78
И C О 9 0 0 0 Р Е И Г С Т Р AQP 42 2863 6 Group P32 THREE-PHASE ACTIVE AND REACTIVE ELECTRIC ENERGY METER CE 304 Operating manual ИНЕС.411152.064 OM Software version v.1.X Manufacturer: JSC"Concern Energomera" 415-А Lenin Street, 355029 Stavropol, Russia, phone (8652) 56-67-21, 35-67-45; fax (8652) 56-40-28, 36-44-17.

ce304_re

Embed Size (px)

DESCRIPTION

n

Citation preview

  • C 90 00

    AQP 42 2863 6 Group P32

    THREE-PHASE ACTIVE AND REACTIVE ELECTRIC ENERGY METER CE 304

    Operating manual .411152.064 OM

    Software version v.1.X Manufacturer: JSC"Concern Energomera" 415- Lenin Street, 355029 Stavropol, Russia, phone (8652) 56-67-21, 35-67-45; fax (8652) 56-40-28, 36-44-17.

  • CONTENTS 1 DEFINITIONS, DESIGNATIONS AND ABBREVIATIONS.. 3 2 SAFETY REQUIREMENTS 4 3 METER AND ITS OPERATION DESCRIPTION 5 3.1 Application 5 3.2 Ambient environment... 11 3.3 Meter nomenclature.. 12 3.4 Specifications 12 3.5 Meter arrangement and operation. 16 4 METER PRE-OPERATION 27 4.1 Unpacking. 27 4.2 Pre-operation. 27 4.3 Installation procedure 27 4.4 Connection diagrams. 27 4.5 Power source replacement. 31 4.6 Software setup 32 5 OPERATION PROCEDURE... 48 5.1 LCD indication of calculating machine channels data.. 50 5.2 Data scrolling in the manual mode 51 5.3 Information messages 60 5.4 Interface data exchange structure.. 64 6 METER VERIFICATION 65 7 MAINTANENANCE..... 65 8 SERVICE 66 9 STORAGE AND TRANSPORTATION.. 67 10 PACKAGE 67 11 MARKING AND SEALING... 68 ANNEX A Accepted value limits of error. 69 ANNEX B Overall dimensions... 85 ANNEX C Diagram of meter connection with power system 86 ANNEX D Diagram of interface meter CE 304 with PC COM-port.. 89 ANNEX E Data formats for exchange via interface.. 93 ANNEX F Type and manner of pressing buttons LCD indication switch structure.. 115

  • This operating manual (hereinafter - OM) covers description of three phase active and reactive energy meter CE304 (hereinafter Meter) arrangement, principle of operation, pre-operation and other information essential for its proper usage.

    It is also necessary to go by the technical passport .411152.064 TP (hereinafter - TP) while studying the meter operation.

    Only persons specially trained for working at voltage up to 1000 V and studied this operating manual are allowed for the meter maintenance.

    1. DEFINITIONS, DESIGNATIONS AND ABBREVIATIONS.

    1.1 This operating manual contains the following abbreviations: AMR automatic meter reading; TS technology software; ADC analogue-to-digital converter; MC microcontroller; PM power module; BPS back-up power source; LCD liquid-crystal display; LI light indicators of active and reactive energy; Kb keyboard; OP optical port; TM (TM1TM6) pulse (digital) outputs; PI (PI1PI4) pulse inputs; RTC real time clock; FLASH nonvolatile bulk storage device; FRAM nonvolatile RAM; COM1, COM2 interfaces 1, 2; DAU data-acquisition unit. 2 SAFETY REQUIREMENTS 2.1 The meter meets GOST 22261-94 and GOST R 51350-99 safety requirements. 2.2 Electrical shock protection method complies with class II of GOST R 51350-99. 2.3 Insulation between all the current and voltage circuits and load control relay finish

    elements connected together and the earth endures 1 minute 50Hz frequency 4kV AC voltage. While testing, electric test output unit terminals, interface circuits, pulse inputs, back-up power source input should be connected with the earth (the earth conducting foil film, encasing the meter and connected with the flat conductive surface, on which the meter base is mounted).

    Insulation between current circuits connected together and voltage circuits connected together; all the current and voltage circuits and load control relay finish elements connected together; electric test output unit terminals; electric test output unit terminals and pulse inputs endures 1 min. 50Hz frequency 4kV AC voltage.

    2.4 Insulation between each current circuit and all the other meter circuits connected with the earth; each voltage circuit and all the other meter circuits including voltage circuit common leg connected with the earth; load control relay finish elements and all the other meter circuits connected with the earth, endures 6kV pulse voltage influence.

    Insulation between all the current and voltage circuits and load control outputs connected together and earth endures 6kV pulse voltage influence. During the test the electric test output unit terminals should be connected with the earth.

    2.5 Insulation resistance between the meter case and circuits is not less than: 20MOhm at Cl. 3.1.7;

  • 7 MOhm at ambient air temperature (402)C and relative humidity 93% 2.6 Meter installation and operation shall be carried out in accordance with the working

    power system safety standards. 2.7 Do not put or hang any foreign objects on the meter, avoid strokes. 3 METER AND ITS OPERATION DESCRIPTION 3.1 Application The meter is three-phase, multi-purpose, transformer or direct connection (depending on

    modification) and designed for active and reactive electric energy, active, reactive and apparent power, energy loss, voltage frequency, phase-angle, voltage and current RMS values in three-phase four-wire AC circuits measurement and multi-rate metering organization. The kind of energy and power measured is specified by the meter configuration.

    The meter may be used in AMR system for data transmission to the electric energy control, metering and distribution dispatch center. For establishing AMR systems interfaces (pulse outputs, EIA232, EIA485) may be used.

    Measurement results are drawn by the meter mother board microprocessor circuit processing and calculating the voltage and current incomers. Mezzanine boards installation, depending on the modification, allows extending the meter capabilities. The data acquired and other information is displayed on the LCD.

    The meter has an electronic register that accomplishes, depending on the current and voltage transformation ratios set, metering of active, reactive electric energy, energy loss in one or two directions (kWh, MWh, GWh, kVArh, MVArh, GVArh correspondingly).

    The time of the variation in the register indication complies with GOST R 52322-2005 (GOST R 52323-2005), GOST R 52320-2005 and GOST 26035-83, IEC 62053-23:2003 requirements.

    The meter provides, in the presence of the authorized access, setting all the energy parameters to zero.

    The meter, in the absence of external supply voltage and back-up power voltage supplied, operates in the indication mode and provides data exchange with external acquisition and transmission units via optical port (IrDA 1.0) and interfaces.

    The technology software Device administration (hereinafter - DA) application allows creating and modifying the programs for the appropriate meter configuration, programming, diagnostic data reading, signal journaling and performing other tasks. PC connection with the meter via optical port at the place of installation may be available through the sensing head.

    The meter has the ability to register profiles with different time intervals for power averaging and energy accumulation in the set interval (load profiles).

    3.1.1 Meter functionality - The meter allows measuring 12 energy (power) types per phase:

    active energy (power) in both directions (Ai, Ae); four quadrant (R1, R2, R3, R4) reactive energy (power); energy loss in both directions (Li, Le); physical unit-counting input meters values (11, 12,13, 14). - The meter measures and rates energies (powers) via six calculation channels. Each

    channel energy (power) type is specified by the channel configuration. The calculation channel energy (power) is the sum of the energy quantity of all the energy

    (power) types specified by the channel configuration. Energy accumulation per tariff and in total (with progressive total, for a month, for a day),

    maximum powers fixation, power overrun determination, load profile registration are accomplished via all the six calculation channels.

    The calculation channels possible configurations are given in Table 3.1

  • To avoid incorrect data generation, it is allowed to combine in calculation channels only energies (powers) identical in type. Recommended combinations of calculated energies (powers) in the channel are given in Table 3.2

    Table 3.1 Measured and stored data Calculation channel

    unidirectional meter bidirectional meter Channel 1 Ai+Ae Ai Channel 2 Ae Channel 3 Channel 4 Channel 5 Channel 6

    Any from Table 3.2 Any from Table 3.2

    Table 3.2

    Active energy import Designation Active energy export Ai Active energy export Ae Total active energy Ai+Ae 1 quadrant reactive energy R1 2 quadrant reactive energy R2 3 quadrant reactive energy R3 4 quadrant reactive energy R4 Reactive energy import R1+R2 Reactive energy export R3+R4 Inductive reactive energy R1+R3 Capacity reactive energy R2+R4 Reactive energy for active energy import R1+R4 Reactive energy for active energy export R2+R3 Total reactive energy R1+R2+R3+R4 Energy loss for active energy import Li Energy loss for active energy export Le Total energy loss Li+Le Physical quantity of unit-counting input 1 I1 Physical quantity of unit-counting input 2 I2 Physical quantity of unit-counting input 3 I3 Physical quantity of unit-counting input 4 I4

    Notes 1. Identical physical quantities values may be combined in one calculation channel; 2. Energies (powers) telemetric pulses connected with external electric energy

    meters unit-counting inputs may be combined in one calculation channel or added to identical in physics.

    3.1.2 Meter modifications designation Meter designation structure is given in Picture 3.1

  • CE 304 X XXX-XXXXXX Extra modifications:

    Y Bidirectional Unidirectional Impulse inputs No impulse inputs

    Q2 control relay for alternating voltage Interface devices: EIA485 EIA 232

    Optical communication ports: I IrD 1.0 J Optical interface

    Nominal, basic (maximum) current:

    0 1(1.5) A Transformer connection 2 5(7.5) A Transformer connection 4 5(50) A Direct connection 8 10(100) A Direct connection Nominal voltage:

    0 57.7 V 3 220 V

    Accuracy class per active/reactive electric energy: 4 0.2S/0.5 6 0.5S/1 8 1/2 9 2/2 Case type: S3X board mounting

    Picture 3.1 Meter designation structure 3.1.2.1 Basic modifications Basic modifications are accuracy class, type of connection, maximum and nominal or

    basic current relationship meter versions. Accuracy class meter versions depending on nominal voltage, nominal, basic (maximum)

    current with appropriate meter constant values are given in Table 3.3 Table 3.3 Meter designation Accuracy

    class Nominal

    voltage, V Nominal, basic (maximum) current, A

    Meter constant imp/kWh, imp/kVArh

    Point position

    CE 304 X 400-XXXXXX 0.2S/0.5 57.7 1 (1.5) 50000 000.0000 CE 304 X 402-XXXXXX 0.2S/0.5 57.7 5 (7.5) 10000 0000.000 CE 304 X 432-XXXXXX 0.2S/0.5 220 5 (7.5) 4000 0000.000 CE 304 X 600-XXXXXX 0.5S/1 57.7 1 (1.5) 50000 000.0000 CE 304 X 602-XXXXXX 0.5S/1 57.7 5 (7.5) 10000 0000.000 CE 304 X 632-XXXXXX 0.5S/1 220 5 (7.5) 4000 0000.000 CE 304 X 800-XXXXXX 1/2 57.7 1 (1.5) 50000 000.0000 CE 304 X 802-XXXXXX 1/2 57.7 5 (7.5) 10000 0000.000 CE 304 X 834-XXXXXX 1/2 220 5 (50) 800 00000.00 CE 304 X 838-XXXXXX 1/2 220 10 (100) 400 00000.00 CE 304 X 934-XXXXXX 2/2 220 5 (50) 800 00000.00

  • CE 304 X 938-XXXXXX 2/2 220 10 (100) 400 00000.00 3.1.2.2 Extra modifications

    Extra modifications bidirectional, unidirectional meter versions with pulse outputs and load control relay , optical interface or IrDA 1.0, pulse input modules, one basic (COM1) or two basic (COM 1) and extra (COM 2) interface module.

    Meter versions depending on interfaces applied are given in Table 3.4. Table 3.4

    Meter designation Interface module EIA485 EIA232 basic

    COM1 extra COM 2

    basic COM 1

    extra COM 2

    CE 304 X XXX-XAXXX + - - - CE 304 X XXX-XAAXXX + + - - CE 304 X XXX-XAEXXX + - - + CE 304 X XXX-XEAXXX - + + - CE 304 X XXX-XEXXX - - + - CE 304 X XXX-XEEXXX - - + + Note + with interface; - no interface. 3.1.2.3 Meter designation example

    While making an order, the necessary meter modification is identified by the designation structure given in Picture 3.1 and in accordance with Clauses 3.1.2.1, 3.1.2.2.

    Meter designation example meter for board mounting, active energy accuracy class 0.5S and reactive energy 1, with 57.7 V nominal voltage, 1A nominal and 1.5 A maximum current, with optical interface, interface modules EIA485/EIA232, with alternating voltage load control relay, pulse inputs, unidirectional, is designated:

    Three-phase active and reactive electric energy meter CE 304 S31 600 JAEQ2H. 3.1.3 The meter is certified.

    Information on meter certification is given in technical passport .411152.064 TP. 3.1.4 Normal application conditions: - ambient temperature (232) C; - relative humidity 3080 %; - atmospheric pressure 70106.7 kPa (537 800 mm of mercury); - measuring network frequency (500.5) Hz; - measuring network current and voltage waveform - sinusoidal with non-sinusoidal

    coefficient not more than 5%. 3.1.5 Operating application conditions The meter is connected with three-phase ac network and installed indoors at the following

    operating application conditions: - operating temperature range -40 60 C; - ambient relative humidity 70106.7 kPa (537 800 mm of mercury); - measuring network frequency (502.5) Hz; - measuring network current and voltage waveform - sinusoidal with non-sinusoidal

    coefficient not more than 8%. 3.2 Environmental conditions 3.2.1 By the resistance to the environment the meter pertains to Group 4 according to

    GOST 22261-94 with extended temperature and humidity range that complies with category 3 modification T according to GOST 15150-69.

  • By the resistance to the mechanical influence the meter pertains to Group 2 according to GOST 22261-94.

    3.2.2 The meter is resistant to dust and water penetration. The degree of protection is IP51 according to GOST 14254-96.

    3.2.3 The meter is resistant to impacts. Half-sine wave pulse - 18 ms, maximum acceleration 30gn (300 m/s ). 3.2.4 The meter is resistant to vibration (10150) Hz. 3.2.5 Transition frequency f 60 Hz, f < 60 Hz constant movement amplitude 0.035

    mm, f > 60 Hz constant acceleration 9.8 m/s2. 3.2.6 The meter case endures (0.220.05) Nm force movement shock influence on the

    case outside surface, including the window, and on the terminal cover. 3.2.7 By resistance to mold-fungi influence the meter buses and components designed for

    operation in tropical zones comply with GOST 9.048-89 requirements. Accepted fungoid growth up to 3 points according to GOST 9.048-89. 3.2.8 The meter is immune to electrostatic discharge of up to 8 kV voltage. 3.2.9 The meter is immune to high-frequency electromagnetic fields. Frequency range

    80-2000 MHz, field voltage 10 V/m. 3.2.10 The meter is resistant to high-speed transient eruptions of up to 4kV voltage. 3.2.11 The meter does not generate conducted or radiated interference, that can influence

    the other equipment operation. By the radio-frequency interference suppression capability the meter meets GOST R

    52320-2005 requirements. 3.3 The meter delivery set 3.3.1 The meter delivery set is given in Table 3.5. Table 3.5

    Documents indexing Nomination and designation

    Quantity Application

    According to Cl. 3.1.2 .411152.064OM .411152.064TP .411152.064D1* .411152.064MR**

    Three-phase active and reactive energy meter CE304_____________ (one of the modifications) Operating manual Technical passport Verification technique Midlife repair manual Technological software***

    1 p. 1 c. 1 c. 1 c. 1 c. 1 CD

    Notes * - supplied on verification body request; ** - supplied on repair organizations request. *** - TSW Device administration for meter scanning and programming can be found on the

    Web site http://www.energomera.ru. For data exchange via optical interface the sensing head compliant with GOST R IEC 61107-

    2001 (optical head) is used. For data exchange via IrDA 1.0 any device supporting protocol IrDA 1.0 (HHC, notebook, PC,

    etc.) is used.

  • 3.4 Specifications 3.4.1 By active energy measurement the meters meet GOST R 52320-2005, GOST R

    52322-2005 (for class 1 and 2), GOST R 52323-2005 (for class 0.2 and 0.5 S), and by reactive energy measurement GOST 26035-83, IEC 62053-23:2003.

    3.4.2 To be guaranteed are considered the specifications that are given with accesses and value limits. Value items without accesses are referential.

    The basic specifications are given in Table 3.6. Accepted value limits of measured value errors are given in Annex A. Table 3.6

    Characteristic nomination Characteristic item Note Nominal (maximum) current 1 (1.5); 5 (7.5) A Basic (maximum) current 5 (50); 10 (100) A Nominal phase voltage 57.7; 220 V

    Depending on modification

    Nominal network frequency 502.5 Hz Measuring network current and voltage nonsinusoidality ratio, %, not more

    8

    direct connection

    transformer connection

    Active/reactive energy

    - 0.001 Inom 0.2S; 0.5S/0.5 0.004Ib 0.002 Inom 1/1

    Threshold sensitivity

    0.005Ib 0.003 Inom 2/2 LCD decimal digits quantity From Table 3.3 Apparent power consumed in each current circuit, not more than

    0.1 VA At nominal (basic) current

    4.0 VA (2.0 W)

    At nominal voltages 57.7 V

    Apparent (active) power consumed in each voltage circuit, not more than

    8.0 VA (2.0 W) 220 V Clock rate basic absolute accuracy limit

    0.5 s/day

    Clock rate complementary error at standard temperature and power-off

    1 s/day

    Clock rate manual adjustment once a day

    30 s Once a day

    0.15 s/Cday -10 45 C Temperature complementary time error limit 0.2 s/Cday -40 60 C Data storage time at power-off 10 years Tariff quantity up to 4 Tariff zones quantity up to 15 Season quantity up to 12 Exceptional days quantity up to 32 Tariffication graphs quantity up to 36 Storage period of metering channels data accumulated during a month per tariff

    up to 13 months

    Storage period of metering channels data accumulated during a day per tariff

    up to 46 days Individual averaging time for each profile

    Load profile quantity up to 16 Each profile period of storage, days, 330 At averaging time

  • not less than 30 min Load control relay quantity up to 2 Dc back-up power source voltage 9-15 V Load-carrying capacity, not

    less than 500 mA Electric pulse outputs nominal (accepted), not more than

    10 (24) V Dc voltage

    Electric pulse outputs nominal (accepted value) current, not more than

    10 (30) mA Dc voltage

    Nominal (accepted) commuted voltage at load control relay terminals, not more than

    220 V (265 V) Ac voltage

    Nominal (accepted) commuted current at load control relay terminals, not more than

    1A Ac voltage

    Output pulse width 1-127 ms or meander Set while programming Input pulse width (minimum), ms 1-255 Each pulse inputs register maximum capacity

    99999999 pulses

    Exchange rate via interface 300-115200 baud Exchange rate via optical port 300-57600 baud Time of power averaging (the averaging period is chosen by the customer from the range)

    1; 2; 3; 4; 5; 6; 10; 12; 15; 20; 30; 60 min

    The time of updating all the meter readings

    1 s

    The time of any meter parameter reading via interface or optical port

    0.06 1000 s (at the rate of 9600 baud)

    Depends on parameter type

    Initial launch, not more 5 s From the moment of voltage supply

    The meter weight, not more 2.0 kg Dimensions (length; width; height), not more

    278; 173; 90 mm

    Mean time to failure 120000 h Average service life 30 years Unauthorized access protection The meter password

    Hardware lock-up

    3.5 The meter arrangement and operation

    3.5.1 The meter arrangement The meter arrangement complies with GOST R 52320-2005 and manufacturer outlines. The meter is produced in plastic case. The meter general arrangement are given in Picture 3.2 The meter overall dimensions are given in Table 3.6 and in Annex B. The meter case comprises upper and lower perimeter conjugated components, transparent

    window and removable terminal cover. The meter front panel comprises: LCD; two light indicators active and reactive energy quantity;

  • optical port elements; lithium battery and AMP button (under the extra cover); SHOT and SCROLL buttons; caption panel, according to Section 11 of this OM. To obtain the access to the AMP button (programming allowance) it is necessary to

    remove the sealing put by the power supply organization that installed the meter and to open the extra cover. Contacts for meter connection with the network, back-up power source, interface lines, pulse inputs and outputs are hidden by the plastic cover (Fig. 3.2). Illustration of the terminal cover under the plastic cover depending on the meter modification is given in Figures 3.3 (for direct connection meters) and 3.4 (for transformer connection meters). Arranged in the case:

    the meter printed-circuit board (the basic one); power module; pulse outputs module; pulse inputs modules (if available, depending on modification); one or two interface modules (depending on modification); three measuring current transformers.

  • 1 - LCD; 2 light indicator of reactive energy quantity; 3 - light indicator of active energy quantity; 4 optical port elements (IrDA 1.0); 5 lithium battery and AMP (under the extra cover); 6 SHOT button; 7 SCROLL button; 8 - caption panel; 9 terminal cover; 10 points of sealing.

    Figure 3.2

    1

    3 2

    4

    5

    6

    8

    10

    10

    10

    9

    8

    7

  • Figure 3.3

    Figure 3.4

  • 3.5.2 The principle of operation The principle of operation is illustrated by the structural diagram given in Figure 3.5. +URES

    Figure 3.5 Structural diagram

    3.5.2.1 The basic printed-circuit board AC line currents and voltages are measured by special current sensors (transformers) and resistance dividers accordingly. Value conversions are accomplished by using six-channel analog-to-digital converter (ADC) that fulfils analog-to-digit conversion of input signals instantaneous amplitude and transmission via serial synchronous interface to MC. ADC digital code values come into serial synchronous microcontroller (MC) port. MC accomplishes calculation of currents and voltages, active, reactive, apparent powers and energies, and also displacement angle and voltage signal basic frequency meansquare values. MC makes connection between all the peripheral units. The basic electronic meter elements are installed on the same printed-circuit board:

    resistance dividers; load resistors for three current sensors; ADC; MC; clearing circuit; memory FRAM with real time clock (RTC);

    PM

    UA

    U

    ADC

    Up

    MC

    FRAM+RTC

    TM

    Kb

    LCD

    PI

    OP

    FLASH

    1

    UB

    UC

    IA

    IA0

    IB

    IB0 IC IC0

    -URES

    2

    LI

  • memory FLASH; optical port elements (OP); liquid-crystal display (LCD).

    3.5.2.2 Power module To supply the meter with power pulse reverse converter, converting rectified input

    voltages into the voltage necessary for supplying all the meter blocks and modules with power, is used. To supply the meter with power from the back-up power source (BPS) low-voltage reverse converter to which the back-up power voltage (915 V) may be supplied. In the input voltages UA, UB, UC absence the meter automatically switches to the BPS operation (if the back-up power is supplied). In the input voltages UA, UB, UC presence the BPS automatically switches off.

    The BPS input circuits are galvanic isolated from the other circuits and endure 4 kV breakdown meansquare voltage.

    3.5.2.3 Voltage transducers To match phase voltages with ADC input amplitude levels the resistance dividers are

    used. Phase (phase-to-phase) voltages are supplied from PM via the upper divider arm resistors

    to the basic printed-circuit board, where the lower divider arm resistors are installed and led up to the input signal level required for ADC. Metal-film resistors with minimum temperature coefficient are used in the dividers.

    3.5.2.4 Current transducers Electronic circuit diagram receives each phase current via meter-mounted current

    transformers. Transformer secondary sides are load resistance connected, as a result the voltages proportional to input currents are supplied to ADC inputs.

    3.5.2.5 Signal conversion and computation ADC measures the instantaneous values proportional to phase voltages and currents via

    six channels parallel, converts them into the digital code and transmits them via the high-speed serial data link to the MC calculating machine.

    By sampling voltage and current instantaneous values the MC calculating machine calculates mean values for the period of measuring the required values considering the calibration factor according to the following formulas:

    For voltage and current RMS values per phase calculation the following formula is used

    N

    UUU

    N

    ii

    F

    == 1

    2

    , (3.1)

    N

    III

    N

    ii

    F

    == 1

    2

    3.2)

    where KU, KI given phase calibration factors (are entered while calibration); N data selections quantity during the time of measuring; Ui, Ii voltage and current data selection instantaneous value Each phase active power is calculated by the formula

  • NIUIU

    N

    iii

    F

    =

    = 1 , (3.3)

    Three-phase network active power: P = PPA + PPB + PPC, (3.4)

    where PPA, PPB, PPC each phase active power. Three-phase network each phase active power is calculated by the formula

    PPP UIS = , (3.5) where UP, IP voltage and current RMS values in a corresponding phase. Three-phase network apparent power:

    S = SPA + SPB + SPC, (3.6) where SPA, SPB, SPC each phase apparent power. Each phase reactive power is calculated by the formula

    22PPP SQ = , (3.7)

    where SP, PP apparent and active power in a corresponding phase. Three-phase network reactive power:

    Q = QPA + QPB + QPC, (3.8) where QPA, QPB, QPC each phase reactive power. Each phase power loss in current circuits is calculated by the formula

    A = RPA I2PA + RPB I2PB + RPC I2PC (3.9) where IPA, IPB, IPC each phase current RMS values; RPA, RPB, RPC each phase transmission line active resistance. Note if RPA, RPB, RPC = 1 Ohm power loss is equal to the specific power loss. While the

    meter verification R reaches the state of 1 Ohm equality (specific energy loss is verified). Active power factors are calculated by the formula

    PA

    PA

    SPA=cos ,

    PB

    PB

    SPB =cos ,

    PC

    PC

    SPC =cos ,

    =

    SPcos , (3.10)

    where PPA, PPB, PPC, - each phase active power calculated by the formula (3.6), W; SPA, SPB, SPC each phase apparent power calculated by the formula (3.8), VA P, S- summarized active and apparent power correspondingly; Reactive power factors are calculated by the formula

    PA

    PA

    SQA=sin ,

    PB

    PB

    SQB =sin ,

    PC

    PC

    SQ

    C =sin , =

    SQsin , (3.11)

    where QPA, QPB, QPC, - each phase reactive power calculated by the formula (3.10), VAr. Q- summarized reactive power. By active and reactive power factors the quadrant number is calculated.

  • Energy quadrant distribution is given in Figure 3.6.

    Figure 3.6 Active and reactive energy (power) quadrant distribution diagram

    For each of the calculating machine six channels, configured for certain energy types

    computation, per-phase values, integrated in the period of 1 sec., are calculated: - of active energy (power) import, Ai, if the phase apparent power phasor is in the I or IV

    quadrants; - of active energy (power) export, Ae, if the phase apparent power phasor is in the II or

    III quadrants; - of reactive energy (power), R1 (R2, R3, R4), if the phase apparent power phasor is in

    the I (II, III, IV) quadrants correspondingly; - of import (export) active energy (power) loss, Li (Le), if the phase apparent power

    phasor is in the I or IV (II or III) quadrants correspondingly. On the basis of the calculating machine channels calculated energies MC transmits

    energy consumption signals to the pulse outputs (in case they are configured as telemetry outputs), which may be connected with AMR system.

    3.5.2.6 FRAM memory All the data necessary for multi-rate calculation results safety provision is stored in the

    nonvolatile memory FRAM on the basic printed-circuit board. The data comprises: calibration factors; configuration parameters; tariffication parameters; six metering channels (metering per tariff and in total) storage units; six metering channels (metering per tariff and in total) storage units values for the

    current and 12 previous months; six metering channels (metering per tariff and in total) storage units values for the

    current and 45 previous days; six metering channels (metering per tariff) maximum power in the set averaging

    time period for the current and 12 previous months; load profile current averaging time active records; logs designed for 40 records each with the event date and time fixation:

    o of changeable parameters programming; o network parameters out-of-tolerance; o self-diagnosis negative results.

    3.5.2 FLASH memory Bulk nonvolatile memory FLASH is designed for load profiles data storage by six metering channels with different averaging times.

  • 3.5.2.8 The meter interfaces The meter provides data exchange with external data processing units depending on

    modification via optical port and two interfaces in accordance with GOST R IEC or IrDA 1.0. Data exchange via optical port and (or IrDA 1.0) and the second interface COM2

    (additional interface module) simultaneously is impossible. All the interfaces contacts are galvanic isolated from the other circuits and endure 4 kV

    breakdown meansquare voltage. The optical port is designed in compliance with GOST R IEC 61107-2001. OP is

    designed for the local meter connection via optical head, connected to the PC COM port. The meter modifications with interface module EIA232 may be connected directly to the

    PC COM port. The meter modifications with interface module EIA485 allow connecting not less than 31

    devices (meters) with one bus. 3.5.2.9 Pulse outputs The meter has six electrical pulse outputs (TM1TM6) designed for the current tariff

    indication, devices (the other meters) tariff switch, the exceedance of maximum indication, remote control, etc.

    Four outputs are realized on the transistors with open collector and designed for dc voltage commutation. Nominal power voltage (102) V, maximum accepted 24 V. Commutated nominal current value is equal to (101) mA, maximum accepted 30 mA. All the four outputs may be used as a basic transmission output unit with parameters compliant with GOST R 52320-2005, GOST R 52322-2005 (GOST R 52323-2005).

    Two outputs are realized on bidirectional thyristors and designed for dc voltage commutation. Nominal power voltage 220 V, maximum accepted 265 V. Commutated nominal current value is not more than 1 A. Both outputs may be used as load control relays.

    All the pulse outputs are galvanic isolated from the other circuits and endure 4 kV breakdown meansquare voltage.

    3.5.2.10 Pulse inputs The meter has four electrical pulse inputs (PI). Each IP is designed for progressive total

    calculation of pulse quantity received from the external devices with electrical test outputs in compliance with GOST R 52322-2005 (GOST R 52323-2005); for metering the energy received from the external measuring units to identify different mechanical sensors condition.

    Pulse inputs module has internal power source, isolated from the other meter circuits, with output voltage (5.00.5) V. Each pulse input current is bounded by 1.5 kOhm resistors.

    All the pulse inputs are galvanic isolated from the other circuits and endure 4 kV breakdown meansquare voltage. 3.5.2.11 Liquid-crystal display LCD is used for indication of the measured and accumulated values, additional parameters and messages. To make scrolling easy all the indicated data is divided into the separate groups. Each group can comprise different parameters quantity.

    Scrolling is accomplished by the customer with the keyboard (Kb). Displayed on LCD data is given in Figure 3.7

  • Figure 3.7 3.5.2.12 Light indicators

    The meter has two light indicators (LI) that operate with the basic transmission unit frequency. The left light indicator displays active energy, the right one reactive energy. Light indicators may be used for verification.

    4 THE METER PREOPERATION

    4.1 Unpacking 4.1.1 Visual examination should be carried out after unpacking to make sure that the sealing is in place and there is no mechanical damage.

    4.2 Preoperation 4.2.1 The meters produced by the manufacturer have factory settings in compliance with

    the programmable parameters list given in TP. Before mounting change the factory settings to the required in case it is necessary. It is

    sufficient to supply one of the phases with nominal voltage. The meter reprogramming may be accomplished via the interfaces and OP with the TSW that can be found on the Web site (Cl. 3.3.1)

    4.3 Installation procedure 4.3.1 Set the reprogrammable parameters in compliance with Cl. 4.2 and 4.6 of this OM. 4.3.2 The meter should be connected to three phase AC network with the nominal

    voltage, indicated on the meter panel. Terminal cover should be removed and conducting wires should be connected according to the connection diagram, indicated on the meter cover. If the meter is to be connected to the AMR system, signal wires should be connected to the telemetric or interface outputs in compliance with the connection diagrams.

    4.4 Connection diagrams 4.4.1 Designation of terminal block contacts for pulse outputs, inputs, back-up power

    source connection is given in Figure 4.1

    Figure 4.1

    TARIFF Mo Tu We Th Fr Sa Su

    88888888 G k/VArh 8 88:88 88

    cos % Hz MONTH DAY

    TOTAL LIMIT

    2

    ERR PHASE ABC

  • 1 TM1TM4 (contacts 1219) pulse outputs connection; 2 pulse inputs (contacts 2025) and back-up power (contacts 6, 27) connection; 3 TM5, TM6 (contacts 3235) pulse outputs (load control relay) connection; 4 interfaces (contacts 16) connection.

    4.4.2 TM1TM4 pulse outputs connection To provide pulse outputs operation it is necessary to supply dc voltage according to the diagram given in Figure 4.2.

    Figure 4.2 Pulse outputs connection diagram Resistance value R in pulse output load circuit is calculated by the formula: ( ) 01.0/0.2= UR where U output supply voltage, V.

    4.4.3 TM5, TM6 pulse outputs connection Load connection diagram is given in Figure 4.3. Commutation current shall be not more

    than 1 A. AC voltage 220 V.

    Figure 4.3 Load connection diagram

    4.4.4 Pulse inputs connection Pulse inputs connection diagram is given in Figure 4.4. Circuit closing connection contacts shall endure 5V voltage, dc 10mA. Contact resistance in closed condition shall be not more than 100 Ohm.

    304 "12" "14"

    "13" "15"

    "16" "18" "17" "19"

    TM4

    -R + 824

    V

    -R + 824

    V

    -R + 824

    V

    -R + 824

    V

    TM3

    TM2

    TM1

    304 "32" "34" "33" "35"

    242 V 242 V

    RL

    RL

    TM5

    TM6

  • Figure 4.4 Pulse inputs connection diagram

    4.4.5 Back-up power source connection Back-up power source (BPS) connection shall have output voltage 915 V, output capacity not less than 500mA. BPS connection diagram is given in Figure 4.5.

    Figure 4.5 Diagram of meter connection with back-up power source 4.4.6 EIA485 interface connection EIA485 interface meter is connected in compliance with EIA485 standard and connection diagram given in Figure 4.6.

    In case earth potentials in places of the meter and DAU (data acquisition unit) mounting are equal, it is sufficient to connect the meter contact 5 to the zero potential point, otherwise drainage cable line should be connected to the contact 5 of each meter through C2-33H-1-100 Ohm resistor or identical one in accordance with Diagram 4.6.

    In case the interconnection line length does not exceed some meters and there are no interference sources, the connection diagram may be essentially simplified by connecting the meter to the DAU or PC with only two signal cables A and B without terminal resistors.

    304 "20" PI 1 "22"

    PI 2

    "23"

    "21" PI 3 "24" PI 4 "25"

    +

    -+

    +

    +

    -

    -

    -

    304+ "26"

    "27" -

    BPS

  • Rb 560 Ohm, bias resistors are installed in the meter. To connect them it is necessary to connect several meters contacts 4 6 and 3 1 COM1 (COM2) depending on the line interference level on the line. RT 120 Ohm, terminal resistor with the rating equal to cable wave impedance. Figure 4.6 EIA485 interface lines connection diagram In EIA485 interface meters not connected to the interface line error messages may appear on LCD. To avoid their appearance it is necessary to connect the meter in accordance with the diagram given in Figure 4.7.

    Figure 4.7 Bias resistor connection diagram

    4.4.7 EIA232 interface connection EIA232 interface meter is connected in accordance with EIA232 standard and connection diagram given in Figure 4.8.

    Figure 4.8 EIA232 interface lines connection diagram 4.4.8 Recommendations on interface circuits connection to PC directly or via external modems are given in Annex D.

    4.5 Power source replacement 4.5.1 Remove the meter programming access cover sealing (Figure 3.2). 4.5.2 Remove the power source holder. 4.5.3 Remove the power source broken-down and install a new BR2032 or analogous.

    "1" ("2") CE 304

    100 Ohm 100 Ohm

    RT

    DAU

    Vcc B A GND 3 4 5

    100 Ohm100 Ohm

    Rd

    RT B Rb

    "1"("2") 304

    3 4 6 1 5

    Rb

    100 OhmRd 100 Ohm

    A

    "1" ("2") 4 3 6 1

    304

    DAU

    304 "1" ("2")

    TxD 4

    3

    RxD

    2 5

    RINGGND

  • 4.5.4 Connect the power source holder plug to the meter and put it in its place. Note To avoid clock inaccuracy while the power source replacement, the activities

    mentioned above should be completed with the meter in operation. 4.6 The meter configuration The meter programming and reading is accomplished with AMR system or PC (with the

    TSW Administration program installed) via one of the interfaces by using a corresponding adaptor or via the optical port by using the optical head in accordance with GOST R IEC 61107-2001 or IrDA 1.0. Data formats for the interface exchange are given in Annex E.

    While the meter programming, the date, time, access passport and parameters list are fixed in the programmable parameters log. Additionally, in some parameter group recorders the date, time, access password and the given group programming quantity are fixed.

    In the identification message line the meter outputs: manufacturer identification code EKT product identification code CE304vX, where X meter data set version.

    The meter programmable parameters typical configuration: calculating machine channels depending on type (CL 4.6.1); external current and voltage transformers transformation ratios 1; phase wires resistance 1 Ohm; calculating machine channels power averaging time period 30min; calculating machine channels power averaged limits 0 (are not set); voltage fluctuation upper (lower) boundaries 120 (80) % of UNOM; time-of-day pulse output control switches 0 (are not set); pulse outputs 1, 2,3, 4 - calculating machine channels 1, 2, 3, 4 energy telemetry meander; pulse outputs 5, 6 direct control, dead condition; pulse inputs switched off; pulse inputs constants 1; pulse inputs transformation ratios -1; rate scale not set; profile configurations not set; time Moscow; summer (winter) time switch months March, (October); access password #1 -777777; other passwords not set; the meter address-identification code not set; initial interface exchange rate 300 bauds; operating interface exchange rate 9600 bauds; interface activity time 4s; response delay time 200 ms; programming authorization with the ACCESS button; accumulated energy reset with buttons unauthorized; consequent same name parameters outputting into interface without a name allowed; indication automatic return allowed. The full list of programmed parameters and their values is given in TP. 4.6.1 Calculating machine channels configuration (KANzz)

  • The meter allows programming six calculation channels for different energy (power) types calculation:

    both directions (Ai, Ae) active energy (power); four quadrants (R1, R2, R3, R4) reactive energy (power); both directions energy (power) loss (Li, Le); external measuring element unit-counting input physical quantity values (11, 12,

    13, 14). Energy (power) proportional to telemetry pulses of the external electricity meters

    connected to unit-counting inputs may be grouped in one calculation channel with meter own measurements.

    ATTENTION! To avoid incorrect data formation only identical in energy (power) type are allowed to be grouped in the calculation channels.

    ATTENTION! To avoid incorrect indication of previously metered energies and powers, after calculation channels reprogramming it is necessary to reset accumulated energies and load profiles.

    For unidirectional meter: The first calculating machine channel is always programmed for total active energy

    calculation (Ai + Ae). Consequently, energy will be metered via this channel independently of energy flux direction.

    For bidirectional meter: The first calculating machine channel is always programmed for imported active energy

    calculation (Ai). Consequently, phase energy with positive active power (P+, quadrant I or IV) will be metered via this channel.

    The second calculating machine channel is always programmed for exported active energy calculation (Ae). Consequently, phase energy with negative active power (P-, quadrant II or III) will be metered via this channel.

    Other five or four calculating machine channels may be programmed for various energy (power) types calculation to meet Customers requirements.

    Example: - total active energy metering (for bidirectional meter); - imported reactive energy metering; - exported reactive energy metering; - total energy loss metering, or - imported reactive energy metering; - exported reactive energy metering; - energy loss metering for imported active energy; - energy loss metering for exported active energy. For active energy (power) import metering and control accomplished by the enterprise that

    has some lead-in feeders (three), it is necessary to install CE304 meter with pulse input module into one feeder. Simple active energy meters shall be installed into other feeders (two) and their main transmitting unit outputs shall be connected to pulse inputs (PI1, PI2). Pulse inputs shall be programmed in accordance with connected external meter parameters (constants and transformation ratios). Calculating machine channel #4 shall be programmed for imported active energy and unit-counting input energies (Ai+11+12) calculation.

    Typical configuration of calculating machine channels is given in Table 4.1 Table 4.1

  • Measured and stored values of Calculation channel unidirectional meter bidirectional meter

    Channel 1 Ai+Ae always Ai always Channel 2 R1 Ae always Channel 3 R4 R1+R2 Channel 4 Li+Le R3+R4 Channel 5 Ai Li Channel 6 R1+R2+R3+R4 Le

    4.6.2 Calculation results reduction to input end (FCCUR, FCVOL) The meter can accomplish input end calculation considering measuring current and voltage

    transformers transformation ratios. Calculated energy and power values and also network quality parameters are automatically multiplied by voltage transformer transformation ratio (Rv) and current transformer transformation ratio (Rc) in metering point. In this case measured values displayed on LCD and transmitted via digital interfaces indicate measuring transformers input end values.

    The meter operation light indicators (LI) and pulse outputs in telemetry mode indicate energy without considering Rv and Rc.

    For the meter direct connection or obtaining the output end (meter terminals) measurement results, it is necessary to set transformation ratios Rv=1, and Rc=1.

    4.6.3 Electric main phase wires resistance (RESzz) The meter can accomplish calculation energy (power) loss in electric main wires for each

    phase. To do this, it is necessary to set each controlled line segment phase wire resistance. Calculation of active power loss in wires is accomplished by the formula P=I2R.

    4.6.4 Power averaging time interval (TAVER) Calculating machine channel power averaging time interval for commercial metering may

    be set in the range of 160 min. interval duration is chosen from the range: 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60 minutes.

    Each calculating machine channel power, averaged in a set interval, is used: For each tariff maximum power finding and fixation during a month; For set power limit exceedence finding per tariff.

    4.6.5 Averaged power limits (LIMzz) For each calculating machine channel and each tariff their own limit of power averaged in

    a set interval may be set. Average power limit value is set in kW (kVAr) considering transformation ratios Rv and Rc used (reduction to input end). For average power limit value equal to zero, power limit exceedence verification is not taken.

    4.6.6 Phase voltage fluctuation boundaries (LEVUP, LEVDN) For event fixation in fluctuation log and signal formation at pulse output in case of

    measured voltage value limit exceedence, upper and lower boundaries of accepted fluctuation are set in percents of nominal voltage. Value range 0130%.

    Phase voltage failure finding boundary is fixed and comprises 5% of nominal voltage. 4.6.7 Time-of-day pulse output control switches (TMTzz) The meter has four independent time-of-day pulse output switches. Any available rate

    scale is fixed for each switch. Pulse output will be in dead mode during tariff #1 operation time of day and in closed mode during tariff #2 operation time of day. Any other scale tariff doesnt cause pulse output mode switch.

    4.6.8 Pulse outputs configuration (TELzz)

  • The meter allows programming of up to eight pulse outputs (TM1TM8) for various verification or control signals formation. Each pulse output is set individually and allows commuting circuits of external devices with electrical pulse output set module characteristics. Each pulse output may be set for performing the following functions:

    calculating machine channel test output unit (telemetry); set calculating machine channel power threshold exceedence response; set time of day response; current tariff response; phase voltage response; direct control by a command via interface; the basic quartz-crystal resonator test. The list of functions (events) for pulse output is given in Table 4.2

    Table 4.2 Number Event description

    0 The basic quartz-crystal resonator test 1 1 calculating machine channel energy telemetry 2 2 calculating machine channel energy telemetry 3 3 calculating machine channel energy telemetry 4 4 calculating machine channel energy telemetry 5 5 calculating machine channel energy telemetry 6 6 calculating machine channel energy telemetry 7 One of the phases is switched off 8 Voltage of any phase is less than the set low level 9 Voltage of any phase is more than the set upper level 10 1 calculating machine channel power limit is exceeded 11 2 calculating machine channel power limit is exceeded 12 3 calculating machine channel power limit is exceeded 13 4 calculating machine channel power limit is exceeded 14 5 calculating machine channel power limit is exceeded 15 6 calculating machine channel power limit is exceeded 16 Time tariff #1 is active 17 Time tariff #2 is active 18 Time tariff #3 is active 19 Time tariff #4 is active 20 Time of day control according to switch #1 21 Time of day control according to switch #2 22 Time of day control according to switch #3 23 Time of day control according to switch #4

    2431 Reserve 32 Direct control

    4.6.8.1 Calculating machine channel test output unit (telemetry) In this mode pulses appear at the output with the frequency proportional to a set

    calculating machine channel energy quantity without considering transformation ratios of current, voltage, pulse input transformers in the metering point. The meter constant pulse quantity for kWh (kVAr), is determined by meter modification according to Table 3.3.

    For pulse output operation in telemetry mode it is necessary to: set the number from the list of functions (calculating machine channel choice); set the required telemetry pulse duration from 1 to 127 ms or meander; set the telemetry pulse active level dead or closed. Pulse output in telemetry mode is usually used for meter verification.

  • 4.6.8.2 Set calculating machine channel power threshold exceedence response While performing this function, calculation of assessed mean power of calculating

    machine channel is used. Assessed mean power is the power averaged from the beginning of the averaging interval up to the current time. It informs about the energy flux tendency in a set interval and serves for indication of the set power level (limit) exceedence in a set averaging interval.

    Assessed power limit exceedence verification for the current tariff is accomplished every minute of the averaging interval.

    In this mode pulse output will be in dead condition during the first minute of the averaging interval. Every next minute pulse output switches to the mode:

    closed at developing assessed power of power limit; dead at assessed power value below power limit. The function is used for the power limit exceedence indication or as a load control relay. For pulse output operation in this mode it is necessary to: set the number from the list of functions (calculating machine channel choice); set the calculating machine channel power limit for tariffs controlled. 4.6.8.3 Set time of day response While performing this function rate scale is used. The meter has four independent time-

    of-day pulse output switches. Any rate scale is fixed for each switch. Pulse output will be in dead mode during time of day when tariff #1 is active and in closed mode during time of day when tariff #2 is active. Any other scale tariff doesnt cause pulse output switch.

    The function is used for control instruction issue in a set time of day. For pulse output operation in this mode it is necessary to: set the number from the list of functions (switch choice); schedule tariff #1 and tariff #2 day switch; set the number of rate scale for the switch chosen (TMTzz). 4.6.8.4 Current tariff response Each pulse output may be fixed for any of four tariffs operation time indication. Pulse

    output will be in closed mode during the fixed tariff operation and in dead mode during the rest of the day. The function is used for tariffication instruction issue to the external nontariff devices.

    For pulse output operation in this mode it is necessary to: set the number from the list of functions (tariff choice). 4.6.8.5 Phase voltage response Each pulse output may be fixed for one of the phase voltage modes indication: any phase voltage is absent; any phase voltage is less than a set low level; any phase voltage is more than a set upper level. Phase mode information refreshment is accomplished once a second. The function is used for bad quality network indication. For pulse output operation in this mode it is necessary to: set the number from the list of functions (controlled mode choice). 4.6.8.6 Direct control by a command via interface Each pulse output may be fixed for indication of the mode set via interface. The function is used for remote external devices control. For pulse output operation in this mode it is necessary to: set the number from the list of functions (control choice);

  • set the required output mode (TMDIR). 4.6.8.7 The basic quartz-crystal resonator test. Each pulse output may be fixed for issue of meander with a period of 10 sec. proportional

    to the basic quartz-crystal resonator frequency. The function is used for verification and calibration of the basic quartz frequency

    technological parameter. For pulse output operation in this mode it is necessary to: set the number from the list of functions (test choice). 4.6.9 Pulse inputs configuration (INMzz, INCzz, INSzz) The meter allows programming four pulse inputs (PI1PI4) for external sensors pulses

    calculation with their successive conversion into named units. Those sensors can be represented by particularly electricity meters, utility meters with pulse outputs. Also pulse input may be used for events quantity calculation and receiving information on connected mechanical burglar and fire alarm sensors condition.

    Pulse quantity metering mode is set individually for each input: no metering; by closed to dead state transition leading edge; by dead to closed state transition trailing edge; by both edges. To avoid metering afterpulses, caused by short spurious signals at pulse input connection

    diagrams, input filter constant is set in the range of 1255 ms. Pulses with the length less than filter constant will be hidden for the meter.

    For the named physical quantities calculation by the unit-counting inputs the external meter constant is entered. That meter transmits pulses proportional to measured value to the basic transmission unit as pulse quantity per kWh (kVArh, m3). To reduce energies (powers), designed for electricity meters, to input end, power transformation ratio is set external meter voltage and current transformers transformation ratios generation.

    Named values calculation is accomplished only for pulse inputs included in calculating machine channel.

    Quantity of pulses metered per each input may be reset only while accumulated energies resetting.

    For pulse input configuration it is necessary to know: pulse metering mode; afterpulse length; inverting input constant (for named values); generalized transformation ratio (for named values). 4.6.10 Multirate mode configuration The meter accumulates calculating channels energies: under four tariffs; under additional tariff, in case it is impossible to define the current tariff (real time

    clock inaccuracy or rate scale is not set); under all the tariffs in total (unrated metering). The meter averages calculating machine channel powers in a set time interval and fixes

    month power maximum value: under four tariffs; under additional tariff. For multirate metering organization it is necessary to set: day rate scales list;

  • day of week season structures and season beginning dates; exceptional days (days when tariffication is different) list. 4.6.10.1 Day rate scales list (GRFzz) It is possible to set up to 15 current tariff switch time within a day period. The switch

    time rating period beginning is set with accuracy to 1 min. During one time of the day only one tariff can be active. Certain tariff is active during the set time till switch time period. In case the basic switch time is defined not from the day beginning the tariff defined for the latest time of day is active.

    The example of rate schedule is given in Table 4.3 and in Figure 4.9 Table 4.3

    Time of tariff activity beginning

    Current tariff Time of tariff activity during a day

    04:30 II 07:30 III

    I tariff 09:0011:00 13:3016:00

    09:00 I 11:00 III

    II tariff 04:0007:30 18:0020:30

    13:30 I 16:00 III 18:00 II

    III tariff 07:3009:00 11:0013:00 16:0018:00

    20:30 IV

    IV tariff 00:0004:30 20:3024:00

    Figure 4.9

    To set one tariff for the whole day its sufficient to specify any time of day. The meter allows setting of up to 36 different day rate scales (rate scale list).

    4.6.10.2 Season structure (SEASON) The season determines fixed tariffication for the time period from a day to a calendar

    year. The time of season activity is defined from the specified date of season beginning till the beginning of the next season in a calendar year. In case the season with the date of calendar year beginning is absent in the list of seasons the last set season is active from the beginning of the year. Within the time period during which the season is active the tariffication per weekday remains unchanged. Certain rate scale may be set for each weekday.

    The example of a calendar year rate schedule is given in Table 4.4. Table 4.4

    The number of day rate scale active on

    Seas

    on #

    Time of tariff activity beginning

    Monday Tuesday Wednesday Thursday Friday Saturday Sunday

    4 April, 5 5 5 3 3 17 1 2 2 October, 12 8 9 21 22 23 11 12

    00:00 12:00 24:00

    18:00 20:30 16:0013:3011:009:007:30 4:30

    II IV III I III I III II IV

  • In this example the year is divided into two seasons. Since the 1st of January till the 4th of April and since the 12th of October till the 31st of December the second season rate scales will be active, since the 5th of April till the 11th of October the first season rate scales will be active.

    The meter allows setting of up to 12 season rate scales. 4.6.10.3 Exceptional days (EXDAY) Exceptional days are days of a calendar year the tariffication of which is different from

    the season weekday tariffication. Such exceptional days are public holidays, holidays and workdays rescheduled. Any rate scale of the list prepared may be specified for each exceptional day.

    The meter allows setting of up to 32 exceptional dates. 4.6.11 Profiles configuration The meter allows forming of up to 16 independent profiles. The data accumulated in

    profiles are accessible only via digital interfaces. A profile can accumulate the energy (power) data of any calculating machine channel with the individual time interval. The profile data values are reduced to input end and registered considering the active transformation factors. For the meter switched off during a day profile data for that day is absent. For the meter switched off during an interval time that interval data is marked as absent. In case the interval is changed by the time correction or the meter is switched off in the interval segment the data is marked as incomplete. For each profile it is possible to set:

    calculating machine channel; data type energy or power; time interval in the range: 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, 60 min. The profile configured for the calculating machine channel #0 or with the interval time 0

    min is considered switched off. ATTENTION! While profile configuration logging into the meter all the previously

    accumulated profile data is reset. Any profile data storage period depends only on time interval and is defined in

    accordance with Table 4.5 Table 4.5 Time interval, minutes

    1 2 3 4 5 6 10 12 15 20 30 60

    Storage period, days

    11 22 33 44 56 67 112 134 168 224 336 512

    4.6.11.1 Profile data formation at clock time change In case the time is put forward (analogous to switching the meter off): within the interval the interval data will be marked as incomplete; within a day the old and the new intervals data will be marked as incomplete,

    the data between the intervals will be marked as absent; into another day the new day data will be formed. In case the time is put backward: within the interval the interval data will be marked as incomplete; within a day the new interval data will be marked as incomplete, all the data of

    the intervals run twice represents the sum of the first and the second runs; into another day the new day data will be formed, and the same day time will be

    stored in profiles. While automatic summer switch from 2:00 to 3:00 on the last Sunday of the switch

    month set, from 2:00 to 3:00 interval data will be marked as absent. While automatic winter time switch from 3:00 to 2:00 on the last Sunday of the switch

    month set, additional hour interval data will be formed separately. Each profile can store interval

  • data of only one (the last one) additional hour. Additional hour interval data is changed (with data creation dating), if the meter was switched on the day of winter time switch. If the meter was switched off during the whole day of time switch the previous additional hour interval data is stored in the profiles.

    4.6.12 Time correction and setting Time setting suggests setting of any time, date and day of week. It is reasonable to use

    this instruction only before putting the meter into operation in case it was taken into another time zone, after repair or long-term storage, and at clock failure resulted from switched off power lithium element failure.

    Time correction (30 s) may be accomplished fingertip only once a day (Cl. 5.2.6), or via digital interfaces (CL. 5.4.3). If the departure comprises more than 30 s. the correction should be accomplished during several days or time setting instruction should be used. The minus correction is accomplished by setting second readings to zero in case the current second value was not more than 29 s. The plus correction is accomplished by setting readings to 59 s. in case the current second value was 30 s. or more.

    At low and high temperatures the clock readings departure may comprise up to 9 s/day. It is possible to set clock rate autocorrection in the meter. At the producing plant the

    clock was calibrated at standard temperature. In case the clock readings departure takes place, it is possible to calculate and change clock rate calibration factor:

    to calculate day clock readings departure for several days to within second deciles (for slow clock with - sign, for fast clock with + sign);

    to read the meter calibration factor and chose the corresponding day clock readings departure from Table 4.6;

    to put together the chosen and the calculated day clock readings departures considering signs;

    to chose the corresponding calibration factor from Table 4.6 and log it into the meter according to the received summarized clock readings departure. Table 4.6

    Positive calibration for slow clock Negative calibration for fast clock Calibration factor

    0 Day clock readings

    departure to, s -0.19

    Calibration factor 0

    Day clock readings departure to, s

    0.19 -1 -0.19 1 0.19 -2 -0.56 2 0.56 -3 -0.94 3 0.94 -4 -1.31 4 1.31 -5 -1.69 5 1.69 -6 -2.06 6 2.06 -7 -2.44 7 2.44 -8 -2.81 8 2.81 -9 -3.19 9 3.19 -10 -3.56 10 3.56 -11 -3.94 11 3.94 -12 -4.31 12 4.31 -13 -4.69 13 4.69 -14 -5.06 14 5.06 -15 -5.44 15 5.44 -16 -5.81 16 5.81 -17 -6.19 17 6.19 -18 -6.56 18 6.56

  • -19 -6.94 19 6.94 -20 -7.31 20 7.31 -21 -7.69 21 7.69 -22 -8.06 22 8.06 -23 -8.44 23 8.44 -24 -8.81 24 8.81 -25 -9.19 25 9.19 -26 -9.56 26 9.56 -27 -9.94 27 9.94 -28 -10.31 28 10.31 -29 -10.69 29 10.69 -30 -11.06 30 11.06 -31 -11.44 31 11.44

    -11.81 11.81

    4.6.13 Access passwords (PSWzz, CRWzz) Programming and parameter reading access limit is realized with passwords. The

    password, with which the access to programming was accomplished, is fixed in the programming log. The meter supports up to 4 passwords of up to 8 symbols length. Administrator (password #1) can change any password, the others only their own ones. Empty password (with no symbols) is considered inactive.

    Only the administrator can change the configuration of the accessible for Users (passwords #2, #3, #4) programmable and readable parameter groups and configuration of the parameters output in the mode of reading data with no password.

    ATTENTION! At triple incorrect password introduction the access to the meter is blocked till the end of a day.

    4.6.14 Accumulated calculating machine channel data reset After calculating machine channels programming, it is recommended to set to zero the

    accumulated data on: energy with progressive total of all the channels per tariff; energy accumulated during all the months of all the channels per tariff; energy accumulated during all the days of all the channels per tariff; maximum average powers for all the months of all the channels per tariff. Accumulated data reset is accomplished in manual mode (in case it is enabled). To set calculating machine channel data to zero it is necessary to: enable reset mode (to log the instruction via interface); place the meter in the programming mode press the button Access (the text

    Access and countdown is displayed on LCD); press the button SCROLL (the text CLEAR and countdown is displayed on

    LCD); press the button Access not later than in 3 seconds. The date and time of setting to zero are fixed in the corresponding register. Note each profile data is reset individually (Cl. 4.6.11). 4.6.15 Access password, record locking, response delay reset The meter allows changing access passwords to prohibit unauthorized programming and

    reading. The meter allows prohibiting programming via any digital interface to reduce the

    possibility of unauthorized programming.

  • The meter allows changing the time of delay via interface from 1 to 255 ms. The parameter serves for reducing the time of exchange and can be collated depending on the apparatus connected and PC software support. For instance, some EIA485 interface adaptors with automatic transmission direction switch require the response delay of more than 70 ms.

    In critical situations when the access password is lost, the programming for all interfaces is prohibited and response delay time is less than accepted, setting of the following parameters is supported by default:

    access password #1 777777; other passwords not set; programming via all the interfaces is enabled; response delay 200 ms. For value default setting it is necessary to: place the meter in the programming mode press the button Access (the text

    Access and countdown is displayed o LCD); press the button SCROLL (the text CLEAR and countdown is displayed on

    LCD); press the button Access not later than in 3 seconds. The date and time of value default setting is fixed in the corresponding register. 5 OPERATION PROCEDURE The meter reading is possible both in manual and automated modes. In the automated mode the complete information on energy consumption may be

    obtained with PC via interfaces. Data exchange via interfaces is given in Cl. 5.4. In manual mode the data is displayed on LCD in the window of seven decimals with

    decimal point and character multipliers width (k=103, M=106, G=109). The full list of output formats of measured, calculated and accumulated parameters is

    given in Table 5.1 Table 5.1

    on LCD via interfaces Names of indicated parameters

    Displayed value of a quantity

    Units of measurement

    Quantity of positions on the right of the point

    Units of measurement

    Quantity of positions on the right of the point

    Voltage to 10 to 100 to 1000

    V, kV, MV 4 3 2

    V 3

    Current to 10 to 100 to 1000

    , k, 4 3 2

    4

    Power to 10 to 100 to 1000

    W, kW, MW, (VAr, kVAr, MVAr), (VA, kVA, MVA)

    4 3 2

    kW, (kVAr), (kVA)

    6

    Power factors 3 3 Angles degree 1 degree 1 Network frequency

    Hz 2 Hz 2

    Calculating machine channel energy progressive total (per

    see Cl. 5.1

    KWh, (kVArh)

    5

  • month, day) Average power maximums

    to 10 to 100 to 1000

    W, kW, MW, (VAr, kVAr, MVAr)

    4 3 2

    kW, (kVAr)

    6

    Predictable calculating machine channel power

    to 10 to 100 to 1000

    W, kW, MW, (VAr, kVAr, MVAr)

    4 3 2

    kW, (kVAr)

    6

    Current averaging interval calculating machine channel energies

    not indicated kWh, (kVArh)

    5

    Profile interval values

    not indicated kW, kWh, (kVAr,

    (kVArh)

    5

    5.1 Calculating machine channel data display on LCD

    5.1.1 Register values display

    Calculating machine channel energies are stored in registers of 19 decimal width with 10 mWh resolution (i.e. 5 decimals after the point for units of kWh measurement). Maximum accepted value of accumulated calculating machine channel energy comprises 401012 kWh, that cannot be exceeded even in case of meter operation at maximum load, with maximum accepted measuring transformers ratios during the whole service life. To meet GOST R 52320-2005 requirements to register for different modifications meters, different variants of register display on LCD are chosen (Table 3.3). As the meter accomplishes input end metering, the register display window automatically undents by the value proportional to power transformation ratio (Rp=RvRc). Register value on the left of the window is a number of window width overflows. Register value on the right of the window is a fraction of display least significant bit unit. The example of 57.7 V 5 A transformer connection meter LCD display window is given in Table 5.2 Table 5.2 Register and display window position

    Display window with character multiplier

    Value of input end power factor (Rp=RvRc)

    43210987654321.12345 54321.123 kWh up to 10 43210987654321.12345 654321.12 kWh 10100 43210987654321.12345 7654321.1 kWh 1001000 43210987654321.12345 87654.321 MWh 100010000 43210987654321.12345 987654.32 MWh 10000100000 43210987654321.12345 0987654.3 MWh 1000001000000 43210987654321.12345 10987.654 GWh 100000010000000 43210987654321.12345 210987.65 GWh 10000000100000000 5.1.2 Calculating machine channel identification While calculating machine channel data indication on LCD, on the left of value display window indicated channel number sign is displayed ( =1, = 2, = 3, = 4, = 5, = 6). Calculating machine channel mnemonic is also displayed:

    | A imported active energy (Ai); | A exported active energy (Ae);

  • P | - imported reactive energy (R2+R3); P | - exported reactive energy (R1+R4); | energy loss for imported active energy (Li); | energy loss for exported active energy (Le). In case calculating machine channel contains only unit-counting inputs energy mnemonics

    is not displayed. 5.1.3 Tariff identification Calculating machine channels data (energy) is accumulated per tariff in accordance with set

    tariffication parameters and inbuilt clock time. Tariff designation: tariff 0 total energy; tariff 1 energy accumulated during the first tariff operation; tariff 2 energy accumulated during the second tariff operation; tariff 3 energy accumulated during the third tariff operation; tariff 4 energy accumulated during the forth tariff operation; tariff 5 energy accumulated after clock failure or at incorrect (not set)

    tariffication parameters; tariff 6 energy accumulated in accordance with specified criterion; tariff 7 - energy accumulated in accordance with specified criterion. Accumulated calculating machine channel data value tariff 0is equal to the sum of

    accumulated data values for 5 tariffs (from the first to the fifth). 5.2 Data scrolling in manual mode Data scrolling is accomplished with the SHOT and SCROLL buttons. Two types of pressing buttons are distinguished:

    short a button is kept pressed for less than 1s. long a button is kept pressed for more than 1s.

    Pressing the SHOT button for long time switches in a successive order the display of the following groups of parameters:

    TOTAL calculating machine channels data accumulated with progressive total;

    MONTH - calculating machine channels data accumulated for a month; DAY - calculating machine channels data accumulated for a day; AVERAGE POWER MAXIMUMS; FORECASTING POWER; SERVICE INFORMATION; QUALITY PARAMETERS; PULSE INPUTS.

    LCD indication switch structure by type (SHOT or SCROLL) and manner of

    pressing (short or long) buttons are given in Annex G. 5.2.1 Group TOTAL Values of calculating machine channels data accumulated with progressive total per tariff

    and in total are displayed. The data displayed on LCD: calculating machine energy value with progressive total; number label and constituents of calculating machine channel; displayed tariff number; TOTAL indicator; phase voltage indicators.

  • Figure 5.1

    Total (tariff 0) active (A) imported (|) energy value (0012.345 kWh) of the (whole) first calculating machine channel () progressive total is given in Figure 5.1.

    Additionally the phase voltage presence is indicated (Phase ABC). The button Scroll short-time pressing gradually switches calculating machine channel

    consumed energy indication per tariff (8 tariffs in total). The button Scroll long-time pressing gradually switches different calculating machine

    channels consumed energy indication (6 channels in total). 5.2.2 Group MONTH Calculating machine channels data accumulated with progressive total for the month in

    total and per tariff are displayed. On LCD the following data is displayed: energy value of calculating machine channel progressive total for the month in the end of the month; label number and calculating machine channel constituents; month and year of fixation; displayed tariff number; marker MONTH; phase voltage presence markers.

    Figure 5.2

    In Figure 5.2 active (A) exported (|) energy value (0000.789 kWh) of the second calculating machine channel () progressive total fixed in the end of March 2006 (0306) by the first tariff (tariff 1) is given. If the date value is equal to 0000, the months metering data is absent.

    TARIFF PHASE

    TOTAL

    kWh

    TARIFF MONTH

    PHASE ABC

    kWh

  • View of calculating machine channel progressive total readings in the end of the previous month is accomplished by the short-time pressing the button SHOT (only 13 months).

    The button Scroll short-time pressing gradually switches calculating machine channel consumed energy end-month indication with progressive total per tariff (8 tariffs in total).

    The button Scroll long-time pressing gradually switches different calculating machine channels consumed energy end-month indication with progressive total (6 channels in total).

    5.2.3 Group DAY Calculating machine channels end-day data accumulated with progressive total in total

    and per tariff are displayed. On LCD the following data is displayed: energy end-day value of calculating machine channel progressive total; label number and calculating machine channel constituents; date, month and year of fixation; displayed tariff number; marker DAY; phase voltage presence markers.

    Figure 5.3

    In Figure 5.3 reactive (R) imported (|) energy value (0000.047 kVArh) of the fourth calculating machine channel () progressive total fixed in the end of March, 17 2006 (17:0306) by the second tariff (tariff 2) is given. If the date value is equal to 00:0000, the days metering data is absent.

    Additionally the phase voltage presence is indicated (Phase ABC). Index mark flashing informs of phase voltage value outside set access.

    View of calculating machine channel progressive total readings in the end of the previous day is accomplished by the short-time pressing the button SHOT (only 46 days).

    The button Scroll short-time pressing gradually switches calculating machine channel consumed energy end-day indication with progressive total per tariff (8 tariffs in total).

    The button Scroll long-time pressing gradually switches different calculating machine channels consumed energy end-day indication with progressive total (6 channels in total). 5.2.4 Group AVERAGE POWER MAXIMUMS

    Average power maximums (averaged in a set interval) of calculating machine channels registered per tariff during a calendar month are displayed.

    On LCD the following data is displayed: average power maximum of calculating machine channel in a set interval; label number and calculating machine channel constituents; date and time of the month maximum fixation; displayed tariff number;

    TARIFF PHASE

    DAY

    kVARh

    R

  • marker PREV.

    Figure 5.4

    Figure 5.5

    In figures reactive (R) exported (|) power maximum (73.020 kVArh) of the third calculating machine channel () fixed on March, 20 2006 (20:0306) (Figure 5.4) by the third tariff (tariff 3) with the beginning of averaging time at 12.10 oclock (Figure 5.5) is given. Date and time are displayed alternatively with 2 s interval. If the date day value is equal to zero, the given tariff month maximum was not fixed.

    View of calculating machine channel maximum power readings for the previous month is accomplished by the short-time pressing the button SHOT (only 13 months).

    The button Scroll short-time pressing gradually switches calculating machine channel power maximums indication per tariff (5 tariffs in total).

    The button Scroll long-time pressing gradually switches different calculating machine channels power maximums indication (6 channels in total).

    5.2.5 Group FORECASTING POWER On LCD the following data is displayed:

    forecasting power of calculating machine channel since current averaging period till current time; label number and calculating machine channel constituents; time before the end of the averaging period current tariff; marker set power limit exceedence; marker pulse output is active in case of power limit exceedence

    Figure 5.6

    In the figure forecasting active (A) exported (|) power value (1.7452W) of the first calculating machine channel () for 5 min 17 s (05:17) before the time of averaging expiration,

    TARIFF

    VAr

    RPREV

    TARIFF

    VAr

    PREV

    R

    W

    TARIFF

  • set power limit exceedence with control signal generation to pulse output are given, the fourth tariff is active (tariff 4). Every minute (value of seconds = 0) the calibration is carried out and in case of power limit exccedence marker is displayed. The marker indicates control signal appearance at the pulse output. The button Scroll short-time pressing gradually switches different calculating machine channels forecasting power values indication (6 channels in total). 5.2.6 Group SERVICE INFORMATION

    The button Shot short-time pressing gradually switches indication in the group (3 subgroups in total).

    1) Subgroup RELEVANT INFORMATION On LCD the data given in Figure 5.7 is displayed: current time 09:3052 hours, minutes, seconds; current date 29-03-06 real time clock day, month, year; weekday Wed - real time clock; current tariff tariff 2; current direction IV quadrant; indexes A, B, C phase voltage presence; marker S summer time; marker c clock rate correction 30 s is allowed; marker pulse output is active in accordance with current tariff.

    Figure 5.7

    Phase index absence informs of voltage absence in a phase (voltage is less than 5% Unom). Phase index flashing informs of phase voltage outside the set access. For each phase the quadrant of apparent power phasor position is defined. Current direction indicates obtained quadrants for all phases:

    | AP | - quadrant I; | AP | - quadrant II; | AP | - quadrant III; | AP | - quadrant IV. The meter allows manual clock rate correction once a day. The button SCROLL long-

    time pressing in case of c marker presence leads to not exceeding 30 s value clock rate correction, with the correction allowance marker disappearing. The correction allowance marker will appear again at the beginning of another day.

    If the button SCROLL will be pressed for up to 30 s, second values will be set to zero (time s is corrected with the sign -). If the button SCROLL will be pressed for more than 30 s, second value will be equal to 59 (the time s is corrected with the sign +).

    It is necessary to consider the correction is carried out approximately in a second after the button pressing.

    2) Subgroup INTERFACE PARAMETERS On LCD the data given in Figure 8 is displayed: 2 interface number;

    TARIFF

    PHASE ABC

    Wed(C) Wed(C) Wed

    c S

    AP

  • 01:0005 active protocol (01=GOST IEC 61107-2001), initial (00=300 baud) and operating (05=9600 baud) exchange speed via interface;

    10s interface activity time; 200 interface response delay time, ms.

    Figure 8

    The initial exchange speed may be set only manually. To change the initial exchange speed it is necessary to go into the mode of initial speed choice (flashing of value) by the button ACCESS short-time pressing. By the button SCROLL short-time pressing choose the required speed value:

    0 = 300 baud; 1 = 600 baud; 2 = 1200 baud; 3 = 2400 baud; 4 = 4800 baud; 5 = 9600 baud; 6 = 19200 baud; 7 = 38400 baud; 8 = 57600 baud; 9 = 115200 baud. By the button ACCESS short-time pressing go out of the initial speed choice mode. The button SCROLL short-time pressing gradually switches indication of different

    interfaces parameters (2 interfaces in total). 3) Subgroup EXTERNAL TRANSFORMERS AND INTERVAL The button SCROLL short-time pressing gradually switches indication of parameters: FU voltage transformer transformation ratio; FI current transformer transformation ratio; :03 meter model (5A, 220V) P1.2 t30M meter program version 1.2 and averaging time duration 30 min. 5.2.7 Group NETWORK QUALITY PARAMETERS The button SHOT short-time pressing gradually switches indication in the group (11

    subgroups in total). Inside a subgroup the button SCROLL short-time pressing switches indication of parameter value for different phases (indexes A, B, C) and total three phase network value (index ABC).

    1) Subgroup Active Voltage Input end phase voltage MRS values are displayed in V (kV, MV). 2) Subgroup Active Current Input end phase current MRS values are displayed in A (kA, MA). 3) Subgroup Active power Active input end phase and three-phase network powers are displayed in W (kW, MW). 4) Subgroup Reactive Power Reactive input end phase and three-phase network powers are displayed in VAr (kVAr,

    MVAr).

    s

  • 5) Subgroup Apparent Power Apparent input end phase and three-phase network powers are displayed in VA (kVA,

    MVA). 6) Subgroup Power Loss Active input end phase and three-phase network power losses are displayed in W (kW,

    MW). 7) Subgroup Angle between current and voltage vectors Angles between phase current and voltage are displayed in the range 180 Degrees. 8) Subgroup Active Power Factor Active phase and three-phase network power factors are displayed, marker COS. 9) Subgroup Reactive Power Factor Reactive phase and three-phase network power factors are displayed, marker Sin. 10) Subgroup Network Frequency Three phase network frequency is displayed in Hz. 11) Subgroup Angle between voltage vectors Angles between voltage vectors of different three-phase network phases in the range

    180 Degrees. Negative angle values display incorrect phase sequence. Markers for phase angles indexes AB, BC, AC.

    5.2.8 Group PULSE INPUTS On LCD the data given in Figure 5.9 is displayed: displayed pulse input number; pulse quantity metered via pulse input; marker TOTAL; marker pulse input closed condition.

    Figure 5.9

    Pulse quantity (5873) metered via pulse input 3 is given in the figure, the input is closed. The button SCROLL short-time pressing gradually switches indication of different pulse inputs (4 inputs in total).

    5.3 Information Messages During meter operation on LCD mnemonic and text messages about meter mode

    conditions are displayed (irrespective of displayed data). 5.3.1 Mnemonic Messages Such messages appearance doesnt disturb the displayed data. 1) Marker ERR The basic meter power is absent the voltage in all phases is not sufficient for power unit

    PU operation, the meter operates with back-up power. In this mode data read-out from LCD or via interfaces is possible.

    2) Marker

    Session of communication via interfaces.

    TOTAL

  • 3) Tariffication is absent, real time clock failure. Disappears after new time value

    registration via interfaces. 4) Marker Clock power lithium element replacement is required. 5) Marker Power limit is exceeded. 5.3.2 Text Messages

    The meter displays on LCD text messages that may be divided into several groups.

    1) Meter Condition Messages. ACCES appears after pressing the button ACCESS and informs about

    allowance of parameter registration via interfaces programming mode. Disappears on countdown expiration, by the button ACCESS repeated pressing or parameters registration via interfaces.

    CLEAr appears after the button SCROLL short-time pressing only in case the text ACCES is displayed and informs of sanitization allowance Cls 4.5.14, 4.5.15. disappears on countdown expiration or by sanitizing.

    OPtO appears after optical head connection out of communication session via additional interface (COM2) and informs about possibility of exchange via optical port (OP). Disappears on countdown expiration or while exchange via OP. For OP reclosing it is necessary to disconnect and reconnect OP to the meter. In case OP is active, exchange via additional interface (COM 2) is impossible.

    2) Messages about interface exchange errors. This message group is indicated during two seconds. Messages with numbers more than

    10 are output via interfaces as well. Err 03 Wrong password means that during programming the password not

    matching the back-end passwords was entered. Enter a valid password (for the second or third attempts). The message is not output via interfaces.

    Err 04 Interface exchange failure means that during interface exchange the failure took place or meter interface part or connected device is out-