flue system installation
Lmax = 10 m Lmax = 10m
Lmax = 9 m
Lmax = 9 m
L
L
L
L
Examples of installation with horizontal flue system 80/125 mm (Luna Duo-tec MP 1.35-1.50-1.60-1.70 kW) and 110/160 mm (Luna Duo-tec MP 1.90-1.110 kW)
80/125 and 110/160
Examples of installation with vertical flue system 80/125 mm (Luna Duo-tec MP 1.35-1.50-1.60-1.70 kW) and 110/160 mm (Luna Duo-tec MP 1.90/1.110 kW) The installation can be made both with pitched and flat roof using the chimney accessory and the special tile available as option
80/125 and 110/160
Lmax = 10 m Lmax = 10 m Lmax = 8 m Lmax = 9 m 80/125 mm
12
Coaxial flue system accessories Luna Duo-tec MP 1.35-1.50-1.60-1.70
Luna Duo-tec MP 1.90-1.110
Picture Description Code
PP coaxial flue pipe with terminal 80/125 L=1000 mm supplied with wind proof terminal and sealing collar
KHG 714088910 .
PP coaxial flue pipe extension 80/125 L=1000 mm KHG 714088511 .
PP coaxial flue pipe extension 80/125 L=500 mm KHG 714088610 .
PP coaxial 90 bend - 80/125 KHG 714088711 .
PP coaxial 45 bend - 80/125 KHG 714088811 .
PP vertical chimney terminal 80/125 KHG 714093510 .
Flat roof tile to be used with a vertical chimney terminal 80/125
KHG 714093610 .
Pitched roof tile to be used with a vertical chimney terminal 80/125; it is adjustable from 15 to 45
KHG 714093710 .
Picture Description Code
PP coaxial flue pipe extension 110/160 L=1000 mm KUG 714133810 .
PP coaxial flue pipe extension 110/160 L=500 mm KUG 714133710 .
PP coaxial 90 bend - 110/160 KUG 714133610 .
PP coaxial 45 bend - 110/160 KUG 714133510 .
PP vertical chimney terminal 110/160 KUG 714133410 .
PP horizontal coaxial chimney 110/160 KUG 714133310 .
Flat roof tile to be used with a vertical chimney terminal 110/160
KHG 714104810 .
Pitched roof tile to be used with a vertical chimney terminal 110/160; it is adjustable from 15 to 45
KHG 714104910 .
13
Solutions for centralized heating systems installations
Coaxial flue system accessories Dual flue system installationThis type of duct allows the discharge of flues that derives from the combustion both out of the building and in single flues. The intake of the comburent air can be made in zones which are different from those of the dischargeThe dual flue system accessory includes flue reduction ( 125/80) and an intake connection .The gasket and the screws of the intake connection to be used are those taken before from the cap.
The 90 bend allows to connect the boiler to the flues discharge/intake in any direction thanks to the 360 rotation possibility. It can be used as additional bend together with the flue or the 45 bend.
229225144
140
Luna Duo-tec MP 1.35
14
Installation examples with horizontal dual flue system.
The minimum slope of the flue discharge towards the boiler has to be 1 cm for each meter of length. Make sure that the flue discharge and air intake are well fixed on the wall..
Installation examples with vertical dual flue system
(L1 + L2) max = 60 mL max=15 m
L max=15 m L max=14 m
The air inlet has a maximum length of 15 meters.
15
Solutions for centralized heating systems installations
Dual flue system accessories 80
Picture Description Code
PP dual flue system 80 it includes: flue reduction, intake connection
KHG 714089010 .
PP pipe extension 80 L=1000 mm KHG 714059411 .
PP pipe extension 80 L=500 mm KHG 714059910 .
PP pipe extension 80 l=250 mm 710718301 .
PP 87 bend 80 KHG 714059211 .
PP 45 bend 80 KHG 714059311 .
Pipe 80 centring kit (pack of 5) KHG 714037411 .
Clamp centring kit 80 KHG 714106110 .
Pipe 80 supporting bracket (pack of 5) KHG 714037310 .
Internal sealing collar 80 KHG 714018510 .
External sealing collar 80 KHG 714018411 .
Coaxial vertical chimney terminal 80/125 KHG 714093510 .
Dual flue pipes adapter for coaxial chimney KHG 714093810 .
Flue terminal 80 LSD 790000150 .
Dual flue terminal 80 KHG 714010410 .
Flat roof tile 125 to be used with a vertical chimney terminal
KHG 714093610 .
Pitched roof tile 125 to be used with a vertical chimney terminal; it is adjustable from 15 to 45
KHG 714093710 .
Luna Duo-tec MP 1.35
16
Flexible ducting system accessories
Picture Description Code
PP flexible pipe 80 L= 1,5 m KHG 714105710 .
PP flexible pipe 80 L= 20 m KHG 714105810 .
PP tee joint 80 with supporting bracket and condensate drainings
KHG 714105910 .
PP 90 bend 80 with supporting bracket KHG 714106010 .
Flexible centring kit 80 (pack of 3) KHG 714106210 .
Triple lips gaskets kit 80 (pack of 5) KHG 714111210 .
Luna Duo-tec MP 1.35
17
Solutions for centralized heating systems installations
Dual flue system accessories 110
Immagine Descrizione Codice
PP dual fllue kit 110/110 710631401 .
PP pipe extension 110 L=1000 mm KUG 714133210 .
PP pipe extension 110 L=500 mm KUG 714133110 .
PP pipe extension 110 L=250mm 710718501 .
PP 90 bend 110 KUG 714133010 .
PP 45 bend 110 KUG 714132910 .
PP vertical chimney terminal 110 KUG 714132810 .
PP horizontal chimney terminal 110 KUG 714132710 .
Flat roof tile to be used with a vertical chimney terminal 110/160
KHG 714104810 .
Pitched roof tile to be used with a vertical chim-ney terminal 110/160; it is adjustable from 15 to 45
KHG 714104910 .
Luna Duo-tec MP 1.90-1.110
18
Electronics
Regulation of sanitary water temperatureTemperature reduction
Regulation of heating water temperatureTemperature increase
Functioning mode Sanitary, Sanitary & Heating, Heating Only
Troubleshooting
Regulation of sanitary water temperatureTemperature increase
Regulation of sanitary water temperatureTemperature reduction
Boiler functioning information Off, Reset, Exit menu/functions
The whole range of LUNA DUO-TEC MP high power wall-mounted boilers are equipped with an extensive control panel: each key activates a specific function and the LCD simultaneously shows numbers and symbols indicating the functioning status, facili-tating easy interpretation and immediate programming, adjustment and control of parameters.
The boiler electronic PCB has been specially designed to run premixing condensation boilers and permits start-up, control and supervision of this kind of gas fired heat generator with view to obtaining best use of the burner for applications in the field of central heating and the generation of hot sanitary water. Indubitably the most important feature of this new generation of electronic boards is its ability to integrate different heat gen-eration technologies through the use of small interface boards and by means of a communication protocol that allows dialogue among the various parts of the heating system.
All the control, management and communications software (meaning the whole intelligent part of a heating system) resides in the boiler PCB, so the only interfaces needed for integration with other types of generator are hardware items such as extensions of connectors on the motherboard and, where required, an additional display (text knob) for the parameter programming of a complex heating system.
Features: double microprocessor: latest generation software for control of the generator, or also of a complete heating system. management of primary circuit pump modulation by PWM controller daily heating programme and generation of hot sanitary water electronic thermometer automatic troubleshooting: signalling and description of possible anomalies incorporated climatic regulation (external probe available as optional) automatic summer/winter changeover with external probe connected preset for installation in cascade with control software included in the PCB preset for installation in mixing systems (low and high temperature)
19
Solutions for centralized heating systems installations
Programming, setting and digital control
Picture Model Description Code
Remote control THINK
The room unit is an accessory for controlling the temperature of the space to be heated. It is not only a modulating climate controller, capable of adjusting the delivery temperature from the boiler to obtain the desired room temperature with greatest efficiency: it also functions as a programmer, setting heating system parameters. including boilers in cascade and various low temperature zones.
710244202 . (wired)710244302 . (wireless)
Programmable clip-in module THINK
With this accessory the device can run: heating circuits at different temperatures, solar system and other specific applications (pools, sanitary recirculation pump etc.). This accessory can directly manage the circuitcomponents (pump, temperature sensor, mixing valve etc.) up to a maximum of 3 independent relayoutlets, 2 temperature sensors and 1 control inlet. Some predefined functions can be used.
710034502 .
Interface kit for boilers in cascade THINK
Interface kit for boilers in cascade is an electronic device that permits communication via bus (two cables) between boilers connected in cascade or between one boiler (or the boilers in cascade) and a mixing zone controller.
710440802 .
Programmable external module THINK
Use of the external module means that a heating system with max 16 boilers in cascade can be run, with separate storage for hot sanitary water where required. This accessory, connected to one of the boilers, can directly control the circuit components up to a max of 3 independent relay outlets, 2 inlet temperature sensors, 1 connector for limit thermostat in HV and one control inlet (for example TA).
710503704 .
Outdoor sensor THINK*
Outdoor sensor is a temperature sensor which communicates to the boiler the temperature outside the dwelling so that the generator adapts the flow temperature to the effective needs of heating the environment as set by the user.
710487301 . (wired)710302701 . (wireless)
Interface kit for remote control THINK - 5 leds wireless
This accessory allows to install the control panel wireless in a representative room. It can be used to control the room temperature and to set and control a heating circuit including a cascade installation and several low temperature zones
710244102 .
Heating controller for mixing zones THINK
Heat regulation control unit for piloting a mixing zone (usually low temperature). It can run a mixing valve, a pump and the flow sensor of the controlled zone. It can also exchange data with the boiler board by means of the connection bus.
710519902 .
* wireless model to be ordered with the interface kit for remote control THINK - 5 leds (710244102 .) or the wireless aerial (710234301 .)
20
Remote control THINKRemote control THINK is a multifunctional accessory to control the temperature of the room to heat. It is a modulating climatic regulator that adjusts the flow temperature of the boiler to obtain the desired room temperature and the best efficiency.Setting times, it is possible to adjust the functioning of the heating circuit and DHW production Setting Holiday it is possible to set specific periods of the boiler functioning when you are not at home. You can set specific function to adjust the gas valve and to control the cleanliness of the combustion flues. In case of anomaly it shows the error code of the anomaly and a short description
In case of cascade installations, the remote control THINK allows to set and show parameters of the cascade system. This is not possible through the control panel for Luna Duo-tec MP range of boilers so it is necessary to use this accessory in high efficiency condensing applications.This accessory can be installed in a separate room, that can be far from the installation place of the generator allowing an easier control.A wireless version of the remote control is available as well, when the extension of connection cables is difficult.
DHWprogramming
Room temperaturecomfort mode
Roomtemperature
Date: day, month,year, time
Outdoortemperature
Boiler pressure/heating circuit
Navigation knob/ menuregulation and programming
End user menu 1 Standby/operation2 Hot water boost3 Central heating mode4 Room temperature5 Hot water mode6 Hot water temperature set-point
Complete menu 1 Information2 Set time and date3 Operator unit4 Time central heating 15 Time central heating 36 Time hot water7 Time auxiliary8 Holiday heating 19 Heating circuit10 DHW circuit11 Instantaneous DHW heater12 Error13 Diagnostics
Heatingprogramming
Heating zones
DHW temperature ON Automatic heating
programming
Data transmission(only with WIRELESSdevice)
2 heatingtemperature levels:comfort/ reduced
21
Solutions for centralized heating systems installations
Single installationLuna Duo-tec MP 1.35-1.50-1.60-1.70
Extension vessel connection kit
Boiler-manifolds connection kit
Manifold insulation kit for a boiler
* The hydraulic separator is handled as a separate accessory
Flanges and gasket kit
Flow-return-gas manifolds kitfor individual boiler
Manifold hydraulickit for hydraulic separator
22
Installation Kit Boiler-manifolds connection kit
Models Luna Duo-tec MP Code Kit consisting of:
35-50-60-70 kW 710673801 .
gas manifold hook-up with cock shutoff valve 3 way on flow G1-1/4 shutoff valve 2 way on return G1-1/4 cap g1-1/4 and gaskets check valve nipples G1-1/4 extension vessel connector
Extension vessel connection kit
Models Luna Duo-tec MP Code Kit consisting of:
35-50-60-70 kW 710583801 . boiler-extension vessel connection pipe extension vessel 10 litres extension vessel support brackets
Flow-return-gas kit for individual boiler
Models Luna Duo-tec MP Code Kit consisting of:
35-50-60-70 kW 710577501 . gas manifold 2 Flow manifold 3 DN80 PN6 return manifold 3 DN80 PN6
Manifold insulation kit for one boiler
Models Luna Duo-tec MP Code Kit consisting of:
35-50-60-70 kW 710587001 . insulation kit for individual boiler flow/return manifolds
Flanges and gasket kit
Models Luna Duo-tec MP Code Kit consisting of:
35-50-60-70 kW 710582701 . flanges and gaskets for completion of installation
Manifold hydraulic kit for hydraulic separator
Models Luna Duo-tec MP Code Kit consisting of:
Manifold for separator 8,5 m3/h 710686501 .
flow/return manifolds to separatorManifold for separator 18 m3/h 710687501 .
Manifold for separator 28 m3/h 710687601 .
Manifold ins. kit for separator 8,5 m3/h 710687901 . Insulation kit for flow/return manifolds of connection between boilers and hydraulic separators
Manifold ins. kit for separator 18 m3/h 710688901 .
Manifold ins. kit for separator 28 m3/h 710689201 .
Flanges and gaskets kit for separator 8,5 m3/h LSD 790000440 .
Flanges and gaskets kit for separator 18 m3/h LSD 790000430 .
Flanges and gaskets kit for separator 28 m3/h LSD 790000420 .
23
Solutions for centralized heating systems installations
Single installationLuna Duo-tec MP 1.90-1.110
Extension vessel connection kit
Boiler-manifolds connection kit
Manifold insulation kit for a boiler
* The hydraulic separator is handled as a separate accessory
Flange and gasket kit
Flow-return-gas manifolds kitfor individual boiler
24
Installation kit Boiler-manifolds connection kit
Models Luna Duo-tec MP Code Kit consisting of:
90-110 kW 710678301 .
gas manifold hook-up with cock shutoff valve 3 way in delivery G1-1/4 shutoff valve 2 way on return G1-1/4 cap g1-1/4 and gaskets check valve nipples G1-1/4 extension tank connector
Extension tank connection kit
Models Luna Duo-tec MP Code Kit consisting of:
90-110 kW 710583801 . boiler-extension tank connection pipe extension tank 10 litres extension tank support brackets
Flow-return-gas manifold kit for individual boiler
Models Luna Duo-tec MP Code Kit consisting of:
90-110 kW 710584601 . gas manifold 2 delivery manifold 3 DN80 PN6 return manifold 3 DN80 PN6
Manifold insulation kit for individual boiler
Models Luna Duo-tec MP Code Kit consisting of:
90-110 kW 710587801 . insulation kit for individual boiler flow/return manifolds
Flanges and gasket kit
Models Luna Duo-tec MP Code Kit consisting of:
90-110 kW 710582701 . flanges and gaskets for completion of installation
Manifold hydraulic kit for hydraulic separator
Models Luna Duo-tec MP Code Kit consisting of:
Manifold for separator 8,5 m3/h 710686501 .
flow/return manifolds to separatorManifold for separator 18 m3/h 710687501 .
Manifold for separator 28 m3/h 710687601 .
Manifold ins. kit for separator 8,5 m3/h 710687901 . Insulation kit for flow/return manifolds of connection between boilers and hydraulic separators
Manifold ins. kit for separator 18 m3/h 710688901 .
Manifold ins. kit for separator 28 m3/h 710689201 .
Flanges and gaskets kit for separator 8,5 m3/h LSD 790000440 .
Flanges and gaskets kit for separator 18 m3/h LSD 790000430 .
Flanges and gaskets kit for separator 28 m3/h LSD 790000420 .
25
Solutions for centralized heating systems installations
DimensionsLuna Duo-tec 1.35-1.50-1.60-1.70
DimensionsLuna Duo-tec 1.90-1.110
450
600
99
213
229
511
220
1866
5319
19
160
511
220
2052
110
2162
160
99
213
115
450
600
99
213
229
511
220
1866
5319
19
160
511
220
2052
110
2162
160
99
213
115
26
Connection of clip-in module THINK
With clip-in module THINK the heater can manage either a mixing zone, controlling the mixing valve, zone sensor and pump, or a solar system by means of the sensors on the collector, tank and solar pump. This accessory is installed in the boiler dashboard. You must remove cover A from dashboard B. Raise dashboard B and hook up the flat cable between connector X50 of clip-in module and connector X41 of the boiler board, passing through the hole in dashboard B. Close dashboard B and insert the clip-in module. Carry out the electrical hook-ups necessary for installation and fix the new cover C found in the pack.
Clip-in module
27
Solutions for centralized heating systems installations
Connection of external module THINK
External module THINK is a device which, in a heating system run with LUNA DUO-TEC MP boilers, supplies several programmable inlets/outlets necessary to complete the heating system.As for individual installations, the module external module can supply the boiler with the inlets/outlets necessary for management of a mixing zone or, alternatively, a solar system.The accessory is connected to the cascade of LUNA DUO-TEC MP boilers by means of a local bus through which the information regarding the devices connected is received and transmitted.
For each individual boiler a maximum of three extension modules can be installed, one clip-in module and two external module for the management of a maximum of three mixing zones.When it is used for management of mixing zones the external module requires the presence of a remote control (see relevant section on page 20) for programming the zone control parameters. In this case the remote control may also be used as a room sensor for the mixing zone.
The external module may also be used to manage solar system by means of the boiler. In this case the connections supplied by the module are the two inlets related to the sensor on the collectors and to the sensor on the tank, whereas the outlet regards control of the solar pump (see figure).
NL
EX21FX23
L CS
T
QX23
QX22
LN
QX21
NL
NL
X50
H2
MBX22
MBX21
X30n
nn
A
D
CB
M
ON
1 2
1 212
3
230V
A Flow sensorB Mixing valveC Mixing zone pumpD Safety thermostat
A Tank sensor (supplied as optional)
B Collectors sensor (supplied as optional)
C Solar circuit pump (supplied as optional)
In the case of a mixing zone, hook up the safety thermostat between the FX23-L terminals and jump the terminals EX21-FX23. In this way the circuit pump connected to relay QX23 is internally connected in series with the safety thermostat.
Should it be necessary to use relay outlet QX23 for functions other than those envisaged for the mixing zone, jump terminals FX23-L.
28
Some easy schemes to enter the THINK world
Heating circuit with 2 high temperature zones, one zone controlled with a thermostat and one zone controlled with THINK remote control.
1) How many independent zones are in the system?
There are 2 independent zones, so the 2 heating zones HC1 and HC2 must be activated. This means to set the 2 registers:
5710 zone HC1 On (factory set)5715 zone HC2 On
2) The valve of HC1 zone is controlled by the boiler PCB, it means the relevant parameter of the QX1 terminal to which the valve is connected has to be set and it must be fixed that is the pump (or the valve) of HC1 zone
5890 OUTPUT QX1 pump of the circuit HC1 (factory set)
3) The thermostat of the high temperature zone HC2 is connected to RT terminal of the boiler (input H5). It has to be set the thermostat connected to the relay is the zone HC2 one.
5977 INPUT H5 RT of the circuit HC2
4) Then it has to be set the remote control that is the address 1 and it is assigned to the zone HC1, it means:
40 (of the remote control) use Room Unit 142 (of the remote control) assignation zone HC1 To invert the 2 zones and make 1 the zone HC2 and 2 the zone HC1, without switching the connections, it would be enough to change the setting of the parameter 5890
5890 OUTPUT QX1 pump of the circuit HC2
then to set the release to the valve as the release to valve of the zone HC2, change the parameter 5977
5977 INPUT H5 RT of the circuit HC1
Example scheme of heating circuit with 2 high temperature zones
HC1HC2
29
Solutions for centralized heating systems installations
to set on the PCB of the boiler that the RT is the zone HC1 thermostat and to change the parameters of the remote control:
40 (of the remote control) use Unit Ambiente 142 (of the remote control) assignation Multi-function
Example scheme of heating circuit with 3 high temperature zones
Heating circuit with 3 high temperature zones, one zone controlled with a thermostat and two zones controlled with THINK remote controls.An external programmable module has been installed to in increase the number of the connections of the PCB and to control the 3 zone valves.
1) How many independent zones are in the system?
There are 3 independent zones, so the 3 heating zones HC1, HC2 and HC3 must be activated. This means to set the 3 registers:
5710 zone CR1 On (factory set)5715 zone CR2 On5721 zone CR3 On
2) An external programmable module THINK has been used, so this accessory has to be set by the activation on the register 6020:
6020 FUNCTION EM1 Multi-functionThis setting defines the external module with the address 1 (EM1) as multi-functional.
3) The valves of the 3 zones HC1, HC2 and HC3 are controlled by the external programmable module, so the relevant parameters of the external module have to be set to define which terminals of the external module control the valves (in this contest pump and valve have the same meaning)
6030 OUTPUT QX21 EM Pump of the circuit CR1 6031 OUTPUT QX22 EM Pump of the circuit CR26032 OUTPUT QX23 EM Pump of the circuit CR3
4) The thermostat of the high temperature zone HC3 is connected to the terminal RT of the external module (input H2). It has to be set that the thermostat connected to that terminal is the one of the zone HC3
6046 INPUT H2 EM1 RT of the circuit HO3
HC1HC2HC3
30
5) Then the remote controls of the zone HC1 and HC2 have to be linked to the relevant zones, it means
40 (of the remote control address 1) use Room Unit 142 (of the remote control address 1) assignation Zone HC1
40 (of the remote control address 2) use Room Unit 2In this case it is not necessary to give the assignation, because it is automatically set in those units where the use is different form Room Unit 1.
Example scheme with 2 low temperature zones and 1 high temperature zone
Heating circuit with 2 zones low temperature controlled by remote controls THINK and 1 zone with high temperature controlled by room thermostat.
To control low temperature zones it is ALWAYS necessary to use a programmable module (clip-in or external module). In this case, 2 modules are necessary.
First of all, the 3 heating zones HC1, HC2 and HC3 have to be activated. This means to set the 3 registers:
5710 zone HC1 On (factory set)5715 zone HC2 On5721 zone HC3 On 2 programmable modules have been used, so they must be qualified by means of the activation on the register 6020 and 6021:
6020 FUNCTION EM1 Zone HC16021 FUNCTION EM2 Zone HC2
These settings assign the external module with address 1 (EM1) to the zone HC1 and assign the external module with address 2 (EM2) to the zone HC2.
Since the safety thermostats of the low temperature zones are both connected to the terminal EX21 of the relevant external modules, this choice has to be to be set:
6024 Terminal EX21 of EM1 Safety thermostat zone HC16026 Terminal EX21 of EM2 Safety thermostat zone HC2
The thermostat of the high temperature zone HC3 is linked to the terminal RT of the PCB of the boiler (H5). It must be defined that the thermostat connected to this terminal is the thermostat of the zone HC3
Ext. module THINK
Ext. module THINK
HC1HC2HC3
31
Solutions for centralized heating systems installations
6046 INPUT H3 RT of circuit HC3
Also the valve of the zone HC3 is connected to the programmable output QX1 of the PCB of the boiler. So it is necessary to set the following parameter:
5890 OUTPUT QX1 Pump of the circuit HC3
Then the remote controls of the zone HC1 and HC2 have to be linked to the relevant zones, it means
40 (of the remote control address 1) use Room Unit 142 (of the remote control address 1) assignation Zone HC1
40 (of the remote control address 2) use Room Unit 2In this case it is not necessary to give the assignation, because it is automatically set in those units where the use is different form Room Unit 1.
Example scheme of heating circuit with 1 high temperature zone, 1 low temperature zone and a solar tank for DHW production with solar integration
Heating circuit with 2 zones, 1 with high temperature and 1 with low temperature controlled by room thermostat, with a solar system
To control low temperature zones it is ALWAYS necessary to use a programmable module (clip-in or external module). Also to control a solar system it is necessary to employ an external programmable module. In this case, then, 2 modules are necessary.
First of all, as we have seen, the 2 zones HC1 and HC2 have to be activated. This means to set the 2 registers:
5710 zone HC1 On (factory set)5715 zone HC2 On
2 programmable modules have been used, so they must be qualified by means of the activation on the register 6020 and 6021:
6020 FUNCTION EM1 Zone HC16021 FUNCTION EM2 Solar system for DHW production
Ext. module THINK
Ext. module THINK
32
These settings assign the external module with address 1 (EM1) to the zone HC1 and assign the external module with address 2 (EM2) to the control of the solar collectors. Obviously the sensors and the pump of the solar system have to be connected to the relevant terminals, specified in the technical manual of the external programmable module:
BX22 Solar sensor tank side
BX21 Solar sensor collectors side (Pt 1000)
QX23 Solar pump circuit
Since the low temperature safety thermostat is linked to EX21 terminal of the external module EM1, this choice has to be set on the relevant register:
6024 Terminal EX21 di EM1 Safety thermostat zone HC1
The thermostat of the low temperature zone HC1 is connected to the terminal of the external module EM1 (H2), while the thermostat of the high temperature zone HC2 is linked to the terminal RT of the PCB of the boiler (H5). It must be defined that the thermostat connected to this terminal is the thermostat of the zone HC2
6046 INPUT H2 EM1 RT of circuit HC15977 INPUT H5 RT of circuit HC2
Finally, also the valve of the zone HC2 is connected to the programmable output QX1 of the PCB of the boiler. So it is necessary to set the following parameter:
5890 OUTPUT QX1 Pump of the circuit HC2
33
Solutions for centralized heating systems installations
Single installation schemes
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
Mano
metro
mmH2
O
mbar
60
012
0
20
4080
100
TER
MO
ME
TRO
C
1
24
3
6
7
8
9
13
12
11
AGU2
.550
10
5
1 H
igh
outp
ut c
onde
nsin
g bo
iler L
UN
A D
UO
-TE
C M
P2
Flow
-ret
urn-
gas
man
ifold
s ki
t for
indi
vidu
al b
oile
r3
Clip
-in m
odul
e TH
INK
4 H
ydra
ulic
sep
arat
or5
Out
door
sen
sor
6 H
ot w
ater
tem
pera
ture
sen
sor
7 D
oubl
e co
il (D
C) s
tora
ge ta
nk fo
r sol
ar s
yste
m in
tegr
atio
n8
Saf
ety
devi
ce IS
PE
SL
(ava
ilabl
e as
opt
iona
l - c
ompu
lsor
y
acce
ssor
y on
ly fo
r Ita
lian
mar
ket)
9 S
olar
circ
olat
ion
grou
p10
S
olar
hot
wat
er te
mpe
ratu
re s
enso
r11
S
olar
col
lect
ors
SB
25+
V12
C
olle
ctor
s se
nsor
13
Air
vent
val
ve
SY
STE
M M
AD
E O
F 1
HIG
H O
UTP
UT
CO
ND
EN
SIN
G B
OIL
ER
LU
NA
DU
O-T
EC
MP,
1 D
IRE
CT
HIG
H T
EM
PE
RAT
UR
E
CIR
CU
IT, 1
DH
W T
AN
K W
ITH
SO
LAR
INTE
GR
ATIO
N
34
TABLE OF THE CONNCETION TO BE MADE
PROGRAMMABLE CLIP-IN MODULE THINK
Terminals Device to be connected
Terminal QX23 N Solar circuit pump
Terminal BX22 M Solar tank sensor (solar system side)
Terminal BX21 M Solar collectors sensor
CONNECTION ON THE PCB OF THE BOILER
Terminals 4-5 of terminal board M2 Outdoor sensor
Terminals 4-5 of terminal board M3 Tank pump (tank side)
Terminals 9-10 of terminal board M2 Tank sensor (boiler side)
Terminals 6-7 of terminal board M3 Heating pump users side (downstream of the hydraulic separator)
Terminals 2-3 of terminal board M3 ISPESL safety kit
Further the physical connections, it is necessary to set some software parameters on the PCB by means of the display of the boiler.
The parameters to be set are the following:
System with high power condensing boiler Luna Duo-tec MP 1 direct high temperature circuit 1 DHW tank with solar integrationThe system shown in the previous page could represent a centralized system of a small multi-dwelling building with only one distribution raiser. In this case the programmable clip-in module THINK to control the hydraulic circuit of the solar collectors. In the scheme are showed the connection to be made on the programmable clip-in module.
A Tank sensor
B Solar collectors sensor (supplied as optional)
C Solar circuit pump
35
Solutions for centralized heating systems installations
On the programmable clip-in module THINK, it has to be set the address 1.
Menu Programme line Description
Configuration 6020 Enabling of solar function
Menu Programme line Value Description
Configuration
3810 Default 8 CDifference in temperature between collectors and tank solar sensor for solar pump activation
3811 Default 4 CDifference in temperature between collector and tank solar sensors for solar pump switch-off
3850 Default "---"Temperature above which the collector pump circulates (only if the maximum tank temperature is not reached)
The parameters that may be used are shown below. In the case of solar panels with vacuum pipes, activate the specific protection function (parameters 3830, 3831)
Solar3830 Default "---"
Maximum solar pump block time if collector temperature reaches maximum value (parameter 3850) in the minimum circulation time (parameter 3831)
3831 Default 30s Collector pump minimum circulation time
For more general heating and DHW production systems settings, consult the manual of the programmable clip-in module THINK.
LIST OF THE COMPONENTS OF THE SYSTEM
n Component Boiler 35-70 kW Boiler 90-110 kW
1 Flow-return-gas manifolds kit for individual boiler 710577501 . 710584601 .
1 Boiler-manifolds connection kit 710673801 . 710678301 .
1 Terminals 4-5 of terminal board M2 Outdoor sensor
1 Terminals 4-5 of terminal board M3 Tank pump (boiler side)
1 Extension vessel connection kit 710583801 .
1 Flange and gasket kit 710582701 .
1 Manifold insulation kit for individual boiler 710587001 . 710587801 .
1Safety device ISPESL (available as optional - compulsory accessory only for Italian market)
KHW 714098411 .
1 Connection manifold kit for hydraulic separator Depending on the hydraulic separator
1 Flange and gasket kit for hydraulic separator manifold Depending on the hydraulic separator
1 Hydraulic separator kit Depending on the hydraulic separator
2 Tank sensor KHG714076810 .
36
Single installation schemes
Manometro
bar
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
QAZ 21
QA
D
Mano
metro
mmH2
O
mbar
4
AGU2
.550
Solar c
ollector
Solar c
ollector
1 52
3
6
107
8 9
1 H
igh
outp
ut c
onde
nsin
g bo
iler L
UN
A D
UO
-TE
C M
P2
Saf
ety
devi
ce IS
PE
SL
(ava
ilabl
e as
opt
iona
l - c
ompu
lsor
y ac
cess
ory
on
ly fo
r Ita
lian
mar
ket)
3 H
ydra
ulic
sep
arat
or4
Out
door
sen
sor
5 C
lip-in
mod
ule
THIN
K6
Flow
/retu
rn s
enso
r7
DH
W s
enso
r8
Dou
ble
coil
(DC
) sto
rage
tank
for s
olar
sy
stem
inte
grat
ion
9 Th
erm
osta
tic m
ixer
10 S
olar
circ
olat
ion
grou
p
SY
STE
M M
AD
E O
F 1
HIG
H E
FFIC
IEN
CY
CO
ND
EN
SIN
G B
OIL
ER
LU
NA
DU
O-T
EC
MP,
1 H
IGH
TE
MP
ER
ATU
RE
DIR
EC
T C
IRC
UIT
, 1
LOW
TE
MP
ER
ATU
RE
DIR
EC
T C
IRC
UIT
, 1 D
HW
TA
NK
WIT
H S
OLA
R IN
TEG
RAT
ION
37
Solutions for centralized heating systems installations
System with high power condensing boiler Luna Duo-tec MP 1 direct high temperature circuit 1 low temperature mixing circuit 1 DHW tank with solar integration
This system could be a small multi-familiar building (4-6 flats), where every flat is supplied with low temperature zones with integration (for example in the bathrooms) of high temperature elements.This system could also be one single premise (commercial building, sport center or factory) with underfloor heating system and high temperature integration.In both cases, the DHW is delivered to the users from a central tank whose thermal load is provided with a solar collectors system, eventually integrated with the centralized boiler.
Also for this system, it is necessary to use a programmable clip-in module THINK to control the hydraulic circuit of the solar collectors. Moreover, a programmable external module THINK is required to control the low temperature zone.
In the picture are showed the connections to be done on the programmable clip-in module
A Tank sensor (supplied as accessory)
B Solar collector sensor (supplied as accessory)
C Solar circuit pump
A Delivery sensor C Mixing zone pump
B Mixing valve D Safety thermostat
In the following parameters, the heating circuit 1 (HC1) is the low temperature zone, while the heating circuit 2 (HC2) is the high temperature circuit.
38
PROGRAMMABLE CLIP-IN MODULE THINK
Terminals Device to be connected
Terminal QX23 N Solar circuit pump
Terminal BX22 M Solar tank sensor (solar system side)
Terminal BX21 M Solar collectors sensor
PROGRAMMABLE EXTERNAL MODULE THINK
Terminal QX21 N QX22 Low temperature zone mixing valve
Terminal QX23 N Low temperature circuit pump
Terminal BX21 M Low temperature circuit sensor
Terminal FX21 L Low temperature zone safety thermostat
CONNECTION ON THE PCB OF THE BOILER
Terminals 4-5 of terminal board M2 Outdoor sensor
Terminals 4-5 of terminal board M3 Tank pump (tank side)
Terminals 9-10 of terminal board M2 Tank sensor (boiler side)
Terminals 6-7 of terminal board M3 Heating pump users side (downstream of the hydraulic separator)
Terminals 2-3 of terminal board M3 ISPESL safety kit
Morsetti 123 della morsett. M2 Eventuale unit ambiente zona a bassa temperatura
Morsetti 1-2 della morsettiera M1 Termostato ambiente zona alta temperatura
On the PROGRAMMABLE external module THINK, it has to be set the address 1.On the programmable clip-in module THINK, it has to be set the address 2.
Menu Programme line Value Decription
Configuration 5715 On Enabling of the heating circuit HC2 (high temperature)
Configuration 5977 Room thermostat HC2 Enabling of the thermostat of the heating circuit HC2 (high temperature)
Configuration 5890 Heating circuit HC2 (high temperature) pump
Configuration 6020 Enabling of the heating circuit HC1 (low temperature)
Configuration 6024 Safety thermostat HC Input EX21 enabled as protection of the low temperature circuit
Configuration 6046 ------- Input H2 without functions
Heating circuit 1 742 ------- Enabling modulating flow temperature (low temperature circuit)
Heating circuit 1 834 Default 180s Mixing valve closure time
Configuration 6021 Enabling of the solar function
Configuration 3810 Default 8CDifference in temperature between collectors and tank solar sensor for solar pump activation
Configuration 3811 Default 4CDifference in temperature between collector and tank solar sensors for solar pump switch-off
Configuration 3850 Default "---"Temperature above which the collector pump circulates (only if the maximum tank temperature is not reached)
Solar configuration3830 Default "---"
Maximum solar pump block time if collector temperature reaches maximum value (parameter 3850) in the minimum circulation time (parameter 3831)
3831 Default 30s Collector pump minimum circulation time
The room thermostat of the high temperature heating circuit has to be linked, as already specified, to the terminals 1-2 of the terminal board (room thermostat).
39
Solutions for centralized heating systems installations
LIST OF THE COMPONENTS OF THE SYSTEM
n Component Boiler 35-70 kW Boiler 90-110 kW
1 Flow-return-gas manifolds kit for individual boiler 710577501 . 710584601 .
1 Boiler-manifolds connection kit 710673801 . 710678301 .
1 Extension vessel connection kit 710583801 .
1 Flange and gasket kit 710582701 .
1 Manifold insulation kit for individual boiler 710587001 . 710587801 .
1Safety device ISPESL (available as optional - compulsory accessory only for Italian market)
KHW 714098411 .
1 Connection manifold kit for hydraulic separator Depending on the hydraulic separator
1 Flange and gasket kit for hydraulic separator manifold Depending on the hydraulic separator
1 Hydraulic separator kit Depending on the hydraulic separator
1 Programmable clip-in module THINK 710034503 .
1 Programmable external module THINK 710503704 .
2 Tank sensor KHG714076810 .
1 Outdoor sensor 710487301 .
1Solar collectors sensor for programmable clip-in or external module THINK
LNC 710000040 .
1 Heating flow/return sensor KHG714078910 .
40
Single installation schemes
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
0
120
2040
80100
TERMOMETRO
C 60
0
120
2040
80100
TERMOMETRO
C 60
0
120
2040
80100
TERMOMETRO
C 60
0
120
2040
80100
TERMOMETRO
C
QA
DQ
AD
AVS7
5
60
012
0
20
4080
100
TER
MO
MET
RO
C
60
012
0
20
4080
100
TER
MO
MET
RO
C
60
012
0
20
4080
100
TER
MO
MET
RO
C
60
012
0
20
4080
100
TER
MO
MET
RO
C
60
012
0
20
4080
100
TER
MO
MET
RO
C
Ramp
a GAS
G2"
To u
sers
To th
e he
atin
g ci
rcui
t
1
25
3
4
UBTT
1000
AVS7
5
6
8
11
13
12
14 7
10
9AG
U2.55
0
1 H
igh
outp
ut c
onde
nsin
g bo
iler L
UN
A D
UO
-TE
C M
P2
Flow
-ret
urn-
gas
man
ifold
s ki
t for
indi
vidu
al b
oile
r3
Flue
pip
es fo
r ind
ivid
ual b
oile
r4
Saf
ety
devi
ce IS
PE
SL
(ava
ilabl
e as
opt
iona
l - c
ompu
lsor
y ac
cess
ory
on
ly fo
r Ita
lian
mar
ket)
5 H
ydra
ulic
sep
arat
or6
Tank
-in ta
nk c
ylin
der U
BTT
100
07
DH
W s
enso
r8
Ext
erna
l mod
ule
THIN
K9
Clip
-in m
odul
e TH
INK
10
Tank
sen
sor
11
Sol
ar c
ircol
atio
n gr
oup
12
Col
lect
ors
sens
or13
A
ir ve
nt v
alve
14
Sol
ar c
olle
ctor
s S
B25
+ V
SYST
EM M
ADE
WIT
H H
IGH
OU
TPU
T C
ON
DEN
SIN
G B
OIL
ER L
UN
A D
UO
-TEC
MP,
2 L
OW
TEM
PER
ATU
RE
MIX
ING
CIR
CU
ITS,
1 D
HW
TA
NK
WIT
H S
OLA
R IN
TEG
RAT
ION
FO
R H
EATI
NG
AN
D D
HW
PR
OD
UC
TIO
N
41
Solutions for centralized heating systems installations
System with high output condensing boiler Luna Duo-tec MP 2 low temperature mixing circuits 1 DHW tank with solar integration for heating and DHW production
This system could be a quite big house, with at least 2 zones (ground/first floor) with independent climatic regulation.This system could also be one single premise (commercial building, sport center or factory) with underfloor heating system and high temperature integration.In both cases, the DHW is delivered to the users from a central tank whose thermal load is provided with a solar collectors system, eventually integrated with the centralized boiler.
Also for this system, it is necessary to use a programmable clip-in module THINK to control the hydraulic circuit of the solar collectors. Moreover, 2 programmable external modules THINK are required to control the low temperature zone.
In the picture are showed the connections to be done on the programmable clip-in modules
A Tank sensor (supplied as accessory)
B Solar collector sensor (supplied as accessory)
C Solar circuit pump
A Delivery sensor C Mixing zone pump
B Mixing valve D Safety thermostat
In the following parameters, the heating circuit 1 (HC1) is the low temperature zone, while the heating circuit 2 (HC2) is the other low temperature circuit.
42
PROGRAMMABLE CLIP-IN MODULE THINK
Terminals Device to be connected
Terminal QX23 N Solar circuit pump
Terminal BX22 M Solar tank sensor (solar system side)
Terminal BX21 M Solar collectors sensor
PROGRAMMABLE EXTERNAL MODULE THINK (EM1)
Terminal QX21 N QX22 Low temperature zone mixing valve
Terminal QX23 N Low temperature circuit pump
Terminal BX21 M Low temperature circuit sensor
Terminal FX21 L Low temperature zone safety thermostat
PROGRAMMABLE EXTERNAL MODULE THINK (EM2)
Terminal QX21 N QX22 Low temperature zone mixing valve
Terminal QX23 N Low temperature circuit pump
Terminal BX21 M Low temperature circuit sensor
Terminal FX21 L Low temperature zone safety thermostat
CONNECTION ON THE PCB OF THE BOILER
Terminals 4-5 of terminal board M2 Outdoor sensor
Terminals 9-10 of terminal board M2 Tank sensor (boiler side)
Terminals 6-7 of terminal board M3 Heating pump users side (downstream of the hydraulic separator)
Terminals 2-3 of terminal board M3 ISPESL safety kit
Terminals 1-2-3 of terminal board M2 Eventual room unit of the zone 1 (low temperature)
Terminals 1-2-3 of terminal board M2 Eventual room unit of the zone 2 (low temperature)
Menu Programme line Value Decription
Configuration 5710 On Enabling of the heating circuit HC1 (low temperature)
Configuration 5715 On Enabling of the heating circuit HC2 (low temperature)
Configuration 6020 Enabling of the heating circuit HC1 (low temperature)
Configuration 6021 Enabling of the heating circuit HC2 (low temperature)
Configuration 6024 Safety thermostat HC Input EX21 enabled as protection of the low temperature circuit HC1
Configuration 6026 Safety thermostat HC Input EX21 enabled as protection of the low temperature circuit HC2
Configuration 6022 Enabling of the solar function
Use Par. 40 EM1 Room Unit 1
Assignation Par. 42 EM1 Zone HC1
Use Par. 40 EM2 Room Unit 2
The programmable external module of the zone HC1 has to be set with address 1 on DIP-SWITCHThe programmable external module of the zone HC2 has to be set with address 2 on DIP-SWITCHThe programmable clip-in module of the solar system has to be set with address 3 on DIP-SWITCH
43
Solutions for centralized heating systems installations
LIST OF THE COMPONENTS OF THE SYSTEM
N Component Boiler 35-70 kW Boiler 90-110 kW
1 Flow-return-gas manifolds kit for individual boiler 710577501 . 710584601 .
1 Boiler-manifolds connection kit 710673801 . 710678301 .
1 Extension vessel connection kit 710583801 .
1 Flange and gasket kit 710582701 .
1 Manifold insulation kit for individual boiler 710587001 . 710587801 .
1Safety device ISPESL (available as optional - compulsory accessory only for Italian market)
KHW 714098411 .
1 Connection manifold kit for hydraulic separator Depending on the hydraulic separator
1 Flange and gasket kit for hydraulic separator manifold Depending on the hydraulic separator
1 Hydraulic separator kit Depending on the hydraulic separator
1 Programmable clip-in module THINK 710034503 .
2 Programmable external module THINK 710503704 .
2 Tank sensor KHG714076810 .
1 Outdoor sensor 710487301 .
1Solar collectors sensor for programmable clip-in or external module THINK
LNC 710000040 .
2 Heating flow/return sensor KHG714078910 .
44
Luna Duo-tec MP da 1.35 a 1.110
Manifolds connector kit
Flow-return-gas manifoldskit for individual boiler
Manifold hydraulic kitfor hydraulic separator
Cascade installation
TUBO COLLEGAMENTO COLLETTORI GAS
Flow - return - gas manifolds for 2 boilers
Extension vessel connection kit
Boiler-manifolds connection kit
45
Solutions for centralized heating systems installations
List of hydraulic accessories, boilers in cascade:Cascade of 2 boilers of 35-70 kW
Quantity Description Code
n.1 Flow-return-gas manifolds kit for 2 boilers 710577701 .
n.2 Extension tank connection kit from 35 to 70 kW 710583801 .
n.2 Boiler-manifolds connection kit from 35 to 70 kW 710673801 .
n.1 Insulation kit for two boilers from 35 to 70 kW 710587501 .
n.1 Flange and gasket kit 710582701 .
n.1 Manifold kit for hydraulic separator See relevant section on page 77
Cascade of 2 boilers of 90-110 kW
Quantity Description Code
n.1 Flow-return-gas manifolds kit for 2 boilers 710584901 .
n.2 Extension vessel connection kit from 90 to 110 kW 710583801 .
n.2 Boiler-manifolds connection kit from 90 to 110 kW 710678301 .
n.1 Insulation kit for two boilers from 90 to 110 kW 710588501 .
n.1 Flange and gasket kit 710582701 .
n.1 Manifold kit for hydraulic separator See relevant section on page 77
Cascade of 3 boilers of 35-70 kW
Quantity Description Code
n.1 Flow-return-gas manifolds kit for 2 boilers 710577701 .
n.3 Extension vessel connection kit from 35 to 70 kW 710583801 .
n.1 Flow-return-gas manifolds kit for 1 boiler 710577501 .
n.3 Boiler-manifolds connection kit from 35 to 70 kW 710673801 .
n.1 Insulation kit for two boilers from 35 to 70 kW 710587501 .
n.1 Flange and gasket kit 710582701 .
n.1 Manifolds connection kit 710583201 .
n.1 Manifold kit for hydraulic separator See relevant section on page 77
Cascade of 3 boilers of 90-110 kW
Quantity Description Code
n.1 Flow-return-gas manifolds kit for 2 boilers 710584901 .
n.3 Extension vessel connection kit from 90 to 110 kW 710583801 .
n.1 Flow-return-gas manifolds kit for 1 boiler 710584601 .
n.3 Boiler-manifolds connection kit from 90 to 110 kW 710678301 .
n.1 Insulation kit for two boilers from 90 to 110 kW 710588501 .
n.1 Flange and gasket kit 710582701 .
n.1 Manifolds connection kit 710583201 .
n.1 Manifold kit for hydraulic separator See relevant section on page 77
46
List of hydraulic accessories, boilers in cascade:Cascade of 4 boilers of 35-70 kW
Quantity Description Code
n.2 Flow-return-gas manifolds kit for 2 boilers 710577701 .
n.4 Extension vessel connection kit from 35 to 70 kW 710583801 .
n.4 Boiler-manifolds connection kit from 35 to 70 kW 710673801 .
n.1 Insulation kit for two boilers from 35 to 70 kW 710587501 .
n.1 Flange and gasket kit 710582701 .
n.1 Manifolds connection kit 710583201 .
n.1 Manifold kit for hydraulic separator See relevant section on page 77
Cascade of 4 boilers of 90-110 kW
Quantity Description Code
n.2 Flow-return-gas manifolds kit for 2 boilers 710584901 .
n.4 Extension vessel connection kit from 90 to 110 kW 710583801 .
n.4 Boiler-manifolds connection kit from 90 to 110 kW 710678301 .
n.1 Insulation kit for two boilers from 90 to 110 kW 710588501 .
n.1 Flange and gasket kit 710582701 .
n.1 Manifolds connection kit 710583201 .
n.1 Manifold kit for hydraulic separator See relevant section on page 77
Cascade of 5 boilers of 35-70 kW
Quantity Description Code
n.2 Flow-return-gas manifolds kit for 2 boilers 710577701 .
n.1 Flow-return-gas return manifolds kit for 1 boiler 710577501 .
n.5 Extension vessel connection kit from 35 to 70 kW 710583801 .
n.5 Boiler-manifolds connection kit from 35 to 70 kW 710673801 .
n.1 Insulation kit for two boilers from 35 to 70 kW 710587501 .
n.1 Flange and gasket kit 710582701 .
n.2 Manifolds connection kit 710583201 .
n.1 Manifold kit for hydraulic separator See relevant section on page 77
Cascade of 5 boilers of 90-110 kW
Quantity Description Code
n.2 Flow-return-gas manifolds kit for 2 boilers 710584901 .
n.1 Flow-return-gas manifolds kit for 1 boiler 710584601 .
n.5 Extension vessel connection kit from 90 to 110 kW 710583801 .
n.5 Boiler-manifolds connection kit from 90 to 110 kW 710678301 .
n.1 Insulation kit for two boilers from 90 to 110 kW 710588501 .
n.1 Flange and gasket kit 710582701 .
n.2 Manifolds connection kit 710583201 .
n.1 Manifold kit for hydraulic separator See relevant section on page 77
47
Solutions for centralized heating systems installations
(*) flanged flow-return hydraulic manifolds, diameter 3 with flange DN80 PN6 -2 gas manifold, threaded internally
Dimensions*Luna Duo-tec MP 1.35 - 1.50 - 1.60 - 1.70
Dimensions*Luna Duo-tec MP 1.90 - 1.110
470
53160
220
1866
1919
511
620
110
20522162
160
220
511
48
(*) flanged flow-return hydraulic manifolds, diameter 3 with flange DN80 PN6 -2 gas manifold, threaded internally
Dimensions*Luna Duo-tec MP 1.35 - 1.50 - 1.60 - 1.70
Dimensions*Luna Duo-tec MP 1.90 - 1.110
470 470
1919 1866
511
220160
53
620 620
110
20522162
160
220
511
49
Solutions for centralized heating systems installations
2 m
A
B
H
The distance of the flue manifold from the first boiler to the vertical flue is 2 metres
Flue shutter installed on each boiler in cascade
The flue pipes and connections between the flue manifold of the cascade and the flue are not supplied by BAXI
Manifolds in cascade over 200 mm in diameter are not supplied by BAXI
These figures were calculated based on a polypropylene dual wall flue manifold for the flue
The table on the following page shows the diameters of the flue manifold and the flue for various configurations of boilers in
cascade and for various heights of flue.
Overview
How to calculate the diameter of the flue manifold (A) and the chimney (B)
50
N Boilers in cascade
Duo-tec MP1.50
Duo-tec MP1.60
Duo-tec MP1.70
Duo-tec MP1.90
Duo-tec MP1.110
2
Nominal Thermal Power Total 80/60 C (kW)
100 120 140 180 220
Flue manifold mm (A) 125 125 125 160 160
Flue mm (B) -H= 5-10 m 125 125 125 160 160
Flue mm (B) -H=10-15 m 125 125 125 160 160
Flue mm (B) -H=15-20 m 125 125 125 160 160
3
Nominal Thermal Power Total 80/60 C (kW)
150 180 210 270 330
Flue manifold mm (A) 125 125 125 160 160
Flue mm (B) -H= 5-10 m 125 125 160 160 160
Flue mm (B) -H=10-15 m 125 125 160 160 160
Flue mm (B) -H=15-20 m 125 125 160 160 160
4
Nominal Thermal Power Total 80/60 C (kW)
200 240 280 360 440
Flue manifold mm (A) 125 125 160 200 200
Flue mm (B) -H= 5-10 m 160 160 160 200 200
Flue mm (B) -H=10-15 m 160 160 160 200 200
Flue mm (B) -H=15-20 m 160 160 160 200 200
5
Nominal Thermal Power Total 80/60 C (kW)
250 300 350 450 550
Flue manifold mm (A) 160 160 160 200 200
Flue mm (B) -H= 5-10 m 160 160 200 200 200
Flue mm (B) -H=10-15 m 160 160 200 200 200
Flue mm (B) -H=15-20 m 160 160 200 200 200
6
Nominal Thermal Power Total 80/60 C (kW)
300 360 400 540 660
Flue manifold mm (A) 160 200 200 200 200
Flue mm (B) -H= 5-10 m 160 200 200 200 250
Flue mm (B) -H=10-15 m 160 200 200 200 250
Flue mm (B) -H=15-20 m 160 200 200 200 250
51
Solutions for centralized heating systems installations
Connection of the interface bus for boilers in cascade THINK
The interface bus is an electronic device enabling communication with and therefore the management of boilers in cascade. Thus used, the communication bus also permits remote monitoring and management of the cascade. The interface bus slot is inside the control panel of each boiler in the cascade. There are two possible positions of the accessory inside the panel:
1- If the clip-in module THINK has not already been installed in the boiler, then remove the protective cover on the back of the command panel on the boiler, place the interface bus in the relative slot and, once the electronic circuit of the boiler has been turned on, connect the interface using the cable provided to the connector of the electronic circuit X30.
2- If the clip-in module THINK has already been installed in the boiler, then access the electronic circuit by removing the protective cover on the panel and slot in the interface bus as illustrated below making sure to connect the cable provided to the connector of the electronic circuit X30.
X30
INTERFACE KIT FOR BOILERS IN CASCADE THINKLPB BUS
X30
INTERFACE KIT FOR BOILERS IN CASCADE THINK
LPB BUS
52
Connection of clip-in module THINK
With clip-in module THINK the heater can manage either a mixing zone, controlling the mixing valve, zone sensor and pump, or a solar system by means of the sensors on the collector, tank and solar pump. This accessory is installed in the boiler dashboard. You must remove cover A from dashboard B. Raise dashboard B and hook up the flat cable between connector X50 of clip-in module and connector X41 of the boiler board, passing through the hole in dashboard B. Close dashboard B and insert the clip-in module. Carry out the electrical hook-ups necessary for installation and fix the new cover C found in the pack.
Clip-in module
53
Solutions for centralized heating systems installations
Connection of external module THINKExternal module THINK is a device which, in a heating system run with LUNA DUO-TEC MP boilers, supplies several programmable inlets/outlets necessary to complete the heating system.As for cascade systems, the external module THINK allows connection of a cascade pump (output side) downstream of the hydraulic separator, a loading pump for hot sanitary water storage and, where required, a room thermostat and sensors for flow (usually downstream of the hydraulic separator) and for return (usually upstream) of the cascade. The external module THINK can also supply another programmable outlet at 230V for system necessities.The accessory is connected to the cascade of LUNA DUO-TEC MP boilers by means of a local bus through which the information regarding the devices connected is received and transmitted.
Programming of parameters regarding the cascade of boilers is carried out by means of the remote control to be installed externally (see remote control kit on page 20).
nnn X30
BX21MBX22MH2M
X50
LN
LNQX21NL QX22QX23
TSC
LFX23EX21
2
1 1 2
3
1 2
ON
230V
M2
21
3
10
M1
KEY FOR CONNECTOR HOOK-UP
nnn X30
BX21MBX22MH2M
X50
LN
LNQX21NL QX22QX23
TSC
LFX23EX21
2
1 1 2
3
1 2
ON
X50 Connector for hook up between the electronic board and external module THINK
C (EX21-FX23) Not used for cascades
S (QX23-L9 Relay outlet 230V programmable
T (QX21-N) Relay outlet 230V supply CASCADE PUMP
T (QX22-N) Relay outlet 230V supply any loading PUMP for sanitary water STORAGE
NOL (L-N) Supply external module THINK
n (H2-M) ROOM THERMOSTAT connector
n (BX22-M) CASCADE FLOW SENSOR inlet
M Common sensor earth
54
Connection of external module THINK
External module THINK is a device which, in a heating system run with LUNA DUO-TEC MP boilers, supplies several programmable inlets/outlets necessary to complete the heating system.As for individual installations, the module external module can supply the boiler with the inlets/outlets necessary for management of a mixing zone or, alternatively, a solar system.The accessory is connected to the cascade of LUNA DUO-TEC MP boilers by means of a local bus through which the information regarding the devices connected is received and transmitted.
For each individual boiler a maximum of three extension modules can be installed, one clip-in module and two external module for the management of a maximum of three mixing zones.When it is used for management of mixing zones the external module requires the presence of a remote control (see relevant section on page 20) for programming the zone control parameters. In this case the remote control may also be used as a room sensor for the mixing zone.
The external module may also be used to manage solar system by means of the boiler. In this case the connections supplied by the module are the two inlets related to the sensor on the collectors and to the sensor on the tank, whereas the outlet regards control of the solar pump (see figure).
NL
EX21FX23
L CS
T
QX23
QX22
LN
QX21
NL
NL
X50
H2
MBX22
MBX21
X30n
nn
A
D
CB
M
ON
1 2
1 212
3
230V
A Flow sensorB Mixing valveC Mixing zone pumpD Safety thermostat
A Tank sensor (supplied as optional)
B Collectors sensor (supplied as optional)
C Solar circuit pump (supplied as optional)
In the case of a mixing zone, hook up the safety thermostat between the FX23-L terminals and jump the terminals EX21-FX23. In this way the circuit pump connected to relay QX23 is internally connected in series with the safety thermostat.
Should it be necessary to use relay outlet QX23 for functions other than those envisaged for the mixing zone, jump terminals FX23-L.
55
Solutions for centralized heating systems installations
Cascade installation schemes
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
60
012
0
20
4080
100
TER
MO
ME
TRO
C
Mano
metro
mmH2
O
mbar
60
012
0
20
4080
100
TER
MO
ME
TRO
C
QA
D
QA
D
QAZ 21
AVS7
5
2
7
3
5
4
10
11
12OC
I 345
OCI 3
45
11
896
4
1 H
igh
outp
ut c
onde
nsin
g bo
ilers
DU
O-T
EC
MP
2 Fl
ow-r
etur
n-ga
s m
anifo
lds
for 2
boi
lers
3 Fl
ue p
ipes
for t
wo
boile
rs4
Flow
-ret
urn
sens
or5
Hyd
raul
ic s
epar
ator
6 O
utdo
or s
enso
r 7
Inte
rface
kit
for c
asca
de s
yste
m (O
CI 3
45)
8 E
xter
nal m
odul
e TH
INK
9 R
emov
able
con
trol p
anel
10 D
HW
sen
sor
11 S
ingl
e co
il (S
C) t
ank
12 S
afet
y de
vice
ISP
ES
L (a
vaila
ble
as o
ptio
nal)
SYST
EM M
ADE
OF
2 H
IGH
OU
TPU
T C
ON
DEN
SIN
G B
OIL
ERS
LUN
A D
UO
-TEC
MP,
1 H
IGH
TEM
PER
ATU
RE
DIR
ECT
CIR
CU
IT, 1
DH
W T
ANK
(SC
)
56
System with two high output condensing boilers Luna Duo-tec MP in cascade 1 high temperature direct circuit 1 DHW tank
This system is similar to the Luna Duo-tec MP single installation already seen, with the difference of the cascade. The example is useful to see the different uses of the electronic devices in presence of a cascade installation.For complete management of the cascade it has to be installed a interface bus kit for boilers in cascade THINK (one in each boiler in cascade), an external module THINK and a remote control THINK for programming all system parameters.The figure shows the connection of the bus modules and the external module.
The connections of external module THINK are highlighted in the figure.
KEY FOR CONNECTOR HOOK-UP
nnn X30
BX21MBX22MH2M
X50
LN
LNQX21NL QX22QX23
TSC
LFX23EX21
2
1 1 2
3
1 2
ON
X50 Connector for hook up between the electronic board and external module THINK
C (EX21-FX23) Not used for cascades
C (FX23-L) Safety thermostat 230V not used for cascades
S (QX23-L) Relay outlet 230V programmable
T (QX21-N) Relay outlet 230V supply CASCADE PUMP
T (QX22-N) Relay outlet 230V supply any loading PUMP for sanitary water STORAGE
NOL (L-N) Supply external module THINK
n (H2-M) ROOM THERMOSTAT connector
n (BX22-M) CASCADE FLOW SENSOR inlet
n (BX21-M) CASCADE RETURN SENSOR inlet
M Common sensor earth
57
Solutions for centralized heating systems installations
Table of the connection to be donePROGRAMMABLE EXTERNAL MODULE THINK
Terminals Device to be connected
Terminal QX21 N Cascade pump downstream of the hydraulic separator
Terminal BX22 M Cascade flow sensor
Terminal BX21 M Cascade return sensor
Terminal H2 M Eventual room thermostat
CONNECTION ON THE PCB OF THE BOILER
Terminals 4-5 of terminal board M2 Outdoor sensor
Terminals 4-5 of terminal board M3 DHW tank pump (boiler side)
Terminals 9-10 of terminal board M2 DHW tank sensor (boiler side)
Terminals 2-3 of terminal board M3 ISPESL safety kit (optional)
MASTER (main) boiler parameter configurationFurther the physical connections, it is necessary to set some software parameters on the PCB by means of the display of the remote control THINK.The parameters to be set are the following:
On the programmable clip-in module THINK, it has to be set the address 1.
MenuProgramme
lineValue Description
Configuration 5977 None Disabling of the thermostat on the terminal board M1 (1-2)
Configuration 6020 Multi-function Enabling of the programmable external module THINK
Configuration 6030 Heating circuit 1 pump Q2 Control of heating circuit 1 pump
Configuration 6040 Cascade flow sensor B10 Control of cascade flow temperature
Configuration 6041Cascade return sensor
B70Control of cascade return sensor temperature
Configuration 6046 Room Thermostat HC1 Enabling of the thermostat in input H2 of the external module THINK
Configuration 6200 Yes* Saving of the settings
LPB 6630 Always Identification of master boiler
LPB 6640 Autonomous Setting of master cascade clock
*The value returns automatically to No immediately after setting.
58
Parameter configuration on non-MASTER boilerHaving configured the master boiler parameters as described in the previous paragraph, proceed to configuration of the other boiler.For correct system functioning an address must be assigned to the non-master boiler (parameter 6600) so that it can be recognized by the master boiler (the master boiler has default =1). Moreover it is also necessary to synchronize the boiler clocks with that of the master boiler (parameter 6640).
LPB 6600 2..3..4.. Address of the boiler on bus LPBLPB 6640 Slave with remote setting Set cascade boiler clock
LIST OF THE COMPONENTS OF THE SYSTEM
n Component Boiler 35-70 kW Boiler 90-110 kW
1 Flow-return-gas manifolds kit for 2 boilers 710577701 . 710584901 .
2 Boiler-manifolds connection kit 710673801 . 710678301 .
2 Extension vessel connection kit 710583801 .
1 Flange and gasket kit 710582701 .
1 Manifold insulation kit for 2 boilers 710587501 . 710588501 .
1 Safety device ISPESL (available as optional - compulsory accessory only for Italian market) KHW 714098411 .
1 Connection manifold kit for hydraulic separator Depending on the hydraulic separator
1 Flange and gasket kit for hydraulic separator manifold Depending on the hydraulic separator
1 Hydraulic separator kit Depending on the hydraulic separator
1 Programmable external module THINK 710503704 .
2 Tank sensor KHG714076810 .
1 Outdoor sensor 710487301 .
2 Heating flow/return sensor KHG714078910 .
59
Solutions for centralized heating systems installations
Cascade installation schemes
60
012
0
20
4080
100
TER
MO
MET
RO
C
60
012
0
20
4080
100
TER
MO
MET
RO
C
QA
D
60
012
0
20
4080
100
TER
MO
MET
RO
C
60
012
0
20
4080
100
TER
MO
MET
RO
C
60
012
0
20
4080
100
TER
MO
MET
RO
C
QAZ 21
Mano
metro
mmH2
O
mbar
QA
D
AVS7
5
OCI 3
45OC
I 345
6
23
11
9
5
1313
1313
1313
1313
4
712
4
810
1112
1 H
igh
outp
ut c
onde
nsin
g bo
ilers
LU
NA
DU
O-
TEC
MP
2 Sa
fety
dev
ice
ISPE
SL (a
vaila
ble
as o
ptio
nal)
3 Fl
ue p
ipes
for t
wo
boile
rs4
Hea
ting
flow
/retu
rn s
enso
r 5
Hyd
raul
ic s
epar
ator
6 O
utdo
or s
enso
r 7
Inte
rface
kit
for b
oile