    PARAMETER LIST

    Compact Genset Controller, CGC 400 Alarm list Parameter list

    Document no.: 4189340789ASW version:

  • 1. General information1.1. Warnings, legal information and safety..................................................................................................4

    1.1.1. Warnings and notes ......................................................................................................................41.1.2. Legal information and disclaimer ..................................................................................................41.1.3. Safety issues ................................................................................................................................41.1.4. Electrostatic discharge awareness ...............................................................................................41.1.5. Factory settings ............................................................................................................................5

    1.2. About the Parameter List........................................................................................................................51.2.1. General purpose of the Parameter List..........................................................................................51.2.2. Intended users...............................................................................................................................51.2.3. Contents and overall structure ......................................................................................................5

    2. Alarm list2.1. General information about the alarm list................................................................................................6

    2.1.1. Alarm list features and options .....................................................................................................62.2. Protection parameters............................................................................................................................8

    2.2.1. Reverse power and overcurrent protection....................................................................................82.2.2. Voltage protections......................................................................................................................122.2.3. Frequency protections.................................................................................................................142.2.4. Busbar voltage protections..........................................................................................................172.2.5. Busbar frequency protections......................................................................................................192.2.6. Overload protections....................................................................................................................212.2.7. Undervoltage and reactive power low..........................................................................................23

    2.3. Breaker control parameters..................................................................................................................252.3.1. Breaker alarms............................................................................................................................25

    2.4. Input/output parameters, binary input setup.........................................................................................282.4.1. Digital input 10-15 and 56-57 setup.............................................................................................282.4.2. Digital input 6-8 setup..................................................................................................................292.4.3. Emergency stop...........................................................................................................................302.4.4. M-Logic alarm 1-5 setup .............................................................................................................31

    2.5. Analogue input setup............................................................................................................................322.5.1. Multi-input no. 6...........................................................................................................................322.5.2. Multi-input no. 7 ..........................................................................................................................372.5.3. Multi-input no. 8...........................................................................................................................422.5.4. Speed and running feedback setup.............................................................................................472.5.5. Differential measurement.............................................................................................................502.5.6. Aux. supply setup........................................................................................................................532.5.7. Multi-input no. 58.........................................................................................................................542.5.8. Multi-input no. 59.........................................................................................................................59

    2.6. System parameters, general setup......................................................................................................642.6.1. Engine heater failure....................................................................................................................642.6.2. Max. ventilation............................................................................................................................652.6.3. Switchboard error - Block and Stop.............................................................................................662.6.4. Switchboard error - Not in auto....................................................................................................672.6.5. Avg U BB.....................................................................................................................................68

    2.7. System parameters, communication....................................................................................................692.7.1. External communication error......................................................................................................692.7.2. Engine interface communication alarms......................................................................................70

    3. Parameter list3.1. General information about the parameter list.......................................................................................74

    3.1.1. Parameter list settings.................................................................................................................743.2. Control parameter, regulation...............................................................................................................75

    3.2.1. Regulation....................................................................................................................................753.3. Control parameters, output setup.........................................................................................................76

    3.3.1. Digital output setup......................................................................................................................763.4. System parameters..............................................................................................................................773.5. System parameters, general setup......................................................................................................78

    CGC 400 parameter list 4189340789 UK

    DEIF A/S Page 2 of 98

  • 3.5.1. General setup..............................................................................................................................783.5.2. Counters and timers....................................................................................................................813.5.3. Alarm horn...................................................................................................................................823.5.4. Run coil setup..............................................................................................................................823.5.5. Running, start and stop................................................................................................................833.5.6. Breaker control............................................................................................................................853.5.7. Idle start.......................................................................................................................................853.5.8. Engine heater..............................................................................................................................863.5.9. Cooling ventilation.......................................................................................................................863.5.10. Summer/winter time...................................................................................................................863.5.11. Fuel transfer pump logic............................................................................................................873.5.12. Alarm jump.................................................................................................................................873.5.13. Command timers.......................................................................................................................88

    3.6. System parameters, mains setup.........................................................................................................893.6.1. Test..............................................................................................................................................893.6.2. Mains failure................................................................................................................................90

    3.7. System parameters, external communication......................................................................................913.7.1. External communication..............................................................................................................91

    3.8. System parameters, engine interface communication.........................................................................923.8.1. Engine interface communication..................................................................................................92

    3.9. System parameters, setup menu.........................................................................................................933.9.1. Password config. ........................................................................................................................933.9.2. AC config.....................................................................................................................................933.9.3. Display control ............................................................................................................................93

    3.10. System parameters, RMI inputs.........................................................................................................943.10.1. RMI 6.........................................................................................................................................943.10.2. RMI 7.........................................................................................................................................953.10.3. RMI 8.........................................................................................................................................953.10.4. RMI 58.......................................................................................................................................963.10.5. RMI 59.......................................................................................................................................963.10.6. Multi-input selections.................................................................................................................973.10.7. Analogue unit input scaling........................................................................................................98

    CGC 400 parameter list 4189340789 UK

    DEIF A/S Page 3 of 98

  • 1. General information1.1 Warnings, legal information and safety1.1.1 Warnings and notesThroughout this document, a number of warnings and notes with helpful user information will be presented.To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-al text.

    Warnings

    Warnings indicate a potentially dangerous situation, which could result in death, personal in-jury or damaged equipment, if certain guidelines are not followed.

    Notes

    Notes provide general information, which will be helpful for the reader to bear in mind.

    1.1.2 Legal information and disclaimerDEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about howto install or operate the engine/generator controlled by the unit, the company responsible for the installation orthe operation of the set must be contacted.

    The unit is not to be opened by unauthorised personnel. If opened anyway, the warranty will belost.

    DisclaimerDEIF A/S reserves the right to change any of the contents of this document without prior notice.

    1.1.3 Safety issuesInstalling and operating the unit may imply work with dangerous currents and voltages. Therefore, the instal-lation should only be carried out by authorised personnel who understand the risks involved in working withlive electrical equipment.

    Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-puts as this could lead to injury or death.

    DEIF do not recommend to use the USB as the primary power supply for the unit.

    1.1.4 Electrostatic discharge awarenessSufficient care must be taken to protect the terminal against static discharges during the installation. Once theunit is installed and connected, these precautions are no longer necessary.

    CGC 400 parameter list 4189340789 UK General information

    DEIF A/S Page 4 of 98

  • 1.1.5 Factory settingsThe unit is delivered from factory with certain factory settings. These are based on average values and arenot necessarily the correct settings for matching the engine/generator set in question. Precautions must betaken to check the settings before running the engine/generator set.

    1.2 About the Parameter List1.2.1 General purpose of the Parameter ListThis document is a complete parameter list including all parameters, which means that some of the optionparameters included may not be accessible in the system in question.

    The document includes a complete standard alarm list and a complete standard parameter list for setup.Therefore, this document is to be used for reference, when information about specific alarms and parametersis needed.

    Please make sure to read this document before starting to work with the unit and the genset tobe controlled. Failure to do this could result in human injury or damage to the equipment.

    1.2.2 Intended usersThis Parameter List is mainly intended for the person responsible for the unit parameter setup. In most cases,this would be a panel builder designer. Naturally, other users might also find useful information here.

    1.2.3 Contents and overall structureThis document is divided into chapters, and in order to make the structure simple and easy to use, eachchapter will begin from the top of a new page.

    CGC 400 parameter list 4189340789 UK General information

    DEIF A/S Page 5 of 98

  • 2. Alarm list2.1 General information about the alarm list2.1.1 Alarm list features and options

    In the following, these abbreviations are used:G: GeneratorGB: Generator breakerMB: Mains breakerN/A: Not available

    This chapter includes a complete alarm list, including all possible options. Therefore, this chapter is to beused for reference when specific information about the individual parameters is needed for the unit setup.

    The table consists of the following possible adjustments:

    Set point: The alarm set point is adjusted in the set point menu. The setting is a percentage ofthe nominal values.

    Delay: The timer setting is the time that must expire from the alarm level is reached until thealarm occurs.

    Relay output A: A relay can be activated by output A.

    Relay output B: A relay can be activated by output B.

    Enable: The alarm can be activated or deactivated. ON means always activated, RUN meansthat the alarm has run status. This means it is activated when the running signal ispresent.

    Fail class: When the alarm occurs the unit will react depending on the selected fail class.

    Fail classes are:

    Fail class DG (diesel generator) Mains unitF1 Block BlockF2 Warning WarningF3 Trip GB Trip TBF4 Trip + Stop Trip MBF5 Shutdown N/AF6 Trip MB N/AF7 Safety stop N/AF8 Trip MB/GB N/A

    Small differences due to the character of the parameters may exist between the individual ta-bles.

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 6 of 98

  • It is also possible to configure the param-eters by using the PC utility software. Itwill be possible to make the same config-urations as described above.

    By using the PC utility software, extrafunctionality is available. For all the pro-tections it is possible to make an auto-matic acknowledgement of the alarm.

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 7 of 98

  • 2.2 Protection parameters2.2.1 Reverse power and overcurrent protection

    No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    1000 Reverse power 11001 P> 1 Set

    point-200.0 %0.0 %

    -5.0 % DesignersReferenceHandbook

    The alarm and fail class are ac-tivated when the reverse powerhas been continuously abovethe programmed value duringthe programmed delay.

    1002 P> 1 Timer 0.1 s100.0 s

    10.0 s

    1003 P> 1 RelayoutputA

    Not usedOption-depend-ent

    Not used

    1004 P> 1 RelayoutputB

    Not usedOption-depend-ent

    Not used

    1005 P> 1 Enable OFFON

    ON

    1006 P> 1 Failclass

    F1F8 Trip GB(F3)

    1010 Reverse power 21011 P> 2 Set

    point-200.0 %0.0 %

    -5.0 % DesignersReferenceHandbook

    The alarm and fail class are ac-tivated when the reverse powerhas been continuously abovethe programmed value duringthe programmed delay.

    1012 P> 2 Timer 0.1 s100.0 s

    10.0 s

    1013 P> 2 RelayoutputA

    Not usedOption-depend-ent

    Not used

    1014 P> 2 RelayoutputB

    Not usedOption-depend-ent

    Not used

    1015 P> 2 Enable OFFON

    ON

    1016 P> 2 Failclass

    F1F8 Trip GB(F3)

    1030 Overcurrent 1

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 8 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    1031 I> 1 Setpoint

    50.0 %200.0 %

    115.0 % DesignersReferenceHandbook

    The alarm and fail class are ac-tivated when the current hasbeen continuously above theprogrammed value during theprogrammed delay.

    1032 I> 1 Timer 0.1 s3200.0 s

    10.0 s

    1033 I> 1 RelayoutputA

    Not usedOption-depend-ent

    Not used

    1034 I> 1 RelayoutputB

    Not usedOption-depend-ent

    Not used

    1035 I> 1 Enable OFFON

    ON

    1036 I> 1 Failclass

    F1F8 Warn-ing(F2)

    1040 Overcurrent 21041 I> 2 Set

    point50.0 %200.0 %

    120.0 % DesignersReferenceHandbook

    The alarm and fail class are ac-tivated when the current hasbeen continuously above theprogrammed value during theprogrammed delay.

    1042 I> 2 Timer 0.1 s3200.0 s

    5.0 s

    1043 I> 2 RelayoutputA

    Not usedOption-depend-ent

    Not used

    1044 I> 2 RelayoutputB

    Not usedOption-depend-ent

    Not used

    1045 I> 2 Enable OFFON

    ON

    1046 I> 2 Failclass

    F1F8 Trip GB(F3)

    1050 Overcurrent 31051 I> 3 Set

    point50.0 %200.0 %

    115.0 % DesignersReferenceHandbook

    The alarm and fail class are ac-tivated when the current hasbeen continuously above theprogrammed value during theprogrammed delay.

    1052 I> 3 Timer 0.1 s3200.0 s

    10.0 s

    1053 I> 3 RelayoutputA

    Not usedOption-depend-ent

    Not used

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 9 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    1054 I> 3 RelayoutputB

    Not usedOption-depend-ent

    Not used

    1055 I> 3 Enable OFFON

    ON

    1056 I> 3 Failclass

    F1F8 Trip GB(F3)

    1060 Overcurrent 41061 I> 4 Set

    point50.0 %200.0 %

    120.0 % DesignersReferenceHandbook

    The alarm and fail class are ac-tivated when the current hasbeen continuously above theprogrammed value during theprogrammed delay.

    1062 I> 4 Timer 0.1 s3200.0 s

    5.0 s

    1063 I> 4 RelayoutputA

    Not usedOption-depend-ent

    Not used

    1064 I> 4 RelayoutputB

    Not usedOption-depend-ent

    Not used

    1065 I> 4 Enable OFFON

    ON

    1066 I> 4 Failclass

    F1F8 Trip GB(F3)

    1080 I> inverse1081 I> in-

    verseType

    Setpoint

    IEC In-verseCustom

    IEC In-verse

    DesignersReferenceHandbook

    Type selections are:IEC InverseIEC Very InverseIEC Extremely Inv.IEEE Moderately Inv.IEEE Very InverseIEEE Extremely Inv.Custom

    Output B is only available in theutility software.

    1082 I> in-verseLimit

    Setpoint

    50 %200 %

    110.0 %

    1083 I> in-verseTMS

    Setpoint

    0.1100.0

    1.0

    1084 I> in-verse k

    Setpoint

    0.001 s32.000 s

    0.140 s

    1085 I> in-verse c

    Setpoint

    0.000 s32.000 s

    0.000 s

    1086 I> in-verse a

    Setpoint

    0.00132.000

    0.020

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 10 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    1087 I> in-verse

    RelayoutputA

    Not usedOption-depend-ent

    Not used

    1088 I> in-verse

    Enable OFFON

    ON

    1089 I> in-verse

    Failclass

    F1F8 Trip GB(F3)

    1130 Fast overcurrent 11131 I>> 1 Set

    point150.0 %350.0 %

    150.0 % DesignersReferenceHandbook

    The alarm settings relate to thenominal current setting. Thealarm and fail class are activa-ted when the current has beencontinuously above the pro-grammed value during the pro-grammed delay.

    1132 I>> 1 Timer 0.0 s100.0 s

    2.0 s

    1133 I>> 1 RelayoutputA

    Not usedOption-depend-ent

    Not used

    1134 I>> 1 RelayoutputB

    Not usedOption-depend-ent

    Not used

    1135 I>> 1 Enable OFFON

    OFF

    1136 I>> 1 Failclass

    F1...F8 Trip GB(F3)

    1140 Fast overcurrent 21141 I>> 2 Set

    point150.0 %350.0 %

    200 % DesignersReferenceHandbook

    The alarm and fail class are ac-tivated when the current hasbeen continuously above theprogrammed value during theprogrammed delay

    1142 I>> 2 Delay 0.0 s100.0 s

    0.5 s

    1143 I>> 2 RelayoutputA

    Not usedOption-depend-ent

    Not used

    1144 I>> 2 RelayoutputB

    Not usedOption-depend-ent

    Not used

    1145 I>> 2 Enable OFFON

    OFF

    1146 I>> 2 Failclass

    F1...F8 Trip GB(F3)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 11 of 98

  • 2.2.2 Voltage protectionsNo. Setting Min.

    Max.Factorysetting

    Notes Ref. Description

    1150 G overvoltage 11151 G U>

    1Setpoint

    100.0 %120.0 %

    103.0 % DesignersReferenceHandbook

    The alarm and fail class are acti-vated when the voltage has beencontinuously above the program-med value during the program-med delay.

    1152 G U>1

    Timer 0.1 s100.0 s

    10.0 s

    1153 G U>1

    RelayoutputA

    Not usedOption-dep.

    Notused

    1154 G U>1

    RelayoutputB

    Not usedOption-dep.

    Notused

    1155 G U>1

    Enable OFFON

    OFF

    1156 G U>1

    Failclass

    F1F8 Warning(F2)

    1160 G overvoltage 21161 G U>

    2Setpoint

    100.0 %120.0 %

    105.0 % DesignersReferenceHandbook

    The alarm and fail class are acti-vated when the voltage has beencontinuously above the program-med value during the program-med delay.

    1162 G U>2

    Timer 0.1 s100.0 s

    5.0 s

    1163 G U>2

    RelayoutputA

    Not usedOption-dep.

    Notused

    1164 G U>2

    RelayoutputB

    Not usedOption-dep.

    Notused

    1165 G U>2

    Enable OFFON

    OFF

    1166 G U>2

    Failclass

    F1F8 Warning(F2)

    1170 G undervoltage 11171 G U3

    Failclass

    F1F8 Warning(F2)

    1240 G underfrequency 11241 G f

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    1254 G f

  • 2.2.4 Busbar voltage protections

    Voltage settings relate to the nominal voltage setting.

    No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    1270 Busbar overvoltage 11271 BB

    U> 1Setpoint

    100.0 %120.0 %

    103.0 % DesignersReferenceHandbook

    The alarm and fail class are acti-vated when the voltage has beencontinuously above the program-med value during the program-med delay.

    1272 BBU> 1

    Timer 0.00 s99.99 s

    10.00 s

    1273 BBU> 1

    RelayoutputA

    Not usedOption-depend-ent

    Notused

    1274 BBU> 1

    RelayoutputB

    Not usedOption-depend-ent

    Notused

    1275 BBU> 1

    Enable OFFON

    OFF

    1276 BBU> 1

    Failclass

    F1F8 Warning(F2)

    1280 Busbar overvoltage 21281 BB

    U> 2Setpoint

    100.0 %120.0 %

    105.0 % DesignersReferenceHandbook

    The alarm and fail class are acti-vated when the voltage has beencontinuously above the program-med value during the program-med delay.

    1282 BBU> 2

    Timer 0.00 s99.99 s

    10.00 s

    1283 BBU> 2

    RelayoutputA

    Not usedOption-depend-ent

    Notused

    1284 BBU> 2

    RelayoutputB

    Not usedOption-depend-ent

    Notused

    1285 BBU> 2

    Enable OFFON

    OFF

    1286 BBU> 2

    Failclass

    F1F8 Warning(F2)

    1300 Busbar undervoltage 1

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 17 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    1301 BBU< 1

    Setpoint

    40.0 %100.0 %

    97.0 % DesignersReferenceHandbook

    The alarm and fail class are acti-vated when the voltage has beencontinuously under the program-med value during the program-med delay.

    1302 BBU< 1

    Timer 0.00 s99.99 s

    10.00 s

    1303 BBU< 1

    RelayoutputA

    Not usedOption-depend-ent

    Notused

    1304 BBU< 1

    RelayoutputB

    Not usedOption-depend-ent

    Notused

    1305 BBU< 1

    Enable OFFON

    OFF

    1306 BBU< 1

    Failclass

    F1F8 Warning(F2)

    1310 Busbar undervoltage 21311 BB

    U< 2Setpoint

    40.0 %100.0 %

    95.0 % DesignersReferenceHandbook

    The alarm and fail class are acti-vated when the voltage has beencontinuously under the program-med value during the program-med delay.

    1312 BBU< 2

    Timer 0.00 s99.99 s

    5.00 s

    1313 BBU< 2

    RelayoutputA

    Not usedOption-depend-ent

    Notused

    1314 BBU< 2

    RelayoutputB

    Not usedOption-depend-ent

    Notused

    1315 BBU< 2

    Enable OFFON

    OFF

    1316 BBU< 2

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 18 of 98

  • 2.2.5 Busbar frequency protections

    Frequency settings relate to the nominal frequency setting.

    No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    1350 Busbar overfrequency 11351 BB f>

    1Setpoint

    100.0 %120.0 %

    103.0 % DesignersReferenceHandbook

    The alarm and fail class are acti-vated when the frequency hasbeen continuously above the pro-grammed value during the pro-grammed delay.

    1352 BB f>1

    Timer 0.00 s99.99 s

    10.00 s

    1353 BB f>1

    RelayoutputA

    Not usedOption-dep.

    Notused

    1354 BB f>1

    RelayoutputB

    Not usedOption-dep.

    Notused

    1355 BB f>1

    Enable OFFON

    OFF

    1356 BB f>1

    Failclass

    F1F8 Warning(F2)

    1360 Busbar overfrequency 21361 BB f>

    2Setpoint

    100.0 %120.0 %

    105.0 % DesignersReferenceHandbook

    The alarm and fail class are acti-vated when the frequency hasbeen continuously above the pro-grammed value during the pro-grammed delay.

    1362 BB f>2

    Timer 0.00 s99.99 s

    5.00 s

    1363 BB f>2

    RelayoutputA

    Not usedOption-dep.

    Notused

    1364 BB f>2

    RelayoutputB

    Not usedOption-dep.

    Notused

    1365 BB f>2

    Enable OFFON

    OFF

    1366 BB f>2

    Failclass

    F1F8 Warning(F2)

    1380 Busbar underfrequency 11381 BB f 2 Failclass

    F1F8 Trip GB(F3)

    1470 Overload 31471 P> 3 Set

    point-200.0 %200.0 %

    100.0 % DesignersReferenceHandbook

    The alarm and fail class are activa-ted when the power has been con-tinuously above the programmedvalue during the programmed de-lay.

    1472 P> 3 Timer 0.1 s3200.0 s

    10.0 s

    1473 P> 3 RelayoutputA

    Not usedOption-dep.

    Notused

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 21 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    1474 P> 3 RelayoutputB

    Not usedOption-dep.

    Notused

    1475 P> 3 Enable OFFON

    OFF

    1476 P> 3 Failclass

    F1F8 Trilp GB(F3)

    1480 Overload 41481 P> 4 Set

    point-200.0 %200.0 %

    110.0 % DesignersReferenceHandbook

    The alarm and fail class are activa-ted when the power has been con-tinuously above the programmedvalue during the programmed de-lay.

    1482 P> 4 Timer 0.1 s3200.0 s

    5.0 s

    1483 P> 4 RelayoutputA

    Not usedOption-dep.

    Notused

    1484 P> 4 RelayoutputB

    Not usedOption-dep.

    Notused

    1485 P> 4 Enable OFFON

    OFF

    1486 P> 4 Failclass

    F1F8 Trip GB(F3)

    1490 Overload 51491 P> 5 Set

    point-200.0 %200.0 %

    100.0 % DesignersReferenceHandbook

    The alarm and fail class are activa-ted when the power has been con-tinuously above the programmedvalue during the programmed de-lay.

    1492 P> 5 Timer 0.1 s3200.0 s

    10.0 s

    1493 P> 5 RelayoutputA

    Not usedOption-dep.

    Notused

    1494 P> 5 RelayoutputB

    Not usedOption-dep.

    Notused

    1495 P> 5 Enable OFFON

    OFF

    1496 P> 5 Failclass

    F1...F8 Trip GB(F3)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 22 of 98

  • 2.2.7 Undervoltage and reactive power lowNo. Setting Min.

    Max.Factorysetting

    Notes Ref. Description

    1960 U and Q < 11961 U and

    Q < 1Setpoint

    40.0 %100.0 %

    85.0 % Option A1 The setting relates to the genera-tor nominal voltage.The condition for trip is that the ac-tual voltage drops below the set-ting value and the reactive poweris 0 kVAr.

    1962 U andQ < 1

    Timer 0.1 s3200.0 s

    0.5 s

    1963 U andQ < 1

    RelayoutputA

    Option-dep.

    Notused

    1964 U andQ < 1

    RelayoutputB

    Option-dep.

    Notused

    1965 U andQ < 1

    Enable OFFON

    OFF

    1966 U andQ < 1

    Failclass

    F1F8 Warning(F2)

    1970 U and Q < 21971 U and

    Q < 2Setpoint

    40.0 %100.0 %

    85.0 % Option A1 The setting relates to the genera-tor nominal voltage.The condition for trip is that the ac-tual voltage drops below the set-ting value and the reactive poweris 0 kVAr.

    1972 U andQ < 2

    Timer 0.1 s3200.0 s

    0.5 s

    1973 U andQ < 2

    RelayoutputA

    Option-dep.

    Notused

    1974 U andQ < 2

    RelayoutputB

    Option-dep.

    Notused

    1975 U andQ < 2

    Enable OFFON

    OFF

    1976 U andQ < 2

    Failclass

    F1F8 Warning(F2)

    1980 GB/MB external trip1981 GB ext.

    tripEnable OFF

    ONON Design-

    er's Refer-enceHandbook

    The generator breaker or themains breaker has been tripped byan external device.1982 GB ext.

    tripFailclass

    F1...F8 Warning(F2)

    1983 MB ext.trip

    Enable OFFON

    ON

    1984 MB ext.trip

    Failclass

    F1...F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 23 of 98

  • Minimum current and minimum Phi angle

    No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    1990 U and Q< 11991 I Min. 1 Set

    point0 %20 %

    0 % OptionA1

    Settings relate to U and Q< parameters1960 and 1970.Condition for "U and Q

  • 2.3 Breaker control parameters2.3.1 Breaker alarms

    No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    2110 Sync. blackout2111 Sync.

    blackoutdfMax. 0.0 Hz

    5.0 Hz3.0 Hz Designers

    ReferenceHandbook

    Settings are accepted limits forclosing of the breaker, refer-ring to nominal frequency andvoltage.

    2112 Sync.blackout

    dUMax. 2 %10 %

    5 %

    2150 Phase sequence error2151 Phase

    seq er-ror

    Relayoutput A

    Not usedOption-dep.

    Not used DesignersReferenceHandbook

    Prior to closing a breaker, theunit checks that the phase se-quence is correct, dependingon the chosen phase directionin parameter 2154: Phase ro-tation. If it is incorrect (re-versed), an alarm will be is-sued and the breaker in ques-tion will not be closed.

    2152 Phaseseq er-ror

    Relayoutput B

    Not usedOption-dep.

    Not used

    2153 Phaseseq er-ror

    Failclass

    F1F8 Block(F1)

    2154 Phaserotation

    Set point L1L2L3L1L3L2

    L1L2L3

    2160 GB open failure2161 GB

    open failTimer 1.0 s

    10.0 s2.0 s Designers

    ReferenceHandbook

    The breaker open failure willoccur if the unit has transmit-ted a breaker open signal andthe breaker feedback has notchanged position from ON toOFF within the time delay.

    2162 GBopen fail

    Relayoutput A

    Not usedOption-dep.

    Not used

    2163 GBopen fail

    Relayoutput B

    Not usedOption-dep.

    Not used

    2164 GBopen fail

    Enable OFFON

    ON

    2165 GBopen fail

    Failclass

    F1F8 Warning(F2)

    2170 GB breaker close failure2171 GB

    closefail

    Timer 1.0 s5.0 s

    2.0 s DesignersReferenceHandbook

    The breaker close failure willoccur if the unit has transmit-ted a breaker close signal andthe breaker feedback has notchanged position from OFF toON within the time delay.

    2172 GBclosefail

    Relayoutput A

    Not usedOption-dep.

    Not used

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 25 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    2173 GBclosefail

    Relayoutput B

    Not usedOption-dep.

    Not used

    2174 GBclosefail

    Enable OFFON

    ON

    2175 GBclosefail

    Failclass

    F1F8 Warning(F2)

    2180 GB breaker position failure2181 GB pos

    failTimer 1.0 s

    5.0 s1.0 s Designers

    ReferenceHandbook

    This alarm will occur if thebreaker feedbacks for ON andOFF are both missing or activefor more than the time delay.

    2182 GB posfail

    Relayoutput A

    Not usedOption-dep.

    Not used

    2183 GB posfail

    Relayoutput B

    Not usedOption-dep.

    Not used

    2184 GB posfail

    Enable OFFON

    ON

    2185 GB posfail

    Failclass

    F1F8 Warning(F2)

    2200 MB open failure2201 MB

    open failTimer 1.0 s

    10.0 s2.0 s Designers

    ReferenceHandbook

    The breaker open failure willoccur if the unit has transmit-ted a breaker open signal andthe breaker feedback has notchanged position from ON toOFF within the time delay.

    2202 MBopen fail

    Relayoutput A

    Not usedOption-dep.

    Not used

    2203 MBopen fail

    Relayoutput B

    Not usedOption-dep.

    Not used

    2204 MBopen fail

    Enable OFFON

    ON

    2205 MBopen fail

    Failclass

    F1F8 Warning(F2)

    2210 MB close failure2211 MB

    closefail

    Timer 1.0 s5.0 s

    2.0 s DesignersReferenceHandbook

    The breaker close failure willoccur if the unit has transmit-ted a breaker close signal andthe breaker feedback has notchanged position from OFF toON within the time delay.

    2212 MBclosefail

    Relayoutput A

    Not usedOption-dep.

    Not used

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 26 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    2213 MBclosefail

    Relayoutput B

    Not usedOption-dep.

    Not used

    2214 MBclosefail

    Enable OFFON

    ON

    2215 MBclosefail

    Failclass

    F1F8 Warning(F2)

    2220 MB position failure2221 MB pos

    failTimer 1.0 s

    5.0 s1.0 s Designers

    ReferenceHandbook

    This alarm will occur if thebreaker feedbacks for ON andOFF are both missing or activefor more than the time delay.

    2222 MB posfail

    Relayoutput A

    Not usedOption-dep.

    Not used

    2223 MB posfail

    Relayoutput B

    Not usedOption-dep.

    Not used

    2224 MB posfail

    Enable OFFON

    ON

    2225 MB posfail

    Failclass

    F1F8 Warning(F2)

    No. Setting Min. setting Max. setting Factory setting2770 EIC control2771 EIC control Droop 0.0 % 25.0 % 0.0 %2772 EIC control Scania rpm User

    1500 rpm1800 rpmLow Idle

    User

    2773 EIC control Cummins gain 0.00 10.00 5.002790 EIC speed demand switch2791 EIC speed demand

    switchLocal normal sw. Analogue CAN

    UpDown ECUUpDown CANAnalogue ECUAnalogue ECU relativeFrequency

    Analogue CAN

    2792 EIC speed demandswitch

    Local emergency sw.

    2793 EIC speed demandswitch

    Remote normal sw.

    2794 EIC speed demandswitch

    Remote emergency sw.

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 27 of 98

  • 2.4 Input/output parameters, binary input setup2.4.1 Digital input 10-15 and 56-57 setup

    No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    3000 Digital input 103001 Dig. in-

    put 10Timer 0.0 s

    100.0 s10.0 s Designers

    ReferenceHandbook

    The input is configurableand can have differentfunctions in different units.3002 Dig. in-

    put 10Relayoutput A

    Not usedOption-dep.

    Not used

    3003 Dig. in-put 10

    Relayoutput B

    Not usedOption-dep.

    Not used

    3004 Dig. in-put 10

    Enable OFFON

    OFF

    3005 Dig. in-put 10

    Fail class F1F8 Warning(F2)

    3006 Dig. in-put 10

    HighAlarm

    OFFON

    ON

    The same settings apply to inputs 11-15 and 56-57, menus 3010 to 3070.

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 28 of 98

  • 2.4.2 Digital input 6-8 setupNo. Setting Min.

    Max.Facto-ry set-

    ting

    Notes Ref. Description

    3400 Digital input 63401 Wire

    fail 6Enable OFF OFF Designers

    ReferenceHandbook

    The input is configurable and canhave different functions in differentunits.(Only available if multi-input 6 isconfigured to "binary" in menu10980).

    3402 Dig. in-put 6

    Timer 0.0 s100.0 s

    10.0 s

    3403 Dig. in-put 6

    RelayoutputA

    NotusedOption-dep.

    Notused

    3404 Dig. in-put 6

    RelayoutputB

    NotusedOption-dep.

    Notused

    3405 Dig. in-put 6

    Enable OFFON

    OFF

    3406 Dig. in-put 6

    Failclass

    F1F8 Warn-ing(F2)

    3410 Digital input 73411 Wire

    fail 7Enable OFF OFF Designers

    ReferenceHandbook

    The input is configurable and canhave different functions in differentunits.(Only available if multi-input 7 isconfigured to "binary" in menu10990).

    3412 Dig. in-put 7

    Timer 0.0 s100.0 s

    10.0 s

    3413 Dig. in-put 7

    RelayoutputA

    NotusedOption-dep.

    Notused

    3414 Dig. in-put 7

    RelayoutputB

    NotusedOption-dep.

    Notused

    3415 Dig. in-put 7

    Enable OFFON

    OFF

    3416 Dig. in-put 7

    Failclass

    F1F8 Warn-ing(F2)

    3420 Digital input 8

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 29 of 98

  • No. Setting Min.Max.

    Facto-ry set-

    ting

    Notes Ref. Description

    3421 Wirefail 8

    Enable OFF OFF DesignersReferenceHandbook

    The input is configurable and canhave different functions in differentunits.(Only available if multi-input 8 isconfigured to "binary" in menu11000).

    3422 Dig. in-put 8

    Timer 0.0 s100.0 s

    10.0 s

    3423 Dig. in-put 8

    RelayoutputA

    NotusedOption-dep.

    Notused

    3424 Dig. in-put 8

    RelayoutputB

    NotusedOption-dep.

    Notused

    3425 Dig. in-put 8

    Enable OFFON

    OFF

    3426 Dig. in-put 8

    Failclass

    F1F8 Warn-ing(F2)

    2.4.3 Emergency stopNo. Setting Min.

    Max.Factorysetting

    Notes Ref. Description

    3490 Emergency stop3491 Emer.

    stopTimer 0.0 s

    60.0 s0.0 s Designers

    ReferenceHandbook

    Emergency stop input isintended for a normallyclosed contact.3492 Emer.

    stopRelayoutput A

    Not usedOption-dependent

    Not used

    3493 Emer.stop

    Relayoutput B

    Not usedOption-de-pendent

    Not used

    3494 Emer.stop

    Enable OFFON

    ON

    3495 Emer.stop

    Fail class F1F8 Shut-down(F5)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 30 of 98

  • 2.4.4 M-Logic alarm 1-5 setupNo. Setting Min.

    Max.Factorysetting

    Notes Ref. Description

    3570 Mlogic alarm 13570 Mlogic alarm 1 Timer 0.0 s

    100.0 s10.0 s The input is configura-

    ble.3571 Mlogic alarm 1 Relay output

    ANot usedOption-dep.

    Not used

    3572 Mlogic alarm 1 Relay outputB

    Not usedOption-dep.

    Not used

    3573 Mlogic alarm 1 Enable OFFON

    OFF

    3574 Mlogic alarm 1 Fail class F1F8 Warning(F2)

    3575 Mlogic alarm 1 High alarm OFFON

    ON

    The same settings apply to alarm inputs 2-5, menus 3580 to 3610.

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 31 of 98

  • 2.5 Analogue input setup2.5.1 Multi-input no. 6

    The available menus for multi-input no. 6 depend on the input type configured in the PC utilitysoftware (menu 10980).

    No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4120 4-20 mA 6.14121 4-20

    mA 6.1Setpoint

    4 mA20 mA

    10 mA DesignersReferenceHandbook

    The multi-input 6 has beenconfigured as 4-20 mA.

    4122 4-20mA 6.1

    Timer 0.0 s999.0 s

    120.0 s

    4123 4-20mA 6.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4124 4-20mA 6.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4125 4-20mA 6.1

    Enable OFFON

    OFF

    4126 4-20mA 6.1

    Failclass

    F1F8 Warning(F2)

    4130 4-20 mA 6.24131 4-20

    mA 6.2Setpoint

    4 mA20 mA

    10 mA DesignersReferenceHandbook

    The multi-input 6 has beenconfigured as 4-20 mA.

    4132 4-20mA 6.2

    Timer 0.0 s999.0 s

    120.0 s

    4133 4-20mA 6.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4134 4-20mA 6.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4135 4-20mA 6.2

    Enable OFFON

    OFF

    4136 4-20mA 6.2

    Failclass

    F1F8 Warning(F2)

    4160 Pt100/Pt1000 6.14161 PT 6.1 Set

    point-49482

    80 DesignersReferenceHandbook

    The multi-input 6 has beenconfigured as Pt100 orPt1000.4162 PT 6.1 Timer 0.0 s

    999.0 s5.0 s

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 32 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4163 Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).

    PT 6.1 Relayoutput A

    Not usedOption-dep.

    Notused

    4164 PT 6.1 Relayoutput B

    Not usedOption-dep.

    Notused

    4165 PT 6.1 Enable OFFON

    OFF

    4166 PT 6.1 Failclass

    F1F8 Warning(F2)

    4167 PT 6.1 Offset 0.0 Ohm5.0 Ohm

    0.0 Ohm

    4170 Pt100/Pt1000 6.24171 PT 6.2 Set

    point-49482

    80 DesignersReferenceHandbook

    The multi-input 6 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).

    4172 PT 6.2 Timer 0.0 s999.0 s

    10.0 s

    4173 PT 6.2 Relayoutput A

    Not usedOption-dep.

    Notused

    4174 PT 6.2 Relayoutput B

    Not usedOption-dep.

    Notused

    4175 PT 6.2 Enable OFFON

    OFF

    4176 PT 6.2 Failclass

    F1...F8 Warning(F2)

    4180 Resistance measurement input, oil pressure 6.14181 RMI oil

    6.1Setpoint

    0.0145.0

    2.0 DesignersReferenceHandbook

    The multi-input 6 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).

    4182 RMI oil6.1

    Timer 0.0 s999.0 s

    5.0 s

    4183 RMI oil6.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4184 RMI oil6.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4185 RMI oil6.1

    Enable OFFON

    OFF

    4186 RMI oil6.1

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 33 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4190 Resistance measurement input, oil pressure 6.24191 RMI oil

    6.2Setpoint

    0.0145.0

    1.0 DesignersReferenceHandbook

    The multi-input 6 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).

    4192 RMI oil6.2

    Timer 0.0 s999.0 s

    5.0 s

    4193 RMI oil6.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4194 RMI oil6.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4195 RMI oil6.2

    Enable OFFON

    OFF

    4196 RMI oil6.2

    Failclass

    F1F8 Shut-down(F5)

    4200 Resistance measurement input, water temperature 6.14201 RMI

    water6.1

    Setpoint

    -49482

    100 DesignersReferenceHandbook

    The multi-input 6 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).

    4202 RMIwater6.1

    Timer 0.0 s999.0 s

    5.0 s

    4203 RMIwater6.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4204 RMIwater6.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4205 RMIwater6.1

    Enable OFFON

    OFF

    4206 RMIwater6.1

    Failclass

    F1F8 Warning(F2)

    4210 Resistance measurement input, water temperature 6.24211 RMI

    water6.2

    Setpoint

    -49482

    110 DesignersReferenceHandbook

    The multi-input 6 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).

    4212 RMIwater6.2

    Timer 0.0 s999.0 s

    5.0 s

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 34 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4213 RMIwater6.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4214 RMIwater6.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4215 RMIwater6.2

    Enable OFFON

    OFF

    4216 RMIwater6.2

    Failclass

    F1F8 Trip +Stop(F4)

    4220 Resistance measurement input, fuel level 6.14221 RMI

    fuel 6.1Setpoint

    0 %100 %

    10 % DesignersReferenceHandbook

    The multi-input 6 has beenconfigured as RMI fuel level.

    4222 RMIfuel 6.1

    Timer 0.0 s999.0 s

    10.0 s

    4223 RMIfuel 6.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4224 RMIfuel 6.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4225 RMIfuel 6.1

    Enable OFFON

    OFF

    4226 RMIfuel 6.1

    Failclass

    F1F8 Warning(F2)

    4230 Resistance measurement input, fuel level 6.24231 RMI

    fuel 6.2Setpoint

    0 %100 %

    5 % DesignersReferenceHandbook

    The multi-input 6 has beenconfigured as RMI fuel level.

    4232 RMIfuel 6.2

    Timer 0.0 s999.0 s

    10.0 s

    4233 RMIfuel 6.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4234 RMIfuel 6.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4235 RMIfuel 6.2

    Enable OFFON

    OFF

    4236 RMIfuel 6.2

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 35 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4240 Wire fail 64241 W. fail

    6Relayoutput A

    Not usedOption-dep.

    Notused

    DesignersReferenceHandbook

    The wire break fault detectionis activated.

    4242 W. fail6

    Relayoutput B

    Not usedOption-dep.

    Notused

    4243 W. fail6

    Enable OFFON

    OFF

    4244 W. fail6

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 36 of 98

  • 2.5.2 Multi-input no. 7The available menus for multi-input no. 7 depend on the input type configured in the PC utilitysoftware (menu 10990).

    No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4250 4-20 mA 7.14251 4-20

    mA 7.1Setpoint

    4 mA20 mA

    10 mA DesignersReferenceHandbook

    The multi-input 7 has beenconfigured as 4-20 mA.

    4252 4-20mA 7.1

    Timer 0.0 s999.0 s

    120.0 s

    4253 4-20mA 7.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4254 4-20mA 7.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4255 4-20mA 7.1

    Enable OFFON

    OFF

    4256 4-20mA 7.1

    Failclass

    F1F8 Warning(F2)

    4260 4-20 mA 7.24261 4-20

    mA 7.2Setpoint

    4 mA20 mA

    10 mA DesignersReferenceHandbook

    The multi-input 7 has beenconfigured as 4-20 mA.

    4262 4-20mA 7.2

    Timer 0.0 s999.0 s

    120.0 s

    4263 4-20mA 7.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4264 4-20mA 7.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4265 4-20mA 7.2

    Enable OFFON

    OFF

    4266 4-20mA 7.2

    Failclass

    F1F8 Warning(F2)

    4290 Pt100/Pt1000 7.14291 PT 7.1 Set

    point-49482

    80 DesignersReferenceHandbook

    The multi-input 7 has beenconfigured as Pt100 orPt1000.4292 PT 7.1 Timer 0.0 s

    999.0 s5.0 s

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 37 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4293 PT 7.1 Relayoutput A

    Not usedOption-dep.

    Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).

    Notused

    4294 PT 7.1 Relayoutput B

    Not usedOption-dep.

    Notused

    4295 PT 7.1 Enable OFFON

    OFF

    4296 PT 7.1 Failclass

    F1F8 Warning(F2)

    4297 PT 7.1 Offset 0.0 Ohm5.0 Ohm

    0.0 Ohm

    4300 Pt100/Pt1000 7.24301 PT 7.2 Set

    point-49482

    80 DesignersReferenceHandbook

    The multi-input 7 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).

    4302 PT 7.2 Timer 0.0 s999.0 s

    10.0 s

    4303 PT 7.2 Relayoutput A

    Not usedOption-dep.

    Notused

    4304 PT 7.2 Relayoutput B

    Not usedOption-dep.

    Notused

    4305 PT 7.2 Enable OFFON

    OFF

    4306 PT 7.2 Failclass

    F1...F8 Warning(F2)

    4310 Resistance measurement input, oil pressure 7.14311 RMI oil

    7.1Setpoint

    0.0145.0

    2.0 DesignersReferenceHandbook

    The multi-input 7 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).

    4312 RMI oil7.1

    Timer 0.0 s999.0 s

    5.0 s

    4313 RMI oil7.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4314 RMI oil7.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4315 RMI oil7.1

    Enable OFFON

    OFF

    4316 RMI oil7.1

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 38 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4320 Resistance measurement input, oil pressure 7.24321 RMI oil

    7.2Setpoint

    0.0145.0

    1.0 DesignersReferenceHandbook

    The multi-input 7 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).

    4322 RMI oil7.2

    Timer 0.0 s999.0 s

    5.0 s

    4323 RMI oil7.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4324 RMI oil7.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4325 RMI oil7.2

    Enable OFFON

    OFF

    4326 RMI oil7.2

    Failclass

    F1F8 Shut-down(F5)

    4330 Resistance measurement input, water temperature 7.14331 RMI

    water7.1

    Setpoint

    -49482

    100 DesignersReferenceHandbook

    The multi-input 7 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).

    4332 RMIwater7.1

    Timer 0.0 s999.0 s

    5.0 s

    4333 RMIwater7.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4334 RMIwater7.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4335 RMIwater7.1

    Enable OFFON

    OFF

    4336 RMIwater7.1

    Failclass

    F1F8 Warning(F2)

    4340 Resistance measurement input, water temperature 7.24341 RMI

    water7.2

    Setpoint

    -49482

    110 DesignersReferenceHandbook

    The multi-input 7 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).

    4342 RMIwater7.2

    Timer 0.0 s999.0 s

    5.0 s

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 39 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4343 RMIwater7.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4344 RMIwater7.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4345 RMIwater7.2

    Enable OFFON

    OFF

    4346 RMIwater7.2

    Failclass

    F1F8 Trip +Stop(F4)

    4350 Resistance measurement input, fuel level 7.14351 RMI

    fuel 7.1Setpoint

    0 %100 %

    10 % DesignersReferenceHandbook

    The multi-input 7 has beenconfigured as RMI fuel level.

    4352 RMIfuel 7.1

    Timer 0.0 s999.0 s

    10.0 s

    4353 RMIfuel 7.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4354 RMIfuel 7.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4555 RMIfuel 7.1

    Enable OFFON

    OFF

    4356 RMIfuel 7.1

    Failclass

    F1F8 Warning(F2)

    4360 Resistance measurement input, fuel level 7.24361 RMI

    fuel 7.2Setpoint

    0 %100 %

    5 % DesignersReferenceHandbook

    The multi-input 7 has beenconfigured as RMI fuel level.

    4362 RMIfuel 7.2

    Timer 0.0 s999.0 s

    10.0 s

    4363 RMIfuel 7.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4364 RMIfuel 7.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4365 RMIfuel 7.2

    Enable OFFON

    OFF

    4366 RMIfuel 7.2

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 40 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4370 Wire fail 74371 W. fail

    7Relayoutput A

    Not usedOption-dep.

    Notused

    DesignersReferenceHandbook

    The wire break fault detectionis activated.

    4372 W. fail7

    Relayoutput B

    Not usedOption-dep.

    Notused

    4373 W. fail7

    Enable OFFON

    OFF

    4374 W. fail7

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 41 of 98

  • 2.5.3 Multi-input no. 8The available menus for multi-input no. 8 depend on the input type configured in the PC utilitysoftware (menu 11000).

    No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4380 4-20 mA 8.14381 4-20

    mA 8.1Setpoint

    4 mA20 mA

    10 mA DesignersReferenceHandbook

    The multi-input 8 has beenconfigured as 4-20 mA.

    4382 4-20mA 8.1

    Timer 0.0 s999.0 s

    120.0 s

    4383 4-20mA 8.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4384 4-20mA 8.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4385 4-20mA 8.1

    Enable OFFON

    OFF

    4386 4-20mA 8.1

    Failclass

    F1F8 Warning(F2)

    4390 4-20 mA 8.24391 4-20

    mA 8.2Setpoint

    4 mA20 mA

    10 mA DesignersReferenceHandbook

    The multi-input 8 has beenconfigured as 4-20 mA.

    4392 4-20mA 8.2

    Timer 0.0 s999.0 s

    120.0 s

    4393 4-20mA 8.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4394 4-20mA 8.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4395 4-20mA 8.2

    Enable OFFON

    OFF

    4396 4-20mA 8.2

    Failclass

    F1F8 Warning(F2)

    4420 Pt100/Pt1000 8.14421 PT 8.1 Set

    point-49482

    80 DesignersReferenceHandbook

    The multi-input 8 has beenconfigured as Pt100 orPt1000.4422 PT 8.1 Timer 0.0 s

    999.0 s5.0 s

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 42 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4423 PT 8.1 Relayoutput A

    Not usedOption-dep.

    Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).

    Notused

    4424 PT 8.1 Relayoutput B

    Not usedOption-dep.

    Notused

    4425 PT 8.1 Enable OFFON

    OFF

    4426 PT 8.1 Failclass

    F1F8 Warning(F2)

    4427 PT 8.1 Offset 0.0 Ohm5.0 Ohm

    0.0 Ohm

    4430 Pt100/Pt1000 8.24431 PT 8.2 Set

    point-49482

    80 DesignersReferenceHandbook

    The multi-input 8 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).

    4432 PT 8.2 Timer 0.0 s999.0 s

    10.0 s

    4433 PT 8.2 Relayoutput A

    Not usedOption-dep.

    Notused

    4434 PT 8.2 Relayoutput B

    Not usedOption-dep.

    Notused

    4435 PT 8.2 Enable OFFON

    OFF

    4436 PT 8.2 Failclass

    F1...F8 Warning(F2)

    4440 Resistance measurement input, oil pressure 8.14441 RMI oil

    8.1Setpoint

    0.0145.0

    2.0 DesignersReferenceHandbook

    The multi-input 8 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).

    4442 RMI oil8.1

    Timer 0.0 s999.0 s

    5.0 s

    4443 RMI oil8.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4444 RMI oil8.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4445 RMI oil8.1

    Enable OFFON

    OFF

    4446 RMI oil8.1

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 43 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4450 Resistance measurement input, oil pressure 8.24451 RMI oil

    8.2Setpoint

    0.0145.0

    1.0 DesignersReferenceHandbook

    The multi-input 8 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).

    4452 RMI oil8.2

    Timer 0.0 s999.0 s

    5.0 s

    4453 RMI oil8.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4454 RMI oil8.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4455 RMI oil8.2

    Enable OFFON

    OFF

    4456 RMI oil8.2

    Failclass

    F1F8 Shut-down(F5)

    4460 Resistance measurement input, water temperature 8.14461 RMI

    water8.1

    Setpoint

    -49482

    100 DesignersReferenceHandbook

    The multi-input 8 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).

    4462 RMIwater8.1

    Timer 0.0 s999.0 s

    5.0 s

    4463 RMIwater8.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4464 RMIwater8.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4465 RMIwater8.1

    Enable OFFON

    OFF

    4466 RMIwater8.1

    Failclass

    F1F8 Warning(F2)

    4470 Resistance measurement input, water temperature 8.24471 RMI

    water8.2

    Setpoint

    -49482

    110 DesignersReferenceHandbook

    The multi-input 8 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection(menu 10970).

    4472 RMIwater8.2

    Timer 0.0 s999.0 s

    5.0 s

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 44 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4473 RMIwater8.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4474 RMIwater8.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4475 RMIwater8.2

    Enable OFFON

    OFF

    4476 RMIwater8.2

    Failclass

    F1F8 Trip +Stop(F4)

    4480 Resistance measurement input, fuel level 8.14481 RMI

    fuel 8.1Setpoint

    0 %100 %

    10 % DesignersReferenceHandbook

    The multi-input 8 has beenconfigured as RMI fuel level.

    4482 RMIfuel 8.1

    Timer 0.0 s999.0 s

    10.0 s

    4483 RMIfuel 8.1

    Relayoutput A

    Not usedOption-dep.

    Notused

    4484 RMIfuel 8.1

    Relayoutput B

    Not usedOption-dep.

    Notused

    4485 RMIfuel 8.1

    Enable OFFON

    OFF

    4486 RMIfuel 8.1

    Failclass

    F1F8 Warning(F2)

    4490 Resistance measurement input, fuel level 8.24491 RMI

    fuel 8.2Setpoint

    0 %100 %

    5 % DesignersReferenceHandbook

    The multi-input 8 has beenconfigured as RMI fuel level.

    4492 RMIfuel 8.2

    Timer 0.0 s999.0 s

    10.0 s

    4493 RMIfuel 8.2

    Relayoutput A

    Not usedOption-dep.

    Notused

    4494 RMIfuel 8.2

    Relayoutput B

    Not usedOption-dep.

    Notused

    4495 RMIfuel 8.2

    Enable OFFON

    OFF

    4496 RMIfuel 8.2

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 45 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4500 Wire fail 84501 W. fail

    8Relayoutput A

    Not usedOption-dep.

    Notused

    DesignersReferenceHandbook

    The wire break fault detectionis activated.

    4502 W. fail8

    Relayoutput B

    Not usedOption-dep.

    Notused

    4503 W. fail8

    Enable OFFON

    OFF

    4504 W. fail8

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 46 of 98

  • 2.5.4 Speed and running feedback setupNo. Setting Min.

    Max.Factorysetting

    Notes Ref. Description

    4510 Overspeed 14511 Over-

    speed 1Setpoint

    100.0 %150.0 %

    110.0 % DesignersReferenceHandbook

    The set point in percentagerelates to nominal RPM.

    4512 Over-speed 1

    Timer 0.0 s100.0 s

    5.0 s

    4513 Over-speed 1

    RelayoutputA

    Not usedOption-dep.

    Notused

    4514 Over-speed 1

    RelayoutputB

    Not usedOption-dep.

    Notused

    4515 Over-speed 1

    Enable OFFON

    OFF

    4516 Over-speed 1

    Failclass

    F1F8 Warn-ing(F2)

    4520 Overspeed 24521 Over-

    speed 2Setpoint

    100.0 %150.0 %

    120.0 % DesignersReferenceHandbook

    The set point in percentagerelates to nominal RPM.

    4522 Over-speed 2

    Timer 0.0 s100.0 s

    1.0 s

    4523 Over-speed 2

    RelayoutputA

    Not usedOption-dep.

    Notused

    4524 Over-speed 2

    RelayoutputB

    Not usedOption-dep.

    Notused

    4525 Over-speed 2

    Enable OFFON

    OFF

    4526 Over-speed 2

    Failclass

    F1F8 Shut-down(F5)

    4530 Crank failure4531 Crank

    failureSetpoint

    1 RPM400 RPM

    50 RPM DesignersReferenceHandbook

    If MPU is chosen as the pri-mary running feedback, thisalarm will be raised if thespecified RPM is not reachedbefore the delay has expired.

    4532 Crankfailure

    Timer 0.0 s20.0 s

    2.0 s

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 47 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4533 Crankfailure

    RelayoutputA

    Not usedOption-dep.

    Notused

    4534 Crankfailure

    RelayoutputB

    Not usedOption-dep.

    Notused

    4535 Crankfailure

    Enable OFFON

    OFF

    4536 Crankfailure

    Failclass

    F1F8 Warn-ing(F2)

    4540 Running feedback failure4541 Run

    feedb.fail

    Timer 0.0 s20.0 s

    2.0 s DesignersReferenceHandbook

    If running is detected on thefrequency (secondary), butthe primary running feedback,e.g. digital input, has not de-tected running, this alarm willbe raised after the adjusteddelay time.

    4542 Runfeedb.fail

    RelayoutputA

    Not usedOption-dep.

    Notused

    4543 Runfeedb.fail

    RelayoutputB

    Not usedOption-dep.

    Notused

    4544 Runfeedb.fail

    Enable OFFON

    ON

    4545 Runfeedb.fail

    Failclass

    F1...F8 Warn-ing(F2)

    4560 Hz/voltage failure4561 Hz/V fail-

    ureTimer 1.0 s

    99.0 s30.0 s Designers

    ReferenceHandbook

    If the frequency and voltageare not within the limits afterthe running feedback is re-ceived, this alarm will beraised when the delay timehas expired. Limits are placedin menu 2110 (Sync. black-out).

    4562 Hz/V fail-ure

    RelayoutputA

    Not usedOption-dep.

    Notused

    4563 Hz/V fail-ure

    RelayoutputB

    Not usedOption-dep.

    Notused

    4564 Hz/V fail-ure

    Enable OFFON

    ON

    4565 Hz/V fail-ure

    Failclass

    F1...F8 Shut-down(F5)

    4570 Start failure

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 48 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4571 Start fail-ure

    RelayoutputA

    Not usedOption-dep.

    Notused

    DesignersReferenceHandbook

    The start failure alarm occursif the genset has not startedafter the number of start at-tempts.4572 Start fail-

    ureRelayoutputB

    Not usedOption-dep.

    Notused

    4573 Start fail-ure

    Failclass

    F1F8 Block(F1)

    4580 Stop failure4581 Stop fail-

    ureTimer 10.0 s

    120.0 s30.0 s Designers

    ReferenceHandbook

    A stop failure alarm will ap-pear if the primary runningfeedback or the generatorvoltage and frequency are stillpresent after the delay timehas expired.

    4582 Stop fail-ure

    RelayoutputA

    Not usedOption-dep.

    Notused

    4583 Stop fail-ure

    RelayoutputB

    Not usedOption-dep.

    Notused

    4584 Stop fail-ure

    Enable OFFON

    ON

    4585 Stop fail-ure

    Failclass

    F1F8 Shut-down(F5)

    4590 Underspeed 14591 Under-

    speedSetpoint

    50.0 %100.0 %

    90.0 % DesignersReferenceHandbook

    The set point in percentagerelates to nominal RPM.

    4592 Under-speed

    Timer 0.0 s100.0 s

    5.0 s

    4593 Under-speed

    RelayoutputA

    Not usedOption-dep.

    Notused

    4594 Under-speed

    RelayoutputB

    Not usedOption-dep.

    Notused

    4595 Under-speed

    Enable OFFON

    OFF

    4596 Under-speed

    Failclass

    F1F8 Warn-ing(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 49 of 98

  • 2.5.5 Differential measurementNo. Setting Min.

    Max.Factorysetting

    Notes Ref. Description

    4600 Delta ana 1/2/3 Inp4601 Delta

    ana1 InpASet point Multi-input

    6EIC

    Multi-in-put 6

    Designers Ref-erence Hand-book

    Delta analogue Inp1/2/3 setting.Choose betweenmulti-inputs, externalanalogue inputs andEIC values

    4602 Deltaana1 InpB

    Set point Multi-input6EIC

    Multi-in-put 6

    4603 Deltaana2 InpA

    Set point Multi-input6EIC

    Multi-in-put 6

    4604 Deltaana2 InpB

    Set point Multi-input6EIC

    Multi-in-put 6

    4605 Deltaana3 InpA

    Set point Multi-input6EIC

    Multi-in-put 6

    4606 Deltaana3 InpB

    Set point Multi-input6EIC

    Multi-in-put 6

    4610 Delta ana1 14611 Delta

    ana1 1Set point -9999

    999910 Designers Ref-

    erence Hand-book

    Delta analogue alarmsetting 1.1

    4612 Deltaana1 1

    Timer 0.0 s999.0 s

    5.0 s

    4613 Deltaana1 1

    Relayoutput A

    Not usedOption-dep.

    Not used

    4614 Deltaana1 1

    Relayoutput B

    Not usedOption-dep.

    Not used

    4615 Deltaana1 1

    Enable OFFON

    OFF

    4616 Deltaana1 1

    Failclass

    F1F8 Warning(F2)

    4620 Delta ana1 24621 Delta

    ana1 2Set point -9999

    999910 Designers Ref-

    erence Hand-book

    Delta analogue alarmsetting 1.2

    4622 Deltaana1 2

    Timer 0.0 s999.0 s

    5.0 s

    4623 Deltaana1 2

    Relayoutput A

    Not usedOption-dep.

    Not used

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 50 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4624 Deltaana1 2

    Relayoutput B

    Not usedOption-dep.

    Not used

    4625 Deltaana1 2

    Enable OFFON

    OFF

    4626 Deltaana1 2

    Failclass

    F1F8 Warning(F2)

    4630 Delta ana2 14631 Delta

    ana2 1Set point -9999

    999910 Designers Ref-

    erence Hand-book

    Delta analogue alarmsetting 2.1

    4632 Deltaana2 1

    Timer 0.0 s999.0 s

    5.0 s

    4633 Deltaana2 1

    Relayoutput A

    Not usedOption-dep.

    Not used

    4634 Deltaana2 1

    Relayoutput B

    Not usedOption-dep.

    Not used

    4635 Deltaana2 1

    Enable OFFON

    OFF

    4636 Deltaana2 1

    Failclass

    F1F8 Warning(F2)

    4640 Delta ana2 24641 Delta

    ana2 2Set point -9999

    99910 Designers Ref-

    erence Hand-book

    Delta analogue alarmsetting 2.2

    4642 Deltaana2 2

    Timer 0.0 s999.0 s

    5.0 s

    4643 Deltaana2 2

    Relayoutput A

    Not usedOption-dep.

    Not used

    4644 Deltaana2 2

    Relayoutput B

    Not usedOption-dep.

    Not used

    4645 Deltaana2 2

    Enable OFFON

    OFF

    4646 Deltaana2 2

    Failclass

    F1...F8 Warning(F2)

    4650 Delta ana3 14651 Delta

    ana3 1Set point -9999

    999910 Designers Ref-

    erence Hand-book

    Delta analogue alarmsetting 3.1

    4652 Deltaana3 1

    Timer 0.0 s999.0 s

    5.0 s

    4653 Deltaana3 1

    Relayoutput A

    Not usedOption-dep.

    Not used

    4654 Deltaana3 1

    Relayoutput B

    Not usedOption-dep.

    Not used

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 51 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4655 Deltaana3 1

    Enable OFFON

    OFF

    4656 Deltaana3 1

    Failclass

    F1...F8 Warning(F2)

    4660 Delta ana3 24661 Delta

    ana3 2Set point -9999

    999910 Designers Ref-

    erence Hand-book

    Delta analogue alarmsetting 3.2

    4662 Deltaana3 2

    Timer 0.0 s999.0 s

    5.0 s

    4663 Deltaana3 2

    Relayoutput A

    Not usedOption-dep.

    Not used

    4664 Deltaana3 2

    Relayoutput B

    Not usedOption-dep.

    Not used

    4665 Deltaana3 2

    Enable OFFON

    OFF

    4666 Deltaana3 2

    Failclass

    F1...F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 52 of 98

  • 2.5.6 Aux. supply setupNo. Setting Min.

    Max.Factorysetting

    Notes Ref. Description

    4960 U< auxiliary power supply terminal 14961 U< aux.

    term. 1Setpoint

    8.0 Vdc32.0 Vdc

    18.0 Vdc DesignersReferenceHandbook

    The power supply on terminal1 and 2 has been continu-ously below the adjusted setpoint during the programmeddelay.

    4962 U< aux.term. 1

    Timer 10.0 s999.0 s

    10.0 s

    4963 U< aux.term. 1

    Relayoutput A

    Not usedOption-dep.

    Not used

    4964 U< aux.term. 1

    Relayoutput B

    Not usedOption-dep.

    Not used

    4965 U< aux.term. 1

    Enable OFFON

    ON

    4966 U< aux.term. 1

    Failclass

    F1F8 Warning(F2)

    4970 U> auxiliary power supply terminal 14971 U> aux.

    term. 1Setpoint

    12.0 Vdc36.0 Vdc

    30.0 Vdc DesignersReferenceHandbook

    The power supply on terminal1 and 2 has been continu-ously above the adjusted setpoint during the programmeddelay.

    4972 U> aux.term. 1

    Timer 10.0 s999.0 s

    10.0 s

    4973 U> aux.term. 1

    Relayoutput A

    Not usedOption-dep.

    Not used

    4974 U> aux.term. 1

    Relayoutput B

    Not usedOption-dep.

    Not used

    4975 U> aux.term. 1

    Enable OFFON

    ON

    4976 U> aux.term. 1

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 53 of 98

  • 2.5.7 Multi-input no. 58The available menus for multi-input no. 58 depend on the input type configured in the PC utilitysoftware (menu 11300).

    No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4740 Digital input 584741 Dig. in-

    put 58Enable OFF

    ONOFF Designers

    ReferenceHandbook

    The input is configurable andcan have different functions indifferent units.The multi-input 58 has beenconfigured as Binary.

    4742 Dig. in-put 58

    Timer 0.0 s999.0 s

    10.0 s

    4743 Dig. in-put 58

    RelayoutputA

    Not usedOption-dep.

    Notused

    4744 Dig. in-put 58

    RelayoutputB

    Not usedOption-dep.

    Notused

    4745 Dig. in-put 58

    Enable OFFON

    OFF

    4746 Dig. in-put 58

    Failclass

    F1F8 Warning(F2)

    4740 4-20 mA 58.14741 4-20

    mA58.1

    Setpoint

    4 mA20 mA

    10 mA DesignersReferenceHandbook

    The multi-input 58 has beenconfigured as 4-20 mA.

    4742 4-20mA58.1

    Timer 0.0 s999.0 s

    120.0 s

    4743 4-20mA58.1

    RelayoutputA

    Not usedOption-dep.

    Notused

    4744 4-20mA58.1

    RelayoutputB

    Not usedOption-dep.

    Notused

    4745 4-20mA58.1

    Enable OFFON

    OFF

    4746 4-20mA58.1

    Failclass

    F1F8 Warning(F2)

    4750 4-20 mA 58.2

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 54 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4751 4-20mA58.2

    Setpoint

    4 mA20 mA

    10 mA DesignersReferenceHandbook

    The multi-input 58 has beenconfigured as 4-20 mA.

    4752 4-20mA58.2

    Timer 0.0 s999.0 s

    120.0 s

    4753 4-20mA58.2

    RelayoutputA

    Not usedOption-dep.

    Notused

    4754 4-20mA58.2

    RelayoutputB

    Not usedOption-dep.

    Notused

    4755 4-20mA58.2

    Enable OFFON

    OFF

    4756 4-20mA58.2

    Failclass

    F1F8 Warning(F2)

    4740 Pt100/Pt1000 58.14741 PT

    58.1Setpoint

    -49482

    80 DesignersReferenceHandbook

    The multi-input 58 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).

    4742 PT58.1

    Timer 0.0 s999.0 s

    5.0 s

    4743 PT58.1

    RelayoutputA

    Not usedOption-dep.

    Notused

    4744 PT58.1

    RelayoutputB

    Not usedOption-dep.

    Notused

    4745 PT58.1

    Enable OFFON

    OFF

    4746 PT58.1

    Failclass

    F1F8 Warning(F2)

    4750 Pt100/Pt1000 58.24751 PT

    58.2Setpoint

    -49482

    80 DesignersReferenceHandbook

    The multi-input 58 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).

    4752 PT58.2

    Timer 0.0 s999.0 s

    10.0 s

    4753 PT58.2

    RelayoutputA

    Not usedOption-dep.

    Notused

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 55 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4754 PT58.2

    RelayoutputB

    Not usedOption-dep.

    Notused

    4755 PT58.2

    Enable OFFON

    OFF

    4756 PT58.2

    Failclass

    F1...F8 Warning(F2)

    4740 Resistance measurement input, oil pressure 58.14741 RMI oil

    58.1Setpoint

    0.0145.0

    2.0 DesignersReferenceHandbook

    The multi-input 58 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).

    4742 RMI oil58.1

    Timer 0.0 s999.0 s

    5.0 s

    4743 RMI oil58.1

    RelayoutputA

    Not usedOption-dep.

    Notused

    4744 RMI oil58.1

    RelayoutputB

    Not usedOption-dep.

    Notused

    4745 RMI oil58.1

    Enable OFFON

    OFF

    4746 RMI oil58.1

    Failclass

    F1F8 Warning(F2)

    4750 Resistance measurement input, oil pressure 58.24751 RMI oil

    58.2Setpoint

    0.0145.0

    1.0 DesignersReferenceHandbook

    The multi-input 58 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).

    4752 RMI oil58.2

    Timer 0.0 s999.0 s

    5.0 s

    4753 RMI oil58.2

    RelayoutputA

    Not usedOption-dep.

    Notused

    4754 RMI oil58.2

    RelayoutputB

    Not usedOption-dep.

    Notused

    4755 RMI oil58.2

    Enable OFFON

    OFF

    4756 RMI oil58.2

    Failclass

    F1F8 Shut-down(F5)

    4740 Resistance measurement input, water temperature 58.14741 RMI

    water58.1

    Setpoint

    -49482

    100 DesignersReferenceHandbook

    The multi-input 58 has beenconfigured as RMI water tem-perature.

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 56 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4742 Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection (menu10970).

    RMIwater58.1

    Timer 0.0 s999.0 s

    5.0 s

    4743 RMIwater58.1

    RelayoutputA

    Not usedOption-dep.

    Notused

    4744 RMIwater58.1

    RelayoutputB

    Not usedOption-dep.

    Notused

    4745 RMIwater58.1

    Enable OFFON

    OFF

    4746 RMIwater58.1

    Failclass

    F1F8 Warning(F2)

    4750 Resistance measurement input, water temperature 58.24751 RMI

    water58.2

    Setpoint

    -49482

    110 DesignersReferenceHandbook

    The multi-input 58 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection (menu10970).

    4752 RMIwater58.2

    Timer 0.0 s999.0 s

    5.0 s

    4753 RMIwater58.2

    RelayoutputA

    Not usedOption-dep.

    Notused

    4754 RMIwater58.2

    RelayoutputB

    Not usedOption-dep.

    Notused

    4755 RMIwater58.2

    Enable OFFON

    OFF

    4756 RMIwater58.2

    Failclass

    F1F8 Trip +Stop(F4)

    4740 Resistance measurement input, fuel level 58.14741 RMI

    fuel58.1

    Setpoint

    0 %100 %

    10 % DesignersReferenceHandbook

    The multi-input 58 has beenconfigured as RMI fuel level.

    4742 RMIfuel58.1

    Timer 0.0 s999.0 s

    10.0 s

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 57 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4743 RMIfuel58.1

    RelayoutputA

    Not usedOption-dep.

    Notused

    4744 RMIfuel58.1

    RelayoutputB

    Not usedOption-dep.

    Notused

    4745 RMIfuel58.1

    Enable OFFON

    OFF

    4746 RMIfuel58.1

    Failclass

    F1F8 Warning(F2)

    4750 Resistance measurement input, fuel level 58.24751 RMI

    fuel58.2

    Setpoint

    0 %100 %

    5 % DesignersReferenceHandbook

    The multi-input 58 has beenconfigured as RMI fuel level.

    4752 RMIfuel58.2

    Timer 0.0 s999.0 s

    10.0 s

    4753 RMIfuel58.2

    RelayoutputA

    Not usedOption-dep.

    Notused

    4754 RMIfuel58.2

    RelayoutputB

    Not usedOption-dep.

    Notused

    4755 RMIfuel58.2

    Enable OFFON

    OFF

    4756 RMIfuel58.2

    Failclass

    F1F8 Warning(F2)

    4760 Wire fail 584761 W. fail

    58RelayoutputA

    Not usedOption-dep.

    Notused

    DesignersReferenceHandbook

    The wire break fault detectionis activated.

    4762 W. fail58

    RelayoutputB

    Not usedOption-dep.

    Notused

    4763 W. fail58

    Enable OFFON

    OFF

    4764 W. fail58

    Failclass

    F1F8 Warning(F2)

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 58 of 98

  • 2.5.8 Multi-input no. 59The available menus for multi-input no. 59 depend on the input type configured in the PC utilitysoftware (menu 11310).

    No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4770 Digital input 594771 Dig. in-

    put 59Enable OFF

    ONOFF Designers

    ReferenceHandbook

    The input is configurable andcan have different functions indifferent units.The multi-input 59 has beenconfigured as Binary.

    4772 Dig. in-put 59

    Timer 0.0 s999.0 s

    10.0 s

    4773 Dig. in-put 59

    RelayoutputA

    Not usedOption-dep.

    Notused

    4774 Dig. in-put 59

    RelayoutputB

    Not usedOption-dep.

    Notused

    4775 Dig. in-put 59

    Enable OFFON

    OFF

    4776 Dig. in-put 59

    Failclass

    F1F8 Warning(F2)

    4770 4-20 mA 59.14771 4-20

    mA59.1

    Setpoint

    4 mA20 mA

    10 mA DesignersReferenceHandbook

    The multi-input 59 has beenconfigured as 4-20 mA.

    4772 4-20mA59.1

    Timer 0.0 s999.0 s

    120.0 s

    4773 4-20mA59.1

    RelayoutputA

    Not usedOption-dep.

    Notused

    4774 4-20mA59.1

    RelayoutputB

    Not usedOption-dep.

    Notused

    4775 4-20mA59.1

    Enable OFFON

    OFF

    4776 4-20mA59.1

    Failclass

    F1F8 Warning(F2)

    4780 4-20 mA 59.2

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 59 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4781 4-20mA59.2

    Setpoint

    4 mA20 mA

    10 mA DesignersReferenceHandbook

    The multi-input 59 has beenconfigured as 4-20 mA.

    4782 4-20mA59.2

    Timer 0.0 s999.0 s

    120.0 s

    4783 4-20mA59.2

    RelayoutputA

    Not usedOption-dep.

    Notused

    4784 4-20mA59.2

    RelayoutputB

    Not usedOption-dep.

    Notused

    4785 4-20mA59.2

    Enable OFFON

    OFF

    4786 4-20mA59.2

    Failclass

    F1F8 Warning(F2)

    4770 Pt100/Pt1000 59.14771 PT

    59.1Setpoint

    -49482

    80 DesignersReferenceHandbook

    The multi-input 59 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).

    4772 PT59.1

    Timer 0.0 s999.0 s

    5.0 s

    4773 PT59.1

    RelayoutputA

    Not usedOption-dep.

    Notused

    4774 PT59.1

    RelayoutputB

    Not usedOption-dep.

    Notused

    4775 PT59.1

    Enable OFFON

    OFF

    4776 PT59.1

    Failclass

    F1F8 Warning(F2)

    4780 Pt100/Pt1000 59.24781 PT

    59.2Setpoint

    -49482

    80 DesignersReferenceHandbook

    The multi-input 59 has beenconfigured as Pt100 orPt1000.Pt100/Pt1000 set point can bein deg. C or F, dependent onthe unit selection (menu10970).

    4782 PT59.2

    Timer 0.0 s999.0 s

    10.0 s

    4783 PT59.2

    RelayoutputA

    Not usedOption-dep.

    Notused

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 60 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4784 PT59.2

    RelayoutputB

    Not usedOption-dep.

    Notused

    4785 PT59.2

    Enable OFFON

    OFF

    4786 PT59.2

    Failclass

    F1...F8 Warning(F2)

    4770 Resistance measurement input, oil pressure 59.14771 RMI oil

    59.1Setpoint

    0.0145.0

    2.0 DesignersReferenceHandbook

    The multi-input 59 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).

    4772 RMI oil59.1

    Timer 0.0 s999.0 s

    5.0 s

    4773 RMI oil59.1

    RelayoutputA

    Not usedOption-dep.

    Notused

    4774 RMI oil59.1

    RelayoutputB

    Not usedOption-dep.

    Notused

    4775 RMI oil59.1

    Enable OFFON

    OFF

    4776 RMI oil59.1

    Failclass

    F1F8 Warning(F2)

    4780 Resistance measurement input, oil pressure 59.24781 RMI oil

    59.2Setpoint

    0.0145.0

    1.0 DesignersReferenceHandbook

    The multi-input 59 has beenconfigured as RMI oil pres-sure.Oil pressure set point can bein Bar or PSI, dependent onthe unit selection (menu10970).

    4782 RMI oil59.2

    Timer 0.0 s999.0 s

    5.0 s

    4783 RMI oil59.2

    RelayoutputA

    Not usedOption-dep.

    Notused

    4784 RMI oil59.2

    RelayoutputB

    Not usedOption-dep.

    Notused

    4785 RMI oil59.2

    Enable OFFON

    OFF

    4786 RMI oil59.2

    Failclass

    F1F8 Shut-down(F5)

    4770 Resistance measurement input, water temperature 59.14771 RMI

    water59.1

    Setpoint

    -49482

    100 DesignersReferenceHandbook

    The multi-input 59 has beenconfigured as RMI water tem-perature.

    CGC 400 parameter list 4189340789 UK Alarm list

    DEIF A/S Page 61 of 98

  • No. Setting Min.Max.

    Factorysetting

    Notes Ref. Description

    4772 Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection (menu10970).

    RMIwater59.1

    Timer 0.0 s999.0 s

    5.0 s

    4773 RMIwater59.1

    RelayoutputA

    Not usedOption-dep.

    Notused

    4774 RMIwater59.1

    RelayoutputB

    Not usedOption-dep.

    Notused

    4775 RMIwater59.1

    Enable OFFON

    OFF

    4776 RMIwater59.1

    Failclass

    F1F8 Warning(F2)

    4780 Resistance measurement input, water temperature 59.24781 RMI

    water59.2

    Setpoint

    -49482

    110 DesignersReferenceHandbook

    The multi-input 59 has beenconfigured as RMI water tem-perature.Water temperature set pointcan be in deg. C or F, depend-ent on the unit selection (menu10970).

    4782 RMIwater59.2

    Timer 0.0 s999.0 s

    5.0 s

    4783 RMIwater59.2

    RelayoutputA

    Not usedOption-dep.

    Notused

    4784 RMIwater59.2

    RelayoutputB

    Not usedOption-dep.