1 CEPEL Enhancement of Transmission Capability by Luiz A.S. Pilotto Research & Development Director Palo Alto, October 11, 2001 NSF/EPRI Workshop Urgent Opportunities for Transmission System Enhancement Enhancement of Transmission Capability by Luiz A.S. Pilotto Research & Development Director Palo Alto, October 11, 2001 NSF/EPRI Workshop Urgent Opportunities for Transmission System Enhancement CEPEL

CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

Embed Size (px)

Citation preview

Page 1: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

1

CEPEL

Enhancement of Transmission Capability

by

Luiz A.S. PilottoResearch & Development Director

Palo Alto, October 11, 2001

NSF/EPRI WorkshopUrgent Opportunities for Transmission System Enhancement

Enhancement of Transmission Capability

by

Luiz A.S. PilottoResearch & Development Director

Palo Alto, October 11, 2001

NSF/EPRI WorkshopUrgent Opportunities for Transmission System Enhancement

CEPEL

Page 2: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

2

CEPEL

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

Page 3: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

3

CEPEL

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

BASIC CONCEPTSBASIC CONCEPTS

•• Expanded Bundle Geometry Optimizes the Electric Field Expanded Bundle Geometry Optimizes the Electric Field at the Surface of All Sub-Conductors at the Surface of All Sub-Conductors

•• Result: an Expressive Reduction of the Positive Sequence Result: an Expressive Reduction of the Positive Sequence Impedance of the Transmission Line Impedance of the Transmission Line

Electric Field ProfileElectric Field Profile0,6

0,7 0,8

0,7 0,8

0,9 0,9

0,8 0,7

0,8 0,7

0,6

0,9

0,9 0,9

0,90,7

0,7 0,9

0,8 0,8

0,9 0,7

0,7

1,0

1,0 1,0

1,01,0

1,01,0

1,0 1,0

1,01,0

1,0

Conventional BundleConventional Bundle

Expanded Bundle Expanded Bundle (EXB) (EXB)

HSIL - EXBHSIL - EXB

Page 4: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

4

CEPEL

BASIC CONCEPTSBASIC CONCEPTS

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

Electric Field CalculationElectric Field Calculation

Conventional BundleConventional Bundle

Expanded Bundle (EXB)Expanded Bundle (EXB)

HSIL - EXBHSIL - EXB

Page 5: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

5

CEPEL

Surge Impedance LoadingSurge Impedance Loading

BASIC CONCEPTSBASIC CONCEPTS

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

VV 22

ZZ11SIL =SIL =

Voltage Level (kV)

Conventional Line(MW)

HSIL Line(MW)

69 9 - 12 10 - 40138 40 - 50 50 - 120230 120 - 130 130 - 440500 900 - 1020 950 - 2000

Source: CHESFSource: CHESF

Page 6: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

6

CEPEL

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

CHARACTERISTICS OF AN HSIL LINECHARACTERISTICS OF AN HSIL LINE

Enhanced Power Transfer Capacity Enhanced Power Transfer Capacity

Improved Power Systems Transient Stability Limits Improved Power Systems Transient Stability Limits

Reduced Environmental Impact, for the Same Power Reduced Environmental Impact, for the Same Power Transmission Level Transmission Level

Maximum Utilization of Existing Right-of-Ways Maximum Utilization of Existing Right-of-Ways

Improved Voltage Regulation of Highly Stressed Improved Voltage Regulation of Highly Stressed Transmission Lines Transmission Lines

Page 7: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

7

CEPEL

TECHNOLOGY OVERVIEWTECHNOLOGY OVERVIEW

GROUNDINGGROUNDINGTOWERS &TOWERS &

FOUNDATIONSFOUNDATIONS

ELECTRICALELECTRICALEQUIPMENTEQUIPMENT

ELECTRICALELECTRICALDESIGNDESIGN

ENVIRONMENTALENVIRONMENTALISSUESISSUES

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

Page 8: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

8

CEPEL

ELECTRICAL DESIGNELECTRICAL DESIGN

DELTADELTA

Risk of FailureRisk of Failure

PCORPCOR

Corona LossesCorona Losses

TENCRITENCRI

Critical FlashoverCritical FlashoverVoltageVoltage

CODIN IVCODIN IV

Lightning SurgesLightning Surges

SELECSELEC

Economic AC/DCEconomic AC/DCConductor SelectionConductor Selection

TRICAMPTRICAMP

3D Electric and3D Electric andMagnetic FieldMagnetic Field

OTLINOTLIN

ConfigurationConfigurationOptimizationOptimization

SIGASIGA

Magnetic Field,Magnetic Field,Audible Noise,Audible Noise,

Radio InterferenceRadio Interference

ZYCORZYCOR

TL Parameters andTL Parameters andCurrent DistributionCurrent Distribution

AMPACIDADEAMPACIDADE

ConductorConductorTemperature AnalysisTemperature Analysis

RECAP LTRECAP LT

Technical Solutions forTechnical Solutions forTL UpgradingTL Upgrading

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

Page 9: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

9

CEPEL

TOWERS AND FOUNDATIONSTOWERS AND FOUNDATIONS

FLECHAFLECHA

Conductor SagConductor Sag

TRAPIIITRAPIII

Compact TowerCompact TowerDesignDesign

OTIMASOTIMAS

OptimizationOptimization Mast Mast

TRAPVVVTRAPVVV

Non-Conventional TowerNon-Conventional TowerDesignDesign

AQUISAQUIS

Mechanical DataMechanical DataAcquisition & AnalysisAcquisition & Analysis

TORRESTORRES

Integrated Design ofIntegrated Design ofTowers and FoundationsTowers and Foundations

GEOMEFGEOMEF

Geologic AnalysisGeologic Analysis

PLOTTORPLOTTOR

Towers and FoundationsTowers and FoundationsSketch DesignSketch Design

AQUIEEEAQUIEEE

Vibration DataVibration DataAcquisition & AnalysisAcquisition & Analysis

TORTRETORTRE

Lattice TowerLattice TowerDesignDesign

GRELHASGRELHAS

Metallic GrillageMetallic GrillageFoundationFoundation

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

Page 10: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

10

CEPEL

DEVELOPED TOOLS FOR ANALYSIS AND DESIGNDEVELOPED TOOLS FOR ANALYSIS AND DESIGN

ELECTRIC FIELD

0

1

2

3

4

5

6

7

0 5 10 15 20 25 30 35 40

distance to the center of TL (m)

elec

tric

fiel

d (k

V/m

)

CONVENTIONAL TLHSIL TLcriteria at right of way

VΦΦ: 500 kVprofile height: 1 m

right of way

MAGNETIC FIELD

0

10

20

30

40

50

60

70

80

0 5 10 15 20 25 30 35 40

distance to the center of TL (m)

mag

netic

fiel

d (m

G)

CONVENTIONAL TLHSIL TL

I/phase: 1155 (A)profile height: 1 mcriteria at right of way: 1000 mG

right of way

RADIO INTERFERENCEDRY WEATHER

0

5

10

15

20

25

30

35

40

45

0 5 10 15 20 25 30 35 40

distance to the center of TL (m)

radi

o in

terf

eren

ce (d

B/1µV

/m)

CONVENTIONAL TLHSIL TLcriteria at right of way

right of way

VΦΦ: 500 kVfrequency: 0.5 MHzresistivity of the soil: 500 Ωmprofile height: 1m

AUDIBLE NOISE15 MINUTES AFTER RAIN

0

10

20

30

40

50

60

70

80

0 5 10 15 20 25 30 35 40

distance to the center of TL (m)

audi

ble

nois

e dB

(A)

CONVENTIONAL TLHSIL TLcriteria at right of way

VΦΦ: 500 kVfrequency: 60 Hzresistivity of the soil: 1000 Ωmprofile height: 1 m

right of way

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

Page 11: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

11

CEPEL

LABORATORY STRUCTURELABORATORY STRUCTURE

230 kV HSIL CHESF Line Prototype 230 kV HSIL CHESF Line Prototype at CEPEL’s High Voltage Laboratoryat CEPEL’s High Voltage Laboratory

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

Page 12: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

12

CEPEL

LABORATORY STRUCTURELABORATORY STRUCTURE

HSIL (EXB) Banabuiú-Fortaleza - CHESF - Line: 2 x 230 kVHSIL (EXB) Banabuiú-Fortaleza - CHESF - Line: 2 x 230 kV

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

Page 13: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

13

CEPEL

LABORATORY STRUCTURELABORATORY STRUCTURE

CHESF 500 kV CHESF 500 kV expanded bundleexpanded bundletesting at CEPEL’stesting at CEPEL’sHigh Voltage LaboratoryHigh Voltage Laboratory

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

Page 14: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

14

CEPEL

Already Installed AssetsAlready Installed Assets230 kV CHESF HSIL Line – 1.6 km Full Scale Prototype: 230 kV CHESF HSIL Line – 1.6 km Full Scale Prototype: 199419942 x 230 kV Paulo 2 x 230 kV Paulo AfonsoAfonso – – FortalezaFortaleza HSIL-EXB Line – 640 km: HSIL-EXB Line – 640 km: 19991999500 kV P.500 kV P.DutraDutra – – FortalezaFortaleza HSIL-EXB Line- 740 km: HSIL-EXB Line- 740 km: 20002000

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

Page 15: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

15

CEPEL

HSIL Technology is Mature—HSIL Technology is Mature—

Already Adopted by the Already Adopted by the Coordinating Committee for the Brazilian System Coordinating Committee for the Brazilian System

Expansion Planning (CCPE)Expansion Planning (CCPE)

Currently in Operation: Currently in Operation: 740 km @ 500 kV740 km @ 500 kV

Avoided Investment Costs may Reach US$ 1.1 Billion in the Next 10 Years

Avoided Investment Costs may Reach US$ 1.1 Billion in the Next 10 Years

640 km @ 230 kV - double circuit640 km @ 230 kV - double circuitExperimental 230 kV and 500 kV Lines Report Experimental 230 kV and 500 kV Lines Report NO Electrical or Mechanical Incidents for NO Electrical or Mechanical Incidents for More than 4 YearsMore than 4 Years

CONCLUSIONSCONCLUSIONS

High Surge Impedance Loading Line - HSILHigh Surge Impedance Loading Line - HSIL

Page 16: CEPEL Enhancement of Transmission Capability · 3 CEPEL High Surge Impedance Loading Line - HSIL BASIC CONCEPTS • Expanded Bundle Geometry Optimizes the Electric Field at the Surface

16

CEPEL

Enhancement of Transmission Capability

Palo Alto, October 11, 2001

NSF/EPRI WorkshopUrgent Opportunities for Transmission System Enhancement

Enhancement of Transmission Capability

Palo Alto, October 11, 2001

NSF/EPRI WorkshopUrgent Opportunities for Transmission System Enhancement